Vacon NX OPTCJ User Manual

Page 1
vacon nx
ac drives
optcj
bacnet option board
user manual
Page 2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
INDEX
Document code: DPD00901A
Date edited: 19.01.2012
1. General info ........................................................................................................................ 3
2. BACnet Option Board Technical data ................................................................................. 4
2.1 System Software versions ........................................................................................................ 5
3. BACnet FIELDBUS BOARD LAYOUT AND CONNECTIONS ................................................... 6
4. Grounding cable shield ...................................................................................................... 7
4.1 Grounding by clamping the cable to the converter frame (recommended)............................. 7
4.2 Grounding only one point on the net ........................................................................................ 8
4.3 Bus terminal resistors ............................................................................................................. 9
4.4 Bus Biasing ............................................................................................................................. 10
5. LED indications ................................................................................................................ 11
6. INSTALLATION OF VACON NX BACnet BOARD ................................................................. 12
7. COMMISSIONING .............................................................................................................. 14
7.1 Fieldbus board parameters .................................................................................................... 14
7.2 Expander board menu (M7) .................................................................................................... 14
7.3 BACnet parameters ................................................................................................................ 14
7.3.1 MS/TP MAC address (P7.x.1.1) ....................................................................................... 15
7.3.2 Baud rate (P7.x.1.2) ........................................................................................................ 15
7.3.3 Instance number (P7.x.1.3)............................................................................................. 15
7.3.4 Communication status (V7.x.2.1) .................................................................................... 16
7.3.5 Baud Rate (V7.x.2.2) ........................................................................................................ 16
7.3.6 Fault (V7.x.2.3) ............................................................................................................... 16
7.3.7 Index Nr. (V7.x.2.4) ......................................................................................................... 16
7.4 ANNEX - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) ...... 17
7.5 Object Map .............................................................................................................................. 19
7.5.1 Binary Value Object ........................................................................................................ 20
7.5.2 Analog Value Object ........................................................................................................ 21
8. FAULT TRACKING ............................................................................................................. 23
Page 3
general vacon • 3
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
1. GENERAL INFO
Instead of sending and receiving information to and from frequency converters through I/O, you can connect them to a fieldbus.
Vacon NX frequency converters can be connected to the RS-485 bus using a fieldbus board. The converter can then be controlled, monitored and programmed from the host system.
BACnet is also known by names Direct Digital Control Systems and Building Management Systems. BACnet technology is used mostly in building automation, lightning control, air conditioning and in heating automation. The protocol is an upper level net protocol suitable for large building automation projects.
BACnet stands for
Building Automation and Control Network. BACnet is a true non-propriatery open
protocol communication standard conceived by a consortium of building management, system users
and manufacturers.
If you purchase your BACnet option board separately, please note that it shall be installed in
slot E
on the control board of the frequency converter.
WARNING!
Internal components and circuit boards are at high potential when the frequency converter is connected to the power source. This voltage is extremely dangerous and may cause death or severe injury if you come into contact with it.
Page 4
4 • vacon technical data
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
2
2. BACNET OPTION BOARD TECHNICAL DATA
Connections
Interface
OPT-CJ
: Pluggable connector (5.08mm)
Data transfer method
RS-485 MS/TP, half-duplex
Transfer cable Twisted pair (1 pair and shield) Electrical isolation 500 VDC
Communications
BACnet MS/TP As described in ANSI/ASHRAE Standards 135-2004 Baud rate 9600, 19200, 38400 and 76800 baud (supports autobaud
detection)
MAC Addresses 1 to 127
Environment
Ambient operating temperature
–10°C…55°C
Storing temperature
–40°C…60°C
Humidity <95%, no condensation allowed Altitude Max. 1000 m
Vibration 0.5 G at 9…200 Hz
Safety
Fulfils EN50178 standard
Table 2-1. BACnet technical data
Page 5
layout and connections vacon • 5
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
2.1 System Software versions
OPT-CJ BACnet option board is supported from system software versions:
NXL NXL00005V149.VCN
NXS NXS00001V161.VCN
NXP NXP00002V160.VCN
Autobaud detection and BACnet specific fault codes (readable from panel) are added from system software versions:
NXL NXL00005V248.VCN
NXS NXS00001V163.VCN
NXP NXP00002V162.VCN
Communication timeout is available from system SW versions. When not supported, the default is 10
seconds.
NXL NXL00005V254.VCN
NXS NXS00001V167.VCN
NXP NXP00002V168.VCN
OPT-CJ software version
OPTCJ_10522V009 and newer:
New baud rate 76800 from software versions:
NXL: NXL00005V257.VCN
NXS: NXS00001V170.VCN
NXP: NXP00002V171.VCN
Page 6
6 • vacon technical data
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
3
3. BACNET FIELDBUS BOARD LAYOUT AND CONNECTIONS
Vacon BACnet option board is connected to the fieldbus through a 5-pin pluggable bus connector. The communication with the control board of the frequency converter takes place through the standard Vacon Interface Board Connector.
Figure 3-1. Vacon BACnet option board OPT-CJ
Signal
Connector
Description
NC* 1* No connection
VP 2 Supply voltage – plus (5V)
RxD/TxD –N 3 Receive/Transmit data – A RxD/TxD –P 4 Receive/Transmit data – B DGND 5 Data ground (reference potential for VP) *You can use this pin (1) to bypass the cable shield to the next slave
Table 3-1. OPT-CJ bus connector signals
X4
X1
Bus connector
Jumpers Interface board connector
Grounding plate
1 2 3 4 5
Page 7
grounding cable shield vacon • 7
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
4. GROUNDING CABLE SHIELD
4.1 Grounding by clamping the cable to the converter frame (recommended)
This manner of grounding is the most effective and especially recommended when the distances between the devices are relatively short or if the device is the last device on
the net.
Note: Normally, the option board has already been installed in slot D or slot E of the control board. It
is not necessary to detach the whole board for the grounding of the bus cable shield. Just detach the terminal block.
1 Strip about 5 cm of the cable and cut off the grey cable shield.
Remember to do this for both bus cables (except for the last device). See pictures below.
2 Leave no more than 1 cm of the cable outside the terminal block and strip the data cables
at about 0.5 cm to fit in the terminals. See pictures below. Note: Do this for both bus cables.
Figure 4-1.
Figure 4-2.
Cut here
Strip this part
1 2 3 4 5
B
A
Page 8
8 • vacon grounding cable shield
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
4
3 Insert the data cables of both cables into terminals #3 (Line B) and #4 (Line A). 4 Strip the cable at such a distance from the terminal that you can fix it to the frame with the
grounding clamp. See pictures below:
Figure 4-3.
4.2 Grounding only one point on the net
In this manner of grounding, the shield is connected to ground only at the last device on the net in the same way as described in chapter 4.1. Other devices of the net just pass the shield. We recommend you to use an Abico connector to fit the shields into the terminal.
1. Strip about 5 cm of the cable and cut off the grey cable shield. Remember to do this for both bus cables (except for the last device).
2. Leave no more than 1 cm of the cable outside the terminal block and strip the data cable at about 0.5 cm to fit in the terminals. See Figure 4-4.
Figure 4-5.
Note! Do this for both cables.
1 2 3 4 5
B
A
Shield
Page 9
grounding cable shield vacon • 9
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
3. Fix both the cables on the frame with the clamp. See Figure 4-5.
Figure 4-6.
4.3 Bus terminal resistors
Figure 4-8. Using jumper X4 to set the bus termination.
If Vacon is the last device of the fieldbus line the bus termination must be set. Use jumper X4 (ON
position). See Figure 4-7.
Note: Jumper X1 is only used when D9 type connector is assembled (Not used with BACnet protocol)
Page 10
10 • vacon grounding cable shield
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
4
4.4 Bus Biasing
Bus biasing is required to ensure faultless communication between devices at RS-485 bus. Bus biasing makes sure that the bus state is at proper potential when no device is transmitting. Without biasing, faulty messages can be detected when the bus is in idle state. RS-485 bus state should be neather +0,200..+7V or –0,200..-7V. Illegal bus state is <200mV..-200mV.
Number of nodes Bias resistance 2-5 1.8 kohm 5-10 2.7 kohm 11-20 12 kohm 21-30 18 kohm
31-40
27 kohm
Table 4-1. Bias resistor size vs number of node
Fail safe
biasing in OPT-CJ option board
Connect resistor biasing resistors between pins #2 and #4 as well as pins #3 and #5 as shown in picture.
Matters related to this are discussed in the application note
Failsafe Biasing of Differential Buses
(an-847.pdf) published by National Semiconductor (www.national.com).
5
DAT A A
DAT A B
1 2 3 4 5
Page 11
led indications vacon • 11
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
5
5. LED INDICATIONS
The two LED indications next to the connector show the present statuses of the BACnet board (yellow) and the Fieldbus Module (green).
Figure 5-1. LED indications on the BACnet board
BACnet board status LED (BS) YELLOW
LED is:
Meaning:
OFF Option board not activated ON Option board in initialisation state waiting for activation
command from the frequency converter
Blinking fast
(once/sec)
Option board is activated and in RUN state
Option board is ready for external communication
Blinking slow
(once/5 secs)
Option board is activated and in FAULT state
Internal fault of option board
Fieldbus status LED (FS) GREEN
LED is:
Meaning:
OFF Fieldbus module is waiting for parameters from the
frequency converter
No external communication
ON Fieldbus module is activated
Parameters received and module activated
Module is waiting for messages from the bus
Blinking fast
(once/sec)
Module is activated and receiving messages from the bus
Blinking slow
(once/5 secs)
Module is in FAULT state
No messages from Master within the watchdog time
Bus broken, cable loose or Master off line
X4
X1
1 2 3 4 5
Yellow Green
Page 12
12 • vacon installation of bacnet board
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
6
6. INSTALLATION OF VACON NX BACNET BOARD
A
Vacon NX frequency converter
B
Remove the cable cover.
C
Open the cover of the control unit.
Page 13
installation of bacnet board vacon • 13
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
D
Install BACnet option board in slot E on the control board of the frequency
converter. Make sure that the grounding plate (see below) fits tightly in the clamp.
E
Make a sufficiently wide opening for your cable by cutting the grid as wide as necessary.
F
Close the cover of the control unit and the cable cover.
Page 14
14 • vacon commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
7. COMMISSIONING
READ FIRST CHAPTER 8 'COMMISSIONING' IN VACON NX USER'S MANUAL (Document nr. ud00701, please visit http://www.vacon.com/Default.aspx?id=450403&FileView=462792).
Note! You must select Fieldbus as the active control place, if you wish to control the frequency converter through fieldbus. See Vacon NX User’s Manual, Chapter 7.3.3.1.
7.1 Fieldbus board parameters
The Vacon BACnet board is commissioned with the control keypad by giving values to appropriate parameters in menu
M7 (for locating the expander board menu see Vacon NX User's Manual,
Chapter 7).
7.2 Expander board menu (M7)
The
Expander board menu
makes it possible for the user 1) to see what expander boards are
connected to the control board and 2) to reach and edit the parameters associated with the expander board.
Enter the following menu level
(G#) with the
Menu button right
. At this level, you can browse
through slots A to E with the
Browser buttons
to see what expander boards are connected. On the
lowermost line of the display you also see the number of parameter groups associated with the board.
If you still press the
Menu button right
once you will reach the parameter group level where there
are two groups: Editable parameters and Monitored values. A further press on the
Menu button right
takes you to either of these groups.
7.3 BACnet parameters
To commission the RS-485 board, enter the level P7.5.1.# from the
Parameters
group (G7.5.1). Give
desired values to all RS-485 parameters (see Figure 7-1 and Table 7-1).
Figure 7-1. Changing the BACnet board commissioning parameter values
E x p a n d e r B o a r d
G 1
G 5
R E A D Y
I / O t e r m
N X O P T C J
R E A D Y
I / O t e r m
G 1
G 2
S l a v e a d d r e s s
R E A D Y
I / O t e r m
1 2 6
e n t e r
C H A N G E V A L U E
C O N F I R M C H A N G E
P a r a m e t e r s
R E A D Y
I / O t e r m
P 1
P 4
S l a v e a d d r e s s
R E A D Y
I / O t e r m
1 2 6
Page 15
commissioning vacon • 15
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
#
Name
Default
Range
Description
1 MAC ADDRESS 1 1…127 2 BAUD RATE
1
0 - Auto 1 – 9600 baud 2 – 19200 baud 3 – 38400 baud 4 – 76800 baud
Communication speed
3 INDEX NR.
Counting
number
0-65535
Instance Number. Zero means that unique default device object instance number is used.
4 Comm. time-out
10 s
0 = OFF 10 – 60 s
Communication time-out 0 = Not in use
Table 7-1. BACnet option board parameters
7.3.1
MS/TP MAC address (P7.x.1.1)
The parameters of every device must be set before connecting to the bus. Especially the parameters
MAC Address
and
Baud Rate
must be the same as in the master configuration.
The first parameter, MAC (Medium Access Control) address, must be unique on the network to which it is connected. The same MAC address may be used on a device on another network within the internetwork. Addresses 128-254 are reserved for slaves. Addresses 1-127 are valid for both masters and slaves. The portion of the address space that is actually used for masters in a particular installation is determined by the value of the Max_Master property of the Device object. It is recommended that MAC address 0 be reserved for use by the MS/TP router and 255 is reserved for broadcasts.
7.3.2
Baud rate (P7.x.1.2)
Select the communication speed for the network. Default value is 9600 baud. 0 (– Auto) means that automatic baud rate detection is used. The used Baudrate is shown in monitor
menu.
7.3.3
Instance number (P7.x.1.3)
The Device Object's Instance number must be unique across the entire BACnet internetwork because it is used to uniquely identify the BACnet devices. It may be used to conveniently identify the BACnet device from other devices during installation. If 0 (default) is selected, the Device Instance number is read from Drive. This unique number is then shown in Monitor menu. If any other value than zero is selected, the value is used as Device Object’s Instance number. The actual value is shown in monitor menu.
7.3.4
Communication time-out
BACnet board initiates a communication error if the communication is broken for as long as defined by the parameter Communication time-out. Communication time-out is disabled when the parameter is given the value 0. The step for setting the time-out time is 10 seconds.
Page 16
16 • vacon commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
7.3.5
Communication status (V7.x.2.1)
To see the present status of the RS-485 fieldbus, enter the
Comm.Status
page from
Monitor
menu
(G7.5.2). See Table 7-2 and Table 7-2 below.
Figure 7-2. Communication status
Good messages
0…999 Number of messages received without
communication errors
Bad Frames
0…64
Number of messages received with
CRC or parity errors
Table 7-2. BACnet message indications
7.3.6
Baud Rate (V7.x.2.2)
Shows the actual baud rate.
7.3.7
Fault (V7.x.2.3)
Shows BACnet fault codes. See Table 8-3 from Chapter 8.
7.3.8
Index Nr. (V7.x.2.4)
Shows the Device Object's Instance number.
Page 17
commissioning vacon • 17
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
7.4 ANNEX - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)
(This annex is part of this Standard and is required for its use.)
BACnet Protocol Implementation Conformance Statement
Date: May 31, 2005 Vendor Name: Vacon Product Name: Vacon Drive – xxx (xxx = MAC ID) Product Model Number: OPTCJ Applications Software Version: 10522 Firmware Revision: 1 BACnet Protocol Revision: 4
Product Description:
BACnet Option board is designed for Vacon NX family devices.
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
List all BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B, DS-WP-B, DM- DDB-B, DM-DOB-B.
Segmentation Capability:
Segmented requests supported Window Size  Segmented responses supported Window Size
Standard Object Types Supported:
An object type is supported if it may be present in the device. For each standard Object Type supported provide the following data:
1) Whether objects of this type are dynamically creatable using the CreateObject service
2) Whether objects of this type are dynamically deletable using the DeleteObject service
3) List of the optional properties supported
4) List of all properties that are writable where not otherwise required by this standard
5) List of proprietary properties and for each its property identifier, datatype, and meaning
6) List of any property range restrictions
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 34800, 76800 (supports autobaud detection)
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No
Page 18
18 • vacon commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
Networking Options:
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4 IBM
/Microsoft DBCS ISO 8859-1
ISO 10646 (UCS-2)  ISO 10646 (UCS-4)  JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports.
Page 19
commissioning vacon • 19
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
7.5 Object Map
Object types and properties supported:
Figure 7-3. Object types and properties supported:
* Only with commandable values
Property
Object Type
Device
Binary
Value
Analog Value
Object Identifier
X
X X
Object Name X X X Object Type X X X System Status X Vendor Name X Vendor Identifier X Model Name X Firmware Revision X Appl Software revision X Protocol Version X Protocol Revision X
Services Supported
X
Object Types supported X Object List X Max APDU Length X Segmentation Support X APDU Timeout X Number ADPU Retries X Max Master X Max Info Frames X Device Address Binding X Database Revision X
Preset Value
X X
Status Flags X X Event State X X Out-of-Service X X Units X Priority Array X*) X*) Relinquish Default X*) X*) Polarity Active Text X Inactive Text X
Page 20
20 • vacon commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
7.5.1
Binary Value Object
Instance ID
Object Name
Description
Inactive / Active
Present Value
Access Type
BV0
Ready State Indicates whether the
drive is ready or not
Not Ready / Ready R
BV1
Run/Stop State Indicates whether the
drive is running or
stopped
Stop / Run R
BV2
Fwd/Rev State
Indicates the rotation
direction of the motor
Fwd / Rev
R
BV3
Fault State Indicates if a fault is
active
OK / Fault R
BV4
Warning State Indicates if a warning is
active
OK / Warning R
BV5
At Setpoint
Ref. Frequency reached
False / True
R
BV6
At Zero Speed Motor Running at zero
speed
False / True R
BV7
General 0
Application specific bit
from drives General Status Word
0 / 1
R
BV8
General 1 Application specific bit
from drives General Status Word
0 / 1 R
BV9
General 2 Application specific bit
from drives General Status Word
0 / 1 R
BV10
General 3 Application specific bit
from drives General Status Word
0 / 1 R
BV11
General 4 Application specific bit
from drives General Status Word
0 / 1 R
BV12
General 5
Application specific bit
from drives General Status Word
0 / 1 R BV13
General 6 Application specific bit
from drives General Status Word
0 / 1 R
BV14
General 7 Application specific bit
from drives General Status Word
0 / 1 R
BV15
Run/Stop CMD Command to start drive
(FB control is active)
Stop / Run C
BV16
Fwd/Rev CMD Command to change
rotational direction (FB control is active)
Fwd / Rev C
BV17
Reset Fault Command to reset
Active Fault from dirve
0 / Reset C
BV18
FBFixedControlWord
Bit_3
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV19
FBFixedControlWord
Bit_4
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV20
FBFixedControlWord
Bit_5
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV21
FBFixedControlWord
Bit_6
Application Specific bit
From the Fixed Control
Word
0 / 1
C
Page 21
commissioning vacon • 21
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
BV22
FBFixedControlWord
Bit_7
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV23
FBFixedControlWord
Bit_8
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV24
FBFixedControlWord
Bit_9
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV25
FBFixedControlWord
Bit_10
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV26
FBFixedControlWord
Bit_11
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV27
FBFixedControlWord
Bit_12
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV28
FBFixedControlWord
Bit_13
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV29
FBFixedControlWord
Bit_14
Application Specific bit From the Fixed Control
Word
0 / 1 C
BV30
FBFixedControlWord
Bit_15
Application Specific bit From the Fixed Control
Word
0 / 1 C
NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays & relinquish defaults.
7.5.2
Analog Value Object
Instance ID
Object Name
Description
Units
Present Value
Access Type
AV0
Frequency Setpoint Frequency Setpoint
Hz R
AV1
Output Frequency Output Frequency
Hz R
AV2
Motor Speed Motor Speed
Rpm R
AV3
Load (power) Motor Shaft Power
Percent
R
AV4
Kilowatt Hours total
Megawatt Hour Counter (Total)
kWh R
AV5
Motor Current Motor Current
Amps R
AV6
DC link Voltage DC link Voltage
Volts R
AV7
Motor Voltage Motor Voltage
Volts R
AV8
Unit Temperature
Heatsink Temperature
NOT IN NXL -series
° C
R
AV9
Motor Torque
In % of motor nominal Torque
Percent R
AV10
Operating Days
Operating Days (resettable)
Day R
AV11
Operating Hours
Operating Hours (resettable)
Hour R
AV12
Kilowatt Hours
Kilowatt Hours (resettable)
kWh R
AV13
Torque Reference
Torque Reference
NOT
IN NXL -series
Percent R
Page 22
22 • vacon commissioning
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
AV14
Temperature Rise
Calculated motor
temperature 100,0% = nominal temperature of motor
NOT IN NXL -series
Percent R
AV15
FBProcessDataOut1 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV16
FBProcessDataOut2 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV17
FBProcessDataOut3 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV18
FBProcessDataOut4 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV19
FBProcessDataOut5 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV20
FBProcessDataOut6 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV21
FBProcessDataOut7 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV22
FBProcessDataOut8 Application specific
-32768.0 to +32767.0 resolution 1.0
R
AV23
Active Fault Code Active Fault Code -
R
AV24
Speed Reference
Speed Reference,
percentage of nominal speed
Percent C
AV25
Current Limit Current Limit
Amps W
AV26
Min Frequency Minimum Frequency
Hz W
AV27
Maximum Frequency Maximum Frequency
Hz W
AV28
Accel Time Acceleration Time
seconds W
AV29
Decel Time Deceleration Time
seconds W
AV30
FBProcessDataIN 1 Application specific
-32768.0 to +32767.0 resolution 1.0
C
AV31
FBProcessDataIN 2 Application specific
-32768.0 to +32767.0 resolution 1.0
C
AV32
FBProcessDataIN 3
Application specific
-32768.0 to +32767.0 resolution 1.0
C
AV33
FBProcessDataIN 4
Application specific
-32768.0 to +32767.0 resolution 1.0
C
AV34
AnyParam ID
ID number that is used in AV35
0.0 to 65535.0 resolution 1.0
W
AV35
AnyParam Value
Value of ID defined by
AV34
-32768.0 to +32767.0
resolution
W
AV36
FBFixedControlWord PDI 0 1) (see next page) C
AV37
FBGeneralControlWord PDI 1 2) (see next page) C
AV38
FBFixedStatusWord PDO 0
3) (see next page)
R AV39
FBGeneralStatusWord PDO 1 4) (see next page) R
NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays & relinquish defaults.
Page 23
fault tracking vacon • 23
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
Note: These Analog Value objects are introduced in BACnet SW version: OPTCJ_10522V009.vcn
1) FBFixedControlWord PDI 0, bit encoding (
All-in-One Applications)
B0=RUN; 0=Stop, 1=Run B1=DIRECTION; 0=Fwd, 1=Rev B2=FaultRST; Reset on rising edge
B3-15 Application Specific
2) FBGeneralControlWord PDI 1, bit encoding
Application Specific
3) FBFixedStatusWord (MCStatus) PDO 0, bit encoding
B0=Ready; 0=not ready, 1=ready B1=Run; 0=stopped, 1=running B2=Direction; 0=clockwise, 1=counterclockwise B3=Fault; 1=the FC is faulted and stopped (?) B4=Warning; 1=warning B5=AtReference; 1=at reference speed B6=ZeroSpeed; 1=at zero speed B7=FluxReady; 1=flux ready B8=TCSpeedLimitActive; B9=DetectedEncoderDirection; B10=UVFastStop; B11=DC brake status 1=DC brake active
B12-15 Firmware Specific
* Not all the bits are supported in every application
4) FBGeneralStatusWord PDO 1, bit encoding
Application Specific
Page 24
24 • vacon fault tracking
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
8
8. FAULT TRACKING
The table below presents the faults related to the BACnet option board. For more information, see also Vacon NX User's Manual, Chapter 9. The
BACnet option board status LEDs have been described in more detail in Chapter 5.
Fault
code
Fault
Possible cause
Correcting measures
37
Device change Option board changed. Reset
38
Device added Option board added. Reset
39
Device removed Option board removed. Reset
40
Device unknown
Unknown option board.
53
Fieldbus fault -The board has lost all contact with other
devices on the network.
- Duplicate MAC ID (Bad Frames in “Comm. status” is incremented every time a frame is received from a device with the same MAC id on the same
segment.)
Check the installation. If installation is correct contact the nearest Vacon distributor. Check that MAC ID is unique.
54
Slot fault Defective option board or slot. Check the board and slot.
Contact the nearest Vacon distributor.
Table 8-1. RS-485 option board faults
You can define with parameters how the frequency converter shall react to certain faults:
Code
Parameter
Min
Max
Unit
Step
Default
ID
Note
P2.7.22
Respo
nse to fieldbus
fault
0 3 1 0 733
0
=No response
1
=Warning
2
=Fault,stop acc. to 2.4.7
3
=Fault,stop by coasting
P2.7.23
Response to slot
fault
0 3 1 0 734
0
=No response
1
=Warning
2
=Fault,stop acc. to 2.4.7
3
=Fault,stop by coasting
Table 8-2. Frequency converter responses to faults
These BACnet Specific fault codes can be read from panel V7.x.2.3 (x is the used, D=4, E=5).
Fault
code
Fault
Possible cause
Correcting measures
0
None
1
Sole Master Only device on the network Add devices
2
Duplicate MAC ID Some other device has the same MAC ID Check MAC Addresses
3
Baudrate fault
Option card notices traffic, but can’t lock
to the selected baudrate.
Check Baudrate
Table 8-3. BACnet specific faults
Page 25
fault tracking vacon • 25
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
The MSTP- and BACnet-stack on the option board uses files from BACnetSim, a GPL'd project on SourceForge. The licence for BACnetSim is GPL with a special exception that allows linking without requiring the rest of the code to be GPL'd. The source code for the GPL'd parts can be downloaded from SourceForge.
Page 26
Document ID:
Rev. A
Manual authoring: documentation@vacon.com
Vacon Plc. Runsorintie 7 65380 Vaasa Finland
Subject to change without prior notice © 2012 Vacon Plc.
Find your nearest Vacon office
on the Internet at:
www.vacon.com
Find your nearest Vacon service centre
on the Extranet at:
www.extra.vacon.com
Loading...