Vaillant aroCOLLECT VWL 11/4 SA Installation And Maintenance Instructions Manual

Page 1
For the competent person
Installation and maintenance instructions
aroCOLLECT
VWL 11/4 SA
GB
Installation and maintenance instructions
Publisher/manufacturer Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18‑0 Fax +49 21 91 18‑2810 info@vaillant.de www.vaillant.de
Page 2
Contents
2 Installation and maintenance instructions aroCOLLECT 0020217119_01
Contents
1 Safety .................................................................... 3
1.1 Action-related warnings ......................................... 3
1.2 Intended use.......................................................... 3
1.3 General safety information .................................... 3
1.4 Regulations (directives, laws, standards) .............. 4
2 Notes on the documentation .............................. 6
2.1 Observing other applicable documents ................. 6
2.2 Storing documents................................................. 6
2.3 Applicability of the instructions .............................. 6
3 System overview.................................................. 6
3.1 Heat pump system design ..................................... 6
4 Product description............................................. 6
4.1 Information on the identification plate.................... 6
4.2 CE label ................................................................. 6
4.3 Product design....................................................... 7
5 Installation............................................................ 7
5.1 Checking the scope of delivery.............................. 7
5.2 Removing the transport locks ................................ 7
5.3 Selecting the installation site ................................. 8
5.4 Dimensions............................................................ 9
5.5 Minimum clearances.............................................. 9
5.6 Creating the foundation ....................................... 11
5.7 Hydraulics installation.......................................... 12
5.8 Filling and purging the brine circuit ...................... 14
5.9 Electrical installation ............................................ 17
6 Start-up ............................................................... 20
6.1 Start-up ................................................................ 20
6.2 Handing the product over to the operator............ 20
7 Inspection and maintenance ............................ 20
7.1 Inspection and maintenance interval ................... 20
7.2 Carrying out inspection and maintenance
work ..................................................................... 21
7.3 Procuring spare parts .......................................... 21
7.4 Cleaning the product............................................ 21
7.5 Cleaning the condensate discharge .................... 21
8 Decommissioning.............................................. 21
8.1 Temporary decommissioning .............................. 21
8.2 Permanently decommissioning............................ 21
9 Customer service............................................... 21
10 Recycling and disposal..................................... 21
Appendix ............................................................................ 22
A Product diagram ................................................ 22
A.1 Product diagram .................................................. 22
B Connection diagram .......................................... 23
C Technical data.................................................... 24
C.1 General................................................................ 24
C.2 Air heat source..................................................... 26
Index ................................................................................... 29
Page 3
Safety 1
0020217119_01 aroCOLLECT Installation and maintenance instructions 3
1 Safety
1.1 Action-related warnings
Classification of action-related warnings
The action-related warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words:
Warning symbols and signal words
Danger!
Imminent danger to life or risk of severe personal injury
Danger!
Risk of death from electric shock
Warning.
Risk of minor personal injury
Caution.
Risk of material or environmental damage
1.2 Intended use
There is a risk of injury or death to the user or others, or of damage to the product and other property in the event of improper use or use for which it is not intended.
The product is intended exclusively for do­mestic use as an air/brine collector to be connected to the VWF xx1/4, VWF xx2/4, VWF xx7/4, VWF xx7/4 S1 or VWF xx8/4 heat pumps. Operating the heat pump in con­junction with the air/brine collector and out­side the application limits results in the heat pump being switched off by the internal con­trol and safety devices.
Intended use includes the following:
– observance of accompanying operating,
installation and servicing instructions for the product and any other system compon­ents
– installing and fitting the product in accord-
ance with the product and system approval
– compliance with all inspection and main-
tenance conditions listed in the instruc­tions.
Intended use also covers installation in ac­cordance with the IP class.
Any other use that is not specified in these instructions, or use beyond that specified in
this document shall be considered improper use. Any direct commercial or industrial use is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
1.3 General safety information
1.3.1 Risk caused by inadequate qualifications
The following work must only be carried out by competent persons who are sufficiently qualified to do so:
InstallationDisassemblyInstallationStart-upMaintenanceRepairDecommissioning
Observe all instructions that are included
with the product.
Proceed in accordance with the current
state of technology.
Observe all applicable directives, stand-
ards, laws and other regulations.
1.3.2 Danger caused by improper operation
Improper operation may present a danger to you and others, and cause material damage.
Carefully read the enclosed instructions
and all other applicable documents, par­ticularly the "Safety" section and the warn­ings.
Only carry out the activities for which in-
structions are provided in these operating instructions.
1.3.3 Risk of death due to lack of safety devices
The schematic drawings included in this doc­ument do not show all safety devices re­quired for correct installation.
Install the necessary safety devices in the
system.
Observe the applicable national and inter-
national laws, standards and guidelines.
Page 4
1 Safety
4 Installation and maintenance instructions aroCOLLECT 0020217119_01
1.3.4 Risk of death from electric shock
There is a risk of death from electric shock if you touch live components.
Before commencing work on the product:
Disconnect the product from the power
supply by switching off all power supplies (electrical partition with a contact opening of at least 3 mm, e.g. fuse or line protec­tion switch).
Secure against being switched back on
again.
Wait for at least 3 minutes until the capa-
citors have discharged.
Check that there is no voltage.
1.3.5 Risk of injury due to chemical burns caused by brine fluid
The brine fluid ethylene glycol is harmful to health.
Avoid contact with the skin and eyes.Always wear gloves and protective
goggles.
Do not inhale or swallow.Observe the safety data sheet that accom-
panies the brine fluid.
1.3.6 Risk of burns due to hot and cold components
There is a risk of burns and frostbite from any uninsulated pipelines and from the auxiliary electric heating.
Only carry out work on the components
once they have reached ambient temperat­ure.
1.3.7 Risk of death due to changes to the product or the product environment
Never remove, bridge or block the safety
devices.
Do not alter the safety devices in any way.Do not damage or remove any seals on
components. Only authorised competent persons or customer services may modify sealed components.
Do not make any changes to:
The product itselfThe product environmentThe brine fluid, air and current supply
lines
– The drain line and expansion relief valve
for the heat source circuit
– to constructional conditions that may
affect the operational reliability of the product
1.3.8 Material damage due to unsuitable installation surface
The installation surface must be even and have sufficient load-bearing capacity to sup­port the operating weight of the product. An uneven installation surface may cause leaks in the product.
If the installation surface does not have suffi­cient load-bearing capacity, the product may topple.
There is a risk of death if the connections are subject to leaks.
Make sure that the product is positioned
flush against the installation surface.
Ensure that the installation surface has
sufficient load-bearing capacity to bear the operating weight of the product.
1.3.9 Risk of injury during transport due to a high product weight
Make sure that the product is transported
by at least two people.
1.3.10 Risk of material damage caused by
using an unsuitable tool
Use the correct tool to tighten or loosen
screw connections.
1.4 Regulations (directives, laws, standards)
When setting up, installing and operating the heat pump and the domestic hot water cylin­der, you must observe the following points in particular:
– Local specifications, regulations, rules and
directives regarding electrical connections
– Local specifications, regulations, rules and
directives for the power company
– Local specifications, regulations, rules and
directives for the water supply company
– Local specifications, regulations, rules and
directives regarding the use of geothermal energy
Page 5
Safety 1
0020217119_01 aroCOLLECT Installation and maintenance instructions 5
– Local specifications, regulations, rules and
directives regarding the integration of heat source systems and heating installations
– Local specifications, regulations, rules and
directives regarding saving energy
– Local specifications, regulations, rules and
directives regarding hygiene
Page 6
2 Notes on the documentation
6 Installation and maintenance instructions aroCOLLECT 0020217119_01
2 Notes on the documentation
2.1 Observing other applicable documents
You must observe all the operating and installation in-
structions included with the system components.
2.2 Storing documents
Pass these instructions and all other applicable docu-
ments on to the system operator.
2.3 Applicability of the instructions
These instructions apply only to:
Product
VWL 11/4 SA
3 System overview
3.1 Heat pump system design
5 - 11 kW
15 - 19 kW
The heat pump system consists of the following components, as a minimum:
Air/brine collector(s)Heat pumpSystem controller
The heat pump system generates heat in heating installa­tions and in hot water generation by extracting the thermal energy from a heat source circuit and releasing this into the heating circuit via the internal refrigeration circuit. At the same time, there is an opportunity for active cooling to take place via circulation reversal. For this, the heat pump is con­nected to the air/brine collector(s). The air/brine collector is used to exchange heat between the brine circuit and the out­side air.
4 Product description
4.1 Information on the identification plate
The identification plate is attached at the factory to the un­derside of the electronics box.
Information on the identi­fication plate
Meaning
Rated voltage and frequency of the fan, controller and de-icer
P max Maximum rated power
Rated power of the fan and controller
De-icer rated power
A2/W35
Rated power and pressure of the air/brine collector at an air inlet temperature of 2 °C and a heating flow temperature of 35 °C
IP Level of protection
Verband deutscher Elektrotech­niker (German Association for Electrical, Electronic & Informa­tion Technologies)
Electromagnetic Compatibility in accordance with the Verband deutscher Elektrotechniker
Read the instructions.
Bar code with serial number,
7th to 16th digit = product article number
4.2 CE label
The CE label shows that the products comply with the basic requirements of the applicable directives as stated on the identification plate.
The declaration of conformity can be viewed at the manufac­turer's site.
Page 7
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 7
4.3 Product design
4.3.1 Front view, closed
1
1 Type designation with
serial number
4.3.2 Front view, open
12
11
3
6
2
1
8
9
4
5
10
7
1 Purging valves
2 Simple identification
plate
3 Electronics box
4 De-icer
5 Connection box
6 Identification plate with
service sticker
7 Warning sticker
8 Connecting the brine
line to the heat pump (hot brine)
9 Connecting the brine
line from the heat pump (cold brine)
10 Base (accessory)
11 Condensate tray
12 Ventilator
5 Installation
5.1 Checking the scope of delivery
1. Carefully remove the packaging and padding without damaging the parts of the product.
2. Check that the scope of delivery is complete.
Quantity Description
1 Box: Cover and side sections of the casing
2 Louvred grill (pre-installed)
1 Air/brine collector
1 Installation material:
2 x O-ring seals10 x M8x20 screws (to secure the cover,
the side casing and the air/brine collector to the base (accessories))
1 Enclosed documentation
5.2 Removing the transport locks
2 x
Remove the transport locks as shown in the illustration.
Page 8
5 Installation
8 Installation and maintenance instructions aroCOLLECT 0020217119_01
5.3 Selecting the installation site
Caution. Risk of material damage caused by corro-
sion.
Caustic vapours may cause corrosion dam­age on the product. The extracted air must be free from ammonia, methane gas and other corrosive elements.
Do not install the product close to stables
and manure pits.
Set up the product outdoors away from rooms. Depend-
ing on the weather, condensate may form and appear under the collector.
– Maximum installation height: 2000 m above normal
sea level
Ensure that there is a sufficiently stable, frost-proof, hori-
zontal foundation that meets local requirements and com­plies with the rules of structural engineering.
For efficiency reasons, the clearance between the heat
pump and the air/brine collector should be kept as small as possible.
– Total length of the connection line, cold brine and hot
brine: 2 x 30 m
If the clearance between the product and the building
falls below 3 m, position the product in such a way that the outlet side does not point towards the building.
Assess the installation site to ensure that no persons can
be at risk at the outlet side. No public roads/pathways should run through the area of the outlet side.
Install the product with the intake side towards the wall
(recommended installation).
Comply with the local and statutory minimum clearances
with regards to:
VegetationWallsAwningsOpen fire or embersChildren's toys
When selecting the installation site, take into consider-
ation the fact that, during full load mode in winter, noise (depending on the current output requirement, up to ap­prox. 66 dB(A) sound power level) is emitted from the product, and this noise may be amplified by reverberative surfaces.
Observe the national regulations regarding noise.
Sound propagation form: Hemisphere
Sound propagation with a free-standing air/brine collector.
Sound propagation form: Quarter-sphere
Sound propagation for the adjacent building: On just one side.
Page 9
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 9
Sound propagation form: An eighth of a sphere
Sound propagation for the adjacent building: On two sides and at a right-angle.
LWA= L
PFA
– 10 lg S
LWA= Sound pressure level (dB(A))
L
PFA
= Sound power level (dB(A))
S = Sound propagation form* (clearance from the product in m)²
Sound propagation form: Hemisphere = 6.28
Sound propagation form: Quarter-sphere = 3.14
Sound propagation form: Eighth of a sphere = 1.57
Example
L
PFA
= 54 dB(A), max. sound power level without noise re-
duction
Sound propagation form = Hemisphere = 6.28
Distance to the product = 10 m
LWA= 54 dB(A) – 10 lg (6.28 * 100)
LWA= 54 dB(A) – 10 lg (628)
LWA= 54 dB(A) – 28
LWA= 26 dB(A)
Choose the installation site so that the legally required
emissions values for noise outside of buildings can be complied with, without having to use the heat pump sys­tem's noise reduction function, if possible.
In certain weather conditions, take into consideration
the possibility of black ice forming directly in front of the product's outlet side; if condensate escapes, the black ice may form all around the product.
5.4 Dimensions
1192
785
1256
1162
5.5 Minimum clearances
≥ 0,3 m
≥ 0,5 m
≥ 0,5 m
≥ 3 m
ca. 0,5 m
≥ 0,5 m
< +5 °C
Clearances that must be complied with for an air/brine col­lector
Page 10
5 Installation
10 Installation and maintenance instructions aroCOLLECT 0020217119_01
ca. 0,5 m
≥ 0,3 m
≥ 0,5 m
≥ 0,5 m ≤ 5 m
≥ 3 m
≥ 0,5 m
< +5 °C
< +5 °C
0,5 m
Clearances that must be complied with for two air/brine col­lectors
Positioning of the collectors
Use the mounting base, which is available as an access-
ory, for the installation.
To guarantee sufficient air flow and to facilitate mainten-
ance work, observe the minimum clearances that are specified above.
Ensure that there is sufficient room to install the hydraulic
lines.
If the product is to be installed in areas where heavy
snow falls, ensure that the snow does not accumulate around the product and that the minimum clearances specified above are observed. If you cannot ensure this, install an additional heat generator in the heating circuit. An elevating base and condensate tray heating are avail­able as accessories.
Page 11
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 11
If you install two air/brine collectors, you must create a
concrete foundation and use the connection pipe set that is available as an accessory.
5.6 Creating the foundation
³ 0,8 m
1
3
5
2
4
6
1 Air/brine collector
2 Foundation
3 Compacted gravel
4 Ground
5 Condensate drain pipe
6 Gravel bed in a frost-
free area
1. Prepare the ground for the foundation in accordance with the illustration.
2. As a condensate drain pipe, route a pipe that drops vertically and that is DN 110. Route this pipe as far as the frost-free ground. To lay the pipe at ground level and so that it comes out of the mounting base at the side, use the accessory that is available for this.
A
A
B
B
Ø 12
120 x=cm
34 18
62
52
49
41
Ø 5
14
Ø 7
8
18
110
60
23
15
13
10
26
Ø 7
A Connecting the air/brine
collector to the heat pump (hot brine)
B Connecting the heat
pump to the air/brine collector (cold brine)
3. Create a frost-free and stable foundation or set the product on paving slabs. When doing so, observe the rules of structural engineering and the instructions that are enclosed with the recommended VWL S installation set for PE pipes.
³ 0,8 m
DN 110
4. Establish the connections for a foundation made of pav­ing slabs in accordance with the illustration.
Page 12
5 Installation
12 Installation and maintenance instructions aroCOLLECT 0020217119_01
DN 110
³ 0,8 m
5. Establish the connections for a concrete foundation in accordance with the illustration.
6. Install the base that is available as an accessory.
5.7 Hydraulics installation
5.7.1 Routing the connection lines
Caution. Risk of material damage caused by
ground lifting up as a result of frozen ground.
At operating temperatures close to freezing level, the ground in the area of the PE pipes may freeze and therefore damage the struc­ture as a result of the ground lifting up.
Insulate all of the PE lines that are to be
routed under buildings, terraces, path­ways, etc. so that they are vapour-diffu­sion-tight.
If possible, route PE pipes in the ground
with a clearance of 70 cm from each other and from adjacent supply lines (except for electrical lines).
The total length (connection lines from the heat pump to the product and from the product to the heat pump) must be no greater than 60 m.
Keep the clearance between the product and the heat
pump as short as possible and minimise the use of el­bows and angles. This is because each additional pres­sure loss that is caused by the use of these reduces effi­ciency.
Route the PE pipes in accordance with the applicable
technical directives.
For a total line length of between 20 m and 60 m, use
a PE pipe with DN 50 (e.g. PE 80/100, outer diameter 50 mm, wall thickness 4.6 mm). Up to a total line length of 20 m, you can also use a PE pipe with DN 40 (e.g. PE 80/100, outer diameter 40 mm, wall thickness
3.7 mm).
When using more than eight PE elbows, use an extra
2 m of pipeline for each elbow.
When using copper pipes, use only copper pipes that
have a cross-section of 35 mm. If you use a smaller cross-section (e.g. copper 28 mm), this will result in pres­sure losses (2 m copper 28 = 8 m copper 35).
Note
If the prescribed line cross-sections are not complied with, this results in efficiency losses and reduced annual operating figures.
If required, when routing the PE pipes above-ground,
ensure that they are protected against UV radiation.
Conditions: Installing two air/brine collectors
Page 13
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 13
≤ 10m DN 40* > 10m ≤ 30m DN 50*
A
B
A
B
* = one way
Connect the air/brine collector in accordance with the
Tichelmann principle. This means that the air/brine col­lector with the shorter flow has the longest return.
Caution. Risk of material damage caused by a leak.
When tightening screwed connections, ensure that O-rings are inserted correctly as, otherwise, they may pop out or become jammed, become damaged, or cause leaks.
Insert the O-rings properly and untwisted
into the cap nuts for the air/brine collect­or's brine connections.
Screw the cap nuts to the connection adaptors on the
"hot brine" and "cold brine" brine lines in the brine circuit (cross-reference) on the mounting base.
To purge each individual air/brine collector, install
two shut-off units.
5.7.2 Transporting the product
Caution. Risk of material damage caused by incor-
rect transport.
Do not transport the product using a hand
truck.
If required, remove the louvred grill to prevent damage.
5.7.3 Installing the product
1. Place the product on the base that is available as an accessory.
2. Connect the brine lines to the product as shown.
3. Screw the product to the base.
5.7.4 Installing brine lines in the building
71
42a
65
48
64
56
62
61
63
70
72
A
B
A
B
≤ 10m DN 40* > 10m ≤ 30m DN 50*
42a Expansion relief valve
48 Pressure gauge
56 Heat pumps for brine
filling unit (accessory)
61 Stop valve
62 Stop valve
63 Stop valve
64 Stop valve
65 Brine collecting con-
tainer
70 Stop valve
71 Brine diaphragm expan-
sion tank
72 Stop valve
Page 14
5 Installation
14 Installation and maintenance instructions aroCOLLECT 0020217119_01
A From the heat source
to the heat pump (hot brine)
B From the heat pump to
the heat source (cold brine)
* One way
1. Install the brine lines between the product and the heat pump within the building and using all of the associated components in accordance with the applicable technical directives.
Note
Do not install dirt filters in the brine circuit for a prolonged period of time. The brine fluid is cleaned during the filling process.
2. Reduce the pre-charge pressure of the brine diaphragm expansion tank (which is available as an accessory) from 0.25 MPa (2.5 bar) to 0.10 MPa (1.0 bar).
3. Insulate all of the brine lines and the connections for the heat pump and product so that they are vapour­diffusion-tight.
Note
Vaillant recommends that you install the Vaillant heat pump brine filling unit. By do­ing this, it is then possible to carry out a pre­paratory partial bleed of the brine circuit, e. g. the flow and return of the brine circuit to the product.
5.8 Filling and purging the brine circuit
5.8.1 Calculating the required volume of brine
fluid
Use the information in the following table to calculate the
required volume of brine fluid.
Plan an allowance of 10 l for the calculated volume in
order to facilitate the rinsing process.
Label the vessel for the remaining volume with informa-
tion about the type and concentration of brine fluid and, after start-up, pass the vessel on to the operator so that they have brine fluid available for when the tank needs to be topped up.
Brine fluid volume in the product in litres (± 1 litre)
Total
VWF 5x/4 + VWL 11/4 SA 2.5 + 19 21.5
VWF 57/4 S1 + VWL 11/4 SA 2.5 + 19 21.5
VWF 8x/4 + VWL 11/4 SA 3.1 + 19 22.1
VWF 87/4 S1 + VWL 11/4 SA 3.1 + 19 22.1
VWF 11x/4 + VWL 11/4 SA 3.6 + 19 22.6
VWF 117/4 S1 + VWL 11/4 SA 3.6 + 19 22.6
VWF 157/4 + 2x VWL 11/4 SA 4.5 + 38 42.5
VWF 157/4 S1 + 2x VWL 11/4 SA 4.5 + 38 42.5
VWF 197/4 + 2x VWL 11/4 SA 5.3 + 38 43.3
VWF 197/4 S1 + 2x VWL 11/4 SA 5.3 + 38 43.3
Pipe type Brine fluid volume per running metre
in litres
DN 40 0,8
DN 50 1,26
Example
VWF 197/4 with VWL 11/4 SA and 60 m DN 50 PE pipe provides the following total content in litres:
5.3 + 2 x 19 + 60 x 1.26 + 10 (reserve) = 129 l.
Page 15
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 15
5.8.2 Filling the brine circuit (1 air/brine collector)
29
69
66
64
48
56
62
71
42a
63
61
33
67
65
A
B
70
72
A
B
≤ 10m DN 40* > 10m ≤ 30m DN 50*
29 Brine pump
33 Dirt filter
42a Expansion relief valve
48 Pressure gauge
56 Heat pumps for brine filling unit
61 Stop valve
62 Stop valve
63 Stop valve
64 Stop valve
65 Brine collecting container
66 Brine container
67 Filling pump
69 Purging valves
70 Stop valve
71 Brine diaphragm expansion tank
72 Stop valve
A From the heat source to the heat pump (hot brine)
B From the heat pump to the heat source (cold brine)
* One way
1. Connect the filling pump's pressure line to the stop valve (62).
2. Close stop valves (63), (70) and (72).
3. Open stop valves (62) and (64).
4. Connect a hose, which leads to the brine fluid, to the stop valve (61).
5. Open the stop valve (61).
Caution. Risk of material damage caused by an incorrect filling direction.
If you fill the brine pump against the direction of flow, this may lead to a turbine effect which can damage the pump's electronics.
Ensure that the brine pump is filled in the direction of flow.
6. Use the filling pump (67) to pour the brine fluid from the brine container (66) into the brine circuit.
5.8.3 Filling the brine circuit (two air/brine collectors)
29
66
64
48
56
62
71
42a
63
61
33
67
65
A
B
70
72
69 69
A
B
A
B
≤ 10m DN 40* > 10m ≤ 30m DN 50*
29 Brine pump 33 Dirt filter
Page 16
5 Installation
16 Installation and maintenance instructions aroCOLLECT 0020217119_01
42a Expansion relief valve
48 Pressure gauge
56 Heat pumps for brine filling unit
61 Stop valve
62 Stop valve
63 Stop valve
64 Stop valve
65 Brine collecting container
66 Brine container
67 Filling pump
69 Purging valves
70 Stop valve
71 Brine diaphragm expansion tank
72 Stop valve
A From the heat source to the heat pump (hot brine)
B From the heat pump to the heat source (cold brine)
* One way
1. Connect the filling pump's pressure line to the stop valve (62).
2. Close stop valves (63), (70) and (72).
3. Open stop valves (62) and (64).
4. Connect a hose, which leads to the brine fluid, to the stop valve (61).
5. Open the stop valve (61).
Caution. Risk of material damage caused by an incorrect filling direction.
If you fill the brine pump against the direction of flow, this may lead to a turbine effect which can damage the pump's electronics.
Ensure that the brine pump is filled in the direction of flow.
6. Use the filling pump (67) to pour the brine fluid from the brine container (66) into the brine circuit.
Page 17
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 17
5.8.4 Purge the brine circuit
1. Position a second person at the air/brine collector(s).
Note
The entire purging/filling process should last at least 30 minutes. During this time, the pur­ging valves for the air/brine collector(s) must be opened and closed every five minutes. We recommend the brine purging support set for the air/brine collector as this makes the purging process significantly easier if it is to be carried out by one person.
2. Remove the protective caps, which are attached and transparent in their as-delivered condition, from the purging valves on the air/brine collector and dispose of these. These are no longer required.
3. Open the purging valves (69) on the air/brine collector(s).
4. Start up the filling pump (67) in order to fill and rinse the brine circuit.
5. Allow the filling pump (67) to run.
6. Close the purging valves on the air/brine collector(s) as soon as brine fluid escapes from the purging valves (69).
7. If required, open all of the other stop valves that are not shown in the illustrations.
8. Open and close the purging valves (69) on the air/brine collector(s) every five minutes consistently until air is no longer escaping.
9. Open the stop valve (63) so that air in the pipeline between the stop valves (61) and (62) can escape.
10. Close the stop valve (61).
11. Build up pressure in the system, as described in the
installation instructions for the heat pump.
5.9 Electrical installation
Danger! Risk of death from electric shock caused
by a residual-current circuit breaker.
In certain cases, residual-current circuit breakers may not work.
If, to ensure that people are protected
properly and fire is prevented, residual­current circuit breakers are required, use type A pulse-current-sensitive residual­current circuit breakers or type B univer­sal-current-sensitive residual-current cir­cuit breakers.
Observe the technical connection conditions for connect-
ing to the power supply network operator's low-voltage network.
Use the values for the maximum rated power that are
specified in the technical data to determine the required line cross-sections.
In each case, take into consideration the on-site installa-
tion conditions.
Connect the product using a fixed connection and a parti-
tion with a contact opening of at least 3 mm (e.g. fuses or power switches).
For the electricity supply, connect the product to a three-
phase 400 V AC network with a neutral line and an earth line.
Fuse this connection using the exact values that are spe-
cified in the technical data.
At lengths of 10 m or more, supply lines must be laid sep-
arately from sensor or bus lines. Minimum clearance for the extra-low voltage and mains voltage line at a line length of > 10 m: 25 cm. If this is not possible, use shiel­ded lines. Lay the shielding on one side of the sheet for the product's electronics box.
80 mm max.
1
2
1 Connecting wires 2 Insulation
Strip the outer sheathing on the line to the connection
box by approximately 80 mm. Shorten all of the conduct­ors, except for PE, to 60 mm.
Secure the conductors in the connection terminals.
Max. torque of the connection terminals: 0.5 Nm
Page 18
5 Installation
18 Installation and maintenance instructions aroCOLLECT 0020217119_01
5.9.1 Switch box
L1 L 2L 3 N P E
1
2
3
4
6
7
5
1 Switch box
2 Strain relief
3 eBUS line
4 Connection box
5 Strain relief
6 Voltage supply line
7 Cable duct
5.9.2 Air/brine collector controller PCB
L3 L2 L1 N
1 2 3 4 5 6 7 8 9 10
11
12
1 Fan control signal con-
nection
2 eBUS connection
3 eBUS address switch
(default setting 1)
4 TT40 sensor connection
(pink); TT34 sensor connection (white)
5 Operating LED
6 Controller PCB power
supply
7 F1 T2 230 V fuse for
fan and safety cut-out
8 Fan voltage supply
9 Safety cut-out connec-
tion
10 De-icer connection
11 Optional 200 W connec-
tion accessory
12 F3 T2 230 V fuse for
optional connection accessory
Display Meaning
Flashing slowly OK
Display Meaning
1 x brief flash Fan fault
2 x brief flash Fault TT40 (air inlet)
3 x brief flash Fault TT34 (hot brine)
4 x brief flash
The safety cut-out has been triggered. Fuse F1 is defective.
5 x brief flash
No eBUS connection to the heat pump's controller PCB
6 x brief flash Power supply not OK (1-2 phases are
missing) or safety relay (OMU) is defect­ive
The flashing period lasts for approx. 3-4 seconds.
5.9.3 Establishing the power supply
eBUS
400 V400 V
1
1
1
1 400 V power supply
network (on-site)
Electrical wiring of one air/brine collector
eBUS
400 V
400 V
1
1
2
2
1
2
1 400 V power supply
network (on-site)
2 eBUS distributor (on-
site)
Electrical wiring of two collectors
Page 19
Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions 19
Connect each air/brine collector to a three-phase 400 V
AC network with a neutral line and an earth line.
Strip the voltage supply line by approximately 80 mm.
Shorten all of the conductors, except for PE, to 60 mm. Remove the insulation by a maximum of 8 mm. If these lengths are exceeded, there is a risk of a short circuit.
If the energy supply company requires that the heat
pump is controlled using a blocking signal, also connect the air/brine collector to the heat pump via the electricity meter so that a block by the energy supply company can be switched off for both products at the same time.
Connect the eBUS connection X3 to the eBUS connec-
tion on the heat pump. Use a ground connection that is suitable for laying cables underground and that has a cross-section of at least 2 x 1.5 mm².
Conditions: Installing two air/brine collectors
Place a junction box close to the heat pump and connect
the eBUS lines to this.
Set the eBUS address switch for the first air/brine col-
lector to 1 and the eBUS address switch for the second air/brine collector to 2.
5.9.4 Circuit breaker for the air/brine collector
A circuit breaker is used to secure the air/brine collector against short circuits. If the circuit breaker has been triggered, the air/brine collector remains switched off until the short circuit has been rectified and the circuit breaker in the connection box has been manually reset.
The fault message F.708 or F.782 is shown in the heat pump display.
5.9.5 Resetting the circuit breaker for the
air/brine collector
1. Check the supply line to the mains connection PCB in the air/brine collector's electronics box.
2. Check that the air/brine collector's mains connection PCB is working correctly.
3. Check the supply lines for the air/brine collector.
4. Check that the de-icer is working correctly.
5. Rectify the short circuit.
6. Reset the circuit breaker in the connection box.
5.9.6 Installing the side casing and cover
1
4
2
3
1
1. Arrange each of the side casing sections (1) and (4) tilted downwards on the product's frame (2) and, in do­ing so, let the nipples clip into place in the cut-outs that are provided for this.
2. Move the side casing sections to the correct, vertical position.
3. Screw each of the side casing sections tightly to the frame using two screws (3).
4. When installing the retaining bracket, you must observe the installation location as shown in the illustration.
5. Secure each of the retaining brackets to the cover using two self-cutting screws.
6. Place the cover on the product.
Page 20
6 Start-up
20 Installation and maintenance instructions aroCOLLECT 0020217119_01
7. Anchor the cover to the product by turning each screw through the slot in the retaining bracket in the frame.
6 Start-up
6.1 Start-up
1. Ensure that the heat pump and system controller are installed correctly.
2. Switch the fuses on so that the heat pump and air/brine collector(s) are supplied with power.
As soon as the heat pump is supplied with power
during the initial start-up, the software initialisation starts in the heat pump and in the system controller.
3. Implement the other settings with the help of the install­ation instructions for the heat pump and for the system controller.
6.2 Handing the product over to the operator
When you have finished the installation, affix the en-
closed sticker (which requests that the user reads the instructions) to the front of the product in the operator's language.
Explain to the operator how the safety devices work and
where they are located.
Inform the operator how to handle the product.In particular, draw attention to the safety information
which the operator must follow.
Inform the operator of the necessity to have the product
maintained according to the specified intervals.
Pass all of the instructions and documentation for the
product to the operator for safe-keeping.
7 Inspection and maintenance
7.1 Inspection and maintenance interval
Annual inspection/maintenance of the product by a compet­ent person is a prerequisite for ensuring that the system is constantly ready for operation, reliable and has a long ser­vice life.
The inspection is intended to determine the actual condition of the product and compare it with the target condition. This is done by measuring, checking and observing.
Maintenance is required in order to eliminate any deviations between the actual condition and the target condition. This is normally done by cleaning, setting and, if necessary, repla­cing individual components that are subject to wear.
Danger! Risk of death from electric shock!
The air/brine collector has its own, separate power supply and is not automatically de-en­ergised when the heat pump is disconnected from the power source.
Always switch off the power supply for
each air/brine collector before carrying out any inspection or maintenance work.
Secure the power supply against being
switched on again.
Danger! Risk of death from electric shock!
Due to electrical discharge processes, con­tact with components inside the product may cause an electric shock.
Do not open the cover for the electronics
box in the product until three minutes after the all-pole disconnection of the supply voltage.
Do not remove the louvred grill until at
least three minutes after the all-pole dis­connection of the power supply. Never try to take hold of the ventilator before the three minutes have elapsed.
Page 21
Decommissioning 8
0020217119_01 aroCOLLECT Installation and maintenance instructions 21
7.2 Carrying out inspection and maintenance work
Note
Due to the fluctuating outside temperature and air humidity, it is normal for frost to form or for the heat exchanger to freeze in the product. In normal mode, the product automatically starts up a thawing procedure.
Check the product for dirt and, if required, clean it.Check the condensate discharge for blockages and, if
required, remove any dirt/blockages.
Check the air inlet and outlet to ensure that the supply
and exhaust air is unobstructed and, if required, request that the operator removes any vegetation or similar (min­imum clearances). (Page 9)
Request that, in winter, the operator regularly ensures
that the product is free of snow on the intake and outlet side.
7.3 Procuring spare parts
The original components of the product were also certified by the manufacturer as part of the declaration of conformity. If you use other, non-certified or unauthorised parts during maintenance or repair work, this may void the conformity of the product and it will therefore no longer comply with the applicable standards.
We strongly recommend that you use original spare parts from the manufacturer as this guarantees fault-free and safe operation of the product. To receive information about the available original spare parts, contact the contact address provided on the reverse of these instructions.
If you require spare parts for maintenance or repair
work, use only the spare parts that are permitted for the product.
7.4 Cleaning the product
When the casing is completely installed, clean the
product using a sponge and hot water (max. 70 °C) along with commercially available household cleaners that do not contain any abrasive elements in an aqueous solution up to max. 2%. Do not use any sanitary cleaners that contain chlorine or ammonia.
7.5 Cleaning the condensate discharge
3
2
1
1 Screws for the base
panel
2 Base panel
3 Condensate tray
1. Remove the side sections of the casing (Page 19)
and the front louvred grill (outlet side).
2. Unscrew the screws (1) in the front base panel (2) and remove the base panel.
3. Carefully pull the condensate tray (3) forwards and out from below the fan.
4. Clean the connectors.
5. Check that the outflow is free of obstructions. If required, clean or replace this.
6. Insert the condensate tray.
7. Install the side casing and the cover. (Page 19)
8 Decommissioning
8.1 Temporary decommissioning
Disconnect the product from the power supply.
8.2 Permanently decommissioning
1. Disconnect the product from the power supply.
2. Drain the product. For this, use suitable collecting con­tainers and only dispose of heat transfer media, such as brine, at appropriate collection points.
3. Dispose of or recycle the product and its components.
9 Customer service
10 Recycling and disposal
Disposing of the packaging
Dispose of the packaging correctly.Observe all relevant regulations.
Page 22
Appendix
22 Installation and maintenance instructions aroCOLLECT 0020217119_01
Appendix
A Product diagram
A.1 Product diagram
F1
HG2
HE7
8a
7a
TT 40
TZ 33
TT 34
7a Hot brine to the heat pump (A)
8a Cold brine from the heat pump (B)
TT40 Air inlet temperature sensor
TT34 Hot brine temperature sensor
TZ33 De-icer safety cut-out
F1 Ventilator
HG2 De-icer
HE7 Air/brine heat exchanger
Page 23
Appendix
0020217119_01 aroCOLLECT Installation and maintenance instructions 23
B Connection diagram
L1
NL3
L2
X11 X2
X8
X4
X3
BUS
X6
T10
X5
T9
X1
X9
F3 T2
PE PE
NN
PE
N
L2L1
N
L3
F2 T2
230V
24V
K2
K3
K1
K200
1 2
15
3
4
6
7
8
9
14
5
13
12
10
11
1 Air inlet temperature sensor
2 Hot brine temperature sensor
3 Fan control line
4 Fan voltage supply
5 F3 T2 fuse
6 Connection option: Condensate tray heating
7 Connection option: Safety cut-out
8 Safety cut-out with temperature switch and thermal
fuse
9 Heating element de-icer
10 Connection box
11 Line protection switch
12 Mains connection
13 F2 T2 fuse
14 Control unit
15 Address switch: Address 1 (10 kW), address 1/2
(>10 kW)
Page 24
Appendix
24 Installation and maintenance instructions aroCOLLECT 0020217119_01
C Technical data
C.1 General
Dimensions
VWL 11/4 SA
Product dimensions, height with base
1,260 mm
Product dimensions, width
1,200 mm
Product dimensions, depth
785 mm
Weight with packaging
160 kg
Weight without packaging and base
95 kg
Weight without packaging
140 kg
Weight when ready for operation
185 kg
Electrics
VWL 11/4 SA
Measuring voltage
3~/N/PE 400 V / 50 Hz
Fuse type, characteristic B, three-pole switching (disconnection of the three mains connection lines by a switching operation)
10 A
Optional on-site residual-current circuit breaker
RCCB type A (type A
pulse-current-sensitive
residual-current circuit
breakers) or RCCB type B
(type B universal-current­sensitive residual-current
circuit breakers)
Electrical power consumption, max. total
6.5 kW
Electrical power consumption, de-icer
6.0 kW
Electrical power consumption, fan
0 … 0.25 kW
Electrical power consumption, control system
0.01 kW
Electrical power consumption, optional accessory
0.2 kW
Level of protection EN 60529
IP 25
Hydraulics
VWL 11/4 SA
Flow/return heat source connections
Rp 1 1/4"
Diameter of the condensate discharge
70 mm
Installation site
VWL 11/4 SA
Installation site
Outside
Permissible ambient temperature at the installation site
30 … 70
Permissible ambient temperature during operation
22 … 40
Brine circuit
VWL 11/4 SA
Brine fluid
Ethylene glycol 44% vol.
/56% water
Max. operating pressure
0.3 MPa
(3.0 bar)
Min. inlet temperature, cold brine
28
Max. inlet temperature, hot brine
60
Page 25
Appendix
0020217119_01 aroCOLLECT Installation and maintenance instructions 25
VWL 11/4 SA
Brine content of the brine circuit in the air/brine collector
19.8 l
Materials
Cu, CuZn alloy, stainless
steel, EPDM
Total length of the connection line, cold brine and hot brine
2 x 30 m
Diameter of the connection line's cross­section up to a total length of 10 m
DN 40 (40 x 3.8 mm)
Diameter of the connection line's cross­section up to a total length of > 10 and 30 m
DN 50 (50 x 4.6 mm)
Connection line installation depth
0.2 … 1.5 m
Connection line material
PE pipe, PE 100 or PE 80
Sound power level
VWL 11/4 SA
Sound power level A7/W35, A7/W45, A7/W55 in accordance with EN 12102/EN 14511 LWAin heating mode
VWF 57/4
42.7 dB(A)
VWF 58/4
42.7 dB(A)
VWF 87/4
50.6 dB(A)
VWF 88/4
50.6 dB(A)
VWF 117/4
56.0 dB(A)
VWF 118/4
56.0 dB(A)
VWF 157/4
49.5 dB(A)
Note
When two air/brine
collectors (with VWF 157/4
and VWF 197/4) are
running with the same
sound power level at the
same time, the total sound
power level result is 3
dB(A) higher.
VWF 197/4
53.0 dB(A)
Note
When two air/brine
collectors (with VWF 157/4
and VWF 197/4) are
running with the same
sound power level at the
same time, the total sound
power level result is 3
dB(A) higher.
Sound power level A35/W18 in accord­ance with EN 12102/EN 14511 LWAin cool­ing mode
VWF 57/4
53.5 dB(A)
VWF 58/4
53.5 dB(A)
VWF 87/4
60.5 dB(A)
VWF 88/4
60.5 dB(A)
VWF 117/4
66.3 dB(A)
VWF 118/4
66.3 dB(A)
Page 26
Appendix
26 Installation and maintenance instructions aroCOLLECT 0020217119_01
VWL 11/4 SA
Sound power level A35/W18 in accord­ance with EN 12102/EN 14511 LWAin cool­ing mode
VWF 157/4
59.2 dB(A)
Note
When two air/brine
collectors (on VWF 157/4,
VWF 157/4 S1 and VWF 197/4) are running at the
same sound power level at
the same time, the total
sound power level result is
3 dB(A) higher.
VWF 197/4
63.7 dB(A)
Note
When two air/brine
collectors (on VWF 157/4,
VWF 157/4 S1 and VWF 197/4) are running at the
same sound power level at
the same time, the total
sound power level result is
3 dB(A) higher.
Fan rotational speed
VWL 11/4 SA
Fan rotational speed A7/W35, A7/W45, A7/W55 EN 14511 in heating mode
VWF 57/4
300 rpm
VWF 58/4
300 rpm
VWF 87/4
400 rpm
VWF 88/4
400 rpm
VWF 117/4
490 rpm
VWF 118/4
490 rpm
VWF 157/4
390 rpm
VWF 197/4
440 rpm
Fan rotational speed A35/W18 EN 14511 in cooling mode
VWF 57/4
450 rpm
VWF 58/4
450 rpm
VWF 87/4
580 rpm
VWF 88/4
580 rpm
VWF 117/4
710 rpm
VWF 118/4
710 rpm
VWF 157/4
550 rpm
VWF 197/4
650 rpm
C.2 Air heat source
Heat source circuit/brine circuit
VWF 58/4 VWF 88/4 VWF 118/4
Heat source module
1 x VWL 11/4 SA 1 x VWL 11/4 SA 1 x VWL 11/4 SA
Brine fluid type
Ethylene glycol 44% vol. Ethylene glycol 44% vol. Ethylene glycol 44% vol.
Heat source circuit/brine circuit
VWF 57/4 VWF 87/4 VWF 117/4 VWF 157/4 VWF 197/4
Heat source module
1 x
VWL 11/4 SA
1 x
VWL 11/4 SA
1 x
VWL 11/4 SA
2 x
VWL 11/4 SA
2 x
VWL 11/4 SA
Brine fluid type
Ethylene glycol
44% vol.
Ethylene glycol
44% vol.
Ethylene glycol
44% vol.
Ethylene glycol
44% vol.
Ethylene glycol
44% vol.
Performance data
The following performance data is applicable to new products with clean heat exchangers.
Page 27
Appendix
0020217119_01 aroCOLLECT Installation and maintenance instructions 27
VWF 58/4 VWF 88/4 VWF 118/4
Heat source module
1 x VWL 11/4 SA 1 x VWL 11/4 SA 1 x VWL 11/4 SA
A2/W35 heating output
5.70 kW 7.80 kW 10.30 kW
A2/W35 power consumption
1.40 kW 2.10 kW 2.70 kW
A2/W35 output figure/EN 14511 coefficient of performance
4.20 4.00 3.90
Heating output A7/W35 ΔT 5 K
6.20 kW 8.80 kW 11.50 kW
Power consumption A7/W35 ΔT 5 K
1.40 kW 2.00 kW 2.60 kW
Output figure A7/W35 ΔT 5 K/coefficient of performance EN 14511
4.80 4.60 4.60
Heating output A7/W45 ΔT 5 K
6.10 kW 9.00 kW 12.00 kW
Power consumption A7/W45 ΔT 5 K
1.70 kW 2.50 kW 3.20 kW
Output figure A7/W45 ΔT 5 K/coefficient of performance EN 14511
3.70 3.70 3.80
Heating output A7/W55 ΔT 8 K
6.10 kW 9.50 kW 12.20 kW
Power consumption A7/W55 ΔT 8 K
2.00 kW 3.00 kW 3.90 kW
Output figure A7/W55 ΔT 8 K/coefficient of performance EN 14511
3.10 3.20 3.20
Cooling output A35/W18 ΔT 5 K, active
6.60 kW 8.60 kW 12.10 kW
Power consumption A35/W18 Δ T 5 K, act­ive
1.60 kW 2.80 kW 3.70 kW
Energy efficiency ratio A35/W18 EN 14511
4,30 3,20 3,40
Hot water output figure/coefficient of per­formance A7/Wxx DIN EN 16147 at target cylinder temperature of 50 °C and 6 K hys­teresis
2,80 2,60 2,50
Hot water draw-off profile A7/Wxx DIN EN 16147
XL XL XL
Hot water mixed water volume 40 °C (V40) A7/Wxx at target cylinder temperature of 50 °C
229 l 233 l 231 l
Sound power level A7/W35 EN 12102/EN 14511 LWIin heating mode
41.3 dB(A) 43.2 dB(A) 42.5 dB(A)
Sound power level A7/W45 EN 12102/EN 14511 LWIin heating mode
41.6 dB(A) 45.7 dB(A) 44.2 dB(A)
Sound power level A7/W55 EN 12102/EN 14511 LWIin heating mode
44.1 dB(A) 47.4 dB(A) 46.6 dB(A)
Sound power level A35/W18 EN 12102/EN 14511 LWIin cooling mode
51.8 dB(A) 52.6 dB(A) 50.0 dB(A)
Performance data
The following performance data is applicable to new products with clean heat exchangers.
VWF 57/4 VWF 87/4 VWF 117/4 VWF 157/4 VWF 197/4
Heat source module
1 x
VWL 11/4 SA
1 x
VWL 11/4 SA
1 x
VWL 11/4 SA
2 x
VWL 11/4 SA
2 x
VWL 11/4 SA
A2/W35 heating output
5.70 kW 7.80 kW 10.30 kW 13.90 kW 17.40 kW
A2/W35 power consumption
1.40 kW 2.10 kW 2.70 kW 3.50 kW 4.80 kW
A2/W35 output figure/EN 14511 coefficient of performance
4.20 4.00 3.90 4.10 3.70
Heating output A7/W35 ΔT 5 K
6.20 kW 8.80 kW 11.50 kW 15.30 kW 19.80 kW
Power consumption A7/W35 ΔT 5 K
1.40 kW 2.00 kW 2.60 kW 3.30 kW 4.60 kW
Output figure A7/W35 ΔT 5 K/coefficient of performance EN 14511
4.80 4.60 4.60 4.80 4.40
Heating output A7/W45 ΔT 5 K
6.10 kW 9.00 kW 12.00 kW 15.60 kW 20.60 kW
Power consumption A7/W45 ΔT 5 K
1.70 kW 2.50 kW 3.20 kW 4.20 kW 5.70 kW
Output figure A7/W45 ΔT 5 K/coefficient of performance EN 14511
3.70 3.70 3.80 3.90 3.70
Heating output A7/W55 ΔT 8 K
6.10 kW 9.50 kW 12.20 kW 16.00 kW 20.90 kW
Page 28
Appendix
28 Installation and maintenance instructions aroCOLLECT 0020217119_01
VWF 57/4 VWF 87/4 VWF 117/4 VWF 157/4 VWF 197/4
Power consumption A7/W55 ΔT 8 K
2.00 kW 3.00 kW 3.90 kW 5.00 kW 6.70 kW
Output figure A7/W55 ΔT 8 K/coefficient of performance EN 14511
3.10 3.20 3.20 3.30 3.20
Cooling output A35/W18 ΔT 5 K, active
6.60 kW 8.60 kW 12.10 kW 15.80 kW 22.30 kW
Power consumption A35/W18 Δ T 5 K, act­ive
1.60 kW 2.80 kW 3.70 kW 4.40 kW 6.20 kW
Energy efficiency ratio A35/W18 EN 14511
4,30 3,20 3,40 3,90 3,40
Sound power level A7/W35 EN 12102/EN 14511 LWIin heating mode
40.3 dB(A) 45.8 dB(A) 44.4 dB(A) 48.7 dB(A) 48.1 dB(A)
Sound power level A7/W45 EN 12102/EN 14511 LWIin heating mode
41.0 dB(A) 50.1 dB(A) 46.4 dB(A) 49.4 dB(A) 46.1 dB(A)
Sound power level A7/W55 EN 12102/EN 14511 LWIin heating mode
40.9 dB(A) 52.7 dB(A) 46.1 dB(A) 48.0 dB(A) 46.4 dB(A)
Sound power level A35/W18 EN 12102/EN 14511 LWIin cooling mode
48.3 dB(A) 54.7 dB(A) 49.7 dB(A) 46.8 dB(A) 47.2 dB(A)
Application limits for the heat pump: Heating and cooling (heat source = air)
At the same volume flow rates in the heating circuit (ΔT 5K or ΔT 8 K) as for the nominal heat output test under standard nominal conditions.
Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
VWF 58/4 VWF 88/4 VWF 118/4
Application limits for the heat pump: Heat­ing (Air heat source)
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
Application limits for the heat pump: Cool­ing (Air heat source)
A20/W20 A40/W20 A40/W5 A20/W5
A20/W20 A40/W20 A40/W5 A20/W5
A20/W20 A40/W20 A40/W5 A20/W5
Application limits for the heat pump: Heating (heat source = air)
At the same volume flow rates in the heating circuit (ΔT 5K or ΔT 8 K) as for the nominal heat output test under standard nominal conditions.
Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
VWF 57/4 VWF 87/4 VWF 117/4 VWF 157/4 VWF 197/4
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
A40/W65 A40/W25 A22/W25 A22/W50 A2/W65 A15/W65
Application limits for the heat pump: Cooling (heat source = air)
At the same volume flow rates in the heating circuit (ΔT 5K or ΔT 8 K) as for the nominal heat output test under standard nominal conditions.
Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
VWF 57/4 VWF 87/4 VWF 117/4 VWF 157/4 VWF 197/4
A20/W20 A40/W20 A40/W5 A20/W5
A20/W20 A40/W20 A40/W5 A20/W5
A20/W20 A40/W20 A40/W5 A20/W5
A20/W20 A40/W20 A40/W5 A20/W5
A20/W20 A40/W20 A40/W5 A20/W5
Page 29
Index
0020217119_01 aroCOLLECT Installation and maintenance instructions 29
Index
B
Brine fluid, volume...............................................................14
Brine lines, installing............................................................ 13
C
CE label.................................................................................6
Clean the condensate discharge......................................... 21
Clean the product ................................................................ 21
Cleaning the product ...........................................................21
Competent person ................................................................. 3
Connection lines, routing..................................................... 12
Controller PCB .................................................................... 18
Cover, installing................................................................... 19
Creating, foundation ............................................................ 11
D
Decommissioning, permanent ............................................. 21
Decommissioning, temporary .............................................. 21
Design, product .....................................................................7
Design, system...................................................................... 6
Dimensions............................................................................9
Disposal, packaging ............................................................21
Disposing of the packaging ................................................. 21
Documents ............................................................................6
E
Electricity ............................................................................... 4
Electronics box .................................................................... 18
Establishing, power supply.................................................. 18
F
Filling the brine circuit (1 air/brine collector)........................ 15
Filling the brine circuit (two air/brine collectors) .................. 15
Foundation, creating............................................................11
H
Handing over to the operator............................................... 20
I
Identification plate ................................................................. 6
Inspection ............................................................................ 21
Inspection intervals..............................................................20
Installation site....................................................................... 8
Installing, brine lines............................................................13
Installing, cover ................................................................... 19
Installing, product ................................................................13
Installing, side cladding .......................................................19
Intended use..........................................................................3
M
Maintenance........................................................................ 21
Maintenance intervals ......................................................... 20
Minimum clearances ............................................................. 9
N
Noise emission ...................................................................... 8
P
Power supply, establishing.................................................. 18
Product design ...................................................................... 7
Product, installing ................................................................ 13
Purging the brine circuit....................................................... 17
Purging, brine circuit............................................................ 17
Q
Qualification...........................................................................3
R
Removing, transport locks ..................................................... 7
Routing, connection lines ....................................................12
S
Safety device.........................................................................3
Schematic drawing ................................................................ 3
Scope of delivery...................................................................7
Side cladding, installing....................................................... 19
Sound propagation ................................................................ 8
Spare parts..........................................................................21
Starting up ........................................................................... 20
System design.......................................................................6
T
Tool ....................................................................................... 4
Transport ......................................................................... 4, 13
Transport locks, removing ..................................................... 7
V
Voltage ..................................................................................4
Page 30
Page 31
Page 32
0020217119_01 10.05.2016
Vaillant Ltd.
Nottingham Road Belper Derbyshire DE56 1JT Telephone 0330 100 3461
info@vaillant.co.uk www.vaillant.co.uk
© These instructions, or parts thereof, are protected by copyright and may be reproduced or distributed only with the manufacturer's written consent.
We reserve the right to make technical changes.
Loading...