Vacon 8000 solar User Manual

Page 1
vacon 8000 solar
power inverters
3-phase photovoltaic inverters
user manual
Page 2
Page 3
vacon • 0
INDEX
Document: DPD00728B
1. SAFETY ............................................................................................................. 1
1.1 Danger and warning symbols used in this manual ........................................................... 1
1.2 Symbols and warning marks used in the product............................................................. 1
1.3 Safety rules ........................................................................................................................ 2
1.4 Earthing and earth fault protection ................................................................................... 3
2. TECHNICAL SPECIFIATIONS ............................................................................. 6
2.1 Inverter ratings .................................................................................................................. 6
2.2 Technical data .................................................................................................................... 7
3. RECEIPT OF DELIVERY...................................................................................... 8
3.1 Type designation code........................................................................................................8
3.2 Lifting the unit out of the transport packaging.................................................................. 9
3.3 Storage ............................................................................................................................. 11
3.4 Maintenance..................................................................................................................... 12
3.5 Warranty........................................................................................................................... 12
4. INSTALLATION ............................................................................................... 13
4.1 Free space around the cabinet ........................................................................................ 16
4.2 Fixing the unit to the floor................................................................................................ 17
4.3 Fixing cabinets to each other........................................................................................... 18
5. ELECTRICAL CONNECTION ............................................................................. 22
5.1 Electrical diagrams..........................................................................................................22
5.2 Cabling.............................................................................................................................. 23
5.2.1 Earth connection .............................................................................................................. 23
5.2.2 Connection to mains ........................................................................................................23
5.2.3 Connection to photovoltaic panels................................................................................... 25
5.3 Fuse selection .................................................................................................................. 28
5.3.1 Fuses for inverters........................................................................................................... 28
5.3.2 Fuse for charging............................................................................................................. 28
5.3.3 Fuse for EMC capacitors.................................................................................................. 28
5.3.4 Fuse for measuring.......................................................................................................... 29
5.4 Control connections ......................................................................................................... 29
5.4.1 Basic board OPTA1........................................................................................................... 30
5.4.2 Option board OPTA2 .........................................................................................................33
5.4.3 Option board OPTB5.........................................................................................................34
5.5 Option board OPTC2 (RS-485).......................................................................................... 35
5.6 Option board OPTD2......................................................................................................... 36
5.7 Option board OPTD7 (Line voltage measurement board) ............................................... 40
5.8 Option board OPTCI (Modbus/TCP board) ....................................................................... 42
6. START UP ....................................................................................................... 43
7. THE SOLAR MULTIMASTER APPLICATION...................................................... 44
8. CONTROL INTERFACES .................................................................................. 45
8.1 Screens and Navigation ................................................................................................... 45
8.2 Main view.......................................................................................................................... 46
8.2.1 System Activation............................................................................................................. 46
8.2.2 System status................................................................................................................... 47
8.2.3 Total Power ...................................................................................................................... 48
Page 4
vacon • 1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.2.4 Total energy counter........................................................................................................ 48
8.2.5 DC Bus Voltage................................................................................................................. 48
8.2.6 Main View Units ................................................................................................................ 49
8.2.7 Event Banner.................................................................................................................... 49
8.2.8 Start Cond......................................................................................................................... 50
8.3 Events ............................................................................................................................... 51
8.4 System Trends.................................................................................................................. 52
8.4.1 System Total..................................................................................................................... 52
8.4.2 DC Insulation Monitoring ................................................................................................. 53
8.4.3 Energy tables.................................................................................................................... 53
8.5 Unit View........................................................................................................................... 55
8.5.1 Master button................................................................................................................... 57
8.5.2 Reset button ..................................................................................................................... 57
8.5.3 Unit Trend......................................................................................................................... 57
8.5.4 Unit event ......................................................................................................................... 58
8.6 Settings............................................................................................................................. 58
8.6.1 Settings 1.......................................................................................................................... 59
8.6.2 Settings 2.......................................................................................................................... 63
8.6.3 Settings 3 ......................................................................................................................... 64
8.6.4 Settings 4.......................................................................................................................... 66
8.6.5 Settings 5.......................................................................................................................... 66
9. INVERTER CONTROL KEYPAD......................................................................... 68
9.1 Indicators of the inverter condition.................................................................................. 68
9.2 State leds.......................................................................................................................... 69
9.3 Text lines .......................................................................................................................... 69
9.4 Panel push buttons .......................................................................................................... 69
9.4.1 Description of push buttons............................................................................................. 69
9.5 Browsing the control panel.............................................................................................. 70
9.5.1 Monitoring menu.............................................................................................................. 70
9.5.2 Active faults menu............................................................................................................ 72
9.5.3 Fault history menu (M5)................................................................................................... 72
10. MAINTENANCE AND TROUBLESHOOTING ...................................................... 75
10.1 Maintenance..................................................................................................................... 75
10.2 Troubleshooting ............................................................................................................... 75
11. APPENDIX A SINGLE LINE EXAMPLES............................................................ 82
12. APPENDIX B GROUNDING OVERVIEW .............................................................85
Page 5
SAFETY vacon • 1
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
1. SAFETY
1.1 Danger and warning symbols used in this manual
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
1.2 Symbols and warning marks used in the product
The product carries some additional symbols and marks. The meanings of these are as follows:
= Dangerous voltage! Risk of electric shock
= General warning! Risk of equipment damage
= Dangerous voltage! Risk of electric shock
= See User’s Manual
= Caution! Risk of electric shock! Energy storage timed discharge: 5 minutes
= Caution, risk of hearing damage, wear hearing protection
9000.emf
13006.emf
9000.emf
i
5
min
Page 6
1
vacon • 2 SAFETY
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1.3 Safety rules
The solar inverter VACON 8000 SOLAR has been designed to be installed in enclosed places. It shall be protected against harsh weather conditions.
The solar inverter VACON 8000 SOLAR can only be opened by qualified technicians. Inside the in­vert-er module, there is no element which can be fixed or adjusted by the user.
Even when the solar inverter has been disconnected from mains and solar panels, wait until the con-trol panel switches off. After this, it is recommended that you wait at least 5 minutes before opening, and /or making any kind of alteration or connection to, the device.
Check that there is no voltage present before handling and performing any kind of work on the de­vice. To verify the absence of voltage, type III measurement elements (1000 volts) must be used.
Do not perform any measurement or test when the VACON 8000 SOLAR is connected to mains or solar panels.
Do not perform any kind of dielectric strength test on the VACON 8000 SOLAR. Unless the appropri­ate process is followed, performing this test may damage the inverter module.
Appropriate personal protective equipment (PPEs) must be used:
•Helmet
Safety goggles for electrical risk
Safety footwear
Hearing protection
Electrically resistant gloves adequate for the voltage
Protective gloves against mechanical risk
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY OUT THE ELECTRICAL INSTALLATION! RISK OF ELECTRIC SHOCK!
There is a serious risk of electrick shock, even after the device has been discon­nected from the mains supply or solar panels. This electrick shok may cause death or serious injury.
If the short circuit current of the grid is higher than the short circuit withstanding capability of the QA2, additional circuit breaker must be installed. if the possible short circuit current at the grid point of connection is higher than the solar inverter’s breaking capacity, additional current limiting device must be installed (see chapter 5,3).
If the equipment is used in a manner not specified by the manufacturer, the protec­tion provided by the equipment may be impaired.
Access to the photo-voltaic field is strictly prohibited!
9000.emf
9000.emf
9000.emf
13006.emf
9000.emf
Page 7
SAFETY vacon • 3
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
1.4 Earthing and earth fault protection
The Vacon 8000 Solar inverter must always be earthed with an earthing conductor connected to the earthing terminal marked with .
The touch current of Vacon 8000 Solar exceeds 3.5mA AC. According to EN62109-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
A fixed connection and
a) the protective earthing conductor shall have a cross-sectional area of at least 10 mm
2
Cu or 16
mm
2
Al.
or
b) an automatic disconnection of the supply in case of discontinuity of the protective earthing con- ductor. See chapter 4.
or
c) provision of an additional terminal for a second protective earthing conductor of the same cross­sectional area as the original protective earthing conductor.
The cross-sectional area of every protective earthing conductor which does not form a part of the supply cable or cable enclosure shall, in any case, be not less than
2.5 mm2 if mechanical protection is provided or
4 mm
2
if mechanical protection is not provided. For cord-connected equipment, provisions shall be made so that the protective earthing conductor in the cord shall, in the case of failure of the strain-relief mechanism, be the last conductor to be interrupted.
However, always follow the local regulations for the minimum size of the protective earthing conductor.
CAUTION!
Table 1.
Cross-sectional area of phase
conductors
(S)
[mm
2
]
Minimum cross-sectional area of the corresponding
protective earthing conductor
S16
16 <
S35
35 <
S
S
16
S/2
The values above are valid only if the protective earthing conductor is made of the same metal as the phase conductors. If this is not so, the cross-sectional area of the protective earthing conduc­tor shall be determined in a manner which produces a conductance equivalent to that which results from the application of this table.
13006.emf
Page 8
1
vacon • 4 SAFETY
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
NOTE: Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
Do not perform any voltage withstand tests on any part of Vacon 8000 Solar.
There is a certain procedure according to which the tests shall be performed.
Ignoring this procedure may result in damaged product.
13006.emf
Page 9
TECHNICAL SPECIFIATIONS vacon • 6
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
2. TECHNICAL SPECIFIATIONS
2.1 Inverter ratings
Range of input voltages 410-800Vcc, 50/60 Hz, 3~
Inverter
type
Nom. output power
[kW]
Recom-
mended
max PV
power
[kW]
Max al-
lowed
PV Isc
[A]
Max effi-
ciency
[%]
Max
Power
consump-
tion
at
night
[W]
Inverter
dimensions
[mm]
Inverter
weight
[kg]
Connection cabinet
[mm] (kg)
Incoming
Outgoing
AC-
cabinet
(optional)
NXV0125 125 150 353 96.8 0 800x2281x600 450
1
)
N/A
NXV0200 200 240 613 98.6 0 800x2281x600 645
1
)
N/A
NXV0400 400 480 1226 98.6 60 1600x2281x600 1220 600 (205) 600 (215) NXV0600 600 720 1839 98.6 60 2400x2281x600 1830 600 (205) 600 (215) NXV0800 800 960 2452 98.6 60 3200x2281x600 2440 800 (355) 600 (320)
NXV1000 1000 1200 3065 98.6 60 4000x2281x600 3050 800 (355) 600 (320) NXV1200 1200 1440 3678 98.6 60 4800x2281x600 3660 800 (355) 600 (320)
Table 2. Power ratings, dimensions and weights
Page 10
2
vacon • 7 TECHNICAL SPECIFIATIONS
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2.2 Technical data
1
Inverter types NXV0125 and NXV0200 have an optional incoming connection box
Table 3. Technical data
DC Input
Range of input volt­ages
410...800 VDC
Maximum input volt­age
900 VDC
AC input
Mains voltage 3*280±10%
Galvanic isolation No
Frequency 50/60 Hz ±0,5%
Cos >0.99, for output 20%-100% of Pn
Harmonic distortion <3% at Pn
Consumption at night 30W
Maximum efficiency 98.6%
Ambient temperature
-10...+40ºC; 1-% derating for each degree up to 50ºC required
Relative humidity <95% no condensation
Protection IP21
Display
Alfanumeric display per unit with two lines of 14 charac­ters, leds indicating functioning, plus fault and function push buttons. Units above and including NXV0400 also equipped with a PLC touch screen user interface.
Signalling 3 potential free contacts to indicate faults and alarms
Aux. supply (for units > 200kW)
230VAC, 16A MCB provided, 2,5…16 mm
2
Communications
May include one of the following communication buses as an optional feature: Modbus RTU, Ethernet (Modbus/TCP), RS485, GPRS, string and inverter monitoring May include a monitoring system with http-access as an optional feature.
Step-up transformer
Not included in delivery. Allowed types: DyN11 or YyN0, neutral should not be con­nected on inverter side Impedance voltage: Higher or equal to 6%
Ambient conditions
Altitude
Max. 2,000m
Environmental cate­gory
Indoor, conditioned
OIvervoltage
category
Pollution degree PD2
AC (Mains) OVCIII
AC (Aux.supply) OVCII
DC (Panels) OVCII
Page 11
RECEIPT OF DELIVERY vacon • 8
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
3. RECEIPT OF DELIVERY
3.1 Type designation code
Vacon 8000 Solar inverters have undergone scrupulous tests and quality checks at the factory be­fore they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below).
VACON NXV 0125 4 A 2 L A1A2 D700XX
nk3_1_solar.fh11
Vacon NXV = Solar power inverter
Nominal power
e.g. 0125 = 1 25 kW, 0400 = 4 00 kW, 1000 = 1 MW
2 = No galvanic isolation transformer, output 3 x 280 VAC• 4=Galvanicisolationtransformer,ouptut 3x400VAC
Control keypad and display on the cabinet door:
A=standard(alpha-numeric) B=nolocalcontrolkeypad F = dummy keypad G = graphic display
Enclosure class:
2 = IP21/NEMA 1
EMC emiss ion level:
L = fulfils requirements of category C3 of standard EN61800-3 (2004),
2nd environment and rated voltage less than 1000V
T = fulfils standard EN61800-3 (2004) whenused in IT networks
Option boards; each slot is represented by two characters where:
A = basic I/O board, B = expander I/O board, • C = fieldbus board, D = special board, 00 = Not used
Page 12
3
vacon • 9 RECEIPT OF DELIVERY
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.2 Lifting the unit out of the transport packaging
Before unpacking the device, check the correctness of delivery by comparing your order data to the drive information found on the package label.
The unit is delivered either in a wooden box or a wooden cage. The box may be transported either horizontally or vertically, while transportation of the cage in a horizontal position is not allowed. Al­ways refer to shipping marks for more detailed information. To lift the unit out of the box, use lifting equipment capable of handling the weight of the cabinet.
There are lifting lugs on the top of the cabinet and these lugs can be used to lift the cabinet into an upright position and to move it to the place needed.
Units NXV 0125 and NXV0200 may be lifted as shown in Figure 3-2, in vertical or horizontal position. However, bigger units (NXV0400 to NXV1200) must always be lifted in vertical position, see Figure 3-3.
Figure 1.Lifting 1-cabinet unit
Min 60°
Min 60°
Min 60°
Page 13
RECEIPT OF DELIVERY vacon • 10
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
After unpacking the product, check that no signs of transport damages are to be found on the prod­uct and that the delivery is complete.
If the delivery does not correspond to your order, contact the supplier immediately.
Should the drive have been damaged during the shipping, please contact primarily the cargo insur­ance company or the carrier.
If the equipment has been damaged, do not install it.
Keep the original packaging in case it is necessary to return the equipment to the manufacturer. Otherwise recycle the packaging material according to local regulations.
Figure 2.Lifting several-cabinet units
Page 14
3
vacon • 11 RECEIPT OF DELIVERY
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.3 Storage
If the inverter is to be kept in store before use make sure that the ambient conditions are accept­able:
Storing temperature -40...+70
ºC
Relative humidity <95%, no condensation
The environment should also be free from dust. If there is dust in the air the inverter should be well protected to make sure dust does not get inside it.
If the inverter is to be stored during longer periods the power should be connected to the inverter once in 24 months and kept on for at least 2 hours. If the storage time exceeds 24 months the elec­trolytic DC capacitors need to be charged with caution. Therefore, such a long storage time is not recommended.
If the storing time is much longer than 24 months, the recharging of the capacitors has to be carried out so that the possible high leakage current through the capacitors is limited. The best alternative is to use a DC-power supply with adjustable current limit. The current limit has to be set for exam­ple to 300…500mA and the DC-power supply has to be connected to the B+/B- terminals (DC supply terminals).
DC-voltage must be adjusted to nominal DC-voltage level of the unit (1.35*Un AC) and supplied at least for 1 hour.
If DC-voltage is not available and the unit has been stored de-energized much longer than 1 year consult factory before connecting power.
3.4 Maintenance
Please contact Vacon service for recommended maintenance schedule.
3.5 Warranty
Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsi­bility for damages caused during or resulting from transport, receipt of the delivery, installation, com-missioning or use.
The manufacturer shall in no event and under no circumstances be held responsible for damages and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust, corrosive substances or operation outside the rated specifications.
Neither can the manufacturer be held responsible for consequential damages.
The Manufacturer's standard time of warranty is 18 months from the delivery or 12 months from the commissioning whichever expires first (Vacon Warranty Terms).
The local distributor may grant a warranty time different from the above. This warranty time shall be specified in the distributor's sales and warranty terms. Vacon assumes no responsibility for any oth-er warranties than that granted by Vacon itself.
In all matters concerning the warranty, please contact first your distributor.
Page 15
INSTALLATION vacon • 13
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
4. INSTALLATION
The installation of the VACON 8000 SOLAR solar inverter may only be carried out by a qualified technician who fully understands the safety and installation instructions included in this manual. The IP21 protection of the VACON 8000 SOLAR inverter only allows for installation in enclosed places.
Note the locations of some essential components of the inverters in pictures below:
Figure 3.NXV0125 inverter mocule (standalone) and some essential components
L1, L2, L3
PE busbar
DC busbar s
Cfilter unit
AFE unit
PE ter minal s
Op en in gs for mains cables
Con t rol unit
Bus bar supports
AC busbar s (option)
AC sw it ch
Lfilter unit
DC swit ch
PE
DC swit ch
AC swit ch
Page 16
4
vacon • 14 INSTALLATION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Due to the heavy weight of the device, it must be placed on a firm and horizontal surface. The equipment has to be installed in a place where the room temperature is between -10ºC and +40ºC. Lower temperatures prevent the equipment from starting up and higher temperatures limit the output power.
Figure 4.NXV0200 inverter module (standalone) and some essential compo-
nents
Figure 5.NXV0200 inverter module (line unit) and some essential components
DC swi tch
Emergency stop
AC switch
AFE un it
Cont ro l unit
PE ter minals
L1, L2, L3
DC+ DC-
Openings for mains cables
PE busbar
Cfilter unit
Lfilter unit
DC swi tch
AC swi tch
L1, L2, L3
PE busbar
DC busbar s
Cfilter unit
AFE unit
PE ter minals
Openings for mains cables
Con t rol unit
Bus bar suppor ts
AC bu sbar s (opt ion)
AC swit ch
Lfilter unit
DC swi tch
PE
DC swi tch
AC swit ch
Page 17
INSTALLATION vacon • 15
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
The buzzing noise occurring during the operation of the equipment is normal. Do not install the equipment in an occupied dwelling.
NOTE: It is important to prevent small particles falling onto the device. Small particles may enter the equipment through the ventilation grids and damage the equipment.
Do not block the ventilation grids.
Unit must be installed on non-flammable ground.
The unit is not intended for wet location.
13006.emf
13006.emf
13006.emf
13006.emf
Page 18
4
vacon • 16 INSTALLATION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4.1 Free space around the cabinet
Enough space must be left above, behind and in front of the cabinet to ensure sufficient cooling and space for maintenance. The amount of cooling air required is indicated in the table below. Also make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of the inverter.
Figure 6. Space to be left free above (left) and in front of (right) the cabinet
Type Cooling air required [m3/h)
NXV0125
800
NXV0200
1000
NXV0400
2000
NXV0600 3000
NXV0800 4000
NXV1000 5000
NXV1200 6000
Table 4. Required cooling air
200 mm
800 mm
Page 19
INSTALLATION vacon • 17
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
4.2 Fixing the unit to the floor
The cabinet should always be fixed to the floor. There are holes in all four corners to be used for fixing, see Figure 4-5.
Figure 7.Fixing the cabinet to the floor
Welding of the cabinet might risk sensitive components in the converter. Ensure that no grounding currents can flow through any part of the converter.
13006.emf
Page 20
4
vacon • 18 INSTALLATION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4.3 Fixing cabinets to each other
In case the delivery consists of several cabinets sections including drives the cabinets must be joined to each other. This will take place by 1) connecting the PE bars and 2) using the components of accessories kit attached to the delivery. To join two cabinet sections to each other you will need 3
angular baying brackets (A)
and
6 quick-fit baying clamps (B) (see Figure4-6 below).
The angular baying brackets are used in top rear and top front as well as bottom rear corners of the cabinet.
Figure 8.Baying brackets
Figure 9.Fixing corners
AB
Top rear and front corner fixing
Bottom rear corner fixing
Page 21
INSTALLATION vacon • 19
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
Use the quick-fit baying clamps to join the cabinets at points approximately shown in picture on the right.
Note! Attach the baying clamps from the inside!
Finally join together the PE busbars (Figure 4-9) as well as AC or DC bars (Figure 4-10) by bolting together the baying bracket of the one and the busbar of the other cabinet.
Figure 10.Cabinet fixing points
Page 22
4
vacon • 20 INSTALLATION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
In Figure 4-10 right, the connection is not yet made. In the magnification (left), the connection of the upper bars is complete (1) and the lower bars shall be connected by sliding the longitudinal busbar connector (2) to the right on the busbar joint and tightening the bolts.
Figure 11.Joining the PE bars
Figure 12.Joining the AC or DC bars (AC bars in this exaple)
1
2
Page 23
ELECTRICAL CONNECTION vacon • 22
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5. ELECTRICAL CONNECTION
5.1 Electrical diagrams
For larger types see Appendix A
Only a competent electrician is allowed to install the electrical connection. The equipment uses dangerous voltages. There is danger of electrical shock which may cause death or serious injury.
Figure 13.Electrical diagram for NXV0125
Figure 14.Electrical diagram for NXV0200
9000.emf
Page 24
5
vacon • 23 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5.2 Cabling
Before connecting the cables to the solar inverter, use a multimeter to check that the cables to be
connected are not live.
Cables coming from photovoltaic panels will be active while panels are lit.
The tightening torques of all power connections are given in table below:
5.2.1 Earth connection
The solar inverter has an earth connection terminal to which all the inverter's metallic parts are connected. This connection terminal must be connected to earth. After the PE busbars have been
joined together as instructed in chapter 4.3, the PE busbar must be earthed. See appendix B.
5.2.2 Connection to mains
The terminals of the power supply can be reached through the bottom part of the equipment. The solar inverter has three connection terminals, to which mains cables are connected. Make openings for the cables in the grommets on the bottom of the cabinet and lead through the
cables. See Figure 5-5.
Figure 15.Main cabling NXV0125 standalone unit (cable clamps not included in delivery)
Table 5. Tightening torques of power connections
Screw/Bolt
size
Tightening torque
[Nm]
M6 8...10
M8 18...22 M10 35...45 M12 65...75
L1 L2 L3
DC+
DC-
PE busbar
Page 25
ELECTRICAL CONNECTION vacon • 24
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
Figure 16. Main cabling NXV0200 standalone unit (cable clamps not included in delivery)
Figure 17. Mains cabling NXV0200 line unit (cable clamps not included in delivery)
L3 L2 L1
PE busbar
DC+ DC-
L3 L2 L1
PE busbar
Page 26
5
vacon • 25 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Figure 18. Main cabling with optional AC-section
The cable cross section will be determined according to the power and distance to the connection point, following the local regulations.
5.2.3 Connection to photovoltaic panels
Run the solar panel cables to the respective terminals on the drive through the bottom of the supply unit (see Figure 5-6 left). Check for the cable sizes and the appropriate number of cables in tables on page 25. Always connect the two cables on both sides of the terminal bar (see Figure 5-6 right). Connect the positive pole of the photovoltaic panel to the terminal marked with ‘+’ and the negative
pole to the terminal marked with ‘-‘.
Model Minimum cross section
per unit
[mm2]
Maximum cross section
per unit
[mm2]
All 10 240
Remember that photovoltaic panels produce a current while they are illuminated. Be sure to check that cables are not live.
NOTE! Wrongly connected cables may damage the equipment.
9000.emf
13006.emf
Page 27
ELECTRICAL CONNECTION vacon • 26
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
Figure 19.Inverter connection to solar panels (units below NXV0800)
Figure 20.Inverter connection solar panels (units above and including
NXV0800)
Table 6. Panel input cable dimensions
Model Minimum cross section Recommended cross section Maximum cross section
NXV0125
3x 2x70mm
2
3x 2x95mm
2
4x 2x185mm
2
NXV0200
4x 2x95mm
2
4x 2x95mm
2
4x 2x240mm
2
NXV0400
8x 2x95mm
2
8x 2x95mm
2
20x 2x185mm
2
NXV0600
12x 2x95mm
2
12x 2x95mm
2
20x 2x185mm
2
Make t he sol ar panel connection here
DC+ DC-
DC+
DC-
Connect one cable on either side of th e ter minal bar
PE PE
PE PE
PEPE
Connect one cable on either side of the ter m inal bar.
Make the solar panel connection here.
DC+ DC-
DC-
DC+
Page 28
5
vacon • 27 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
The minimum cable cross section is calculated in compliance with loading capacity of cables. The recommended cross section is calculated in compliance with 1-% voltage drop for a cable 100 m in length on DC-side and 50 m in length on AC-side.
NXV0800
15x 2x95mm
2
16x 2x95mm
2
32x 2x185mm
2
NXV1000
19x 2x95mm
2
20x 2x95mm
2
32x 2x185mm
2
NXV1200
23x 2x95mm
2
24x 2x95mm
2
32x 2x185mm
2
Table 7. Panel output cable dimensions
Model
Minimum cross
section
Recommended cross
section
Maximum cross section
NXV0125
2x 3x95mm
2
2x 3x120mm
2
2x 3x240mm
2
NXV0200
3x 3x95mm
2
2x 3x185mm
2
4x 3x240mm
2
NXV0400
6x 3x95mm
2
4x 3x185mm
2
12x 3x240mm
2
NXV0600
9x 3x95mm
2
6x 3x185mm
2
12x 3x240mm
2
NXV0800
12x 3x95mm
2
8x 3x185mm
2
16x 3x185mm
2
NXV1000
15x 3x95mm
2
10x 3x185mm
2
16x 3x185mm
2
NXV1200
17x 3x95mm
2
2x 3x185mm
2
16x 3x185mm
2
Table 8. Panel earthing cable
dimensions
Model Cross section
NXV0125
50mm
2
NXV0200
50mm
2
NXV0400
50mm
2
NXV0600
50mm
2
NXV0800
50mm
2
NXV1000
50mm
2
NXV1200
50mm
2
Table 6. Panel input cable dimensions
Model Minimum cross section Recommended cross section Maximum cross section
Page 29
ELECTRICAL CONNECTION vacon • 28
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.3 Fuse selection
The table below shows typical cable sizes and types that can be used with the Vacon 8000 Solar inverter. The final selection should be made according to local regulations, cable installation conditions and cable specification.
5.3.1 Fuses for inverters
5.3.2 Fuse for charging
5.3.3 Fuse for EMC capacitors
CAUTION! Maximum AC-side short-circuit breaking capacity Icu=30kA. With optional AC-section I
cu=40kA.
Inverter
type
Nominal
current
[A]
Nominal
voltage
[V]
Braking capacity
[kA]
Acting
behaviour
Fuse size
Suitable fuse type
(Cat. nr by Ferraz-
Shawmut
NXV0125 400 810 125 aR 71 DIN110 PC71UD13C400D1A NXV0200 630 930 125 aR 73 DIN110 PC73UD13C630D1A NXV0400 630 930 125 aR DIN3 PC73UD13C630PA NXV0600 630 930 125 aR DIN3 PC73UD13C630PA NXV0800 630 930 125 aR DIN3 PC73UD13C630PA NXV1000 630 930 125 aR DIN3 PC73UD13C630PA NXV1200 630 930 125 aR DIN3 PC73UD13C630PA
Table 9. Fuse selection; suitable fuses for Vacon 8000 Solar inverter types
Nominal
current
[A]
Nominal
voltage
[V]
Braking
capacity
[kA]
Acting
behaviour
Fuse
size
Suitable fuse type (Cat.
nr by Ferraz-Shawmut
32 810 125 aR DIN00 NH00UD10C32P
Table 10. Fuse selection, fuse for charging
Nominal
current
[A]
Nominal
voltage
[V]
Braking capacity
[kA]
Acting
behaviour
Fuse
size
Suitable fuse type (Cat. nr by Ferraz-Shawmut
25 1000 10 gPV 10*38 HP10M4
Table 11. Fuse selection, fuse for EMC capacitors
13006.emf
Page 30
5
vacon • 29 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5.3.4 Fuse for measuring
5.4 Control connections
The control boards are situated inside the control unit of the Vacon 8000 Solar inverter (see Figure 5-8). Four different board types can be used with the inverter: A1, A2, B5, C2, D2, D7 and CI. The control connections of these boards are described below. For more detailed information on the boards you can find in Vacon Option Board Manual.
Nominal
current
[A]
Nominal
voltage
[V]
Braking capacity
[kA]
Acting
behaviour
Fuse
size
Suitable fuse type (Cat.
nr by Ferraz-Shawmut
4 1000 10 gPV 10*38 HP10M4
Table 12. Fuse selection, fuse for measuring
Figure 21.Board slots
in control unit
Page 31
ELECTRICAL CONNECTION vacon • 30
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.4.1 Basic board OPTA1
Figure 22.Vacon OPT-A1 option board
Description: Standard I/O board with digital inputs/outputs and analogue inputs/outputs Allowed slots: A Type ID: 16689 Terminals: Two terminal blocks (coded = mounting of blocks in wrong order prevented,
terminals
#1 and #12);
Screw terminals (M2.6)
Jumpers:
4; X1, X2, X3 and X6 (See Figure 5-10.)
Board param­eters:
Yes (s e e page 3 1 )
Page 32
5
vacon • 31 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Terminal Parameter reference
on keypad and NCDrive
Technical information
1 +10 Vref Reference output +10V; Maximum current 10 mA
2 AI1+ An.IN:A.1 Selection V or mA with jumper block X1 (see page 30):
Default: 0– +10V (Ri = 200 k)
(-10V..+10V Joy-stick control, selected with ajumper) 0– 20mA (Ri = 250 ? )
Resolution 0.1%; Accuracy ±1%
3 AI1– Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
3AI1
4 AI2+ An.IN:A.2 Selection V or mA with jumper block X2 (see page 30):
Default: 0– 20mA (Ri = 250)
0– +10V (Ri = 200 k)
(-10V..+10V Joy-stick control, selected with a jumper)
Resolution: 0.1%; Accuracy ±1%
5 AI2– Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
5AI2
6 24 Vout (bidirec-
tional)
24V auxiliary voltage output. Short-circuit protected.
±5%, maximum current 150 mA
+24Vdc external supply may be connected.
Galvanically connected to terminal #12.
7 GND Ground for reference and controls
Galvanically connected to terminals #13,19.
8 DIN1 DigIN:A.1 Digital input
1 (common CMA); Ri = min. 5
9 DIN2 DigIN:A.2 Digital input
2 (common CMA); Ri = min. 5
10 DIN3 DigIN:A.3 Digital input
3 (common CMA); Ri = min. 5
11 CMA Digital input common A for DIN1, DIN2 and DIN3.
Connection by default to GND.
Selection with jumper block X3 (see page 30):
12 24 Vout (bidirec-
tional)
Same as terminal #6
Galvanically connected to terminal #6.
13 GND Same as terminal #7
Galvanically connected to terminals #7 and 19
14 DIN4 DigIN:A.4 Digital input
4 (common CMB); Ri = min. 5
15 DIN5 DigIN:A.5 Digital input
5 (common CMB); Ri = min. 5
16 DIN6 DigIN:A.6 Digital input
6 (common CMB); Ri = min. 5
17 CMB Digital input common B for DIN4, DIN5 and DIN6.
Connection by default to GND.
Selection with jumper block X3 (see page 30):
18 AO1+ AnOUT:A.1 Analogue output
19 AO1– Output signal range:
Current
0(4)–20mA, RL max 500 or
Voltage
0—10V, RL >1k
Selection with jumper block X6 (see page 30): Maximum
Resolution: 0.1% (10 bits); Accuracy ±2%
20 DO1 DigOUT:A.1 Open collector output
Maximum
U
in
= 48VDC
Maximum current = 50 mA
Table 13. I/O terminals on OPTA1 (coded terminals painted black)
Page 33
ELECTRICAL CONNECTION vacon • 32
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
Jumper selections
There are four jumper blocks on the OPTA1 board. The factory defaults and other available jumper
selections are presented below.
OPTA1 parameters
Figure 23.Jumper block selection on OPTA1
Number Parameter Min Max Default Note
1 AI1 mode 1 5 3 1 = 0...20mA
2 = 4...20mA 3 = 0...10V 4 = 2...10V 5 = -10...+10V
2 AI2 mode 1 5 1 1 = 0...20mA
2 = 4...20mA 3 = 0...10V 4 = 2...10V 5 = -10...+10V
Table 14. OPTA1 board-related parameters
ABCD
ABCD
ABCD
ABCD
ABCD
ABCD
ABCD
ABCD
ABCD
ABCD
Jum pe r b lo ckX1:
AI1 m ode
AI1 mode: Voltage input; 0...10 V
AI1 mode: Voltage input; 0...1 0V (differential)
AI1 mode: Voltage input; -10...10 V
Jum pe r b lo ckX2:
AI2 mode
AI2 mode: 0 ... 20 mA; Current i nput
AI2 mode: Voltage i nput; 0.. .10 V
AI2 mode: Voltage input; 0 ...10V (differential)
AI2 mode: Voltage input; -10 ...10 V
Ju mp e r b l ock X 3 :
CM A a nd CM B gr o u nd i n g
CMB connected to GND CMA connected to GN D
CMB isolated from G ND CMA isolated from GND
CMB and CM A inter nally connec ted tog ether, isolated from GN D
=Factorydefault
Ju mp e r b lo ck X 6 :
AO1 mode
AO 1 mod e: 0 ... 20 mA; Cur rent output
AO 1 mod e: Vol tag e o utput; 0 ... 10V
AI1 mode: 0. ..20 mA; Current i nput
Page 34
5
vacon • 33 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5.4.2 Option board OPTA2
I/O terminals on OPTA2
3AO1 mode 1411 = 0...20mA
2 = 4...20mA 3 = 0...10V 4 = 2...10V
Description:
Standard Vacon NX frequency converter relay board with two relay outputs
Type ID: 16690 Allowed slots:
B
Terminals: Two terminal blocks; Screw terminals (M3); No coding Jumpers: None Board parame-
ters:
None
Termina l
Parameter reference
on keypad and NCDrive
Technical information
21 22 23
RO1/normal closed
RO1/common
RO1/normal open
DigOUT:B.1
Relay output 1 (NO/NC) Switching capacity
Min. switching load
24VDC/8A 250VAC/8A 125VDC/0.4A 5V/10mA
24 25 26
RO2/normal closed
RO2/common
RO2/normal open
DigOUT:B.2
Relay output 2 (NO/NC) Switching capacity
Min. switching load
24VDC/8A 250VAC/8A 125VDC/0.4A 5V/10mA
Table 15. OPTA2 I/O terminals
Number Parameter Min Max Default Note
Table 14. OPTA1 board-related parameters
Page 35
ELECTRICAL CONNECTION vacon • 34
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.4.3 Option board OPTB5
I/O terminals on OPTB5
Note: This expander board can be placed into four different slots on the control board. Therefore,
the 'X' given in the Parameter reference shall be replaced by the slot letter (B, C, D, or E) depending on the slot which the expander board is plugged into.
Description: I/O expander board with three relay outputs.
Allowed slots: B, C, D, E
Type ID: 16949
Terminals: Three terminal blocks; Screw terminals (M3); No coding
Jumpers: None
Board parameters: None
Termina l
Parameter reference
Keypad/NCDrive
Technical information
2223RO1/common
RO1/normal open
DigOUT: X.1 Switching capacity
Min. switching load
24VDC/8A 250VAC/8A 125VDC/0.4A 5V/10mA
2526RO2/common
RO2/normal open
DigOUT: X.2 Switching capacity
Min. switching load
24VDC/8A 250VAC/8A 125VDC/0.4A 5V/10mA
2829RO3/common
RO3/normal open
DigOUT: X.3 Switching capacity
Min. switching load
24VDC/8A 250VAC/8A 125VDC/0.4A 5V/10mA
Page 36
5
vacon • 35 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5.5 Option board OPTC2 (RS-485)
Figure 24.Vacon RS-458 option board OPTC2
Signal Connector Description
NC* 1* No connection
VP 2 Supply voltage – plus (5V)
RxD/TxD –N 3 Receive/Transmit data – A
RxD/TxD –P 4 Receive/Transmit data – B
DGND 5 Data ground (reference potential for VP)
*You can use this pin (1) to bypass the cable shield to the next slave
X4
X1
Bus connector
Jumper s Interface board connector
Grounding plate
1 2 3 4 5
Page 37
ELECTRICAL CONNECTION vacon • 36
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.6 Option board OPTD2
Note! This figure presents the layout of D2 board version H or later. See Chapter Jumper selections below.
I/O terminals on OPTD2
Description:
System Bus adapter board with single optical input and output; Interface to fast mon-
itor bus used by the NCDrive PC tool.
Allowed slots:
(B,)D, E; Note: If only the Monitor Bus (terminals 21 to 23) is used the board
can also be placed in slot B. The System Bus is then unavailable. Remove
therefore jumpers X5 and X6. See page 36. Type ID: 17458 Terminals:
Single optical input and output; one screw terminal block (M3),
Agilent HFBR-1528 (Receiver), HFBR-2528 (Transmitter). Jumpers:
4; X3, X4, X5 and X6. See page 36
Board parameters:
None
Term in al Tech n ical information
1
H1 System Bus optical input 1 (RX1)
Use 1-mm optical cable (e.g. Agilent HFBR-RUS500 & HFBR-4531/4532/ 4533 connectors) Note: Not available if the board is placed in slot B
2
H2 System Bus optical output 1/2 (TX1/TX2);
Selected with jumper X5 Use 1-mm optical cable (e.g. Agilent HFBR-RUS500 & HFBR-4531/4532/4533 connectors) Note: Not available if the board is placed in slot B
21
CAN_L Monitor Bus negative data
22
CAN_H Monitor Bus positive data
23
CAN_SHIELD Monitor Bus shield
H1
H2
Page 38
5
vacon • 37 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Jumper selections
There are four jumper blocks on the OPTD2 board. The factory defaults and other available jumper
selections are presented below.
Note! Position C can be used with 3- or 4-wire CAN cable to interconnect isolated CAN ground levels in the network. It is recommended to connect the cable shield to the grounding clamp of the drive.
Figure 25.Jumper selections for OPT-D2, up to version G
Figure 26.X3 jumper selections for OPT-D2, version H and lat-
er
Jumpe r block X3:
CAN grounding
Connected to shield Not connected to shield
Jumper block X4:
CAN termination
Terminated Not ter minated
Jumper block X5*:
System bus output
Output TX1 Output TX2
Jumper block X6*:
SystemBus input ON/OFF
ON OFF
= Factory default
*IftheboardisplacedinslotBtheSystemBusisnot available. Remove jumpers X5 and X6.
CAN grounding
ABC
A: Connected to ground B: Connect ed to grou nd via LC filter C: Conne cted to CAN isolated grou nd Not assembled: No con nection S
ee fur the r clar ifi c a tions of the alte rna tives ne xt page !
Page 39
ELECTRICAL CONNECTION vacon • 38
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
Alternative connection of “CAN GND” signal: connect ‘CAN GND’ together between all nodes. Use the signal wire inside the shield for this purpose, see figure below:
Figure 27.CAN grounding alternatives
PE NC GND
PE NC GND
PE NC GND
A
23
chassis
CAN GND
chassis
- Used when the shield is connected to terminal 23 and the distance between the devices is short
B
chassis
chassis
23
CAN GND
- Used when the shield is connected to terminal 23 and the distance between the devices is long
C
23
CAN GND
chassis
- Used when CAN GND is connected to terminal 23. This setting is recommended for best noise immunity
= Factory default
= Recommended setting
Page 40
5
vacon • 39 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Connections between drives with OPTD2
Special connection:
In this connection example, the leftmost device is the Master and the others are slaves. The Master can send and receive data from the slaves. The slaves cannot communicate with each other. Changing of masters is not possible, the first device is always the Master. The OPTD2 board in the Master has the default jumper selections, i.e. X6:1-2, X5:1-2. The jumper
positions have to be changed for the slaves: X6: 1-2, X5:2-3.
Figure 28.Alternative connection of “CAN GND” signal
Max.
number of devices
in line
Max.
speed achieved
[Mbit/s]
312
66
12 3
24 1.5
Shield
IHNACIHNAC
OLNACOLNAC
CAN GND
CAN GND
21 22 23
OPTD2 / OPTD6
OPTD2 / OPTD6
OPTD2 / OPTD6
Grounding clamp
Conn ect th e data GND tightly to the chassis on one point in the net
21 22 23
21 22 23
Page 41
ELECTRICAL CONNECTION vacon • 40
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.7 Option board OPTD7 (Line voltage measurement board)
OPTD7 is an AC sinusoidal voltage measurement board. Using this board, the drive measures the line voltage, frequency and voltage angle information. The drive can compare this information with its output voltage angle when running. This feature can be used to develop applications for different purposes using NC61131-3 application programming tool. The OPTD7 board is delivered with the transformer which is suitable for voltage range 380V …690V. Please note that the transformer can not be used with the pulse width modulated (PWM) voltage input. It is possible to use custom built transformer when the input voltage to be measured is not within the above voltage range. The transformation ratio parameter then can be adjusted as per the transformer primary to secondary ratio. Please refer to specification section for further engineering. The measurement signal connected into the OPT-D7 option board can not exceed 14.26 Vrms.
Figure 29.Connection example of drives with OPTD2
OPTD2
Jumper X5 : TX2
X6 : ON
OPTD2
Jumper X5 : TX2
X6 : ON
OPTD 2
Jum pe r X5 : T X2
X6 : ON
OPTD2
Jumper X5 : TX1
X6 : ON
H1
(RX)
H2
(TX)
Master SBInUse = Yes SBID = 1 SBNextID = 2 SBLastID = 4
Follower
SBIn Use = Yes SBID = 2 SBNext ID = 3
Follower
SBInUse = Yes SBID = 3 SBNext ID = 4
Follower
SBInUse = Yes SBID = 4 SBNext ID = 1
H1
(RX)
H1
(RX)
H1
(RX)
H2
(TX)
H2
(TX)
H2
(TX)
Page 42
5
vacon • 41 ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
The board can only be placed in slot C.
OPTD7 connections
OPTD7 board specification
Transformer primary/ input voltage range
Min 380VAC -15% Max 690VAC +15%
Transformer ratio Primary : secondary
60:1
Transformer secondary/ output voltage range
14V rms Between the terminals L1/L2/L3.
Input impedence L1/L2 =50kOhm
L1/L3 = 25kOhm L2/L3 = 25kOhm
L3 is internal virtual common
Cable recommendation Max 1.5 mm2, shielded From transformer output to OPTD7 Measurement resolution 10 bit Voltage measurement
Accuracy
0.2%
Page 43
ELECTRICAL CONNECTION vacon • 42
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.8 Option board OPTCI (Modbus/TCP board)
Vacon NX frequency converters can be connected to Ethernet using an Ethernet fieldbus board OPTCI.
The OPTCI can be installed in the card slots D or E
Figure 30.OPTCI option board
General Board name OPTCI Ethernet connections Interface RJ-45 connector Communications Transfer cable Shielded CAT5e
Speed 10 / 100 Mb Duplex half / full Default IP-address 192.168.0.10
Protocols Modbus / TCP Environment Ambient operating
temperature
–10°C…50°C
Storing temperature –40°C…70°C Humidity <95%, no condensation allowed Altitude Max. 1000 m Vibration 0.5 G at 9…200 Hz
Safety Fulfils EN50178 standard
Page 44
6
vacon • 43 START UP
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6. START UP
Starting up the VACON 8000 SOLAR inverter is simple, but it is important that the following instructions are followed:
1. Check that the cables from the solar panels are correctly connected and that the DC con­nection switch is closed.
2. Ensure that the cables coming from the mains supply, including the earth cable, are cor­rectly connected. Check that the main AC-circuit breaker and possible auxiliary circuit breakers are connected and closed.
3. Press the START button on the control panel.
Once these steps have been followed, the inverter will automatically start when the voltage of solar panels exceeds the minimum wake-up voltage, 340 V DC, provided that there is mains voltage. The inverter starts up every day in the morning and automatically stops at night. Due to different atmospheric conditions, the inverter may start up and stop more than once each day.
Page 45
THE SOLAR MULTIMASTER APPLICATION vacon • 44
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
7
7. THE SOLAR MULTIMASTER APPLICATION
The Solar Multimaster is a unique concept that improves efficiency, reliability and functionality in all large-scale applications. The concept allows a series of two to five separate inverter units to be connected together in sequence. This means that only the optimal needed number of inverter modules is powered up for minimal power loss. By rotating the inverters in use we can ensure equal usage, thereby extending the entire setup’s overall lifetime. The entire setup is centrally controlled via the touch screen on the control unit. This modular approach creates numerous advantages compared to conventional single inverter setups. In addition to allowing for optimisation according to sunlight, the modularity allows for repairs and maintenance to be carried out without complete shutdowns. The charging fuse disconnectors allow single units to be safely connected and disconnected while the setup is up and running.
The modular setup makes it possible to design the layout according to the available space, and means that the entire solution is extremely flexible. As a system integrator you can have a buffer stock of single modules and configure the right power level by paralleling the modules and selecting the right power setup using the touch screen. The setup allows you to have fast deliveries when needed. The Solar Multimaster solution also makes expansion extremely easy. Instead of replacing the entire inverter, you can simply add inverter units onto the setup. Depending on your needs, the set­up can include 1 to 5 individual units. The setup within the individual units is also modular and uncluttered. This means that access to single components, such as the inverter module and LCL­filter, is also easy and fast.
Page 46
8
vacon • 45 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8. CONTROL INTERFACES
8.1 Screens and Navigation
TA70 is a touch screen panel. Operations and navigations of the panel are done by touching the
screen.
Transitions to sub-screens is made by touching one of the buttons at bottom of main view.
Every sub-screen has a Main View –button that returns to the main view
Figure 31.Buttons to sccess sub-screens
Figure 32.Ho
me button
returns to
main view
Page 47
CONTROL INTERFACES vacon • 46
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.2 Main view
Main view presents all the essential information of the Vacon 8000 Solar system. For more specific information of individual units and historical data there are several sub- screens. System activation and stop buttons are located in main view.
Master is a device that is “The Boss” of the communication. The purpose of the Master is to mea­sure a Grid status, DC voltage and by the DC Voltage it counts a reference value of the DC. By the Grid status master works with Grid standards. Master sends values to slaves and TA70 touch panel. The TA70 touch panel is response to these values and commands the slave units to ON or OFF states, if there is any. Usually in a device combination there are more than one similar devices con­nected to each other. In these cases one of the devices must be set to be as master and the rest as slave.
Slave is a device that is a “listener” of the communication. The purpose of the Slave is to listen val­ues and commands coming from the Master device.
All units are send status information to the TA70 touch panel.
When the system is stopped there is an arrow indicating which unit will start as a master next time.
8.2.1 System Activation
System activation and stop –buttons are placed on top left corner of main view. Buttons also indi­cates the actual state of system activation. The system remembers the activation state during pow­er downs. See Table 1. Activation/Stop.
Figure 33.Main view present all the essential informa-
tion of system
Figure 34.Indica-
tor showing the
next master in-
verter
Page 48
8
vacon • 47 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
If system is activated, it will not necessary mean that the system starts. It could e.g. be that the in­verters are not ready to be started because of low irradiation. However, the system goes into a mode where it either tries to start or waits for the inverters to get ready.
8.2.2 System status
Figure 35.System Activation/Stopped
status
System stopped
System activated
Enter State
Not Ready
Stopped
Standby
Generating
Faulted
Critical Faults?
Yes
Start Criterions
Fullfilled?
Start button
pushed?
No
Is any of units
Ready ?
Yes
Is the Master
Ready ?
No
Waking
Is DC Voltage
enough?
Yes
No
No
Yes
Is 10min
waiting time
over?
Yes
No
Change Master
Yes
No
Sleepi ngNo
Is Output
power
enough?
Stop button
pushed?
No
Turn off UnitNo
Turn on Unit
Is Output
power max
limit?
Yes
YesNo
Ready
Yes
Yes
Critical Faults?
No
Criti cal Fa ults?
No
Yes
Criti cal Fa ults?
No
Yes
Is the re any
unit run?
Yes
No
Yes
Page 49
CONTROL INTERFACES vacon • 48
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
Systems actual status is shown as text in the top of the main view. For different status of system please refer Table 2 System statuses
8.2.3 Total Power
When system is generating the total power of all units is shown in top right corner of the main view.
8.2.4 Total energy counter
The total energy counter is shown below total power. It is the total accumulated energy produced by all inverter units.
8.2.5 DC Bus Voltage
The DC voltage is shown below total energy counter.
Caution: If all the units are unavailable, e.g. during night time, the value of voltage is blinking red “-
-“. That means the actual DC Voltage is unknown but the DC link might actually have hazardous voltage.
Table 16. System statuses
Faulted System is stopped because of a critical fault. Critical faults are
explained in chapter 2.3 Start Cond
Not ready System is stopped due to missing external run enable signal. (For
programming of external signals see 2.7.3 Settings 3)
Stopped System is in stop mode Sleeping System is sleeping. There are no unit available. System stays in
sleeping state until there are units in ready mode
Waking There are ready units but the system waits for the master to go to
ready state. (The system will change master automatically if not in ready state within 10min {default}.)
Generating System is running and generating power. Standby System is in standby mode.
Table 17. Total power, Total energy counter and DC bus voltage
Figure 36.Blinking red “--” indicates no valid
DC bus voltage read
VDC
--
Page 50
8
vacon • 49 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.2.6 Main View Units
Unit status, power generated and total running hour are shown in main view for each unit. Number of unit rows is depending on size of the Vacon 8000 Solar system.
The unit row shows the status of the unit as symbol animation. Indication is explained in Table 8-2.
The power generated in kW is shown as number and bar graph animation in percentage. Running hours is a total counter.
Value “- -“ indicates that unit is unavailable or communication not working and actual value or sta­tus is unknown.
8.2.7 Event Banner
Last occurred event, alarm or fault is shown in the bottom of the main view.
Figure 37.Unit status, power and total running
hours are shown for all units
Figure 38.Unit status indication
Unit is ready
Unit is runnig as master
Unit is running as slave
Unit is not ready
DBlinking red: Unit is faulted
Master in standby
Unit is unavailable
Figure 39.Last occured event in main view
Time stamp Source Event description
M
Page 51
CONTROL INTERFACES vacon • 50
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.2.8 Start Cond
System start conditions screen summarizes critical faults and states. These faults or states will stop and/or prevents system to start.
Symbols explained below:
Figure 40.System start conditions
Figure 41.Conditions
Fault or Not OK. Stops the system and/or prevents system to start
Ok
N/A. This fault is used in system
Table 18. Conditions
Condition
Possible Fault cause
AC Main Switch AC Main Switch is not closed.
DC Main Switch DC Main Switch is not closed. All DC charging switches
needs to be opened before the DC Main Switch can be closed.
Emergency Switch Emergency Stop has been activated.
Run Enable External run enable signal is not activated.
Insulation DC There is an insulation fault on the DC side coming from dig-
ital input signal.
Insulation AC Signal from external AC insulation measurement indicates
insulation fault on AC side.
External Fault 1 External fault signal from digital input.
External Fault 2 External fault signal from digital input.
DC Insulation Monitor There is an insulation fault on the DC side coming from
analog input measurements.
Page 52
8
vacon • 51 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.3 Events
Event list shows faults, alarms and events of system and individual units.
Each row in list is an event, alarm or fault. Active time is the timestamp when an event has occurred, group indicates the source of event, alarm or fault; it is either system or a specific unit. For events and cleared faults/alarms the background colour of the row is white. For active faults the back­ground colour is red and for active alarms background colour is yellow.
The event list can be filtered to show only faults by choosing the “Basic” radio button. By choosing “Full” the list will show all possible events, faults and alarms of the system and units.
DC Swiches Units DC Switches are not closed although DC Main switch
is closed, or they are closed when the DC Main Switch is open.
Overvoltage One or many inverter(s) have tripped on Overvoltage fault
Communication IO Communication to Remote I/O module is lost.
Figure 42.Event list
Figure 43.Event list filter options
Event list is filtered. Only faults of system and units are shown. Green dot indicates the selection
Event list shows all the faults, alarms and events
Table 18. Conditions
Condition
Possible Fault cause
Page 53
CONTROL INTERFACES vacon • 52
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
There is also the possibility to filter the list by only showing the events of a specific unit or system events by selection in the drop down list.
8.4 System Trends
Historical trend of the system are total counters for procured energy and DC insulation measure­ment.
8.4.1 System Total
System total trend shows the historical value for the total current and total produced power of the system in a time span of last 24 hours. Red trend is the current and blue is the total power produced. Scale of the Y-axis is can be optimized for Output Current or Output Power by the buttons in the top of the screen.
Figure 44.Even t list can be fil-
tered also by
group. Group is
either system
or an unit
Figure 45.System total current and power monitoring
Figure 46.Y-axis scale of trends
Scale of Y-axel for the trend is the current [A]. Green dot indicates actual selection
Scale of Y-axel for the trend is the power [kW]
Page 54
8
vacon • 53 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.4.2 DC Insulation Monitoring
DC insulation trend shows historical measurement of the DC insulation value in scale of 0..100%. This sheet is visible only when DC insulation is measured by analog input.
Time span of trend is 24 hours by default. The scale can be changed by touching the trend view and then select another time span.
8.4.3 Energy tables
Total Energy kWh page show the total and unit specific energy produced during the present day, week and month.
There are also buttons for accessing historical data on a daily, weekly or monthly basis.
Figure 47.DC insulation measurement trend
Figure 48.Time span
scaling dialog
Figure 49.Produced energy table menu page
Page 55
CONTROL INTERFACES vacon • 54
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.4.3.1 Daily energy history
Produced daily energy historical trend summarises the total energy for the system and units pro­duces per day in kWh.
8.4.3.2 Weekly energy history
Produced weekly energy historical trend summarises the total energy for the system and units per week in kWh.
Figure 50.Daily energy produced for whole
system and units in kWh
Figure 51.Weekly energy produced for and units
in kWh
Page 56
8
vacon • 55 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.4.3.3 Monthly energy history
Produced monthly energy historical trend summarises the total energy for the system per month in kWh.
8.5 Unit View
Unit view shows detailed information of the units. There is a screen for every unit defined in the sys­tem. Navigation between screens is done by pressing the Prev and Next buttons in the bottom of the screen.
Figure 52.Monthly energy produced for system
in kWh
Figure 53.Navigation be-
tween units
Figure 54.Unit detailed information
Page 57
CONTROL INTERFACES vacon • 56
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
Unit status, fault, alarm and master/slave state is presented in the status bar on the top of the screen. It has 4 different sections: The general state of the unit, active fault, active alarm or master/ slave.
The different general states of the units are listed in table below
The monitor values are explained in table below.
Last occurred event, fault or alarm for unit is shown in the bottom of screen.
Figure 55.The status bar shows information about
the unit
Table 19. Unit statuses
Not ready Unit is not ready. Unit may have been disabled by the stop button on the units
keypad or because of low DC Voltage. Stopped Unit is stopped Running Unit is running and generating power to the grid. Standby Unit is in standby mode because of low irradiation. No Comm, Unit is unavailable because of no irradiation during night or e.g. loss of commu-
nication. All the statuses and values are also showing “- -“
Table 20. Unit monitor values
Output Power Output power of the Inverter in kW Output Current Output current of the Inverter in A Temperature Temperature of the Inverter in °C Total Run Time Total run time of the Inverter in hours Energy Total Total accumulated amount of energy fed into the grid by the Inverter in kWh Daily Energy Todays energy fed into the grid in kWh Daily Energy
Previous
Yesterdays energy fed into the grid the previous day in kWh
DC Voltage Voltage on the DC bus in VDC Net AC Voltage Voltage at the output in V Net Frequency Output frequency of the Inverter in Hz Active Fault
Code
Fault code of last active fault
Figure 56.Unit event banner
Page 58
8
vacon • 57 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.5.1 Master button
On right of side lays a Master button. When an unit is running as slave, pressing this button will set the unit to master on the fly. Button is only visible when the unit is running as a slave or system is Stopped. If system is stopped with this button can choose next master.
8.5.2 Reset button
Reset button resets faults and alarms on the Inverter unit.
8.5.3 Unit Trend
Unit trend for the DC voltage, unit temperature and output power is shown in a time span of last 24 hours by default. Green trend is the DC Voltage yellow trend is unit temperature and blue trend is produced output power of unit. Scale of Y-axis can be optimized by the buttons in the top of the screen.
Figure 57.Mas
ter button
Figure 58.Re-
set button
Figure 59.Unit trend
Figure 60.Scale of trends
Scale of Y-axis for trends is the DC voltage in VDC. Green dot indicates actual selection
Scale of Y-axis for trends is the unit temperature in °C
Scale of Y-axis for trends is the output power in kW
Page 59
CONTROL INTERFACES vacon • 58
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.5.4 Unit event
If jumping to the event list from the unit view by pressing the event button. The event list will be set to showing only the events of unit visible in the unit view before jumping to the list. Event list is oth­erwise the same as in paragraph 0 except for the pre-set filtering of event source. “Prev view” –but­ton returns to unit view.
8.6 Settings
Pressing settings button opens the pop-up login menu. Select User: Admin and touch password field to insert Password. Default Password is: 8000
Access to the settings pages requires a valid password to be entered.
Figure 61.Unit event list
Figure 62.Unit event list
Page 60
8
vacon • 59 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.6.1 Settings 1
This is the first view accessed when going into the settings. It contains System and control param­eters that affects to whole system.
Language:
The language of the operator panel can be set by pressing the language button on the right side.
Time zone:
Time zone and daylight saving can be configured by pressing the Time Zone button, please refer Picture 31. Region setting affects date and time format and also the decimal symbol of numbers.
Date/Time: Date and Time of the TA70 can be changed by pressing the Date Time buttons, please refer Picture 32.
Figure 63.System and control parameters
Figure 64.L
anguage
change but-
ton
Figure 65.Time zone and
regional settings
Figure 66.Date and time
settings
Page 61
CONTROL INTERFACES vacon • 60
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
System parameters:
Inverter type: Size of one inverter unit in the MultiMaster setup. Usually 200kW.
Number of inverters: The amount of inverter units in the system. (E.g. a 600kW system con-
sisting of 200kW units should be set to 3.) NOTE! The appropriate amount of active commu­nication controllers for the units has to be activated in the Units & Communications dialog.
Unit & Communications: If the system consist of e.g. 3 inverter units (“Number of Inverter”),
then the controllers of Unit01, Unit02 and Unit03 has to be activated. If 5 units then control­lers Unit01 through Unit05 and vice versa.
Control parameters
Power Max Limit: If the output power of the master unit exceeds this limit for a time longer
than the “Power Max Delay” then a new slave unit is started.
Power Max Delay: If the output power of the master unit exceeds “Power Max Limit” for a
time longer than defined with this parameter then a new slave unit is started.
Power Min Limit: Same as for Max but in the opposite direction, units are removed.
Power Min Delay: Same as for Max but in the opposite direction, units are removed.
Master Wait time-out: Wait time for the selected master to get ready if there are other units
in ready state. If ready state for the master unit is not entered within this time, the next ready unit is automatically assigned as a new master and system started.
IP Settings
Pressing the IP Settings button gives the possibility to set the Ethernet settings. NOTE! Port 1 is for the internal use MultiMaster system only and should never be changed. Port 2 can be used for con­nection an external supervisory or SCADA system for monitoring purpose. The IP address of port 2 is not allowed to be in the same range as port 1, hence 192.168.0.X .
Figure 67.Active controllers
are selected according num-
ber of inverters
Figure 68.IP Settings pop-up
menu
Page 62
8
vacon • 61 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Backlight Settings
Screen brightness and delay for turning the backlight off when the panel is not used can be set here. Note! If the automatic turn off of the backlight is not used, then the life time of the panel will be re­duced.
Clear Event List
Clear event list will erase the historical data in the event list. Confirmation will be asked.
Show Dialog
This is a debug mode to access fieldbus and panel system data(CPU load, etc.).
Figure 69.Backlight settings
pop-up menu
Figure 70.Clear event list
pop-up menu
Figure 71.Show dia-
log buttons
Page 63
CONTROL INTERFACES vacon • 62
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
D button gives you access to the Panel diagnostic tool where e.g. CPU Load, Used Memory, Tem­perature and Screen info can be seen.
S button gives you access to the System diagnostic pop-up screen for internal use and debugging by Vacon service personnel only.
Save Parameters to USB
This function needs an USB memory stick to be connected to the USB port.
Figure 72.Panel diagnostic tool pop-up
Figure 73.Connect to USB memory to touch pan-
el
Page 64
8
vacon • 63 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Pressing Save parameters to USB button will open a pop-up menu for choosing the name of the pa­rameter file to be saved on the USB memory stick. The parameters are saved as an .ini file.
Load Parameters from USB
This function needs an USB memory stick to be connected to the USB port and contain a valid pa­rameter file in .ini format.
Selecting the wanted parameter file and pressing the Load button will override the current setting with the settings of the parameter file.
8.6.2 Settings 2
This view contains the settings for DC Insulations monitoring through analog input and Wake Power control.
DC Insulation Monitor (Only if Analog Input is used for DC Insulation monitoring):
Actual Measurement Live updated value of the DC Insulation level. DC Insulation Alarm Level DC Insulation measurement warning level. DC Insulation Fault Level DC Insulation measurement trip level. Note! By pressing the button on the right of the fault level parameter, one can choose if exceed-
ing the fault level should trip/stop the system or only indicate a fault event in the event list.
DC Insulation Hysteresis DC Insulation measurement hysteresis level for returning from a fault
or alarm state..
DC Insulation Delay Time to exceed the fault/alarm level before a fault/alarm occurs.
Wake Power:
Figure 74.Save parameters to USB pop-up menu
Figure 75.Load parameters from
USB pop-up menu
Page 65
CONTROL INTERFACES vacon • 64
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
Wake Power is auxiliary power (24VDC) backup to the control boards of every inverter unit.
Wake power is set on when there is communication to any unit and the DC bus and voltage above 220VDC. The Wake Power is removed in the evening when DC voltage reaches Wake Power Off Level for a time longer than Wake Power Off Delay.
8.6.3 Settings 3
Screen shows definitions of the I/O connections.
Figure 76.Setting for DC insulation monitor
Figure 77.System IO functions
Table 21. Selection of possible input values
Input name Definition
Not Used Not Used AC Main Switch Closed AC Main Switch feedback input (NO)* DC Main Switch Closed DC Main Switch feedback input (NO)* No Insulation Fault DC External DC Insulation measuring device Fault input (NC)** No Insulation Fault AC External AC Insulation measuring device Fault input (NC)** No External Fault 1 External Fault Input (NO)* No External Fault 2 External Fault Input (NO)*
Page 66
8
vacon • 65 CONTROL INTERFACES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
(* Normally Open contact
(** Normally Close contact
8.6.3.1 IO Diag
On IO Diagnostic screen show actual status of system IO. Digital and analog inputs shows actual state or value of input. Relay output shows actual state of output. Output status can also be changed via this screen.
No Emergency Switch-off Emergency switch Input (NC)** Run Enable External Run Enable input (NO)* No Surge Arrester Alarm External surge arrester alarm input. (NO)* No External Alarm 1 External Alarm Input (NO)* No External Alarm 2 External Alarm Input (NO)* DC Switch ON DC Switch feedback input (NC)**
Table 22. Selection of possible Output values
Output name Definition
Not Used Not Used Running System is Running state Alarm System is Alarm state Fault System is Fault state Wake Power On This is output what wake up the power in the units DC Main Switch Cntrl Control DC main switch state.
Figure 78.Status of system IO
Table 21. Selection of possible input values
Input name Definition
Page 67
CONTROL INTERFACES vacon • 66
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.6.4 Settings 4
Settings 4 screen show communication status of system IO and units.
8.6.5 Settings 5
Screen shows TA70 version information as well as system IO version number and Total Energy Counter value. There is also a possibility to save Energy tables and Event list to the USB memory.
Figure 79.Communication status for system IO and
units
Figure 80.Communication status animation
Communication OK
Communication error. System IO or an unit is unavailable
Figure 81.Settings 5/5
Page 68
9
vacon • 68 INVERTER CONTROL KEYPAD
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9. INVERTER CONTROL KEYPAD
The inverter has a control panel that displays its different variables and conditions.
9.1 Indicators of the inverter condition
Inverter state informs the user about conditions of the inverter and whether the control software has detected any operating fault.
Control place indications:
= The inverter is running.
= Indicates the order of phases in the mains.
= Indicates that the inverter is not running.
= Illuminated when DC level is OK. In case of a fault, the symbol will not light up. Also signifies a valid license or trial time.
= Indicates that the unit is running above a certain limit and issues an alarm.
= Indicates that there are unsafe running conditions and therefore the unit has stopped.
= I/O terminals are the selected control place; i.e. START/STOP commands or reference values etc. are given through the I/O terminals.
= Control keypad is the selected control place; i.e. the Inverter can be started or stopped, or its reference values etc. altered from the keypad.
= The inverter is controlled through a fieldbus.
= Run enable not active
= Unit is ready to start in the morning.
RUN
STOP
READY
ALARM
FAULT
Page 69
INVERTER CONTROL KEYPAD vacon • 69
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
9
9. 2 S ta t e l e d s
State LEDs light up according to state indicators READY, RUN and FAULT of the inverter. If all LEDs blink the drive is uncommissioned.
9.3 Text lines
The three text lines (, ••, ••• )provide the user with information about the current location within the
menu structure of the panel, separate from information related to the operation of the unit.
9.4 Panel push buttons
The alphanumeric control panel of the inverter VACON 8000 SOLAR has 9 push buttons used to control the inverter and to monitor values.
9.4.1 Description of push buttons
= Lights up with DC voltage connected to the converter with no active failure. The state indicator READY also lights up simultaneously.
= Lights up when the converter is running.
= Blinks when there are unsafe running conditions and the unit has therefore stopped (fault trip). Simultaneously, the state indicator FAULT blinks in the dis­play and shows a description of the fault; see chapter Active Faults.
= Indication of the place in the panel; it shows the menu symbol and number, parameter, etc. Example: M1 = Menu 1 (Display); P1.3 = Generated power
••
= Description line; Shows the description of the menu, value or fault.
•••
= Value line; it shows numeric values and reference texts, parameters, etc, as well as the number of submenus available for each menu.
= This push button is used to reset active faults.
= This push button is used to switch between the two last displays.
reset
select
Page 70
9
vacon • 70 INVERTER CONTROL KEYPAD
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9.5 Browsing the control panel
Data on the control panel is arranged in menus and submenus. Menus are used, for example, to display control signals and the measurements of reference values and faults shown.
The first menu level has menus from M1 to M7 and it is called Main menu. The user can browse the
main menu using the Browse push buttons up and down. The chosen submenu can be accessed from the main menu using the Menu push buttons. When there are pages under the menu or page shown, you will see an arrow ( ) in the bottom right corner of the display and you will be able to access
the following menu level by pressing the Push button Menu right.
9.5.1 Monitoring menu
To enter the Monitoring menu from the Main menu, press the Push button Menu right when the location indication M1 appears in the first line of the screen. The following figure shows how to view the monitored values.
The monitored signals have the indication V
#.# and are listed in the following table. Values are updated
every 0.3 seconds.
= The Enter push button serves to: Restore the fault history (2-3 seconds)
= Push button browser up Browse the main menu and the pages of different submenus.
= Push button browser down Browse the main menu and the pages of different submenus.
= Push button Menu left Return to the menu.
= Push button Menu right Go forward in the menu.
= To start-up the inverter In a Multi-Master system: Enable inverter
= To stop the inverter In a Multi-Master system: Disable inverter
enter
+
-
3
4
start
stop
V1ÎV14
REA D Y
Lo cal
RU N
Monitor
Location
Description
Number of available eleme nts;
eleme nt value
Page 71
INVERTER CONTROL KEYPAD vacon • 71
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
9
This menu is used only to verify the signals. Values can not be modified.
Code Parameter Min Max Unit ID Description
V1.1 Output power 0 1000 kW 1707 Output power of inverter, with
compensated LCL filter losses.
V1.2 Total energy kWh 0 4,29E+09 kWh 1837 Total energy of inverter fed into
the grid.
V1.3 Energy today
kWh
0 6553,5 kWh 1708 Energy fed into the grid today.
V1.4 Energy yesterday 0 6553,5 kWh 1733 Energy fed into the grid yesterday. V1.5 DC voltage refer-
ence
50 150 % 1200 Used DC voltage reference by the
regenerative unit in % of the nominal DC volt-
age. V1.6 DC-link voltage 0 1000 V 1839 Filtered DC-link voltage in Volt. V1.7 Unit temperature -50 200
ºC
1109 Temperature of the unit in Celsius
V1.8 AC voltage 0 1000 V 1709 AC voltage measured on the grid
side of the
main contactor by an external
measurement
circuit. V1.9 AC frequency -60 60 Hz 1835 Grid frequency in Hz. The sign
indicates the
phase order. Can be monitored
only when
UNIT is in RUN state.
V1.10 Output current 0 Varies A 1834 Output current of the inverter
coming out of
the cabinet (transformers inside
cabinet are
taken into consideration).
V1.11 Run time total [h] 0 99999999 h 1836 Total time the inverter has been
running.
Table 23. Monitoring values
RUN RE ADY
Lo cal
M1
Monitor
V1ÎV14
RU N RE ADY
Loc al
V1.1
Output power
19.4 kW
RUN READY
Local
V1.1
Daily energy
125 kWh
Page 72
9
vacon • 72 INVERTER CONTROL KEYPAD
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9.5.2 Active faults menu
The Active faults menu can be reached from Main menu pressing the Menu right push button when
the location indication M4 can be seen in the first line of the panel display.
When the frequency converter stops due to a fault, the location indication F1, the fault code, a short
description of the fault and the symbol of the fault type appear on the display. Besides, the indication FAULT or ALARM will appear and, in case of FAULT, the red LED of the panel will start to blink. If there are several faults simultaneously, the list of active faults may be browsed using the push but­tons
in the browser
Fault codes are listed in chapter 7.2.
The memory of active faults can store a maximum of 10 faults in order of occurrence. You can delete
the display using the Reset push button and the reading device will go back to the same state where you were before the fault trip. The fault is active until it is deleted with the
Reset push button.
9.5.3 Fault history menu (M5)
The Fault history menu can be accessed from the Main menu pressing the Menu right Push button
when the location indication M5 is visible on the first line of the panel display.
All faults are stored in the Fault history menu,which can be browsed with Browser Push buttons.
You can go back to the previous menu at any time, pressing the
Menu left push button .
The memory can store a maximum of 30 faults in order of appearance. The number of faults includ­ed in the fault history is shown in the value line of the main page (H1
Hnº). The order of faults is
indicated through the place indication on the top left corner of the screen. The last fault is indicated by F5.1, the penultimate fault, F5.2, etc. If there are 30 faults not deleted in the memory, the next fault will delete the oldest one.
V1.12 Run time today 0 255 h 1731 The time the inverter has been
running today.
V1.13 Run time yester-
day
0 255 h 1732 The time the inverter ran yester-
day.
V1.14 Grid connections 0 4,29E+09 1706 Total number of times the inverter
has closed
the main contactor and connected
to the grid.
V1.15 Standby remain-
ing
0 65535 s 1201 Remaining time in standby mode,
if standby
mode is activated.
Normal state, no faults
Code Parameter Min Max Unit ID Description
Table 23. Monitoring values
RU N READY
Lo cal
M4
Active faults
F0
Page 73
INVERTER CONTROL KEYPAD vacon • 73
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
9
If you press the Enter push button for 2-3 seconds, the fault history will be restored. The number of
the symbol Hnº will change to 0.
Page 74
10
vacon • 75 MAINTENANCE AND TROUBLESHOOTING
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
10. MAINTENANCE AND TROUBLESHOOTING
10.1 Maintenance
Maintaining the solar inverter VACON 8000 SOLAR is simple. It is recommended that the following checks are carried out at least once a year.
Visually check the external condition of the inverter, checking mainly the good condition of
the door and its locking elements.
Visually check the internal condition of the inverter, checking mainly that wires are correctly
located, wearing of isolation of wires, lack of hot points on checking the color of terminals
and isolations. Check also for humidity and the correct fixing of the elements of the inverter.
Check the tightness of connection screws on the terminals.
Check that the fans operate correctly. Check if they need to be cleaned.
Clean the ventilation grids.
Check that the acoustic noise produced by the inverter has not increased.
If there is something wrong, please contact the installer.
10.2 Troubleshooting
The microprocessor for the Vacon solar inverter continuously monitors the running condition of the inverter and the elements connected to it. If the microprocessor finds any abnormal running values or that some of the elements do not work correctly, the device issues an alarm signal, if the malfunction does not imply any kind of a safety hazard for the inverter or the installation, and it issues a fault signal if there is any kind of a safety hazard for the inverter or the installation. Every indication of fault or alarm is shown on the control panel described in chapter 6. In the control panel, the letter A (Alarm) or F (Fault) appears together with the order number of the Fault or Alarm, the fault or alarm code and a short description. The fault can be reset using the reset push button on the control panel.
Below you can find the fault and alarm codes, their causes and how to solve them.
Only a qualified electrician may carry out the maintenance work. There is risk of electric shock.
No maintenance must be given unless the unit is reliably isolated from AC and DC power sources.
Safety instructions included in chapter 1 must be followed.
THE SOLUTION FOR SOME OF THE PROBLEMS INDICATED HERE IMPLIES TO PERFORM CHECKING INSIDE THE INVERTER, THE WIRES OF AC MAINS OR THE DC WIRES IN THE SOLAR PANELS. THESE CHECKS HAVE TO BE CARRIED OUT TAK ING THE INSTRUCTIONS IN CHAPTER 1 INTO ACCOUNT.
REPAIR WORK SHOULD ONLY BE CARRIED OUT BY A QUALIFIED TECHNICIAN. THERE IS A RISK OF AN ELECTRIC SHOCK.
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
Page 75
MAINTENANCE AND TROUBLESHOOTING vacon • 76
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
10
Fault
code
Fault Possible cause Correcting measures
Auto
Reset
1
Overcurrent AFE has detected too high a current
(>4*IH) in the cables
X
2
Overvoltage The DC-link voltage has exceeded the
inverter limit. See User manual.
- high overvoltage spikes in supply
- Check DC voltage
X
3
Earth fault Current measurement has detected
that the sum of phase currents is not zero.
- insulation failure in cables
- Check cables.
---
4
Inverter fault
---
5
Charging switch The charging switch is open, when the
START command has been given.
- faulty operation
- component failure
- Reset the fault and restart.
- Should the fault re­occur, contact your local distributor.
---
7
Saturation trip Various causes:
- defective component
- Cannot be reset from the keypad.
- Switch off power.
- DO NOT RE-CON­NECT POWER!
- Contact your local distributor.
---
8
System fault - component failure
- faulty operation Note exceptional fault data record Subcode in T.14: S1 = Reserved S2 = Reserved S3 = Reserved S4 = Reserved S5 = Reserved S6 = Reserved S7 = Charging switch S8 = No power to driver card S9 = Power unit communication (TX) S10 = Power unit communication (Trip) S11 = Power unit comm. (Measure­ment)
Reset the fault and restart. Should the fault re­occur, contact your local distributor.
---
Page 76
10
vacon • 77 MAINTENANCE AND TROUBLESHOOTING
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9
Undervoltage DC-link voltage is under the inverter
fault voltage limit. See user manual.
- most probable cause: too low a supply voltage
- Inverter internal fault
- One of input fuse is broken.
- In case of temporary supply voltage break, reset the fault and restart the inverter
- Check the supply voltage.
- If it is adequate, an internal failure has occurred.
- Check input fuses
- Check DC charge function
---
10
Line Sync Fail Output line phase is missing.
Subcode in T.14: S1 = Phase supervision diode supply S2 = Phase supervision active front end
Check supply voltage, fuses and cable.
X
11
Output phase supervision
Output line phase is missing. Check supply voltage,
fuses and cable.
---
13
Inverter under­temperature
Heatsink temperature is under –10
ºC
---
14
Inverter overtem­perature
Heatsink temperature is over 90
ºC
Overtemperature warning is issued when the heatsink temperature exceeds
85
ºC.
- Check the correct amount and flow of cooling air.
- Check the heatsink for dust.
- Check the ambient temperature.
---
18
Unbalance (Warning only)
Unbalance between power modules in paralleled units. Subcode in T.14: S1 = Current unbalance S2 = DC-Voltage unbalance
Should the fault re­occur, contact your local distributor.
---
22
EEPROM check­sum fault
Parameter save fault
- faulty operation
- component failure
Should the fault re­occur, contact your local distributor.
---
24
Counter fault Values displayed on counters are
incorrect
Have a critical attitude towards values shown on coun­ters.
---
25
Microprocessor watchdog fault
-faulty operation
- component failure
Reset the fault and restart. Should the fault re­occur, contact your local distributor.
---
Fault
code
Fault Possible cause Correcting measures
Auto
Reset
Page 77
MAINTENANCE AND TROUBLESHOOTING vacon • 78
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
10
26
Start-up pre­vented
- Start-up of the inverter has been prevented.
- Run request is ON when new appli­cation is loaded to inverter
- Cancel prevention of start-up if this can be done safely.
- Remove Run Request.
---
29
Thermistor fault The thermistor input of option board
has detected too high temperature
Check thermistor con­nection (If thermistor input of the option board is not in use it has to be short circuited)
---
31
IGBT tempera­ture (hardware)
IGBT Inverter Bridge over tempera­ture protection has detected too high a short term overload current
- Check loading.
X
32
Fan cooling Cooling fan of the inverter does not
start, when ON command is given
Contact your local dis­tributor.
---
35
Application Problem in application software Contact your distribu-
tor. If you are application pro­grammer check the application program.
---
36
Control unit NXS Control Unit can not control
NXP Power Unit and vice versa
Change control unit
---
37
Device changed (same type)
Option board or power unit changed. New device of same type and rating.
Reset. Device is ready for use. Old parameter set­tings will be used.
---
38
Device added (same type)
Option board added. Reset. Device is ready
for use. Old board settings will be used.
---
39
Device removed Option board removed. Reset. Device no lon-
ger available.
---
40
Device unknown Unknown option board or inverter.
Subcode in T.1 4: S1 = Unknown device S2 = Power1 not same type as Power2
Contact the distributor near to you.
---
41
IGBT tempera­ture
IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current
- Check loading.
X
Fault
code
Fault Possible cause Correcting measures
Auto
Reset
Page 78
10
vacon • 79 MAINTENANCE AND TROUBLESHOOTING
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
44
Device changed (different type)
Option board or power unit changed. New device of different type or differ­ent rating than the previous one.
Reset Set the option board parameters again if option bard changed. Set inverter parameters again if power unit changed.
---
45
Device added (different type)
Option board of different type added. Reset
Set the option board parameters again.
---
48
Parameter Fault Parameter Fault Check parameters
value
---
49
Division by zero in application
Division by zero has occurred in appli­cation programm
Contact your distribu­tor if the fault re-occurs while the inverter is in run state. If you are application programmer check the application program.
---
51
External Trip Trip signal from digital input. Remove fault situation
from external device.
X
53
Fieldbus Board A Fieldbus card in slot D or E has sta-
tus “Faulted”
Check installation. If installation is cor­rect contact the nearest distributor.
---
54
Slot Communica­tion
A option board in slot B,C,D or E has status “Communication Lost”
Check board and slot. Contact the nearest Vacon distributor.
---
55
SB Board Fault A systembus card in slot D or E has
status “Faulted”
Check the System bus Board
---
59
SB Heartbeat An inverter is activated as a slave
inverter in array configuration without a heartbeat signal on the bus, Hence, no master inverter active.
Check the System bus
---
64
MCC Fault Contactor acknowledgment is used
through digital input and close com­mand is given without response within the time set with parameter “MCont FaultDelay”
Check the main power switch of the Inverter and Acknowl­edge input.
---
Fault
code
Fault Possible cause Correcting measures
Auto
Reset
Page 79
MAINTENANCE AND TROUBLESHOOTING vacon • 80
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
10
70
LCL Temperature LCL Overtemp trip from digital input. Check the LCL filter
and signal connection. Check fan
---
72
AC VoltMax Trip AC voltage on line side is above the
max limit.
Check AC Voltage
Delayed
73
AC VoltMin Trip AC voltage on line side is below the
min limit.
Check AC Voltage
Delayed
74
FreqOverLimit AC frequency on line side is above the
max limit.
Check AC Frequency
Delayed
75
FreqUnderLimit AC frequency on line side is below the
min limit.
Check AC Frequency
Delayed
76
DC Ground Warn­ing
DC Insulation measurement signal has gone above the warning limit.
Check DC Insulation
---
77
DC Ground Fault DC Insulation measurement signal
has gone above the fault limit.
Check DC Insulation
Delayed
83
Surge Alarm Surge alarm from digital input. Remove fault situation
from external device.
---
85
Fieldbus Heartbeat signal from touchpad panel
is missing while running in array con­figuration. Warning = inverter not active Fault = inverter active
Check touchpad panel. Check the control place
Delayed
86
Input Switch Input Switch in wrong state Check the input Switch
---
90
High Voltage Time limit at HIGH voltage level
reached. Grid Code
Check grid voltage
---
91
Low Voltage Time limit at LOW voltage level
reached. Grid Code
Check grid voltage
---
92
High Frequency Time limit at HIGH frequency level
reached. Grid Code
Check grid frequency
---
93
Low Frequency Time limit at LOW voltage level
reached. Grid Code
Check grid frequency
---
94
Re Connect Time Grid has been faulty and Unit has
delay when that is reconnection to grid.
Wait 0-10minutes depending Grid standard.
---
95
Emergency Switching
Command for emergency stop received from digital input.
New run command is accepted after reset.
---
97
Power Limit Warning
Power is limited by temperature. Temperature is over 75degrees
Check Cooling sys­tems.
---
Fault
code
Fault Possible cause Correcting measures
Auto
Reset
Page 80
11
vacon • 82 APPENDIX A SINGLE LINE EXAMPLES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
11. APPENDIX A SINGLE LINE EXAMPLES
Sample diagrams of multimaster systems
NXV0400 without AC-section
Page 81
APPENDIX A SINGLE LINE EXAMPLES vacon • 83
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
11
NXV0600 with AC-section
Table 24.
Page 82
11
vacon • 84 APPENDIX A SINGLE LINE EXAMPLES
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
NXV1000 without AC-section
Page 83
APPENDIX B GROUNDING OVERVIEW vacon • 85
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
12
12. APPENDIX B GROUNDING OVERVIEW
Page 84
Document ID:
Rev. B
Manual authoring: documentation@vacon.com
Vacon Plc. Runsorintie 7 65380 Vaasa Finland
Subject to change without prior notice © 2012 Vacon Plc.
Find your nearest Vacon office
on the Internet at:
www.vacon.com
Find your nearest Vacon service centre
on the Extranet at:
www.extra.vacon.com
Loading...