Vacon nxs robust drive for heavy use Sales Brochure

vacon nxs
robust drive for heavy use
the reliable choice
The Vacon NXS is a compact AC drive in the power range of 0.37—560 kW and supply voltages of 208—690 V for heavy use in machines, buildings and all branches of industry.
The robust design incorporates effective protection against supply network disturbances. Trip-free operation is also guaranteed due to sophisticated motor control principles and motor/drive protection features, component selection and ef­fective cooling.
Enclosure classes of IP21 and IP54 and integrated high-lev­el EMC fi lters make the Vacon NXS suitable for all environ­ments.
The Start-Up Wizard and the standard All-In-One Application Package make parameter setting extremely easy in all cases, from simple to complex.
The wide and fl exible standard I/O and option for fi ve I/O boards provide versatile controllability. The most common fi eldbus options are also available.
The modular design of the Vacon NXS brings several advan­tages: the control terminals are safely separated from power terminals, upgrading the control inputs and outputs is easy and convenient, replacing the cooling fan (the only regularly replaceable component) is fast, the display panel can be uti­lized for parameter copying, etc.
Features
• Easy to use display panel
• Interactive programming with Start-Up Wizard
• Versatile All-in-One Package
• Special applications available (water application package, high speed, etc.)
• Five slots for control boards (2 ba­sic boards and 3 option boards)
• High switching frequency, low noise
• Steady state speed error < 1%
• Low torque ripple
• Starting torque > 200%, depending on AC drive sizing
• Suitable for multi-motor applications
Snap-on fan
Robust power module
Connection to PC or door installation kit
Removable display
vacon nxs ip21
fr4
fr5 fr6
Tou ch-p rote cted connections
fr7
Separate control unit, fl exible I/O interface
fr8 fr9
22
design & dimensions
The mechanical design is extremely compact. The IP54 units in particular are the smallest AC drives on the market. All units are suit­able for both wall and enclosure mounting with all necessary components: integrated EMC fi lters, AC chokes, cable protection, dust and water protection. The effective super-cooling principle allows high ambient temperatures and high switching frequencies without derating.
Mains voltage 380—500 V, 50/60 Hz, 3~, Wall-mounted units
Loadability Motor shaft power
Low (+40°C) High (+50°C) 400 V supply
AC drive type Rated
NXS
0003 0004 0005 0007 0009 0012
0016 0022 0031 0038 0045 0061
0072 0087 0105
0140 0168 0205
0261 0300
5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 SSS
5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 SSS 5 A 2 H 1 S 5 A 2 H 1 SSS
5 A 2 H 0 SSS 5 A 2 H 0 SSS 5 A 2 H 0 SSS
5 A 2 H 0 SSS 5 A 2 H 0 SSS 5 A 2 H 0 SSS
5 A 2 H 0 SSF 5 A 2 H 0 SSF
NXS NXS NXS NXS NXS
NXS NXS NXS NXS NXS NXS
NXS NXS NXS
NXS NXS NXS
NXS NXS
SS
continuous
current I
3.3
4.3
5.6
7.6 9
12 16
23 31 38 46 61
72 87
105 140
170 205
261 300
L
(A)
10%
overload
current (A)
3.6
4.7
6.2
8.4
9.9
13.2
17.6
25.3 34 42 51 67
79 96
116
154 187 226
287 330
Rated
continuous
current I
2.2
3.3
4.3
5.6
7.6 9
12 16 23 31 38 46
61 72 87
105 140 170
205 245
H
(A)
50%
overload
current (A)
3.3
5.0
6.5
8.4
11. 4
13.5
18.0
24.0 35 47 57 69
92
108 131
158 210 255
30
8
368
Maximum current I
4.4
6.2
8.6
10.8 14 18
24 32 46 62 76 92
122 144 174
210 280 336
349 444
10%
overl.
S
P (kW)
1.1
1.5
2.2 3 4
5.5
7.5
11 15
18.5 22 30
37 45 55
75 90
110 132
160
50%
overl.
P (kW)
0.75
1.1
1.5
2.2 3 4
5.5
7.5
11 15
18.5 22
30 37 45
55 75 90
110 132
Frame
size
FR4 FR4 FR4 FR4 FR4 FR4
FR5 FR5 FR5 FR6 FR6 FR6
FR7 FR7 FR7
FR8 FR8 FR8
FR9 FR9
Dimensions
W*H*D (mm)
128*2 92*190 128*2 92*190 128*2 92*190 128*2 92*190 128*2 92*190 128*2 92*190
144*391*214 144*391*214 144*391*214 195* 519*23 7 195* 519*23 7 195* 519*23 7
237*591*257 237*591*257 237*591*257
291*758*344 291*758*344 291*758*344
480*1150*362 480*1150*362
Mains voltage 380—500 V, 50/60 Hz, 3˜, Standalone units
Loadability Motor shaft power
Low (+40°C) High (+40°C) 400 V supply
AC drive type Rated
continuous
L
(A)
current I
NXS 0385 5 A 2 L 0 SSA 385 424 300 450 540 200 160 FR10 595*2020*602 NXS 0460 5 A 2 L 0 SSA 460 506 385 578 693 250 200 FR10 595*2020*602 NXS 0520 5 A 2 L 0 SSA 520 572 460 690 828 250 250 FR10 595*2020*602 NXS 0590 5 A 2 L 0 SSA 590 649 520 780 936 315 250 FR11 794*2020*602 NXS 0650 5 A 2 L 0 SSA 650 715 590 885 1062 355 315 FR11 794*2020*602 NXS 0730 5 A 2 L 0 SSA 730 803 650 975 1170 400 355 FR11 794*2020*602
10%
overload
current (A)
Rated
continuous
current I
H
(A)
50%
overload
current (A)
Maximum current I
S
10%
overload
P (kW)
50%
overload
P (kW)
Frame
size
Dimensions
W*H*D (mm)
vacon nxs ip54
fr4
fr5 fr6
fr7
fr8 fr9
3
product range
Mains voltage 525—690 V, 50/60 Hz, 3~, Wall-mounted units
Loadability Motor shaft power
Low (+40°C) High (+50°C) 690 V supply
AC drive type Rated
continuous
NXS NXS NXS NXS NXS NXS NXS NXS NXS
NXS NXS
NXS NXS NXS
NXS NXS NXS NXS
0004 0005 0007 0010 0013 0018 0022 0027 0034
0041 0052
0062 0080 0100
0125 0144 0170 0208
current I
6 A 2 L 0 SSS
6 A 2 L 0SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS
6 A 2 L 0 SSS 6 A 2 L 0 SSS
6 A 2 L 0 SSS 6 A 2 L 0 SSS 6 A 2 L 0 SSS
6 A 2 L 0 SSF 6 A 2 L 0 SSF 6 A 2 L 0 SSF 6 A 2 L 0 SSF
4.5
5.5
7.5 10
13.5 18
22 27 34
41 52
62 80
100 125
144 170 208
L
(A)
For all Vacon NXS drives, overloadability is defi ned as follows: High: 1.5 x I
(1 min/10 min) @ 50°C; Low: 1.1 x IL (1 min/10 min) @ 40°C; IS for 2 sec every 20 sec.
H
10%
overload
current (A)
5.0
6.1
8.3
11.0
14.9
19.8
24.2
29.7 37
45 57
68 88
110 138
158 187
229
continuous
current I
Rated
3.2
4.5
5.5
7.5 10
13.5 18 22 27
34 41
52 62 80
100 125 144 170
(A)
H
50%
overload
current (A)
4.8
6.8
8.3
11. 3
15.0
20.3
27.0
33.0 41
51 62
78 93
120 150
188
216
255
Maximum current I
6.4
9.0
11.0
15.0
20.0 27 36 44 54
68 82
104 124 160
200 213 245 289
10%
overl.
S
P (kW)
3 4
5.5
7.5 11 15
18.5 22 30
.5
37
45 55
75 90
110 132 160 200
50%
overl.
P (kW)
2.2 3 4
5.5
7.5
11 15
18.5 22
30
37.5
45 55 75
90 110 132 160
Frame
size
FR6 FR6 FR6 FR6 FR6 FR6 FR6 FR6 FR6
FR7 FR7
FR8 FR8 FR8
FR9 FR9 FR9 FR9
Dimensions
W*H*D (mm)
195* 519*23 7 195* 519*23 7 195* 519*23 7 195* 519*23 7 195* 519*23 7 195* 519*23 7 195* 519*23 7 195* 519*23 7 195* 519*23 7
237*591*257 237*591*257
291*758*344 291*758*344 291*758*344
480*1150*362 480*1150*362 480*1150*362 480*1150*362
Mains voltage 525—690 V, 50/60 Hz, 3~, Standalone units
Loadability Motor shaft power
Low (+40°C) High (+40°C) 690 V supply
AC drive type Rated
continuous
L
(A)
current I
NXS 0261 6 A 2 L 0 SSA 261 287 208 312 375 250 200 FR10 595*2020*602 NXS 0325 6 A 2 L 0 SSA 325 358 261 392 470 315 250 FR10 595*2020*602 NXS 0385 6 A 2 L 0 SSA 385 424 325 488 585 355 315 FR10 595*2020*602 NXS 0416 6 A 2 L 0 SSA* 416 458 325 488 585 400 315 FR10 595*2020*602 NXS 0460 6 A 2 L 0 SSA 460 506 385 578 693 450 355 FR11 794*2020*602 NXS 0502 6 A 2 L 0 SSA 502 552 460 690 828 500 450 FR11 794*2020*602 NXS 0590 6 A 2 L 0 SSA* 590 649 502 753 904 560 500 FR11 794*2020*602
* max. ambient temperature of +35˚C
10%
overload
current (A)
Rated
continuous
current I
(A)
H
50%
overload
current (A)
Maximum current I
S
10%
overload
P (kW)
50%
overload
P (kW)
Frame
size
Dimensions
W*H*D (mm)
Hardware configurations, Standalone units
FUNCTION AVAILABILITY
IP21 Standard IP54 (FR10 only) Optional (H: +20mm) Integrated fuses Standard Integrated load switch Optional EMC fi ltering L Standard EMC fi ltering T Optional Integrated brake chopper
(cabling top entry)
Optional (H: +122 mm)
fr10 fr11
44
Loading...