3.7.1 How to add extensions ............................................ 46
3.7.2 How to install 2x 87° elbows ................................. 47
3.7.3 How to install 87° elbows ....................................... 49
3.7.4 How to install 45° elbows ....................................... 50
Flue installation instructions ecoTEC 834449_132
Notes on the documentation 1
Standard Concentric Systems Ø 60/100 2
1 Notes on the documentation
The following instructions are intended to help you
throughout the entire documentation.
Further documents apply in combination with this installation manual.
We accept no liability for any damage caused by non-observe these instructions.
Other applicable documents
For the heating engineer:
- Installation instructions for installed gas fired wall
hung high efficiency boiler.
1.1 Storage of documents
Please pass on this installation manual, all other applicable documents any auxiliary equipment that may be required to the operator of the system whose responsibility it is to ensure the manuals and auxiliary equipment
are available whenever required.
1.2 Symbols used
Please observe the safety instructions in this manual
when using the device!
Danger!
d
Immediate risk of serious injury or death!
Caution!
a
Potentially dangerous situation for the product
and environment!
2 Standard Concentric Systems
Ø 60/100
Galvanized steel air duct/plastic flue duct.
2.1 Requirements
Regulations and standards to be observed
Caution!
a
The air/flue duct must be installed by a suitably qualified service provider, which is responsible for observing the relevant specifications,
regulations and standards.
Note
h
Vaillant ecoTEC gas fired wall hung boilers are
certified as boiler systems with corresponding
flue gas systems according to the EU gas appliance directive 90/396/EEC. The installation
guide is part of the certification and is cited in
the prototype test certificate. The usability
proof of products identified by Vaillant item
numbers for air/flue gas duct systems is supplied in observance of the specifications in this
installation manual.
Note
These instructions should be read in conjunction with the instructions for installation and
servicing supplied with the boiler.
Note
h
Useful information and instructions.
• Symbol for a necessary task
1.3 Applicability of the manual
This installation manual is only valid for the Vaillant
boilers referred to in the other applicable documents.
Note
Ensure also that all legislation, rules, regulations and directives mentioned in the installation instructions are observed.
Note
The installation of the boiler and its flue must
be carried out by a competent person who is
registered with CORGI (The Council for Registered Gas Installers).
Note
The installation of the boiler and flue must be
in accordance with the Gas Safety (Installation
and Use) Regulations 1998 and the Building
Regulations and BS 5440 Part 1.
Note
The requirements for flue termination detailed
in the boiler installation instructions must be
observed.
3Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
Note
h
Two types of flue gas installation are available
for ecoTEC boilers:
- standard concentric flue gas installations
(outer diameter 100 mm)
- a concentric system with a larger diameter
(outer diameter 125mm) which can be used to
achieve longer air/flue gas pipes.
Note
The air/flue duct operates at very low temperatures therefore no clearance is necessary between the air duct and adjacent services.
Note
Ensure while installation work is being carried
out that no debris such as swarf, filings or fragments of mortar are allowed to remain in the
air/flue duct.
2.1.1 Intended use
Valliant flue pipes for ecoTEC are state-of-the-art
appliances which are designed in accordance with
approved safety regulations. Nevertheless, there is still
a risk of death or serious injury to the user or others or
of damage to the device and other property in the event
of improper use or use for which it is not intended.
The Vaillant flue pipes for ecoTEC may only be used
with the unit types named in this installation manual.
Any other use or extended use is considered to be improper. The manufacturer or supplier is not liable for
any resulting damage. The user alone bears the risk. Intended use includes the observance of the relevant
manual.
2.1.2 Preliminary remarks for room sealed appliances
This appliance should only be installed in conjunction
with either a Vaillant flue system or an alternative approved system (details of flue approval categories can
be found in the technical section of the installation manual).
Install the flue system as detailed in the separate flue
installation instructions supplied with this boiler.
BS 6700: Services supplying water for domestic use
within buildings and their curtilages.
BS 6798: Specification for installation of gas fired boil-
ers not exceeding 60 kW input.
BS 6891: Specification for installation of low pressure
gas pipework up to 28 mm (R1) in domestic
premises (2nd family gas).
BS 7593: Treatment of water in domestic hot water
central heating systems.
Institute of Gas Engineers Publication IGE/UP/7/1998:
”Guide for gas installations in timber framed housing”
BS. 5482 Pt. 1 Domestic butane and propane gas burn-
ing installations.
IGE/UP1 Soundness testing and purging of industrial
and commercial gas installation.
IGE/UP2 Gas installation pipework, boosters and com-
pressors on industrial and commercial
premises.
IGE/UP10 Installation of gas appliances in industrial and
commercial premises.
BS. 6644 Installation of gas fired hot water boilers of
rated inputs between 60 kW and 2 MW (2nd
and 3rd family gases).
BS. 5449 Forced circulation hot water central heating
systems for domestic premises. Note: only up
to 45 kW.
BS. 6880 Low temperature hot water heating systems
of output greater than 45 kW.
Part 1 Fundamental and design consid-
erations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and
maintenance.
BS. 4814 Specification for: Expansion vessels using an
internal diaphragm, for sealed hot water heating systems.
BS. 5440 Installation and maintenance of flues and
ventilation for gas appliances of rated input
not exceeding 70 kW net (1st, 2nd and 3rd
familygases).
Part 1 Specification for installation of
flues.
Part 2 Specification for installation and
maintenance of ventilation for gas ap-
pliances.
2.1.3 Related documents
The installation of the boiler must be in accordance with
the relevant requirements of Gas Safety (Installation
and Use) Regulations 1998, Health and Safety Document
No. 635 (The Electricity at Work Regulations 1989),
BS7671 (IEE Wiring Regulations) and the Water Supply
(Water Fitting) Regulations 1999, or The Water Bylaws
2000 (Scotland). It should also be in accordance with
the relevant requirements of the Local Authority, Building Regulations, The Building Regulations (Scotland), he
Building Regulations (Northern Ireland) and the relevant
recommendations of the following British Standards:
Flue installation instructions ecoTEC 834449_134
Standard Concentric Systems Ø 60/100 2
2.2 Planning the air/flue duct layout
2.2.1 Alternative termination accessories available
Only Part of:
Accy. No.: 303 933
Accy. No.: 303 936
94
18
94
27
18
27
70
18
70
65
ElementDescription
Sliding sleeve (PP),
Ø 60/100
Accy. No.: 303 915
37
155
132
498
132
23
Adjustable roof tile for
pitched roof
Accy. No.: 009 076 (black)
255
Flexible pitched roof seal
Accy. No.: 303 980 (black)
140
100
250
13
Flue support clips, Ø 100,
(pack of 5)
Accy. No.: 303 821
Adjustable flue support clips,
Ø 100 (pack of 3)
Accy. No.: 303 935
495
440 – 690
495
Flat roof penetration collar
Accy. No.: 009 056
Telescopic extension (PP),
Ø 60/100
440 mm - 690 mm
Accy. No.: 303 906
70
Table 2.2 Elements 60/100
Table 2.2 Elements 60/100 (continued)
7Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
ElementDescription
Offset section, Ø 60/100
Accy. No.: 303 919
33 – 56
Black terminal kit for horizontal air/flue duct
Accy. No.: 303 934
For 303 933 and 303 936 only
Variable termination kit black
Accy. No.: 303 942
For 303 933 and 303 936 only
Variable termination kit white
Accy. No.: 303 946
For 303 933 and 303 936 only
48
48
290 – 374
ElementDescription
45° bend for variable termination kit - black
Accy. No.: 303 945
45° bend for variable termination kit - white
Accy. No.: 303 948
Deflector set DN 60 PPblack
with wall seal
Accessory No.: 00 2006 0584
Deflector set DN 60 PPwhite
Accessory No.: 00 2006 0585
Flue support clip Ø 60 mm
delivered with kits
60
Extension pipe for variable
termination kit Ø 60 mm 1 m
- black
including 1 support clip
Accy. No.: 303 943
Extension pipe for variable
termination kit Ø 60 mm 1 m
- white
including 1 support clip
Accy. No.: 303 947
87° elbow for variable termination kit - black
including 1 support clip
Accy. No.: 303 944
87° elbow for variable termination kit - white
including 1 support clip
Accy. No.: 303 949
Table 2.2 Elements 60/100 (continued)
Table 2.2 Elements 60/100 (continued)
Flue installation instructions ecoTEC 834449_138
Standard Concentric Systems Ø 60/100 2
2.2.3 Maximum flue lengths for use with ecoTEC
exclusive
AccessoriesAccy.-Nr.
Horizontal
flue systems
Variable termination kit303 942
Vertical flue systems0020060570
Table 2.3 Maximum flue lengths for use with
ecoTEC exclusive
303 933
303 936
303 946
only in combination with
303 933
303 936
0020060571
0020065937
303 982
Max. permitted
concentric
flue length
Max. permitted
concentric
flue length
Max. permitted
concentric
flue length
2.2.4 Maximum flue lengths for use with ecoTEC
ecoTEC exclusive
832
838
4.0 m
incl.
1 elbow 87°
Maximum length of flue is reduced by 1.0 m for each additional 87°
elbow
Maximum length of flue is reduced by 0.5 m for each additional
45° elbow
The maximum permitted concentric flue length given above is reduced as follows:
- Reduced by 0.5 m for the variable terminal
- Reduced by 0.5 m for every 1 m VTK pipe
- Reduced by 0.5 m for every 87° bend
- Reduced by 0.5 m for 2 x 45° bend
7.0 m
Maximum length of flue is reduced by 1.0 m for each additional 87°
elbow
Maximum length of flue is reduced by 0.5 m for each additional
45° elbow
AccessoriesAccy.-Nr.
Horizontal
flue systems
Variable termination kit
Vertical flue
systems
Table 2.4 Maximum flue lengths for use with ecoTEC
303 933Max. permitted
303 942
303 946
only in combination with
303 933
303 936
0020060570
0020060571
0020065937
303 982
concentric
flue length
Max. permitted
concentric
flue length
Max. permitted
concentric
flue length
ecoTEC
plus 612
plus 615
plus 618
8.0 m
incl.
1 elbow 87°
Maximum length of flue is reduced by 1.0 m for each additional 87° elbow
Maximum length of flue is reduced by 0.5 m for each additional 45° elbow
The maximum permitted concentric flue length given above is reduced as follows:
- Reduced by 0.5 m for the variable terminal
- Reduced by 0.5 m for every 1 m VTK pipe
- Reduced by 0.5 m for every 87° bend
- Reduced by 0.5 m for 2 x 45° bend
The flue length ouside shall not exceed 10 m.
12.0 m12.0 m12.0 m8.0 m12.0 m10.0 m
Maximum length of flue is reduced by 1.0 m for each additional 87° elbow
Maximum length of flue is reduced by 0.5 m for each additional 45° elbow
plus 624
plus 824
8.0 m
incl.
1 elbow 87°
plus 630
plus 831
8.0 m
incl.
1 elbow 87°
plus 637
plus 837
plus 937
5.5 m
incl.
1 elbow 87°
pro 24
pro 28
8.0 m
incl.
1 elbow 87°
plus 415
plus 418
plus 428
plus 438
10.0 m
incl.
1 elbow 87°
9Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
A
Fig. 2.1 Horizontal flue systems
Key
A Maximum flue length
A
B
Fig. 2.3 Vertical flue systems
Key
A Maximum flue length
A
Fig. 2.2 Horizontal flue system installed with vertical termina-
tion kit
Key
A Concentric flue length
B Flue length outside
Flue installation instructions ecoTEC 834449_1310
Standard Concentric Systems Ø 60/100 2
2.3 Installing the air/flue duct sliding sleeve
Note
h
For installations where there is insufficient
movement to allow fitting of the flue into flue
outlet, a sliding sleeve (Accy. No. 303 915) is
available. When using the sliding sleeve both
the air and flue ducts of the last extension
must be shortened by a further 95 mm.
12
34
2.4 Installation of the horizontal air/flue duct
2.4.1 Contants included with delivery
Caution!
a
The air/flue duct is not concentric and the air
duct has a slope of 1.5° (if the air flue duct is
not cut). The hole through the wall can therefore be drilled horizontally with no slope.
Where extensions are used, these must be in-
stalled with a slope at 3° ± 1° (equivalent to
50 mm ± 20 mm rise per metre length) to ensure that condensate does not remain in the
sleeve.
754
65
48
13
5
Fig. 2.4 Installing the sliding sleeve
• Push the sliding sleeve (1) over the cut end of the flue
duct (2).
• Place the air duct clamp (7) over the air duct.
• Pull back the sliding sleeve so that it engages into the
socket (3) of the boiler (4). Ensure that the sliding
sleeve penetrates the socket such that there is at
least 20 mm engagement at both ends of the sliding
sleeve.
• Fit the air duct clamp over the air ducts (5 and 6) of
the extension/terminal and boiler outlet. Close the
snap clamp.
• Drill two holes 3 mm diameter through the air duct
clamp (the centre of the holes should be 6 mm from
the edge of the clamp). Ensure that the drill does not
penetrate the inner flue duct. Screw the air duct
clamp to the air duct of the sleeve using the screws
provided.
• Complete the installation of the flue as detailed in
these instructions.
7
6
30
Fig. 2.5 Horizontal air/flue conduit
Horizontal air/flue duct
Accy.-No. 303 933
(Length 0.75 m)
Contents of the accessory:
- Horizontal air/flue duct
- 87° elbow
- 1 x 48 mm air duct clamp
- 1 x 30 mm air duct clamp
- Internal trim ring Ø 100
- External wall seal.
11Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
2.4.2 Preparation
5
4
3
*87
2.4.3 Top outlet flue exiting to rear
• For installations where the air/flue duct is to be installed directly to the rear of the boiler, the installation template details the position of the flue exit hole
for horizontal top outlet installation.
2.4.4 Top outlet flue exiting to side
1
2
Fig. 2.6 Assembly of the boiler and of the roof duct to buildings
with pitched roofs
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
• Determine the installation site for the boiler with reference to the installation and servicing instructions
supplied with the boiler.
• Ensure that all installation and service clearances are
available and that the boiler flue can be installed as
detailed in these instructions.
• Fix the paper template, supplied with the boiler, to the
wall ensuring that the centreline of the template is
vertical using a plumbline or spirit level.
Fig. 2.7 Distance to external wall
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
• For installations where the air/flue duct is to be installed to the side, the position of the flue exit hole
can be determined by carefully levelling across the
wall from the centre line of the air/flue duct hole
marked on the template.
• The position of the flue exit hole should allow the flue
to be installed with a slight upward slope of about
3° ± 1° (equivalent to 50 mm ± 20 mm per metre of
flue duct). Calculate the required rise according to the
flue length and mark the position of the flue exit hole.
• Once the position of the flue exit hole has been determined, the hole should be cut through the wall using a
core drill of 125 mm diameter.
Flue installation instructions ecoTEC 834449_1312
Note
h
If access can be gained to the proposed flue
exit point from outside the dwelling, the hole
can be cut with a 107 mm core drill and the flue
external wall seal fitted from outside the dwelling.
1.
87
B
A
2.
Standard Concentric Systems Ø 60/100 2
• Cut the air duct and flue duct to the lengths shown in
(fig. 2.9).
• All flue sockets should point towards the terminal.
• When cutting the air and flue ducts it is important to
remove any burrs with a file, this ensures easy fitting
of the ducts and prevents any rough edges from damaging the flue seals.
Care should be taken not to scratch the white surface
of the air duct.
• If the installation requires the use of air/flue duct extensions, additional bends or elbows refer to the section 2.11.
• Secure the air duct sections together by drilling a
3 mm diameter hole through the location hole in the
end of the outer air duct. (Ensure that the drill does
not pierce the inner flue duct). Secure the air ducts
together using the screw provided.
87
3°
87
A
Fig. 2.8 Distance to external wall
Key
1. Rear exit
2. Side exit
A Distance to external wall
B Distance to internal wall
= 190 mm ecoTEC exclusive combination
= 176 mm ecoTEC plus open vent
= 125 mm ecoTEC plus system & combination
= 323 mm ecoTEC plus 937
• Measure the distance from the outside face of the wall
to the centre of the fan outlet on the boiler (fig. 2.8).
This is dimension A.
A + 22 mm
13 mm
Fig. 2.9 Length of air pipe
1
13
Fig. 2.10 Assembly of the horizontal wall duct
• Push the air/flue duct assembly (1) including the flexi-
ble external seal through the wall until the seal clears
the outside face of the wall and pull air/flue duct back
towards the boiler until the external seal touches the
outside wall (fig. 2.6 and fig. 2.10).
• Ensure that the air/flue duct (1) is centred in the hole
and the terminal is correctly positioned with the inlet
grille at the bottom (fig. 2.6 and fig. 2.10).
• Slide the internal trim ring (2) over the air duct until it
is flush with the wall (2, fig. 2.6).
• At this stage it is necessary to prepare and fit the
boiler onto the hanging bracket – refer to the boiler
installation instructions.
• Fit the elbow (4) to the boiler by inserting the spigot
of the flue elbow into the flue socket on the boiler and
secure using the 30 mm air duct clamp (3) provided
(fig. 2.6).
• Pull the air/flue duct back through the wall such that
the flue duct fully engages into the flue elbow socket.
• Fit the 48 mm air duct clamp (5) ensuring that it is
positioned centrally (fig. 2.6).
• Drill two holes 3 mm Ø through the air duct of both
the elbow/flue and elbow/boiler clamps at the most
convienient holes on the air duct clamps. (Ensure that
the drill does not penetrate the inner flue duct). Screw
13Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
the clamps to the air ducts of the flue assembly, the
elbow and boiler using the screws supplied.
• Slide the internal trim ring back to the wall, securing
in position with a small amount of sealant if required.
Caution!
a
If installed near a light, insects may fly into the
opening. Tell the homeowner to clean the opening regularly.
2.5 Installation of the telescopic horizontal air/
flue duct
2.5.1 Contents included with delivery
Caution!
a
The air/flue duct is not concentric and the air
duct has a slope of 1.5° (if the air flue duct is
not cut). The hole through the wall can therefore be drilled horizontally with no slope.
Where extensions are used, these must be in-
stalled with a slope at 3° ± 1° (equivalent to
50 mm ± 20 mm rise per metre length) to ensure that condensate does not remain in the
sleeve.
2.5.2 Preparation
*87
5
4
3
1
2
405 - 610
4865
13
30
Fig. 2.11 Horizontal air/flue conduit
Horizontal telescopic air/flue duct
Accy.-No. 303 936
(Length 0.4 - 0.61 m)
Contents of the accessory:
- Horizontal telescopic air/flue duct
- 87° elbow
- 1 x 48 mm air duct clamp
- 1 x 30 mm air duct clamp
- Internal trim ring Ø 100
- External wall seal.
Fig. 2.12 Assembly of the boiler
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
• Determine the installation site for the boiler with reference to the installation and servicing instructions
supplied with the boiler.
• Ensure that all installation and service clearances are
available and that the boiler flue can be installed as
detailed in these instructions.
• Fix the paper template, supplied with the boiler, to the
wall ensuring that the centreline of the template is
vertical using a plumbline or spirit level.
Flue installation instructions ecoTEC 834449_1314
Standard Concentric Systems Ø 60/100 2
2.5.3 Top outlet flue exiting to rear
• For installations where the air/flue duct is to be installed directly to the rear of the boiler, the installation template details the position of the flue exit hole
for horizontal top outlet installation.
2.5.4 Top outlet flue exiting to side
1.
87
B
A
2.
87
A
Fig. 2.13 Installation template
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
• For installations where the air/flue duct is to be installed to the side, the position of the flue exit hole
can be determined by carefully levelling across the
wall from the centre line of the air/flue duct hole
marked on the template (fig. 2.13).
• The position of the flue exit hole should allow the flue
to be installed with a slight upward slope of about
3° ± 1° (equivalent to 50 mm ± 20 mm per metre of
flue duct). Calculate the required rise according to the
flue length and mark the position of the flue exit hole.
• Once the position of the flue exit hole has been determined, the hole should be cut through the wall using a
core drill of 125 mm diameter.
Fig. 2.14 Distance to external wall
Key
1 Rear exit
2 Side exit
A Distance to external wall
B Distance to internal wall
= 190 mm ecoTEC exclusive combination
= 176 mm ecoTEC plus open vent
= 125 mm ecoTEC plus system & combination
= 323 mm ecoTEC plus 937
• Measure the distance from the outside face of the wall
to the centre of the fan outlet on the boiler (fig. 2.14).
This is dimension A.
Note
h
If access can be gained to the proposed flue
exit point from outside the dwelling, the hole
can be cut with a 107 mm core drill and the flue
external wall seal fitted from outside the dwelling.
15Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
1
A + 22 mm
Fig. 2.15 Fixing the air pipe
2
• Adjust the air duct and flue duct to the lengths shown
in (fig. 2.15).
• Secure the air duct sections together by drilling a 3
mm diameter hole through the location hole in the
end of the outer air duct (1). (Ensure that the drill
does not pierce the inner flue duct). Secure the air
ducts together using the screw (1) provided. Place the
adhesive tape (2) across the gap in the telescopic extensions. (fig. 2.15)
• All flue sockets should point towards the terminal.
• Care should be taken not to scratch the white surface
of the air duct.
• If the installation requires the use of air/flue duct extensions, additional bends or elbows refer to the section 2.11.
secure using the 30 mm air duct clamp (3) provided
(fig. 2.12).
• Pull the air/flue duct back through the wall such that
the flue duct fully engages into the flue elbow socket.
• Fit the 48 mm air duct clamp (5) ensuring that it is
positioned centrally (fig. 2.12).
• Drill two holes 3 mm Ø through the air duct of both
the elbow/flue and elbow/boiler clamps at the most
convienient holes on the air duct clamps. (Ensure that
the drill does not penetrate the inner flue duct). Screw
the clamps to the air ducts of the flue assembly, the
elbow and boiler using the screws supplied.
• Slide the internal trim ring back to the wall, securing
in position with a small amount of sealant if required.
Caution!
a
If installed near a light, insects may fly into the
opening. Tell the homeowner to clean the opening regularly.
87
3°
1
13
Fig. 2.16 Assembly of the horizontal wall breakthrough
• Push the air/flue duct assembly (1) including the flexi-
ble external seal through the wall until the seal clears
the outside face of the wall and pull air/flue duct back
towards the boiler until the external seal touches the
outside wall (fig. 2.12 and fig. 2.16).
• Ensure that the air/flue duct (1) is centred in the hole
and the terminal is correctly positioned with the inlet
grille at the bottom (fig. 2.12 and fig. 2.16).
• Slide the internal trim ring (2) over the air duct until it
is flush with the wall (fig. 2.12).
• At this stage it is necessary to prepare and fit the
boiler onto the hanging bracket – refer to the boiler
installation instructions.
• Fit the elbow (4) to the boiler by inserting the spigot
of the flue elbow into the flue socket on the boiler and
Flue installation instructions ecoTEC 834449_1316
Standard Concentric Systems Ø 60/100 2
2.6 Installation of the black terminal kit
2.6.1 Contents included with delivery
Fig. 2.17 Black terminal kit, Accy.-No. 303 934
Black terminal kit
(Accy. No. 303 934)
Contents of the accessory:
- Black terminal
- External wall seal
2.6.2 Assembly of the black terminal kit before in-
stalling the flue duct
Fig. 2.20 Unlocking the catch
• Unlock the catch between the terminal and the flue
duct by twisting them against each other.
• Pull the terminal off the flue duct.
• Push the new terminal into the flue duct and click to
lock.
Fig. 2.18 Releasing the catches
• Use an 8 mm screwdriver to bend the catches inwards.
Fig. 2.19 Pulling out the terminal
• Pull the terminal together with the flue duct out of the
air duct.
Fig. 2.21 Flue duct
Caution!
a
The catch on the top of the terminal must lock
firmly into the notch in the flue duct.
Caution!
a
Make sure the seal fits tightly.
Fig. 2.22 Locking the catch
• Push the flue duct and the terminal back into the air
duct and lock the two catches.
Caution!
a
The seam of the air duct must be at the top.
• Fit the horizontal air/flue duct as described in section
2.4 and 2.5.
17Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
2.6.3 Assembly of the black terminal kit after installing the flue duct
Danger!
d
Risk to life from escaping flue gas!
Before starting work, shut down the appliance
and prevent it from being switched on unintentionally.
• Remove the wall seal from the terminal.
• Use an 8 mm screwdriver to bend the catches inwards
(fig. 2.18).
• Pull the terminal together with the flue duct out of the
air duct (fig. 2.19).
Caution!
a
Do not twist the flue duct, because this might
detach the following flue duct behind the terminal from the spacer.
• Unlock the catch between the terminal and the flue
duct by twisting them against each other (fig. 2.20).
• Pull the terminal off the flue duct.
• Push the new terminal into the flue duct and click to
lock.
Caution!
a
The catch on the top of the terminal must lock
firmly into the notch in the flue duct (fig. 2.21).
Caution!
Make sure the seal fits tightly.
2.7 Installation of the variable termination kit
(VTK)
Caution!
a
The flue outlet of the variable termination must
face directly upwards.
Flue terminal clearances
Minimum flue terminal clearances are defined in
BS5440, and these must apply unless the boiler manufacturer has received approval to quote smaller clearances that are not safety critical. Vaillant have reduced
flue terminal clearances approved and these are given
in the boiler installation instructions. These are the minimum clearances that must apply to all installations, except when a Variable Termination Kit (VTK) is fitted.
When a VTK is fitted to the horizontal flue, the terminal
clearances for the air inlet are reduced. The terminal
clearances for the ‘new’ flue outlet at the end of the
VTK do not change.
The minimum terminal clearances A, B & C for the air
inlet of the VTK are reduced to 150 mm from an opening
such as a window. This means that the terminal on the
horizontal flue becomes the air inlet when a VTK is fitted, and hence can be located less than 300 mm from
an opening window or airbrick.
2.7.1 Contents included with delivery
• Push the flue duct with the terminal back in the air
duct. Carefully push the flue duct back into the sleeve
of the pipe or bend behind it. Lock the two catches
(fig. 2.22).
• Fit the wall seal.
Danger!
d
Before starting up the appliance, check that the
entire flue pipe is firmly seated and sealed.
Fig. 2.23 Variable termination kit
Variable termination kit
Contents of the kit (Accy. No. 303 942, black; 303 946,
white):
- Variable terminal
- 2 x 1 m pipe
- 3 x pipe support clips
- 87° bend with bird protection grille
Flue installation instructions ecoTEC 834449_1318
Standard Concentric Systems Ø 60/100 2
2.7.2 Assembly of the variable terminal kit before
installing the flue pipe
55
Fig. 2.24 Wall clearance
Fig. 2.27 Unlocking the catch
• Unlock the catch between the terminal and the flue
duct by twisting them against each other.
• Pull the terminal out off the flue duct.
• Push the variable terminal into the flue duct and click
to lock.
Fig. 2.25 Releasing the catches
• Use an 8 mm screwdriver to bend the catches inwards.
Fig. 2.26 Pulling out the terminal
• Pull the terminal with the flue duct out of the air duct.
Fig. 2.28 Flue pipe
Caution!
a
The catch on the top of the terminal must lock
firmly into the notch in the flue duct.
Caution!
Make sure the seal fits tightly.
Fig. 2.29 Locking the catch
• Push the flue duct and the variable terminal back into
the air duct and lock the two catches.
Caution!
a
The seam of the air duct must be at the top.
• Fit the horizontal air/flue duct as described in section
2.4 and 2.5.
Caution!
a
It cannot be fitted from inside.
19Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
• Fit the rest of the variable termination kit as described in section 2.7.4.
2.7.3 Installing the variable terminal kit after in-
stalling the flue duct
Danger!
d
Risk to life from escaping flue gas!
Before starting work, shut down the appliance
and prevent it from being switched on unintentionally.
• Remove the wall seal from the terminal.
• Use an 8 mm screwdriver to bend the catches inwards
(fig. 2.25).
• Pull the terminal with the flue duct out of the air duct
(fig. 2.26).
Caution!
a
Do not twist the flue duct, because this might
detach the following flue duct behind the terminal from the spacer.
• Unlock the catch between the terminal and the flue
duct by twisting them against each other (fig. 2.27).
• Pull the terminal out of the flue duct.
• Push the new variable terminal onto the flue duct.
2.7.4 Installing the pipes
Caution!
a
The catch on the top of the variable terminal
must lock firmly into the notch in the flue duct
(fig. 2.28).
Caution!
Make sure the seal fits tightly.
• Push the flue duct with the variable terminal back in
the air duct. Carefully push the flue duct back into the
sleeve of the duct or bend behind it. Lock the two
catches (fig. 2.29).
• Fit the wall seal on the variable terminal.
• Fit the rest of the VTK as described in section 2.7.4.
Fig. 2.30 Installation of basic kit showing position of support
clips
Flue installation instructions ecoTEC 834449_1320
Fig. 2.31 Bird protection grille
Standard Concentric Systems Ø 60/100 2
Fig. 2.32 Installation of basic kit with two additional 87° bends
showing position of support clips
Fig. 2.33 Installation of basic kit with two additional 45° bends
showing position of support clips
• Fit the pipes and bends, working from the variable terminal to the selected location for the flue exit using
support clips supplied fig. 2.30, 2.31, 2.32 or 2.33.
Caution!
a
Pipe extensions must be fixed to the wall using
support clips. Use one clamp for each extension
directly beside the sleeve. Fit another clamp to
the extension after each 87° bend (fig. 2.32).
Caution!
The extension pipe expands when heated. Leave
1 cm expansion space in eachsleeve.
Note
h
The maximum flue lengths where the variable
termination kit is installed are shown in tables
2.3 and 2.4.
Note
The parts are simply pushed together (not bolted).
Caution!
a
Fasten the 87° bend with bird protection grille
using a separate support clip (fig. 2.31).
21Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
Caution!
a
If installed near a light, insects may fly into the
opening. Tell the home owner to clean the opening regularly.
Danger!
d
Before starting up the appliance, check that the
entire flue pipe is firmly seated and sealed.
Caution!
a
During annual maintenance, check the flue system for
- visible defects, such as embrittlement or
damage
- tight connection of the pipes
- dirt in the air intake and flue exits due to
leaves, insects etc.
2.7.5 Routing around roof eaves
min. 400 mmmin. 100 mm
Fig. 2.34 Routing around roof eaves
When routing the variable termination kit around the
roof eaves, additional lengths of M8 threaded bar will be
required for the support clips. Threaded bar can be purchased from most local merchants.
• Change the bird protection grille from the 87° elbow
to the extension installed at the end.
Flue installation instructions ecoTEC 834449_1322
Note
h
If using the 87° elbow, use the seal from the
pipe extension.
• The final pipe extension must be fixed to the wall
using two support clips with a minimum distance of
400 mm.
• Additional 45° bends may be required.
Standard Concentric Systems Ø 60/100 2
2.8 Installing the deflector set
2.8.1 Contents included with delivery
Fig. 2.35 Deflector set
Deflector set DN 60 PP-black
(Accessory No.: 00 2006 0584)
Contents of the accessory:
- Black terminal
- External wall seal
Deflector set DN 60 PP-white
(Accessory No.: 00 2006 0585)
Contents of the accessory:
- White terminal
Fig. 2.37 Pulling out the terminal
• Pull the terminal with the flue duct out of the air duct.
Fig. 2.38 Unlocking the catch
• Unlock the catch between the terminal and the flue
duct by twisting them against each other.
• Pull the terminal out of the flue duct.
• Push the variable terminal into the flue duct and click
to lock.
2.8.2 Assembly of the deflector set before installing the flue gas pipe
Fig. 2.36 Releasing the catches
• Use an 8 mm screwdriver to bend the catches in-
wards.
Fig. 2.39 Flue duct
Caution!
a
The catch on the top of the terminal must lock
firmly into the notch in the flue duct.
Caution!
Make sure the seal fits tightly.
23Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
Fig. 2.40 Locking the catch
• Push the flue gas pipe and the deflector back into the
air pipe and lock the two catches.
Fig. 2.41 Releasing the catches
Caution!
a
The seam of the air duct must be at the top.
• Fit the horizontal air/flue duct as described in section
2.4 and 2.5.
2.8.3 Installation of the deflector set after installing the flue gas pipe
Caution!
a
The deflector flue terminal must point directly
upwards in the centre position.
Flue terminal clearances
The minimum flue terminal clearances are defined in BS
5440, and these must be adhered to unless the boiler
manufacturer has received approval to use smaller
clearances that are not considered to be safety critical.
Vaillant have reduced the flue terminal clearances and
these are given in the boiler installation instructions.
These are the minimum clearances to be used on all installations.
The minimum terminal clearances A, B and C for the deflector are reduced to 150 mm from an opening such as
a window. This means that the terminal on the horizontal flue gas pipe becomes the air inlet when a deflector
is connected, and hence can be situated less than
300 mm from an opening window or airbrick.
• Use an 8 mm screwdriver to bend the catches inwards.
Fig. 2.42 Pulling out the terminal
• Pull the terminal with the flue duct out of the air duct.
Caution!
a
Do not twist the flue gas pipe when doing this.
Turning can cause the following flue gas pipe to
come away from the spacer.
2.8.4 Installing the variable terminal set after installing the flue gas pipe
Danger!
d
Risk to life from escaping flue gas!
Before starting work, shut down the boiler and
prevent it from being switched on unintentionally.
• Remove the wall seal from the terminal.
Fig. 2.43 Unlocking the catch
• Unlock the catch between the terminal and the flue
duct by twisting them against each other.
• Pull the terminal out of the flue gas pipe.
• Fit the deflector to the flue gas pipe.
Flue installation instructions ecoTEC 834449_1324
Fig. 2.44 Flue pipe
Standard Concentric Systems Ø 60/100 2
Setting the deflector in the centre position will direct
the stream of flue gases upwards at an angle of approx.
45°.
45°45°
Caution!
a
The catch on the top of the terminal must lock
firmly into the notch in the flue duct.
Caution!
Make sure the seal fits tightly.
Fig. 2.45 Locking the catch
• Push the flue gas pipe with the terminal back into the
air duct.
• Carefully push the flue gas pipe back into the sleeve
of the pipe or bend behind it.
• Lock the two catches (fig. 2.45).
Caution!
a
The seam of the flue gas pipe must be at the
top.
Fig. 2.47 Lateral setting options
The terminal of the deflector can be turned to the left
or the right by 45°, if required.
These settings permit additional optimisation of the flue
gas guiding.
Caution!
a
Turn the deflector until it latches palpably in
one of the three positions shown in Fig. 2.47.
The latching ensures that the deflector cannot
twist of its own accord.
• Fit the wall seal to the deflector.
Fig. 2.46 Angle of flue gas stream in centre position
45°
25Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
2.9 Installation of the vertical air/flue duct
Note
h
Observe the maximum flue lengths as detailed
in sections 2.2.3 and 2.2.4.
• Determine the installation site for the boiler with reference to the installation and servicing instructions
supplied with the boiler.
• Ensure that all installation and service clearances are
available and that the boiler flue can be installed as
detailed in these instructions.
• Determine the point where the vertical air/flue duct
and terminal assembly will penetrate the roof.
Note
h
The vertical air/flue duct and terminal accessory (Accy. No. 0020060570, 0020060571,
0020065937) may be shortened. The outer
‘white’ duct should be shortened first, then the
inner flue duct cut so that it protrudes 13 mm
out of the air duct. In case of installation directly to the boiler without elbows or bends, it
is essential that the roof tile/collar is vertically
aligned with the air/flue duct of the boiler.
Note
If a 87° elbow is connected directly to the boiler, use the
the vertical air flue duct at this position.
48 mm air duct clamp supplied with
Contents of the accessory:
• Vertical air/flue duct and terminal assembly
• 48 mm air duct clamp
• Fixing bracket
Note
h
See section 2.2 for details of air/flue duct elements.
The air/flue duct assembly may be connected directly to
the flue outlet on top of the boiler.
In addition to the vertical air/flue duct and terminal accessory, air/flue duct extensions can be added to increase the length of the flue.
Flue installation instructions ecoTEC 834449_1326
Standard Concentric Systems Ø 60/100 2
2.9.3 Pitched roof installation
5
542
1
20 - 50
6
0-5
8
Fig. 2.49 Fitting the appliance and the vertical roof duct to a
building with a pitched roof
Ø 100
2
4
100-110
901
7
8
3
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
** = 750 mm ecoTEC exclusive combination
** = 530 mm ecoTEC plus open vent (top holes of
bracket)
** = 622 mm ecoTEC plus system & combination
** = 622 mm ecoTEC plus 937
Note
h
See section 2.11 for further details on the installation of extensions and elbows.
• Push the sliding sleeve (4) firmly into place on the ex-
tension.
• Join the vertical roof duct (5) to the extension (7).
• Join the sliding sleeve (4) to the appliance’s connection piece (8).
Note
h
Using the sliding sleeve allows the appliance to
be easily removed and replaced without dismantling the flue.
• Drill two holes 3 mm Ø through the air duct of the
flue/boiler clamp at the most convienient holes on the
air duct clamp. (Ensure that the drill does not penetrate the inner flue duct). Screw the clamp to the air
ducts of the flue assembly and the boiler using the
screws supplied.
• Ensure that any air duct clamps used are positioned
centrally and fixed to the air duct using the self tapping screws supplied.
Note
h
The air/duct clamp must not be screwed to the
bottom of the vertical air/flue duct and terminal accessory to allow for any slight movement
in the roof structure.
• Ensure that at least one pipe clamp supports the air/
flue duct at each extension fitted.
• Determine the point where the vertical air/flue duct
and terminal assembly will penetrate the roof.
• Fit the flexible pitched roof (Accy. No. 303 980) tile (1,
Accy. No. 303 980).
• Working from above, insert the vertical roof duct (5)
through the roof tile and push it firmly into place.
• Vertically align the roof duct and attach it to the roof
structure with the fixing bracket (6) supplied.
• Fit the boiler hanging bracket (2).
• Install the appliance (3) with reference to the installation and servicing instructions supplied with the boiler.
27Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
2.9.4 Flat-roof installation
5
542
AB
901
3
2
Ø 100
*
Fig. 2.50 Fitting the appliance and vertical flue duct to a build-
ing with a flat roof
1
120
6
7
100 - 110
4
7
• Join the sliding sleeve (4) to the appliance’s connec-
tion piece. This permits easy separation between the
air/flue duct and the appliance.
• Drill two holes 3 mm Ø through the air duct of the
flue/boiler clamp at the most convienient holes on the
air duct clamp. (Ensure that the drill does not penetrate the inner flue duct). Screw the clamp to the air
ducts of the flue assembly and the boiler using the
screws supplied.
• Ensure that any air duct clamps used are positioned
centrally and fixed to the air duct using the self tapping screws supplied.
Note
h
The air/duct clamp must not be screwed to the
bottom of the vertical air/flue duct and terminal accessory to allow for any slight movement
in the roof structure.
• Ensure that at least one pipe clamp supports the air/
flue duct at each extension fitted.
Key
A cold roof
B warm roof
* = 750 mm ecoTEC exclusive combination
* = 530 mm ecoTEC plus open vent (top holes of bracket)
* = 622 mm ecoTEC plus system & combination
* = 622 mm ecoTEC plus 937
• Determine the point where the vertical air/flue duct
and terminal assembly will penetrate the roof.
• Fit the flat roof penetration collar (1).
• Stick the flat roof penetration collar firmly into place
with adhesive in accordance with the codes of practice for flat roofs (CP 144) to ensure a watertight seal.
• Working from above, insert the vertical roof duct (5)
through the flat roof collar and push it firmly into
place.
• Vertically align the roof duct and attach it to the roof
structure with the fixing bracket (6) supplied.
• Fit the boiler hanging bracket (2).
• Install the appliance (2) with reference to the installation and servicing instructions supplied with the boiler.
Note
h
See section 2.11 for further details on the installation of extensions and elbows.
• Push the sliding sleeve (4) firmly into place on the extension.
• Join the vertical roof duct (5) to the extension (3).
Flue installation instructions ecoTEC 834449_1328
Standard Concentric Systems Ø 60/100 2
2.10 Installing the ridge tile terminal
Note
h
Observe the maximum flue gas pipe lengths as
detailed in sections 2.2.3 and 2.2.4.
2.10.1 Contents included with delivery
760
40
Fig. 2.51 Ridge tile terminal
Ridge tile terminal
Accessory No.: 303 982 (black)
Contents of the accessory:
- Ridge tile terminal
- 40 mm air duct clamp
2.10.3 Installing the ridge tile
130
130
min.25
133
R
Fig. 2.52 Ridge tile dimensions
The ridge tile must be purchased from a roof tile manufacturer:
Recommended manufacturer:
Aspect East Anglia Limited
The Old Mill, East Harling
NORWICH, Norfolk
NR16 2QW
Website: www.aspectroofing.co.uk
Contact: Chris Haythorpe
General Manager - Tile Division
Tel: 01953 717777
Fax: 01953 717164
130
130
min.20
max.125°
1
Note
h
See section 2.2 for details of air/flue gas pipe
elements.
When connecting the ridge tile terminal to the boiler, elbows and extensions can be added to the air/flue gas
pipe to produce longer flue gas pipes.
2.10.2 Preparation
Determine the installation site for the boiler with reference to the installation and maintenance instructions
supplied with the boiler.
• Ensure that all the clearances required for installation
and maintenance are available and that the boiler flue
gas pipe can be installed as detailed in these instructions.
• Determine the point where the ridge tile terminal is to
pass through the ridge.
Note
h
If an 87° elbow is connected directly to the
boiler, use the 40 mm air duct clamp supplied
with the vertical air flue duct at this position.
Fig. 2.53 Assembly of the ridge tile
• Fit the ridge tile (1) in accordance with the tile manufacturer's guidelines.
29Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
2.10.4 Installing the ridge tile terminal
1
Fig. 2.54 Installing the ridge tile terminal
• Insert the ridge tile terminal into the ridge tile.
• Align the ridge tile terminal in such a way that the two
fixing straps (1) are sitting across the run of the ridge
tile. This ensures that the combustion air can be
drawn in between the ridge tile and the cowling above
it.
Note
h
See section 2.11 for further details on the installation of extensions and elbows.
• Connect the ridge tile terminal and the boiler using
extensions and elbows.
• Drill two holes (3 mm Ø) in the air duct of the flue
gas/boiler clamp through the most convenient holes
on the air duct clamp. (Ensure that the drill does not
penetrate the inner flue gas pipe).
• Screw the clamp to the air ducts of the flue assembly,
the elbow and the boiler using the bolts supplied.
• Ensure that any air duct clamps used are positioned
centrally and fixed to the air duct using the self tapping screws supplied.
• Ensure that at least one pipe clamp supports the air/
flue gas pipe at each extension fitted.
2.11 Fitting air/flue duct extensions
2.11.1 How to add extensions
4
3
2
1
2
1
Fig. 2.55 Fastening the ridge tile terminal
• Bend the two fixing straps (1) over a beam (2) and se-
cure with nails or bolts.
• Install the boiler with reference to the installation and
maintenance instructions supplied with the boiler.
Fig. 2.56 Loosening the flue conduit
Note
h
No tools are required when separating extensions for cutting to size air and flue tubes separately. When doing so, the flue conduit should
be twisted into a position where the shoulders
on the plastic tube can be pushed through the
spacer-piece. After cutting to size, refit the
flue conduit and secure it to the air conduit.
Flue installation instructions ecoTEC 834449_1330
Standard Concentric Systems Ø 60/100 2
2
1
+ 40 mm
Fig. 2.57 Cutting tubes to size
A
B
1.
2.
2
1
13
70
27
• Use a saw, tin-snips, etc. to cut tubes to size.
• Start by measuring the required length of air conduit*
), and then calculate the corresponding length of
(L
air
flue conduit (L
= L
L
exhaust
L
exhaust
= length of air conduit (A)
L
air
* Minimum length of air-conduit extension: 80 mm.
+ 40 mm
air
= length of flue conduit (B)
) as follows:
exhaust
Caution!
a
You must fasten extensions to the ceiling or
wall using pipe clamps. Use one clamp for each
extension.
Caution!
Where extensions are used, these must be installed with a slope of 3° ± 1° to ensure that
condensate does not remain in the sleeve
(equivalent to 50 mm ± 20 mm rise per metre
length).
2.11.2 How to install 2x 87° elbows
1
Fig. 2.58 Arrangement of 2 x 87° elbows – View from above
2
1
* = 3°
Fig. 2.59 Arrangement of 2 x 87° elbows – View from front
2
2
*
Caution!
The seals are sensitive to mineral oil-based
grease products. For this reason, the seals
must not be greased. If the seals need wetting
to aid in installation, use water only.
Caution!
De-burr and file down any rough edges on the
tubes before fitting in order to prevent damage
to the seals. Remove all metal filings and other
debris.
Caution!
Do not use damaged or dented tubes, as they
will not form an adequate seal.
Caution!
Ensure that the seals remain correctly aligned
when installing the tubes. Do not fit damaged
seals.
Caution!
Secure the exhaust conduit with the fixing device in order to ensure that it is correctly centred relative to the air conduit.
1
Fig. 2.60 Arrangement of 2 x 87° elbows – View from side
*
* = 3°
When using 2 x 87° elbows follow fig. 2.58 to fig. 2.60
to avoid obstructions on outer wall.
Caution!
a
The elbows must be correctly aligned to avoid
undue stress on the joints and risk of leakage.
• The elbow fitted to the top of the boiler (1) should be
twisted by 3° to ensure that the second 87° elbow (2)
exits the wall perpendicular.
31Flue installation instructions ecoTEC 834449_13
2 Standard Concentric Systems Ø 60/100
90°
max. 5 m
*
1
Fig. 2.61 Connecting extensions with 87° elbows
max. 5 m
2
* = 3°
90°
1
Fig. 2.62 Connecting extensions with 45° elbows
When using elbows for long flue runs in a corner follow
fig. 2.61 and fig. 2.62 to avoid obstructions.
Caution!
a
The elbows must be correctly aligned to avoid
undue stress on the joints and risk of leakage.
Note
h
The elbow fitted to the top of the boiler (1)
should be twisted by 3° to ensure that the second 87° elbow (2) exits the wall perpendicular.
Note
When using 87° elbow install with a slope of 3°
between wall and air-flue pipe (fig. 2.61) or use
2 x 45° elbows (fig. 2.62).
max. 5 m
max. 5 m
Flue installation instructions ecoTEC 834449_1332
2.11.3 How to install 87° elbows
Standard Concentric Systems Ø 60/100 2
A
Key
A = Offset
B = Length of air conduit
Note
h
190
The elbow delilvered with the flue kits 303 933
and 303 936 is not the same dimension as
shown here.
Caution!
a
95
10
Fig. 2.63 Installation of 87° elbows, Accy. No.: 303 910
B
95
10
This gives a corresponding exhaust-conduit
length of 190 + 40 = 230 mm.
Example:
An offset of 400 mm is measured. This value is then
used, along with the table below, to determine the
length of the air conduit ( = 190 mm in this case).
This gives a corresponding exhaust-conduit
length of 284 + 40 = 324 mm.
Example:
An offset of 400 mm is measured. This value is then
used, along with the table below, to determine the
length of the air conduit (= 284 mm) and the height
10
Fig. 2.64 Installation of 45° bends, Accy. No.: 303 911
Offset
[in mm]
900210325320445525602645
950215330327450530610650
1000220335334455535617655
> 105 to
< 155 mm
The air/flue duct must be installed by a suitably qualified service provider, which is responsible for observing the relevant specifications,
regulations and standards.
Note
h
Vaillant ecoTEC gas fired wall hung boilers are
certified as boiler systems with corresponding
flue gas systems according to the EU gas appliance directive 90/396/EEC. The installation
guide is part of the certification and is cited in
the prototype test certificate. The usability
proof of products identified by Vaillant item
numbers for air/flue gas duct systems is supplied in observance of the specifications in this
installation manual.
Note
These instructions should be read in conjunction with the instructions for installation and
servicing supplied with the boiler.
Note
h
Two types of flue gas installation are available
for ecoTEC boilers:
- standard concentric flue gas installations
(outer diameter 100 mm)
- a concentric system with a larger diameter
(outer diameter 125mm) which can be used to
achieve longer air/flue gas pipes.
Note
The air/flue duct operates at very low temperatures therefore no clearance is necessary between the air duct and adjacent services.
Note
Ensure while installation work is being carried
out that no debris such as swarf, filings or fragments of mortar are allowed to remain in the
air/flue duct.
Note
Ensure also that all legislation, rules, regulations and directives mentioned in the installation instructions are observed.
Note
The installation of the boiler and its flue must
be carried out by a competent person who is
registered with CORGI (The Council for Registered Gas Installers).
Note
The installation of the boiler and flue must be
in accordance with the Gas Safety (Installation
and Use) Regulations 1998 and the Building
Regulations and BS 5440 Part 1.
Note
The requirements for flue termination detailed
in the boiler installation instructions must be
observed.
35Flue installation instructions ecoTEC 834449_13
3 Optional Concentric System Ø 80/125
3.2 Planning the air/flue duct layout
3.2.1 Alternative termination accessories available
303 200 = Vertical air/flue duct (black)
303 209 = Horizontal air/flue duct
Optional connection accessoriesAccy. No.
Appliance connection piece
Air/flue duct extensions, concentric
470 mm - Ø 80/125
Air/flue duct extensions, concentric
970 mm - Ø 80/125
Air/flue duct extensions, concentric
1970 mm - Ø 80/125
3.2.3 Maximum flue lengths for use with ecoTEC
exclusive
AccessoriesAccy.-Nr.
Horizontal
flue systems
Vertical flue systems303 200Max. permitted
Table 3.3 Maximum flue lengths for use with ecoTEC exclusive
303 209Max. permitted
concentric
flue length
concentric
flue length
Maximum length of flue is reduced by 2.5 m for each additional 87° elbow
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow
Maximum length of flue is reduced by 2.5 m for each additional 87° elbow
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow
3.2.4 Maximum flue lengths for use with ecoTEC
AccessoriesAccy.-Nr.
Horizontal
flue systems
Vertical flue systems
303 209Max. permitted
303 200Max. permitted
concentric
flue length
concentric
flue length
plus 612
plus 615
13.0 m
1 elbow 87°
Maximum length of flue is reduced by 2.5 m for each additional 87° elbow
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow
14.0 m27.0 m23.0 m27.0 m20.0 m
Maximum length of flue is reduced by 2.5 m for each additional 87° elbow
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow
incl.
plus 618
plus 624
plus 630
plus 824
plus 831
25.0 m
incl.
1 elbow 87°
ecoTEC exclusive
832
838
21.0 m
incl.
1 elbow 87°
22.0 m
ecoTEC
plus 637
plus 837
plus 937
21.0 m
incl.
1 elbow 87°
pro 24
pro 28
25.0 m
incl.
1 elbow 87°
plus 415
plus 418
plus 428
plus 438
20.0 m
incl.
1 elbow 87°
Table 3.4 Maximum flue lengths for use with ecoTEC
Flue installation instructions ecoTEC 834449_1338
Fig. 3.1 Horizontal flue systems
Key
A Maximum flue length
Optional Concentric System Ø 80/125 3
3.3 Changing the appliance connection piece
Installation
Accy No.: 303 926
A
2
1
Fig. 3.2 Vertical flue systems
Key
A Maximum flue length
A
Fig. 3.3 Fitting the appliance connection piece
The appliance is supplied ready-fitted with the connection piece for the 60/100 air/flue duct system.
• Loosen the four screws (2) and pull the appliance connection piece (1) upwards to remove it.
• Push the appliance connection piece with the selected
connection diameter down from above, inserting the
push-in end onto the sleeve of the flue collecting
chamber. Now push the appliance connection piece
downwards until the flange comes into contact with
the low-pressure chamber.
• Refit the fixing screws (2).
Caution!
a
The seals are sensitive to mineral oil-based
grease products. For this reason, the seals
must not be greased. If the seals need wetting
to aid in installation, use water only.
39Flue installation instructions ecoTEC 834449_13
3 Optional Concentric System Ø 80/125
3.4 Installation of the sliding sleeve
Installing the air/flue duct sliding sleeve
Note
h
For installations where there is insufficient
movement to allow fitting of the flue into flue
outlet, a sliding sleeve (Accy. No. 303 215) is
available. When using the sliding sleeve both
the air and flue ducts of the last extension
must be shortened by a further 85 mm.
12
34
3.5 Installation of the horizontal air/flue duct
Caution!
a
The air/flue duct is not concentric and the air
duct has a slope of 1.5° (if the air flue duct is
not cut). The hole through the wall can therefore be drilled horizontally with no slope.
Where extensions are used, these must be in-
stalled with a slope at 3° ± 1° (equivalent to
50 mm ± 20 mm rise per metre length) to ensure that condensate does not remain in the
sleeve.
Note
h
Observe the maximum flue lengths as detailed
in sections 3.2.3 and 3.2.4.
Note
See section 3.2 for details of air/flue duct elements.
3.5.1 Contents included with delivery
1103
5
Fig. 3.4 Installing the sliding sleeve
• Push the sliding sleeve (1) over the cut end of the flue
duct (2).
• Place the air duct clamp (7) over the air duct.
• Pull back the sliding sleeve so that it engages into the
socket (3) of the boiler (4). Ensure that the sliding
sleeve penetrates the socket such that there is at
least 20 mm engagement at both ends of the sliding
sleeve.
• Fit the air duct clamp over the air ducts (5 and 6) of
the extension/terminal and boiler outlet. Close the
snap clamp.
• Drill two holes 3 mm diameter through the air duct
clamp (the centre of the holes should be 6 mm from
the edge of the clamp). Ensure that the drill does not
penetrate the inner flue duct. Screw the air duct
clamp to the air duct of the sleeve using the screws
provided.
• Complete the installation of the flue as detailed in
these instructions.
7
6
15
70
70
Fig. 3.5 Horizontal air/flue conduit
Horizontal air/flue duct
Accy. No. 303 209
Contents of the accessory:
- Horizontal air/flue duct
- 87° elbow
- 2 x 70 mm air duct clamps
- 1 x internal plastic ring Ø 125
- 1 x external metal plate
Flue installation instructions ecoTEC 834449_1340
Optional Concentric System Ø 80/125 3
A
Fig. 3.6 Example of installation with horizontal air/flue duct
3.5.2 Preparation
• Determine the installation site for the boiler with reference to the installation and servicing instructions
supplied with the boiler.
• Ensure that all installation and service clearances are
available and that the boiler flue can be installed as
detailed in these instructions.
• Fix the paper template, supplied with the boiler, to the
wall ensuring that the centreline of the template is
vertical using a plumbline or spirit level.
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
• Identify the correct measurement as shown in fig. 3.7,
carefully measure the distance from the bottom centre of the boiler hanging bracket (centreline of the
two lower hanging bracket fixing holes). This gives the
position of the centreline of the 127 mm flue elbow
and adaptor when installed.
• The position of the flue exit hole can be determined
by carefully levelling across the wall from this mark.
3.5.3 Side flue installations
• For installations where the air/flue duct is to be installed to the side, the position of the flue exit hole
can be determined as follows:
Fig. 3.8 Distance between hanging bracket and wall break-
through
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
• The position of the flue exit hole should allow the flue
to be installed with an upwards slope towards the terminal of approximately 3° ± 1°, equivalent to
50 mm ± 20 mm rise per metre of flue length. Calculate the required rise according to the flue length and
mark the position of the flue exithole (fig 3.8).
Fig. 3.7 Installation template
41Flue installation instructions ecoTEC 834449_13
3 Optional Concentric System Ø 80/125
Note
h
Due to the long lengths of flue possible and the
slope required, it may be necessary to adjust
the location of the boiler installation template.
Please check that both the boiler installation
site and flue termination are in accordance with
these instructions prior to drilling any holes for
the boiler hanging bracket.
• Once the position of the flue exit hole has been determined, the hole should be cut through the wall using a
core drill of 127 mm diameter. The flue exit hole
should be cut with a rise towards outside of 3°.
• Measure the distance from the outside face of the wall
to the centre of the fan outlet on the boiler (fig. 3.9).
This is dimension A.
A
Fig. 3.9 Distance to external wall
• For installations where the measured distance dimension A (fig. 3.9) is greater than 960 mm, an air/flue
extension accessory will be required. The number of
air/flue duct extensions which can be used depends
on the boiler.
• Taking each extension to be used, fit the flue duct into
the air duct and secure using the 3 screws provided.
Note
h
The joints between the flue duct sections are of
a push-fit type, with the flue duct spigot inserted into a socket containing a sealing ring. For
ease of installation lubricate the seal using
soap solution prior to assembling.
• Assemble the flue such that there is a gap of about
5 mm between each air duct, which will ensure the
correct flue duct penetration into the flue sockets of
30 mm. All flue sockets should point towards the flue
terminal.
• Measure from the flue terminal and mark the air duct
to a length of: Dimension A + 60 mm.
• Take the extension(s) to be shortened and remove the
3 screws. Separate the ducts.
Note
h
For assembly reasons do not shorten any air
duct to a length of less than 100 mm. If necessary shorten two adjacent extensions to
achieve the overall required length.
• Cut the air duct square and remove any burrs.
• Refit the flue duct into the air duct and secure using
the 3 screws.
15 mm
A
25 mm
A
5 mm
B
Fig. 3.10 Air duct
Key
A = Mark air duct here
B = Dimension A + 10 mm
• For ease of measuring and marking the air/flue duct
extensions, assemble them loosely together with the
air/flue duct and terminal assembly as shown (fig.
3.10).
Fig. 3.11 Flue duct
Key
A = Mark flue duct here
• Cut the flue duct as detailed in fig. 3.11.
• When cutting the air and flue ducts it is important to
remove any burrs with a file, this ensures easy fitting
of the ducts and prevents any rough edges from damaging the flue seals.
• Care should be taken not to scratch the white surface
of the air duct.
• If the installation requires the use of air/flue duct extensions, additional bends or elbows refer to the section 3.7.
• At this stage it is necessary to prepare and fit the
boiler onto the hanging bracket – refer to the boiler
installation instructions.
• Fit the appliance flue outlet adaptor to the boiler.
Flue installation instructions ecoTEC 834449_1342
220
82 - 90
7
Optional Concentric System Ø 80/125 3
• Change the appliance connection piece (3) as described in section 3.3.
• Join the 87° elbow to the appliance connection piece.
• Push the sliding sleeve (7) firmly into place on the ap-
3°
propriate extensions (6).
• Install the extensions and join the sliding sleeve to the
87° elbow.
1
15
Fig. 3.12 Installing the horizontal wall duct
• Push the assembled air/flue duct and terminal assembly through the flue exit hole until it protrudes 220
mm out from the outside wall.
• Ensure that the terminal is correctly positioned with
the air inlet grille at the bottom.
• Slide one of the two trim rings over the air duct until
it is flush with the internal wall face.
3.5.4 Indirect installation
1
2
3
**
4
5
*
6
This section functions subsequently as a sepa-
h
ration point.
• Join all separation points with the air-conduit fixing
collars (1).
See section 3.7 for further details on the in-
h
stallation of extensions and elbows.
For horizontal flue installations through sloping
roofs, please order the Horizontal Flue Flashing
from Ubbink (Nothants, Tel: 01280 700211)
Fig. 3.13 Distance to external wall
Key
* = 750 mm ecoTEC exclusive combination
* = 530 mm ecoTEC plus open vent (from top holes on bracket)
* = 622 mm ecoTEC plus system & combination
* = 622 mm ecoTEC plus 937
** = 253 mm ecoTEC exclusive combination
** = 210 mm ecoTEC plus open vent (from top holes on bracket)
** = 238 mm ecoTEC plus system & combination
** = 238 mm ecoTEC plus 937
• Fit the wall mounting (4).
• Install the appliance (5) with reference to the installation and servicing instructions supplied with the boiler.
43Flue installation instructions ecoTEC 834449_13
0-5
82 - 90
3 Optional Concentric System Ø 80/125
3.6 Installation of the vertical air/flue duct
Note
h
Observe the maximum flue lengths as detailed
in sections 3.2.3 and 3.2.4.
3.6.1 Contents included with delivery
1430
70
Fig. 3.14 Vertical roof duct
Vertical air/flue duct
Accy. No.: 303 200 (black)
Contents of the accessory:
• Vertical roof duct
• Adapter (air) for Ø 110/125
• 70 mm air duct clamp
• Fixing bracket
Please note: The vertical air/flue duct and ter-
h
minal accessory (Accy. No. 303 200) may be
shortened. The outer ‘white’ duct should be
shortened first, then the inner flue duct cut so
that it protrudes 15 mm out of the air duct. In
case of installation directly to the boiler without elbows or bends, it is essential that the
roof tile/collar is vertically aligned with the air/
flue duct of the boiler.
3.6.3 Pitched roof installation
1
2
20 - 50°
8
3
Ø 125
*
545885
4
5
6
7
**
Note
h
See section 3.2 for details of air/flue duct elements.
The air/flue duct assembly may be connected directly to
the flue outlet on top of the boiler.
In addition to the vertical air/flue duct and terminal accessory, air/flue duct extensions can be added to increase the length of the flue.
3.6.2 Preparation
• Determine the installation site for the boiler with reference to the installation and servicing instructions
supplied with the boiler.
• Ensure that all installation and service clearances are
available and that the boiler flue can be installed as
detailed in these instructions.
• Determine the point where the vertical air/flue duct
and terminal assembly will penetrate the roof.
5
Fig. 3.15 Fitting the appliance and the vertical roof duct to a
building with a pitched roof
Key
* = 190 mm ecoTEC exclusive combination
* = 176 mm ecoTEC plus open vent
* = 125 mm ecoTEC plus system & combination
* = 323 mm ecoTEC plus 937
** = 750 mm ecoTEC exclusive combination
** = 530 mm ecoTEC plus open vent (top holes of bracket)
** = 622 mm ecoTEC plus system & combination
** = 622 mm ecoTEC plus 937
• Determine the point where the vertical air/flue duct
and terminal assembly will penetrate the roof.
• Fit the flexible pitched roof seal (2).
• Working from above, insert the vertical roof duct (1)
through the roof tile and push it firmly into place.
• Vertically align the roof duct and attach it to the roof
structure with the fixing bracket (3) supplied.
• Fit the boiler hanging bracket (6).
Flue installation instructions ecoTEC 834449_1344
7
82 - 90
Optional Concentric System Ø 80/125 3
• Install the appliance (7) with reference to the installa-
tion and servicing instructions supplied with the boiler.
Note
h
See section 3.7 for further details on the installation of extensions and elbows.
• Push the sliding sleeve (8) firmly into place on the ex-
tension.
• Join the vertical roof duct (1) to the extension (4).
• Join the sliding sleeve (8) to the appliance’s connection piece (5).
Note
h
Using the sliding sleeve allows the appliance to
be easily removed and replaced without dismantling the flue.
• Drill two holes 3 mm Ø through the air duct of the
flue/boiler clamp at the most convienient holes on the
air duct clamp. (Ensure that the drill does not penetrate the inner flue duct). Screw the clamp to the air
ducts of the flue assembly and the boiler using the
screws supplied.
• Ensure that any air duct clamps used are positioned
centrally and fixed to the air duct using the self tapping screws supplied.
Note
h
The air/duct clamp must not be screwed to the
bottom of the vertical air/flue duct and terminal accessory to allow for any slight movement
in the roof structure.
• Ensure that at least one pipe clamp supports the air/
flue duct at each extension fitted.
3.6.4 Flat-roof installation
1
545
A
885
3
4
5
6
*
Fig. 3.16 Fitting the appliance and vertical flue duct to a build-
ing with a flat roof
Key
A cold roof
B warm roof
* = 750 mm ecoTEC exclusive combination
* = 530 mm ecoTEC plus open vent (top holes of bracket)
* = 622 mm ecoTEC plus system & combination
* = 622 mm ecoTEC plus 937
• Determine the point where the vertical air/flue duct
and terminal assembly will penetrate the roof.
• Fit the flat roof penetration collar (2).
• Stick the flat roof penetration collar firmly into place
with adhesive in accordance with the codes of practice for flat roofs (CP 144) to ensure a watertight seal.
• Working from above, insert the vertical roof duct (1)
through the flat roof collar and push it firmly into
place.
• Vertically align the roof duct and attach it to the roof
structure with the fixing bracket (3) supplied.
• Fit the boiler hanging bracket (5).
• Install the appliance (6) with reference to the installation and servicing instructions supplied with the boiler.
B
Ø 125
2
Ø 120
4
Note
h
See section 3.7 for further details on the installation of extensions and elbows.
45Flue installation instructions ecoTEC 834449_13
3 Optional Concentric System Ø 80/125
• Push the sliding sleeve (7) firmly on to the vertical
roof duct (1) or, where appropriate, on to an extension.
• Where appropriate, join the vertical roof duct (1) to an
extension.
• Join the sliding sleeve (7) to the appliance’s connection piece. This permits easy separation between the
air/flue duct and the appliance.
• Drill two holes 3 mm Ø through the air duct of the
flue/boiler clamp at the most convienient holes on the
air duct clamp. (Ensure that the drill does not penetrate the inner flue duct). Screw the clamp to the air
ducts of the flue assembly and the boiler using the
screws supplied.
• Ensure that any air duct clamps used are positioned
centrally and fixed to the air duct using the self tapping screws supplied.
Note
h
The air/duct clamp must not be screwed to the
bottom of the vertical air/flue duct and terminal accessory to allow for any slight movement
in the roof structure.
• Ensure that at least one pipe clamp supports the air/
flue duct at each extension fitted.
3.7 Fitting air/flue duct extensions
3.7.1 How to add extensions
4
Fig. 3.17 Loosening the flue conduit
3
2
Note
h
No tools are required when separating extensions for cutting to size air and flue tubes separately. When doing so, the flue conduit should
be twisted into a position where the shoulders
on the plastic tube can be pushed through the
spacer-piece. After cutting to size, refit the
flue conduit and secure it to the air conduit.
1
2
1
+ 40 mm
Fig. 3.18 Cutting tubes to size
A
B
1.
2.
2
1
13
70
27
• Use a saw, tin-snips, etc. to cut tubes to size.
• Start by measuring the required length of air conduit*
), and then calculate the corresponding length of
(L
air
flue conduit (L
L
= L
exhaust
L
exhaust
= length of air conduit (A)
L
air
* Minimum length of air-conduit extension: 80 mm.
+ 40 mm
air
= length of flue conduit (B)
) as follows:
exhaust
Flue installation instructions ecoTEC 834449_1346
Optional Concentric System Ø 80/125 3
Caution!
a
You must fasten extensions to the ceiling or
wall using pipe clamps. Use one clamp for each
extension.
Caution!
Where extensions are used, these must be installed with a slope of 3° ± 1° to ensure that
condensate does not remain in the sleeve
(equivalent to 50 mm ± 20 mm rise per metre
length).
Caution!
The seals are sensitive to mineral oil-based
grease products. For this reason, the seals
must not be greased. If the seals need wetting
to aid in installation, use water only.
Caution!
De-burr and file down any rough edges on the
tubes before fitting in order to prevent damage
to the seals. Remove all metal filings and other
debris.
Caution!
Do not use damaged or dented tubes, as they
will not form an adequate seal.
2
1
*
* = 3°
Fig. 3.20 Arrangement of 2 x 87° elbows – View from front
2
1
*
* = 3°
Caution!
Ensure that the seals remain correctly aligned
when installing the tubes. Do not fit damaged
seals.
Caution!
Secure the exhaust conduit with the fixing device in order to ensure that it is correctly centred relative to the air conduit.
3.7.2 How to install 2 x 87° elbows
1
Fig. 3.19 Arrangement of 2 x 87° elbows – View from above
Fig. 3.21 Arrangement of 2 x 87° elbows – View from side
When using 2 x 87° elbows follow fig. 3.19 to fig. 3.21 to
avoid obstructions on outer wall.
Caution!
a
The elbows must be correctly aligned to avoid
undue stress on the joints and risk of leakage.
• The elbow fitted to the top of the boiler (1) should be
twisted by 3° to ensure that the second 87° elbow (2)
exits the wall perpendicular.
2
47Flue installation instructions ecoTEC 834449_13
3 Optional Concentric System Ø 80/125
h
90°
max. 5 m
*
1
Fig. 3.22 Connecting extensions with 87° elbows
max. 5 m
2
* = 3°
Note
When using 87° elbow install with a slope of 3°
between wall and air-flue pipe (fig. 3.22) or use
2 x 45° elbows (fig. 3.23).
90°
1
Fig. 3.23 Connecting extensions with 45° elbows
When using elbows for long flue runs in a corner follow
fig. 3.22 and fig. 3.23 to avoid obstructions.
Caution!
a
The elbows must be correctly aligned to avoid
undue stress on the joints and risk of leakage.
Note
h
The elbow fitted to the top of the boiler (1)
should be twisted by 3° to ensure that the second 87° elbow (2) exits the wall perpendicular.
max. 5 m
max. 5 m
Flue installation instructions ecoTEC 834449_1348
3.7.3 How to install 87° elbows
Optional Concentric System Ø 80/125 3
A
Key
A = Offset
B = Length of air conduit
Caution!
a
190
This gives a corresponding exhaust-conduit
length of 190 + 40 = 230 mm.
Example:
An offset of 400 mm is measured. This value is then
95
10
Fig. 3.24 Installation of 87° elbows, Accy. No.: 303 210
used, along with the table below, to determine the
length of the air conduit ( = 190 mm in this case).
conduit [in mm]
Offset [in mm]Length of air
conduit [in mm]
49Flue installation instructions ecoTEC 834449_13
3 Optional Concentric System Ø 80/125
3.7.4 How to install 45° elbows
A
Key
A = Offset
B = Length of air conduit
C = Height
Caution!
C
10
B
a
This gives a corresponding exhaust-conduit
length of 284 + 40 = 324 mm.
Example:
An offset of 400 mm is measured. This value is then
used, along with the table below, to determine the
length of the air conduit (= 284 mm) and the height
10
Fig. 3.25 Installation of 45° bends, Accy. No.: 303 211
Offset
[in mm]
900210335334455535617655
950215340341460540624660
1000220345348465545631665
> 100 to
< 170 mm