When you want to slow down a running asynchronous motor fed by a frequency converter it turns
into a generator, feeding energy back into the frequency converter. The energy increases the voltage
in the DC-link. The frequency converter compensates for this increase by increasing the output
frequency, decreasing the instantaneous slip and increasing the motor load. The deceleration is, in
this case, dependent on the power losses in the converter and in the motor. This is usually sufficient
in most cases, for pumps, fans, conveyors etc. where the kinetic energy in the load is small or the
braking time is not critical.
When you have to brake down the motor faster than the losses allow, you have to use BCU module
and an external brake resistor (or resistors) for energy dissipation. The extra energy from the load
is turned into heat in the brake resistor. If the DC link voltage increases too much, the BCU turns on
and discharges the capacitors through the brake resistor. Applications where dynamic braking is
usually needed include centrifuges, cranes, some conveyors and drives requiring very fast
reversing.
Modules can be connected parallel with other BCU modules in order to increase braking capacity
(Figure 1).
In BCU application you can use either Analogue input or OPT-B8 option board for PT100 sensor
connection.
Start-up sequence of BCU application has been illustrated in Figure 2.
Figure 1. BCU in common DC bus system
24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com
4 • vacon Introduction
Init
Softwar e Ini t
complete
Read y to
switch on
DC link voltage
OK?
No
Yes
RunEna ble from I/O (P2.2.1.3)
No
or fieldbus (MCW,bit 1)
Ready to Run
(Ready led is on)
Fault?
Yes
BCU Ru nning
(Run le d is on )
Figure 2. Start-up sequence
Yes
No
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
Introduction vacon • 5
1.2 Quick start instructions
NOTE! Before taking any commissioning actions read carefully the safety instructions in Vacon NX
User's Manual, chapter 1.
1. Check installations (see Figure 3, Table 2-1 and Table 2-2).
2. Check resistor(s) max. temperature durability.
3. Switch power on.
4. Set PT-100 parameters (P2.2.2.1, P2.2.2.2 and P2.6.1 – P2.6.3) or KLIXON input settings
(P2.2.1.4).
5. Set brake chopper operation level to preferred value (P2.1.2).
6. In case of parallel BCU set Drooping (P2.4.1) = 5%.
7. Set Digital input parameters (P2.2.1.1 – P2.2.1.4) according to connections.
8. Test BCU.
9. If fault occurs see chapter 6.
DC+
DC-
-R1
-U1
DC+
-F1
BCU
UVW
DC-
-R2
Figure 3. Resistor connections
24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com
6 • vacon Control I/O
2. CONTROL I/O
OPT-A1
Terminal Signal Description
1 +10V
2 AI1+ Analogue input 1, voltage or
3 AI1- Analogue input common Ground for reference and controls
4 AI2+
5 AI26 +24V Control voltage output Voltage for switches, etc. max 0.1 A
7 GND I/O ground Ground for reference and controls
8 DIN1 Digital input 1
9 DIN2 Digital input 2
10 DIN3 Digital input 3
11 CMA Common for DIN 1—DIN 3 Connect to GND or +24V
12 +24V Control voltage output Voltage for switches (see #6)
13 GND I/O ground Ground for reference and controls
14 DIN4 Digital input 4
15 DIN5 Digital input 5
16 DIN6 Digital input 6
17 CMB Common for DIN4—DIN6 Connect to GND or +24V
18 AO1+
19 AO120 DO1 Digital output
Reference voltage Maximum current 10 mA
ref
current
Analogue input 2 Same as A1 but default is 0-20mA.
Fault Reset (Par. P2.2.1.1)
Run enable (Par. P2.2.1.3)
Analogue output 1 Programmable
READY (Par. P2.2.5)
Default: 0– +10V (Ri = 200 kΩ)
(-10V…..+10V Joy-stick control,
selected with a jumper)
0– 20mA (Ri = 250 Ω)
Ri = min. 5kΩ 18…30V = "1"
Ri = min. 5kΩ 18…30V = "1"
.
Range 0—20 mA/R
Programmable
Open collector, I≤50mA, U≤48 VDC
, max. 500Ω
L
OPT-A2
21RO1
22RO1
23RO1
24RO2
25RO2
26RO2
Relay output 1
Running
Relay output 2
Fault
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load 5V/10mA
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load 5V/10mA
On the next pages you will find the lists of parameters within the respective parameter groups.
Column explanations:
Code = Location indication on the keypad; Shows the operator the present parameter
number
Parameter = Name of parameter
Default = Value preset by factory
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; given if available
ID = ID number of the parameter (used with PC tools and fieldbus)
Note = Description of parameter
3.1 Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See Vacon NX User's Manual, Chapter 7 for more information.
Code Parameter Unit ID Note
V1.1 Total Current A 1104 Filtered braking current in Amperes.
V1.2 Power kW 1106 Braking power in kW.
V1.3 DC-link Voltage V 1108 DC intermediate voltage in Volts
V1.4 Unit Temperature °C 1109 Unit temperature C-degrees.
V1.5 ANALOG OUTPUT 1 % 1112 Analog Output 1 in%
V1.6 DIN1, DIN2, DIN3 15 Digital Inputs A1, A2 and A3 Status (sum)
V1.7 DIN4, DIN5, DIN6 16 Digital Inputs B4, B5 and B6 Status (sum)
V1.8 DO1, RO1, RO2 17 Digital Output and Relay 1&2 Status (sum)
V1.9 Unit Nom Voltage V 111 Nominal voltage rating of the Frequency
V1.10 Unit Nom Current A 1118 Nominal current rating of Frequency Converter.
V1.11 DC Nom Voltage V 1120 Nominal value of Dc-link voltage in Volts.
V1.12 MainControlWord 1160 See the chapter 5
V1.13 MainStatusWord 1162 See the chapter 5
V1.14 Active Fault 37 Active fault code
V1.15 PT100(1) Temperature °C 50 Temperature measured with PT100 sensor 1
V1.16 PT100(2) Temperature °C 51 Temperature measured with PT100 sensor 2
V1.17 PT100(3) Temperature °C 52 Temperature measured with PT100 sensor 3
Table 3-1. Monitoring values
Converter.
(only when OPT-B8 is used)
(only when OPT-B8 is used)
24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.