NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from www.vacon.com/downloads
.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde
applicables sur le site www.vacon.com/downloads
.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
vacon • 5Basic Application
1.BASIC APPLICATION
Software code: ASFIFF01
1.1Introduction
The Basic Application is a simple and easy-to-use application. It is the default setting on delivery
S6.2
from the factory. Otherwise select the Basic Application in menu M6 on page
User's Manual.
Digital input DIN3 is programmable.
The parameters of the Basic Application are explained in Chapter of this manual. The explanations
are arranged according to the individual ID number of the parameter.
1.1.1Motor protection functions in the Basic Application
The Basic Application provides almost all the same protection functions as the other applications:
•External fault protection
•Input phase supervision
•Undervoltage protection
•Output phase supervision
•Earth fault protection
•Motor thermal protection
•Thermistor fault protection
•Fieldbus fault protection
•Slot fault protection
Unlike the other applications, the Basic Application does not provide any parameters for choosing
the response function or limit values for the faults. The motor thermal protection is explained in
more detail on pages 200.
. See the product's
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Basic Application vacon • 6
Reference potentiometer,
1…10 k
Jum pe r b l o ck X 3 :
CMA a nd CMB grounding
CMB connected to GND
CM A connected to G ND
CMB isolated from GN D
CMA i solated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
: See jumper selections below.
More information in the product's
User's Manual.
3AI1-I/O GroundGround for reference and controls
4AI2+Analogue input 2Analogue input 2 frequency reference
5AI2-Current range 0—20mA
6+24VControl voltage outputVoltage for switches, etc. max 0.1 A
7GNDI/O groundGround for reference and controls
8DIN1Start forwardContact closed = start forward
9DIN2Start reverseContact closed = start reverse
10DIN3External fault input Programma-
11CMACommon for DIN 1—DIN 3Connect to GND or +24V
12+24VControl voltage outputVoltage for switches (see #6)
13GNDI/O groundGround for reference and controls
14DIN4Preset speed select 1DIN4
15DIN5Preset speed select 2Open
16DIN6Fault resetContact open = no action
17CMBCommon for DIN4—DIN6Connect to GND or +24V
18AO1+Analogue output 1
I/O ref (P2.14)
Preset speed1
Preset speed 2
Max frequency
, max. 500
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 1.
1
vacon • 7Basic Application
DI N4
DI N5
AI1
AI2
DI N1
DI N2
DI N6
DI N3
>1
3.2 Key p ad re fe renc e
3.1 Co ntro l pl ace
Internal frequency
reference
Start forward
Start reverse
Start/Stop and
reverse logic
Start/Stop
Rev ers e
Internal Start/ Stop
Internal reverse
Internal fault reset
Fault r eset input
External fault input (programmable)
Reset button
Start/Stop buttons
Reference from fieldbus
Start/Stop from fieldbus
Direction from fieldbus
3.3 Keypad direction
2.1 4 I/O Ref ere nce
2.19 Preset Speed 2
2.18 Preset Speed 1
2.2 Max Frequenc y
7075.emf
1.3Control signal logic in Basic Application
Figure 2. Control signal logic of the Basic Application
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Basic Application vacon • 8
1.4Basic Application – Parameter lists
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 131 to pages 230.
Column explanations:
Code = Location indication on the keypad; Shows the operator the present parameter number
Parameter = Name of parameter
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; Given if available
Default = Value preset by factory
Cust = Customer’s own setting
ID = ID number of the parameter
= Parameter value can only be changed after the frequency converter has been stopped.
1.4.1Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See the product's User's Manual for more information.
Table 2. Monitoring values
CodeParameterUnitIDDescription
V1.1Output frequencyHz1Output frequency to motor
V1.2Frequency referenceHz25
V1.3Motor speedrpm2Motor speed in rpm
V1.4Motor currentA3
V1.5Motor torque%4Calculated shaft torque
V1.6Motor power%5Motor shaft power
V1.7Motor voltageV6
V1.8DC link voltageV7
V1.9Unit temperature
V1.10Motor temperature%9Calculated motor temperature
V1.11Analogue input 1V/mA13AI1
V1.12Analogue input 2V/mA14AI2
V1.13DIN1, DIN2, DIN315Digital input statuses
V1.14DIN4, DIN5, DIN616Digital input statuses
V1.15DO1, RO1, RO217Digital and relay output statuses
V1.16
M1.17Multimonitoring items
Analogue I
out
C
mA26AO1
Frequency reference to motor
control
8Heatsink temperature
Displays three selectable monitoring values
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
vacon • 9Basic Application
1.4.2Basic parameters (Control keypad: Menu M2 -> G2.1)
Table 3. Basic parameters G2.1
CodeParameterMinMaxUnitDefaultCustIDNote
P2.1Min frequency0,00P2.2Hz0,00101
NOTE: If f
P2.2Max frequencyP2.1320,00Hz50,00102
chronous speed, check suitability
for motor and drive system
P2.3Acceleration time 10,13000,0s3,0103
P2.4Deceleration time 10,13000,0s3,0104
P2.5Current limit
P2.6
P2.7
Nominal voltage of
the motor
Nominal frequency
of the motor
0,1 x I
2 x I
H
A
H
180690V
8,00320,00Hz50,00111
I
L
NX2:230V
NX5:400V
NX6:690V
107
Check the rating plate of the
110
motor.
Check the rating plate of the
motor.
Check the rating plate of the
motor.
The default applies for a 4-pole
motor and a nominal size fre-
P2.8
Nominal speed of
the motor
2420 000rpm1440112
quency converter.
P2.9
Nominal current of
the motor
0,1 x I
2 x I
H
A
H
I
H
Check the rating plate of the
113
motor.
P2.10Motor cos0,301,000,85120 Check the rating plate of the motor
4 = Output current (0-I
5 = Motor torque (0—T
6 = Motor power (0—P
7 = Motor voltage (0-U
8 = DC-link volt (0—1000V)
0 = Not used
1 = Ext. fault, closing cont.
2 = Ext. fault, opening cont.
P2.17DIN3 function071301
3 = Run enable, cc
4 = Run enable, oc
5 = Force cp. to IO
6 = Force cp. to keypad
7 = Force cp. to fieldbus
> than the motor syn-
max
)
max
max
nMotor
nMotor
nMotor
nMotor
)
)
)
)
)
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Basic Application vacon • 10
Table 3. Basic parameters G2.1
CodeParameterMinMaxUnitDefaultCustIDNote
P2.18Preset speed 10,00P2.2Hz0,00105 Speeds preset by operator
P2.19Preset speed 20,00P2.2Hz50,00106 Speeds preset by operator
P2.20Automatic restart010731
0 = Disabled
1 = Enabled
1.4.3Keypad control (Control keypad: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See
the Keypad control menu in the product's User's Manual.
Table 4.
CodeParameterMinMaxUnitDefaultCustIDNote
P3.1Control place131125
P3.2Keypad referenceP2.1P2.2Hz
P3.3Direction (on keypad)
R3.4Stop button
010123
011114
Keypad control parameters, M3
1 = I/O terminal
2 = Keypad
3 = Fieldbus
Reverse request activated
from the panel
0 = Limited function of Stop
button
1 = Stop button always
enabled
1.4.4System menu (Control keypad: Menu M6)
For parameters and functions related to the general use of the frequency converter, such as application and language selection, customised parameter sets or information about the hardware and
software, see the product's User's Manual.
1.4.5Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more information, see the product's User's Manual.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
vacon • 11Standard Application
2.STANDARD APPLICATION
Software code: ASFIFF02
2.1Introduction
Select the Standard Application in menu M6 on page
The Standard Application is typically used in pump and fan applications and conveyors for which the
Basic Application is too limited but where no special features are needed.
•The Standard Application has the same I/O signals and the same control logic as the Basic
Application.
•Digital input DIN3 and all the outputs are freely programmable.
Additional functions:
•Programmable Start/Stop and Reverse signal logic
•Reference scaling
•One frequency limit supervision
•Second ramps and S-shape ramp programming
•Programmable start and stop functions
•DC-brake at stop
•One prohibit frequency area
•Programmable U/f curve and switching frequency
•Autorestart
•Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Standard Application are explained in Chapter 8 of this manual. The explanations are arranged according to the individual ID number of the parameter.
S6.2
.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Standard Applicationvacon • 12
Reference potentiometer,
1…10 k
Jum p e r b l ock X 3 :
CM A and CMB grounding
CMB co nnected to GN D
CMA connected to GN D
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
inter nall y connected together,
isolated from GN D
= Factory default
Note: See jumper selections below.
More information in the product's
User's Manual.
7076.emf
RUN
2.2Control I/O
Table 5. Standard application default I/O configuration
OPTA1
TerminalSignalDescription
READY
mA
1+10V
2AI1+Analogue input 1
3AI1-I/O GroundGround for reference and controls
4AI2+Analogue input 2
5AI26+24VControl voltage outputVoltage for switches, etc. max 0.1 A
7GNDI/O groundGround for reference and controls
8DIN1 Start forward
9DIN2Start reverse
10DIN3 External fault input Programmable
11CMACommon for DIN 1—DIN 3Connect to GND or +24V
12+24VControl voltage outputVoltage for switches (see #6)
13GNDI/O groundGround for reference and controls
14DIN4 Preset speed select 1DIN4DIN5Frequency ref.
DIN5 Preset speed select 2Open
15
16DIN6 Fault resetContact open = no action
17CMB Common for DIN4—DIN6Connect to GND or +24V
18AO1+ Analogue output 1
19AO1-
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 3.
2
vacon • 13Standard Application
DIN4
DIN5
AI1
AI2
DIN1
DIN2
DIN6
DIN3
>1
3.2Keypadreference
2.1. 11 I/O Ref ere n ce
2.1.12 Keypad Ctrl Reference
2.1. 13 F ie ldbus C trl R eferen ce
2.1. 14 Pre set Spee d 1
2.1. 15 Pre set Spee d 2
3.1 Co n tr o l pla ce
Inte rnal fre quen cy
reference
Start forward
(programmable)
Start reverse (programmable)
Programmable
Start/Stop and
reverse logic
Start/Stop
Rev e rse
Internal Start/Stop
Internal re verse
Inte rnal fau lt reset
Fault reset inp ut
External fault input (programmable)
Reset bu tto n
Start/Stop buttons
Refe r ence f rom fi eldbus
Start/Stop f rom fi eldbu s
Direction from fieldbus
3.3 Keypad direction
7077.emf
2.3Control signal logic in Standard Application
Figure 4. Control signal logic of the Standard Application
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Standard Applicationvacon • 14
2.4Standard Application – Parameter lists
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on Pages 131 to230. The descriptions are arranged according to
the ID number of the parameter.
Column explanations:
Code= Location indication on the keypad; Shows the operator the present parameter
number
Parameter= Name of parameter
Min= Minimum value of parameter
Max= Maximum value of parameter
Unit= Unit of parameter value; Given if available
Default= Value preset by factory
Cust= Customer’s own setting
ID= ID number of the parameter
= In parameter row: Use TTF method to program these parameters.
= On parameter code: Parameter value can only be changed after the frequency
converter has been stopped.
2.4.1Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See the product's User's Manual for more information.
Table 6. Monitoring values
CodeParameterUnitIDDescription
V1.1Output frequencyHz1Output frequency to motor
V1.2Frequency referenceHz25Frequency reference to motor control
V1.3Motor speedrpm2Motor speed in rpm
V1.4Motor currentA3
V1.5Motor torque%4Calculated shaft torque
V1.6Motor power%5Motor shaft power
V1.7Motor voltageV6
V1.8DC link voltageV7
V1.9Unit temperature
V1.10Motor temperature%9Calculated motor temperature
V1.11Analogue input 1V/mA13AI1
V1.12Analogue input 2V/mA14AI2
V1.13DIN1, DIN2, DIN315Digital input statuses
V1.14DIN4, DIN5, DIN616Digital input statuses
V1.15DO1, RO1, RO217Digital and relay output statuses
V1.16
M1.17Monitoring itemsDisplays three selectable monitoring values
Analogue I
out
C
mA26AO1
8Heatsink temperature
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 15Standard Application
2.4.2Basic parameters (Control keypad: Menu M2 -> G2.1)
Table 7. Basic parameters G2.1
CodeParameterMinMaxUnitDefaultCustIDNote
P2.1.1Min frequency0,00P2.1.2Hz0,00101
P2.1.2Max frequencyP2.1.1 320,00Hz50,00102
P2.1.3 Acceleration time 10,13000,0s3,0103
P2.1.4 Deceleration time 10,13000,0s3,0104
P2.1.5Current limit
P2.1.6
P2.1.7
P2.1.8
P2.1.9
P2.1.10Motor cos0,301,000,85120
P2.1.11I/O reference030117
P2.1.12
P2.1.13
P2.1.14Preset speed 10,00P2.1.2Hz10,00105
P2.1.15Preset speed 20,00P2.1.2Hz50,00106
Nominal voltage of
the motor
Nominal frequency
of the motor
Nominal speed of
the motor
Nominal current of
the motor
Keypad control
reference
Fieldbus control
reference
0,1 x I
180690V
8,00320,00Hz50,00111
0,1 x I
2 x I
H
2420 000rpm1440112
2 x I
H
032121
033122
A
H
A
H
I
L
NX2: 230V
NX5: 400V
NX6: 690V
I
H
107
110
113
NOTE: If f
synchronous speed, check suit-
ability for motor and drive system
Check the rating plate of the
motor
The default applies for a 4-pole
motor and a nominal size frequency converter.
Check the rating plate of the
motor.
Check the rating plate of the
motor
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
0 = AI1
1= AI2
2 = Keypad
3 = Fieldbus
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
Speeds preset by operator
> than the motor
max
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Standard Applicationvacon • 16
2.4.3Input signals (Control keypad: Menu M2 -> G2.2)
Table 8. Input signals, G2.2
CodeParameterMinMaxUnit Default CustIDNote
DIN 1 DIN2
0
Start fwd
1
Start/Stop
2
Start/Stop
P2.2.1Start/Stop logic060300
P2.2.2DIN3 function081301
P2.2.3
P2.2.4
P2.2.5
P2.2.6Reference inversion010
P2.2.7Reference filter time 0,0010,00s0,103060 = No filtering
P2.2.8AI1 signal selectionA1377
P2.2.9AI2 signal selectionA2388
Analogue input 2
reference offset
Reference scaling
minimum value
Reference scaling
maximum value
011302
0,00
320,00Hz0,00
0,00
320,00Hz0,00304
3
Start pulse
4
Start fwd*
5
Start*/Stop
6
Start*/Stop
0 = Not used
1 = Ext. fault, closing cont.
2 = Ext. fault, opening cont.
3 = Run enable
4 = Acc./Dec. time select.
5 = Force cp. to IO
6 = Force cp. to keypad
7 = Force cp. to fieldbus
8 = Reverse
0 = 0—20mA (0—10V)**
1 = 4—20mA (2—10V)**
Selects the frequency that cor-
303
responds to the min. reference
signal
0,00 = No scaling
Selects the frequency that corresponds to the max. reference signal
0,00 = No scaling
3050 = Not inverted
1 = Inverted
TTF programming method
used. See page 72.
TTF programming method
used. See page 72.
Start rvs
Rvs/Fwd
Run enable
Stop pulse
Start rvs*
Rvs/Fwd
Run enable
* = Rising edge required to start
** = Remember to place jumpers of block X2 accordingly. See the product’s User Manual
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 17Standard Application
2.4.4Output signals (Control keypad: Menu M2 -> G2.3)
Table 9. Output signals, G2.3
CodeParameterMinMaxUnitDefault CustIDNote
P2.3.1
P2.3.2Analogue output function081307
P2.3.3Analogue output filter time0,0010,00s1,003080 = No filtering
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
0 = Fault stored in history
1 = Fault not stored
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 21Standard Application
Table 13. Protections, G2.7
CodeParameterMinMaxUnitDefault CustIDNote
0 = No response
P2.7.13Stall protection030709
P2.7.14Stall current0,00
P2.7.15Stall time limit1,00120,00s15,00711
P2.7.16Stall frequency limit1,0P2.1.2Hz25,0712
P2.7.17Underload protection030713
P2.7.18Field weakening area load10150%50714
P2.7.19Zero frequency load5,0150,0%10,0715
P2.7.20
P2.7.21 Response to thermistor fault032732
P2.7.22Response to fieldbus fault032733See P2.7.21
P2.7.23Response to slot fault032734See P2.7.21
Underload protection time
limit
2 x I
2600s20716
A
H
I
H
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
710
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Standard Applicationvacon • 22
2.4.9Autorestart parameters (Control keypad: Menu M2 -> G2.8)
Table 14. Autorestart parameters, G2.8
CodeParameterMinMax Unit Default CustIDNote
P2.8.1Wait time0,10 10,00s0,50717
P2.8.2Trial time0,00 60,00s30,00718
0 = Ramp
P2.8.3Start function020719
P2.8.4Number of tries after undervoltage trip0100720
P2.8.5Number of tries after overvoltage trip0100721
P2.8.6Number of tries after overcurrent trip030722
P2.8.7 Number of tries after 4mA reference trip0100723
P2.8.8
P2.8.9Number of tries after external fault trip0100725
P2.8.10
Number of tries after motor temperature
fault trip
Number of tries after underload fault
trip
0100726
0100738
1 = Flying start
2 = According to P2.4.6
2.4.10Keypad control (Control keypad: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See
the Keypad control menu in the product's User's Manual.
Table 15. Keypad control parameters, M3
CodeParameterMinMaxUnitDefault CustIDNote
1 = I/O terminal
P3.1Control place131125
R3.2Keypad referenceP2.1.1P2.1.2Hz
P3.3Direction (on keypad)010123
R3.4Stop button011114
2 = Keypad
3 = Fieldbus
0 = Forward
1 = Reverse
0 = Limited function of Stop button
1 = Stop button always enabled
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 23Standard Application
2.4.11System menu (Control keypad: M6)
For parameters and functions related to the general use of the frequency converter, such as application and language selection, customised parameter sets or information about the hardware and
software, see the product's User's Manual.
2.4.12Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more information, see the product's User's Manual.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Local/Remote Control Applicationvacon • 24
3.LOCAL/REMOTE CONTROL APPLICATION
Software code: ASFIFF03
3.1Introduction
Select the Local/Remote Control Application in menu M6 on page
Utilising the Local/Remote Control Application it is possible to have two different control places.
For each control place the frequency reference can be selected from either the control keypad, I/O
terminal or fieldbus. The active control place is selected with the digital input DIN6.
•All outputs are freely programmable.
Additional functions:
•Programmable Start/Stop and Reverse signal logic
•Reference scaling
•One frequency limit supervision
•Second ramps and S-shape ramp programming
•Programmable start and stop functions
•DC-brake at stop
•One prohibit frequency area
•Programmable U/f curve and switching frequency
•Autorestart
•Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Local/Remote Control Application are explained in Chapter 8 of this manual.
The explanations are arranged according to the individual ID number of the parameter.
S6.2
.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 25Local/Remote Control Application
Reference potentiometer,
1…10 k
Ju m p er b lo ck X 3 :
CM A and CMB grounding
CMB connected to GND
CM A connected to G ND
CMB isolated from GN D
CMA i solated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
Note: See jumper selections below.
More information in the product's
User's Manual.
7078.emf
RUN
3.2Control I/O
Table 16. Local/Remote control application default I/O configuration.
OPTA1
Ter min alSignalDescription
Remote Reference
0(4) - 20 mA
Remote Control ground
READY
mA
1+10V
2AI1+Analogue input 1
3AI1-I/O GroundGround for reference and controls
4AI2+Analogue input 2
5AI2-
6+24VControl voltage outputVoltage for switches, etc. max 0.1 A
7GNDI/O groundGround for reference and controls
8DIN1Place A: Start forward
9DIN2Place A: Start reverse
10DIN3External fault input Programmable
11CMACommon for DIN 1—DIN 3Connect to GND or +24V
12+24VControl voltage outputVoltage for switches (see #6)
13GNDI/O groundGround for reference and controls
14DIN4Place B: Start forward
15DIN5Place B: Start reverse
16DIN6Place A/B selectionContact open = place A is active
17CMBCommon for DIN4—DIN6Connect to GND or +24V
18AO1+Analogue output 1
19AO1-
Range 0—20 mA/R
Output frequency
Programmable (P2.3.2)
Open collector, I50mA, U48 VDC
READY
Programmable (P2.3.7)
RUN
Programmable (P2.3.8)
FAU LT
Programmable (P2.3.9)
, max. 500
L
3
Figure 5.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Local/Remote Control Applicationvacon • 26
DIN3
>1
DIN6
DIN2
DIN3
AI1
AI2
DIN1
DIN2
DIN3
DIN4
DIN5
A
B
A
B
A
B
Inte rnal re ve rse
Internal fault reset
Fa ult res e t in put (pro gram mabl e)
3.3 Key pad direc ti o n
Inte rna l Start /Stop
Reference from fieldbu s
Start/Sto p from fieldbu s
Direction from fieldb us
St art/ St op bu ttons
Internal
fr equ ency ref .
Reset button
Pr ogra mm able
Start/Sto p and
re ver se l og ic A
Pr ogra mm able
Start/Sto p and
re ver se l og ic B
Start forward
(pro grammable)
Start reverse
(programmable)
St art f or ward
Start rever se
( prog ramma ble )
( prog ramma ble )
Start/Stop
Revers e
Up
Down
3.1 C on tro l pla ce
2. 1.1 5 Jo ggi ng spe ed ref .
2.1.14 F i eldb us C trl r efer en c e
2.1.13 K eypa d C trl referen ce
2. 1. 12 I /O B refe renc e
2.1.11 I/O A refer ence
R3.2 Keypad referen ce
Moto r
potentiomete r
7079.emf
3.3Control signal logic in Local/Remote Application
Figure 6. Control signal logic of the Local/Remote Control Application
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 27Local/Remote Control Application
3.4Local/Remote control application – Parameter lists
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 131 to 229.
Column explanations:
Code= Location indication on the keypad; Shows the operator the present parameter
number
Parameter= Name of parameter
Min= Minimum value of parameter
Max= Maximum value of parameter
Unit= Unit of parameter value; Given if available
Default= Value preset by factory
Cust= Customer’s own settings
ID= ID number of the parameter
= In parameter row: Use TTF method to program these parameters.
= On parameter number: Parameter value can only be changed after the frequency
converter has been stopped.
3.4.1Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited. See the product's User's Manual for more information.
Table 17. Monitoring values
CodeParameterUnitIDDescription
V1.1Output frequencyHz1Output frequency to motor
V1.2Frequency referenceHz25
V1.3Motor speedrpm2Motor speed in rpm
V1.4Motor currentA3
V1.5Motor torque%4Calculated shaft torque
V1.6Motor power%5Motor shaft power
V1.7Motor voltageV6
V1.8DC link voltageV7
V1.9Unit temperature
V1.10Motor temperature%9
V1.11Analogue input 1V/mA13AI1
V1.12Analogue input 2V/mA14AI2
C
Frequency reference to
motor control
8Heatsink temperature
Calculated motor
temperature
3
V1.13DIN1, DIN2, DIN315Digital input statuses
V1.14DIN4, DIN5, DIN616Digital input statuses
V1.15DO1, RO1, RO217
V1.16
M1.17
Analogue I
Multimonitoring
items
out
mA26AO1
Digital and relay output
statuses
Displays three selectable
monitoring values
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Local/Remote Control Applicationvacon • 28
3.4.2Basic parameters (Control keypad: Menu M2 -> G2.1)
Table 18. Basic parameters G2.1
CodeParameterMinMaxUnitDefaultCustIDNote
P2.1.1Min frequency0,00P2.1.2Hz0,00101
P2.1.2Max frequencyP2.1.1320,00Hz50,00102
P2.1.3Acceleration time 10,13000,0s3,0103
P2.1.4Deceleration time 10,13000,0s3,0104
P2.1.5Current limit
P2.1.6
P2.1.7
P2.1.8
P2.1.9
P2.1.10Motor cos0,301,000,85120
P2.1.11I/O A reference041117
P2.1.12I/O B reference040131
P2.1.13
P2.1.14
P2.1.15
Nominal voltage of the
motor
Nominal frequency of
the motor
Nominal speed of the
motor
Nominal current of the
motor
Keypad control refer-
ence
Fieldbus control refer-
ence
Jogging speed refer-
ence
0,1 x I
180690V
8,00320,00Hz50,00111
2420 000rpm1440112
0,1 x I
03 2121
03 3122
0,00P2.1.2Hz0,00 124
2 x I
H
2 x I
H
A
H
A
H
I
L
NX2:
230V
NX5:
400V
NX6:
690V
I
H
107
110
113
NOTE: If f
motor synchronous speed,
check suitability for motor
and drive system
Check the rating plate of
the motor
The default applies for a 4pole motor and a nominal
size frequency converter.
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
0 = Fault stored in history
1 = Fault not stored
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
710
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Local/Remote Control Applicationvacon • 36
Table 24. Protections, G2.7
CodeParameterMinMaxUnitDefault CustIDNote
P2.7.16Stall frequency limit1,0P2.1.2Hz25,0712
0 = No response
P2.7.17Underload protection030713
P2.7.18Field weakening area load10150%50714
P2.7.19Zero frequency load5,0150,0%10,0715
P2.7.20
P2.7.21
P2.7.22Response to fieldbus fault032733 See P2.7.21
P2.7.23Response to slot fault03734 See P2.7.21
Underload protection time
limit
Response to thermistor
fault
2600s20716
032732
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 37Local/Remote Control Application
3.4.9Autorestart parameters (Control keypad: Menu M2 -> G2.8)
Table 25. Autorestart parameters, G2.8
Code
P2.8.1Wait time0,1010,00s0,50717
P2.8.2Trial time0,0060,00s30,00718
P2.8.3Start function020719
P2.8.4
P2.8.5
P2.8.6
P2.8.7
P2.8.8
P2.8.9
P2.8.10
Parameter
Number of tries after
undervoltage trip
Number of tries after
overvoltage trip
Number of tries after
overcurrent trip
Number of tries after
4mA reference trip
Number of tries after
motor temp fault trip
Number of tries after
external fault trip
Number of tries after
underload fault trip
MinMaxUnitDefault
0100720
0100721
030722
0100723
0100726
0100725
0100
Cust
738
IDNote
0 = Ramp
1 = Flying start
2 = According to P2.4.6
3.4.10Keypad control (Control keypad: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See
the Keypad control menu in the product's User's Manual.
Table 26. Keypad control parameters, M3
CodeParameterMinMaxUnit Default CustIDNote
1 = I/O terminal
P3.1Control place131125
P3.2Keypad referenceP2.1.1 P2.1.2Hz
P3.3Direction (on keypad)010123
R3.4Stop button011114
2 = Keypad
3 = Fieldbus
0 = Forward
1 = Reverse
0 = Limited function of Stop button
1 = Stop button always enabled
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Local/Remote Control Applicationvacon • 38
3.4.11System menu (Control keypad: Menu M6)
For parameters and functions related to the general use of the frequency converter, such as application and language selection, customised parameter sets or information about the hardware and
software, see the product's User's Manual.
3.4.12Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more information, see the product's User's Manual.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 39Multi-step Speed Control Application
4.MULTI-STEP SPEED CONTROL APPLICATION
Software code: ASFIFF04
4.1Introduction
Select the Multi-step Speed Control Application in menu M6 on page
The Multi-step Speed Control Application can be used in applications where fixed speeds are needed. Totally 15 + 2 different speeds can be programmed: one basic speed, 15 multi-step speeds and
one jogging speed. The speed steps are selected with digital signals DIN3, DIN4, DIN5 and DIN6. If
jogging speed is used, DIN3 can be programmed from fault reset to jogging speed select.
The basic speed reference can be either voltage or current signal via analogue input terminals (2/
3 or 4/5). The other one of the analogue inputs can be programmed for other purposes.
•All outputs are freely programmable.
Additional functions:
•Programmable Start/Stop and Reverse signal logic
•Reference scaling
•One frequency limit supervision
•Second ramps and S-shape ramp programming
•Programmable start and stop functions
•DC-brake at stop
•One prohibit frequency area
•Programmable U/f curve and switching frequency
•Autorestart
•Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Multi-Step Speed Control Application are explained in Chapter 8 of this manual. The explanations are arranged according to the individual ID number of the parameter.
S6.2
.
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-step Speed Control Application vacon • 40
Reference potentiometer,
1…10 k
Basic reference
(optional)
Ju m p er b lo ck X 3 :
CM A and CMB grounding
CMB connected to GND
CM A connected to G ND
CMB isolated from GN D
CMA i solated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
Note: See jumper selections below.
Moreinformationintheproduct's
User's Manual.
7080.emf
RUN
4.2Control I/O
Table 27. Multi-step speed control application default I/O configuration.
OPTA1
TerminalSignalDescription
READY
mA
1+10V
2AI1+Analogue input 1.
3AI1-I/O GroundGround for reference and controls
4AI2+Analogue input 2.
5AI2-
6+24VControl voltage outputVoltage for switches, etc. max 0.1 A
7GNDI/O groundGround for reference and controls
8DIN1Start forward
9DIN2Start reverse
10DIN3External fault input Programma-
11CMACommon for DIN 1—DIN 3Connect to GND or +24V
12+24VControl voltage outputVoltage for switches (see #6)
13GNDI/O groundGround for reference and controls
14DIN4Preset speed select 1sel 10sel 2
15DIN5Preset speed select 21
16DIN6Preset speed select 3- - - - - -
17CMBCommon for DIN4—DIN6Connect to GND or +24V
18AO1+Analogue Output 1:
19AO1-
Range 0—20 mA/R
Output frequency
Programmable (P2.3.2)
Open collector, I50mA, U48 VDC
READY
Programmable (P2.3.7)
Programmable
RUN
Programmable (P2.3.8)
Programmable
FAU LT
Programmable (P2.3.9)
, max. 500
L
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 7.
4
vacon • 41Multi-step Speed Control Application
DIN4
DIN5
AI1
AI2
DIN1
DIN2
DIN3
>1
DIN6
DIN3
DIN3
3.2 Keypad reference
2.1.11 I/O Reference
2.1.12 Keypad Ctrl Reference
2.1.13 Fieldbus Ctrl Reference
2.1.15 Preset Speed 1
...2.1.29 Pre set Speed 15
3.1 Control place
Internal frequency
reference
Start forward
(programmable)
Start reverse (programmable)
Programmable
Start/Stop and
reverse logic
Start/Stop
Reverse
Internal Start/Stop
Internal reverse
Internal fault reset
Fault reset input
Reset button
Start/Stop buttons
Reference from fieldbus
Start/Stop from fieldbus
Direction from fieldbus
3.3 Keypad direction
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
2.1.14 Jogging speed
reference
(programmable)
7081.emf
4.3Control signal logic in Multi-Step Speed Control Application
Figure 8. Control signal logic of the Multi-step Speed Application
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-step Speed Control Application vacon • 42
4.4Multi-step speed control application – Parameter lists
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 131 to 229.
Column explanations:
Code= Location indication on the keypad; Shows the operator the present parameter
number
Parameter= Name of parameter
Min= Minimum value of parameter
Max= Maximum value of parameter
Unit= Unit of parameter value; Given if available
Default= Value preset by factory
Cust= Customer’s own setting
ID= ID number of the parameter
= In parameter row: Use TTF method to program these parameters.
= On parameter code: Parameter value can only be changed after the frequency
converter has been stopped.
4.4.1Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See the product's User's Manual for more information.
Table 28. Monitoring values
CodeParameterUnitIDDescription
V1.1Output frequencyHz1Output frequency to motor
V1.2Frequency referenceHz25Frequency reference to motor control
V1.3Motor speedrpm2Motor speed in rpm
V1.4Motor currentA3
V1.5Motor torque%4Calculated shaft torque
V1.6Motor power%5Motor shaft power
V1.7Motor voltageV6
V1.8DC link voltageV7
V1.9Unit temperatureC8Heatsink temperature
V1.10Motor temperature%9Calculated motor temperature
V1.11Analogue input 1V/mA13AI1
V1.12Analogue input 2V/mA14AI2
V1.13DIN1, DIN2, DIN315Digital input statuses
V1.14DIN4, DIN5, DIN616Digital input statuses
V1.15DO1, RO1, RO217Digital and relay output statuses
V1.16
M1.17Multimonitoring itemsDisplays three selectable monitoring values
Analogue I
out
mA26AO1
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
vacon • 43Multi-step Speed Control Application
4.4.2Basic parameters (Control keypad: Menu M2 -> G2.1)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
vacon • 51Multi-step Speed Control Application
4.4.8Protections (Control keypad: Menu M2 -> G2.7)
Table 35. Protections, G2.7
CodeParameterMinMaxUnitDefaultCustIDNote
0 = No response
1 = Warning
P2.7.1
P2.7.2
P2.7.3
P2.7.4
P2.7.5
P2.7.6
P2.7.7
P2.7.8
P2.7.9
P2.7.10
P2.7.11
P2.7.12Motor duty cycle0150%100708
P2.7.13Stall protection030709
P2.7.14Stall current0,00
P2.7.15Stall time limit1,00120,00s15,00711
P2.7.16
P2.7.17
P2.7.18
P2.7.19 Zero frequency load5,0150,0%10,0715
P2.7.20
P2.7.21
P2.7.22
P2.7.23
Response to 4mA
reference fault
4mA refe rence fault
frequency
Response to
external fault
Input phase
supervision
Response to under-
voltage fault
Output phase
supervision
Earth fault
protection
Thermal protection
of the motor
Motor ambient
temperature factor
Motor cooling fac-
tor at zero speed
Motor thermal time
constant
Stall frequency
limit
Underload protec-
tion
Field weakening
area load
Underload protec-
tion time limit
Response to
thermistor fault
Response to field-
bus fault
Response to slot
fault
05 0700
0,00P2.1.2Hz0,00728
03 2701
03 0730
01 0727
03 2702
03 2703
03 2704
–100,0100,0%0,0705
0,0150,0%40,0706
1200minVaries707
2 x I
1,0P2.1.2Hz25,0712
03 0713
10150%50714
2600s20716
03 2732
032733See P2.7.21
032734See P2.7.21
A
H
I
H
2 = Warning+Previous Freq.
3 = Wrng+PresetFreq 2.7.2
4 = Fault,stop acc. to 2.4.7
5 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
0 = Fault stored in history
1 = Fault not stored
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
710
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-step Speed Control Application vacon • 52
4.4.9Autorestart parameters (Control keypad: Menu M2 -> G2.8)
Table 36. Autorestart parameters, G2.8
Code
P2.8.1
P2.8.2Trial time0,0060,00s30,00718
P2.8.3Start function020719
P2.8.4
P2.8.5
P2.8.6
P2.8.7
P2.8.8
P2.8.9
P2.8.10
Parameter
Wait time0,1010,00s0,50717
Number of tries after
undervoltage trip
Number of tries after
overvoltage trip
Number of tries after
overcurrent trip
Number of tries after
4mA reference trip
Number of tries after
motor temp fault trip
Number of tries after
external fault trip
Number of tries after
underload fault trip
MinMaxUnitDefaultCustIDNote
0100720
0100721
030722
0100723
0100726
0100725
0100738
0 = Ramp
1 = Flying start
2 = According to P2.4.6
4.4.10Keypad control (Control keypad: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See
the Keypad control menu in the product's user's manual.
Table 37. Keypad control parameters, M3
CodeParameterMinMaxUnit Default
P3.1Control place131125
P3.2Keypad referenceP2.1.1 P2.1.2Hz
P3.3Direction (on keypad)010123
R3.4Stop button011114
Cust
IDNote
1 = I/O terminal
2 = Keypad
3 = Fieldbus
0 = Forward
1 = Reverse
0 = Limited function of Stop button
1 = Stop button always enabled
4.4.11System menu (Control keypad: M6)
For parameters and functions related to the general use of the frequency converter, such as application and language selection, customised parameter sets or information about the hardware and
software, see the product's user's manual.
4.4.12Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more information, see the product's user's manual.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
vacon • 53PID Control Application
5.PID CONTROL APPLICATION
Software code: ASFIFF05
5.1Introduction
Select the PID Control Application in menu M6 on page
In the PID Control Application, there are two I/O terminal control places; place A is the PID controller and source B is the direct frequency reference. The control place A or B is selected with digital
input DIN6.
The PID controller reference can be selected from the analogue inputs, fieldbus, motorised potentiometer, enabling the PID Reference 2 or applying the control keypad reference. The PID controller
actual value can be selected from the analogue inputs, fieldbus, the actual values of the motor or
through the mathematical functions of these.
The direct frequency reference can be used for the control without the PID controller and selected
from the analogue inputs, fieldbus, motor potentiometer or keypad.
The PID Application is typically used to control level measuring or pumps and fans. In these applications, the PID Application provides a smooth control and an integrated measuring and controlling
package where no additional components are needed.
•Digital inputs DIN2, DIN3, DIN5 and all the outputs are freely programmable.
Additional functions:
•Analogue input signal range selection
•Two frequency limit supervisions
•Torque limit supervision
•Reference limit supervision
•Second ramps and S-shape ramp programming
•Programmable start and stop functions
•DC-brake at start and stop
•Three prohibit frequency areas
•Programmable U/f curve and switching frequency
•Autorestart
•Motor thermal and stall protection: fully programmable; off, warning, fault
•Motor underload protection
•Input and output phase supervision
•Sum point frequency addition to PID output
•The PID controller can additionally be used from control places I/O B, keypad and fieldbus
•Easy ChangeOver function
•Sleep function
S6.2
.
5
The parameters of the PID Control Application are explained in Chapter 8 of this manual. The explanations are arranged according to the individual ID number of the parameter.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
PID Control Application vacon • 54
Reference potentiometer,
1…10 k
Ju m p er b lo ck X 3 :
CM A and CMB grounding
CMB connected to GND
CM A connected to G ND
CMB isolated from GN D
CMA i solated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
Note: See jumper selections below.
Moreinformationintheproduct's
user's manual.
Voltage for potentiometer, etc.
Voltage range 0—10V DC
Programmable (P2.1.11)
3AI1- I/O GroundAnalogue input 1 PID reference
4AI2+ Analogue input 2
5AI2-Analogue input 2 PID actual value 1
Current range 0—20mA
Ground for reference and controls
Programmable (P2.2.9)
6+24V Control voltage output
7GND I/O groundVoltage for switches, etc. max 0.1 A
8DIN1 Place A: Start forward
R
min. = 5k
i
9DIN2 External fault input
Programmable (P2.2.1)
10DIN3 Fault reset
Programmable (P2.2.2)
Ground for reference and controls
Start signal for control place A
PID Controller.
Contact closed = fault
Contact open = no fault
11CMA Common for DIN 1—DIN 3Contact closed = fault reset
12+24V Control voltage outputConnect to GND or +24V
13GND I/O groundVoltage for switches (see #6)
14DIN4 Place B: Start forward
R
min. = 5k
i
15DIN5 Jogging speed selection
Programmable (P2.2.3)
Ground for reference and controls
Start signal for control place B
Frequency reference (P2.2.5.)
16DIN6 Control place A/B selectionContact closed = Jogging speed active
17CMB Common for DIN4—DIN6Contact open = Control place A is
active
Contact closed = Control place B is
active
18AO1+ Analogue output 1
19AO1-Range 0—20 mA/R
Output frequency
Programmable (P2.3.2)
20DO1Digital output
Connect to GND or +24V
, max. 500
L
Open collector, I50mA, U48 VDC
READY
Programmable (P2.3.7)
OPTA2
21RO1Relay output 1
22RO1
23RO1
Programmable (P2.3.8)
RUN
24RO2Relay output 2
25RO2
26RO2
Programmable (P2.3.9)
FAU LT
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 9.
5
vacon • 55PID Control Application
DI N2
DI N5
DI N3
>1
DI N2
DI N3
DI N5
DI N6
DI N2
DI N3
AI1
AI2
0
1
2
3
4
0
1
2
3
4
5
+A
A
B
0
1
2
3
4
5
0
1
2
3
4
5
K
0
1
2
3
4
5
F
PID
+
DIN1
DIN4
A
B
A
B
A/B
Internal revers e
Internal fault reset
Fault reset input (programmable)
3. 3 Key pad dire ction
Internal Start/Stop
Reference from fieldbus
Start/Stop fro m fieldbus
Direct ion from fi eldbus
External fault (programmable)
Jogging speed (programmable)
Place A/B selection
2. 2.4 PID main re fer ence
Motor
potentiomet er
Up
Do wn
2.1. 11 PID r efe rence
I/O revers e
R3.4 PID keypad refer.
R3.2 Keypad reference
Actual values
sel ect ion, par.
2.2.9 & 2.2.10
Actua l value
select ion par . 2.2 .8
Act 1
Act 2
R3.5 PID keypad ref. 2
Enabl e PID k eypad re f. 2 ( DI N5=13)
Start; Place A
Start ; Place B
Start/Stop
Star t/Sto p b utton s
Inter nal
frequency ref.
2. 1.1 9 Jog ging s peed r ef.
Key pad
Fieldbus
Reset button
3.1 Control place
2.2.7 Fieldbus Ctrl Reference
2.2.6 Keypad Crtl Reference
2.2.5 I/O B Reference
7083.emf
5.3Control signal logic in PID Control Application
Figure 10.Control signal logic of the PID Control Application
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
PID Control Application vacon • 56
5.4PID Application – Parameter lists
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 131 to 229.
Column explanations:
Code = Location indication on the keypad; Shows the operator the present param. number
Parameter = Name of parameter
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; Given if available
Default = Value preset by factory
Cust = Customer’s own setting
ID = ID number of the parameter
= In parameter row: Use TTF method to program these parameters.
= On code: Parameter value can only be changed after the FC has been stopped.
5.4.1Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See the product's user's manual for more information. Note that the monitoring values V1.19 to
V1.22 are available with the PID control application only.
Table 39. Monitoring values
CodeParameterUnitIDDescription
V1.1Output frequencyHz1Output frequency to motor
V1.2Frequency referenceHz25Frequency reference to motor control
0 = Actual value 1
1 = Actual 1 + Actual 2
2 = Actual 1 – Actual 2
3 = Actual 1 * Actual 2
4 = Min(Actual 1, Actual 2)
5 = Max(Actual 1, Actual 2)
6 = Mean(Actual1, Actual2)
7 = Sqrt (Act1) + Sqrt (Act2)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
vacon • 59PID Control Application
Table 41. Input signals, G2.2
CodeParameterMinMaxUnitDefaultCustIDNote
0 = Not used
1 = AI1 signal (c-board)
2 = AI2 signal (c-board)
3 = AI3
P2.2.9
P2.2.10Actual value 2 input090335
P2.2.11
P2.2.12
P2.2.13
P2.2.14
P2.2.15AI1 signal selection0.1E.10A.1377
P2.2.16AI1 signal range020320
P2.2.17
P2.2.18
P2.2.19AI1 inversion010323
P2.2.20AI1 filter time0,0010,00s0,10324 0 = No filtering
P2.2.21AI2 signal selection0.1E.10A.2388
P2.2.22AI2 signal range021325
P2.2.23
P2.2.24
P2.2.25AI2 inversion000328
P2.2.26AI2 filter time
Actual value 1 selec-
tion
Actual value 1 mini-
mum scale
Actual value 1 maxi-
mum scale
Actual value 2 mini-
mum scale
Actual value 2 maxi-
mum scale
AI1 custom minimum
setting
AI1 custom maximum
setting
AI2 custom minimum
setting
AI2 custom maximum
setting
0102334
–1600,01600,0%0,0336 0 = No minimum scaling
–1600,01600,0%100,0337 100 = No maximum scaling
–1600,01600,0%0338 0 = No minimum scaling
–1600,0
-160,00160,00
-160,00160,00%100,0322
-160,00160,00
-160,00
0,0010,00
1600,0%100,0339
%0,00321
%0,00326
160,00%
s0,10329 0 = No filtering
0,00
4 = AI4
5 = Fieldbus
6 = Motor torque
7 = Motor speed
8 = Motor current
9 = Motor power
10 = Encoder frequency
0 = Not used
1 = AI1 signal
2 = AI2 signal
3 = AI3
4 = AI4
5 = Fieldbus
6 = Motor torque
7 = Motor speed
8 = Motor current
9 = Motor power
100 = No maximum scaling
TTF programming method
used. See page 72
0 = 0—10 V (0—20 mA*)
1 = 2—10 V (4 – 20 mA*)
2 = Custom range*
0 = Not inverted
1 = Inverted
0 = 0—20 mA (0—10 V *)
1 = 4 – 20 mA (2—10 V *)
2 = Custom range*
0 = 0—20 mA*
1 = 4—20 mA*
2 = Customised*
327
0 = Not inverted
1 = Inverted
ProcessDataIN2
ProcessDataIN3
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
PID Control Application vacon • 60
Table 41. Input signals, G2.2
CodeParameterMinMaxUnitDefaultCustIDNote
P2.2.27
P2.2.28
P2.2.29
P2.2.30PID minimum limit–1600,0P2.2.31%0,00359
P2.2.31PID maximum limitP2.2.301600,0%100,00360
P2.2.32Error value inversion010340
P2.2.33
P2.2.34
P2.2.35
Motor potentiometer
ramp time
Motor potentiometer
frequency reference
memory reset
Motor potentiometer
PID reference memory
reset
PID reference
rising time
PID reference
falling time
Reference scaling
minimum value, place B0,00320,00Hz0,00344
0,12000,0Hz/s10,0331
021367
020370
0,0100,0s5,0341
0,0100,0s5,0342
0 = No reset
1 = Reset if stopped or pow-
ered down
2 = Reset if powered down
0 = No reset
1 = Reset if stopped or pow
ered down
2 = Reset if powered down
0 = No inversion
1 = Inversion
Reference scaling
P2.2.36
P2.2.37Easy changeover010366
P2.2.38AI3 signal selection0.1E.100.1141
P2.2.39AI3 signal range011143
P2.2.40AI3 inversion010151
P2.2.41AI3 filter time0,0010,00s0,10142 0 = No filtering
P2.2.42AI4 signal selection0.1E.100.1152
P2.2.43AI4 signal range011154
P2.2.44AI4 inversion010162
P2.2.45AI4 filter time0,0010,00s0,10153 0 = No filtering
P2.2.46
P2.2.47
P2.2.48
P2.2.49
maximum value, place B0,00320,000,00345
Actual value special
display minimum
Actual value special
display maximum
Actual value special
display decimals
Actual value special
display unit
03000001033
0300001001034
0411035
02841036 See page 220 .
0 = Keep reference
1 = Copy actual reference
TTF programming method
used. See page 72
0 = Signal range 0—10V
1 = Signal range 2—10V
0 = Not inverted
1 = Inverted
TTF programming method
used. See page 72
0 = Signal range 0—10V
1 = Signal range 2—10V
0 = Not inverted
1 = Inverted
CP=control place, cc= contact oc=opening contact
*Remember to place jumpers of block X2 accordingly. See the product's User's Manual.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
vacon • 61PID Control Application
5.4.4 Output signals (Control keypad: Menu M2 -> G2.3)
Table 42. Output signals, G2.3
CodeParameterMinMaxUnitDefaultCustIDNote
P2.3.1
P2.3.2
P2.3.3
P2.3.4
P2.3.5
P2.3.6
P2.3.7
Analogue output 1
signal selection
Analogue output
function
Analogue output filter
time
Analogue output
inversion
Analogue output
minimum
Analogue output
scale
Digital output 1
function
0.1E.10A.1464
0141307
0,00
101000%100
10,00s1,00
01 0
01 0
0231
TTF programming method
used. See page 72
0 = Not used
1 = Output freq. (0—f
2 = Freq. reference (0—f
3 = Motor speed (0—Motor
nominal speed)
4 = Motor current (0—I
5 = Motor torque (0—T
6 = Motor power (0—P
7 = Motor voltage (0-U
8 = DC-link volt (0—1000V)
9 = PID controller ref. value
10 = PID contr. act. value 1
11 = PID contr. act. value 2
12 = PID contr. error value
13 = PID controller output
14 = PT100 temperature
308
0 = No filtering
0 = Not inverted
309
1 = Inverted
0 = 0 mA (0 V)
310
1 = 4 mA (2 V)
311
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat warning
6 = Ext. fault or warning
7 = Ref. fault or warning
8 = Warning
9 = Reversed
10 = Preset speed 1
11 = At speed
312
12 = Mot. regulator active
13 = OP freq. limit superv.1
14 = OP freq.limit superv.2
15 =Torque limit superv.
16 = Ref. limit supervision
17 = External brake control
18 = Control place: IO
19 = FC temp. limit superv.
20 = Unrequested direction
21 = Ext. brake control inv.
22 = Thermistor fault/warn.
23 = Fieldbus DIN1
max
nMotor
nMotor
nMotor
nMotor
)
max
)
)
)
)
)
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
PID Control Application vacon • 62
Table 42. Output signals, G2.3
CodeParameterMinMaxUnitDefaultCustIDNote
P2.3.8
P2.3.9Relay output 2 function0233314
Relay output 1
function
0232
As parameter 2.3.7
313
As parameter 2.3.7
P2.3.10
P2.3.11
P2.3.12
P2.3.13
P2.3.14
P2.3.15
P2.3.16
P2.3.17
P2.3.18
P2.3.19
P2.3.20
P2.3.21
P2.3.22
P2.3.23
P2.3.24
P2.3.25
P2.3.26
P2.3.27
Output frequency
limit 1 supervision
Output frequency
limit 1;
Supervised value
Output frequency
limit 2 supervision
Output frequency
limit 2;
Supervised value
Torque limit
supervision
Torque limit
supervision value
Reference limit
supervision
Reference limit
supervision
External
brake-off delay
External
brake-on delay
FC temperature
supervision
FC temperature
supervised value
Analogue output 2
signal selection
Analogue output 2
function
Analogue output 2
filter time
Analogue output 2
inversion
Analogue output 2
minimum
Analogue output 2
scaling
020315
0,00320,00Hz0,00316
0
0,00
0
-
300,0
020350
0,00100,00%0,00351
0,0100,0s0,5352
0,0100,0s1,5353
020354
–10
0.1E.100.1
0144472
0,0010,00s
01
01
101000%100476
20346
320,00
20348
300,0%100,0349
100
Hz
0,00347
C40355
471
1,00473
0474
0475
0 = No limit
1 = Low limit supervision
2 = High limit supervision
0 = No limit
1 = Low limit supervision
2 = High limit supervision
0 = Not used
1 = Low limit supervision
2 = High limit supervision
0 = Not used
1 = Low limit
2 = High limit
0 = Not used
1 = Low limit
2 = High limit
TTF programming method
used. See page .
As parameter 2.3.2
0 = No filtering
0 = Not inverted
1 = Inverted
0 = 0 mA
1 = 4 mA
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
vacon • 63PID Control Application
5.4.5Drive control parameters (Control keypad: Menu M2 -> G2.4)
Table 43. Drive control parameters, G2.4
CodePara meterMinMaxUnitDefault CustIDNote
P2.4.1Ramp 1 shape0,010,0s0,1500
P2.4.2Ramp 2 shape0,010,0s0,0501
P2.4.3Acceleration time 20,13000,0s0,1502
P2.4.4Deceleration time 20,13000,0s0,1503
P2.4.5Brake chopper040504
P2.4.6Start function020505
P2.4.7Stop function030506
P2.4.8DC braking current0,00
P2.4.9
P2.4.10
P2.4.11
P2.4.12Flux brake010520
P2.4.13Flux braking current0,00
DC braking time
at stop
Frequency to start DC
braking during
ramp stop
DC braking time
at start
0,00600,00s0,005080 = DC brake is off at stop
0,1010,00Hz1,50515
0,00600,00s0,005160 = DC brake is off at start
I
L
I
L
0,7 x I
A
A
H
I
H
507
519
0 = Linear
>0 = S-curve ramp time
0 = Linear
>0 = S-curve ramp time
0 = Disabled
1 = Used when running
2 = External brake chopper
3 = Used when stopped/running
4 = Used when running (no test-
5.4.8Protections (Control keypad: Menu M2 -> G2.7)
Table 46. Protections, G2.7
CodeParameterMinMaxUnitDefault CustIDNote
0 = No response
1 = Warning
P2.7.1
P2.7.2
P2.7.3
P2.7.4
Response to 4mA
reference fault
4mA reference fault
frequency
Response to external
fault
Input phase
supervision
054700
0,00P2.1.2Hz0,00728
032701
030730
2 = Warning+Previous Freq.
3 = Wrng+PresetFreq 2.7.2
4 = Fault,stop acc. to 2.4.7
5 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.7.5
P2.7.6
P2.7.7Earth fault protection032703
P2.7.8
P2.7.9
P2.7.10
P2.7.11
P2.7.12Motor duty cycle0150%100708
P2.7.13Stall protection031709
P2.7.14Stall current0,00
Response to
undervoltage fault
Output phase
supervision
Thermal protection of
the motor
Motor ambient
temperature factor
Motor cooling factor at
zero speed
Motor thermal time
constant
010727
032702
032704
–
100,0
0,0150,0%40,0706
100,0%0,0705
1200minVaries707
2 x I
A
H
I
H
710
0 = Fault stored in history
1 = Fault not stored
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.7.15Stall time limit1,00120,00s15,00711
P2.7.16Stall frequency limit1,0P2.1.2Hz25,0712
P2.7.17Underload protection030713
P2.7.18
P2.7.19Zero frequency load5,0150,0%10,0715
P2.7.20
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Field weakening area
load
Underload protection
time limit
10150%50714
2600s20716
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
5
vacon • 67PID Control Application
Table 46. Protections, G2.7
CodeParameterMinMaxUnitDefault CustIDNote
0 = No response
P2.7.21
P2.7.22
P2.7.23Response to slot fault032734See P2.7.21
P2.7.24No. of PT100 inputs030739
P2.7.25
P2.7.26
Response to
thermistor fault
Response to fieldbus
fault
Response to PT100
fault
PT100 warning limit
032732
032733See P2.7.21
032740
–30,0200,0Cº120,0741
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.7.27
PT100 fault limit
–30,0200,0Cº130,0742
5.4.9Autorestart parameters (Control keypad: Menu M2 -> G2.8)
Table 47. Autorestart parameters, G2.8
CodeParameterMinMaxUnitDefaultCustIDNote
P2.8.1Wait time0,1010,00s0,50717
P2.8.2Trial time0,0060,00s30,00718
0 = Ramp
P2.8.3Start function020719
P2.8.4
P2.8.5
P2.8.6
P2.8.7
P2.8.8
P2.8.9
P2.8.10
Number of tries after
undervoltage trip
Number of tries after
overvoltage trip
Number of tries after
overcurrent trip
Number of tries after
4mA reference trip
Number of tries after
motor temp fault trip
Number of tries after
external fault trip
Number of tries after
underload fault trip
0100720
0100721
030722
0100723
0100726
0100725
0100738
1 = Flying start
2 = According to P2.4.6
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
PID Control Application vacon • 68
5.4.10Keypad control (Control keypad: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See
the Keypad control menu in the product's user's manual.
Table 48. Keypad control parameters, M3
Code
P3.1Control place
R3.2
P3.3Direction (on keypad)
P3.4
P3.5
R3.6
Parameter
Keypad referenceP2.1.1P2.1.2Hz
PID reference0,00100,00%0,00167
PID reference 2
Stop button
MinMaxUnit
131
010123
0,00100,00%0,00168
011114
Default
CustIDNote
125
1 = I/O terminal
2 = Keypad
3 = Fieldbus
0 = Forward
1 = Reverse
0 = Limited function of Stop
button
1 = Stop button always
enabled
5.4.11System menu (Control keypad: M6)
For parameters and functions related to the general use of the frequency converter, such as application and language selection, customised parameter sets or information about the hardware and
software, see the product's user's manual.
5.4.12Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more information, see the product's user's manual.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
vacon • 69PID Control Application
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-purpose Control Applicationvacon • 69
6.MULTI-PURPOSE CONTROL APPLICATION
Software codes: ASFIFF06 (NXS); APFIFF06 (NXP)
6.1Introduction
Select the Multi-purpose Control Application in menu M6 on page
Multi-purpose control application provides a wide range of parameters for controlling motors. It
can be used for various kinds of different processes, where wide flexibility of I/O signals is needed
and PID control is not necessary (if you need PID control functions, use the PID Control Application
or Pump and Fan Control Application).
The frequency reference can be selected e.g. from the analogue inputs, joystick control, motor
potentiometer and from a mathematical function of the analogue inputs. There are parameters also
for Fieldbus communication. Multi-step speeds and jogging speed can also be selected if digital inputs are programmed for these functions.
•The digital inputs and all the outputs are freely programmable and the application supports
all I/O-boards
Additional functions:
•Analogue input signal range selection
•Two frequency limit supervisions
•Torque limit supervision
•Reference limit supervision
•Second ramps and S-shape ramp programming
•Programmable Start/Stop and Reverse logic
•DC-brake at start and stop
•Three prohibit frequency areas
•Programmable U/f curve and switching frequency
•Autorestart
•Motor thermal and stall protection: fully programmable; off, warning, fault
•Motor underload protection
•Input and output phase supervision
•Joystick hysteresis
•Sleep function
S6.2.
NXP functions:
•Power limit functions
•Different power limits for motoring and generating side
•Master Follower function
•Different torque limits for motoring and generating side
•Cooling monitor input from heat exchange unit
•Brake monitoring input and actual current monitor for immediate brake close.
•Separate speed control tuning for different speeds and loads
•Inching function two different references
•Possibility to connect the FB Process data to any parameter and some monitoring values
•Identification parameter can be adjusted manually
The parameters of the Multi-Purpose Control Application are explained in Chapter 8 of this manual.
The explanations are arranged according to the individual ID number of the parameter.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
6
vacon • 70Multi-purpose Control Application
Reference potentiometer,
1…10 k
Ju m p er b lo ck X 3 :
CM A and CMB grounding
CMB connected to GN D
CMA connected to GND
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
inter nall y connected tog ether,
isolated from GND
= Factory default
Note: See jumper selections below.
More information in the product's
user's manual.
7084.emf
RUN
6.2Control I/O
Table 49. Multi-purpose control application default I/O configuration
and connection example.
OPTA1
TerminalSignalDescription
READY
1+10V
2AI1+Analogue input 1
3AI1-I/O GroundGround for reference and controls
4AI2+Analogue input 2
5AI26+24VControl voltage outputVoltage for switches, etc. max 0.1 A
7GNDI/O groundGround for reference and controls
8DIN1Start forward
9DIN2Start reverse
10DIN3Fault reset
11CMACommon for DIN 1—DIN 3Connect to GND or +24V
12+24VControl voltage outputVoltage for switches (see #6)
13GNDI/O groundGround for reference and controls
14DIN4Jogging speed selection
15DIN5External fault
16DIN6Accel. /decel. time select Pro-
17CMBCommon for DIN4—DIN6Connect to GND or +24V
18AOA1+Analogue output 1
19AOA1-
Contact open = IO reference active
Programmable (G2.2.7)
Contact closed = Jogging speed active
Contact open = no fault
Programmable (G2.2.7)
Contact closed = external fault
Contact open = P2.1.3, and P2.1.4 in
grammable (G2.2.7)
use
Contact closed = P2.4.3., and P2.4.4 in
use
Range 0—20 mA/R
Output frequency
Programmable (P2.3.5.2)
Open collector, I50mA, U48 VDC
READY
Programmable (G2.3.3)
RUN
Programmable (G2.3.3)
FAULT
Programmable (G2.3.3)
, max. 500
L
6
Figure 11.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-purpose Control Applicationvacon • 71
DIN#
DIN#
AIA#AIA#
DIN#
DIN#
DIN#
>1
DIN#
DIN#
DIN#
DIN#
DIN#
DIN#
AI#
AI#
DIN#
DIN#
DIN#
>1
DIN#
DIN#
DIN#
DIN#
3.2 Keypad reference
2.1.11 I/O Reference
2.1.12 Keypad Ctrl Reference
2.1.13 Fieldbus Ctrl Reference
2.1.15 Preset Speed 1
...2 .1.21 Preset Speed 7
3.1 Control place
Internal frequency
reference
Start forward
(programmable)
Start reverse (programmable)
Programmable
Start/Stop and
reverse logic
Start/Stop
Reverse
Internal Start/Stop
Internal reverse
Int erna l fa ul t reset
Fault reset input
Reset button
Start/Stop buttons
Reference from fieldbus
Start/Stop from fieldbus
Direction from fieldbus
3.3 Keypad direction
Preset Speed 1
Preset Speed 2
Preset Speed 3
2.1.14 Jogging speed
referenc e
(programmable)
Motor
Potentiometer
7085.emf
6.3Control signal logic in Multi-Purpose Control Application
Figure 12.Control signal logic of the Multi-purpose Control Application
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
6
vacon • 72Multi-purpose Control Application
Function name
rebmunlanimreTtolS
epytlanimreT
READ Y
I/O term
DigOUT :B.1
AI Ref Faul/Warn
7086.emf
RE ADY
I/Oterm
DigOUT:0.0
REA DY
I/O term
DigOUT:0.0
RE ADY
I/Oter m
DigOUT:B.1
AI Ref Faul/WarnAI Ref Faul/WarnAI Ref Faul/Warn
7087.emf
6.4“Terminal To Function” (TTF) programming principle
The programming principle of the input and output signals in the Multipurpose Control Application
as well as in the Pump and Fan Control Application (and partly in the other applications) is different
compared to the conventional method used in other Vacon NX applications.
In the conventional programming method,
have a fixed input or output that you define a certain function for. The applications mentioned above,
however, use the
cess is carried out the other way round: Functions appear as parameters which the operator defines a certain input/output for. See
6.4.1Defining an input/output for a certain function on keypad
Connecting a certain input or output with a certain function (parameter) is done by giving the parameter an appropriate value. The value is formed of the
(see the product's user's manual) and the
Terminal to Function Programming method (TTF)
Warning
Function to Terminal Programming Method (FTT),
in which the programming pro-
on page 73.
Board slot
respective signal number
on the Vacon NX control board
, see below.
you
Example: You want to connect the digital output function
2.3.3.7) to the digital output DO1 on the basic board OPTA1 (see the product's user's manual).
First find the parameter 2.3.3.7 on the keypad. Press the
mode. On the
and on the right, the present input/output the function is connected to (B.3, A.2 etc.), or if not connected, a value (0.#).
When the value is blinking, hold down the
and signal number. The program will scroll the board slots starting from 0 and proceeding from A
to E and the I/O selection from 1 to 10.
Once you have set the desired value, press the
value line
, you will see the terminal type on the left (DigIN, DigOUT, An.IN, An.OUT)
Browser button up
Enter button
Reference fault/warning
Menu button right
or
down
to find the desired board slot
once to confirm the change.
once to enter the edit
(parameter
6
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-purpose Control Applicationvacon • 73
6.4.2Defining a terminal for a certain function with NCDrive programming tool
If you use the NCDrive Programming Tool for parametrizing you will have to establish the connection between the function and input/output in the same way as with the control panel. Just pick
Value
the address code from the drop-down menu in the
column (see the Figure below).
Figure 13. Screenshot of NCDrive programming tool; Entering the address code
Be ABSOLUTELY sure not to connect two functions to one and same
output
operation.
NOTE: The
6.4.3Defining unused inputs/outputs
All unused inputs and outputs must be given the board slot value 0 and the value 1 also for the terminal number. The value 0.1 is also the default value for most of the functions. However, if you want
to use the values of a digital input signal for e.g. testing purposes only, you can set the board slot
value to 0 and the terminal number to any number between 2…10 to place the input to a TRUE state.
In other words, the value 1 corresponds to 'open contact' and values 2 to 10 to 'closed contact'.
In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0% signal level, value 2 corresponds to 20%, value 3 to 30% and so on. Giving value 10 for the terminal number
corresponds to 100% signal level.
inputs
, unlike the
in order to avoid function overruns and to ensure flawless
outputs
, cannot be changed in RUN state.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
6
vacon • 74Multi-purpose Control Application
6.5Master/Follower function (NXP only)
The Master/Follower function is designed for applications in which the system is run by several NXP
drives and the motor shafts are coupled to each other via gearing, chain, belt etc. It is recommended
that the Closed Loop control mode be used.
The external Start/Stop control signals are connected to the Master drive only. Speed and torque
references and control modes are selected for each drive separately. The Master controls the Follower(s) via a SystemBus. The Master station is typically speed-controlled and the other drives follow its torque or speed reference.
Torque control of the Follower should be used when the motor shafts of the Master and Follower
drives are solidly coupled to each other by gearing, a chain etc., so that no speed difference between
the drives is possible. Window control is recommended to keep the speed of the follower close to
that of the master.
Speed control of the Follower should be used when the demand of speed accuracy is lower. In such
cases, use of load drooping is recommended in all drives to balance the load.
6.5.1Master/Follower link physical connections
In figures below, the master drive is located on the left side and all others are followers. The master/follower physical link can be built with OPTD2 option board. See Vacon Option Board Manual
(ud00741) for further information.
6.5.2Optical fibre connection between frequency converters with OPTD2
The OPTD2 board in the Master has the default jumper selections, i.e. X6:1-2, X5:1-2. For the followers, the jumper positions have to be changed: X6:1-2, X5:2-3. This board also has a CAN communication option that is useful for multiple drive monitoring with NCDrive PC software, when
commissioning Master Follower functions or line systems.
Figure 14.System bus physical connections with the OPTD2 board
6
For information on the OPTD2 expander board parameters, see Vacon Option Board User's Manual
(document code ud00741).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-purpose Control Applicationvacon • 75
6.6Multi-purpose Control Application – Parameter lists
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 131 to 230.
Column explanations:
Code= Location indication on the keypad; Shows the operator the present parameter
number
Parameter = Name of parameter
Min= Minimum value of parameter
Max= Maximum value of parameter
Unit= Unit of parameter value; Given if available
Default= Value preset by factory
Cust= Customer’s own setting
ID= ID number of the parameter
= On param.code: Parameter value can only be changed after the FC has been stopped
= Apply the Terminal to Function method (TTF) to these parameters (see chapter 6.4)
= Monitoring values controllable from fieldbus using the ID number
6.6.1Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values on shadowed background can be controlled from the fieldbus.
See the product's user's manual for more information.
Table 50. Monitoring values, NXS drives
CodeParameterUnitIDDescription
V1.1Output frequencyHz1Output frequency to motor
V1.2Frequency referenceHz25Frequency reference to motor control
V1.3Motor speedrpm2Motor speed in rpm
V1.4Motor currentA3
V1.5Motor torque%4Calculated shaft torque
V1.6Motor power%5Motor shaft power
V1.7Motor voltageV6
V1.8DC link voltageV7
V1.9Unit temperature
V1.10Motor temperature%9Calculated motor temperature
V1.11Analogue input 1V/mA13AI1
6.6.1.7Follower drive Status Word
Table 58. Follower drive Status Word
FAL SETRUE
b0Flux not readyFlux ready (>90 %)
b1Not in Ready stateReady
b2Not runningRunning
b3No faultFault
b4Charge switch state
b5
b6Run disabledRun enable
b7No warningWarning
b8
b9
b10
b11No DC brakeDC brake is active
b12No run requestRun request
b13No limit controls activeLimit control active
b14External brake control OFF External brake control ON
b15 Heartbeat
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
6
vacon • 82Multi-purpose Control Application
6.6.1.8Application Status Word
Application Status Word
Value V1.21.4 Status Word). Status Word is visible on keypad in Multi-Purpose application only. The Status Word of any other application can be read with the NCDrive PC software.
combines different drive statuses to one data word (see Monitoring
Table 59. Application Status Word content
Application Status Word
(NXP)
b8
b9
b10
b11DC BrakeDC BrakeDC BrakeDC BrakeDC BrakeDC Brake
b12Run request Run requestRun requestRun requestRun requestRun request
b13Limit control Limit control Limit control Limit controlLimit controlLimit control
b14Brake controlAux 1
b15Place B is
active
PID activeAux 2
6
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Multi-purpose Control Applicationvacon • 83
6.6.2Basic parameters (Control keypad: Menu M2 -> G2.1)
Table 60. Basic parameters G2.1
CodeParameterMinMaxUnitDefaultCustIDNote
P2.1.1Min frequency0,00P2.1.2Hz0,00101
NOTE: If f
motor synchronous
P2.1.2Max frequencyP2.1.1320,00Hz50,00102
P2.1.3Acceleration time 10,13000,0s3,01030 Hz to Max frequency
P2.1.4Deceleration time 10,13000,0s3,0104Max frequency to 0 Hz
P2.1.5Current limit
P2.1.6
Nominal voltage of the
motor
0,1 x I
180690V
2 x I
H
H
A
I
L
NX2: 230V
NX5: 400V
NX6: 690V
speed, check suitability
for motor and drive system
107
Check the rating plate of
the motor. Note also
110
used connection Delta/
Star.
> than the
max
P2.1.7
P2.1.8
P2.1.9
P2.1.10Motor cos0,301,000,85120
P2.1.11I/O Reference015/160117
P2.1.12
P2.1.13
Nominal frequency of
the motor
Nominal speed of the
motor
Nominal current of the
motor
Keypad control refer-
ence
Fieldbus control refer-
ence
8,00320,00Hz50,00111
2420 000rpm1440112
0,1 x I
098121
099122See P2.1.12
2 x I
H
A
H
I
H
113
Check the rating plate of
the motor
The default applies for a
4-pole motor and a nominal size frequency converter.