Vaillant ECOTEC PLUS VU 80, ECOTEC PLUS VU 100, ECOTEC PLUS VU 120 Installation And Maintenance Instructions Manual

Installation and maintenance instructions
For the competent person
Installation and maintenance instructions
ecoTEC plus
VU 80, 100, 120kW
GB, IE
Table of contents
Table of contents
1 Notes on the documentation .....................................3
1.1 Storing documents ..........................................................3
1.2 Applicability of the instructions ...................................3
1.3 Identification plate ...........................................................3
1.4 CE label ...............................................................................3
1.5 Type overview ...................................................................4
2 Safety .................................................................................5
2.1 Safety and warning information ..................................5
2.2 Intended use ......................................................................5
2.3 Basic safety information ................................................ 6
2.4 General requirements .....................................................7
3 Unit and functional description ................................11
4 Installation ......................................................................12
4.1 Scope of delivery ............................................................12
4.2 Transporting the unit .....................................................12
4.3 Dimension drawing and connection dimensions .....15
4.4 Requirements for the installation site .......................15
4.5 Wall-mounting the boiler ...............................................16
4.6 Removing/fitting the front casing ..............................16
5 Gas installation ..............................................................17
5.1 Preparing for installation ..............................................17
5.2 Connecting the gas line .................................................17
6 Hydraulic installation ................................................. 18
6.1 Preparing for installation ............................................. 18
6.2 Connecting the heating flow and heating return....19
6.3 Connecting the condensate drain pipework ........... 20
6.4 Connecting the discharge pipe to the expansion
relief valve on the heating installation ......................21
7 Flue gas installation ...................................................22
7.1 Preparing for installation .............................................22
7.2 Installing the flue pipe ..................................................22
7.3 Flue gas guiding opening .............................................22
8 Electrical installation .................................................24
8.1 Preparing for installation .............................................24
8.2 Opening/closing the electronics box .........................24
8.3 Establishing the mains connection and
connecting the pump group ........................................24
8.4 Connecting the controller ............................................26
8.5 Connecting additional units ........................................27
8.6 Connection wiring diagram .........................................28
10 Operation ........................................................................33
10.1 Calling up the installer level ........................................33
10.2 Overview of the menu structure ............................... 34
11 Start-up ...........................................................................36
11.1 Switching on the boiler .................................................36
11.2 Installation assistant .....................................................36
11.3 Appliance configuration and diagnostics menu .....37
11.4 Using test programmes ................................................37
11.5 Checking the function of the boiler ......................... 38
12 Adapting the unit to the heating installation ....39
12.1 Overview of the parameters in the diagnostics
menu .................................................................................39
12.2 Handing the boiler over to the operator ................. 43
13 Inspection and maintenance ................................... 44
13.1 Inspection and maintenance intervals ..................... 44
13.2 Inspection and maintenance work ............................ 48
13.3 Using the function menu ............................................49
13.4 Removing/fitting the upper casing ........................... 50
13.5 Carrying out maintenance work ................................ 50
14 Troubleshooting ........................................................... 55
14.1 Contacting Vaillant customer service ...................... 55
14.2 Performing diagnostics ............................................... 55
14.3 Using the function menu ..............................................61
14.4 Running check programmes ........................................61
14.5 Resetting parameters to factory settings .................61
15 Replacing components ...............................................62
15.1 Preparing for and completing replacement work ..62
15.2 Removing/fitting the side section (ifrequired) .....62
15.3 Replacing the gas valve ................................................63
15.4 Replacing the burner ....................................................63
15.5 Replacing insulating mats ........................................... 64
15.6 Replacing the fan .......................................................... 64
15.7 Replacing the heat exchanger ................................... 64
15.8 Replacing the PCB and/or the display ..................... 65
15.9 Ending repairs ................................................................ 65
16 Decommissioning ........................................................ 66
16.1 Temporarily shutting down the boiler ..................... 66
16.2 Permanently decommissioning the boiler .............. 66
16.3 Disposing of the boiler ................................................66
17 Vaillant Commercial Service ................................... 66
9 Establishing operational readiness ........................29
9.1 Reading the temperature or pressure display ........29
9.2 Preparing the heating water .......................................29
9.3 Filling and purging the heating installation ............29
9.4 Preventing low water pressure .................................. 30
9.5 Filling the condensate siphon ......................................31
9.6 Checking the gas ratio setting .....................................31
18 Technical data
19 Glo
20 Appendix ........................................................................ 69
Index ...........................................................................................72
ssary ......................................................................... 68
...............................................................67
Notes on the documentation
1
1 Notes on the documentation
The following information is intended to help you through­out the entire documentation. Other documents apply in addition to these Installation instructions. We accept no lia­bility for any damage caused by failure to observe these instructions.
Other applicable documents
> During installation, you must observe all the installation
instructions for the assemblies and components of the
system. These installation instructions are enclosed with the various system parts and supplementary components.
> Furthermore, observe all operating instructions enclosed
with components of the system.
1.1 Storing documents
> Pass these installation instructions and all other applica-
ble documents and, if necessary, any required tools to
the system operator. The system operator should retain these instructions and tools so that they are available when required.
1.2 Applicability of the instructions
These instructions apply for the following products only:
Unit Type designation
ecoTEC plus 806 (VU GB 806/5-5) 0010010767 41-044-68
ecoTEC plus 1006 (VU GB 1006/5-5) 0010010780 41-044-69
Article number
Gas Council Number
1.4 CE label
CE labelling shows that, based on the type overview, the units comply with the basic requirements of the following directives:
– Directive 2009/142/EC of the Council with amendments
"Directive for Harmonisation of Legal Regulations of the Member States for Gas Consumption Appliances" (GasAppliances Directive)
– Directive 92/42/EC of the Council with amendments
"Directive Concerning the Efficiency of New Hot Water Heating Boilers Fired by Liquid or Gaseous Fuels" ( Efficiency directive)
– Directive 2006/95/EC of the Council with amendments
"Directive Concerning Electrical Equipment for Use Within Specific Voltage Limits" (Low voltage directive)
– Directive 2004/108/EC of the Council with amendments
"Directive Concerning Electromagnetic Compatibility"
The boilers comply with the type sample described in the EC Type testing certificate PIN no. CE-0085CM0415
The units comply with the following standards:
– EN 12828 – EN 15417 – EN 15420 – EN 50165 – EN 55014 – EN 60335-1 – EN 6100-3-2 – EN 6100-3-3 – prEN 15502-1 – prEN 15502-2
ecoTEC plus 1206 (VU GB 1206/5-5) 0010010791 41-044-70
1.1 Type overview
> The article number of the unit can be found on the iden-
tification plate.
1.3 Identification plate
The identification plate of the Vaillant ecoTEC plus is attached to the bottom of the boiler at the factory. The article number of the gas-fired wall-hung boiler can be found in the serial number. The seventh to sixteenth num­bers constitute the article number. The serial number is also located on a plate, which is placed in a plastic fish plate behind the front flap on the underside of the boiler. The serial number can also be shown in the display of the boiler (¬Operating instructions).
ecoTEC plus installation and maintenance instructions 0020134823_01 3
Notes on the documentation
1
1.5 Type overview
Unit type ecoTEC plus
806 (VU GB 806/5-5)
1006 (VU GB 1006/5-5)
1206 (VU GB 1206/5-5)
1.2 Type overview
Designated country (designation in accord­ance with ISO 3166)
GB (Great Britain) IE (Ireland)
GB (Great Britain) IE (Ireland)
GB (Great Britain) IE (Ireland)
Approval category
II
2H3P
II
2H3P
II
2H3P
Gas group
Natural gas H - G20 - 2kPa (20mbar)
Propane - G31 - 3.7kPa (37mbar)
Propane - G31 - 5kPa (50mbar)
Natural gas H - G20 - 2kPa (20mbar)
Propane - G31 - 3.7kPa (37mbar)
Propane - G31 - 5kPa (50mbar)
Natural gas H - G20 - 2kPa (20mbar)
Propane - G31 - 3.7kPa (37mbar)
Propane - G31 - 5kPa (50mbar)
Nominal heat output
range [kW]
16 - 80
20 - 100
24 - 120
a
Safety
2
a
2 Safety
2.1 Safety and warning information
> When installing the ecoTEC plus, you must observe all
the general safety information and the warning notes
that appear before all of the actions.
2.1.1 Classification of warnings
The warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words:
Warning symbol
a
Signal word
Danger!
Danger!
Explanation
Imminent danger to life or risk of severe personal injury
Risk of death from electric shock
e
Warning. Risk of minor personal injury
a
Risk of material or environ-
Caution.
mental damage
b
2.2 Intended use
There is a risk of injury or death to the user or others, or of damage to the product and other property, in the event of improper use or use for which it is not intended. The product is intended as a heat generator for closed hot water/central heating installations and for hot water gener­ation. The products referred to in this manual must only be installed and operated in conjunction with the accessories listed in the associated flue pipe installation manual. Intended use includes the following:
– observance of accompanying operating, installation and
servicing instructions for the Vaillant product, as well as all other components of the system
– installing and fitting the product in accordance with the
product and system approval
– compliance with all inspection and maintenance condi-
tions listed in the instructions. The use of the product in vehicles, such as mobile homes and caravans, is not classed as intended use. Units that are not classed as vehicles are those that are installed in a fixed and permanent location (known as "fixed installa­tion"). Installing and using the product in locations where it will be subject to possible moisture or spray water is considered to be improper use. Any other use that is not specified in these instructions, or use beyond that specified in this document, shall be consid­ered improper use. Any direct commercial or industrial use is also deemed to be improper. The manufacturer/supplier is not liable for any claims or damage resulting from improper use. The user alone bears the risk.
Caution.
Improper use of any kind is prohibited.
2.1 Classification of warnings
2.1.2 Structure of warnings
Warning signs are identified by an upper and lower separat­ing line. and are laid out according to the following basic principle:
Signal word!
Type and source of danger!
a
ecoTEC plus installation and maintenance instructions 0020134823_01 5
Explanation of the type and source of danger
> Measures for averting the danger
a
2
Safety
a
2.3 Basic safety information
> Observe the following safety information at all times.
European installation directive
Installation and maintenance of the boiler must only be per­formed by a competent person with valid accreditation from the Health and Safety Executive in accordance with the "Gas Safety (Installation and Use) Regulations 1998" (here­inafter abbreviated to "competent person" or "heating spe­cialist company"). The existing regulations, rules and guide­lines must be observed when doing so. The competent per­son is also responsible for inspection, maintenance and repairs to the boiler, and alterations to the gas volume set­ting. IE only: The installation must comply with the current Ver­sion of I.S.813 ‘Domestic Gas Installations’ and current Building Regulations. The current ETCI Regulations for installing electrical sys­tems must also be observed.
Risk of poisoning and burns caused by escaping hot flue gases!
Hot flue gas can escape and cause poisoning and burns if the boiler is operated with an incompletely installed or flue pipe or if the boiler is operated with internal leaks with the front casing open.
> Operate the boiler for start-up and in continuous mode
only when the front casing is fitted and closed and the flue pipe is completely fitted.
> For test purposes only (such as gas flow pressure test-
ing), the boiler may be operated with the front casing removed for short durations ONLY but must have a com­pletely installed flue pipe.
What to do in an emergency if you smell gas
Installation errors, damage, tampering, unauthorised instal­lation sites or similar can cause gas to escape and result in a risk of poisoning and explosion. If there is a smell of gas in the building, proceed as follows:
> Avoid rooms that smell of gas. > If possible, open doors and windows fully and ensure
adequate ventilation. > Do not use naked flames (e.g. lighters, matches). > Do not smoke. > Do not use any electrical switches, mains plugs, door-
bells, telephones or other communication systems in the
building. > Close the gas meter isolator device or the main isolator. > If possible, close the gas isolator cock in the gas supply. > Warn other occupants in the building by yelling or bang-
ing on doors or walls. > Leave the building. > If you can actually hear gas leaking, leave the building
immediately and ensure that others do not enter the
building. > Alert the fire brigade and police when you are outside
the building.
> Notify the gas supply company or National Grid Transco
0800 111999 by telephone from outside the building!
What to do if you smell flue gas
Installation errors, damage, tampering with the unit, unau­thorised installation sites or similar can cause flue gas to escape and result in a risk of poisoning. If there is a smell of flue gas in the building, proceed as follows:
> If possible, open doors and windows fully and ensure
adequate ventilation. > Switch the boiler off. > Check the flue gas routes in the boiler and the flue gas
pipes. > In particular, check that the flue gas opening is not
blocked. If required, seek expert assistance for this.
Installation in rooms with ventilation
For open-flued operation, the unit must not be placed in rooms from which the air is extracted using fans (for exam­ple, ventilation systems, extractor hoods, tumble dryer ven­tilation). These systems create negative pressure in the room. As a result of the negative pressure, flue gas from the opening is drawn through the annular gap between the flue gas pipe and the shaft into the installation room. The unit may only be operated dependent on the room air, if simultaneous operation of the unit and fan is not possible.
> To interlock the fan and unit, install the Vaillant acces-
sory multi-functional module 2 from 7. > Please inform the system operator of the possible risk
from running exhaust fans.
Material damage caused by corrosion
To prevent corrosion on the boiler and also in the flue pipe, note the following:
> Do not use sprays, solvents, chlorinated cleaning agents,
paint, adhesives or similar substances in the vicinity of
the boiler.
Under unfavourable circumstances, these substances may cause corrosion.
Material damage due to improper use and/or unsuitable tools
The use of unsuitable tools or improper use thereof may cause damage, such as gas or water leaks.
> To tighten or loosen threaded connections, only use a
suitable open-ended spanner (combination wrench) – do
not use pipe wrenches, extensions, etc.
Changes to the surroundings of the boiler
Changes may not be made to the following equipment:
– the boiler – the gas, air and water pipes and power lines – the flue pipe – the drain line and expansion relief valve for the heating
water
– constructional conditions that could affect the opera-
tional safety of the boiler
6 ecoTEC plus installation and maintenance instructions 0020134823_01
a
Safety
2
a
Using the correct gas type
Using the wrong gas type may cause a fault shutdown on the boiler. Furthermore, ignition and combustion noise may occur in the boiler.
> Observe the gas setting values in accordance with
¬section1.5.
Risk of death due to lack of safety devices
A lack of safety devices (e.g. expansion relief valve, expan­sion vessel) can lead to potentially fatal scalding and other injuries, e.g. due to explosions. The schematic drawings included in this document do not show all safety devices required for correct installation.
> Install the necessary safety devices in the system. > Inform the operator about the function and position of
the safety devices.
> Observe the applicable national and international laws,
standards and guidelines.
2.4 General requirements
2.4.1 Related documents
To ensure the safe installation and continued satisfactory operation of your appliance, all works shall be carried out by a competent installer fully conversant with the equired current and up to date, acts standards, laws and regulations relevant for this range of equipment at the time of installa­tion. In addition any special requirements of Local Authori­ties, gas undertakings or insurers must be complied with. Installers shall carryout a full site risk assessment and put into place all necessary steps and procedures to comply with Health and Safety at Work Act and ensure safety of themselves and others with regard to manual handling and working at height requirements. Attention shall be paid to (but not restricted to) the follow­ing:
– Gas Safety (Installation and Use) regulations. – Non Domestic Heating, Cooling and Ventilation Compli-
ance Guide.
– All Building Regulations 2000 for England and Wales,(as
amended).
– (Includes Approved Codes of Practice and Approved Doc-
uments for building regulations e.g. L1, L2A, L2B, L8.)
– The Building Standards, Scotland, and any requirements
determined by the local authorities within.
– BS 7671 Requirements for electrical installations. IEE Wir-
ing Regulations – The Electricity at Work Regulations. – The Clean Air Act 1993, 1968 and the 3rd Edition of the
1956 Clean Air Act. (installations exceeding 150kW) – The Water supply (water fittings) regulations 1999. – BS 5854 Code of practice for flues and flue structures in
buildings. – BS EN 12828 Design of water-based heating systems.
– BS 6644 Specification for the installation of gas fired
hot water boilers with rated inputs between 70 kW (net)
and 1.8 MW (net) (2nd and 3rd family gases). – I.S. 820 Non Domestic gas Installations (Ireland) – BS 6700 Specification for the design, installation, testing
and maintenance of services supplying water for domes-
tic use within buildings and their curtilages. – BS 6880 Code of practice for low temperature heating
systems with outputs greater than 45 kW.
Part 1 Fundamental and design considerations. Part 2 Selection of equipment. Part 3 Installation, commissioning and maintenance.
– BS 6981 Installation of low pressure gas pipework of up
to 35mm in domestic premises. – BS 4814 Specification for: Expansion vessels using an
internal diaphragm, for sealed hot water and heating sys-
tems. – BS 7074 Application, selection and installation of expan-
sion vessels and ancillary equipment for sealed water
systems.
Part 1 Code of practice for domestic heating and hot water. Part 2 Code of practice for low and medium temperature hot water systems.
– BS 7593 Code of practice for treatment of water in
domestic hot water central heating systems – BS EN 13831 Closed expansion vessels with built in dia-
phragm – BS EN 14336 Heating systems in buildings. Installation
and commissioning of water based heating systems.
Institute of Gas Engineers Publications:
– IGE/UP/1 (Edition 2) Strength testing, tightness testing
and direct purging of industrial and commercial gas
installations. – IGE/UP/1A (Edition 2) Strength testing, tightness testing
and direct purging of small, low pressure industrial and
commercial natural gas installations. – IGE/UP/1B (Edition 2) Tightness testing and direct purg-
ing of small natural gas installations. – IGE/UP/ 7 (Edition 2) Gas in timber and light steel
framed buildings.
IGE/UP/10 Installation of gas appliances in industrial and
commercial premises.
Part 1 Flued appliances.
ecoTEC plus installation and maintenance instructions 0020134823_01 7
a
2
Safety
a
2.4.2 Installation site
The installation site of the boiler should allow proper con­nection of the flue pipe to the boiler. In addition, there should be adequate room for maintenance work and air cir­culation around the boiler. The boiler must be set up in a separate installation room. In case of installation of the boiler in an unusual location, special procedures may be necessary and BS 5546 and BS6798 give detailed instructions on this aspect. The boiler must be installed on a flat, vertical wall, which must be suf­ficiently robust to take the weight of the boiler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regula­tions.
If the boiler is to be installed in a timber frame
house, the installation must be performed in
i
b
> Observe the following when choosing the installation site
and operating the boiler:
> Operate the boiler independently of room air or in a sep-
arate installation room, otherwise this may cause corro­sion in the boiler and in the flue gas installation, if
> Do not route the combustion air through an old oil fur-
nace hearth, as this can also cause corrosion.
> When installing the unit, please observe the local con-
densate regulations,
The condensate connection must not be modified or blocked.
accordance with the Institute of Gas Engineers Publication IG/UP/7 edition 2 "Guideline for gas installations in wooden and light metal-clad resi­dences".
Caution.
Risk of damage caused by aggressive vapours and dust.
Aggressive vapours and dust in the installa­tion room may cause corrosion damage to the boiler and to the flue gas installation.
> Ensure that the boiler is room-sealed if
the air in the installation room contains aggressive vapours or dust.
– Do not install the boiler in rooms prone to frost. – Do not install the boiler in rooms in which the com-
bustion air contains chemical substances, e.g. fluoride, chlorine, sulphur, dust, etc. (e.g. sprays, solvents, cleaning agents, paint, adhesives).
– the combustion air supply contains the aforemen-
tioned substances,
– you install the boiler in hairdresser salons, painter's or
joiner's workshops, cleaning businesses or similar.
– avoid horizontal sections in the condensate and flue
gas route.
2.4.3 Gas supply
An existing gas meter should be checked to ensure that it is capable of passing the rate of gas supply required. The lines must be fitted in accordance with BS 6891. In IE in accordance with the current issue of IS813. The lines between the gas meter and boiler must be of an appropri­ate size. Do not use any lines that are smaller than the connection to the boiler (25mm). The complete system must be tested for leaks and purged as described in BS 6891.
2.4.4 Electrical connection
Danger!
Risk of death from electric shock!
e
A common, single-phase 230V-, ~50Hz electricity supply fused to a max. 3 A must be provided for the boiler and its additional controllers in accordance with the latest edition of the directive BS7671 (IEE Wiring Regulations) and any other local regulations that may apply. In IE reference should be made to the current edition of the ETCI rules. The method of connection to the power mains must provide a means of completely isolating the boiler and its ancillary controllers from the power mains. It is preferable to isolate the boiler using a two-pin switch with a 3-mm contact open­ing on both pins. The isolator should be attached and marked accordingly so that it is easily accessible and adja­cent to the boiler.
2.4.5 System of parts through which water flows
Lines which do not form part of the usable heating surface should be insulated to prevent heat losses and possible freezing up, especially where the lines run under roofs and ventilated cellar spaces. The drain connections must be eas­ily accessible, so that the entire system including the boiler and hot water system can be drained. The drain connec­tions should be at least 1/2" (BSP nominal size) and must be in accordance with BS2879. The water pipes must be thoroughly cleaned, especially when connecting a new boiler to an existing system.
If the boiler is not earthed, it may be elec­trically live if a defect occurs.
> Earth the boiler and the metal pipes that
are connected to the boiler.
8 ecoTEC plus installation and maintenance instructions 0020134823_01
a
Safety
2
a
Caution.
Risk of material damage if the heating
b
Mixing additives with the heating water may result in mate­rial damage. However, no incompatibility with Vaillant boil­ers has been detected with proper use of the following products over a long period.
> When using additives, follow the manufacturer's instruc-
tions without exception. Vaillant accepts no liability for the compatibility of any addi­tive or its effectiveness in the rest of the heating installa­tion.
Additives for cleaning measures (subsequent flushing required)
– Fernox F3 – Sentinel X 300 – Sentinel X 400
Additives intended to remain permanently in the system
– Fernox F1 – Fernox F2 – Sentinel X 100 – Sentinel X 200
Additives for frost protection intended to remain permanently in the system
– Fernox Antifreeze Alphi 11 – Sentinel X 500
> Inform the operator about the measures required if you
have used these additives.
> Inform the operator about the measures required for
frost protection.
water is treated with unsuitable frost or corrosion protection agents!
Frost and corrosion protection agents may cause changes in the seals, noises during heating and may lead to further damage.
> Do not use any unsuitable frost or corro-
sion protection agents.
Permissible salt content
Heating water characteristics
Electrical conductivity at 25 °C
Appearance
pH value at 25 °C 8.2 - 10.0
Oxygen mg/l
1) For aluminium and aluminium alloys, the pH value range is restricted from 6.5 to 8.5.
2.2 Guideline values for heating water: Salt content
Permissible water hardness
Caution.
Heating water that is extremely calcifer-
b
ous or corrosive or contaminated by chemicals may cause damage to the boiler.
Unsuitable heating water damages the seals and diaphragms, blocks components in the boiler and heating installation through which the water flows, and causes noise. The heating water must fulfil the limit val­ues based on the system volume in accord­ance with fig.2.1 and, if required, must be treated. In addition, the national regulations with regard to water treatment shall apply. To treat the water, we recommend treat­ment plants that work according to the reverse osmosis process.
> Condition the water for the initial filling
as well as the water for any subsequent fillings.
Unit Low-salt Saline
1)
100 - 1500
8.2 - 10.0
mS/cm < 100
Free of sedimentary materials
< 0.1 < 0.02
1)
ecoTEC plus installation and maintenance instructions 0020134823_01 9
a
2
Safety
3,6
3,3
3
2,7
2,4
]
3
2,1
1,8
1,5
y [mol/m
1,2
0,9
0,6
0,3
0,0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
80 kW
100/120 kW
80 kW: A
B
a
A
100/120 kW: B
x [l]
2.1 Water preparation depending on water hardness and system volume
Key: x System volume [l] y Water hardness [mol/m3]
(1 mol/m3 corresponds to 100 mg/l CaCO3)
A Water treatment required B Water treatment not required
2.4.6 Expansion relief valve
The boiler is supplied with a 6bar presure relief valve, which must be fitted to the boiler and drained to a safe but visible location. The safety discharge pipe must be a mini­mum of 18mm diameter and must be solely used for this purpose. Ensure that all components that are fitted in the heating installation are suitable for a max. operating pressure of 6bar.
2.4.7 Purging
The boiler is equipped with an automatic air vent. Other measures need to be taken to allow the heating system to be purged during filling and during commissioning either manually or using an automatic air vent.
Risk of damage due to frost
Insufficient frost protection measures may cause frost dam­age to the heating installation
> Explain to the operator how to protect the heating instal-
lation against frost.
10 ecoTEC plus installation and maintenance instructions 0020134823_01
3 Unit and functional description
Unit and functional description
3
Construction and function
15
14
13
12
11
10
9
8
15
14
1
2
13
12
11
3
10 4 5
6
7
9
8
3.2 Functional elements (VUGB1006/5-5 and VUGB1206/5-5)
1
2
3
4
5
6
7
3.1 Functional elements (VUGB806/5-5)
Key
1 Connection for the flue pipe 2 Fan 3 Gas valve 4 Connection for air intake pipe 5 Flue gas pressure cartridge 6 Return sensor 7 Water pressure sensor 8 Electronics box 9 Stainless steel heat exchanger 10 Pressure gauge 11 Flow sensor 12 Safety cut-out 13 Ignition electrode 14 Automatic air vent 15 Monitoring electrode
Key
1 Connection for the flue pipe 2 Fan 3 Gas valve 4 Supply air collector 5 Flue gas pressure cartridge 6 Return sensor 7 Water pressure sensor 8 Electronics box 9 Stainless steel heat exchanger 10 Feed sensor 11 Safety cut-out 12 Ignition electrode 13 Automatic air vent 14 Monitoring electrode
ecoTEC plus installation and maintenance instructions 0020134823_01 11
Installation
4
4 Installation
4.1 Scope of delivery
The Vaillant ecoTEC plus is delivered pre-assembled in a packaging unit.
4.1.1 Unpacking the boiler
> Open the box by pulling on the tear-off strings. > Remove the boiler from its box. > Remove the protective film from all parts of the boiler. > Place the boiler so that it is vertical on the foot pad.
4.1.2 Checking the scope of delivery
> Check that the scope of delivery is complete and intact
(¬ table 4.1).
Number Description
1 Hanging bracket
1 Unit
Enclosed documentation
1
- Installation and maintenance instructions
- Operating instructions
- Flue pipe installation manual
- Installation template
- Guarantee card
- Various stickers
1 Condensate siphon
Bag containing small parts (assembly kit)
1
- 1 x expansion relief valve, 6bar
- 2 x service valves
- 6 x wood screws
- 6 x rawl plug, 10 x 60 mm
- 6 x washers
4.1 Scope of delivery
4.1.3 Disposing of the packaging
> Dispose of the cardboard packaging used on the ecoTEC
plus at a recovered paper collection point.
> Dispose of the plastic film and plastic filling at an appro-
priate plastic recycling site.
> Observe valid national regulations.
4.2 Transporting the unit
Important:
In regard to the regulations of 1992 concerning the manual handling of loads, the unit exceeds the weight which can be lifted by a single person.
General handling recommendations
> Clear your path before lifting the unit. > Use safe lifting techniques – keep your back straight –
and bend your legs at the knee.
> Hold the load as close as possible to your body. Do not
twist your body – instead, reposition your feet.
> If the unit is being lifted by 2 persons, ensure your move-
ments are coordinated during lifting.
> Avoid bending your upper body - do not lean forwards or
to the side.
> Wear appropriate cut resistant and non-slip gloves to
protect yourself against sharp edges and maintain a safe and secure grip.
> If required, get somebody to assist you in this.
Unloading the box from the delivery van
It is recommended that two people lift the unit together.
> Lift the box using the straps provided. > Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Hold the load as close as possible to your body. > If the unit is being lifted by 2 persons, ensure your move-
ments are coordinated during lifting. > If required, get somebody to assist you in this.
Transporting the box from the delivery point to the installation site – ground floor
It is recommended that two people lift the unit together.
> Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Hold the load as close as possible to your body. > If the unit is being lifted by 2 persons, ensure your move-
ments are coordinated during lifting. > Clear your path before lifting the unit. > Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Do not twist your body – instead, reposition your feet. > Avoid tripping hazards, slippery or wet surfaces as well
as steps and stairs. > If required, get somebody to assist you in this.
Installation
4
Transporting the box from the delivery point to the installation site – first or higher floor, cellar
It is recommended that two people lift the unit together.
> Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Hold the load as close as possible to your body. > If the unit is being lifted by 2 persons, ensure your move-
ments are coordinated during lifting. > Avoid bending your upper body - do not lean forwards or
to the side. > Clear your path before lifting the unit. > Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Do not twist your body – instead, reposition your feet. > Avoid tripping hazards, slippery or wet surfaces as well
as steps and stairs. > If required, get somebody to assist you in this.
Transporting the box from the delivery point to the installation site – roof
> The unit must be lifted by two persons. > Coordinate your movements. > Avoid bending your upper body - do not lean forwards or
to the side. > Clear your path before lifting the unit. > Avoid tripping hazards, slippery or wet surfaces as well
as steps and stairs. > If the unit is being transported to an attic storey, one
person must guide the unit from above, while the other
supports the unit from below. > Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Hold the load as close as possible to your body. > If required, get somebody to assist you in this. > The attic storey must be safely accessible and must have
a solid floor and suitable lighting. > If the attic storey is accessed via a hatch, the hatch must
be secured against falling using a suitable guard rail. > Before setting up the unit, it is recommended that you
perform a risk assessment of the attic storey, to clarify
access, floor rigidity, lighting and other factors, and any
measures to be undertaken in advance.
Unpacking the unit from the box
> It is recommended that two persons lift the unit out of
the box. > Always keep the working area free from obstacles. > Cut through the two straps. > Open the box flaps. > Remove the polystyrene parts from the box > Separate the box in the centre at the pull-out strap. > Lift the upper part of the box away. > Lift the unit out of the box. > Use safe lifting techniques – keep your back straight –
and bend your legs at the knee. > Hold the load as close as possible to your body. > If required, get somebody to assist you in this. > Dispose of the packaging responsibly.
> Wear appropriate cut-resistant and non-slip gloves to
protect yourself against sharp edges and maintain a safe and secure grip while handling the unpackaged unit.
Positioning the unit for final installation – no obstacles
> If the unit weighs more than 25 kg, it should always be
transported by two persons, where possible.
> Fix the unit bracket securely to the wall before lifting the
unit and placing it in position.
> Ensure that you hold on to the front and side of the unit
securely, lift it, hold it in a balanced position and then lift it further upwards and position it on the bracket.
> Use safe lifting techniques – keep your back straight –
and bend your legs at the knee –if you are lifting some-
thing from the floor. > Do not twist your body – instead, reposition your feet. > During the entire lifting process, hold the boiler as close
as possible to your body to minimise the strain on your
back. > Ensure your movements are coordinated so that the
weight of the unit is evenly distributed. > If required, get somebody to assist you in this. > Wear appropriate cut-resistant and non-slip gloves to
protect yourself against sharp edges and maintain a safe
and secure grip while handling the unit.
Positioning the unit for final installation – above a work surface, possible obstacles, etc.
If the unit weighs more than 25 kg, it should always be transported by two persons, where possible.
> Fix the unit bracket securely to the wall before lifting the
unit and placing it in position. > If required, provide the work surface with sufficient pro-
tection against damage. > Ensure that you hold the unit securely at the front and
side and lift it - if available - onto the work surface. > Hold the unit in a balanced position and then lift it fur-
ther upwards and position it on the bracket. > If the unit is being positioned on the bracket by two per-
sons, ensure that you have a firm grip on the front and
side/bottom of the boiler. > Ensure your movements are coordinated if the unit is
being lifted by 2 persons, so that its weight is evenly dis-
tributed.
Use safe lifting techniques – keep your back straight – and bend your legs at the knee –if you are lifting something from the floor.
> Do not twist your body – instead, reposition your feet. > During the entire lifting process, hold the boiler as close
as possible to your body to minimise the strain on your
back. > Avoid bending your upper body - do not lean forwards or
to the side. > If required, get somebody to assist you in this. > Wear appropriate cut-resistant and non-slip gloves to
protect yourself against sharp edges and maintain a safe
and secure grip while handling the unit.
ecoTEC plus installation and maintenance instructions 0020134823_01 13
Installation
4
Positioning the unit for final installation – restricted installation
> If the unit weighs more than 25 kg, it should always be
transported by two persons, where possible.
> Fix the unit bracket securely to the wall before lifting the
unit and placing it in position.
> If required, provide the work surface with sufficient pro-
tection against damage.
> Ensure that you hold the unit securely at the front and
side and lift it - if available - onto the work surface.
> Hold the unit in a balanced position and then lift it fur-
ther upwards and position it on the bracket.
> If the unit is being positioned on the bracket by two per-
sons, ensure that you have a firm grip on the front and side/bottom of the boiler.
> Ensure your movements are coordinated if the unit is
being lifted by 2 persons, so that its weight is evenly dis­tributed.
> Use safe lifting techniques – keep your back straight –
and bend your legs at the knee –if you are lifting some-
thing from the floor. > Do not twist your body – instead, reposition your feet. > During the entire lifting process, hold the boiler as close
as possible to your body to minimise the strain on your
back. > If required, get somebody to assist you in this. > Wear appropriate cut-resistant and non-slip gloves to
protect yourself against sharp edges and maintain a safe
and secure grip while handling the unit.
Positioning the unit for final installation – with restricted installation position under the roof.
> If the unit weighs more than 25 kg, it should always be
transported by two persons, where possible.
> Ensure that you hold onto the front and side of the unit
securely, lift it, hold it in a balanced position and then lift it further upwards and position it on the bracket.
> If the unit is being positioned on the bracket by two per-
sons, ensure that you have a firm grip on the front and side/bottom of the boiler.
> Ensure your movements are coordinated if the unit is
being lifted by 2 persons, so that its weight is evenly dis­tributed.
> If the unit is being positioned on the bracket by one per-
son, ensure that you have a firm grip and lift the boiler from the bottom.
> Use safe lifting techniques – keep your back straight –
and bend your legs at the knee –if you are lifting some-
thing from the floor. > Do not twist your body – instead, reposition your feet. > During the entire lifting process, hold the boiler as close
as possible to your body to minimise the strain on your
back. > If required, get somebody to assist you in this. > Wear appropriate cut-resistant and non-slip gloves to
protect yourself against sharp edges and maintain a safe
and secure grip while handling the unit. > Before setting up the unit, it is recommended that you
perform a risk assessment of the attic storey, in order to
check the access, floor rigidity, lighting, and railing, and
to take all required remedial actions before the unit is
installed.
4.3 Dimension drawing and connection dimensions
G 1 1/4
4
7
Ø25
49
482
Installation
Key
1 Wall breakthrough for flue pipe 2 Flue pipe connection 3 Hanging bracket 4 Heating flow 5 Condensate siphon connection 6 Gas connection 7 Heating return
4.4 Requirements for the installation site
4
960
190
287
673
5
70
172 172
480
138
6
1
2
3
22
4.4.1 Required minimum clearances/installation clearances
AB
477
CC
4.2 Recommended minimum clearances/installation clearances
680,5
Key
A 350 mm (flue pipe diameter 110/160 mm) 450 mm (with cascade design) B 400 mm C optional approx. 200 mm
> When using the accessories, observe the minimum clear-
ances/installation clearances.
> Where units are installed in cascade, observe the gradi-
ent of the flue pipe (approx. 50mm/m).
4.1 Connection dimensions in mm
ecoTEC plus installation and maintenance instructions 0020134823_01 15
175
603
When installing the 110/160 mm flue pipe,
observe the minimum clearances in accordance
i
A side gap is not required, however you can remove the side panels if there is sufficient space at the side (approx.200 mm) for maintenance. It is not necessary to ensure sufficient clearance between the boiler and combustible materials or components as the temperature of the boiler will always be less than the maxi­mum permissible temperature of 85 °C due to its nominal heat output.
with ¬fig. 4.1.
Installation
4
4.5 Wall-mounting the boiler
Danger!
Risk of death if the load-bearing capacity
a
of the fixing elements used is insuffi­cient!
If the fixing elements or wall do not have sufficient load-bearing capacity, the boiler can come loose and fall down. This may also cause leaks in the gas line, which is potentially fatal.
> When installing the boiler, make sure that
the fixing elements have a sufficient load-bearing capacity.
> Check if the supplied fixing kit may be
used for the wall. > Check the quality of the wall. > If required, use individual stands from
the cascade programme which is availa-
ble as an accessory.
4.6 Removing/fitting the front casing
2
1
4.4 Removing the front casing
Removing the front casing
1
> Undo the screw (1) > Push in both retaining clips (2) so that the front casing is
released. > Pull the front casing forwards at the bottom edge. > Lift the front casing upwards from the bracket.
4.3 Wall-mounting the boiler
> Fit the hanging bracket (1) to the wall using the rawl
plugs and screws provided with the unit.
> Hang the boiler (3) on the hanging bracket from above
using the suspension bracket.
Fitting the front casing
> Place the front casing on the upper brackets. > Push the front casing onto the boiler until the retaining
clips (2) on the front casing snap into place. For support,
you can also pull the retaining clips (2) downwards at the
same time. > Secure the front casing by tightening the screw (1).
Gas installation
5
5 Gas installation
The work described in this section must only be carried out by a competent person.
5.1 Preparing for installation
Danger!
Risk of death caused by improper gas
a
a
b
b
installation!
An incorrect gas installation may result in leaks and an explosion.
> During installation, the legal directives
and the local regulations for gas supply companies must be observed.
Danger!
Risk of death caused by improper gas installation!
Tension in the gas line may result in leaks or an explosion.
> Make sure there are no stresses in the
gas lines when it is installed.
Caution.
Risk of material damage caused by incor­rect gas installation.
Excess test pressure may cause damage to the gas valve.
> When checking the gas valve for leak-
tightness, use a max. test pressure of
1.1kPa (110mbar).
> During the gas installation, ensure that
the home pressure regulation for the required gas flow pressure of 5mbar is maintained in accordance with the tech­nical data (
Caution.
Risk of material damage caused by con­taminated lines.
Foreign bodies, such as welding remnants, sealing residue or dirt in the supply lines for gas, may cause damage to the boiler.
> Blow the gas line thoroughly clean prior
to installation.
¬section18).
Caution.
Risk of material damage caused by the
b
5.2 Connecting the gas line
5.1 Gas connection
> Fit an approved gas valve to the unit with a screw
connector. > Fit the gas supply line to the gas valve. > Purge the gas line before you start up the unit. > Check the gas connection for leak-tightness.
incorrect gas type.
Using the wrong gas type may cause a fault shutdown on the boiler. Furthermore, igni­tion and combustion noise may occur in the boiler.
> Only use the gas type specified in the
type overview (
¬section1.5).
ecoTEC plus installation and maintenance instructions 0020134823_01 17
Hydraulic installation
6
6 Hydraulic installation
The work described in this section must only be carried out by a competent person.
6.1 Preparing for installation
Danger!
Risk of personal injury caused by incor-
a
Any condensate that occurs must only be fed in under con­sideration of the local regulations regarding neutralisation.
b
b
rect installation!
Heating water that leaks from the drain line of the expansion relief valve can cause severe burns.
> Install the expansion relief valve to
ensure that there is no danger to other persons.
> Route a discharge pipe with inlet funnel
and siphon on the customer side from the discharge line of the expansion relief valve to a suitable drain.
> Make sure that the drain is visible.
Caution.
Risk of material damage caused by con­taminated lines.
Foreign bodies such as welding remnants, sealing residue or dirt in the water pipes may cause damage to the boiler.
> Flush the heating installation thoroughly
prior to installation.
Caution.
Risk of damage from corrosion.
If non-diffusion-tight plastic pipes are used in the heating installation, this may cause air to enter the heating water and corrosion of the heat generation circuit and the boiler.
> If using non-diffusion-tight plastic pipes
in the heating installation, separate the system by installing an external heat exchanger between the boiler and the heating installation.
Danger!
Risk of scalding and/or damage due to
a
b
b
The Vaillant ecoTEC boiler should be connected using a Vaillant pump group with modulating pumps (available as an accessory). This pump group has a connection option for an expansion vessel (right-hand connection) and an expansion relief valve (left-hand connection). You can also purchase these as accessories.
> When installing the pump group, observe the installation
sequence for the insulation and the hydraulic pipes
(¬pump group installation instructions). > Note that the boiler pump must always be fitted in the
return line. Otherwise, this may lead to a unit fault.
When connecting several units in cascade operation, you must install a non-return flap from the cascade connection set for each individual unit in the unit supply. A non-return flap from a third-party manufacturer must have no more than 30mbar pressure losses for a volume flow of 4.5m
leaking water.
Stresses in the supply line may cause leaks.
> Make sure there is no voltage in the sup-
ply lines when they are installed.
Caution.
Risk of damage caused by incorrect installation.
Stresses in the supply line may cause leaks.
> Make sure there is no voltage in the sup-
ply lines when they are installed.
Caution.
Risk of damage caused by heat transfer when soldering.
Heat that is transferred during soldering may cause damage to the seals in the serv­ice valves.
> Do not solder the connection pieces if
the connection pieces are screwed to the service valves.
3
/h.
Hydraulic installation
6
6.2 Connecting the heating flow and heating return
Caution.
Risk of material damage caused by incor-
b
b
i
rect installation.
Stresses in the supply line may cause leaks.
> Make sure there is no voltage in the sup-
ply lines when they are installed.
Caution.
Risk of damage to the service valves.
> Do not solder the connection pieces if
the connection pieces are screwed to the service valves.
Seals made of rubber-like materials may be sub-
ject to plastic deformation, which may lead to pressure losses. We recommend using seals made of a paste-like fibre material.
Hydraulic connection
For connection to the system a hydraulic header has to be used. In difficult cases a plate to plate heat exchanger is recommended. In all instances the system water should be adequately treated. To this end, various plate heat exchangers are available as accessories, depending on the output of a unit or in cas­cade connection. The pressure loss is adjusted to the pump group that is offered as an accessory. The minimum volume of circulating water is guaranteed in the unit circuit thanks to the original plate heat exchangers and pump groups, pro­vided the maximum pressure losses are not exceeded in the piping. To prevent contamination, it is recommended that you install a dirt filter when using plate heat exchangers. This prevents excessive contamination of the heat exchanger. Back-purging devices for cleaning the plate heat exchanger are to be placed on-site.
Ø 1 1/4"
6.2 Diameter of the supply lines
1
6.1 Installing the heating flow and heating return
> Insert a flat gasket in each. > Screw the service valves onto the flow and return con-
nection (1) of the pump group.
> Screw the service valves to the customer's installation.
The diameter of the line is 1 1/2".
ecoTEC plus installation and maintenance instructions 0020134823_01 19
The following remaining feed heads are available at the unit supply:
Power Description
80 kW Modulating pump
100 kW
120 kW
6.1 Remaining feed head pump group
If you are using a plate heat exchanger to hydraulically sep­arate the system, the following pressure losses must be maintained:
Modulating pump
Modulating pump
Remaining feed head
0.042 MPa (420mbar)
0.026 MPa (260mbar)
0.024 MPa (240mbar)
Hydraulic installation
min.
180
6
Power
< 120 kW in conjunction with the hydraulic cascade
< 240 kW < 360 kW
< 480 kW < 600 kW < 720 kW
6.2 System separation pressure loss
Max. pressure loss (mbar)
86
96 76
82 87 92
6.3 Connecting the condensate drain pipework
Danger!
Risk of death from escaping flue gases!
a
An empty or insufficiently filled condensate siphon may allow flue gases to escape into the room air.
> Make sure that the condensate siphon is
filled with water when switching on the boiler.
Danger!
Risk of death from escaping flue gases!
a
If the condensate drain pipework is con­nected tightly to a fixed connection on the waste-water piping, the internal condensate siphon can be fully drained until empty.
> Do not connect the condensate drain
pipework tightly to the waste-water piping.
> It is recommended that the condensate
is drained into a tundish. The condensate drain is totally sealed. It may be possible to empty the trap due to syphonic action causing leackage of combustion products:
Condensate forms in the boiler during combustion. The con­densate drain pipework routes the condensate to the waste water connection via a tundish. The boiler is equipped with a condensate siphon. The filling height is 145mm. The condensate siphon collects any con­densate that occurs and feeds it into the condensate drain pipework.
1
2
3
6.3 Condensate siphon
Install the enclosed condensate siphon as follows:
> Place the condensate siphon on the underside of the
boiler on the condensate drain pipe and secure it using the retaining clips.
> Leave an installation space of at least 180mm beneath
the condensate siphon so that you can clean the conden-
sate siphon in the case of service work. > Check the connection for leaks. > Check if a neutralising unit is required in accordance
with national regulations.
To connect the condensate drain pipework, proceed as follows:
> Hang the condensate drain pipework of the boiler in the
pre-installed tundish. > If required, guide the drain hose (1) of the automatic air
vent into the tundish.
The condensate drain pipework connected to the
condensate discharge of the boiler must have a
i
> The connections for the condensate drain pipework must
not be modified or blocked > The condensate drain pipework must terminate in a suit-
able location.
downward gradient throughout its entire length (45mm per metre) and should be installed and connected within the building to prevent possi­ble freezing.
Further information can be obtained from "BS 6798 Specifi­cation for installation of gas-fired boilers of rated input not exceeding 70 kW net". Before the boiler is started up, the condensate siphon (1) must be filled with water as described in the relevant section.
6.4 Connecting the discharge pipe to the
min.
180
expansion relief valve on the heating installation
The expansion relief valve for the heating installation can be connected to the pump group (left-hand side)
> Install the drain line for the expansion relief valve so that
it is not damaged when removing and fitting the lower part of the condensate siphon.
We do not recommend shortening the discharge
pipe that is supplied.
i
> Leave an installation space of at least 180mm beneath
the condensate siphon.
Hydraulic installation
6
1 2
3
6.4 Install the discharge pipe on the expansion relief valve
> Insert a seal (1) in the cap nut (2). > Screw the discharge pipe (3) onto the expansion relief
valve.
> Make the drain line routing as short as possible and in a
downward gradient away from the boiler.
> Allow the line to terminate in such a way that nobody
can be injured and no cable or other electrical compo­nents can be damaged if water or steam is ejected.
> Please note that the end of the line must be visible.
ecoTEC plus installation and maintenance instructions 0020134823_01 21
Flue gas installation
7
7 Flue gas installation
7.1 Preparing for installation
Danger!
Risk of personal injury and material dam-
a
age due to unapproved flue pipes.
Vaillant boilers are certified only with genu­ine Vaillant flue pipes. The use of other accessories may cause personal injury and material damage as well as operating faults.
> Only use genuine Vaillant flue pipes.
You will find a list of genuine flue pipes in the
Vaillant installation instructions for flue pipes.
i
All ecoTEC plus boilers feature an 110/160mm diameter air/ flue gas connection as standard. Selecting the most suita­ble system depends on the individual installation and appli­cation conditions.
> When installing the flue pipe, observe the provisions of
the applicable national regulations. > Agree the flue pipe with your chimney sweep. > Lay the flue pipe with a downward gradient so that any
escaping condensate can easily flow into the drain
(siphon) provided for it without leaving any backwater
residues.
7.2 Installing the flue pipe
> Install the flue pipe using the enclosed installation
instructions.
7.1 Installation example: Vertical roof duct
7.3 Flue gas guiding opening
The following information applies to all flue pipe systems. a. The terminal must be positioned so that the products
of combustion can disperse freely at all times.
b. Water vapour will sometimes be visible from the ter-
minal of the flue gas system. Fitting locations where this could be a nuisance should be avoided.
c. If the terminal is installed less than 2 m above a bal-
cony, above ground or above a flat roof to which peo­ple have access, a suitable terminal guard must then be provided and fitted (contact Tower Flue Compo­nents, Tonbridge, TN9 1TB).
Vertical flues must not terminate within 600mm
of an openable window, air vent or any other
i
The flue gas system must be attached or shielded in such a way that ignition (causing fire) or damage to any part of the building is avoided.
ventilation opening.
Flue gas installation
7
B
D,E
2m
H
E
7.2 Opening of the flue pipe
Installation site
Horizontal flue gas pipes
A Directly below an opening, air bricks, opening
windows, etc.
(5)
Above an opening, air bricks, opening windows,
B
etc.
C Horizontally to an opening, air bricks, opening
windows, etc.
D Below temperature-sensitive building compo-
nents e.g. plastic gutters, down pipes or waste­water pipes
(4)
Below eaves, adjacent to wastewater pipes 50 mm
E F Below balconies or car port roofs 25 mm
(4)
G
From a vertical wastewater pipes or down pipes 50 mm
H From internal or external corners 50 mm
(2)
H
From the edges along to a terminal/outside corner
J Opposite an edge or a terminal 2000 mm
(2)
J
From a surface facing a terminal 1000 mm
L From an opening in the car port (e.g. door,
window) which leads into the dwelling M Vertical from a terminal 1500 mm N Horizontal from a terminal 600 mm
Vertical flue gas pipes
P From another terminal 600 mm Q Above the roof area 600 mm
(3)
R
From adjacent windows that cannot be opened 1000 mm
(2)
From an adjacent wall to the flue gas pipe 300 mm
S
7.1 Position of the opening of a fan-assisted flue gas guiding
Key:
(1)
There should be no ventilation/opening in the eaves within
600mm distance of the terminal.
(2)
These dimensions comply with the building regulations, but they
may need to be increased to avoid wall staining and nuisance fron pluming depending on site conditions.
(3)
It is recommended that an elbow termination is fitted to direct
the plume away from windows.
(4)
If the pipe is shielded from the heat this dimension may be
reduced to 25mm.
A
S
Minimum
dimen-
sions
600 mm
600 mm
600 mm
25 mm
300 mm
N/A
P
Q
Q
B
C
A
B
C
M
H
H
N
(5)
The flue through the roof should not be located within the
shaded area.
(6)
Is is recommended that the terminal should not be located
below 2m in any occupied space.
BS 5440–1: It is recommended that the fanned flue terminal should be positioned as follows:
– at least 2 m from an opening in the building directly
opposite, and
– so that the products of combustion are not discharged
directly across a property boundary.
– Dimensions D, E and F:
(1)
These clearances may be reduced to 25 mm without affecting the performance of the boiler. In order to ensure that the condensate vapour plume does not dam­age adjacent surfaces, the terminal should be extended as shown in ¬fig.7.3.
– Dimension H:
This clearance may be reduced to 25mm without adversely affecting the performance of the boiler. How­ever, in order to ensure that the condensate vapour plume does not damage adjacent surfaces, a clearance of 300mm is preferred. For IE, recommendations are given in the current issue of the IS 813.
Balcony/eaves
Adequately secured air/flue gas pipe
7.3 Opening of the flue gas system under balconies or eaves
The flue pipe must protrude beyond any overhang
Gutter
ecoTEC plus installation and maintenance instructions 0020134823_01 23
8 Electrical installation
8 Electrical installation
The work described in this section must only be carried out by a competent person.
8.1 Preparing for installation
Danger!
Risk of death from electric shock!
e
e
Touching live connections may cause seri­ous personal injury.
> Switch off the power supply. > Secure the power supply against being
switched on again by unauthorised per­sons while you are working on the boiler.
Danger!
Risk of death from electric shock as a result of an improper electrical connection!
An improper electrical connection may adversely affect the operational safety of the boiler and result in material damage or personal injury.
> The electrical installation must be car-
ried out by a suitably qualified compe­tent person who is responsible for com­plying with the existing standards and directives.
> Connect the boiler in accordance with
BS7671 (IEE Regulations).
> For IE: Observe the current ETCI regula-
tions (Electro Technical Council for Ireland).
> Earth the boiler.
8.2 Opening/closing the electronics box
> Remove the front casing of the boiler (¬ section. 4.6).
2
1
8.1 Opening the back wall of the electronics box
> Tilt the electronics box (1) forwards. > Loosen the clips (3) from the brackets. > Tilt the cover (2) upwards.
Closing the electronics box
> Close the cover (2) by pushing downwards on the elec-
tronics box (1).
> Ensure that all clips (3) audibly click into the brackets. > Tilt the electronics box upwards. > Push the four right and left clips of the box against the
side panels on the boiler until you hear them click into place.
> Attach the front casing of the boiler (¬section4.6).
8.3 Establishing the mains connection and connecting the pump group
3
e
b
Danger!
Risk of death from electric shock!
Mains connection terminals L and N remain permanently live even if the boiler on/off button is switched off!
> Before establishing the mains connec-
tion, switch off the power supply.
Caution.
Risk of material damage caused by the incorrect supply voltage!
At mains voltages greater than 253 V and less than 190 V, the functions may be impaired.
> Make sure that the rated voltage of the
mains is 230 V.
Caution.
230V~ 230V~
NL
Risk of damage caused by incorrect
b
b
In IE, reference should be made to the current edition of the ETCI (Electro-Technical Council for Ireland) rules.
The boiler is supplied for connection to 230 V, ~ 50 Hz sup­ply fused at 3 A. The connection to the supply network is made using a 3 A fused double-pole isolator with a contact opening of at least 3 mm at all poles. A prerequisite here is that only the boiler and controllers are connected). At the connection point to the mains, it must be possible to com­pletely isolate the boiler and its auxiliary controllers electri­cally. The connection should be easily accessible and adja­cent to the boiler. Use a three-core flexible cable in accord­ance with BS 6500, tables 6, 8 or 16 (3 x 0.75 to 3 x 1.5mm The rated voltage of each line in the mains must be 230 V; with mains voltages over 253 V and below 190 V, the unit may not function properly.
> Open the electronics box (¬section8.2). > Use a flexible, commercial mains connection cable that is
compliant with standards.
> Guide the mains connection cable through the cable duct
on the left of the base of the unit.
> Use the grommet supplied to seal the cable duct.
installation.
Mains voltage at the incorrect plug termi­nals on the ProE system may destroy the electronics.
> Only connect the mains connection cable
to the terminals marked for the purpose.
> Use a flexible connection cable.
Caution.
Risk of damage caused by incorrect installation.
Connecting wires that have been stripped too far may cause short circuits and dam­age the electronics if a strand accidentally comes loose.
> Only strip the lines a maximum of 3 cm
to prevent short circuits. > Lay the lines correctly. > Use strain reliefs.
2
).
Electrical installation
NL
230V~ 230V~
8.2 Cable routing of the mains connection cable
> Insert the mains connection cable into the electronics
box. > Uses the strain reliefs provided. > Shorten the flexible mains connection cable as neces-
sary. > Strip the flexible mains connection cable by 2-3 cm, but
not more than 3 cm. > Insulate the conductor of the flexible mains connection
cable. > Fit conductor end sleeves on the stripped ends of the
conductors. > Connect the provided green ProE plug for the mains con-
nection to the flexible mains connection cable using a
screwdriver. > Insert the ProE plug into the corresponding PCB slot
(L, N and earth) (¬fig.8.2). > Lay the lines correctly. > Secure the cable in the electronics box using the strain
reliefs. > Close the electronics box (¬section8.2).
Ensure that the connection cables are securely
fastened to the plug terminals.
i
8
ecoTEC plus installation and maintenance instructions 0020134823_01 25
Electrical installation
8
X22
X18
230 V
8.3 Connecting the pump group to the PCB
> Guide the pump cable for the pump group through the
cable duct to the right on the underside of the unit. > Uses the strain reliefs provided. > Connect the power supply network plug of the pump
group to the X18 slot on the PCB (¬fig.8.3). > Connect the control cable of the pump group to the X22
slot on the PCB (¬fig.8.3). > Lay the lines correctly. > Secure the lines using the strain reliefs in the electronics
box. > Close the electronics box (¬section8.2).
Ensure that the connection cables are securely
fastened to the plug terminals.
i
8.4 Connecting the controller
8.4.1 Fitting the controller
> Fit the controller in accordance with the respective
installation instructions.
8.4.2 Connecting controllers to the electronic system
Caution.
Risk of damage caused by incorrect
b
b
installation.
Connecting wires that have been stripped too far may cause short circuits and dam­age the electronics if a strand accidentally comes loose.
> Only strip the lines a maximum of 3 cm
to prevent short circuits. > Lay the lines correctly. > Use strain reliefs.
Caution.
Risk of material damage caused by incor­rect installation.
Mains voltage at the incorrect plug termi­nals on the ProE system may destroy the electronics.
> Do not connect a mains voltage to the
eBUS terminals (+/-).
Make sure that the conductors are securely fas-
tened to the plug terminals of the ProE plug.
i
> Open the electronics box (¬section8.2). > Guide the supply lines of the components to be con-
nected (e.g. external controller, external sensor) through
the cable duct to the left on the underside of the unit. > Insert the supply lines into the electronics box. > Uses the strain reliefs provided. > Shorten the supply lines as necessary. > Strip the supply lines 2 - 3 cm, but not more than 3 cm. > Strip the conductor on the supply lines. > Fit conductor end sleeves on the stripped ends of the
conductors. > Connect the ProE plug to the supply lines of the control-
ler using a screwdriver. > Insert the ProE plug into the associated PCB slot
(¬fig.8.4). > Lay the lines correctly. > Secure the cable in the electronics box using the strain
reliefs. > If you do not connect a room/timer thermostat to the
boiler, bridge the input RT 24 V if no bridge exists. > If you connect a room/timer thermostat to the boiler,
remove the bridge at input RT 24 V, if a bridge exists. > If you connect a weather-controlled compensator or
room temperature control system via eBUS, then bridge
input RT 24 V, if no bridge exists. > Close the electronics box (¬section8.2).
Electrical installation
8
> In order to achieve pump operating mode 1 "Comfort"
(continuously running pump) for multi-circuit controllers, set the diagnostics code D.018 Pump operating mode from 3 = "Eco" (intermittent pump) to 1 = "Comfort" (¬section12.1.2).
> If the system partition is installed, set the pump to Com-
fort (D.018) and set the pump output to at least 4 (85 %, D.014). The same setting applies for installing units in cascade.
Please note that the bridge at the ProE plug
must be removed when connecting a maximum
i
8.5 Connecting additional units
b
thermostat (contact thermostat) for underfloor heating.
Caution.
Risk of damage caused by incorrect installation.
Connecting wires that have been stripped too far may cause short circuits and dam­age the electronics if a strand accidentally comes loose.
> Only strip the lines a maximum of 3 cm
to prevent short circuits. > Lay the lines correctly. > Use strain reliefs.
For cascade operation according to the B23p configuration, you must provide a motorised flue non-return flap for each unit and this is actuated by the VR40 multi-functional module. The installation instructions for the VR 40 describe how the flue non-return flap is activated.
> For smooth operation in cascade, use the diagnostics
code D.050 to raise the fan speed in partial load opera­tion to 1500 rpm.
8.5.1 VR 40 - Connecting the "2 from 7" multi­functional module
You can connect two additional components to the ecoTEC plus using the Vaillant multi-functional module "2 from 7" ( Accessories).
You can switch the following components:
– Circulation pump – External pump – Cylinder charging pump – Fume extractor hood/flue non-return flap – External solenoid valve – External fault signal – Not active – Remote control eBUS (not active) – Anti-legionella pump (not active)
> Install the components in accordance with the respective
installation instructions.
> Select diagnostics code D.018 to actuate relay 1 on the
multi-functional module at installer level (¬section12.1).
> Select diagnostics code D.028 to actuate relay 2 on the
multi-functional module at installer level (¬section12.1).
ecoTEC plus installation and maintenance instructions 0020134823_01 27
Electrical installation
8
8.6 Connection wiring diagram
Display connection
blue
pink
white
white
blue
Safety cut-out
red
Gas valve
Wate r pressure sensor
Cylinder sensor (optional)
Cylinder contact “C1-C2“
Wate r DD
Safety cut-out
Pump PWM signal
Flow sensor
Flow sensor
Flue gas DD
Remote control circulation pump External sensor Flow sensor (optional) DCF connection Earth
Edge connector
blue
white
pink
Earth
Contact thermostat/burner off
Ext. room th. 3-4 (contact, 24 V) Bus connection
(Controller(room th. digital)
Accessory output
pink
grey
blue
green
white
(Select via D.26)
Unit earth
Mains connection
turquoise
8.4 Connection diagram for the ecoTEC plus electronics box
Ioni. signal
Unit earth
Fa n
Charging pump
internal pump
Ext. ignition transformer (supply)
PWM
Hall signal
Earth
Establishing operational readiness
9
9 Establishing operational readiness
The Vaillant ecoTEC plus boiler is fitted with a digital infor­mation and analysis system (DIA). If additional settings are required, which have not been configured using the installa­tion assistant, you can view and modify further parameters using the DIA.
The operating concept and operation of the boiler are described in the ¬Operating instructions of the boiler. The read-off and setting facilities of the operator level are also described in the ¬Operating instructions.
9.1 Reading the temperature or pressure display
Left-hand button : Hot water handling ¬ Cylinder temperature Right-hand button temperature/water pressure
: Heating mode ¬ Heating
50
Press the right-hand selection button twice to read off the digital filling pressure value.
9.2 Preparing the heating water
Observe the specifications concerning heating water prepa­ration in (¬section2.4.5).
9.3 Filling and purging the heating installation
Caution.
Risk of material damage caused by con-
b
taminated lines!
Foreign bodies, such as welding remnants, sealing residue or dirt in the water pipes, may cause damage to the boiler. It is rec­ommended that you use a dirt trap on older systems upstream of the ecoTEC plus.
> Thoroughly flush newly installed part of
the heating installation prior to start-up.
The system is filled via a filling connection installed on-site, which must be fitted at a suitable location in the heating circuit. This connection must be removed again after the filling process is complete. If the local water authority does not permit temporary connections you must use a closed system filling pump with an interrupt vessel. Automatic fill­ing of the heating system does not take place from the hot water side. (Alternative procedures for filling closed sys­tems are described in BS 5449). To ensure the correct operation of the heating installation, the indicator on the pressure gauge must point to the upper half of the grey area or in the middle of the bar graph display (marked by the dashed limit value) when the heating installation is cold. This corresponds to the filling pressure between the minimum and maximum recom­mended pressure. You can also display the exact filling pressure.
9.1 Reading the temperature or pressure display
The boiler is fitted with an analogue pressure gauge and also has a symbolic bargraph display for the fill pressure of the heating installation and a digital pressure and tempera­ture display. You can see the pressure gauge once you have removed the front casing of the boiler.
ecoTEC plus installation and maintenance instructions 0020134823_01 29
> Flush the newly installed part of the heating installation
thoroughly before filling it.
> Open all thermostatic radiator valves in the heating
installation.
> Select check programme P.6 (¬section11.4).
The check programme starts, the burner and pump are switched off (to fill or drain the boiler).
9.3.1 Filling the heating installation
> Connect a hose between a cold water valve and the fill-
ing line of the heating system.
> In order to fill the heating installation, first open the cold
water valve.
> Open all thermostatic radiator valves.
Establishing operational readiness
9
> Check that both service valves on the boiler are open. > Slowly open the stop valve on the filling line so that the
water flows into the heating system.
If the water pressure in the heating system is
too low, the display view switches between fault
i
> Purge the lowest radiator until water flows out of the
purging valve without bubbles.
> Purge all other radiators until the entire heating system
has been filled with water. Close all purging valves.
> Use the display to monitor the rising filling pressure in
the heating installation.
> Top up with water until the pressure gauge display is in
the middle of the grey area and the required filling pres­sure appears on the display.
> After filling, close the stop valve on the filling line as well
as the cold water valve and remove the filling hose. > Check all connections and the entire system for leaks. > Each time the unit is filled and topped up, document this
in a system book.
i
message F.22 and the display of the actual pres­sure when the boiler is switched on.
Ensure that the filling and drainage tap in the
heating installation is connected to a cold water valve in accordance with the standard.
9.3.3 Flush the heating installation for the first time ("cold")
The complete heating system must be flushed at
least twice: once with cold water and once with
i
> Check whether all thermostatic radiator valves and both
service valves on the boiler are open.
> Connect a hose to the drain valve that is located at the
lowest position in the heating system.
> Fully open the radiator valves and drain cocks to ensure
that the water drained quickly. Starting at the top of the system open the air vents on the radiators to aid com-
plete draining of the contaminated water. > Close the drain cocks. > Refill the heating system with water, as described in
(¬section9.3). > Check that the expansion relief valve of the heating sys-
tem is functioning correctly by turning the handle on the
valve. > Check the pressure in the heating system and top up
with water if necessary. > Close the filling valve and the cold water valve.
hot water in accordance with the following instructions.
9.3.2 Purging the heating installation
> To purge the heating installation, select check pro-
gramme P.0 (¬section11.4).
The boiler does not start up, the internal pump operates intermittently and, as an option, purges the heating circuit or the hot water circuit. The display shows the filling pres­sure of the heating installation.
> The filling pressure of the heating installation must not
fall below 0.08 MPa (0.8 bar) when purging is in progress as, otherwise, this will not be carried out properly.
Check programme P.0 runs for 6.5 minutes.
> Purge all the radiators. > Then check the water pressure in the heating installation
again. At the end of the filling procedure, the filling pressure of the heating installation should be at least 0.02 MPa (0.2bar) above the counterpressure of the expansion vessel
P
("Exp") (P
> If there is still too much air in the heating installation at
> Check all connections for leak-tightness.
Installation
the end of check programme P.0, repeat the check pro-
gramme.
+ 0.02 MPa (0.2 bar)).
Exp
9.4 Preventing low water pressure
To prevent damage to the heating installation that is caused by low water pressure, the boiler is fitted with a water pres­sure sensor. If the water pressure falls below 0.1 MPa (1.0bar), the boiler indicates low pressure by displaying a flashing pressure value. If the water pressure falls below
0.05MPa (0.5bar), the boiler switches off. The display shows F. 2 2 .
> Top up the heating water and switch the boiler on again.
A flashing pressure value appears on the display until a pressure of 0.11 (1.1 bar) or higher has been reached.
> If you notice frequent drops in pressure, then determine
and eliminate the cause.
Establishing operational readiness
9
9.5 Filling the condensate siphon
Danger!
Risk of poisoning due to escaping flue
a
gas.
An empty or insufficiently filled condensate siphon may allow flue gas to escape into the room air.
> Fill the condensate siphon with water
before starting up the boiler.
1
2
9.6 Checking the gas ratio setting
9.6.1 Default setting
Caution.
An incorrect gas-family setting can
b
If the unit should be operated with liquid gas (propane), do not start up the unit. Instead, contact Vaillant Customer Service. They will convert the unit and then start it up. The same applies for the conversion from liquid gas (pro­pane) to natural gas. This conversion must also only be car­ried out by Vaillant Customer Service.
The combustion of the ecoTEC plus has been factory tested and is preset for operation with the gas group indicated on the identification plate (¬ table 13.1). In some areas these settings may need to be adjusted at the installation site.
cause operating faults or a reduction in the working life of the boiler!
If the unit design does not correspond to the locally available gas family, you will experience error functions or you will have to replace boiler components prematurely
for example, a liquid-gas boiler must not be operated with natural gas.
> Before starting up the boiler, compare
the details concerning the set type of gas on the identification plate with the type of gas supply at the installation site.
;
It is not necessary to check the gas volume dur-
9.2 Filling the condensate siphon
i
> Remove the siphon lower section (2) by unscrewing it
from the condensate siphon (1).
> Fill the siphon lower section with water up to about
10mm below the upper edge.
> Secure the siphon lower section correctly to the conden-
sate siphon again.
ecoTEC plus installation and maintenance instructions 0020134823_01 31
9.6.2 Checking the leak-tightness of the flue gas
> Check that the flue gas system is intact, in accordance
with British Gas TB 200.
> If the flue gas system is longer than 2m, we urgently
recommend that you test the system for flue gas recircu­lation as described below.
ing initial start-up. The adjustment takes place based on the CO gas ratio setting must be defined in the attached commissioning checklist.
system and for flue gas recirculation
component in the flue gas. The
2
Establishing operational readiness
9
9.3 Flue gas and air analysis points
Key:
1 Flue gas analysis point 2 Air analysis point
> Use the air analysis point (2) to check for flue gas recir-
culation.
> Use the flue gas measuring instrument. > If you discover CO or CO
leak in the flue gas system or for flue gas recirculation.
> Eliminate the damage. > Repeat the above-mentioned test to determine if the
fresh air contains CO or CO
> If you cannot eliminate the damage, you must not start
up the boiler.
in the fresh air, search for a
2
.
2
1
806/5-5
1
1006/5-5 1206/5-5
1
9.6.3 Checking the gas connection pressure
(gasflow pressure)
> Ensure that the gas connection pressure (gas flow pres-
sure) can be still achieved if all other gas-fired boilers in
the dwelling/house are in operation.
> Remove the front casing from the boiler (¬section4.6). > Close the gas isolator cock of the boiler.
Permissible gas connection pressure (gas flow
pressure) for natural gas operation:
i
2 kPa (20mbar) to 2.5kPa(25 mbar)
9.4 Measuring the gas connection pressure (gas flow pressure)
> Undo the sealing screw of the measuring nipple (1)
(lower screw) at the gas valve using a screwdriver.
> Connect a digital pressure gauge or U tube manometer
to the measuring nipple (1).
> Open the gas isolator cock of the boiler. > Start the boiler by activating check programme P.1, as
described in ¬section14.4.
> Turn the room thermostat fully up to that the maximum
heat in the heating installation can be shown.
> Measure the gas connection pressure in comparison with
atmospheric pressure.
Operation
10
Caution.
Possible material damage and operating
b
If the gas connection pressure (gas flow pressure) is within the permissible range, proceed as follows:
> Switch off the boiler by:
> Close the gas isolator cock of the boiler. > Remove the pressure gauge and tighten the sealing
screw of the measuring nipple (1).
> Open the gas isolator cock of the boiler. > Ensure that there are no leaks at the sealing screw. > Refit the front casing. > Reset boiler controls for normal operation. > Make a note of the gas connection pressure (gas flow
pressure) (kPa or mbar) of the boiler in the commission-
ing checklist for starting up the gas-fired boiler.
If the gas connection pressure (gas flow pressure) is not within the permissible range and you cannot eliminate the fault, please notify the gas supply company or the Vaillant Service Solutions Team, and proceed as follows:
> Switch off the boiler by ending check programme P.1. > Close the gas isolator cock of the boiler. > Remove the pressure gauge and re-tighten the sealing
screw of the measuring nipple (1).
> Open the gas isolator cock. > Ensure that there are no leaks at the sealing screw. > Turn the gas isolator cock off. > Refit the front casing. > Disconnect the power supply to the boiler. > You must not start up the boiler yourself.
faults caused by incorrect connection pressure.
If the gas connection pressure lies outside the permissible range, this can cause oper­ating faults on the boiler.
> Do not make any settings on the boiler. > Do not operate the boiler. > Check the pressure control system at the
entrance to the property.
> Advise the responsible gas supply
company.
– Ending check programme P.1 as described in
¬section11.4.
10 Operation
10.1 Calling up the installer level
Caution.
Risk of damage caused by incorrect
b
The following overview shows the options for reading infor­mation and making settings at installer level.
The installer level is secured against unauthorised access with a password because incorrect parameter settings at this level may cause functional faults and damage to the heating installation.
> Press the left
buttons ("i") simultaneously
The following menu appears on the display.
> Scroll using the minus button
ton appears.
> Press the right-hand selection button
select the menu point.
"Enter code" and the value "00" appear in the display.
> Select the value 17 (code) using the minus button
> Press the right-hand selection button
firm the entered code.
The installer level appears with a selection of menu points.
i
handling.
Incorrect settings at installer level can cause damage to the heating installation.
> You must only access the installer level if
you are an approved competent person.
and right selection
or the plus but-
until the menu point "Installer level"
to
or the plus button .
to con-
At the installer level the path to access the Fault
list, Test Programmes, the Appliance Configura­tion, Diagnosis Menue and Installation Assist are outlined in the following overview, e.g.
Menu ¬ Installer level ¬ Test programmes ¬ Check programmes.
ecoTEC plus installation and maintenance instructions 0020134823_01 33
i
If you exit the installer level and then access it
again within 15 minutes, you do not have to enter the code again.
Operation
10
10.2 Overview of the menu structure
Menu Information Reset burner off time
Installer level
Back Select
Enter code
1 7
Back OK
Installer level
Fault list
Test programs Appliance config.
Back Select
Installer level Fault list
Test programs
Appliance config.
Back Select
F. 0 0
F.7 5
Interruption
Fa ul t
Flow sensor
Pump water shortage
Test programs
Check programs
Gas type check Function menu
Back Select
Test programs Check programs
Gas type check
Function menu
Back Select
Test programs Gas type check
Function menu
Self test electronics
Back Select
Test programs Gas type check Function menu
Self test electronics
Back Select
P. 0 0
Purging
P. 0 0
Purging
Pump is
Pump is
cyclically
cyclically
actuated
actuated
Back Select
Back Select
Gas type check
Type of gas
LPG
Select
Back Select
T. 01
T. 01
internal pump
internal pump
Back Select
Back Select
Self test
Self diagnosis
of the electronics
Back Select
Installer level Test programs
Appliance config.
Diagnosis menu
Back Select
10.1 Overview of the menu structure for installer level, part 1
Appliance config.
Language
Target flow temp. DHW temperature
Back Select
Appliance config. Language
Target flow temp.
DHW temperature
Back Select
Appliance config. Language Target flow temp.
DHW temperature
Back Select
Language
01 Deutsch
Cancel OK
Target flow temp.
41
Cancel OK
DHW temperature
35
Cancel OK
Operation
10
Appliance config. Target flow temp. DHW temperature
Comfort mode
Back Select
Appliance config. DHW temperature Comfort mode
Auxiliary relay
Back Select
Appliance config. Comfort mode Auxiliary relay
Accessory relay 1
Back Select
Appliance config. Auxiliary relay Accessory relay 1
Accessory relay 2
Back Select
Appliance config. Accessory relay 1 Accessory relay 2
Heating partial load
Back Select
Comfort mode
Comfort on
Cancel OK
D.026
D.026
Auxiliary relay
Auxiliary relay
Circulation pump
External pump
Back
Cancel OK
D.027
D.027
Accessory relay 1
Accessory relay 1
Circulation pump
External pump
Back
Cancel OK
D.028
D.028
Accessory relay 2
Accessory relay 2
Circulation pump
External pump
Back
Cancel OK
D.000
Heating partial load
0
Cancel OK
Appliance config. Accessory relay 2 Heating partial load
Contact data
Back Select
Appliance config. Heating partial load Contact data
Factory setting
Back Select
Installer level Test programs Appliance config.
Diagnosis menu
Back Select
Installer level Appliance config. Diagnosis menu
Start inst. assistant
Back Select
10.2 Overview of the menu structure for installer level, part 2
D.000
D.001
Heating partial load
Back
To start the In-
stallation assist.
Cancel OK
Pump overrun
Heating
0
0
Back
press OK
Contact data
Phone number
Back
D.096
Reset to
factory settings?
No
Cancel OK
ecoTEC plus installation and maintenance instructions 0020134823_01 35
Start-up
11
11 Start-up
Danger!
Risk of poisoning and scalding caused by
a
i
i
Auxiliary service equipment:
The following test and measuring equipment is required for start-up:
– Calibrated CO – Digital or U tube manometer
escaping hot flue gases.
Hot flue gas may escape and cause poison­ing and scalding, if the boiler is operated with an incompletely fitted or open flue pipe or if the boiler is operated with the front casing open in the event of internal leaks.
> Operate the boiler
- for start-up
- for testing
- in continuous mode only when the front casing is closed and the flue pipe is fully installed and closed.
Initial start-up is performed by a Vaillant cus-
tomer service engineer or by a competent per­son approved by Vaillant. The appliance must be comissioned by a competent person who is in possession of a calibrated gaz analyser. Initial start-up is performed in accordance with the commissioning checklist and is also acknowl­edged there by the approved competent person. The commissioning checklist that is attached to the installation instructions must be filled out and carefully stored with the unit's documentation.
Before filling the heating circuit and during fur-
ther operation, the cap of the automatic air vent must be open. To purge the heating circuit, use purging pro­gramme "P.0" (¬section11.4).
-measuring instrument
2
lation assistant is displayed each time the boiler is switched on until it has been completed successfully. You must confirm the launching of the installation assistant. Once confirmed, all of the heating and process water demands from the boiler are blocked. This status remains until the installation assistant is completed or cancelled. If you do not confirm the launch of the installation assist­ant, it is closed 10 seconds after you switch on the unit and the basic display then appears. The next time the boiler is switched on using the on/off button, the installation assist­ant will be started again.
11.2.1 Language
> Select the required language using the minus or plus
button.
> Press the right-hand selection button to confirm the
selected language.
The language change must be confirmed a second time in order to avoid an unintentional change.
If you unintentionally select a language that you
cannot understand, you can change it again as
i
> Press the right-hand selection button and the plus but-
ton simultaneously and hold them down.
> Press the fault clearance key for a short time. > Continue to press and hold the right-hand selection but-
ton and the plus button until the display offers you the option to set the language.
> Use the minus button or plus button to select your
desired language.
> Confirm the change by pressing the right-hand selection
button ("OK").
11.2.2 Purging
> Fill the heating circuit slowly and purge the boiler via the
purging device fitted in the supply pipe.
> Then start the purging check programme either via the
installation assistant or P.0 (¬section11.4).
described below.
11.1 Switching on the boiler
> Press the on/off button (¬ Operating instructions).
The basic display appears on the display.
11.2 Installation assistant
The installation assistant is started when switching on the boiler for the first time. It provides easy access to the main configuration settings for installation of the unit. The instal-
11.2.3 Heating temperature
> Press the "Operating Mode" selection button.
The heating temperature is displayed.
> Use the plus/minus buttons to set the desired
temperature.
> Confirm your setting with "OK".
Start-up
11
11.2.4 Heating partial load
The heating partial load of the Vaillant ecoTEC plus boiler is factory set to "auto". This means that the boiler independ­ently determines the optimum heating output depending on the current heat demand of the system. A setting is nor­mally no longer required. The setting can also be changed at a later point using diagnostics code D.000.
11.2.5 Auxiliary relay and multi-functional module
Additional components that are attached to the boiler can be adjusted directly here. This setting can be changed using diagnostics codes D.026, D.027 and D.028.
11.2.6 Competent person telephone number
You can store your telephone number in the unit menu. The operator can display this number in the information menu. The telephone numbers can be up to 16 digits long and must not contain any spaces. If the telephone number is shorter, end the entry after the last digit by pressing the right-hand selection button. All of the digits to the right will be deleted.
11.2.7 Ending the installation assistant
If you have successfully run through and confirmed the installation assistant, it will not start up automatically next time the unit is switched on.
11.2.8 Restarting the installation assistant
You can restart the installation assistant any time by calling it up manually in the menu.
Menu ¬ Installer level ¬ Installation assistant
11.4 Using test programmes
In addition to the installation assistant, you can also call up other test programmes for start-up.
Menu ¬ Installer level ¬ Test programmes
There, you can not only find the function menu (¬section13.3) and an electronics self-test (¬section13.3.1) but also the check programmes.
Menu ¬ Installer level ¬ Test programmes ¬ Check programmes
By activating various check programmes, you can trigger special functions on the boilers. The following four check programmes are available:
Display Meaning
1)
P. 0
P.1 Maximum load check programme:
P.2 Minimum load check programme:
P.6 Filling mode check programme:
Purging check programme: The heating circuit and the hot water circuit are purged via the automatic purging valve (the cap of the auto­matic purging valve must be released).
1 x right-hand selection button (" -> "): Start purg-
ing heating circuit
2 x right-hand selection button (" -> "): Start purg-
ing hot water circuit
1 x left-hand selection button ("Cancel"): Exit purging
programme
The heating pump is timed Note: Purging programme runs for 6.5minutes.
After successful ignition, the boiler is operated at maxi­mum heat input.
After successful ignition, the boiler is operated at mini­mum heat input.
The diverter valve (VUV) is moved to the mid-position. The burner and pump are switched off (to fill or drain the boiler).
11.3 Appliance configuration and diagnostics
menu
If you have already filled and purged the heating installa­tion and have ended the installation assistant but wish to set the most important system parameters again, you can also call up the "Appliance configuration" menu point.
Menu ¬ Installer level ¬ Appliance configuration
All of the setting options for more complex systems can be found in the diagnostics menu (¬section12).
Menu ¬ Installer level ¬ Diagnostics menu
ecoTEC plus installation and maintenance instructions 0020134823_01 37
11.1 Overview of the check programmes
1)
Purging the heating circuit:
Diverter valve in heating position, actuation of the heating pump for 15 cycles: 15s on, 10s off. Display: "Active heating circuit".
Purge hot water circuit:
After the above-mentioned cycles have passed or after repeated confirmation using the right-hand selection button: diverter valve in hot water position, actuation of heating pump as above. Display: "Active hot water circuit".
Starting check programmes
Menu ¬ Installer level ¬ Test programmes ¬ Check programmes
Start-up
11
11.5 Checking the function of the boiler
> After completing the installation and the gas ratio set-
ting, perform a complete function check of the boiler
before starting up the boiler and handing it over to the
operator.
> Document the setting values and that all checks have
been performed in the commissioning checklist.
11.5.1 Carrying out a full function test
> Start up the boiler in accordance with the relevant oper-
ating instructions and commissioning checklist. If you have not yet completed the installation assistant and have then confirmed, this will be restarted when you switch on the unit. Before continuing, complete the installation assistant (¬section11.2).
11.5.2 Checking the heating mode
> Switch on the boiler. > Make sure that there is a heat requirement. > Activate the Live monitor (¬section14.2.1).
S.04
Heating mode
Burner on
Back
11.2 Live monitor – display during heating mode
If the boiler is running correctly, the display will show the status code "S04". The status code displayed will also be explained by the plain text display "Heating mode, burner on".
11.5.3 Checking the hot water generation
To test that hot water generation is functioning correctly, proceed as follows:
11.1 Checking leak-tightness
> Check the gas supply line, the flue gas installation, the
heating installation and the hot water pipes for leak-
tightness.
> Check the flue pipe for proper installation. > Make absolutely sure that the front casing is properly
closed.
> Check the operation of the heating (¬section11.5.2). > Hand over the boiler to the operator
(¬section12.2).
> Explain the basic operation of the heating installation to
the operator.
You can display the current operating condition of the boiler in the "Live monitor" on the boiler display (¬section14.2.1).
Menu ¬ Live monitor
> Switch on the boiler. > Turn on a hot water draw-off point fully. > Activate the Live monitor (¬section14.2.1).
When the hot water generation is working correctly the dis­play shows "S.14".
S.14
DHW mode
Burner on
Back
11.3 Live monitor – Hot water generation
Adapting the unit to the heating installation
12 Adapting the unit to the heating
installation
The installation assistant is started when the boiler is switched on for the first time (¬section11.2).
If you have already filled the heating installation and termi­nated the installation assistant, but wish to set the most important system parameters again, you can also call up the "Appliance configuration" menu point.
Menu ¬ Installer level ¬ Appliance configuration
All of the settings for more complex systems can be found in the diagnostics menu.
Menu ¬ Installer level ¬ Diagnostics menu
12.1 Overview of the parameters in the
diagnostics menu
Menu ¬ Installer level ¬ Diagnostics menu
12
You can use the parameters that are marked as adjustable in ¬table12.1 to adapt the boiler to the heating installation and the needs of the customer:
You can enter your settings in the last column
after setting the system-specific parameters.
i
> Press the minus button
to switch between the displayed diagnostics
codes. For modifiable parameters:
> Press the right-hand selection button
("Select") to select the parameters to be changed.
> Press the minus button
to change the current setting.
> Press the right-hand selection button
to confirm the change. The change is saved.
or the plus button
or the plus button
("OK")
ecoTEC plus installation and maintenance instructions 0020134823_01 39
Adapting the unit to the heating installation
12
Code Parameters Adjustable values
D.000 Heating partial load Adjustable heating partial load in kW
D.001 Overrun time of internal heating pump for
heating mode
D.002 Max. burner anti-cycling time heating at
20 °C flow temperature
D.017 Heating flow/return regulation changeover 0 = Flow, 1 = Return 0 do not
D.018 Pump operating mode setting 1 = Comfort (continuously operating pump)
D.027 Switching of relay 1 on the
"2 in 7" multi-functional module VR 40
D.028 Switching of relay 2 on the
"2 in 7" multi-functional module VR 40
D.046 Pump type 0 = Relay with disable facility
D.050 Offset for minimum speed In rpm, adjustment range: 0 to 3000 Rated value D.051 Offset for maximum speed In rpm, adjustment range: -990 to 0 Rated value D.071 Target value maximum heating flow tem-
perature
D.072 Internal pump overrun after cylinder
charging
D.077 Partial load for cylinder charging [kW] D.084 Maintenance indicator: Number of hours
until the next maintenance
D.093 DSN unit variant setting Adjustment range: 0 to 99 D.094 Delete fault history 1 = Delete fault list
D.096 Factory setting 1 = Reset all adjustable parameters to factory setting
auto: Unit automatically adjusts max. partial load to current system demand)
2–60min 5min
2–60min 20min
3 = Eco (intermittently operating pump) 1 = Circulation pump 2 = Ext. pump 3 = Charging pump 4 = Extractor hood 5 = Ext. solenoid valve 6 = Ext. error message 7 = Not active 8 = Remote control eBUS (not yet supported) 9 = Anti-legionella pump (not active) 1 = Circulation pump 2 = Ext. pump 3 = Charging pump 4 = Extractor hood 5 = Ext. solenoid valve 6 = Ext. error message 7 = Not active 8 = Remote control eBUS (not yet supported) 9 = Anti-legionella pump (not active)
1 = PWM with disable facility
40 to 85 °C 75 °C
Adjustable from 0 to 10min 2min
Adjustment range: 0 to 3010hrs und "-" for deacti­vated
Factory setting
Auto
3 = Eco
1
2
0
"-"
Your own setting
adjust
12.1 Adjustable parameters of the diagnostics menu
Adapting the unit to the heating installation
12
12.1.1 Setting the heating partial load
The heating partial load of the Vaillant ecoTEC plus boiler is factory set to "auto". This means that the unit independ­ently determines the optimum heating output depending on the current heat demand of the system. A setting is nor­mally no longer required. If you still want to set a fixed maximum heating partial load, you can set a value under diagnostics code D.000, which equates to the unit output in kW. If the unit is operated in cascade, you must increase the fan speed of the unit partial load to 1500rpm (diagnostics code D.050). If a domestic hot water cylinder (cylinder type VIH) is installed, you can adjust the partial load setting for the cyl­inder charging to the cylinder type.
12.1.2 Adjusting pump overrun and pump
operating mode
The pump overrun time for heating mode is set at the fac­tory to a value of 5 minutes. You can set the pump overrun under diagnostics code D.001 within the range of 1 minute to 60 minutes. You can set a different pump operating mode under diagnostics code D.018. Here you have the choice between Eco and Comfort.
Comfort (continuously operating pump)
The internal pump is switched on when the heating flow temperature is not at "Heating off" (¬Operating instruc- tions) and the heating requirement is enabled via an exter­nal controller.
Eco (intermittently operating pump)
In the factory, the Eco pump operating mode is set. This pump operating mode is useful for removing residual heat after cylinder charging when the heat demand is extremely low and large temperature spreads exist between the cylin­der charging and heating mode target values. This prevents living rooms from being under-supplied. If there is a heat demand, the pump is switched on every 25 minutes for 5minutes once the overrun time has elapsed. If a system partition is installed, you must set the pump to Continuous mode (85%) (set diagnostics code D.014 to 4).
12.1.4 Setting the return flow temperature control
If the boiler is connected to an underfloor heating system, the temperature control can be changed from flow temper­ature regulation (default setting) to return flow temperature control under diagnostics code D.017.
12.1.5 Burner anti-cycling time
Setting the burner anti-cycling time To prevent frequent switching on and off of the burner and therefore energy loss, an electronic restart lockout is acti­vated for a specific period each time the burner is switched off. You can adjust the burner anti-cycling time to the con­ditions of the heating installation. The burner anti-cycling time is only activated for the heat­ing mode. Hot water handling during a burner anti-cycling time does not affect the timer. You can set the maximum burner anti-cycling time in the installer level under diagnostics code D.002 within the range of 2 minutes to 60 minutes (default setting: 20 min­utes). The effective burner anti-cycling time depends on the current target flow temperature and the maximum burner anti-cycling time set.
The effective burner anti-cycling times with respect to the target flow temperature and the maximum set burner anti­cycling time can be found in the following table.
The remaining burner anti-cycling time following
a regular shutdown in heating mode can be
i
called up under diagnostics code D.067.
Resetting the remaining burner anti-cycling time
You have two options to reset the remaining burner anti­cycling time:
1st option
Menu ¬ Reset burner anti-cycling time
The current burner anti-cycling time appears in the display.
> Confirm the reset of the burner anti-cycling time by
pressing the right-hand selection button ("Select").
12.1.3 Setting the maximum flow temperature
The maximum flow temperature for the heating mode is set at the factory to 75 °C. You can set this under diagnostics code D.071 in the range 40 °C to 85 °C.
ecoTEC plus installation and maintenance instructions 0020134823_01 41
2nd option
> Press the fault clearance key (¬Operating instructions).
Adapting the unit to the heating installation
12
T
(target)
Flow
[°C]
20 2.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0 25 2.0 4.5 9.2 14.0 18.5 23.0 27.5 32.0 36.5 41.0 45.0 50.0 54.5 30 2.0 4.0 8.5 12.5 16.5 20.5 25.0 29.0 33.0 37.0 41.0 45.0 49.5 35 2.0 4.0 7.5 11.0 15.0 18.5 22.0 25.5 29.5 33.0 36.5 40.5 44.0 40 2.0 3.5 6.5 10.0 13.0 16.5 19.5 22.5 26.0 29.0 32.0 35.5 38.5 45 2.0 3.0 6.0 8.5 11.5 14.0 17.0 19.5 22.5 25.0 27.5 30.5 33.0 50 2.0 3.0 5.0 7.5 9.5 12.0 14.0 16.5 18.5 21.0 23.5 25.5 28.0 55 2.0 2.5 4.5 6.0 8.0 10.0 11.5 13.5 15.0 17.0 19.0 20.5 22.5 60 2.0 2.0 3.5 5.0 6.0 7.5 9.0 10.5 11.5 13.0 14.5 15.5 17.0 65 2.0 1.5 2.5 3.5 4.5 5.5 6.5 7.0 8.0 9.0 10.0 11.0 11.5 70 2.0 1.5 2.0 2.5 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 75 2.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
12.2 Effective burner anti-cycling times
12.1.6 Setting the maintenance interval
You can define maintenance intervals for the ecoTEC plus. Using this function, the message that the boiler must be serviced appears in the display after a defined, configurable number of burner operating hours. After the set burner operating hours have expired, the maintenance symbol the current flow temperature. The display on the eBUS con­troller ( Accessories) shows the information "Maintenance" "MAIN".
Set maximum burner anti-cycling time [min] 1 5 10 15 20 25 30 35 40 45 50 55 60
12.1.7 Setting the pump output
The ecoTEC plus boiler can be equipped with a pump group with a high-efficiency pump. This pump is fully modulating and is actuated according to the heat requirement The remaining feed head of this pump group is designed so that the full heat output is transported as far as the system
(open-end spanner) appears next to
separation.
The remaining feed heads of the pumps can be found in ¬section6.2.
> Set the operating hours until the next service using diag-
nostics code D.084.
You can see the operating hours in increments of ten from 0 to 3010 h.
If you do not enter a figure under diagnostics code D.084, but instead enter the symbol "–", then the "Maintenance display" function is not active.
On completion of the set operating hours, you
must set the maintenance interval again in diag-
i
nostics mode.
Adapting the unit to the heating installation
12
12.2 Handing the boiler over to the operator
Danger!
Risk of poisoning and burns caused by
a
escaping hot flue gas!
Hot flue gas may escape and cause poison­ing and scalding, if the boiler is operated with an incompletely fitted or open flue pipe or if the boiler is operated with the front casing open in the event of internal leaks.
> Operate the boiler
- for start-up
- for testing
- in continuous mode only when the front casing is closed and the flue pipe is fully installed and closed.
> When you have finished the installation, attach the
sticker supplied (835593) to the front of the unit in the
user's language. The sticker is delivered with the boiler. Initial start-up is carried out by an approved competent per­son. This person documents the initial start-up with the associated setting values on the commissioning checklist. This checklist remains with the unit documentation. You must brief the operator of the boiler on the handling and function of the ecoTEC plus.
> Explain the importance of regular maintenance by a
heating specialist company to the operator.
It is strongly recommended that a maintenance contract
be taken out to ensure regular maintenance. You can
obtain more information from Vaillant Service Solutions
(+44 (0) 870 6060 777).
> In the commissioning checklist, enter the operating pres-
sure of the central heating, the heat supply (in kW) and
the temperature difference between the flow and return.
If this boiler is not installed and commissioned in accord-
ance with the manufacturer's instructions, this may void
the guarantee (Note: Your legal rights remain unaffected
by this.)
> Provide the operator with all relevant instructions and
unit documentation for safe-keeping.
> Go through the operating instructions with the operator > Answer any questions the operator may have. > Make the operator aware of the need to keep the instruc-
tions near the boiler but not in or on the boiler.
> Draw special attention to the safety instructions which
the operator must follow.
> Instruct the operator about measures taken to ensure
the supply of combustion air and flue gas guiding. In par-
ticular, instruct the operator that he must not make any
changes to the combustion air supply and flue gas guid-
ing.
> Explain to the operator how to check the water level/fill-
ing pressure of the system.
> Explain to the operator which measures are required to
top up and purge the heating installation if required.
> Explain to the operator how to correctly set the tempera-
tures, the controllers and the thermostatic radiator valves (economically).
ecoTEC plus installation and maintenance instructions 0020134823_01 43
Inspection and maintenance
13
13 Inspection and maintenance
13.1 Inspection and maintenance intervals
Danger!
Negligent inspection and maintenance
a
a
Any customer service work must be carried out by a profes­sionally qualified person in accordance with the safety, installation and operating provisions for gas-fired units. Professional qualification must be confirmed by a corre­spondingly recognised organisation or public office.
In addition, BS6798: 2009 "Specification for the Installa­tion and Maintenance of Gas-fired Boilers with a Maximum Net Nominal Heat Output of 70kW" contains the following recommendations: The person who carries out a combustion measurement must be trained in the use of a flue gas measuring instru­ment and in interpreting the results. The flue gas measuring instrument used must meet the requirements of BS7927 or BS-EN50379-3 and must be cal­ibrated in accordance with the requirements of the measur­ing instrument manufacturer. Professional qualification can be proven through the suc­cessful completion of the relevant ACS standard assess­ment, which covers the use of portable electronic flue gas
results in a risk of injury as well as a risk of material damage!
Negligence in inspection and maintenance work as well as failure to comply with the specified inspection and maintenance inter­vals can impair the operating safety of the boiler and lead to injuries and material damage.
> Instruct the operator that the prescribed
inspection and maintenance intervals must be complied with as a minimum requirement.
> Carry out a regular inspection once a
year.
> Carry out regular maintenance work in
line with the findings from the inspection. The maintenance interval must not be longer than five years.
Danger!
Risk of injury and death due to improper inspection/maintenance!
Improper performance of inspections and maintenance work can result in leaks or even an explosion.
> Inspection and maintenance work on the
boiler must only be carried out by profes­sionally qualified persons.
measuring instruments in accordance with BS7967, part 1 to 4.
> The correct fuel type must be set on the flue gas meas-
uring instrument.
We recommend completing an inspection and maintenance contract with a correspondingly qualified operator or installer.
Inspection
The inspection is intended to determine the actual condi­tion of the boiler and compare it with the target condition. This is done by measuring, checking, observing. You must carry out an inspection of the ecoTEC plus at least once every year. A quick and economic inspection can be per­formed without having to remove components by request­ing data from the DIA system and carrying out simple visual checks.
Service
Maintenance is required in order to eliminate any deviations of the actual condition from the target condition. This is normally done by cleaning, adjusting and, if necessary, replacing individual components that are subject to wear. Based on experience, it is not necessary to carry out annual cleaning, e.g. on heat exchangers, under normal operating conditions. As a competent person, you determine these maintenance intervals and their scope based on the condi­tion of the unit determined during the inspection, but main­tenance must be carried out at least every 2 years.
> Carry out all inspection and maintenance work in the
order shown in table 13.2.
Danger!
Risk of poisoning and burns caused by
a
escaping hot flue gas!
Escaping hot flue gases can cause poison­ing and scalding if the boiler is operated in the following condition:
- without a completely installed flue pipe
- with an open flue pipe
- with internal leaks and open front casing. > The boiler must only be operated with
the front casing closed and a completely installed and closed flue pipe
- for initial start-up
- for test purposes
- in continuous mode.
Inspection and maintenance
13
13.1.1 General inspection and maintenance instructions
Procuring spare parts
> If you require spare parts for servicing or repair work,
use only Vaillant genuine spare parts. The original components of the unit were also certified as part of the CE declaration of conformity. If you do not use certified Vaillant genuine spare parts, this voids the CE con­formity of the unit. We therefore strongly recommend that you fit Vaillant genuine spare parts. You can find information about available Vaillant genuine spare parts from the contact address provided on the reverse of this document.
During an inspection or maintenance procedure, as well as after replacing components in the combustion circuit, the following checks must be performed:
– The boiler has been installed in accordance with the cor-
responding installation instructions.
– The condition of the flue gas system and the flue gas
seals corresponds to the enclosed instructions for the
flue gas system.
– Visual inspection of the combustion circuit of the boiler
and the associated seals.
– The maximum gas connection pressure (gas flow pres-
sure) corresponds to the information in ¬section9.6.3.
– Correctness of the current, water and gas connections. – Correctness of the water pressure. – Condition of the overall system, in particular the condi-
tion of the radiator valves, indications of leaks in the
heating installation or dripping water taps.
> Eliminate any faults before continuing.
13.1.2 Safety information
Danger!
Risk of injury and death from electric
e
shock!
Even when the boiler is switched off, mains voltage is still present at the power connec­tion terminals of the boiler.
> Avoid any contact with the power con-
nection terminals.
> Protect the switch cabinet from water,
especially from being splashed.
> Before any work on the boiler, switch off
the power supply and secure the boiler against being switched back on acciden­tally.
For certain inspection and maintenance work,
the electrics of the boiler must remain activated;
i
Before starting any inspection and maintenance work, per­form the following steps:
> Switch off the main switch. > Disconnect the boiler from the power supply by
> Also check the electrical isolation of the boiler with a
measuring instrument. > Close the gas isolator cock. > Close the stop valves in the heating flow and return. > Remove the front casing of the boiler. > When removing components which carry water, ensure
that no water comes into contact with electrical compo-
nents.
After completing any inspection and maintenance work, perform the following steps:
> Only use new seals and O-rings when replacing parts. > Open the stop valves in the heating flow and return. > Open the cold water stop valve if necessary. > Reconnect the boiler to the power mains. > Switch on the boiler using the on/off switch. > Fill the heating circuit of the boiler with water up to a
pressure of 0.1 and 0.2MPa (1.0 and 2.0 bar), if neces-
sary. > If you have topped up the heating water, purge the heat-
ing installation (¬section 9.3.2). > Open the gas isolator cock. > Check the boiler for gas and water leaks. > If necessary, refill and purge the heating installation
again. > Reattach the front casing of the boiler (¬section 4.6). > Carry out a functional check of the boiler
(¬section11.5.1 to 11.5.3). > Always check the earth connection, the polarity and the
resistance with a multimeter following completion of the
maintenance or repair work and after replacing electrical
components. > Complete the commissioning checklist that is attached to
these instructions.
this is specified in the description of the respec­tive maintenance task.
– removing the mains plug or – de-energising the boiler with an isolating device with
a contact opening of at least 3mm (e.g. fuses or mains switches).
ecoTEC plus installation and maintenance instructions 0020134823_01 45
Inspection and maintenance
13
13.1.3 Checking the CO2 content
The CO2 content must be checked/set in the following cases:
– When replacing the gas valve – If you suspect incorrect combustion. – At initial start-up – During any maintenance work – When replacing the fan or burner – If there are changes to the gas installation
13.1 Checking the CO2 content
The boiler is equipped with a flue gas analysis
point (1). A suitable flue gas measuring instru-
i
> Remove the front casing (¬section4.6). > Start check programme P.1 (¬section11.4). > Wait at least 5 minutes until the boiler reaches its
operating temperature. > If required, remove the upper casing. > Measure the CO
(1). Compare the measured value with the corresponding
value in ¬table13.1.
Settings Unit
ment can be used to check the combustion per­formance of the measuring instrument at this analysis point.
content at the flue gas analysis point
2
Natural gas H Tolerance
> If all these points meet the requirements, continue in
accordance with ¬section 13.2.
> If one of the flue gas values is above the permissible
value in ¬table13.1, continue in accordance with the following ¬section 13.1.4.
13.1.4 Setting the CO2 content (or setting the air ratio)
1
Danger!
Increased risk of poisoning from incor-
a
rect setting.
If one of the flue gas values is above the permissible values in ¬table 13.1:
> Check that the entire flue gas system is
in good condition.
> Check that the seals of the combustion
system are in good condition.
> Check the gas connection pressure (gas
flow pressure).
> Check the gas volume flow.
806/5-5
1
1
after 5 minutes full load
CO
2
operation with front casing closed
CO2 after 5 minutes full load operation with front casing removed
Set for Wobbe Index W
13.1 Gas default settings
Vol.-% 9.0 +/- 0.5
Vol.-% 8.8 +/- 0.5
3
kWh/m
0
1006/5-5
1206/5-5
15
13.2 Carry out the CO2 measurement, air index setting
If the flue gas value has to be set, proceed as follows. The adjusting screw (1) for the air index setting is located under a sealing sticker.
> Break through the sealing sticker. > Set the CO
turning the screw (1).
content (value with front casing removed) by
2
Turn to the left: Increases the CO2 content
Turn to the right: Decreases the CO
content
2
i
> Only perform the adjustment in 1/8 turns and wait
approximately 1 minute after each adjustment until the value stabilises. For this, always first turn the adjusting screw in and then turn it out again for fine adjustment.
– The adjusting screw must only slightly poke out of the
casing:
On the VU GB 1006/5-5 and VU GB 1206/5-5,
content only changes after approx. 1
the CO
i
2
turn of the adjusting screw (overcoming the adjustment hysteresis).
Inspection and maintenance
13
> Press the "Cancel" selection button once the settings
have been made.
> Reattach the front casing (¬section4.6).
ecoTEC plus installation and maintenance instructions 0020134823_01 47
Inspection and maintenance
13
13.2 Inspection and maintenance work
The following table shows the inspection and maintenance work that must be carried out at specific intervals.
Inspection
No. Work
Isolate the boiler from the power mains. Check that the plug connections and other connections are
1
seated correctly and correct these if necessary.
2 Close the gas isolator cock and the service valves. X
Check the flue pipe for leak-tightness and correct seating. Make sure that it is not blocked or dam-
3
aged and has been installed in accordance with the relevant Installation Manual. Check the general condition of the boiler. Remove general dirt from the boiler and from the vacuum
4
chamber. Visually inspect the general condition of the entire heating cell and specifically check for signs of cor-
5
rosion, soot or other damage. If you notice any damage, carry out maintenance work.
6 Remove the gas-air mixture unit (burner door with fan and gas valve) (¬section13.5.1). X
Check all seals in the combustion area. If you see any damage, replace the seals. Replace the burner
7
door seal every time you open the burner door.
8 Clean the heat exchanger by flushing it with a water hose from above (¬section13.5.2). X 9 Check the burner for dirt and clean if necessary. X 10 Check the condensate siphon in the boiler, clean and top up if necessary. X X 11 Check, and if necessary correct, the charge pressure of the expansion vessel. X X 12 Reinstall all of the previously removed components, up to and including the gas-air mixture unit. X 13 Reinstall the gas-air mixture unit. Caution: Replace the seals. X
14 Replace the ignition and monitoring electrode and the associated seals. X
Motorised flue non-return flaps for cascade operation: Check that the flue non-return flap functions
15
faultlessly. If required, clean the casing from inside and outside, as well as the shut-off disc and the shaft.
16 Open the gas isolator cock, reconnect the boiler to the power mains and switch the boiler on. X X
Open the service valves, fill the boiler/heating installation to 0.1 - 0.2 MPa (1.0 - 2.0 bar) (depending on
17
the static height of the heating installation), start purging programme P.0. Check the gas connection pressure (gas flow pressure) (¬section9.6.3) at maximum output.
18
If the gas connection pressure (gas flow pressure) is not within the correct range, carry out mainte­nance.
19 Check the CO 20 Perform a test operation of the boiler and heating installation and purge the system if necessary. X X 21 Visually inspect the ignition and burner performance. X X 22 Check the CO
23 Check the boiler for gas, flue gas, hot water and condensate leaks and repair if necessary. X X
24 Close the front casing. XX 25 Record the inspection/maintenance work carried out. X X
Check the quality of the heating water (hardness level) and log the values in a system book.
26
If required, use water treatment to correct the water hardness.
13.2 Inspection and maintenance steps
content of the boiler and, if necessary, adjust it (¬section13.1.3). Keep a record of this. X X
2
content (air ratio) of the product again. X X
2
(must be
performed
every year)
XX
XX
XX
XX
XX
XX
Service
(regularly, at
least every
2 years)
X
X
X
Inspection and maintenance
13
13.2.1 Filling the boiler and the heating installation
A description of how to fill the boiler and heating installa­tion is given in section9.3.1.
13.2.2 Draining the boiler
> Switch the boiler off with the on/off button. > Close the service valves of the boiler. > Start the check programme P.6. > Open the drain valves on the service valves.
13.2.3 Draining the entire heating installation
> Attach a hose to the draining device on the system. > Bring the open end of the hose to an appropriate drain
point.
> Start check programme P.6 (¬section11.4). > Make sure that the service valves of the boiler are open. > Open the drain cock. > Open the purging valves on the radiators.
Start from the highest radiator and then work from the top to the bottom.
> Once the water has drained off, close the purging valves
of the radiators and the drain cock.
Display
T.01 Check internal
T.0 3 Check fan You can switch the fan on and off.
T.04 Check cylinder
T.06 Check external
T.08 Check burner The boiler starts, carries out the nec-
13.3 Self-tests in the function menu
Test pro­grammes
pump
charge pump
pump
Action
You can switch the internal pump on and off.
The fan runs at maximum rotational speed. You can switch the cylinder charging pump on and off.
You can switch the external pump on and off.
essary self-test and switches to mini­mum load. The display shows the status and the temperature in turn (alternatively the pressure). If a fault occurs, the dis­play shows the corresponding fault code.
13.3.1 Testing components
If you have opened the function menu, you can select vari­ous self-tests. You can use these self-tests to check the function of the following components of the heating instal­lation or to purge the heating circuit.
You can select the following self-tests:
13.3 Using the function menu
You can use the function menu to service the ecoTEC plus as it allows you to control individual components of the heating installation. In addition, the function menu offers a programme for purging the heating circuit and the hot water circuit.
Menu ¬ Installer level ¬ Test programmes ¬ Function menu
> Use the minus button
or the plus button
to go to the components of the heating
installation.
> Confirm your selection using the right-hand selection
button
("Select").
Cancelling the function test
> Press the left-hand selection button
(" Cancel") to stop the function test.
You can test the operation of the heating installation com­ponents listed below using the self-tests in the function menu.
Test programmes Action
Check pumps of the pump group
Check fan You can switch the fan on and off. The fan
Check charging pump
Check external pump
Check burner The unit starts, carries out the necessary self-
End function menu
The plain text display shows the current mode. If you do not press any buttons for more than 15 minutes, test mode is ended automatically.
13.4 Self-tests in the function menu
You can switch the pump on and off.
runs at maximum rotational speed. You can switch the cylinder charging pump on
and off. You can switch the external pump on and off.
test and switches to minimum load. The display shows the status and the temper­ature in turn (alternatively the pressure). If a fault occurs, the display shows the corre­sponding fault code.
You can exit the function menu here.
ecoTEC plus installation and maintenance instructions 0020134823_01 49
Inspection and maintenance
13
13.3.2 Carrying out electronics self-tests
Menu ¬ Installer level ¬ Test programmes ¬ Electronics self-test
With the electronics self-test, you can test the relays on the PCB.
13.4 Removing/fitting the upper casing
1
2
13.3 Removing/fitting the upper casing
> Switch the boiler off with the on/off button. > Isolate the boiler from the power mains. > Close the gas isolator cock on the boiler. > Close the service valves on the boiler. > Remove the front casing from the boiler (¬section4.6). > Undo the upper screws in the side panels. > Move the side sections slightly outwards. > Tilt the front unit cover upwards and pull it forwards.
Only on VUGB806/5-5:
2
1
13.4 Remove the air intake pipe (only for VUGB806/5-5)
> Undo the clip (1) on the air intake pipe(2). > Remove the air intake pipe from the intake port.
To remove the upper casing:
> Unscrew the screws (2). > Pull out the upper casing (1) towards the front.
To fit the upper casing:
> From above, place the upper casing (2) on the boiler. > Use the screws (1) to secure the upper casing.
13.5 Carrying out maintenance work
13.5.1 Removing the gas-air mixture unit
Danger!
Risk of being burned or scalded by hot
a
components!
There is a risk of being scalded or burned on the gas-air mixture unit and on all water­carrying components.
> Only carry out work on these compo-
nents if they have cooled down.
The gas-air mixture unit consists of four main components:
– Speed-regulated fan – Air intake pipe – Gas valve – Burner
For all units:
3
4
13.5 Separate the gas pipework (VUGB806/5-5)
Inspection and maintenance
13
13
13.6 Separate the gas pipework (VUGB1006/5-5 and
VUGB1206/5-5)
> Undo the four screws on the flange connection (3) to the
gas valve.
> Move the gas pipe (4) to the side.
Danger!
Risk of poisoning and fire caused by
a
escaping gas!
The gas pipe can be damaged.
> Ensure that you do not damage the seals
on the gas pipe when removing and installing the gas-air mixture unit.
11
10
3
9
4
8
806/5-5
13
12
10
8
11
12
5
6
7
1006/5-5 1206/5-5
13.7 Removing the gas-air mixture unit
> Remove the plug for the ionisation line from the ionisa-
tion electrode (11), and remove the plug for the ground connection from the earthing lug.
> Remove the ignition line plug and the ground connection
of the ignition electrode (9) from the ignition trans­former.
The cable is firmly connected to the ignition
electrode.
i
> Remove the plugs (12 and 13) from the fan motor by
pushing in the latching lug.
> Remove the plug from the gas valve (10).
5
6
7
9
ecoTEC plus installation and maintenance instructions 0020134823_01 51
Inspection and maintenance
13
> Remove the plug from the upper safety cut-out (8). > Undo the screws (6) on the burner door. > Remove the complete gas-air mixture unit (5) from the
heat exchanger (7).
> Check the burner and the heat exchanger for damage
and dirt.
13.5.2 Cleaning the heat exchanger
Caution.
Risk of material damage from spraying
b
> Remove the gas-air mixture unit (¬section13.5.1).
1
water.
If you fail to protect the electronics box adequately, water can penetrate the box during cleaning and may damage the elec­tronics.
> Protect the folded down electronics box
against sprayed water.
If you have removed the condensate siphon, reinstall it below the boiler after cleaning (¬section13.5.5) so that the heat exchanger is ready for operation again.
13.5.3 Checking the burner
1
2
3
4
13.8 Cleaning the heat exchanger (example: VUGB806/5-5)
Caution.
Risk of damage to the heat exchanger.
b
Before flushing, we recommend removing the condensate siphon so that the neutralising unit is not damaged.
> Rinse away any dirt from the burner chamber wall and
through the pipes (1) of the heat exchanger using a
strong jet of water or use a plastic brush. The water flows out of the heat exchanger through the drain.
> You should neither loosen nor tighten
the screws (2).
13.9 Check the burner (Example: VUGB806/5-5)
> Check the surface of the burner for damage. If you
notice any damage, replace the burner and seal (¬section15.4).
> Check the insulating mat (2) on the burner door. If you
notice any signs of damage, replace the insulating mat (¬section15.5).
> Check the burner door seal (4) on the burner door. If you
notice any signs of damage, replace the seal. See "Replacing the burner" (¬section15.4).
13.5.4 Replace the ignition and ionisation electrode
We recommend that you replace the ignition and ionisation electrode every 2 years.
1
13.10 Replacing electrodes
> Remove the electrodes (1) from the burner plate from
above.
> Insert the new electrodes with new seals. Tightening
torque: 2.8 Nm
Caution.
Risk of material damage caused by dam-
b
age to the ignition and ionisation elec­trodes.
The electrodes could become damaged dur­ing installation.
> Fit the new electrodes only after first
installing the gas-air mixture unit.
Inspection and maintenance
1
2
13.11 Cleaning the condensate siphon
> Remove the siphon's lower section (2) by unscrewing it
from the condensate siphon (1).
> Flush out the lower section of the siphon with water. > Fill the lower section of the siphon with water up to
about 10mm below the upper edge. > Re-fit the lower part of the condensate siphon. > Check the seal for leak-tightness.
13.5.6 Installing the gas-air mixture unit
13
Danger!
13.5.5 Cleaning the condensate siphon
a
Danger!
Risk of death caused by improper main-
a
ecoTEC plus installation and maintenance instructions 0020134823_01 53
tenance!
If you operate the boiler with an empty condensate siphon, flue gas may escape into the room air.
> Top up the condensate siphon after each
cleaning session.
> Replace the seal in the burner door. > Ensure that the bracket for the insulating mat is fitted
properly again after replacement. > Replace all seals at the sealing point opened during the
maintenance work.
Risk of personal injury and material dam­age due to hot flue gases.
If you do not replace the seal, hot flue gases may escape and cause injuries and material damage.
> Replace the seal each time you open the
burner door.
> If the insulating mat on the burner door
shows signs of damage, then replace it.
Inspection and maintenance
13
13
11
10
9
12
4
5
6
> Connect the plug (10) to the gas valve. > Connect the gas pipe (4) with a new seal to the gas
valve.
Torque (for the VU GB 806/5-5 only): 2Nm
Torque (for the VU GB 1006/5-5 and VU GB 1206/5-5
only): 2.8Nm > Open the gas isolator cock on the boiler.
Danger!
Risk of poisoning and fire caused by
a
escaping gas!
Gas can escape through leaks.
7
> Check the gas tightness at the gas con-
nection using leak detection spray.
8
806/5-5
13
12
10
For the VUGB806/5-5 only: Installing the air intake pipe
2
8
11
1006/5-5 1206/5-5
13.12 Installing the gas-air mixture unit
> Connect the gas-air mixture unit (5) to the heat
exchanger (7).
> Tighten the screws (6) in a cross-wise pattern until the
burner door fits closely and uniformly onto the mating surfaces. Tightening torque: 10 Nm
> Connect the plugs of the ignition lines and the ground
connection to the ignition electrode (9) on the ignition transformer.
> Connect the plug of the ionisation line to the ionisation
electrode (11) and connect the plug of the ground con­nection to the earthing lug.
> Connect the plug of the safety cut-out to the upper
safety cut-out (8).
> Connect the plugs (12 and 13) to the fan motor.
4
13.13 Installing the air intake pipe (Only for VUGB806/5-5)
> Check that the sealing ring in the air intake pipe (2) is
5
6
7
positioned correctly in the seal seat. > Place the air intake pipe back onto the intake nozzle. > Secure the air intake pipe with the clip (1) on the intake
nozzle.
9
For all units:
> Close the electronics box. > Re-establish the connection to the power mains. > Open the service valves in the heating flow and in the
heating return. > If required, refill the boiler with water to a pressure of
between the minimum and the maximum values.
13.5.7 Checking the gas connection pressure (gasflow pressure)
> Check the gas connection pressure (¬section9.6.3).
13.5.8 Checking the CO2 content
> Check the CO2 content (section 13.1.3).
1
Troubleshooting
14
13.5.9 Checking the boiler
> Commission the boiler in accordance with the relevant
operating instructions.
13.14 Leak-tightness test
> Purge the heating installation using check programme
P.0 (¬section11.4).
> Check the boiler for gas and water tightness. > If necessary, refill and purge the heating installation
again.
> Check the ignition and that the flame on the burner is
burning evenly.
> Attach the front casing of the boiler (¬section4.6). > Check the flue pipe for correct seating. > Check the flue pipe for leak-tightness. > Check the function of the heating (¬section11.5.2). > Record the inspection/maintenance work carried out in
the system book that you leave with the unit's documen­tation.
14 Troubleshooting
14.1 Contacting Vaillant customer service
> If you contact your Vaillant Customer Service or Vaillant
Service partner, then please provide, where possible,
– the fault code that is displayed (F.xx), – the unit status (Sxx) that is displayed in the "Live
monitor" (¬section14.2.1).
14.2 Performing diagnostics
You can use the function menu to control and test individ­ual components of the boiler in the fault diagnostics.
Menu ¬ Installer level ¬ Test programmes ¬ Function menu
> Use the function menu for fault diagnostics
(¬section13.3).
14.2.1 Calling up Live monitor (status codes)
Menu ¬ Live monitor
You can call up the boiler status codes in the display which provide information on the current operating condition of the boiler.
S.04
Heating mode
Burner on
Back
ecoTEC plus installation and maintenance instructions 0020134823_01 55
14.1 Display views of the status codes
Troubleshooting
14
14.2.2 Overview of status codes
Display Meaning Heating mode
S00 Heating, no heat demand S 02 Heating mode pump flow S03 Heating mode, ignition S04 Heating mode, burner on S05 Heating mode, pump/fan overrun S06 Heating mode, fan overrun S 07 Heating mode, pump overrun S08 Heating, remaining locking time in xx minutes S09 Heating mode measuring programme
Special cases
S30 Room thermostat is blocking heating mode S 31 Summer mode active or no heat requirement from eBUS
S32 Operation block function due to different fan speed S34 Frost protection mode active S36 Target value of the eBUS controller is < 20 °C and is
S37 Fan waiting period: Fan failure in operation S 39 Contact thermostat/"burner off contact" has responded S40 Comfort protection mode is active: Unit running with
S41 S42 Flue non-return flap return signal blocks burner opera-
S53 Unit is within the waiting period of the modulation
S 54 Unit is within the waiting period of the operation block-
S 96 Return sensor test running, heating demands are
S97 Water pressure sensor test running, heating demands
S98 Supply/return sensor test running, heating demands are
14.1 Overview of status codes
controller
blocking heating mode
limited heating comfort Water pressure > 0.2 MPa (2 bar)
tion (only in connection with VR40 accessory) or con­densate pump faulty, heat requirement is blocked
block/operation block function due to low water pres­sure (flow-return spread too large)
ing function as a result of low water pressure (tempera­ture gradient)
blocked
are blocked
blocked
14.2.3 Service messages
If the "open-end spanner" maintenance symbol appears in the display, there is a service message. The maintenance symbol appears if you have set a maintenance interval, for example, (¬section12.1.6) and it has elapsed. The boiler is not in fault mode but continues to operate.
To obtain more information about the service message:
> Call up the "Live monitor" (¬section14.2.1).
If status code S.40 is displayed as well as the maintenance symbol, the boiler is in Comfort protection mode. This means that the boiler continues to operate with restricted comfort after it has detected a fault (e.g. because of a severe storm).
> In this case, read out the fault memory in order to deter-
mine whether a boiler component is defective (¬section14.2.6).
If no fault message is present, the boiler will automatically switch back to normal operating mode after a certain time. Comfort protection mode may then have been triggered by a severe storm, for example.
Troubleshooting
14.2.4 Calling up diagnostics levels
Menu ¬ Installer level ¬ Diagnostics menu
You can use the diagnostics menu to inspect parameters and modify certain parameters. An overview of all diagnos­tics codes can be found in ¬table12.1.
14.2.5 Overview of diagnostics codes at installer level
Display Meaning Display value/adjustable value
D.000 Heating partial load Adjustable heating partial load in kW
D.001 Pump overrun for heating mode 2 - 60 minutes (factory setting: 5) D.002 Max. burner anti-cycling time heating at 20 °C flow
temperature
D.005 Flow temperature target value (or return target value) In °C, max. of the value set in D.071, limited by an eBUS controller if
D.006 Hot water temperature target value 35 to 65 °C D.007 Warm start temperature target value 40 to 65 °C D.010 Heating pump status of the pump group 1 = on, 0 = off D.011 Status of external heating pump 1 to 100 = on, 0 = off D.014 Target value for pump speed Heating circuit pump target value in %
D.016 Room thermostat 24 V DC at terminal 3'-4‘ (only NL) 0 = Room thermostat open (no heating mode)
D.017 Heating flow/return regulation changeover 0 = flow, 1 = return (default setting: 0) D.018 Pump operating mode setting 1 = Comfort (continuously operating pump)
D.022 Hot water demand via C1/C2, internal hot water control
system
D.023 Summer/winter operating mode (heating on/off) 1 = Heating on, 0 = Heating off (summer mode) D.025 Hot water generation enabled by eBUS controller 1 = Yes, 0 = No D.027 Switching of relay 1 on the
"2 in 7" multi-functional module VR 40
D.028 Switch of relay 2 on the "2 from 7" multi-functional
module VR 40
14.2 Diagnostics codes at installer level
(Factory setting: auto: Unit automatically adjusts max. partial load to current system demand)
2 - 60 minutes (factory setting: 20)
connected
0 = auto (default setting) 1 = 53 2 = 60 3 = 70 4 = 85 5 = 100
1 = Room thermostat closed (heating mode)
3 = Eco (intermittently operating pump, default setting) 1 = on, 0 = off
1 = Circulation pump (default setting) 2 = Ext. pump 3 = Charging pump 4 = Extractor hood 5 = Ext. solenoid valve 6 = Ext. error message 7 = Not active 8 = Remote control eBUS (not active) 9 = Anti-legionella pump (not active)
1 = Circulation pump 2 = Ext. pump (factory setting) 3 = Charging pump 4 = Extractor hood 5 = Ext. solenoid valve 6 = Ext. error message 7 = Not active 8 = Remote control eBUS (not active) 9 = Anti-legionella pump (not active)
14
ecoTEC plus installation and maintenance instructions 0020134823_01 57
Troubleshooting
14
Display Meaning Display value/adjustable value
D.033 Fan speed target value In rpm D.034 Fan speed actual value In rpm D.039 Solar feed temperature Actual value in °C D.040 Flow temperature Actual value in °C D.041 Return temperature Actual value in °C D.044 digitalised ionisation voltage Display field 0 to 102,
D.046 Pump type 0 = Relay with disable facility (default setting)
D.047 Outside temperature
(with weather-controlled Vaillant controller)
D.050 Offset for minimum speed Adjustment range in rpm: 0 to 3000 (factory set nominal value) D.051 Offset for maximum speed Adjustment range in rpm: - 990 to 0 (factory set nominal value)
D.060 Number of temperature limiter shutdowns Number D.061 Number of ignition device cutoffs Number of unsuccessful ignitions in the last attempt D.064 Average ignition time In seconds D.065 Maximum ignition time In seconds D.067 Remaining burner anti-cycling time In minutes D.068 Unsuccessful ignitions at 1st attempt Number D.069 Unsuccessful ignitions at 2nd attempt Number D.071 Target value maximum heating flow temperature Adjustment range in °C: 40 to 85 (factory setting: 75) D.072 Internal pump overrun after Adjustment range in min: 0 to 10 (default setting: 2) D.076 UNit variant (display)(device specific number) 82 = VU GB 806/5-5
D.077 Partial load for cylinder charging in kW D.080 Operating hours, heating In hours (h) D.081 Operating hours, hot water generation In hours (h) D.082 Number of burner start-ups in heating mode Number D.083 Number of burner start-ups in hot water mode Number D.084 Maintenance indicator: Number of hours until the next
maintenance
D.090 Status of digital controller 1 = Recognised, 0 = Not recognised D.091 Status DCF with external sensor connected 0 = No reception, 1 = Reception, 2 = Synchronised, 3 = Valid D.093 DSN unit variant setting Adjustment range: 0 to 99 D.094 Delete fault history 1 = Delete fault list D.095 Software version eBUS components 1. PCB
D.096 Factory setting 1 = Reset all adjustable parameters to factory setting
13.2 Diagnostics codes at Installer level
(continued)
> 80 no flame < 40 good flame
1 = PWM with disable facility Actual value in °C
81 = VU GB 1006/5-5 80 = VU GB 1206/5-5
Adjustment range: 0 to 3010 h and "-" for deactivated (Factory setting: "-")
2. Display
4. VR34
14.2.6 Reading fault codes
If a fault develops in the boiler, the display shows a fault code F.xx. A plain text display explains the displayed fault code. Example F.10: "Short circuit in flow sensor".
Fault codes have priority over all other displays. If a fault occurs, the display no longer shows the current heating flow temperature of the heating installation.
If multiple faults occur at the same time, the display shows the corresponding fault codes for two seconds each in sequence.
> Remedy the fault. > To restart the boiler, press the fault clearance key
(¬Operating instructions).
> If you are unable to remedy the fault and the fault reoc-
curs despite several fault clearance attempts, contact Vaillant Customer Service.
Troubleshooting
14
14.2.7 Querying the fault memory
Menu ¬ Installer level ¬ Fault list
The boiler has a fault memory. You can use this to query the last ten faults that occurred in chronological order. If a DCF sensor is connected, the date on which the fault occurred will also be displayed.
The display shows:
– the number of faults that have occurred – the fault currently selected with fault number F.xx. – a plain text display explaining the fault
> Use the minus button
to view the last ten faults.
or the plus button
14.2.8 Resetting the fault memory
You can delete the entire fault list.
> Press the right-hand selection button
("Delete").
> Confirm the deletion of the fault memory by pressing the
right-hand selection button again
("OK").
ecoTEC plus installation and maintenance instructions 0020134823_01 59
Troubleshooting
14
14.2.9 Overview of fault codes
Code Meaning Cause
F.00 Flow temperature sensor interruption NTC plug not plugged in or has come loose, multiple plug on the PCB
F.01 Return temperature sensor interruption NTC plug not plugged in or has come loose, multiple plug on the PCB
F.10 Short circuit, flow sensor Sensor plug has a short to the casing, short-circuit in cable harness,
F.11 Short circuit, return sensor Sensor plug has a short to the casing, short-circuit in cable harness,
F.20 Temperature safety switch-off Earth connection of cable harness to boiler not correct, when the
F.22 Low water pressure safety switch-off No or too little water in the boiler, water pressure sensor defective,
F.23 Safety switch-off: Temperature difference too great Pump blocked, insufficient pump output, air in boiler, flow and return
F.24 Safety switch-off: Temperature rise too fast Pump blocked, poor pump performance, air in boiler, system pressure
F.25 Safety switch-off: Flue gas temperature too high Break in plug connection for optional flue gas safety temperature
F.27 Safety switch-off: Flame simulation Moisture on the electronics, electronics (flame monitor) defective,
F.28 Failure during start-up: Ignition unsuccessful Gas meter defective or gas pressure monitor has been triggered, air
F.29 Failure during operation: Re-ignition unsuccessful Gas supply temporarily stopped, flue gas recirculation, condensate
F.32 Fan fault Plug on fan not correctly plugged in, multiple plug on PCB not cor-
F.34 Safety switch-off: pressure monitoring Flue gas pressure cartridge: cable break, blocked flue gas route
F.35 Flue pipe fault Flue pipe blocked F.49 eBUS fault Short circuit on eBUS, eBUS overload or two power supplies with dif-
F.61 Fault: Gas valve regulation - Short circuit/short to earth in cable harness for the gas valve
F.62 Fault: Gas valve switch-off delay - Delayed shutdown of gas valve
F.63 EEPROM fault Electronics defective F.64 Electronics/sensor fault Flow or return NTC short circuited, electronics defective F.65 Electronic temperature fault Electronics overheating due to external influences, electronics
F.67 Electronics/flame fault Implausible flame signal, electronics defective F.70 Invalid device code Spare parts case: Display and PCB replaced at the same time and
14.3 Fault codes
not plugged in correctly, interruption in cable harness, NTC defective
not plugged in correctly, interruption in cable harness, NTC defective
sensor faulty
sensor faulty
burner cover safety cut-out triggers: burner door seal or burner iso­lation defective. When the flow safety cut-out triggers: pump fault
cable to pump or water pressure sensor loose/not connected/ defective
NTC interchanged
too low, non-return valve blocked/incorrectly installed
limiter (safety cut-out), break in cable harness
gas solenoid valve leaking
in gas, gas connection pressure (gas flow pressure) too low, Thermal isolator device (TAE) has been triggered, condensate duct blocked, incorrect gas restrictor, incorrect ET gas valve, failure at gas valve, multiple plug on PCB incorrectly plugged in, break in cable har­ness, ignition system (ignition transformer, ignition cable, ignition plug, ignition electrode) defective, ionisation current interrupted (cable, electrode), incorrect earthing of boiler, electronics defective
duct blocked, faulty earthing of boiler, ignition transformer has spark failure
rectly plugged in, break in cable harness, fan blocked, Hall sensor defective, electronics defective
Water pressure switch: hydraulic leak, air in heating circuit
ferent polarities on the eBUS
- Gas valve defective (coils shorted to earth)
- Electronics defective
- Delayed extinguishing of flame signal
- Gas valve leaking
- Electronics defective
defective
unit variant not reset
Troubleshooting
Code Meaning Cause
F.73 Water pressure sensor signal in the wrong range
(too low)
F.74 Water pressure sensor signal outside correct range
(too high)
F.75 Fault, no pressure change detection when starting
pump
F.76 Overheating protection on primary heat exchanger has
responded F.77 Flue non-return flap/condensate pump fault No response from flue non-return flap or condensate pump defective con No communication with the PCB Communication fault between display and PCB in the electronics box
13.3 Fault codes (continued)
14.3 Using the function menu
To remedy faults in the boiler, you can use the function menu to control and check individual components of the heating installation (¬section13.3).
Interruption/short circuit of water pressure sensor, interruption/short circuit to GND in supply line to water pressure sensor or water pres­sure sensor defective
Line to water pressure sensor has short-circuited at 5 V/24 V or internal fault in water pressure sensor
Water pressure sensor and/or pump defective, air in heating installa­tion, too little water in boiler; check adjustable bypass, connect exter­nal diaphragm expansion vessel to the return
Cable or cable connections for safety fuse in primary heat exchanger or primary heat exchanger defective
14
14.4 Running check programmes
By activating various check programmes, you can trigger special functions on the boiler (¬table.11.1). The display shows which check programme you have chosen.
> Read how to start the check programmes in section 11.4.
14.5 Resetting parameters to factory settings
As well as the option to manually reset individual parame­ters to the factory settings specified in ¬table12.1, you can also reset all parameters at once.
> Set the value of the diagnostics code parameter D.096
to "1" (¬section12.1).
You have now reset all parameters to factory settings.
ecoTEC plus installation and maintenance instructions 0020134823_01 61
Replacing components
15
15 Replacing components
The work described in this section must only be carried out by a competent person.
> Only use genuine Vaillant spare parts for repairs . You can find information about available Vaillant genuine spare parts from the contact address provided on the reverse of this document.
15.1 Preparing for and completing replacement
work
Danger!
Risk of death from electric shock!
e
Mains connection terminals L and N remain live even if the continuous voltage on/off switch is turned off.
> Before carrying out maintenance work
on the boiler, switch the boiler off using the on/off button.
> Disconnect the boiler from the power
mains by de-energising the boiler using a partition with a contact opening of at least 3 mm (e.g.fuses or power switches).
15.2 Removing/fitting the side section (ifrequired)
When carrying out any repair to the boiler, make
sure that you observe the following instructions
i
> Switch off the boiler. > Isolate the boiler from the power mains. > Remove the front casing (¬section4.6). > Close the gas isolator cock. > Close the service valves in the heating flow and in the
heating return. > Close the service valve in the cold water pipe. > Drain the boiler if you want to replace components that
carry water (¬section13.2.2). > Make sure that water does not drip on live components
(e.g. the electronics box). > Use only new seals and O-rings.
Completing replacement work
> Check the boiler for gas tightness. > Reattach the front casing (¬section4.6). > Carry out a function test
(¬section 11.5.1 to 11.5.3).
for your own safety and to avoid material dam­age to the boiler.
15.1 Removing/installing the side section
Caution
Risk of material damage caused by
b
To remove one side section:
> Tilt the electronics box forward. > Remove the upper casing (¬section 13.4). > Hold on to the side section so that it cannot fall, and
unscrew the lower front and upper central screws from the side section.
> Tilt the side section slightly to the side and pull it out
towards the front.
To fit the side section:
> Push the side section into the bracket. When doing so,
ensure that all straps on the side panel engage with the rear back wall in order to prevent leaks.
mechanical deformation.
Removing both side sections may cause mechanical distortion in the product, which may cause damage to the piping, for exam­ple, and potentially result in leaks.
> Always only remove one side section –
never both side sections at the same time.
Replacing components
15
> Slide the side section to the rear. > Secure the side section using two screws in the front
lower area and in the upper central area. > Fit the upper casing (¬section 13.4). > Fold up the electronics box.
15.3 Replacing the gas valve
2
806/5-5
> Fit the new gas valve in the same position on the fan as
before. Use new seals for this.
> Tighten the screws (1) in a cross-wise pattern.
Torque (only for VU GB 806/5-5 and VU GB 1006/5-5): 6Nm Torque (only for VU GB 1206/5-5): 10Nm
> Connect the gas pipe (1) with a new seal to the gas valve.
Torque (only for VU GB 806/5-5): 2Nm Torque (only for VU GB 1006/5-5 and VU GB 1206/5-5): 2.8Nm
> After installing the new gas valve, carry out a leak-tight-
ness test (check product function and tightness) (¬sec-
tion 13.5.9) and a gas ratio setting (¬section 13.1.4).
15.4 Replacing the burner
> Remove the gas-air mixture unit (¬section13.5.1).
1
1
2
3
2
1006/5-5 1206/5-5
15.2 Replacing the gas valve
> Remove the gas pipe (1) from the gas valve. > Unscrew the screws (2) from the fan and remove the gas
valve from the fan. > Replace the defective component.
4
15.3 Replace the burner (example: VUGB806/5-5)
1
> Remove the ignition and monitoring electrode. > Remove the seal (4) from the burner door. > Turn the insulation protection plate (1) to remove it. > Remove the insulating mat (2). > Loosen the nuts (3) on the burner.
VU GB 806/5-5: three nuts VU GB 1006/5-5 and VU GB 1206/5-5: four nuts
> On the VU GB 1006/5-5 and VU GB 1206/5-5 only:
Use a suitable socket (with extension) to ensure that the burner mat does not become damaged. You must not use burners that have a damaged mat.
> Remove the burner. When doing so, hold the fan and the
burner door securely.
> Fit the new burner with a new seal.
ecoTEC plus installation and maintenance instructions 0020134823_01 63
Replacing components
15
> On the VU GB 806/5-5 only: Use the three nuts to
secure the burner and the bracket for the insulation pro-
tection plate. Tightening torque: 4Nm > On the VU GB 1006/5-5 and VU GB 1206/5-5 only:
First, use two nuts to secure the burner. Tightening
torque: 4Nm > On the VU GB 1006/5-5 and VU GB 1206/5-5 only:
Use the four remaining nuts to secure the burner and
the bracket for the insulation protection plate. Tighten-
ing torque: 4Nm > When installing the nuts, ensure that the openings in the
insulation protection plate for ignition and monitoring
electrodes lie on top of the corresponding bolts in the
burner door. > Install the insulating mat. Ensure that the insulating mat
lies against the burner door. > Install the insulation protection plate by turning the bay-
onet fitting until it clicks into place. > Install the ignition and monitoring electrodes. Use new
seals for this. Tightening torque: 2.8Nm > Install the gas-air mixture unit (¬section 13.5.6). > Check that the product functions correctly and check the
leak-tightness (¬section 13.5.9).
15.5 Replacing insulating mats
If the safety cut-out on the burner door has been triggered, the insulating mat between the burner door and burner room may be damaged.
> Check and replace the insulating mat.
1
15.4 Replacing the fan
> Unscrew the four screws (1) from the fan. > Install a new fan and burner in the same position as
before.
15.7 Replacing the heat exchanger
> Drain the boiler (¬section13.2.2). > Remove the gas-air mixture unit (¬section13.5.1). > Unscrew the flow and return line in the front area of the
underside of the boiler.
To replace the insulating mat, proceed in the same way as when removing the burner (¬section15.4). It is not neces­sary to remove the burner.
15.6 Replacing the fan
> Remove the gas-air mixture unit (¬section13.5.1). > Remove the burner (¬section15.4).
1
15.5 Loosen the clamps on the flow and return pipes
> Loosen the clamps (1) on the sealing collars of the flow
and return pipes in the base area.
1
15.6 Loosen the locking plate
Replacing components
15.8.1 Replacing either the display or the PCB
> Replace the PCB or display according to the assembly
and installation instructions supplied.
If you are replacing only one component, the set parame­ters are transferred automatically. By switching on the boiler, the new component takes over the previously set parameters from the unreplaced component.
15.8.2 Replacing the PCB and the display at the same time
> Replace the PCB and display according to the assembly
and installation instructions supplied.
15
> On the heat exchanger upper bracket on the back wall,
loosen the locking plate (1).
> Lift the heat exchanger out of its bracket. The pipes can
be used as handles for this.
> Install the new heat exchanger in reverse order. > Install the gas-air mixture unit (¬section 13.5.6). > Fill and purge the boiler and, if necessary, the heating
installation.
15.8 Replacing the PCB and/or the display
Danger!
Risk of death from electric shock!
e
b
Mains connection terminals L and N remain live even if the continuous voltage on/off switch is turned off.
> Before carrying out any repair work on
the boiler, switch off the on/off switch.
> Disconnect the boiler from the power
mains by de-energising the boiler using a partition with a contact opening of at least 3 mm (e.g.fuses or power switches).
Caution.
Risk of material damage caused by incor­rect repairs.
Using an incorrect replacement display can cause damage to the electronics.
> Before replacing, check that the correct
replacement display is available.
> Never use another replacement display.
If you are replacing both components at the same time, the product switches directly to the menu to select the lan­guage after switching on. The default language setting is English.
> Select the required language. > Confirm your setting with (OK).
You are automatically taken to D.093 to set the device spe- cific number.
> Select the correct value for the relevant product type in
accordance with the following table.
Unit
VU GB 806/5-5 ecoTEC plus 82
VU GB 1006/5-5 ecoTEC plus 81
VU GB 1206/5-5 ecoTEC plus 80
15.1 Numbers of the unit variants
> Confirm your setting. The electronics are now set to the unit type and the param­eters of all adjustable diagnostics codes are set to default settings. The display automatically restarts with the installation assistant.
> Make the system-specific settings (¬ section12).
15.9 Ending repairs
> After completing the work, perform a gas tightness
check and a function check (¬section13.5.9).
Number of the
unit variant
ecoTEC plus installation and maintenance instructions 0020134823_01 65
Decommissioning
16
16 Decommissioning
16.1 Temporarily shutting down the boiler
Caution.
Risk of frost damage due to incorrect
b
decommissioning.
If you switch off the boiler using the on/off switch or disconnect it from the power mains, this can cause frost damage to the heating installation.
> Only shut down the boiler fully if the
heating installation is otherwise pro­tected from frost.
> Drain the heating installation fully.
2
50
16.3 Disposing of the boiler
The Vaillant ecoTEC plus boiler consists primarily of materi­als that can be recycled. The boiler and its accessories must not be disposed of with household waste.
> Make sure that the boiler and any existing accessories
are disposed of properly.
17 Vaillant Commercial Service
To ensure efficient and reliable operation of your boiler it is recommended that regular servicing is carried out by your service provider.
Vaillant Applied System Sales:
Vaillant Ltd. Nottingham Road, Belper, Derbyshire, DE56 1JT
Commercial Training
Telephone: 0845 601 8885 Email: training@vaillant.co.uk
Commercial After Sales Service
Telephone: 0870 850 3072 (Mon-Fri 8:30 – 17:30) Technical Help: 1634 292 392 (Mon-Fri 8:30 – 17:30) Fax: 01773 525 946 Email: aftersales@vaillant.co.uk
16.1 Switching off the boiler
> Close the gas isolator cock. > Close the cold water stop valve. > Drain the heating installation fully
(¬section13.2.3).
> Press the on/off switch (1).
The display (2) goes off.
16.2 Permanently decommissioning the boiler
> Close the gas isolator cock. > Close the cold water stop valve. > Drain the heating installation fully
(¬section13.2.3).
> Press the on/off switch (1).
The display (2) goes off.
> Isolate the boiler from the power mains. > Secure the gas line against leaks. > Dispose of the boiler correctly (¬section16.3).
1
18 Technical data
g
p
g
p
g
g
Technical data
18
ecoTEC plus Unit
ecoTEC plus
VU GB 806/5-5
ecoTEC plus
VU GB 1006/5-5
ecoTEC plus
VU GB 1206/5-5
Nominal heat output range P at 80/60 °C kW 14.9 - 74.7 18.7 - 93.3 22.4 - 112 Nominal heat output range P at 60/40 °C kW 16 - 80 20 - 100 24 - 120 Nominal heat output range P at 50/30 °C kW 16.5 - 82.3 20.74 - 102.8 24.7 - 123.4 Nominal rated efficiency (stationary) at 80/60 °C % 98 Nominal rated efficiency (stationary) at 60/40 °C % 105 Nominal rated efficiency (stationary) at 50/30 °C % 108
Standard degree of utilisation at 75/60 °C in accordance with DIN 4702-8 Standard degree of utilisation at 40/30 °C in accordance with DIN 4702-8 Maximum heat input during heating mode
Maximum heat input during cylinder charging Minimum heat input
1)
1)
1)
% 106
% 110
kW 76.2 95.2 114.3 kW 76.2 95.2 114.3 kW 15.2 19.2 22.9
Heating
Max. flow temperature (default setting: 75 °C) °C 85 Permissible operating overpressure MPa (bar) 0.6 (6.0) Rated water volume (when DT = 23 K)
l/h 2990 3740 4485
Condensate rate approx. (pH value 3.5 … 4.0) at 40/30 °C l/h 12.8 16 19.2 Remaining feed head of the high-efficiency pump with pump
rou
Remaining feed head of the modulating pump with pump
rou
MPa (bar) 0.024 (0.24) 0.038 (0.38) 0.036 (0.36)
MPa (bar) 0.042 (0.42) 0.026 (0.26) 0.024 (0.24)
General
Gas connection on unit Inches R 1 Heating connection on unit Inches G 1 1/4 Gas connection pressure (gas flow pressure) natural gas, G20 kPa (mbar) 2 (20)
Connection value at 15 °C and 101.3 kPa (1013 mbar)
Wobbe index (WS) at 0 °C and 101.3 kPa (1013 mbar)
Natural
Natural
EE setting, in relation to WS
Flue gas mass rate min./max.
4)
Natural gas H kWh/m
3)
Flue gas temperature min./max.
as H (Hi = 9.5 kWh/m3)m3/h 8.0 10.1 12.1
as range H kWh/m
3
3
12.0 – 16.1
15.0
g/s 6.9/34.4 8.9/43.6 10.6/52.5
3)
°C 40/85 Approved flue gas connections C13, C33, C43, C53, C93, B23, B23P, B53, B53P Permitted pressure difference in the flue pipe for installation
type B23p as a single occupancy max. Permitted pressure difference in the flue pipe for installation
type B23p as cascade operation max. Air/flue gas connection
Pa (bar) 150 (0.0015) 200 (0.002)
Pa (bar) 50 (0.0005)
mm 110/160 NOx class 5 NOx emissions mg/kWh
3)
CO
2
content
%9.0
< 50
Boiler dimensions (H x W x D) mm 960 x 480 x 602 Weight excl. pump group kg 68 86 90 Electrical connection V/Hz 230/50 Built-in fuse 4A, slow-blow Min. electrical power consumption excl. pump W 25 18 18 Max. electrical power consumption excl. pump W 122 160 160 Level of protection IP X4D Test symbol/registration no. CE- 0085CM0415
18.1 ecoTEC plus Technical Data
4) For operation with a gas quality other than the factory set
1) In relation to the heating value Hi and pure heating mode
2) Determined according to DIN 4702 Part 8
EEsetting, deviations from the specified nominal heat output or set heat output may occur
3) Calculated value for dimensioning of the chimney in accordance with DIN EN 13384-1
ecoTEC plus installation and maintenance instructions 0020134823_01 67
Glossary
19
19 Glossary
Burner anti-cycling time
The burner is electronically locked for a specific time after each time it is switched off ("restart interlock") to avoid fre­quent switching on and off of the burner (energy losses) and to extend the working life of the boiler. The burner anti­cycling time is only activated for the heating mode. Hot water handling is not affected if burner anti-cycling time is running.
Calorific value
Unlike the heating value, the calorific value of a fuel describes the total useable heat during combustion, based on the quantity of fuel used, including the condensation heat in the steam. The energy contained in steam can also be used if the steam liquefies on cooling.
Condensing technology
Technology which uses the calorific value of the fuel that is used. To do this, the flue gases are cooled below the dew point of the flue gas so that the steam they contain con­denses. The condensation heat that this releases can also be used. In particular, the flue gas losses are greatly reduced. The losses from conduction of heat and radiation are also reduced by the lower system temperatures. The entire heat­ing installation should therefore be designed for low system temperatures (flow/return temperature) for the effective use of the calorific value. The level of efficiency attainable for boilers is always given based on the heating value of the gas. Due to the additional condensation heat used, the cal­culated values can exceed 100 %.
of different system components within a heating installa­tion. It provides particular flexibility for retro-fitting and expanding the system. This simplifies the installation of boiler cascades or the subsequent addition of components such as solar hot water generation. The eBUS provides extended possibilities for connecting controllers and also for connecting to the vrnetDIALOG Internet communica­tions system for remote servicing and diagnosis.
Flue pipe
A flue pipe is a line system with two separate flow channels. The flue gas is routed into separate chambers at the same time as the required combustion air is pumped to the boiler. The flue pipe can be designed as a concentric or adjacent double flue gas pipe (the flue gas channel is sealed from the air channel). Floor-standing boilers and gas-fired wall­hung boilers can be operated as room-sealed through the flue pipe. As a result, boilers can be installed in new build­ings that, due to their airtight construction, do not offer sufficient combustion air for open-flued heat generators.
Gas-air mixture unit
The gas-air mixture unit is an assembly in Vaillant condens­ing units, which consists of the following four main compo­nents in the ecoTEC plus: Speed-regulated fan, gas valve, gas supply (mixture pipe) to the premix burner and premix burner
Multi-functional module
The multi-functional module is an accessory that controls additional functions or components in combination with Vaillant boilers with eBUS electronics. It also allows you to select and control 2 in 7 functions, e.g. circulation pump, external heating pump, external solenoid valve or response from the flue non-return flap.
Dew point
The dew point is the temperature at which steam turns to liquid (condensation). The steam in the flue gas from the boiler contains thermal energy, which can be released by condensation. In gas-fired and oil-fired boilers using calo­rific values, the flue gases are cooled so that the steam condenses and the heat that it contains can be output into the heating system.
Digital information and analysis system (DIA)
The Vaillant ecoTEC plus boiler is fitted with a digital infor­mation and analysis system (DIA). If additional settings are required, which have not been configured using the installa­tion assistant, you can view and modify further parameters using the DIA.
vrnetDIALOG Internet communication system
Using the vrnetDIALOG Internet communication system for remote setting and monitoring, you can set the heating installation at the customer's home from your home PC. Sono journey is required. vrnetDIALOG can also forward fault messages by fax, E-mail or SMS to you and thereby help with diagnostics. You can therefore prepare your work in advance and, if required, arrive at the customer's home with the right spare parts for maintenance or repair.
eBUS
eBUS is an abbreviation for energyBUS. The eBUS is a spe­cial bus used in heating technology, which assists the com­munication between intelligent components in the heating technology. In a Vaillant system, up to eight different heat generators can be connected via the eBUS. The eBUS com­munications protocol simplifies the control-related linking
20 Appendix
Commissioning checklist
Appendix
20
ecoTEC plus installation and maintenance instructions 0020134823_01 69
Index
Index
A
Accessories............................................................................. 27, 42
Adjusting the air ratio ............................................................... 46
Auxiliary relay............................................................................... 37
B
Burner ............................................................... 48, 49, 52, 56, 63
Burner anti-cycling time ..................................................... 41, 68
C
CE label ............................................................................................ 3
Checking
Burner ...................................................................................... 52
CO2 content ............................................................................ 46
Connection pressure ............................................................. 32
Flue gas recirculation ............................................................ 31
Function of the boiler ........................................................... 38
Gas ratio setting ..................................................................... 31
Heating mode ......................................................................... 38
Leak-tightness ........................................................................ 38
Leak-tightness of flue gas system ...................................... 31
Scope of delivery .................................................................... 12
Check programmes ............................................................... 37, 61
Circulation pump......................................................................... 27
Cleaning
Cleaning the integral condensation heat exchanger .... 52
Condensate siphon ................................................................ 53
Condensate drain pipework...................................................... 20
Condensate siphon ................................................. 20, 31, 48, 53
Connecting
Condensate drain pipework ................................................ 20
Controllers ............................................................................... 26
Gas line ..................................................................................... 17
Heating flow ............................................................................. 19
Heating return ......................................................................... 19
Connection wiring diagram ...................................................... 28
D
Decommissioning ........................................................................ 66
Diagnostics codes ................................................................ 57, 58
Diagnostics level 1 ....................................................................... 57
Diagnostics level 2 ...................................................................... 58
Disposal
Boiler ........................................................................................ 66
Packaging ................................................................................. 12
Draining
Boiler ........................................................................................ 49
Heating installation ............................................................... 49
E
Expansion relief valve ................................................................. 10
F
Fan .................................................................................... 49, 60, 63
Fault codes ................................................................................... 59
Fault memory ............................................................................... 59
Filling
Condensate siphon ................................................................. 31
Heating installation ............................................................... 29
Fitting
Controllers ............................................................................... 26
Flue gas installation ................................................................... 22
Flue pipe ............................................................. 6, 22, 36, 48, 55
Front casing .................................................................................. 24
Frost protection ........................................................................... 56
Function menu ............................................................................. 49
G
Gas-air mixture unit ................................................................... 50
Gas flow pressure ....................................................................... 32
Gas line ........................................................................................... 17
H
Heat exchanger
Replacing ................................................................................. 64
Heating flow .................................................................................. 19
Heating return .............................................................................. 19
Heating water .............................................................................. 29
Preparation ............................................................................... 8
I
Installation site ........................................................................ 8, 15
Installer level ................................................................................ 33
Installing
Flue pipe .................................................................................. 22
Side section ............................................................................ 62
Intended use ................................................................................... 5
Ionisation electrode ................................................................... 52
L
Language ...................................................................................... 36
Index
M
Mains connection ........................................................................ 24
Multi-functional module ............................................................. 37
O
Overview
Diagnostics codes ..................................................... 39, 57, 58
Fault codes ........................................................................ 60, 61
Inspection and maintenance work .................................... 48
Menu structure ....................................................................... 34
Parameters .............................................................................. 40
Status codes ........................................................................... 56
P
Preparing
Electrical installation ............................................................ 24
Flue gas installation .............................................................. 22
Gas installation ....................................................................... 17
Hydraulic installation ............................................................. 18
Pump group
Electrically connecting ......................................................... 24
Pump operating mode ......................................................... 40, 41
Pump output ................................................................................. 41
Pump overrun ........................................................................ 41, 57
Purging
Heating installation ............................................................... 30
T
Technical data .............................................................................. 67
Troubleshooting .......................................................................... 55
Type of gas ..................................................................................... 4
Type overview ................................................................................ 4
W
Water pressure .............................................................. 30, 43, 56
Water pressure sensor ....................................................... 56, 60
R
Removing
Fan ............................................................................................. 63
Gas-air mixture unit .............................................................. 50
Side section ............................................................................ 62
Repair ..................................................................................... 62, 65
Reset .............................................................................................. 59
S
Safety information ................................................................... 5, 6
Setting
Burner anti-cycling time ....................................................... 41
Language ................................................................................. 36
Parameters .............................................................................. 39
Spare parts ................................................................................... 62
Start-up ......................................................................................... 36
Status codes................................................................................. 56
73ecoTEC plus installation and maintenance instructions 0020134823_01
Supplier
Manufacturer
0020134823_01 GBIE 122012 – Subject to change
Loading...