Vaillant ecoTEC plus 624, ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 824, ecoTEC plus 831, ecoTEC plus 837 Installation And Maintenance Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Installation and maintenance instructions
For the competent person
Installation and maintenance instructions
ecoTEC plus
VU
VUW
GB, IE
Table of Contents
BEFORE PROCEEDING - ENSURE BOILER IS
CORRECT FOR GAS GROUP SUPPLIED!
i
Table of Contents
1 Notes on the documentation .....................................4
20 Benchmark Log Book ................................................. 85
Index ...........................................................................................87
3Installation and maintenance instructions ecoTEC plus 0020116700_01
Notes on the documentation
1
1 Notes on the documentation
The following instructions are intended to guide you
throughout the entire documentation. Further documents
apply in combination with these installation and maintenance instructions.
We accept no liability for any damage caused by nonobservance of these instructions.
Other applicable documents
> Follow all installation instructions for the various parts
and components of the system without exception when
installing the ecoTEC plus.
These installation instructions are enclosed with the various
system components as well as additional components.
> Also observe all the operating instructions included with
the system components.
1.1 Storing documents
> Pass these installation instructions and all other applica-
ble documents and, if necessary, any required aids to the
system operator.
The operator will store the instructions and aids so that
they are available when required.
BoilerType designation
ecoTEC plus 612 (VU GB 126/5-5) 0010011677 41-044-60
ecoTEC plus 615 (VU GB 156/5-5)0010011678 41-044-61
ecoTEC plus 618 (VU GB 186/5-5)0010011679 41-044-62
ecoTEC plus
ecoTEC plus 624 (VU GB 246/5-5)0010011681 41-044-63
ecoTEC plus 630 (VU GB 306/5-5)0010011682 41-044-64
ecoTEC plus
ecoTEC plus 637 (VU GB 376/5-5)0010011684 41-044-65
ecoTEC plus 824 (VUW GB 246/5-5) 0010011685 47-044-40
ecoTEC plus 831 (VUW GB 316/5-5) 0010011686 47-044-41
ecoTEC plus
ecoTEC plus 837 (VUW GB 376/5-5) 0010011688 47-044-42
1.1 Aplliance types, article numbers and Gas Council Number
The article number of the boiler can be found on the identification plate.
618 (VU GB 186/5-5)
(LPG)
630 (VU GB 306/5-5)
(LPG)
831 (VUW GB 316/5-5)
(LPG)
Article
number
0010011680 41-044-66
0010011683 41-044-67
0010011687 47-044-46
Gas
Council
Number
1.2 Symbols used
The symbols used in the text are explained below:
Symbol that denotes useful tips and information
i
> Symbol for a required action
1.3 Applicability of the instructions
These installation instructions are only valid for boilers with
the following article numbers:
1.4 Identification plate
The identification plate of the Vaillant ecoTEC plus is
attached to the underside of the boiler in the factory.
The article number of the gas fired wall hung boiler can be
found in the serial number. The seventh to sixteenth numbers constitute the article number.
The serial number can also be found on a plate, which is in
a plastic bag behind the front flap on the underside of the
boiler. The serial number can also be shown on the display
of the boiler (¬Operating instructions).
1.5 CE label
The CE label shows that the boilers comply
with the basic requirements of the applicable
directives as stated on the identification plate.
– Directive 2009/142/EEC of the Commission with amend-
ments "Directive for Harmonisation of Legal Regulations
of the Member States for Gas Cosumption Appliances"
(Gas equipment directive)
– Directive 92/42/EEC of the Commission with amend-
ments "Directive Concerning the Efficiency of New Hot
Water Heating Boilers Fired by Liquid or Gaseous Fuels"
(Efficiency directive)
4Installation and maintenance instructions ecoTEC plus 0020116700_01
Notes on the documentation
1
– Directive 2006/95/EC of the Council with amendments
"Directive Concerning Electrical Equipment for Use
Within Specific Voltage Limits" (Low voltage directive)
– Directive 2004/108/EC of the Council with amendments
The boilers comply with the type sample described in the
EC Type Sample Test Approval.
PIN No. CE-0085CM320
The boilers comply with the following standards:
– EN 483
– EN 625
– EN 677
– EN 55014
– EN 60335-1
– EN 60335-2-102
– EN 61000-3-2
– EN 61000-3-3
1.6 Benchmark
1.7 Type overview
Appliance type
ecoTEC plus
612 (VU GB 126/5-5)
615 (VU GB 156/5-5)
618 (VU GB 186/5-5)
624 (VU GB 246/5-5)
630 (VU GB 306/5-5)
637 (VU GB 376/5-5)
824 (VUW GB 246/5-5)
831 (VUW GB 316/5-5)
837 (VUW GB 376/5-5)
1.2 Type overview
Designated country
(designation in
accordance with
ISO 3166)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
GB (Great Britain)
IE (Ireland)
Approval
category
I
2H
I
2H
II
2H3P
II
2H3P
II
2H3P
II
2H3P
II
2H3P
II
2H3P
II
2H3P
i
Vaillant Ltd. supports the Benchmark Initiative.
You will find the Benchmark Logbook on the last
pages of this instruction manual. It is very
important that this document be filled out properly when installing, commissioning, and fully
explained at hand over to the operator of the
installation. Installers should point out also the
service record section for completion following
service calls to this appliance.
Installation and maintenance instructions ecoTEC plus 0020116700_01 5
a
2
Safety
a
2 Safety
2.1 Safety and warning information
> When installing the ecoTEC plus, take account of the
general safety instructions and the warning notes that
appear before all of the actions.
2.1.1 Classification of warnings
The warning notes are classified in accordance with the
severity of the possible danger using the following warning
signs and signal words:
Warning
sign
a
Signal
word
Danger!
Danger!
Explanation
Immediate danger to life or
risk of severe personal
injury
Risk of death from electric
shock
e
Warning.Risk of minor personal injury
a
Risk of material or environ-
Caution.
mental damage
b
2.1 Classification of warnings
2.2 Intended use
The Vaillant ecoTEC plus boilers are state-of-the-art units
which have been constructed in accordance with recognised
safety regulations. Nevertheless, there is still a risk of injury
or death to the operator or others or of damage to the
boiler and other property in the event of improper use or
use for which it is not intended.
This boiler is not designed to be used by persons (including
children) with limited mental and sensory capabilities or by
persons who do not have enough experience and/or knowledge, unless they are supervised by a person who is responsible for their safety or they have been instructed by him/
her about how to use the boiler.
Children must be supervised to ensure that they do not
play with the boiler.
The boiler is intended as a heater for closed hot water/central heating installations and for hot water generation.
The use of the ecoTEC plus in vehicles, such as mobile
homes and caravans, is not classed as intended use. Units
that are not classed as vehicles are those that are installed
in a fixed and permanent location and that do not have any
wheels (fixed installation).
Any other use, or use beyond that specified, shall be considered as improper use. Any direct commercial or industrial use is also deemed to be improper.
The manufacturer or supplier is not liable for any damage
resulting from such use. The user alone bears the risk.
Intended use includes the following:
– observance of accompanying operating, installation and
maintenance instructions for Vaillant products as well as
for other parts and components of the system
– installing and fitting the appliance in accordance with the
boiler and system approval
– complying with all of the inspection and maintenance
conditions listed in the instructions.
Caution.
Any improper use is forbidden.
2.1.2 Structure of warnings
Warning signs are identified by an upper and lower separating line. and are laid out according to the following basic
principle:
Signal word!
Type and source of danger!
a
6Installation and maintenance instructions ecoTEC plus 0020116700_01
Explanation of the type and source of danger
> Measures for averting the danger
2.3 Basic safety instructions
> Observe the following safety instructions at all times.
European installation directive
Installation and maintenance of the appliance should only
be undertaken by a competent person (referred to in these
instructions as “competent person” or “skilled trade company” and thereby indicating male and female persons)
approved at the time by the Health and Safety executive
and in accordance with the gas safety (installation and use)
regulations 1998. The existing regulations, rules and guidelines must be observed when doing so. The competent person is also responsible for inspection, maintenance and
repairs to the unit, as well as alterations to the gas volume
setting.
a
Safety
2
a
Only IE: The installation must comply with the current Version of I.S.813 "Domestic Gas Installations" and the current
Building Regulations.
The current ETCI Regulations for installing electrical equipment must also be observed.
Installation and settings
In the following cases, the boiler must be operated only
with the front casing fitted and closed and with a completely mounted air/flue gas duct:
– starting up
– test purposes
– continuous operation,
Otherwise, under unfavourable operating conditions, injury,
death or material damage may occur.
Exclusively for test purposes such as gas working pressure
testing the boiler may be operated with the front casing
removed for short durations ONLY but must have a completely mounted air/flue gas duct.
What to do if you smell gas
Installation errors, damage, manipulation, an unauthorised
installation site or similar can cause gas to escape and
result in a risk of poisoning and explosion. If there is a smell
of gas in the building, proceed as follows:
> Avoid rooms that smell of gas.> If possible, open doors and windows fully and ensure air
is circulating.
> Avoid the use of naked flames (e.g. lighters, matches).> Do not smoke.> Do not use any electrical switches, plugs, doorbells, tele-
phones or other communication systems in the building.
> Close the gas meter isolator device or the main isolator
device.
> If possible, close the gas stop cock on the unit.> Warn the occupants in the building by knocking or call-
ing.
> Leave the building.> If you can actually hear gas leaking, leave the building
immediately and ensure that no third parties enter the
building.
> Alert the police and fire brigade when you are outside
the building.
> Use a telephone outside the building to inform the gas
supply company or National Grid Transco 0800 111999.
Material damage caused by corrosion
To prevent corrosion on the boiler and also on the air/flue
gas duct, note the following:
> Do not use sprays, solvents, chlorinated cleaning agents,
paint, adhesives or similar substances in the vicinity of
the boiler.
Under unfavourable circumstances, these substances may
cause corrosion.
Material damage due to improper use and/or
unsuitable tools
The use of unsuitable tools or improper use thereof may
cause damage, such as gas or water leaks.
> When tightening or loosening threaded connections,
always use suitable open-end spanners, but do not use
pipe wrenches, extensions, etc.
2.4 Important information regarding
propane-fired boilers
Purging the liquid gas tank when installing the system:
> Before installing the boiler, make sure that the gas tank
has been purged.
The liquid gas supplier is responsible for proper ventilation
of the tank. Ignition problems can result if the tank is not
purged properly.
> In such cases, first contact the person in charge of filling
the tank.
> Also observe the information on conversion to liquid gas
in (¬section10.11) of this manual.
Using the correct gas group
Using the wrong gas group may cause a fault shutdown on
the boiler. Furthermore, ignition and combustion noise may
occur in the boiler.
> Only use propane gas G31.
Affix tank sticker
Affix the enclosed tank sticker (propane quality) to the tank
where it will be clearly visible, or on then cylinder cabinet
near the filler nozzle if possible.
What to do if you smell exhaust fumes
Installation errors, damage, manipulation, unauthorised
installation sites or the like can cause flue gas to escape
and result in a risk of poisoning. If there is a smell of
exhaust fumes in the building, proceed as follows:
> If possible, open doors and windows fully and ensure
adequate ventilation.
> Switch the boiler off.> Check the flue gas route in the boiler and the flue gas
pipes.
Installation and maintenance instructions ecoTEC plus 0020116700_01 7
a
2
Safety
a
2.5 General requirements
2.5.1 Related documents
To ensure the safe installation and continued satisfactory
operation of your appliance, all works shall be carried out
by a competent installer fully conversant with the required
current and up to date, acts standards, laws and regulations
relevant for this range of equipment at the time of installation. In addition any special requirements of Local Authorities, gas undertakings or insurers must be complied with.
Installers shall carryout a full site risk assessment and put
into place all necessary steps and procedures to comply
with Health and safety at work act and ensure safety of
themselves and others with regard to manual handling and
working at height requirements.
Attention shall be paid to (but not restricted to) the following:
– Gas Safety (Installation and Use) regulations.
– All Building Regulations 2000 for England and Wales,(as
amended).
– (Includes Approved Codes of Practice and Approved Doc-
uments for building regulations e.g. L1, L1A, L1B, L8.)
– The Building Standards, Scotland, and any requirements
determined by the local authorities within.
– BS 7671 Requirements for electrical installations. IEE
Wiring Regulations
– The Electricity at Work Regulations.
– The Water supply (water fittings) regulations 1999.
– BS 5854 Code of practice for flues and flue structures
in buildings.
– BS EN 12828 Design of water-based heating systems.
– BS 6700 Specification for the design, installation, test-
ing and maintenance of services supplying water for
domestic use within buildings and their curtilages.
– BS 6880 Code of practice for low temperature heating
systems with outputs greater than 45kW.
Part 1 Fundamental and design considerations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and maintenance.
– BS 6981 Installation of low pressure gas pipework of up
to 35mm in domestic premises.
– BS 4814 Specification for: Expansion vessels using an
internal diaphragm, for sealed hot water and heating sys-
tems.
– BS 7074 Application, selection and installation of expan-
sion vessels and ancillary equipment for sealed water
systems.
Part 1 Code of practice for domestic heating and hot
water.
Part 2 Code of practice for low and medium temperature
hot water systems.
– BS 7593 Code of practice for treatment of water in
domestic hot water central heating systems
– BS EN 13831 Closed expansion vessels with built in dia-
phragm
– BS EN 14336 Heating systems in buildings. Installation
and commissioning of water based heating systems.
– BS 5440 – 1 Installation of flues and ventilation for gas
appliances of rated input not exceeding 70kW*
– BS 5440 – 2 Flueing and ventilation for gas appliances
of rated input not exceeding 70kW*
* 1st 2nd and 3rd family gases.
– BS EN 6798 Installation & maintenance of gas fired hot
water boilers of rated input not exceeding 70kW net
Institute of Gas Engineers Publications:
– IGE/UP/1B (Edition 2) Tightness testing and direct purg-
ing of small natural gas installations.
– IGE/UP/ 7 (Edition 2) Gas in timber and light steel
– BS 5482 - Part 1 Domestic butane and propane gas
burning installations
2.5.2 Installation site
The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must
also provide adequate space for servicing and air circulation around the boiler.
Before commencement of any works the installer should
carry out a full risk assessment in accordance with Health
and Safety executive regulations.
The boiler may be installed in any room, although particular
attention is drawn to the requirements of BS 7671 (IEE Regulations), the electrical provisions of the Building Regulations (Scotland) and in IE the current edition of IS 813 and
the current ETCI rules, in respect of the installation of a
boiler in a room containing a bath or shower.
Danger!
Risk of death from electric shock when
e
installing a boiler in a room with a bath
or shower!
If the electrical switches or controllers
are installed too close to the bath or the
shower, the person therein is at risk of electrocution.
> Install electric switches and controllers
that operate using mains voltage outside
the reach of persons in baths or showers.
In case of installation of the boiler in an unusual location,
special procedures may be necessary and BS5546 and
BS6798 give detailed guidance on this aspect. The boiler
must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boiler.
The boiler may be installed on a combustible wall, subject
to the requirements of the Local Authorities and Building
Regulations. A compartment used to enclose the boiler
must be designed and constructed specifically for this purpose. (An existing cupboard or compartment may be used
8Installation and maintenance instructions ecoTEC plus 0020116700_01
a
Safety
2
a
provided that it is modified for the purpose). Details of
essential features of cupboard/compartment design including airing cupboard installations are given in BS 6891. In IE
the current edition of IS 813.
If the boiler is to be installed in a half-timbered
house, the installation must be undertaken in
i
i
b
accordance with the Institute of Gas Engineers
Publication IG/UP/7 Edition 2 "Gas installations
in timber framed and light steel framed buildings"
If the boiler is to be installed in an airing
cupboard it is not required to separate the
boiler with a non-combustible partition. However
installation and servicing clearances must be
maintained, and the boiler kept clear of any
clothing.
Caution.
Risk of damage caused by aggressive
vapours and dust.
Aggressive vapours and dust in the installation room may cause corrosion damage to
the boiler and to the flue gas installation.
> Ensure that the boiler is room sealed if
the air in the installation room contains
aggressive vapours or dust.
– for larger systems IGE/UP/1A and
– for LPG installations refer to BS5482 - 1 or
– IGE/UP1 Edition 2 for larger volume installations.
2.5.4 Air supply
Detailed recommendations for air supply are given in
BS5440: Part2. It is not necessary to have an air vent in
the room or internal space in which the boiler is installed.
2.5.5 Compartment ventilation
The boilers are very high efficiency appliances. As a consequence the heat loss from the appliance casing during
operation is very low. Compartment ventilation is required
if the flue used is not concentric and air is supplied from
the room or compartment the boiler is installed in.
2.5.6 Electrical supply
Danger!
Risk of death from electric shock.
a
If the appliance is not earthed, it may hold
voltage if a defect occurs.
> Earth the appliance.
> Observe the following when choosing the installation site
and operating the boiler,
– Do not install the boiler in rooms prone to frost.
– Do not install the boiler in rooms in which the com-
bustion air contains chemical substances, e.g. fluoride,
chlorine, sulphur, dust, etc. (e.g. sprays, solvents,
cleaning agents, paint, adhesives).
> Please ensure that the boiler is room sealed or in a sepa-
rate installation room if
– the combustion air supply contains the aforemen-
tioned substances,
– you install the boiler in hairdresser salons, painter's or
joiner's workshops, cleaning businesses or similar.
> Do not route the combustion air through an old oil fur-
nace chimney, as this can also cause corrosion.
2.5.3 Gas supply
An existing gas meter should be checked to ensure that it is
capable of passing the rate of gas supply required.
Installation pipes should be fitted in accordance with
BS6891, in IE in accordance with the current issue of IS813.
Pipework from the meter to the boiler must be of an adequate size.
Do not use pipes of a smaller size than the boiler gas connection. The complete installation must be tested and
purged in accordance with:
– IGE/UP /1B for systems up to 0.035m
3
capacity
A 230 V, ~ 50 Hz single phase electricity supply fused to 3
Amp. must be provided in accordance with the latest edition
of BS7671 (IEE Wiring Regulations) and any other local regulations that may apply. In IE reference should be made to
the current edition of the ETCI rules. The method of connection to the mains electricity supply must provide a
means of completely isolating the boiler and its ancillary
controllers. Isolation is preferably by the use of a fused
three pin plug and unswitched shuttered socket outlet, both
complying with the requirements of BS1363. Alternatively, a
3 Amp. fused doublepole switch with a 3mm contact opening on both poles may be used.
2.5.7 Water circulation system
Detailed recommendations concerning the water circuit system can be taken from BS6798 and BS5449, Part1 (for
"Small Bore" and "Micro Bore" central heating installations). Lines which do not form part of the usable heating
surface should be insulated to prevent heat losses and possible freezing up, especially where the lines run under
rooves and ventilated cellar rooms. The drain connections
must be easily-accessible, so that the entire system including the boiler and hot water system can be drained. The
drain connections should be at least 1/2" (BSP nominal
size) and must be in accordance with BS 2879.
Installation and maintenance instructions ecoTEC plus 0020116700_01 9
a
2
Safety
a
The boiler is suitable for Minibore and Microbore systems.
Water lines are to be copper pipes in accordance with
BS2871, Part1. These must be thoroughly cleaned, especially when connecting a new boiler to an existing system.
The use of unsuitable heating water can cause aluminium corrosion and a resulting lack of leaktightness.
In contrast to steel, grey cast iron or copper, for example,
aluminium reacts with alkaline heating water (pHvalue>8.5)
to produce substantial corrosion.
> When using aluminium, make sure that the pH value of
the heating water is between 6.5 and a maximum of 8.5.
Risk of damage if the heating water is treated with
unsuitable frost or corrosion protection agents.
Frost and corrosion protection agents can cause changes to
seals, noise during heating mode and may lead to
other consequential damage.
> Do not use any unsuitable frost or corrosion protection
agents.
Mixing additives with the heating water can result in material damage. However no incompatibility with Vaillant boilers has been detected with proper use of the following
products over a long period.
> When using additives, follow the manufacturer's instruc-
tions without exception.
Vaillant accepts no liability for the compatibility of any additive or its effectiveness in the rest of the heating installation.
Additives for cleaning measures
(subsequent flushing required)
– Fernox F3
– Sentinel X 300
– Sentinel X 400
Provided the national regulations and technical standards
do not stipulate more stringent requirements, the following
applies:
> You must condition the heating water in the following
cases:
– If the entire filling and supplementary water quantity
during the operating life of the system exceeds three
times the nominal volume of the heating installation
or
– If the limit values shown in the tables are not
observed.
Total heating
output
kW
< 50
> 50 to £ 200
>200 to £ 600
> 600
1) on systems with circulation water heaters and for systems with
electric heating elements
2) from the specific system volume (nominal capacity in litres/heating
output; for multiple boiler systems, the lowest individual heating
output should be used). This data only applies up to 3 times the
system volume for filling and top-up water. If 3 times the system
volume figure is exceeded, the water must be treated in exactly the
same way as if the limits quoted in table2.2 were exceeded
(softening, desalination, hardness stabilisation or desludging).
2.2 Guideline values for heating water: water hardness
Overall hardness at smallest boiler heating
2)
surface
3
1)
> 20 l/kW
< 50 l/kW
3
mol/m
(mg/l CaCO3)
2
(200)
1.5
(150)
0.02
(2.0)
0.02
(2.0)
> 50 l/kW
mol/m
(mg/l CaCO3)
0.02
(2.0)
0.02
(2.0)
0.02
(2.0)
0.02
(2.0)
20 l/kW
mol/m
(mg/l CaCO3)
No require-
ment or
1)
< 3
< (300)
2
(200)
1.5
(150)
0.02
(2.0)
3
Additives intended to remain permanently in the
system
– Fernox F1
– Fernox F2
– Sentinel X 100
– Sentinel X 200
Additives for frost protection intended to remain
permanently in the system
– Fernox Antifreeze Alphi 11
– Sentinel X 500
> Inform the operator of the necessary measures if you
have used these additives.
> Inform the operator about the required measures for
frost protection.
Permissible water hardness
> Observe all valid national and technical regulations when
conditioning filling and supplementary water.
10Installation and maintenance instructions ecoTEC plus 0020116700_01
Permissible salt content
Heating water characteristics
Electrical conductivity
at 25 °C
AppearanceFree of sedimentary materials
pH value at 25 °C8.2 - 10.0
Oxygenmg/l< 0.1< 0.02
1) For aluminium and aluminium alloys, the pH range is restricted
from 6.5 to 8.5.
2.3 Guideline values for heating water: Salt content
UnitLow-saltSaline
mS/cm
< 100100 - 1500
1)
8.2 - 10.0
1)
2.5.8 Pressure relief valve
The boiler is equipped with a pressure relief valve. This
safety device is required for all sealed central heating sys-
a
tems, is preset to 3 bar and is fitted with a 15 mm compression connection for the discharge pipe, whose diameter
must not be less than 15 mm. The pressure relief valve must
not be used for draining purposes.
2.5.9 Venting
The boiler is fitted with an automatic air vent. Other measures need to be taken to allow the heating system to be
either automatically or manually vented during filling and
during commissioning.
Safety
3
a
Installation and maintenance instructions ecoTEC plus 0020116700_01 11
Description of the appliance
3
3 Description of the appliance
Design
5
4
3
2
1
3.1 Functional elements of the VU system boiler
5
6
7
8
9
10
11
12
13
14
15
16
4
3
2
1
19
18
17
3.2 Functional elements of the VUW combination boiler
6
7
8
9
10
11
12
13
14
15
16
Key
1 Gas valve
2 Water pressure sensor
3 Venturi with mass flow sensor
4 Heat exchanger
5 Connection for the air/flue gas duct
6 Expansion vessel
7 Air intake pipe
8 Compact thermal module
9 Ignition electrode
10 Fan
11 Automatic air vent
12 Pressure gauge
13 Heating pump
14 By-pass valve
15 Expansion relief valve
16 Electronics box
Key
1 Gas valve
2 Water pressure sensor
3 Venturi with mass flow sensor
4 Heat exchanger
5 Connection for the air/flue gas duct
6 Expansion vessel
7 Air intake pipe
8 Compact thermal module
9 Ignition electrode
10 Fan
11 Automatic air vent
12 Pressure gauge
13 Heating pump
14 By-pass valve
15 Expansion relief valve
16 Electronics box
17 Diverter valve with bypass
18 Impeller sensor (hot water)
19 Secondary heat exchanger
12Installation and maintenance instructions ecoTEC plus 0020116700_01
Installation
4
4 Installation
BEFORE PROCEEDING - ENSURE BOILER IS
CORRECT FOR GAS GROUP SUPPLIED!
i
The work described in this section must only be carried out
by a competent person.
4.1 Accessories
4.1.1 Controller
To control the ecoTEC, Vaillant offers various controller versions for connecting to the switching rail or for plugging
into the operator control screen.
VR 65 – Control Centre
VR 66 – Control Centre
VR 61/2 – Two Zone Wiring Centre
VR 81/2 – Remote Control Unit
VR 68/2 – Solar Module
4.1 Controller accessories
The pipes can be routed upwards behind the
boiler in front of the wall (surface installation)
i
using the spacer frame. Which means the distance between the wall and the boiler increases
by 65mm.
4.2 Scope of delivery
The Vaillant ecoTEC plus is delivered pre-mounted in a
packaging unit.
4.2.1 Unpacking the boiler
> Remove the boiler from its box.> Remove the protective film from all parts of the boiler.
4.2.2 Checking the scope of delivery.
> Check that all parts have been delivered and are intact
(¬fig.4.1 and ¬table4.2 or ¬fig.4.2 and ¬table4.3).
8
7
6
5
1
2
3
4
4.1.2 Installation and operation
Optional accessories are available for use in conjunction
with the installation and operation of the ecoTEC.
The current price list shows the complete range of hydraulic
accessories for the ecoTEC plus series.
Installation and maintenance instructions ecoTEC plus 0020116700_01 13
> Dispose of the cardboard packaging used on the eco-
TEC plus at a cardboard recycling site.
> Dispose of the plastic film and plastic filling at an appro-
priate plastic recycling site.
> Observe national regulations.
4.3 Transporting the appliance
Important:
With regards to the Manual Handling Operations, 1992 Reg-
1
ulations, the following lift operation exceeds the recommended weight for a one man lift.
General recommendations when handling
2
> Clear the route before attempting the lift.> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Keep load as close to body as possible. Do not
twist – reposition feet instead.
> If 2 persons performing lift, ensure co-ordinated move-
ments during lift.
> Avoid upper body/top heavy bending - do not lean
forward/sideways.
> Recommend wear suitable cut resistant gloves with good
3
grip to protect against sharp edges and ensure good
grip.
> Always use assistance if required.
4
Removal of carton from delivery van
Recommend 2 person lift or 1 person with use of sack truck.
> If 1 person is performing lift, straddle the load, tilt and
place carton into position on truck.
> Recommend secure appliance onto truck with suitable
straps.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Keep load as close to body as possible.> If 2 persons performing lift, ensure co-ordinated move-
ments during lift.
> Always use assistance if required.
Carriage of carton from point of delivery to point
of installation – ground floor.
Recommend 2 person lift or 1 person with use of sack truck.
> If 1 person is performing lift, straddle the load, tilt and
place carton into position on truck.
> Recommend secure appliance onto truck with suitable
straps.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Keep load as close to body as possible.> If 2 persons performing lift, ensure co-ordinated move-
ments during lift.
> Clear the route before attempting the lift.
14Installation and maintenance instructions ecoTEC plus 0020116700_01
Installation
4
> If removing boiler from truck straddle the load and tilt
forwards to facilitate secure grip.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Do not twist – reposition feet instead.> Take care to avoid trip hazards, slippery or wet
surfaces and climbing steps and stairs.
> Always use assistance if required.
Carriage of carton from point of delivery to point
of installation – first or higher floor, cellar.
Recommend 2-person lift or 1 person with use of sack truck.
> If 1 person is performing lift, straddle the load, tilt and
place carton into position on truck.
> Recommend secure appliance onto truck with suitable
straps.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Keep load as close to body as possible.> If 2 persons performing lift, ensure co-ordinated move-
ments during lift.
> Avoid upper body/top heavy bending - do not lean
forward/sideways.
> Clear the route before attempting the lift.> If removing boiler from truck straddle the load and tilt
forwards to facilitate secure grip.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Do not twist – reposition feet instead.> Take care to avoid trip hazards, slippery or wet
surfaces and climbing steps and stairs.
> Always use assistance if required.
Carriage of carton from point of delivery to point
of installation – roofspace.
> Recommend 2-person lift.> Ensure co-ordinated movements during lift.> Avoid upper body/top heavy bending - do not lean
forward/sideways.
> Clear the route before attempting the lift.> Take care to avoid trip hazards, slippery or wet
surfaces and climbing steps and stairs.
> When transferring appliance into roofspace,
recommend 1 person to be in roofspace to receive the
appliance and other person to be below to pass up and
support appliance.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Keep load as close to body as possible.> Always use assistance if required.> It is assumed safe access, flooring and adequate
lighting are provided in the roof space.
> It is recommended a risk assessment of the roof space
area be carried out before moving the appliance into the
area to take into account access, stability of flooring,
lighting and other factors, and appropriate measures
taken.
Unpacking of appliance from carton.
> Recommend 2 persons unpack appliance from carton.> Always keep working area clear.> Recommend straps and open carton flaps, then remove
items from the top including the polystyrene packing and
remove carton by sliding up over the boiler.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs.
> Keep load as close to body as possible.> Always use assistance if required.> Dispose of packaging in a responsible manner.> Recommend wear suitable cut resistant gloves with good
grip to protect against sharp edges and ensure good grip
when handling appliance outside packaging.
Positioning of Appliance for Final Installation –
no obstructions.
> If appliance weight is over 25 kg always use 2 persons to
move where practical.
> Fit bracket securely onto wall before lifting appliance
into position.
> Obtain firm grip on front and sides of appliance, lift
upwards, ensure stable balance achieved and lift
upwards to position in place on bracket.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs - when lifting load from floor
level.
> Do not twist – reposition feet instead.> Keep boiler as close as possible to body throughout lift
to minimise strain on back.
> Ensure co-ordinated movements to ensure equal spread
of weight of load.
> Always use assistance if required.> Recommend wear suitable cut resistant gloves with good
grip to protect against sharp edges and ensure good grip
when handling appliance.
Positioning of Appliance for Final Installation –
above worktop, foreseeable obstructions etc.
> If appliance weight is over 25 kg always use 2 persons to
move where practical.
> Fit bracket securely onto wall before lifting appliance
into position.
> Obtain firm grip on front and sides of appliance, lift
upwards, onto worktop if practicable.
> Ensure stable balance achieved and lift upwards to
position in place on bracket.
> If 2 persons positioning onto bracket obtain firm grip at
front and sides/base of boiler.
> Ensure coordinated movements during 2 person lifts to
ensure equal spread of weight of load.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs - when lifting load from floor
level.
> Do not twist – reposition feet instead.> Keep boiler as close as possible to body throughout lift
to minimise strain on back.
> Avoid upper body/top heavy bending - do not lean
forward/sideways.
Installation and maintenance instructions ecoTEC plus 0020116700_01 15
Installation
4
> Always use assistance if required.> Recommend wear suitable cut resistant gloves with good
grip to protect against sharp edges and ensure good grip
when handling appliance.
Positioning of Appliance for Final Installation –
within compartment etc. restricting installation.
> If appliance weight is over 25 kg always use 2 persons to
move where practical.
> Fit bracket securely onto wall before lifting appliance
into position.
> Obtain firm grip on front and sides of appliance, lift
upwards, onto worktop if practicable.
> Ensure stable balance achieved and lift upwards to drop
into place onto bracket.
> If 2 persons positioning onto bracket obtain firm grip at
front and sides/base of boiler.
> Ensure coordinated movements during 2 person lifts to
ensure equal spread of weight of load.
> If 1 person positioning onto bracket recommend obtain
firm grip supporting base of boiler.
> Ensure safe lifting techniques are used – keep back
straight – bend using legs - when lifting load from floor
level.
> Do not twist – reposition feet instead.> Keep boiler as close as possible to body throughout lift
to minimise strain on back.
> Always use assistance if required.> Recommend wear suitable cut resistant gloves with good
grip to protect against sharp edges and ensure good grip
when handling appliance.
flooring, lighting and other factors, and appropriate
measures taken.
A 165mm (air/flue gas duct Æ 60/100mm)
246mm (air/flue gas duct Æ 80/125mm)
B 180mm
C 5mm; optimum approx. 50mm
500mm in front of the boiler to enable easy access for
servicing (may be provided by an opening door).
Clearance at the side is not required, but the side sections
can also be removed if there is adequate side clearance (at
least approx. 50mm) in order to facilitate maintenance or
repair work (¬section.4.8).
It is not necessary to ensure sufficient clearance between
the boiler and combustible materials or components as the
temperature of the boiler will always be less than the maximum permissible temperature of 85 °C due to its nominal
heat output.
4.4.2 Using installation templates
An installation template is supplied with the boiler to aid
wall mounting.
The template shows the following:
16Installation and maintenance instructions ecoTEC plus 0020116700_01
– The position of the fixing holes for the hanging bracket.
– The position of the connections.
– The position of the wall breakthrough of the air/flue gas
duct.
Position the installation template vertically over the installation site.
> Attach the template to the wall, using tacks for example.> Mark the drill holes for the hanging bracket on the wall.> If necessary, mark the position for the wall breakthrough
for the air/flue gas duct.
> Remove the installation template from the wall.> Drill 2 holes > If necessary, cut the wall breakthrough for the air/flue
gas duct.
Æ 10mm for the hanging bracket in the wall.
Installation
4
Installation and maintenance instructions ecoTEC plus 0020116700_01 17
Installation
4
4.5 Dimension drawing and connection
measurements
440
1
A
2
720
624
3
4
5
6
7
20
3535
345
6
8
125
11
7
B
180
125
100100
4.4 Connection measurements inmm
Key
1 Wall breakthrough for air/flue gas duct
2 Hanging bracket
3 Heating flow (22x1.5)
4 Hot water connection (15x1.5), only for VUW boilers
5 Gas connection (15x1.5; ecoTEC 837: 22x1.5)
6 Cold water connection (15x1.5), only for VUW boilers
7 Heating return (22x1.5)
8 Air/flue gas duct connection
9 Condensate siphon
10 Condensate discharge connection, Ø 19mm
11 Heating expansion relief valve discharge pipe connection,
Ø 15mm
Minimum dimension from wall bracket to
center line of air/flue gas duct wall breakthrough
60/100 with elbow 87°, PP175
80/125 with elbow 87°, PP223
4.4 Dimension A for air/flue gas duct wall breakthrough with
4.5 Dimension B for installation depth on VU and VUW boilers
Dimension B
[mm]
335
403
18Installation and maintenance instructions ecoTEC plus 0020116700_01
4Installation
4.6 Wall-mounting the boiler
Danger!
Risk of death if the load-bearing capacity
a
of the fixing elements used is insufficient!
If the fixing elements or wall do not have
sufficient load-bearing capacity, the boiler
can come loose and fall down. This may
also cause leaks in the gas line, which is
potentially fatal.
> When fitting the boiler, ensure that the
fixing elements and the wall have a sufficient load-bearing capacity.
> Check the quality of the wall.
1
4.7 Removing/fitting the front casing
2
1
4.6 Removing the front casing
2
3
4.5 Wall-mounting the boiler
> Mount the hanging bracket (1) on the wall using the wall
plugs and screws (2) provided with the unit.
> Hang the boiler (3) on the hanging bracket from above
using the hanging bracket.
Removing the front casing
> Loosen the screws (1) on the bottom of the boiler using a
screwdriver.
> Push in both retaining clips (2) on the bottom of the
boiler so that the front casing is released.
> Pull the front casing forwards using the bottom edge.> Lift the front casing upwards from the bracket.
Fitting the front casing
> Place the front casing on the upper brackets.> Push the front casing onto the boiler so that until both
retaining clips (2) snap into place at the front casing.
> Fasten the front casing by screwing in the bolt (1) on the
underside of the boiler.
Installation and maintenance instructions ecoTEC plus 0020116700_01 19
Installation
4
4.8 Removing/fitting the side section
You can also remove a side section for installation or maintenance purposes.
Caution.
Risk of damage caused by mechanical
b
tension.
Removing both side sections may cause
mechanical distortion in the boiler, which
can cause damage to the piping and potentially result in leaks.
> Always only remove one side section,
never both side sections at the same
time.
2.
> Unhook the restrictor strap (1.) of the electronics box at
the required side.
> Unscrew the two screws (2.) from the top and bottom of
the side section.
> Hold onto the side section (3.) when doing this.> Swivel the side section outwards and remove it from
below by pulling it downwards (4.).
3.
4.
4.7 Removing/fitting the side section
Caution
Risk of damage to the side section.
b
Unscrewed side sections that are merely
suspended from the back wall can fall
down.
> Hold onto the side section when you are
unscrewing it, and always remove it from
the boiler.
1.
20Installation and maintenance instructions ecoTEC plus 0020116700_01
Gas installation
5
5 Gas installation
The work described in this section must only be carried out
by a competent person.
5.1 Preparing for installation
Danger!
Risk of death from incorrectly installed
a
a
b
gas system!
An incorrect gas installation can result in
leaks and an explosion.
> During installation, the legal directives
and the local regulations for gas supply
companies must be observed.
Danger!
Risk of death from incorrectly installed
gas system!
Tension in the gas line can result in leaks or
an explosion.
> Make sure there are no stresses in the
gas lines when it is installed.
Caution.
Risk of damage caused by incorrect gas
installation.
Excess test pressure or operating pressure
can cause damage to the gas valve.
> When the entire gas installation is tested
for leaks, the maximum pressure at the
gas valve must not exceed 0.75kPa
(75mbar).
5.2 Connecting the gas pipe
1
5
6
7
5.1 Fitting the gas connection (example: VUW boiler)
> Make the gas connection as shown.
2
3
4
Caution.
Risk of damage caused by contaminated
b
b
Installation and maintenance instructions ecoTEC plus 0020116700_01 21
lines.
Foreign bodies such as welding remnants.
sealing residue or dirt in the connection
lines for gas can cause damage to the
boiler.
> Blow the gas line clean prior to installa-
tion.
Caution.
Risk of damage caused by using the
wrong gas group.
Using the wrong gas group can cause a
fault shutdown on the boiler. Furthermore,
ignition and combustion noise may occur in
the boiler.
> Only use propane gas for propane-fired
boilers in accordance with DIN51622.
Hydraulic installation
6
6 Hydraulic installation
The work described in this section must only be carried out
by a competent person.
6.1 Preparing for installation
Danger!
Risk of death caused by an incorrectly
a
b
b
a
installed system!
Heating water that leaks from the discharge
pipe of the expansion relief valve can cause
severe burns.
> Install the expansion relief valve and its
discharge pipe work termination ensuring that there is no danger to persons in
or about the building. This may be outside or to a suitable open drain in the
installation room.
> Make sure that the drain is visible.
Caution.
Risk of damage caused by contaminated
lines.
Foreign bodies such as welding remnants,
sealing residue or dirt in the water lines can
cause damage to the boiler.
> Flush the heating installation thoroughly
prior to installation.
Caution.
Risk of damage from corrosion.
If non-diffusion-tight plastic pipes are used
in the heating installation, this may cause
air to enter the heating water and corrosion
of the heat generator circuit and the boiler.
> If using non-diffusion-tight plastic pipes
in the heating installation, separate the
system by installing an external heat
exchanger between the boiler and the
heating installation.
Danger!
Risk of scalding and/or damage due to
incorrect installation leading to leaking
water.
Stresses in the supply line can cause leaks.
> Make sure there are no stresses in the
supply lines when they are installed.
Caution.
Risk of damage caused by heat transfer
b
i
The Vaillant ecoTEC boiler is equipped with a 10 l expansion
vessel with a gas-side filling pressure of 0.075MPa
(0.75 bar), which is suitable for a closed heating system
with a maximum water volume of 100litres.
> Before installing the boiler, check whether the volume of
the installed expansion tank is sufficient.
> If the volume of the expansion vessel is insufficient, then
install an additional expansion vessel connected as close
to the boiler as possible into the boiler return pipe.
i
Initial system pressure (in bar)1.01.5
Expansion relief valve setting
(inMPa (bar))
With system volumes greater than 100l,
multiply the volume by the adjacent factor.
6.1 Size of an additional expansion vessel
when soldering.
Heat that is transferred during soldering
can cause damage to the seals in the service valves.
> Do not solder the connection pieces if
the connection pieces are screwed to the
service valves.
Seals made of rubber-like materials may be sub-
ject to plastic deformation, which can lead to
pressure losses. We recommend using seals
made of a paste-like fibre material.
When using an external expansion vessel
together with a VUW boiler, it is advisable to
install a non-return valve in the outlet (boiler
flow) or take the internal expansion vessel out of
service.
Otherwise, the warm start function may be more
frequently activated because of backflow, which
causes unnecessary energy loss.
Vessel volume (in l)
0.3 (3.0)
0.1090.156
22Installation and maintenance instructions ecoTEC plus 0020116700_01
Hydraulic installation
6
6.2 Connecting the hot and cold water
(VUWboiler)
7
6
1
2
3
4
5
6.1 Fitting the hot and cold water connection
> Make the water connections as shown.
6.3 Connecting the domestic hot water cylinder
> Make the water connections as shown.
6.4.2 VU boiler
2
3
4
5
6.3 Fitting the heating flow and heating return (VU boiler)
> Make the water connections as shown.
1
> When connecting the domestic hot water cylinder to the
ecoTEC plus, follow the installation instructions for the
domestic hot water cylinder.
6.4 Connecting the heating flow and heating
return
6.4.1 VUW boiler
13
1112
10
9
8
7
6
6.2 Fitting the heating flow and heating return (VUW boiler)
5
1
2
3
4
6.5 Low loss header
A low loss header disconnects the boiler from the heating
system. The system is no longer dependent on the remaining feed head of the boiler. In conjunction with the boiler
circulation pump, the low loss header ensures that a sufficiently high minimum quantity of water is always circulating
through the boiler. No electrical accessories are required in
order to use a low loss header.
6.6 Connecting the condensate discharge
pipework
Danger!
Risk of death from flue gases!
a
An empty or insufficiently filled condensate
water siphon can generate flue gas in the
room air.
> Make sure that the condensate water
siphon is filled with water when switching
on the boiler.
The ecoTEC plus boilers are equipped with a condensate
siphon. (The filling height is 145mm). The siphon collects
the condensate that has formed in a vessel with a capacity
of approx. 200 ml, and intermittently deposits the contents
Installation and maintenance instructions ecoTEC plus 0020116700_01 23
Hydraulic installation
6
to the discharge pipe. This minimises the risk of the discharge pipe freezing up.
11
2
3
4
a
3
Internal
stackpipe
6.4 Condensate discharge pipework
> Connect the condensate discharge (1) of the boiler to a
condensate discharge pipework (3) which has a minimum
internal diameter of 19mm (22mm outside diameter for
all external pipes) and is made from an acid-resistant
material (e.g. plastic overflow pipe).
b
3
Internal
discharge system
c
6
5
Gulley
d
7
Soakaway
6.7 Connecting the discharge pipe to the
expansion relief valve on the boiler
The expansion relief valve for the heating installation is
integrated in the boiler.
> Install the discharge pipe for the expansion relief valve
so that it does not interfere with the removal and fitting
of the siphon trap.
We recommend not to shorten the discharge
pipe supplied.
i
> Leave an installation space of at least 180mm beneath
the condensate siphon.
min.
180
1
2
3
The condensate discharge pipework must have a
continuous fall (45mm per metre) and should
i
> During installation remove all burs from inside of cut
pipe work and avoid excessive adhesive which may trap
small pockets of water close to the pipe wall which can
freeze and build into a larger ice plug.
> As with other pipe work insulate the condensate dis-
charge pipe to minimise any risk of freezing and beware
when crossing cavities that the fall is maintained and the
pipe sleeved.
> The condensate discharge pipework must terminate in a
suitable location.
Further information can be obtained from "BS 6798 Specification for installation of gas–fired boilers of rated input not
exceeding 70 kW net". The condensate siphon (2) must be
filled with water as described in the relevant section before
the boiler is commissioned.
whenever possible terminate at a suitable discharge point within the heated envelope of the
building that will remain frost free under long
periods of low external temperatures.
6.5 Fitting the discharge pipe to the expansion relief valve
(example: VUW boiler)
> Insert a seal (1) in the cap nut (2).> Screw the discharge pipe (3) onto the expansion relief
valve.
> Make the discharge line routing as short as possible and
sloping away from the boiler.
> Allow the line to terminate in such a way that nobody
can be injured and no cable or other electrical components can be damaged if water or steam is ejected.
> Please note that the end of the line must be visible.
24Installation and maintenance instructions ecoTEC plus 0020116700_01
7 Flue gas installation
Flue gas installation
7
7.1 Air/flue gas duct
Danger!
Risk of death and risk of damage from
a
use of non-approved air/flue gas ducts!
Vaillant boilers are system-certified only in
combination with genuine Vaillant air/flue
gas ducts. The use of other accessories can
cause personal injury and material damage
as well as operating faults.
> Only use genuine Vaillant air/flue gas
ducts.
The CE mark is valid only if the appliance is operated with
Vaillant air/flue gas ducts.
All ecoTEC plus boilers feature a 60/100mm diameter air/
flue gas connection as standard. Selecting the most suitable system depends on the individual installation and application conditions.
Standard 100mm air/flue gas duct
667
87
65
74
48
542
1456
8 4
901
7.2 Scope of delivery of vertical air/flue gas duct
Article number 0020060570 and 0020065937
Optional 125mm air/flue gas duct
A concentric air/flue gas duct with an outer diameter of
125 mm is available that can be extended depending on the
boiler output range. The flues gas spigot Ø80/125 (with 2
measuring apertures) Art. No.: 0020130728 will be required.
You can also get a vertical system. For more information
refer to the ¬installation manual for the air/flue gas duct.
1020
51
70
30
7.1 Scope of delivery of horizontal air/flue gas duct
Article number 303933
A concentric air/flue gas duct with an outer diameter of
100mm that can be extended depending on the boiler output range is available.
You can also get a vertical system. For more information
refer to the ¬installation manual for the air/flue gas duct. 87° elbows and 45° elbows are also available for
greater flexibility during installation.
07
7.3 Scope of delivery of horizontal air/flue gas duct
Article number 303209
1430
70
7.4 Scope of delivery of vertical air/flue gas duct
Article number 303200
Installation and maintenance instructions ecoTEC plus 0020116700_01 25
Flue gas installation
7
7.2 Flue termination
The following details refer to all flue systems.
a. The terminal must be positioned such that the prod-
ucts of combustion can disperse freely at all times.
b. A plume of water vapour will sometimes be visible
from the flue terminal. Positions where this could be a
nuisance should be avoided.
c. If the terminal is fitted less than 2m above a balcony,
above ground or above a flat roof to which people
have access then a suitable terminal guard must be
provided and fitted (contact Tower Flue Components,
Tonbridge, TN9 1TB).
Vertical flues must not terminate within 600mm
of an openable window, air vent or any other
i
The flue system shall be so placed or shielded as to prevent
ignition or damage to any part of the building.
ventilation terminal.
P
I
F
J
7.5 Termination of the air/flue gas duct
L
Q
B
G
Q
D, E
C
A
I
I
O
H
H
MM
N
Q
N
K
26Installation and maintenance instructions ecoTEC plus 0020116700_01
Flue gas installation
7
Location
Directly below an opening, air brick, opening win-
A
dows, etc.
B Above an opening, air brick, opening window, etc. 300mm
Horizontally to an opening, air brick, opening win-
C
dow, etc.
Below temperature-sensitive building components
D
e.g. plastic gutters, soil pipes or drain pipes
E Below eaves200mm
F Below balconies or car port roof200mm
G From a vertical drain pipe or soil pipe150mm
H From an internal or external corner200mm
I Above ground, roof or balcony level300mm
J From a surface facing the terminal600mm
K From a terminal facing the terminal1200mm
From an opening in the car port (e.g. door, win-
L
dow) into the dwelling
M Vertically from a terminal on the same wall1500mm
N Horizontally from a terminal on the same wall300mm
O From the wall on which the terminal is mountedN/A
P From a vertical structure on the roofN/A
Q Above intersection with roof300mm
7.1 Position of the termination in a fan-assisted air/flue gas
duct
Minimum
dimensions
300mm
300mm
75 mm
1200mm
BS5440–1 It is recommended that the fanned flue terminal
should be positioned as follows:
a) at least 2 m from an opening in the building directly
opposite, and
b) so that the products of combustion are not straightly
directed to discharge across a boundary.
1) Dimensions D, E and F:
These clearances may be reduced to 25mm without
affecting the performance of the boiler. In order to
ensure that the condensate plume does not affect
adjacent surfaces the terminal should be extended as
shown in ¬fig.7.6.
2) Dimension H:
This clearance may be reduced to 25mm without
affecting the performance of the boiler. However, in
order to ensure that the condensate plume does not
affect adjacent surfaces a clearance of 300mm is preferred. For IE, recommendations are given in the cur-
rent edition of IS813.
For 1 and 2 above you can use the Variable Termination Kit
to move the termination point away from the building fabric.
Article numbers:
0020060584 - White
0020060585 - Black
7.6 Termination of air/flue gas duct under balcony or eaves
Installation and maintenance instructions ecoTEC plus 0020116700_01 27
Electrical installation
8
8 Electrical installation
8.1 Preparing for installation
Danger!
Risk of death from electric shock!
e
e
Touching live connections can cause serious personal injury.
> Switch off the power supply.> Secure the power supply against being
switched on again.
Danger!
Risk of electrocution as a result of an
improper electrical connection!
An improper electrical connection may negatively affect the operational safety of the
boiler and result in material damage or personal injury.
> The electrical connection must be car-
ried out by a suitably qualified competent person who is responsible for complying with the existing standards and
guidelines.
> Connect the boiler in accordance with
BS7671 (IEE Regulations).
> For IE: Please observe the latest edition
of the ETCI regulations (Electro-Technical
Council for Ireland).
> Earth the boiler.
3
4
8.1 Opening the back wall of the electronics box
> Fold the electronics box (1) forwards.> Undo the 4 clips of the rear cover (2) of the electronics
box from the brackets (3) at the rear and sides of the
electronics box.
> Fold up the cover.
Closing the electronics box
> Close the rear panel on the electronics box.> Push in the panel until it clicks into place in the clips.> Fold up the electronics box.> Push the right and left clips of the box against the side
panels on the boiler until they click into place.
> Replace the front casing on the boiler
(¬section4.7).
1
2
8.3 Establishing the mains connection
8.2 Opening/closing the electronics box
Danger!
Opening the electronics box
> Remove the front casing from the boiler
(¬section4.7).
e
b
28Installation and maintenance instructions ecoTEC plus 0020116700_01
Risk of death from electric shock!
Mains connection terminals L and N remain
live even if the continuous on/off switch is
turned off!
> Before establishing a mains connection,
switch off the power supply.
Caution.
Risk of damage from erroneous connected voltage.
At mains voltages greater than 253V and
less than 190V, the functions may be
impaired.
> Make sure that the rated voltage of the
mains is 230 V.
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.