Vacon 20 CP/X Applications Manual

Page 1
vacon®20 cp/x
ac drives
multipurpose application
manual
Page 2
Page 3
Service support: find your nearest Vacon service center at www.vacon.com
INDEX
Document ID: DPD00536H
Order code: DOC-APP03982+DLUK
Rev. H
Version release date: 26.1.15
Corresponds to application package ACIT1075V111.vcx
1. Multipurpose Application................................................................................. 2
1.1 Specific functions of Vacon Multipurpose application...................................................... 2
1.2 Example of control connections ....................................................................................... 3
1.3 Optional boards ................................................................................................................. 5
1.3.1 Option board installation................................................................................................... 8
2. Description of Groups .................................................................................... 12
2.1 Keypad Reference: Menu REF ........................................................................................ 12
2.2 Monitor group: menu MON ............................................................................................. 13
2.3 Parameter Groups: Menu PAR ....................................................................................... 14
2.3.1 Group Basic Parameters: Menu PAR G1 ........................................................................ 15
2.3.2 Group Advanced Settings: Menu PAR G2........................................................................ 16
2.3.3 Group Analogue inputs: Menu PAR G3 ........................................................................... 18
2.3.4 Group Digital inputs: Menu PAR G4 ................................................................................ 19
2.3.5 Group Digital outputs: Menu PAR G5.............................................................................. 21
2.3.6 Group Analogue outputs: Menu PAR G6 ......................................................................... 22
2.3.7 Group Supervisions: Menu PAR G7................................................................................. 23
2.3.8 Group Motor Control: Menu PAR G8............................................................................... 24
2.3.9 Group Protections: Menu PAR G9................................................................................... 26
2.3.10 Group Autoreset: Menu PAR G10.................................................................................... 29
2.3.11 Group Fieldbus: Menu PAR G11...................................................................................... 30
2.3.12 Group PID-controller: Menu Par G12 ............................................................................. 31
2.3.13 Group temperature measurement: Menu Par G13 ........................................................ 32
2.4 System parameters, Faults and History faults: Menu SYS/FLT..................................... 33
3. Parameter description................................................................................... 36
3.1 Basic Parameters............................................................................................................ 36
3.2 Advanced settings ........................................................................................................... 37
3.3 Analogue inputs............................................................................................................... 46
3.4 Digital inputs ................................................................................................................... 50
3.5 Digital outputs ................................................................................................................. 52
3.6 Analogue Output..............................................................................................................54
3.7 Supervisions .................................................................................................................... 55
3.8 Motor control................................................................................................................... 57
3.9 Protections ...................................................................................................................... 61
3.10 Autoreset ......................................................................................................................... 67
3.11 Fieldbus ........................................................................................................................... 69
3.11.1 Fieldbus mapping............................................................................................................ 70
3.12 PID Control ...................................................................................................................... 73
3.13 Temperature measurement ........................................................................................... 75
4. Fault tracing .................................................................................................. 78
Page 4
vacon • 1
Page 5
Multipurpose Application vacon • 2
Service support: find your nearest Vacon service center at www.vacon.com
1
1. MULTIPURPOSE APPLICATION
The VACON® 20 CP/X drive contains a preloaded application for instant use.
The parameters of this application are listed in chapter 2.3 of this manual and explained in more detail in chapter 2.
1.1 Specific functions of Vacon Multipurpose application
The Vacon Multipurpose allows flexible use of VACON® 20 CP/X frequency converters.
Features
The drive can be controlled through I/O terminals, a fieldbus or the optional keypad.Two pro­grammable control places and sources for the frequency reference are available, for easy lo­cal/remote control.
Frequency reference can be direct (analogue input, preset speeds, motor potentiometer, field­bus) or controlled by the internal PID regulator.
PID setpoint and actual value are totally programmable. A "sleep" function is available, with possibility of pressure boost and check of the losses before entering the stand-by state.
All the functionalities can be controlled through a fieldbus.
The motor identification function allows automatic optimization of the voltage/frequency curve, for a optimal torque response also at low motor speed.
It is possible to install one optional board for I/O or fieldbus expansion.
Both AC induction motor and PM motor can be controlled.
Page 6
vacon • 3 Multipurpose Application
1
1.2 Example of control connections
Table 1. Connection example, standard I/O terminals.
Standard I/O terminals
Terminal Signal Default
A
RS485 Serial bus, negative
B
RS485 Serial bus, positive
1
+10 Vref Reference output
2
AI1+
Analogue input, voltage or current
*
*
Selectable with DIP switches, see VACON® 20 CP/X
Installation Manual
Voltage
3
AI1-/GND
Analogue input common (current)
6
24Vout 24V aux. voltage
7
DIN COM Digital input common
8
DI1 Digital input 1 Start FWD
9
DI2 Digital input 2 Start REV
10
DI3 Digital input 3
Preset Speed B0
4
AI2+
Analogue input, voltage or current*
Current
5
AI2-/GND
Analogue input common (current)
13
DO1- Digital Output Common
14
DI4 Digital input 4
Preset Speed B1
15
DI5 Digital input 5
Fault reset
16
DI6 Digital input 6 Ramp 2
18
AO1+ Analogue signal (+output)
Output frequency
20
DO1+ Digital output +
Ready
Reference potentiometer
1...10 kΩ
V
To Relay terminals
1 or 2
PID Actual value
4...20mA/0...10V (programmable)
X1
Page 7
Multipurpose Application vacon • 4
Service support: find your nearest Vacon service center at www.vacon.com
1
Table 2. Connection example, Relay terminals
Relay terminals
Default
Terminal Signal
22 RO1/2 CM
Relay output 1 RUN
23 RO1/3 NO 24 RO1/1 NC
Relay output 1 FAULT
25 RO1/2 CM 26 RO1/3 NO
From
Standard I/O terminals
From term.
#3 or #5
From term.
#6
FAU LT
Page 8
vacon • 5 Multipurpose Application
1
1.3 Optional boards
One optional I/O expansion board can be installed into the slot on the right side of the drive. The following boards are supported:
OPTB1: 6 Digital Inputs-Outputs
The first 3 terminals are reserved as digital inputs (DI7, DI8, DI9). The second 3 terminals can be used as inputs (DI10, DI11, DI12) or digital outputs (EO1, EO2, EO3). The number of terminals used as input must be declared in parameter P2.24 (hidden if the board is not installed). This number determines the higher value for the selection of the digital input connected to a certain logical function. It also changes the visibility of parameters for the selection of digital outputs function (P5.9, P5.10, P5.11).
OPTB2: 1 Thermistor Input, 2 Relays Outputs
Response to thermistor fault can be programmed with parameter P9.16. Relays functions can be programmed with parameters P5.9, P5.10 (hidden if the board is not installed).
OPTB4: 1 Analogue Input, 2 Analogue Outputs
One more input is available as frequency reference. Signal programmable with parameters P3.9 - 12. Two more outputs are available to monitor motor/drive signals. Outputs are pro­grammable with parameters P6.5 - 12.
Parameters are hidden if the board is not installed.
OPTB5: 3 Relays Outputs
Relays functions can be programmed with parameters P5.9, P5.10, P5.11 (hidden if the board is not installed).
OPTB9: 5 Digital Inputs, 1 Relay Output
The higher value for the selection of the digital input (DI7, DI8, DI9, DI10, DI11) connected to a certain logical function is set to 11. Relay functions can be programmed with parameter P5.9 (hidden if the board is not installed).
OPTBF: 1 Analogue Output, 1 Digital Output, 1 Relay Output
The analogue output can be programmed with parameters P6.5 - 8. The digital output can be programmed with parameter P5.12. The relay output can be programmed with parameter P5.9. Parameters are hidden if the board is not installed.
OPTBH: 3 temperature sensors
When the board is installed, the specific menu G13 is visible. Temperature measurement can be used to set a digital/relay output and/or to trigger a fault. It can also be used as direct fre­quency reference or as actual value for PID regulation.
OPTBK: 4 ASi Outputs, 4 ASi Inputs
ASi outputs are managed as 4 optional digital inputs (DI7, DI8, DI9, DI10). The higher value for the selection of the digital input connected to a certain logical function is set to 10.
ASi inputs 1-4 are managed as 4 optional outputs (EO1, EO2, EO3, EO4) programmable with P5.9 - 12.
ASi inputs 1-3 are managed as 3 optional relay outputs (programmable with P5.9 - 11).
Page 9
Multipurpose Application vacon • 6
Service support: find your nearest Vacon service center at www.vacon.com
1
ASi input 4 is managed as optional digital output (programmable with P5.12).
OPTC3/E3: Profibus DPV1 fieldbus board
Vacon 20CP/X frequency converters can be connected to the PROFIBUS DP network using a fieldbus board. The converter can then be controlled, monitored and programmed from the Host system.OPTE3 option board also supports connection from DP Master (class 2) if DP-V1 is enabled. In this case, the Master class 2 can initiate a connection, read and write parameters using the PROFIdrive Parameter Access service, and close the connection. The PROFIBUS DP fieldbus is connected to the OPTE3 board using a 5-pin pluggable bus connector. The only dif­ference between OPTE3 and OPTE5 boards is the fieldbus connector.
OPTC4 Lonworks fieldbus board
Vacon 20CP/X frequency converters can be connected to the LonWorks® network using a fieldbus board. The converter can then be controlled, monitored and programmed from the Host system.
OPTC5/E5: Profibus DPV1 fieldbus board (D-type connector)
Vacon 20CP/X frequency converters can be connected to the PROFIBUS DP network using a fieldbus board. The converter can then be controlled, monitored and programmed from the Host system.OPTE5 option board also supports connection from DP Master (class 2) if DP-V1 is enabled. In this case, the Master class 2 can initiate a connection, read and write parameters using the PROFIdrive Parameter Access service, and close the connection. he PROFIBUS DP fieldbus is connected to the OPTE5 board using a 9-pin female sub-D-connector. The only dif­ference between OPTE3 and OPTE5 boards is the fieldbus connector.
OPTC6/E6: CanOpen fieldbus board
Vacon 20CP/X frequency converters can be connected to the CanOpen system using a fieldbus board. The converter can then be controlled, monitored and programmed from the Host sys­tem. Vacon CanOpen Board is connected to the fieldbus through a 5-pin pluggable bus connec­tor (board NXOPTE6).
OPTC7/E7: DeviceNet fieldbus board
Vacon 20CP/X frequency converters can be connected to the DeviceNet using a fieldbus board. The converter can then be controlled, monitored and programmed from the Host system. Va­con DeviceNet Board is connected to the fieldbus through a 5-pin pluggable bus connector (board OPTE7).
OPTCI: Modbus TCP fieldbus board
Vacon 20CP/X frequency converters can be connected to Ethernet using an Ethernet fieldbus board OPTCI. Every appliance connected to an Ethernet network has two identifiers; a MAC ad­dress and an IP address. The MAC address (Address format: xx:xx:xx:xx:xx:xx ) is unique to the appliance and cannot be changed. The Ethernet board's MAC address can be found on the sticker attached to the board or by using the Vacon IP tool software NCIPConfig. Please find the software installation at www.vacon.com. In a local network, IP addresses can be defined by the user as long as all units connected to the network are given the same network portion of the address. For more information about IP addresses, contact your Network Administrator. Overlapping IP addresses cause conflicts between appliances.
Page 10
vacon • 7 Multipurpose Application
1
OPTCP: Profinet fieldbus board
Vacon 20CP/X frequency converters can be connected to Ethernet using an Ethernet fieldbus board OPTCP. Every appliance connected to an Ethernet network has two identifiers; a MAC address and an IP address. The MAC address (Address format: xx:xx:xx:xx:xx:xx) is unique to the appliance and cannot be changed. The Ethernet board's MAC address can be found on the sticker attached to the board or by using the Vacon IP tool software NCIPConfig. You can find the software installation at www.vacon.com. In a local network, IP addresses can be defined by the user as long as all units connected to the network are given the same network portion of the address. For more information about IP addresses, contact your Network Administrator. Overlapping IP addresses cause conflicts between appliances.
OPTCQ: Ethernet IP fieldbus board
Vacon 20CP/X frequency converters can be connected to Ethernet using an EtherNet/IP field­bus board OPT-CQ. Every appliance connected to an Ethernet network has two identifiers; a MAC address and an IP address. The MAC address (Address format: xx:xx:xx:xx:xx:xx) is unique to the appliance and cannot be changed. The EtherNet/IP board's MAC address can be found on the sticker attached to the board or by using the Vacon IP tool software NCIPConfig. Please find the software installation at www.vacon.com. In a local network, IP addresses can be defined by the user as long as all units connected to the network are given the same network portion of the address. For more information about IP addresses, contact your Network Ad­ministrator. Overlapping IP addresses cause conflicts between appliances.
Page 11
Multipurpose Application vacon • 8
Service support: find your nearest Vacon service center at www.vacon.com
1
1.3.1 Option board installation
Figure 1. Opening the main cover, MU3 example.
NOTE! It is not allowed to add or replace option boards or fieldbus boards on an AC drive with the power switched on. This may damage the boards.
1
Open the cover of the drive.
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when the drive is disconnected from mains.
2
Remove the option slot cover.
Page 12
vacon • 9 Multipurpose Application
1
Figure 2. Removing the option slot cover.
3
Make sure that the sticker on the connector of the board says “dv” (dual voltage). This indicates that the board is compatible with Vacon 20CP/X. See below:
NOTE: Incompatible boards cannot be installed on Vacon 20CP/X. Compat­ible boards have a slot coding that enable the placing of the board (see above).
Slot coding
OPT
dv
9116.emf
Page 13
Multipurpose Application vacon • 10
Service support: find your nearest Vacon service center at www.vacon.com
1
Figure 3. Option board installation.
4
Install the option board into the slot as shown in the picture below.
5
Mount the option slot cover.
Page 14
vacon • 11 Multipurpose Application
1
Figure 4. Mounting of option slot cover: remove the plastic opening for option board termi-
nals.
Page 15
Description of Groups vacon • 12
Service support: find your nearest Vacon service center at www.vacon.com
2
2. DESCRIPTION OF GROUPS
2.1 Keypad Reference: Menu REF
This menu is automatically entered when pressing the LOC/REM keypad and shows the fre­quency reference in Local control mode.
The reference is also active when selected as main reference (P1.12=4) or as secondary refer­ence (P2.15=4).
Value is limited between min frequency P1.1 and max frequency P1.2.
In Local mode, or when keypad is the active control place (P1.11=1 or P2.14=1), direction of ro­tation is determined with P2.23 or by pressing the left or right arrow button: this functionality could be blocked by setting P2.27=1.
Page 16
vacon • 13 Description of Groups
2
2.2 Monitor group: menu MON
VACON® 20 CP/X AC drive provides you with a possibility to monitor the actual values of pa­rameters and signals as well as statuses and measurements. See Table in which the basic monitoring values are presented.
Code Monitoring value Unit ID Description
V1.1 Output frequency Hz 1 Output frequency to motor V1.2 Frequency reference Hz 25 Frequency reference to motor control V1.3 Motor shaft speed rpm 2 Motor speed in rpm V1.4 Motor Current A 3 V1.5 Motor Torque % 4 Calculated shaft torque V1.6 Motor Power % 5 Total power consumption of AC drive V1.7 Motor Voltage V 6 V1.8 Motor temperature % 9 Calculated motor temperature V1.9 DC-link Voltage V 7 V1.10 Unit temperature °C 8 Heatsink temperature V1.11 Board temperature °C 1825 Power board temperature V1.12 Analogue input 1 % 13 Analogue input AI1 V1.13 Analogue input 2 % 14 Analogue input AI2 V1.14 Exp. Analogue input % 1837 Analogue input on OPTB4 V1.15 Analogue output % 26 Analogue output V1.16 Exp. Analogue out 1 % 1838 Analogue output 1 on OPTB4-BF V1.17 Exp. Analogue out 2 % 1839 Analogue output 2 on OPTB4 V1.18 DI1, DI2, DI3 15 Digital inputs status V1.19 DI4, DI5, DI6 16 Digital inputs status V1.20 DI7, DI8, DI9 1835 Digital inputs on OPTB1 status V1.21 DI10, DI11, DI12 1836 Digital inputs on OPTB1 status V1.22 RO1, RO2, DO 17 Digital outputs status V1.23 EO1, EO2, EO3, EO4 1852 Expansion board digital outputs status V1.24 Process variable 29 Scaled process variable. See P7.10 V1.25 PID setpoint % 20 PID controller setpoint V1.26 PID error value % 22 PID controller error V1.27 PID feedback % 21 PID controller actual value V1.28 PID output % 23 PID controller output V1.29 Temperature sensor 1 °C or °K 1860 OPTBH sensor 1 V1.30 Temperature sensor 2 °C or °K 1861 OPTBH sensor 2 V1.31 Temperature sensor 3 °C or °K 1862 OPTBH sensor 3 V1.32 ASi board state 1894 OPTBK state
Table 3: Monitoring menu items.
NOTE!
Values V1.25-28 are hidden when PID output is not used as frequency reference. Values V1.14, V1.17 are hidden when OPTB4 expansion board is not installed. Value V1.16 is hidden when OPTB4-BF expansion board is not installed. Values V1.20, V1.21 are hidden when no expansion board with available inputs is installed. Value V1.23 is hidden when no expansion board with available outputs is installed. Values V1.29, V1.30, V1.31 are hidden when OPTBH expansion board is not installed. Value V1.32 is hidden when OPTBK expansion board is not installed.
Page 17
Description of Groups vacon • 14
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3 Parameter Groups: Menu PAR
The Multipurpose Application embodies the following parameter groups:
Column explanations:
Code = Location indication on the keypad; Shows the operator the parameter num-
ber. Parameter= Name of parameter Min = Minimum value of parameter Max = Maximum value of parameter Unit = Unit of parameter value; Given if available Default = Value preset by factory ID = ID number of the parameter Description= Short description of parameter values or its function
= The parameter may be changed only in Stop state
Menu and Parameter group Description
Group Basic Parameters: Menu PAR G1 Basic settings Group Advanced Settings: Menu PAR G2 Advanced parameter settings Group Analogue inputs: Menu PAR G3 Analogue input programming Group Digital inputs: Menu PAR G4 Digital input programming Group Digital outputs: Menu PAR G5 Digital output programming Group Analogue outputs: Menu PAR G6 Analogue outputs programming Group Supervisions: Menu PAR G7 Prohibit frequencies programming Group Motor Control: Menu PAR G8 Motor control and U/f parameters Group Protections: Menu PAR G9 Protections configuration Group Autoreset: Menu PAR G10 Auto reset after fault configuration Group Fieldbus: Menu PAR G11 Fieldbus data out parameters Group PID-controller: Menu Par G12 Parameters for PID Controller.
Group Temperature measurement: Menu Par G13
Temperature measurement parame­ters.
Table 4. Parameter groups.
Page 18
vacon • 15 Description of Groups
2
2.3.1 Group Basic Parameters: Menu PAR G1
Code Parameter Min Max Unit Default ID Description
P1.1 Min frequency 0.00 P1.2 Hz 0.00 101
Minimum allowed fre­quency reference
P1.2 Max frequency P1.1 320.00 Hz 50.00 102
Maximum allowed frequency reference
P1.3 Acceleration time 1 0.1 3000.0 s 3.0 103
Defines the time required for the output frequency to increase from zero fre­quency to maximum fre­quency
P1.4 Deceleration time 1 0.1 3000.0 s 3.0 104
Defines the time required for the output frequency to decrease from maximum frequency to zero frequency
P1.5 Current limit
0.2 x I
H
2 x I
H
A
I
H
107
Maximum motor current from AC drive
P1.6 Motor nominal voltage 180 500 V 400 110
Find this value U
n
on the
rating plate of the motor. This parameter sets the voltage at the field weaken­ing point to 100% * U
nMotor
.
Note also used connection (Delta/Star).
P1.7
Motor nominal
frequency
8.00 320.00 Hz 50.00 111
Find this value f
n
on the rat-
ing plate of the motor.
P1.8 Motor nominal speed 24 20000 rpm 1440 112
Find this value nn on the rat­ing plate of the motor.
P1.9 Motor nominal current
0.2 x I
H
2 x I
H
A
I
H
113
Find this value In on the rat­ing plate of the motor.
P1.10 Motor Cos ϕ 0.30 1.00 0.85 120
Find this value on the rating plate of the motor
P1.11 Control Place 0 2 0 125
Run and direction control: 0 = I/O terminals 1 = Keypad 2 = Fieldbus
P1.12
Frequency reference
source
0 5-7* 0 1819
Selection of reference source: 0 = AI1 1 = AI2 2 = PID reference 3 = Motor potentiometer 4 = Keypad 5 = Fieldbus 6 = Expansion AI1 7 = Temperature (*)6 requires expansion board OPTB4; 7 requires expansion board OPTBH.
P1.13 Start function 0 1 0 505
0=Ramping 1=Flying start
P1.14 Stop function 0 1 0 506
0=Coasting 1=Ramping
Table 5. Basic parameters.
Page 19
Description of Groups vacon • 16
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.2 Group Advanced Settings: Menu PAR G2
P1.15 Torque boost 0 1 0 109
0 = Not active 1 = Auto torque boost
P1.16 Show all parameters 0 1 0 115
0 = only Basic 1 = All groups
Code Parameter Min Max Unit Default ID Description
P2.1 Start/Stop logic 0 3 0 300
Logic = 0:
Start sign 1 = Start Forward Start sign 2 = Start Back­ward
Logic =1:
Start sign 1 = Start Start sign 2 = Reverse
Logic = 2:
Start sign 1 = Start pulse Start sign 2 = Stop pulse
Logic = 3:
Start sign 1 = Start Forward (edge) Start sign 2 = Start Back­ward (edge)
P2.2 Preset speed 1 0.00 P1.2 Hz 10.00 105 Multistep speed 1
P2.3 Preset speed 2 0.00 P1.2 Hz 15.00 106 Multistep speed 2
P2.4 Preset speed 3 0.00 P1.2 Hz 20.00 126 Multistep speed 3
P2.5 Preset speed 4 0.00 P1.2 Hz 25.00 127 Multistep speed 4
P2.6 Preset speed 5 0.00 P1.2 Hz 30.00 128 Multistep speed 5
P2.7 Preset speed 6 0.00 P1.2 Hz 40.00 129 Multistep speed 6
P2.8 Preset speed 7 0.00 P1.2 Hz 50.00 130 Multistep speed 7
P2.9 Acceleration time 2 0.1 3000.0 s 10.0 502
Time from 0 to max fre­quency
P2.10 Deceleration time 2 0.1 3000.0 s 10.0 503
Time from 0 to max fre­quency
P2.11
Accel1 to Accel2 tran-
sition frequency
0.00 P1.2 Hz 0.00 527
Threshold for auto change from acc1 to acc2
P2.12
Decel1 to Decel2 tran-
sition frequency
0.00 P1.2 Hz 0.00 528
Threshold for auto change from dec2 to dec1
P2.13 S ramp shape 1 0.0 10.0 s 0.0 500 Rounded speed profile.
P2.14
Control place 2
0 2 0 1806
Alternative control place: 0: I/O terminals 1: Keypad 2: Fieldbus
Table 6. Advanced settings group.
Table 5. Basic parameters.
Page 20
vacon • 17 Description of Groups
2
P2.15
Frequency reference
source 2
0 5-7* 1 1820
Selection of reference source 2: 0 = AI1 1 = AI2 2 = PID reference 3 = Motor potentiometer 4 = Keypad 5 = Fieldbus 6 = Expansion AI1 7 = Temperature (*)6 requires expansion board OPTB4; 7 requires expansion board OPTBH.
P2.16
MotorPotentiometer
Ramp
1 50 Hz/s 5 331
Rate of change in the motor potentiometer reference when increased or decreased.
P2.17
MotorPotent Ref Mem-
ory
0 2 0 367
Motor potentiometer fre­quency reference reset logic. 0 = No reset 1 = Reset if stopped or pow­ered down 2 = Reset if powered down
P2.18 Skip range 1 low lim 0.00 P1.2 Hz 0.00 509 0 = Not used
P2.19 Skip range 1 high lim 0.00 P1.2 Hz 0.00 510 0 = Not used
P2.20 Skip range 2 low lim 0.00 P1.2 Hz 0.00 511 0 = Not used
P2.21 Skip range 2 high lim 0.00 P1.2 Hz 0.00 512 0 = Not used
P2.22 Stop button active 0 1 1 114
0 = Limited function of Stop button 1 = Stop button always enabled
P2.23 Keypad Reverse 0 1 0 123
Motor rotation when con­trol place is keypad 0 = Forward 1 = Reverse
P2.24 OPTB1 Digital inputs 3 6 6 1829
Number of terminals used as digital inputs. The parameter is visible only when OPTB1 board is installed
P2.25
Quick Stop decelera-
tion time
0.1 3000.0 s 2.0 1889
Time from max frequency to 0
P2.26 S ramp shape 2 0.0 10.0 s 0.0 501
Rounded speed profile when Acc/Dec 2 is active.
P2.27
Keypad direction
change
0 1 0 1897
Allow to change motor direction using keypad LEFT and RIGHT arrow in REF menu 0: Allowed 1: Locked
NOTE!
Visibility of the group depends on P1.16.
Table 6. Advanced settings group.
Page 21
Description of Groups vacon • 18
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.3 Group Analogue inputs: Menu PAR G3
Code Parameter Min Max Unit Default ID Description
P3.1 AI1 signal range 0 1 0 379
0 = 0…10V / 0…20mA 1 = 2…10V / 4…20mA
P3.2 AI1 custom min -100.00 100.00 % 0.00 380
Custom range min setting 20% = 4-20 mA/2-10 V
P3.3 AI1 custom max -100.00 300.00 % 100.00 381 Custom range max setting
P3.4 AI1 filter time 0.0 10.0 s 0.1 378
Filter time for analogue input
P3.5 AI2 signal range 0 1 1 390
0 = 0…10V / 0…20mA 1 = 2…10V / 4…20mA
P3.6 AI2 custom min -100.00 100.00 % 0.00 391 See P3.2
P3.7 AI2 custom max -100.00 300.00 % 100.00 392 See P3.3
P3.8 AI2 filter time 0.0 10.0 s 0.1 389 See P3.4
P3.9 Exp. AI signal range 0 1 0 1841
0 = 0…10V / 0…20mA 1 = 2…10V / 4…20mA
P3.10
Exp. AI custom
min
-100.00 100.00 % 0.00 1842
Custom range min signal level
P3.11 Exp. AI custom max -100.00 300.00 % 100.00 1843
Custom range max signal level
P3.12 Exp. AI filter time 0.0 10.0 s 0.1 1844
Filter time for analogue input
Table 7. Analogue inputs group.
NOTE!
Visibility of the group depends on P1.16. Parameters P3.9 - P3.12 are shown only when expansion board OPTB4 is installed.
Page 22
vacon • 19 Description of Groups
2
2.3.4 Group Digital inputs: Menu PAR G4
Code Parameter Min Max Unit Default ID Description
P4.1 Start signal 1 0 6* 1 403
Start signal 1 when control place is I/O 1 (FWD) See P2.1 for function. 0 = not used 1 = DIN1 2 = DIN2 3 = DIN3 4 = DIN4 5 = DIN5 6 = DIN6 7 = DIN7 8 = DIN8 9 = DIN9 10 = DIN10 11 = DIN11 12 = DIN12
P4.2 Start signal 2 0 6* 2 404
Start signal 2 when control place is I/O 1 (REV). See P2.1 for function. See P4.1 for selections.
P4.3 Reverse 0 6* 0 412
Independent from P2.1 See P4.1 for selections
P4.4 External fault close 0 6* 0 405
Fault if signal high See P4.1 for selections
P4.5 External fault open 0 6* 0 406
Fault is signal low See P4.1 for selections
P4.6 Fault reset 0 6* 5 414 Resets all active faults
P4.7 Run enable 0 6* 0 407
Must be on to set drive in Ready state
P4.8 Preset speed B0 0 6* 3 419
Binary selector for Preset speeds (0-7).
P4.9 Preset speed B1 0 6* 4 420
Binary selector for Preset speeds (0-7).
P4.10 Preset speed B2 0 6* 0 421
Binary selector for Preset speeds (0-7).
P4.11 Sel Accel/Decel 2 0 6* 6 408
Activates ramp 2 See P4.1 for selections
P4.12
MotorPotent increase
speed
06* 0418
Reference increase See P4.1 for selections
P4.13
MotorPotent decrease
speed
06* 0417
Reference decrease See P4.1 for selections
P4.14 Sel Control Place 2 0 6* 0 1813
Activates control place 2 See P4.1 for selections
P4.15 Sel Freq reference 2 0 6* 0 1814
Activates reference 2 See P4.1 for selections
P4.16 Sel PID setpoint 2 0 6* 0 431
Activates setpoint 2 See P4.1 for selections
Table 8. Digital inputs parameters.
Page 23
Description of Groups vacon • 20
Service support: find your nearest Vacon service center at www.vacon.com
2
P4.17 Quick Stop open 0 6* 0 1888
If configured, low signal acti­vates stop with specific ramp. See P4.1 for selections. NOTE: quick stop function must be enabled with P4.18=1
P4.18 Stop Mode Activation 0 2 0 1895
0: normal 1: quick stop 2: accurate stop (from Start signal 1 or 2)
NOTE!
(*)The maximum value is higher when an optional board with digital inputs is installed (see chapter 1.3 and Table 9 for more details). Parameter is automati­cally reset if value is greater than present limit.
NOTE!
Visibility of the group depends on P1.16.
Option board
installed
Maximum value for
digital input selection
Digital inputs available
OPTB1 12 DIN7, DIN8, DIN9, DIN10, DIN11, DIN12 OPTB9 7 DIN7 OPTBK 10 DIN7, DIN8, DIN9, DIN10
Table 9. Maximum value for digital input selection depending on installed option board.
Table 8. Digital inputs parameters.
Page 24
vacon • 21 Description of Groups
2
2.3.5 Group Digital outputs: Menu PAR G5
Code Parameter Min Max Unit Default ID Description
P5.1 Relay output 1 content 0 14 2 313
Function selection for RO1: 0 = Not used 1 = Ready 2 = Run 3 = General fault 4 = General fault inverted 5 = Warning 6 = Reversed 7 = At speed 8 = Output freq. supervision 9 = Output current superv. 10 = Analogue input superv. 11 = Fieldbus 1 12 = Fieldbus 2 13 = External brake 14 = Temperature supervi­sion (OPTBH)
P5.2 Relay output 2 content 0 14 3 314 See P5.1
P5.3 Digital output content 0 14 1 312 See P5.1
P5.4 Relay output 1 on delay 0.00 320.00 s 0.00 458 ON delay for relay
P5.5 Relay output 1 off delay 0.00 320.00 s 0.00 459 OFF delay for relay
P5.6 Relay output 1 inversion 0 1 0 1804
0 = no inversion 1 = inverted
P5.7 Relay output 2 on delay 0.00 320.00 s 0.00 460 See P5.4
P5.8 Relay output 2 off delay 0.00 320.00 s 0.00 461 See P5.5
P5.9 Exp. EO1 content 0 14 0 1826
Parameter visible when a I/ O expansion board is installed. See P5.1 for selection
P5.10 Exp. EO2 content 0 14 0 1827 See P5.9
P5.11 Exp. EO3 content 0 14 0 1828 See P5.9
P5.12 Exp. EO4 content 0 14 0 1872 See P5.9
Table 10. Digital outputs parameters.
NOTE!
Visibility of the group depends on P1.16. P5.9 is visible when OPTB2,OPTB5, OPTB9 or OPTBF is installed (first relay EO1). P5.10 is visible when OPTB2 or OPTB5 is installed (second relay EO2). P5.11 is visible when OPTB5 is installed (third relay EO3). P5.9, P5.10, P5.11 are also visible when OPTB1 is installed and some outputs have been set with P2.24 (digital outputs EO1, EO2, EO3). P5.12 is visible when OPTBF is installed (digital output EO4). Selection 14 as output function requires OPTBH board installed. P5.9, P5.10, P5.11, P5.12 are also visible when OPTBK is installed (EO1,2,3,4 cor­responding to ASi inputs 1,2,3,4).
Page 25
Description of Groups vacon • 22
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.6 Group Analogue outputs: Menu PAR G6
Code Parameter Min Max Unit Default ID Description
P6.1
Analogue output
function
0 8 2 307
0 = Not used (fixed 100%) 1 = Freq. reference (0-fmax) 2 = Output freq. (0 -fmax) 3 = Motor speed (0 - Speed max) 4 = Output current (0-I
nMotor
)
5 = Motor torque (0-T
nMotor
)
6 = Motor power (0-P
nMotor
)
7 = PID output (0-100%) 8 = Filedbus(0-10000)
P6.2
Analogue output
minimum
0 1 0 310
0 = 0V 1 = 2V
P6.3 Analogue output scale 0,0 1000,0 % 100.0 311 Scaling factor
P6.4
Analogue output filter
time
0.00 10.00 s 0.10 308
Filtering time of analogue out­put signal. 0 = No filtering
P6.5 Exp. AO1 function 0 8 2 1844 See P5.1
P6.6 Exp. AO1 minimum 0 1 0 1845
0 = 0 mA 1 = 4 mA
P6.7 Exp. AO1 Output scale 0,0 1000,0 % 100.0 1846 Scaling factor
P6.8 Exp. AO1 filter time 0.00 10.00 s 0.10 1847
Filtering time of analogue out­put signal. 0 = No filtering
P6.9 Exp. AO2 function 0 8 2 1848 See P6.1
P6.10 Exp. AO2 minimum 0 1 0 1849
0 = 0 mA 1 = 4 mA
P6.11 Exp. AO2 Output scale 0,0 1000,0 % 100.0 1850 Scaling factor
P6.12 Exp. AO2 filter time 0.00 10.00 s 0.10 1851
Filtering time of analogue out­put signal. 0 = No filtering
Table 11. Analogue outputs parameters.
NOTE!
Visibility of the group depends on P1.16. Parameters P6.5 - P6.18 are shown only when expansion board OPTB4 or OPTBF is installed. Parameters P6.9 - P6.12 are shown only when expansion board OPTB4 is installed.
Page 26
vacon • 23 Description of Groups
2
2.3.7 Group Supervisions: Menu PAR G7
Code Parameter Min Max Unit Default ID Description
P7.1
Frequency
supervision 1
02 0315
0 = not used 1 = Low limit 2 = High limit
P7.2
Frequency supervision
value
0.00 P1.2 Hz 0.00 316
Output frequency supervision threshold
P7.3
Current supervision
value
0.00
2 x I
H
A0.001811
Current supervision thresh­old
P7.4 AnalogIn Supv Signal 0 2 0 356
0 = AI1 1 = AI2 2 = AIE (if option OPTB4)
P7.5 AnalogIn Supv ON level 0.00 100.00 % 80.00 357 ON threshold AI supervision
P7.6
AnalogIn Supv OFF
level
0.00 100.00 % 40.00 358 OFF threshold AI supervision
P7.7
External brake open
frequency
0.00 10.00 Hz 2.00 1808
Frequency threshold for brake open
P7.8
External brake open
current
0.0 100.0 % 30.0 1810
Current threshold for brake open
P7.9
External brake close
frequency
0.00 10.00 Hz 2.00 1809
Frequency threshold for brake close (Start = 0)
P7.10 Process Source Select 0 5 2 1036
Selection of variable propor­tional to process: 0 = PID feedback value 1 = Output frequency 2 = Motor speed 3 = Motor torque 4 = Motor power 5 = Motor current
P7.11
Process Val Decim
Digits
0 3 1 1035 Decimals on display
P7.12 Process Max Value 0.0 3276.7 100.0 1034
Process display max value (it depends on P7.11: with zero decimal digit the max value is 32767; with 1 decimal digit the max value is 3276.7)
Table 12. Supervision parameters.
NOTE!
Visibility of the group depends on P1.16.
Page 27
Description of Groups vacon • 24
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.8 Group Motor Control: Menu PAR G8
Code Parameter Min Max Unit Default ID Description
P8.1 Motor control mode(*) 0 1 0 600
0 = Frequency control 1 = Speed control
P8.2 Field Weakening Point 30.00 320.00 Hz 50.00 602
Field weakening point fre­quency
P8.3
Voltage at Field Weak-
ening Point
10.00 200.00 % 100.00 603
Voltage at FWP as % of Motor nominal voltage
P8.4 U/f ratio selection(*) 0 2 0 108
0 = linear 1 = quadratic 2 = programmable
P8.5
U/f curve midpoint
frequency(*)
0.00 P8.2 Hz 50.00 604
Midpoint frequency for pro­grammable U/f curve
P8.6
U/f curve midpoint
voltage(*)
0.00 P8.3 % 100.00 605
Midpoint voltage for pro­grammable U/f curve
P8.7
Output voltage at zero
frequency (*)
0.00 40.00 % 0.00 606
Voltage at 0,00 Hz as % of Motor nominal voltage
P8.8 Switching frequency 1.5 16.0 kHz 6.0 601
Motor noise can be mini­mized using a high switch­ing frequency. Increasing the switching frequency reduces the capacity of the drive. It is recommended to use a lower frequency when the motor cable is long in order to minimize capacitive currents in the cable.
P8.9 Brake chopper 0 2 0 504
0 = Disabled 1 = Enabled in RUN 2 = Enabled in READY
P8.10
Brake chopper thresh-
old
600 900 V 765 1807
DC-link voltage to start chopper.
P8.11 DC brake current
0.3 x I
H
2 x I
H
A
I
H
507
Defines the current injected into the motor dur­ing DC-braking. 0 = Disabled
P8.12
DC braking time at
stop
0.00 600.00 s 0.00 508
Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping.
P8.13
Frequency to start DC
braking at ramp stop
0.10 10.00 Hz 1.50 515
The output frequency at which the DC-braking is applied.
P8.14
DC braking time at
start
0.00 600.00 s 0.00 516
This parameter defines the time for how long DC cur­rent is fed to motor before acceleration starts.
P8.15
Motor stator voltage
drop(*)
0.00 100.00 % 0.00 662
Voltage drop on the motor windings as % of Motor nominal voltage
Table 13. Motor control parameters.
Page 28
vacon • 25 Description of Groups
2
P8.16 Motor Identification 0 1 0 631
0 = not active 1 = standstill identification (to activate, RUN com­mand within 20s)
P8.17
Disable overvoltage
regulator
0 1 0 1853
0 = Enabled 1 = Disabled
P8.18
Disable undervoltage
regulator
0 1 0 1854
0 = Enabled 1 = Disabled
P8.19
Disable switching freq
regulator
0 1 0 1855
0 = Enabled 1 = Disabled
P8.20 Motor Type 0 1 0 650
0: Induction motor 1: Permanent magnet motor (PM motor)
NOTE!
(*) Parameter is automatically set by motor identification.
NOTE!
Visibility of the group depends on P1.16.
Table 13. Motor control parameters.
Page 29
Description of Groups vacon • 26
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.9 Group Protections: Menu PAR G9
Parameters of Motor thermal protection (P9.11 to P9.14 and P9.21-P9.22)
The motor thermal protection is to protect the motor from overheating. The drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that the motor will be thermally overloaded. This is the case especially at low frequen­cies. At low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current I
T
speci­fies the load current above which the motor is overloaded. This current limit is a function of the output frequency.
The thermal stage of the motor can be monitored on the control keypad display. See chapter 1.
Parameters of Stall protection (P9.4 to P9.6)
The motor stall protection protects the motor from short time overload situations such as one caused by a stalled shaft. The reaction time of the stall protection can be set shorter than that of motor thermal protection. The stall state is defined with two parameters, P9.5 (
Stall time)
and P9.6 (
Stall frequency limit). If the current is as high as the P1.5 (Current Limit) and the cur-
rent limiter has reduced the output frequency below the P9.6 for the time P9.5 than the set limit the stall state is true. There is actually no real indication of the shaft rotation. Stall protection is a type of overcurrent protection.
Parameters of Underload protection (P9.7 to P9.10)
The purpose of the motor underload protection is to ensure that there is load on the motor when the drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken belt or a dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters P9.8 (Underload protection: Field weakening area load) and P9.9 (
Underload protection: Zero
frequency load
), see below. The underload curve is a squared curve set between the zero fre­quency and the field weakening point. The protection is not active below 5Hz (the underload time counter is stopped).
If you use long motor cables (max. 100m) together with small drives (1.5 kW) the motor current measured by the drive can be much higher than the actual motor current due to capacitive currents in the motor cable. Consider this when setting up the motor thermal protection functions.
The calculated model does not protect the motor if the airflow to the motor is reduced by blocked air intake grill. The model starts from zero if the control board is powered off.
If you use long motor cables (max. 100m) together with small drives (1.5 kW) the motor current measured by the drive can be much higher than the actual motor current due to capacitive currents in the motor cable. Consider this when setting up the motor thermal protection functions.
Page 30
vacon • 27 Description of Groups
2
The torque values for setting the underload curve are set in percentage which refers to the nominal torque of the motor. The motor's name plate data, parameter motor nominal current and the drive's nominal current I
L
are used to find the scaling ratio for the internal torque val­ue. If other than nominal motor is used with the drive, the accuracy of the torque calculation decreases.
If you use long motor cables (max. 100m) together with small drives (1.5 kW) the motor current measured by the drive can be much higher than the actual motor current due to capacitive currents in the motor cable. Consider this when setting up the motor thermal protection functions.
Code Parameter Min Max Unit Default ID Description
P9.1
Response to 4mA
reference fault
(< 4mA)
04 1700
0 = No action 1 = Warning 2 = Fault 3 = Warning if Start active 4 = Fault if Start active
P9.2
4mA fault detection
time
0.0 10.0 s 0.5 1430 Time limit
P9.3 Earth fault protection 0 2 2 703
0 = No action 1 = Warning 2 = Fault
P9.4 Motor stall protection 0 2 1 709 See P9.3
P9.5 Motor stall delay 0.0 300.0 s 5.0 711
This is the maximum time allowed for a stall stage.
P9.6 Motor stall min freq 0.10 320.00 Hz 15.00 712
For a stall state to occur, the output frequency must have remained below this limit for a certain time.
P9.7 Underload protection 0 2 0 713 See P9.3
P9.8
Underload load curve
at nominal freq
10.0 150.0 % 50.0 714
This parameter gives the value for the minimum torque allowed when the out­put frequency is above the field weakening point.
P9.9
Underload load curve
at zero freq
5.0 150.0 % 10.0 715
This parameter gives value for the minimum torque allowed with zero frequency.
P9.10 Underload time 1.0 300.0 s 20.0 716
This is the maximum time allowed for an underload state to exist.
P9.11
Thermal protection of
the motor
0 2 2 704 See P9.3
P9.12
Motor ambient
temperature
-20 100 °C 40 705 Ambient temperature in °C
P9.13
Motor cooling factor at
zero speed
0.0 150.0 % 40.0 706
Defines the cooling factor at zero speed in relation to the point where the motor is run­ning at nominal speed with­out external cooling.
P9.14
Motor thermal time
constant
1 200 min 45 707
The time constant is the time within which the calculated thermal stage has reached 63% of its final value.
Table 14. Protections settings.
Page 31
Description of Groups vacon • 28
Service support: find your nearest Vacon service center at www.vacon.com
2
P9.15
Response to fieldbus
fault
0 2 2 733 See P9.3
P9.16 Thermistor fault 0 2 2 732
See P9.3 Available only if OPTB2 option board is installed.
P9.17 Parameter lock 0 1 0 1805
0 = Edit enabled 1 = Edit disabled
P9.18
Response to STO
disable
03 11876
0 = No action 1 = Warning 2 = Fault, not stored in his­tory menu 3 = Fault, stored in history menu
P9.19
Response to input
phase fault
0 2 2 1877 See P9.3
P9.20
Input phase fault max
ripple
0 75 0 1893
0 = internal value 1 = max sensitivity -> 75 = min sensitivity
P9.21
Motor temp initial
mode
02 21891
0 = start from minimum 1 = start from constant value 2 = start from last value
P9.22
Motor temp initial value
0100%331892
Initial value(P9.21 = 1) or fac­tor for last previous value(P9.21 = 2)
P9.24 Output phase fault 0 2 2 702 See P9.3
NOTE!
Visibility of the group depends on P1.16.
Table 14. Protections settings.
Page 32
vacon • 29 Description of Groups
2
2.3.10 Group Autoreset: Menu PAR G10
Code Parameter Min Max Unit Default ID Description
P10.1 Automatic fault reset 0 1 0 731
0 = Disabled 1 = Enabled
P10.2 Wait time 0.10 10.0 s 0.50 717
Wait time before the first reset is executed.
P10.3 Trial time 0.00 60.0 s 30.00 718
When the trial time has elapsed, and the fault is still active, the drive will trip to fault.
P10.4 Automatic reset tries 1 10 3 759
NOTE: Total number of trials (irrespective of fault type)
P10.5 Start function 0 2 0 719
The start mode for Automatic reset is selected with this parameter: 0 = Ramp 1 = Flying start 2 = According to par. P1.13
P10.6
Undervoltage fault
autoreset
0 1 1 720 See P10.1
P10.7
Overvoltage fault
autoreset
0 1 1 721 See P10.1
P10.8
Overcurrent fault
autoreset
0 1 1 722 See P10.1
P10.9
Motor Overtemp fault
autoreset
0 1 1 725 See P10.1
P10.10
Underload fault
autoreset
0 1 1 738 See P10.1
Table 15. Autoreset settings
NOTE!
Visibility of the group depends on P1.16.
Page 33
Description of Groups vacon • 30
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.11 Group Fieldbus: Menu PAR G11
Code Parameter Min Max Unit Default ID Description
P11.1
ProcessDataOut 1
selection
0 16 0 852
Variable mapped on PD1: 0 = Output current 1 = Motor speed 2 = Motor current 3 = Motor voltage 4 = Motor torque 5 = Motor power 6 = DC-link voltage 7 = Active fault code 8 = Analogue AI1 9 = Analogue AI2 10 = Digital inputs state 11 = PID feedback value 12 = PID setpoint 13 = Analogue AI3 14 = Temperature 1 15 = Temperature 2 16 = Temperature 3
P11.2
ProcessDataOut 2
selection
0 16 1 853
Variable mapped on PD2. See P11.1
P11.3
ProcessDataOut 3
selection
0 16 2 854
Variable mapped on PD3. See P11.1
P11.4
ProcessDataOut 4
selection
0 16 4 855
Variable mapped on PD4. See P11.1
P11.5
ProcessDataOut 5
selection
0 16 5 856
Variable mapped on PD5. See P11.1
P11.6
ProcessDataOut 6
selection
0 16 3 857
Variable mapped on PD6. See P11.1
P11.7
ProcessDataOut 7
selection
0 16 6 858
Variable mapped on PD7. See P11.1
P11.8
ProcessDataOut 8
selection
0 16 7 859
Variable mapped on PD8. See P11.1
P11.9 FB Aux CW selection 0 5 0 1821
PDI for Aux CW 0 = Not used 1 = PDI1 2 = PDI2 3 = PDI3 4 = PDI4 5 = PDI5
P11.10
FB PID setpoint
selection
0 5 1 1822
PDI for PID Setpoint See P11.9
P11.11
FB PID actual
selection
0 5 2 1823
PDI for PID Feedback See P11.9
P11.12
FB Analogue Out cntrl
selection
0 5 3 1824
PDI for Analogue Out CTRL See P11.9
Table 16. Fieldbus data mapping.
NOTE!
Visibility of the group depends on P1.16. Selection 13 as data out requires board OPTB4 installed. Selections 14, 15, 16 as data out require board OPTBH installed.
Page 34
vacon • 31 Description of Groups
2
2.3.12 Group PID-controller: Menu Par G12
Code Parameter Min Max Unit
Defau
lt
ID Description
P12.1 Setpoint source 0 3 0 332
0 = PID setpoint 1/2 1 = AI1 2 = AI2 3 = Fieldbus
P12.2 PID setpoint 1 0.0 100.0 % 50.0 167 Fixed setpoint 1
P12.3 PID setpoint 2 0.0 100.0 % 50.0 168 Fixed setpoint 2
P12.4 Feedback source 0 4 0 334
0 = AI2 1 = AI1 2 = Fieldbus 3 = AI2- AI1 4 = Temperature (OPTBH)
P12.5 Feedback minimum 0.0 50.0 % 0.0 336 Value at minimum signal
P12.6 Feedback maximum 10.0 300.0 % 100.0 337 Value at maximum signal
P12.7 PID controller P gain 0.0 1000.0 % 100.0 118
If the value of the parameter is set to 100% a change of 10% in the error value causes the con­troller output to change by 10%.
P12.8 PID controller I-time 0.00 320.00 s 10.00 119
If this parameter is set to 1,00 second a change of 10% in the error value causes the control­ler output to change by 10.00%/ s.
P12.9 PID controller D-time 0.00 10.00 s 0.00 132
If this parameter is set to 1,00 second a change of 10% in the error value during 1.00 s causes the controller output to change by 10.00%.
P12.10 Error value inversion 0 1 0 340
0 = Normal (Feedback < Setpoint
-> Increase PID output) 1 = Inverted (Feedback < Set­point ->
Decrease PID output
)
P12.11 PID error limit 0.0 100.0 % 100.0 1812 Limit on error
P12.12 Sleep frequency 0.00 P1.2 Hz 0.00 1016
Drive goes to sleep mode when the output frequency stays below this limit for a time greater than that defined by parameter P12.13.
P12.13 Sleep time delay 0 3600 s 30 1017
The minimum amount of time the frequency has to remain below the Sleep level before the drive is stopped.
P12.14 Wake-up limit 0.0 100.0 % 5.0 1018
Defines the level for the PID feedback value wake-up.
P12.15 Sleep setpoint boost 0.0 50.0 % 10.0 1815 Referred to setpoint
P12.16 Sleep boost time 0 60 s 10 1816 Boost time after P12.13
P12.17 Sleep max loss 0.0 50.0 % 5.0 1817 Referred to feedback after boost
P12.18 Sleep loss check time 1 300 s 30 1818 After boost time P12.16
Table 17. PID controller parameters.
NOTE!
This group is hidden when PID output is not used as frequency reference.
Page 35
Description of Groups vacon • 32
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.13 Group temperature measurement: Menu Par G13
Code Parameter Min Max Unit
Defau
lt
ID Description
P13.1 Temperature unit 0 1 0 1863
0 = °C 1 = °K
P13.2
Superv/Fault sensor
select
0 6 0 1873
0= T1 1= T2 2= T1 + T2 3= T3 4= T3 + T1 5= T3 + T2 6= T3 + T2 + T1
P13.3 Supervision mode 0 2 1 1864
0: not used 1: over threshold 2: below threshold
P13.4 Fault mode 0 2 0 1865
0: not used 1: over threshold 2: below threshold
P13.5 Supervision level
-30.0
223.2
200.0
473.2°C°K
80.0 1867 Threshold for supervision
P13.6 Fault level
-30.0
223.2
200.0
473.2°C°K
100.0 1866
Threshold for fault (F56 fault code)
P13.7 Superv/fault Hysteresis 0.0 50.0
°C °K
2.0 1868 Hysteresis for state change
P13.8
Refer/Actual sensor
select
0 6 0 1869
0= T1 1= T2 2= T3 3= max(T1,T2) 4= min(T1,T2) 5= max(T1, T2, T3) 6= min(T1, T2, T3)
P13.9
Min Ref/Actual
temperature
-30.0
223.2
200.0
473.2°C°K
0.0 1870
Temperature for min reference/ actual
P13.10
Max Ref/Actual
temperature
-30.0
223.2
200.0
473.2°C°K
100.0 1871
Temperature for max reference/ actual
Table 18. Temperature measurement parameters.
NOTE!
This group is hidden when board OPTBH is not installed.
Page 36
vacon • 33 Description of Groups
2
2.4 System parameters, Faults and History faults: Menu SYS/FLT
Code Parameter Min Max Unit
Defa
ult
ID Description
V1.1 API system SW ID 2314
V1.2 API system SW version 835
V1.3 Power SW ID 2315
V1.4 Power SW version 834
V1.5 Application ID 837
V1.6 Application revision 838
V1.7 System load 839
When no fieldbus board or no OPTBH board has been installed, the following values are visible:
V2.1 Communication status 808
Status of Modbus communication. Format: xx.yyy where xx = 0 - 64 (Number of error messages) yyy = 0 ­999 (Number of good messages)
V2.9 Last communication fault 816
The fault code related to the last counted bad messages is shown: 1 = Illegal function 2 = Illegal address 3 = Illegal data value 4 = Illegal slave device 53 = USART receive fault (par­ity error/ frame error/USART buffer overflow) 90 = Receive buffer overflow 100 = Frame CRC Error 101 = Ring buffer overflow
P2.2 Fieldbus protocol 0 1 0 809
0 = Not used 1 = Modbus used
P2.3 Slave address 1 255 1 810
P2.4 Baud rate 0 8 5 811
0 = 300 1 = 600 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200 7 = 38400 8 = 57800
P2.6 Parity type 0 2 0 813
Parity type: 0 = None 1 = Even 2 = Odd Stop bit:
- 2-bits with parity type “None”;
- 1-bit with parity type “Even” and “Odd”.
P2.7 Communication time out 0 255 s 0 814
P2.8 Reset communication status 0 1 0 815
Table 19. System parameters, Faults and History faults.
Page 37
Description of Groups vacon • 34
Service support: find your nearest Vacon service center at www.vacon.com
2
When OPTE6 (CANopen) option board has been installed, the following values are visible:
V2.1
CANopen communication
status
14004
P2.2 CANopen operation mode 1 2 1 14003
P2.3
CANopen Node ID
1 127 1 14001
P2.4 CANopen baud rate 1 8 6 14002
When OPTE7 (DeviceNet) option board has been installed, the following values are visible:
V2.1
DeviceNet communication
status
14014
P2.2 Output assembly type 20 111 21 14012
P2.3 MAC ID 0 63 63 14010
P2.4 Baud Rate 1 3 1 14011
P2.5 Input assembly type 70 117 71 14013
When OPTE3/E5(Profibus) option board has been installed, the following values are visible:
V2.1
Profibus communication sta-
tus
14022
P2.2 Fieldbus protocol 14023
P2.3 Active protocol 14024
P2.4 Active baud rate 14025
P2.5 Telegram type 14027
P2.6 Operate mode 1 3 1 14021
P2.7 Slave address 2 126 126 14020
When OPTEC (EtherCAT) option board has been installed, the following values are visible:
V2.1 Version number 0
Version number of the board software
V2.2 Board status 0 Status of OPTEC board
When OPTC4 (Lonworks) option board has been installed, the following values are visible:
P2.1 Service PIN 0 0 14217
Broadcasts a service pin mes­sage to the network.
When OPTBH option board has been installed, the following values are visible:
P2.1 Sensor 1 type 0 6 0 14072
0 = No Sensor 1 = PT100 2 = PT1000 3 = Ni1000 4 = KTY84 5 = 2 x PT100 6 = 3 x PT100
P2.2 Sensor 2 type 0 6 0 14073 See P2.1
P2.3 Sensor 3 type 0 6 0 14073 See P2.1
Other information:
V3.1 MWh counter 827
V3.2 Power on day counter 828
V3.3 Power on hour counter 829
V3.4 RUN day counter 840
V3.5 RUN hour counter 841
V3.6 Fault counter 842
V3.7
Panel parameter set status
monitor
Hidden when PC is connected
Table 19. System parameters, Faults and History faults.
Page 38
vacon • 35 Description of Groups
2
P4.2 Restore factory defaults 0 1 0 831
1 = Restore factory defaults for all parameters
P4.3 Password 0 9999
000
0
832
P4.4 Time for keypad backlight 0 99 min 5 833
P4.5 Save parameters to Keypad 0 1 0
1= Upload all parameters to Keypad Hidden when PC is connected. This function works properly only with drive supplied.
P4.6
Download parameters from
Keypad
01 0
1= Download all parameters to Keypad Hidden when PC is connected. This function works properly only with drive supplied.
F5.x Active fault menu 0 9 Hidden when PC is connected
F6.x Fault history menu 0 9 Hidden when PC is connected
Table 19. System parameters, Faults and History faults.
Page 39
Parameter description vacon • 36
Service support: find your nearest Vacon service center at www.vacon.com
3
3. PARAMETER DESCRIPTION
Due to its user-friendliness and simplicity of use, the most parameters only require a basic de­scription which is given in the parameter tables in chapter 2.2.
In this chapter, you will find additional information on certain most advanced parameters. Should you not find the information you need contact your distributor.
3.1 Basic Parameters
P1.1 MIN FREQUENCY
Minimum frequency reference.
NOTE: if motor current limit is reached, actual output frequency might be lower than parame­ter. If this is not acceptable, stall protection should be activated.
P1.2 M
AX FREQUENCY
Maximum frequency reference.
P1.3 A
CCELERATION TIME 1
Ramp time, referred to variation from zero frequency to max frequency.
A second acceleration time is available in P2.5.
P1.4 D
ECELERATION TIME 1
Ramp time, referred to variation from max frequency to zero.
A second deceleration time is available in P2.6.
P1.5 C
URRENT LIMIT
This parameter determines the maximum motor current from the AC drive. The parameter value range differs from size to size.
When the current limit is active the drive output frequency is decreased.
NOTE: This is not an overcurrent trip limit.
P1.11 C
ONTROL PLACE
Run and direction control. A second control place is programmable in P2.10.
0: I/O terminals
1: Keypad
2: Fieldbus
P1.12 F
REQUENCY REFERENCE SOURCE
Defines the source of frequency reference. A second reference source is programmable in P2.10.
0: Analogue input AI1
1: Analogue input AI2
2: PID control
Page 40
vacon • 37 Parameter description
3
3: Motorpotentiometer
4: Keypad
5: Fieldbus
6: Expansion AI1 (only with board OPTB4)
7: Temperature (only with board OPTBH, see P13.8-10)
P1.13 S
TART FUNCTION
0: Ramping
1: Flying start
P1.14 S
TOP FUNCTION
NOTE: fall of Enable signal, when configured, always determines stop by coasting.
P1.15 T
ORQUE BOOST
0: Not used
1: Automatic voltage boost (improves motor torque).
P1.16 S
HOW ALL PARAMETERS
0: Only Basic group (and PI Control if function is used)
1: All parameters groups are visible.
3.2 Advanced settings
P2.1 START/STOP LOGIC
These logics are based on Start sign 1 and Start sign 2 signals (defined with P4.1 and P4.2). Usually they are coupled to inputs DIN1 and DIN2.
Values 0...3 offer possibilities to control the starting and stopping of the AC drive with digital signal connected to digital inputs.
The selections including the text 'edge' shall be used to exclude the possibility of an uninten­tional start when, for example, power is connected, re-connected after a power failure, after a fault reset, after the drive is stopped by Run Enable (Run Enable = False) or when the control place is changed to I/O control. The Start/Stop contact must be opened before the motor can
be started.
The used stop mode is
Coasting in all examples.
Selection
number
Selection name Description
0Coasting
The motor is allowed to stop on its own inertia. The control by the drive is discontinued and the drive current drops to zero as soon as the stop command is given.
1Ramp
After the Stop command, the speed of the motor is deceler­ated according to the set deceleration parameters to zero speed.
Page 41
Parameter description vacon • 38
Service support: find your nearest Vacon service center at www.vacon.com
3
Figure 5. Start/Stop logic = 0.
Explanations:
Selection
number
Selection name Note
0
Start sign 1: Start Forward Start sign 2: Start Backward
The functions take place when the contacts are closed.
1
Start sign 1 activates causing the output fre­quency to rise. The motor runs forward.
8
Run enable signal is set to FALSE, which drops the frequency to 0. The run enable signal is con­figured with parameter P4.7.
2
Start sign 2 activates causing the motor drops to
0. Warning 55 appears on the keypad.
9
Run enable signal is set to TRUE, which causes the frequency to rise towards the set frequency because Start sign 1 is still active.
3
Start sign 1 is inactivated which causes the direction to start changing (FWD to REV) because Start sign 2 is still active.
10
Keypad stop button is pressed and the frequency fed to the motor drops to 0. (This signal only works if P2.22 Keypad stop button = 1)
4
Start sign 2 inactivates and the frequency fed to the motor drops to 0.
11
Pushing the Start button on the keypad has no effect on the drive status.
5
Start sign 2 activates again causing the motor to accelerate (REV) towards the set frequency.
12
The keypad stop button is pushed again to stop the drive.
6
Start sign 2 inactivates and the frequency fed to the motor drops to 0.
13
The attempt to start the drive through pushing the Start button is not successful even if Start sign 1 is inactive.
7
Start sign 1 activates and the motor accelerates (FWD) towards the set frequency
t
Output frequency
FWD
REV
Start sgn 2
Start sgn 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad Stop
button
Keypad Start
button
1 2 3 4 5 6 7 8 9 10 11 12 13
Page 42
vacon • 39 Parameter description
3
Figure 6. Start/Stop logic = 1.
Explanations:
Selection
number
Selection name Note
1
Start sign 1: Start Forward Start sign 2: Reverse
The functions take place when the contacts are closed.
1
Start sign 1 activates causing the output fre­quency to rise. The motor runs forward.
7
Run enable signal is set to FALSE, which drops the frequency to 0. The run enable signal is con­figured with parameter P4.7.
2
Start sign 2 activates which causes the direction to start changing (FWD to REV).
8
Run enable signal is set to TRUE, which causes the frequency to rise towards the set frequency because Start sign 1 is still active.
3
Start sign 2 is inactivated which causes the direction to start changing (REV to FWD) because Start sign 1 is still active.
9
Keypad stop button is pressed and the frequency fed to the motor drops to 0. (This signal only works if P2.22 Keypad stop button = Yes)
4
Also Start sign 1 inactivates and the frequency drops to 0.
10
Pushing the Start button on the keypad has no effect on the drive status.
5
Despite the activation of Start sign 2, the motor does not start because Start sign 1 is inactive.
11
The drive is stopped again with the stop button on the keypad.
6
Start sign 1 activates causing the output fre­quency to rise again. The motor runs forward because Start sign 2 is inactive.
12
The attempt to start the drive through pushing the Start button is not successful even if Start sign 1 is inactive.
t
Output frequency
FWD
REV
Start sgn 2
Start sgn 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
Keypad start
button
1 2 3 4 6 7 8 9 10 11 12
5
Page 43
Parameter description vacon • 40
Service support: find your nearest Vacon service center at www.vacon.com
3
Figure 7. Start/Stop logic = 2.
Explanations:
Selection
number
Selection name Note
2
Start sign 1: Start pulse Start sign 2: Stop pulse
The functions take place on the rising edge of the Star pulse and on the falling edge of the Stop pulse.
1
Start sign 1 activates causing the output fre­quency to rise. The motor runs forward.
6
Start sign 1 activates and the motor accelerates (FWD) towards the set frequency because the Run enable signal has been set to TRUE.
2
Start sign 2 inactivates causing the frequency to drop to 0.
7
Keypad stop button is pressed and the frequency fed to the motor drops to 0. (This signal only works if P2.22 Keypad stop button = Yes)
3
Start sign 1 activates causing the output fre­quency to rise again. The motor runs forward.
8
Start sign 1 activates causing the output fre­quency to rise again. The motor runs forward.
4
Run enable signal is set to FALSE, which drops the frequency to 0. The run enable signal is con­figured with parameter P4.7.
9
Start sign 2 inactivates causing the frequency to drop to 0.
5
Start attempt with Start sign 1 is not successful because Run enable signal is still FALSE.
t
Output frequency
FWD
REV
Start sgn 2
Start sgn 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
71 2 3 4 5 6 98
Page 44
vacon • 41 Parameter description
3
Figure 8. Start/Stop logic = 3.
Explanations:
Selection
number
Selection name Note
3
Start sign 1: Start Forward (edge) Start sign 2: Start Back­ward (edge)
Shall be used to exclude the possibility of an unin­tentional start. The Start/Stop contact must be opened before the motor can be restarted.
1
Start sign 1 activates causing the output fre­quency to rise. The motor runs forward.
7
Start sign 1 activates and the motor accelerates (FWD) towards the set frequency
2
Start sign 2 activates causing the motor drops to
0. Warning 55 appears on the keypad.
8
Run enable signal is set to FALSE, which drops the frequency to 0. The run enable signal is con­figured with parameter P4.7.
3
Start sign 1 is inactivated which causes the direction to start changing (FWD to REV) because Start sign 2 is still active.
9
Run enable signal is set to TRUE, which, unlike if value 0 is selected for this parameter, has no effect because rising edge is required to start even if Start sign 1 is active.
4
Start sign 2 inactivates and the frequency fed to the motor drops to 0.
10
Keypad stop button is pressed and the frequency fed to the motor drops to 0. (This signal only works if P2.22 Keypad stop button = Yes)
5
Start sign 2 activates again causing the motor to accelerate (REV) towards the set frequency.
11
Start sign 1 is opened and closed again which causes the motor to start.
6
Start sign 2 inactivates and the frequency fed to the motor drops to 0.
12
Start sign 1 inactivates and the frequency fed to the motor drops to 0.
t
Output frequency
FWD
REV
Start sgn 2
Start sgn 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
1 2 3 4 5 6 7 8 9 10 11 12
Page 45
Parameter description vacon • 42
Service support: find your nearest Vacon service center at www.vacon.com
3
P2.2 TO
P2.8 PRESET SPEED 1 TO 7
You can use the preset frequency parameters to define certain frequency references in ad­vance. These references are then applied by activating/inactivating digital inputs connected to parameters P4.8, P4.9 and P4.10 (binary code). The values of the preset frequencies are auto­matically limited between the minimum and maximum frequencies.
P2.9 A
CCELERATION TIME 2
P2.10 D
ECELERATION TIME 2
Ramp 2 is activated through digital input defined in P4.11 or through fieldbus. Automatic se­lection based on output frequency is also available.
P2.11 A
CCEL1 TO ACCEL2 TRANSITION FREQUENCY
P2.12 DECEL1 TO DECEL2 TRANSITION FREQUENCY
If P2.11 is not 0, acceleration time 2 is activated when output frequency is higher than the value.
If P2.12 is not 0, deceleration time 2 is activated when output frequency is higher than the val­ue.
Required action Activated frequency
B2 B1 B0 Preset frequency 1 B2 B1 B0 Preset frequency 2 B2 B1 B0 Preset frequency 3
B2 B1 B0 Preset frequency 4 B2 B1 B0 Preset frequency 5 B2 B1 B0 Preset frequency 6 B2 B1 B0 Preset frequency 7
Table 20. Selection of preset frequencies; = input activated
Page 46
vacon • 43 Parameter description
3
P2.13 S RAMP SHAPE 1
When value is greater than zero, acceleration and deceleration ramps have a S shape. The pa­rameter is the time needed to reach full acc/dec.
The start and end of acceleration and deceleration ramps can be smoothed with this parame­ter. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped acceleration/deceler­ation. The acceleration time is determined with parameters P1.3 and P1.4.
Figure 9. Acceleration/deceleration (S-shaped).
These parameters are used to reduce mechanical erosion and current spikes when the refer­ence is changed.
P2.14 C
ONTROL PLACE 2
Alternative Run and direction control. Activated by digital input defined in P4.14.
0: I/O terminals
1: Keypad
2: Fieldbus
P2.15 F
REQUENCY REFERENCE SOURCE 2
Alternative source of frequency reference. Activated by digital input defined in P4.15 or field­bus.
0: Analogue input AI1
1: Analogue input AI2
2: PID control
3: Motorpotentiometer
P1.3, P1.4
[Hz]
[t]
P2.13
P2.13
Page 47
Parameter description vacon • 44
Service support: find your nearest Vacon service center at www.vacon.com
3
4: Keypad
5: Fieldbus
6: Expansion AI1 (only with board OPTB4)
7: Temperature (only with board OPTBH, see P13.8-10)
P2.16 M
OTORPOTENTIOMETER RAMP
Speed variation ramp.
P2.17 M
OTORPOTENT REF MEMORY
0: No reset
1: Reset at stop and power down
2: Reset at power down
P2.18 S
KIP RANGE LOW 1 LIM
P2.19 SKIP RANGE HIGH 1 LIM
P2.20 SKIP RANGE LOW 2 LIM
P2.21 SKIP RANGE HIGH 2 LIM
Two skip frequency region are available, if it is needed to avoid certain frequencies because of mechanical resonance.
P2.22 S
TOP BUTTON ACTIVE
0: Active only in keypad control mode
1: Always active
P2.23 K
EYPAD REVERSE
Effective when control is from panel
0: Forward
1: Backward
P2.24 OPTB1
DIGITAL INPUTS
This parameter is shown only when OPTB1 board is installed.
The number of terminals used as input should be programmed, so that the maximum value for parameters of group Digital Inputs is set accordingly.
Parameters for optional digital output functions are shown, if the number of inputs is lower then 6.
P2.25 Q
UICK STOP DECELERATION TIME
Specific ramp time for quick stop. To see description of P4.17 for details about the function.
Page 48
vacon • 45 Parameter description
3
P2.26 S RAMP SHAPE 2
When value is greater than zero, acceleration and deceleration ramps have a S shape. The pa­rameter is the time needed to reach full acc/dec.
The start and end of acceleration and deceleration ramps can be smoothed with this parame­ter. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped acceleration/deceler­ation. The acceleration time is determined with parameters P2.9 and P2.10.
P2.27 K
EYPAD DIRECTION CHANGE
This parameter allows to change motor direction using keypad LEFT and RIGHT arrow in REF menu:
0: Allowed
1: Locked
Page 49
Parameter description vacon • 46
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3 Analogue inputs
P3.1 AI1 SIGNAL RANGE
P3.5 AI2 SIGNAL RANGE
Range of the electrical signal.
0: 0-100%: 0…10V or 0… 20mA
1: 20-100%: 2…10V or 4… 20mA
P3.4 AI1
FILTER TIME
P3.8 AI2 FILTER TIME
Low pass filter time constant, to reduce noise. When this parameter is given a value greater than 0 the function that filters out disturbances from the incoming analogue signal is activated.
NOTE: Long filtering time makes the regulation response slower!
Figure 10.AI1 signal filtering.
P3.2 AI1 CUSTOM MIN
P3.6 AI2 CUSTOM MIN
Customized value for minimum signal. Effective when different than 0%
P3.3 AI1
CUSTOM MAX
P3.7 AI2 CUSTOM MAX
Customized value for maximum signal. Effective when different than 100%.
%
100%
63%
P3.2
t
Filtered signal
Unfiltered signal
Page 50
vacon • 47 Parameter description
3
Example of custom range use with analogue input:
Figure 11.
Description of Figure 11.
Custom min and Custom max parameters configure the input range for analog input that will affect Frequency reference.
Blue line shows an example with Custom Min = -100% and Custom Max = 100%. This settings provides a frequency range between (Maximum frequency - Minimum frequency)/2 and Maxi­mum frequency. With minimum analogue signal the Frequency reference is at 50% of the set frequency range (Max frequency - Min frequency)/2. With maximum analogue signal the Fre­quency reference is at Maximum frequency.
Green line shows the default settings of custom values: Custom Min =0% and Custom Max = 100%. This settings provides a frequency range between Minimum and Maximum frequency. With minimum analogue signal the Frequency reference is at Minimum frequency while with the maximum level is at Maximum frequency.
Orange line shows an example with Custom min = 50% and Custom Max = 100%. These settings provides a frequency range between Minimum and Maximum frequency. The Frequency refer­ence changes linearly within the frequency range with the analogue signal between 50% and 100% of its range.
0100
Max Freq.
-100 20050
Min Freq.
Analogue input AI [%]
Frequency Reference
Page 51
Parameter description vacon • 48
Service support: find your nearest Vacon service center at www.vacon.com
3
Figure 12.
Description of Figure 12:
Green line shows an example with Custom Min = 100% and Custom Max = -100%. This settings provides a frequency range between Minimum frequency and (Maximum frequency - Minimum frequency)/2. With minimum analogue signal the Frequency reference is at 50% of the set fre­quency range (Max frequency - Min frequency)/2, and with maximum analogue signal the Fre­quency reference is at Minimum frequency.
Blue line shows the inversion of the default settings of custom values: Custom Min =100% and Custom Max = 0%. This settings provides a frequency range between the Minimum frequency and the Maximum frequency. With minimum analogue signal the Frequency reference is Max­imum frequency while with the maximum level is Minimum frequency.
Orange line shows an example with Custom min = -100% and Custom Max = 0%. This settings provides a frequency range between Minimum and Maximum frequency. The frequency refer­ence is always at its minimum value (Minimum frequency) within the analogue signal range.
0 100
Max Freq.
-100 20050
Min Freq.
Analogue input AI [%]
Frequency Reference
Page 52
vacon • 49 Parameter description
3
Figure 13.
Description of the Figure 13:
Blue line shows an example with Custom Min = 0% and Custom Max = 200%. This settings pro­vides a frequency range between Minimum frequency and (Maximum frequency - Minimum frequency)/2. With minimum analogue signal the Frequency reference is at minimum value of the set frequency range (Minimum frequency), and with maximum analogue signal the Fre­quency reference is at (Maximum frequency - Minimum frequency)/2.
Green line shows an example with Custom Min =100% and Custom Max = 200%. This settings provides a frequency range always at Minimum frequency. The Frequency reference is at Min­imum frequency within the entire analogue signal range.
Orange line shows an example with Custom min = 0% and Custom Max = 50%. This settings provides a frequency range between Minimum and Maximum frequency. The Frequency refer­ence changes linearly within the frequency range with the analogue signal between the 0% and 50% of its range. With the analogue signal between 50% and 100% of its range, the Frequency reference is always at its maximum value (Maximum frequency).
P3.9 E
XP AI SIGNAL RANGE
P3.10 EXP AI CUSTOM MIN
P3.11 EXP AI CUSTOM MAX
P3.12 E
XP AI FILTER TIME
Parameter for OPTB4 expansion analogue input.
0100
Max Freq.
-100 20050
Min Freq
Analogue input AI [%]
Frequency Reference
Page 53
Parameter description vacon • 50
Service support: find your nearest Vacon service center at www.vacon.com
3
3.4 Digital inputs
P4.1 START SIGNAL 1
P4.2 S
TART SIGNAL 2
Signals for start and direction. Logic is selected with P2.1.
P4.3 R
EVERSE
Should be used when Start signal 2 has not the meaning of reverse.
P4.4 E
XTERNAL FAULT CLOSE
Fault is triggered by high digital input.
P4.5 E
XTERNAL FAULT OPEN
Fault is triggered by low digital input.
P4.6 F
AULT RESET
Active on rising edge.
P4.7 R
UN ENABLE
Motor stops by coasting if the signal is missing.
Note: The drive is not in Ready state when Enable is low.
P4.8 P
RESET SPEED B0
P4.9 P
RESET SPEED B1
P4.10 PRESET SPEED B2
Digital inputs for preset speed selection, with binary coding.
P4.11 S
EL ACCEL/DECEL 2
Ramp 2 is selected by digital input high.
P4.12 M
OTORPOTENT INCREASE SPEED
Digital input high causes speed increase. Motor potentiometer functionality is activated only with P1.12 = 3 or P2.15 = 3.
P4.13 M
OTORPOTENT DECREASE SPEED
Digital input high causes speed reduction. Motor potentiometer functionality is activated only with P1.12 = 3 or P2.15 = 3.
P4.14 S
EL CONTROL PLACE 2
Digital input high activates control place 2 (P2.10).
Page 54
vacon • 51 Parameter description
3
P4.15 SEL FREQ REFERENCE 2
Digital input high activates frequency reference source 2 (P2.11).
P4.16 S
EL PID SETPOINT 2
Digital input high activates setpoint 2 (P8.2), when P8.1=0.
P4.17 Q
UICK STOP OPEN
Digital input low forces drive to stop, ramping down with the time defined in P2.25. The same function can be controlled through the control word of fieldbusses Profibus, Profinet and CANOpen (information in manuals of the specific expansion board).
The drive will exit from Quick stop state when the following conditions are fulfilled:
- stop state
- main Run command is reset
- quick stop digital input is restored (or fieldbus command is cleared).
- Alarm 63 is shown when quick stop is active.
NOTE: quick stop function is enabled with parameter P4.18. The digital input defined in P4.17 and the fieldbus command have no effect if P4.18 in not =1.
P4.18 S
TOP MODE ACTIVATION
This parameter enables special stop modes.
0: Normal. Stop is determined by falling of start command. Stop mode (ramping or coasting) is defined in P1.14
1: Quick stop. A specific digital input (see P4.17) or command from fieldbus is defined to acti­vate quick stop. Stop mode is always by ramping and the deceleration time is defined in P2.25.
2: Accurate. This function gives to Start signal 1 and 2 (defined in P4.1 and P4.2) the maximum repeatability in achieving the stop of the drive.
NOTE:
P4.1 and P4.2 must be within values 1-6 (no expansion board).
P1.14 must be programmed as ramping.
There is no ramp time modification.
This selection disables quick stop signal.
Page 55
Parameter description vacon • 52
Service support: find your nearest Vacon service center at www.vacon.com
3
3.5 Digital outputs
P5.1 RELAY OUTPUT 1 CONTENT
P5.2 RELAY OUTPUT 2 CONTENT
P5.3 DIGITAL OUTPUT CONTENT
Function for relays and digital output.
P5.4 R
ELAY OUTPUT 1 ON DELAY
P5.5 RELAY OUTPUT 1 OFF DELAY
Possible delays for ON/OFF transitions.
P5.6 R
ELAY OUTPUT 1 INVERSION
Inversion of relay state.
P5.7 R
ELAY OUTPUT 2 ON DELAY
P5.8 RELAY OUTPUT 2 OFF DELAY
Selection Selection name Description
0 Not used 1 Ready The frequency converter is ready to operate 2 Run The frequency converter operates (motor is running) 3 General fault A fault trip has occurred 4 General fault inverted A fault trip has not occurred 5 General alarm 6 Reversed The reverse command has been selected 7 At speed The output frequency has reached the set reference
8 Frequency supervision
Output frequency is over/under the limit set with parameters P5.9 and P5.10
9 Current supervision
Motor current is over the limit set with parameter P5.11
10
Analogue inputs supervi­sion
Analogue inputs selected with parameter P5.12 is
over/under the limits set in P5.13 and P5.14 11 Fieldbus bit 1 Bit from fieldbus Aux Control word 12 Fieldbus bit 2 Bit from fieldbus Aux Control word
13 External brake
The drive is running and the thresholds for brake
open have been reached
14 Temperature supervision
Measured temperature is over/below limit (only with
OPTBH board, see P13.2-3-5-7)
Table 21. Functions for digital relays.
Page 56
vacon • 53 Parameter description
3
Possible delays for ON/OFF transitions.
P5.9
TO
P5.12 EXPANSION EO1, EO2, EO3, EO4 OUTPUT CONTENT
These parameters are visible only when an expansion board with outputs is installed (to see table below). Relays are available on boards OPT-B2, B5, B9 and BF.
Digital outputs are available on board OPTB1, if less than 6 terminals are used as inputs, and on OPTBF.
P5.12 is visible only when expansion boards OPTBF or OPTBK are installed.
When OPTBK board is installed, parameters define the meaning of ASi Inputs 1-4.
OPTB1 OPTB2 OPTB5 OPTB9 OPTBF OPTBK
P5.9 EO1
visible if P2.24 < 4 digital out termi­nal 5
visible relay termi­nals 21-22-23
visible relay termi­nals 22-23
visible relay termi­nals 7-8
visible relay termi­nals 22-23
visible ASi bit 1
P5.10 EO2
visible if P2.24 < 5 digital out termi­nal 6
visible relay termi­nals 25-26
visible relay termi­nals 25-26
--
visible ASi bit 2
P5.11 EO3
visible if P2.24 < 6 digital out termi­nal 7
-
visible relay termi­nals 28-29
--
visible ASi bit 3
P5.12 EO4 - - - -
visible digital out terminal 3
visible ASi bit 4
Table 22. Digital outputs available with OPTB-boards
Page 57
Parameter description vacon • 54
Service support: find your nearest Vacon service center at www.vacon.com
3
3.6 Analogue Output
P6.1 ANALOGUE OUTPUT FUNCTION
Signal coupled to analogue output.
P6.2 A
NALOGUE OUTPUT MINIMUM
0: 0V
1: 2V
P6.3 A
NALOGUE OUTPUT SCALE
Scaling factor.
P6.4 A
NALOGUE OUTPUT FILTER TIME
Time constant of low pass filter.
P6.5 E
XP AO1 FUNCTION
P6.6 EXP AO1 MINIMUM
P6.7 EXP AO1 OUTPUT SCALE
P6.8 EXP AO1 FILTER TIME
Parameters for OPTB4-OPTBF expansion analogue output.
P6.9 E
XP AO2 FUNCTION
P6.10 EXP AO2 MINIMUM
P6.11 E
XP AO2 OUTPUT SCALE
P6.12 EXP AO2 FILTER TIME
Parameters for OPTB4 expansion analogue output 2.
Selection Selection name Value corresponding to maximum output
0 Not used output always fixed at 100% 1 Frequency reference Max frequency(P1.2) 2 Output frequency Max frequency(P1.2) 3 Motor speed Motor nominal speed 4 Motor current Motor nominal current 5 Motor torque Motor nominal torque (absolute value) 6 Motor power Motor nominal power (absolute value) 7 PID output 100% 8 Fieldbus control 10000
Table 23. Analogue output signals.
Page 58
vacon • 55 Parameter description
3
3.7 Supervisions
P7.1 FREQUENCY SUPERVISION FUNCTION
0:No supervision
1:Low limit
2: High limit
P7.2 F
REQUENCY SUPERVISION LIMIT
Threshold value for frequency supervision.
P7.3 C
URRENT SUPERVISION LIMIT
Threshold value for current supervision.
P7.4 A
NALOGUE INPUT SUPERVISION
Analogue input selection for supervision:
0: AI1
1: AI2
2: AIE (analogue input on OPTB4 option board).
P7.5 A
NALOGUE SUPERV ON LEVEL
Digital output (programmed as Analogue input supervision) goes high when AI is higher than value.
P7.6 A
NALOGUE SUPERV OFF LEVEL
Digital output (programmed as Analogue input supervision) goes low when AI is lower than val­ue.
P7.7 E
XTERNAL BRAKE OPEN FREQUENCY LIMIT
This value is the output frequency limit of the drive to open the mechanical brake. In open loop control, we recommend that you use a value that is equal to the nominal slip of the motor.
P7.8 E
XTERNAL BRAKE OPEN CURRENT LIMIT
The Mechanical brake opens if the motor current is above the limit set in this parameter. We recommend that you set the value to approximately half of the magnetization current.
When the drive operates on the field weakening area, the brake current limit decreases auto­matically as a function of output frequency.
Note: if a digital output has been programmed for brake control, the frequency reference is in­ternally limited to P7.7 + 0.1Hz until the brake is opened.
P7.9 E
XTERNAL BRAKE CLOSE FREQUENCY LIMIT
The brake is closed when the start command is low and output frequency is below this thresh­old. The brake is also closed whenever the drive is no more in Run state.
Page 59
Parameter description vacon • 56
Service support: find your nearest Vacon service center at www.vacon.com
3
P7.10 PROCESS SOURCE SELECT
Monitor V1.24 can show a process value, proportional to a variable measured by the drive. Source variables are:
0: PID actual value (max: 100%)
1: output frequency (max: Fmax)
2: motor speed (max: Speed at Fmax)
3: motor torque (max: Tnom)
4: motor power (max: Pnom)
5: motor current (max: Inom)
P7.11 P
ROCESS VAL DECIM DIGITS
Number of decimals shown on monitor V1.24 and also on parameter P7.12.
P7.12 PROCESS MAX VALUE
Value shown on V1.24 when source variable is at its maximum. Proportionality is kept if the source overtakes the maximum.
Page 60
vacon • 57 Parameter description
3
3.8 Motor control
P8.1 MOTOR CONTROL MODE
0: Frequency control
1: Speed control (sensorless control)
In speed control, the motor slip is compensated.
Note: motor identification automatically sets this parameter to 1.
P8.2 F
IELD WEAKENING POINT
Output frequency corresponding to max voltage.
Note: if P1.7 Nominal Frequency is changed, P8.2 will be set at same value.
P8.3 V
OLTAGE AT FIELD WEAKENING POINT
Motor voltage when frequency is above FWP, defined as % of nominal voltage.
Note: if P1.6 Nominal Voltage is changed, P8.3 will be set at 100%.
P8.4 U/
F RATIO SELECTION
0: linear
The voltage of the motor changes linearly as a function of output frequency
from zero frequency voltage P8.7 to the field weakening point (FWP)
voltage P8.3 at FWP frequency P8.2 This default setting should be
used if there is no special need for another setting.
Figure 14. Linear and quadratic curve of the motor voltage.
U[V]
f[Hz]
Default: Nominal voltage of the motor
Linear
Squared
Field weakening point
Default: Nominal frequency of the motor
Page 61
Parameter description vacon • 58
Service support: find your nearest Vacon service center at www.vacon.com
3
1: quadratic
(from voltage P8.7 at 0Hz, to voltage P8.3 at P8.2 frequency)
The voltage of the motor changes from zero point voltage P8.7 following a squared curve form from zero to the field weakening point P8.3. The motor runs under-magnetized below the field weakening point and produces less torque. Squared U/f ratio can be used in applications where torque demand is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
2: programmable
The U/f curve can be programmed with three different points: Zero frequency voltage (P1), Midpoint voltage/frequency (P2) and Field weakening point (P3).
Programmable U/f curve can be used if more torque is needed at low frequencies. The optimal settings can automatically be achieved with Motor identification run.
Note: motor identification automatically sets this parameter to 2.
Figure 15. Programmable curve.
P8.5 U/F CURVE MID POINT FREQUENCY
Enabled if P8.4= 2.
Note: motor identification automatically sets this parameter.
P8.6 U/
F CURVE MID POINT VOLTAGE
Enabled if P8.4= 2.
Note: motor identification automatically sets this parameter.
U[V]
f[Hz]
P2
P3
P1
Default: Nominal voltage of the motor
Linear
Field weakening point
Default: Nominal frequency of the motor
Page 62
vacon • 59 Parameter description
3
P8.7 OUTPUT VOLTAGE AT ZERO FREQUENCY
Motor voltage at frequency zero.
Note: motor identification automatically sets this parameter.
P8.8 S
WITCHING FREQUENCY
PWM frequency. Values above default can cause thermic overload of the drive.
P8.9 B
RAKE CHOPPER
0 = Chopper disabled
1 = Chopper enabled in Run state
2 = Chopper enabled in Ready state
P8.10 B
RAKE CHOPPER THRESHOLD
DC link voltage above which chopper is activated.
P8.11 DC
BRAKING CURRENT
DC current injected at start or stop.
P8.12 DC
BRAKING TIME AT STOP
Time for DC current injection at stop.
P8.13 F
REQUENCY TO START DC BRAKING IN RAMP STOP
DC current injection starts below this frequency.
P8.14 DC
BRAKING TIME AT START
Time for DC current injection at start.
P8.15 M
OTOR STATOR VOLTAGE DROP
Voltage drop on stator windings, at motor nominal current, defined as % of nominal voltage. Value affects motor torque estimation, slip compensation and voltage boost.
Note: it is suggested not to program manually the value, but to perform motor identification procedure that automatically sets the value.
P8.16 M
OTOR IDENTIFICATION
This procedure measures motor stator resistance and automatically sets U/f characteristic, to obtain good torque also at low speed.
0 = not active
1 = standstill identification
Run command must be given and hold high within 20s after programming the value 1. The mo­tor does not rotate and the drive will automatically exit run state at the end of the measure­ments.
Note: the drive exits run state only, if the measured current exceeds 55% of the motor nominal current. Procedure sets the following parameters: P8.4, P8.5, P8.6, P8.7, P8.15.
Page 63
Parameter description vacon • 60
Service support: find your nearest Vacon service center at www.vacon.com
3
Note: optimized U/f settings will cause motor current values comparable to nominal one, also at very low speed. External cooling of the motor is needed if the motor works in this condition for significant time.
P8.17 D
ISABLE OVERVOLTAGE REGULATOR
Overvoltage regulator automatically increases deceleration ramp time if the internal DC link voltage is too high.
0: enabled
1: disabled
P8.18 D
ISABLE UNDERVOLTAGE REGULATOR
Undervoltage regulator automatically decelerates the motor if the internal DC link voltage is too low.
0: enabled
1: disabled
P8.19 D
ISABLE SWITCHING FREQ REGULATOR
Switching frequency regulator automatically decreases the PWM frequency if the unit temper­ature is too high.
0: enabled
1: disabled
P8.20 M
OTOR TYPE
In this parameter, you can set the type of motor in your process.
Selections:
0: Induction motor (IM) Make this selection if you use an induction motor.
1: Permanent Magnet Motor (PM) Make this selection if you use a permanent magnet motor.
Page 64
vacon • 61 Parameter description
3
3.9 Protections
P9.1 RESPONSE TO 4MA REFERENCE FAULT (AI< 4mA)
0: No action
1: Warning
2: Fault
3: Warning if Start active
4: Fault if Start active
Analogue reference below 4mA.
P9.2 4mA
FAULT DETECTION TIME
Delay as filter on fault generation
P9.3 E
ARTH FAULT PROTECTION
0: No action
1: Warning
2: Fault
Output currents sum is not zero.
P9.4 M
OTOR STALL PROTECTION
0: No action
1: Warning
2: Fault
This is an overload protection. Stall is recognized by maximum motor current (=P1.5) and low output frequency.
Figure 16. Stall characteristic settings.
f
I
Par. P1.5
Par. P9.6
Stall area
Page 65
Parameter description vacon • 62
Service support: find your nearest Vacon service center at www.vacon.com
3
P9.5 MOTOR STALL DELAY
This time can be set between 0.0 and 300.0 s.
This is the maximum time allowed for all stage. the stall time is counted by an internal up/down counter. If the stall time counter value goes above this limit the protection will cause a trip.
Figure 17. Stall time count.
P9.6 MOTOR STALL MIN FREQ
Stall is recognized when the current limiter has reduced the output frequency below P9.6, for the time in P9.5.
P9.7 U
NDERLOAD PROTECTION
0: No action
1: Warning
2: Fault
Underload is recognized when torque is above the minimum curve defined by P9.8 and P9.9, for the programmed time P9.10.
P9.8
UNDERLOAD LOAD AT NOMINAL FREQ
The torque limit can be set between 10.0-150.0% x T
nMotor
.
This parameter gives the value for the minimum torque allowed when the output frequency is above the field weakening point.
Par. P9.5
Trip area
Time
Stall time counter
Stall• No stall
Trip/warning par. P9.4
Page 66
vacon • 63 Parameter description
3
Figure 18. Underload characteristic settings.
P9.9 UNDERLOAD LOAD AT ZERO FREQ
P9.10 UNDERLOAD TIME
Definition of minimum load at nominal and zero speed zero. Fault condition delay. This time can be set between 1.0 and 300.0 s.
This is the maximum time allowed for an underload state to exist. An internal up/down counter counts the accumulated underload time. If the underload counter value goes above this limit the protection will cause a trip according to parameter P9.7). If the drive is stopped the under­load counter is reset to zero.
Figure 19. Underload time counter.
Par. P9.8
Par. P9.9
f
5 Hz
Underload area
Torque
Fieldweakening point
Par. P9.10
Trip area
Time
Underload time counter
Underload• No underl.
Trip/ war ni ng par. P9.7
Page 67
Parameter description vacon • 64
Service support: find your nearest Vacon service center at www.vacon.com
3
P9.11 THERMAL PROTECTION OF THE MOTOR
0: No action
1: Warning
2: Fault
This is a software protection, based on time integral of current.
P9.12 M
OTOR AMBIENT TEMPERATURE
Change if environment is not standard.
P9.13 M
OTOR COOLING FACTOR AT ZERO SPEED
Defines the cooling factor at zero speed in relation to the point where the motor is running at nominal speed without external cooling. See Figure 20.
The default value is set assuming that there is no external fan cooling the motor. If an external fan is used this parameter can be set to 90% (or even higher).
Setting this parameter does not affect the maximum output current of the drive which is deter­mined by parameter P1.5 alone.
The corner frequency for the thermal protection is 70% of the motor nominal frequency (P1.7).
Set 100% if the motor has independent fan or cooling. Set 30-40% if the fan is on motor shaft.
Figure 20. Motor thermal current IT curve.
f
f
n
Par. P9.13=40%
0
I
T
100%
Overload area
P
cooling
Corner freq
Page 68
vacon • 65 Parameter description
3
P9.14 MOTOR THERMAL TIME CONSTANT
Time at nominal current, to reach nominal temperature.
The time constant is the time within which the calculated thermal stage has reached 63% of its final value. The bigger the frame and/or slower the speed of the motor, the longer the time constant.
The motor thermal time is specific to the motor design and it varies between different motor manufacturers. The default value of the parameter varies from size to size.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate at six times the rated current) is known (given by the motor manufacturer) the time constant parameter can be set basing on it. As a rule of thumb, the motor thermal time constant in minutes equals to 2*t6. If the drive is in stop stage the time constant is internally increased to three times the set pa­rameter value. The cooling in stop stage is based on convection and the time constant is in­creased.
Figure 21. Motor temperature calculation.
P9.15 RESPONSE TO FIELDBUS FAULT
0: No action
1: Warning
2: Fault
Communication lost.
P9.16 T
HERMISTOR FAULT
0: No action
1: Warning
2: Fault
Impedance on thermistor input (optional board OPTB2) is above fault threshold.
105%
Q = (I/IT)2 x (1-e
-t/T )
I/I
T
Trip area
Motor temperature
Time
Motor temperature
Time constant T
*)
*)
Changes by motor size and
adjusted with P9.14
Fault/alarm
P9.11
Motor• current
Page 69
Parameter description vacon • 66
Service support: find your nearest Vacon service center at www.vacon.com
3
P9.17 PARAMETER LOCK
0: Edit enabled
1: Edit disabled
P9.18 R
ESPONSE TO STO DISABLE
0: No action
1: Warning
2: Fault, not stored in history
3: Fault, stored in history
Safe Torque Off disabled.
P9.19 R
ESPONSE TO INPUT PHASE FAULT
0: No action
1: Warning
2: Fault
Input phase missing.
P9.20 I
NPUT PHASE FAULT MAX RIPPLE
Sensitivity for input phases check
0: internal value (default)
1-75: sensitivity from maximum(1) to minimum (75)
P9.21 M
OTOR TEMP INITIAL MODE
Setting of estimated motor temperature at power on
0: initialized at minimum value
1: initialized at constant value from P9.22
2: initialized at last previous value, with P9.22 used as factor
P9.22 M
OTOR TEMP INITIAL VALUE
If P9.21= 1, motor temperature is initialized with this value.
If P9.21= 2, motor temperature is initialized with last previous value, multiplied by this value as % factor.
P9.23 O
UTPUT PHASE FAULT
0: No action
1: Warning
2: Fault
Current measurement has detected that there is no current in one motor phase.
Page 70
vacon • 67 Parameter description
3
3.10 Autoreset
P10.1 AUTOMATIC FAULT RESET
0: Disabled
1: Enabled
The automatic reset function deletes fault state when the fault cause has been eliminated and the wait time P10.2 has elapsed. Parameter P10.4 determines the maximum number of auto­matic resets that can be effected during the trial time set by parameter P10.3. The time count starts from the first automatic reset. If the number of faults detected during the trial time ex­ceeds the values of trials, the fault status becomes permanent and a reset command is need­ed.
P10.2 W
AIT TIME
Time after which the converter attempts to restart the motor automatically after the fault has been eliminated.
P10.3 T
RIAL TIME
Total time for reset attempts.
P10.4 A
UTOMATIC RESET TRIES
Trials attempted during time P10.3.
P10.5 S
TART FUNCTION
Start function after an automatic fault reset.
0: Start with ramp
1: Flying start
2: As defined in P1.13
P10.6 U
NDERVOLTAGE FAULT AUTORESET
0: Disabled
1: Enabled
Enable/disable autoreset function for Undervoltage fault.
P10.7 O
VERVOLTAGE FAULT AUTORESET
0: Disabled
1: Enabled
Enable/disable autoreset function for Overvoltage fault.
P10.8 O
VERCURRENT FAULT AUTORESET
0: Disabled
1: Enabled
Enable/disable autoreset function for Overcurrent fault.
Page 71
Parameter description vacon • 68
Service support: find your nearest Vacon service center at www.vacon.com
3
P10.9 MOTOR OVERTEMP FAULT AUTORESET
0: Disabled
1: Enabled
Enable/disable autoreset function for Motor Overtemperature fault.
P10.10 U
NDERLOAD FAULT AUTORESET
0: Disabled
1: Enabled
Enable/disable autoreset function for Underload fault.
Page 72
vacon • 69 Parameter description
3
3.11 Fieldbus
P11.1 TO
P11.8 PROCESSDATAOUT 1 - 8 SEL
Parameter couples read only variables to output process data 1.
0: output frequency
1: motor speed
2: motor current
3: motor voltage
4: motor torque
5: motor power
6: DC link voltage
7: active fault code
8: analogue AI1
9: analogue AI2
10: digital inputs state
11: PID actual value
12: PID setpoint
13: analogue AI3 (OPTB4 needed)
14: temperature sensor 1 (OPTBH needed)
15: temperature sensor 2 (OPTBH needed)
16: temperature sensor 3 (OPTBH needed)
P11.9 FB A
UX CW SELECTION
Parameter defines the input process data coupled to Aux Control Word.
0: not used
1: PDI1
2: PDI2
3: PDI3
4: PDI4
5: PDI5
P11.10 FB PID
SETPOINT SELECTION
Parameter defines the input process data coupled to PID setpoint. Selections as P11.9.
P11.11 FB PID
ACTUAL SELECTION
Parameter defines the input process data coupled to PID actual value. Selections as P11.9.
Page 73
Parameter description vacon • 70
Service support: find your nearest Vacon service center at www.vacon.com
3
P11.12 FB ANALOGUEOUT CNTRL SELECTION
Parameter defines the input process data coupled to analogue output control. Selections as P11.9.
3.11.1 Fieldbus mapping
3.11.1.1 Fieldbus Data IN: Master -> Slave
Notes:
CW b0 Run is acquired on edge, only if the drive is in Ready state (see Status Word b0) and actual control place is Fieldbus.
CW b2 Fault Reset is active even if control place is not the Fieldbus.
Fieldbus different from Modbus have their own Control Word (see manual of the specific fieldbus board).
Modbus register
Name Description Range
2001 Control word(*) Drive control
Binary coded: b0: Run b1: Reverse b2: Fault Reset(on edge)
b8: forces control place to fieldbus b9: forces reference source to fieldbus
2002 General control word Not used
2003 Speed reference(*) Reference
0...10000 as 0,00...100,00% of Min freq. - Max freq.
range 2004 Fieldbus Data IN 1 Programmable 0...10000 2005 Fieldbus Data IN 2 Programmable 0...10000 2006 Fieldbus Data IN 3 Programmable 0...10000 2007 Fieldbus Data IN 4 Programmable 0...10000 2008 Fieldbus Data IN 5 Programmable 0...10000 2009 Fieldbus Data IN 6 Not used ­2010 Fieldbus Data IN 7 Not used ­2011 Fieldbus Data IN 8 Not used -
Table 24. (*) Modbus Data inputs. They can vary depending on fieldbus used (See
specific fieldbus option board installation manual).
Page 74
vacon • 71 Parameter description
3
Fieldbus data input mapping
Fieldbus Data inputs from 1 to 5 can be configured, with parameters P11.9 - P11.12, as:
Process Data IN Description Note
Aux Control Word
b0: enable
b1: acc/dec ramp 2 selection
b2: freq reference 2 selec­tion
b3: digital output 1 control
b4: digital output 2 control
• b0 Enable is considered only when control place is the Fieldbus. It is computed in AND with a possible enable from digital input. Fall of enable will cause coasting stop.
• b2 FreqRef2 Sel is considered only when control place is the Fieldbus.
• functions related to bit1, b3 and b4 are available also when control place is not the Fieldbus. Aux CW must anyway be mapped onto a PDI, by means of parameter P11.9.
PID Setpoint
active if P12.1 = 3, range 0 ­10000 as 0 - 100,00% of reg­ulation.
PID Actual value
active if P12.4 = 2, range 0 ­10000 as 0 - 100,00% of reg­ulation.
Analogue Out Cntrl
active if P5.1 = 8, range 0 ­10000 as 0 - 100,00% of out­put.
Table 25.
Page 75
Parameter description vacon • 72
Service support: find your nearest Vacon service center at www.vacon.com
3
3.11.1.2 Fieldbus Data OUT: Slave ->Master
Notes:
Fieldbus different from Modbus have their own Status Word (see manual of the specific fieldbus board).
Modbus register
Name Description Range
2101 Status word(*) Drive state
Binary coded: b0: Ready b1: Run b2: Reverse b3: Fault b4: Warning b5: Freq. reference reached b6: Zero speed
2102 General Status word Drive state
As Status word and: b7: Control place is fieldbus
2103 Actual speed(*) Actual speed
0...10000 as 0,00...100,00% of Min freq. - Max freq.
range 2104 Fieldbus Data OUT 1 Programmable See P11.1 2105 Fieldbus Data OUT 2 Programmable See P11.2 2106 Fieldbus Data OUT 3 Programmable See P11.3 2107 Fieldbus Data OUT 4 Programmable See P11.4 2108 Fieldbus Data OUT 5 Programmable See P11.5 2109 Fieldbus Data OUT 6 Programmable See P11.6 2110 Fieldbus Data OUT 7 Programmable See P11.7 2111 Fieldbus Data OUT 8 Programmable See P11.8
Table 26. (*) Modbus data outputs. They can vary depending on fieldbus used (See
specific fieldbus option board installation manual).
Page 76
vacon • 73 Parameter description
3
3.12 PID Control
Parameters of this group are hidden unless the regulator is used as frequency reference (P1.12= or P2.15=2)
P12.1 S
ETPOINT SOURCE
0: fixed setpoint 1-2
1: analogue AI1
2: analogue AI2
3: fieldbus
P12.2 PID S
ETPOINT 1
P12.3 PID SETPOINT 2
Programmable setpoints. Setpoint 2 is activated with digital input defined in P4.16.
P12.4 F
EEDBACK SOURCE
0: analogue AI2
1: analogue AI1
2: fieldbus
3: AI2-AI1 (differential)
4: temperature (only with board OPTBH, see P13.8-10)
P12.5 F
EEDBACK MINIMUM
P12.6 FEEDBACK MAXIMUM
Minimum and maximum feedback values, corresponding to minimum and maximum of the signal.
P12.7 PID
CONTROLLER P GAIN
Proportional gain. If set to 100%, a variation of 10% on error causes a variation of 10% on reg­ulator output.
P12.8 PID
CONTROLLER I-TIME
Integral time constant. If set to 1s, a variation of 10% on error will cause a variation of 10% on regulator output after 1s.
P12.9 PID
CONTROLLER D-TIME
Derivative time. If set to 1s, a variation of 10% in 1s on error causes a variation of 10% on reg­ulator output.
P12.10 E
RROR VALUE INVERSION
0: direct control. Frequency increases if setpoint > feedback
1: inverted control. Frequency increases if setpoint < feedback
Page 77
Parameter description vacon • 74
Service support: find your nearest Vacon service center at www.vacon.com
3
P12.11 PID ERROR LIMIT
If lower than 100%, determines a limit on max error. Useful to avoid excessive reaction at mo­tor startup.
P12.12 S
LEEP FREQUENCY
This function will put the drive into sleep mode if the setpoint is reached and the output fre­quency stays below the sleep frequency for a longer time than that set with the Sleep Delay (P12.13). This means that the start command remains on, but the run request is turned off. When the PID error value goes below, or above, the wake-up level depending on the set acting mode (P12.10) the drive will activate the run request again if the start command is still on.
P12.13 S
LEEP TIME DELAY
Time of working at minimum frequency, before entering sleep condition.
P12.14 W
AKE UP LIMIT
The drive exits from sleep if the error exceeds this value. Direction of regulation (P12.10) is in­ternally considered.
P12.15 S
LEEP SETPOINT BOOST
P12.16 SLEEP BOOST TIME
P12.17 SLEEP MAX LOSS
P12.18 SLEEP LOSS CHECK TIME
These parameters manage a more complex sleep sequence. After the time in P12.13, the set­point is increased of the term in P12.15, for the time in P12.16. This will cause an higher output frequency. Frequency reference is then forced at minimum frequency and the feedback value is sampled.
If the variation on actual value stays then lower than P12.17 for the time in P12.18, the drive will enter sleep condition.
If this sequence is not needed, program P12.15=0%, P12.16=0s, P12.17=50%, P12.18=1s.
Page 78
vacon • 75 Parameter description
3
3.13 Temperature measurement
Parameters of this group are hidden if option board OPTBH is not installed
P13.1 T
EMPERATURE UNIT
0: °C
1: K
P13.2 S
UPERVISION/FAULT SENSOR SELECTION
Temperature sensor(s) used for supervision and fault activation.
0: T1
1: T2
2: T1 +T2
3: T3
4: T3 +T1
5: T3 +T2
6: T3 +T2 +T1
P13.3 S
UPERVISION MODE
A digital/relay output can be activated
0: not used
1: over limit (max temperature if more sensors)
1: below limit (min temperature if more sensors)
P13.4 F
AULT MODE
A fault state can be activated
0: not used
1: over limit (max temperature if more sensors)
1: below limit (min temperature if more sensors)
P13.5 S
UPERVISION LEVEL
Threshold for supervision activation.
P13.6 F
AULT LEVEL
Threshold for fault F56 activation.
P13.7 S
UPERV/FAULT HYSTERESIS
Temperature must change of this value to restore supervision/fault state.
Page 79
Parameter description vacon • 76
Service support: find your nearest Vacon service center at www.vacon.com
3
P13.8 REFERENCE/ACTUAL SENSOR SELECTION
Temperature sensor(s) used for direct reference control or as PID actual value.
0: T1
1: T2
2: T3
3: max (T1, T2)
4: min (T1, T2)
5: max (T1, T2, T3)
6: min (T1, T2, T3)
P13.9 M
IN REFERENCE/ACTUAL TEMPERATURE
Temperature corresponding to minimum reference/actual.
P13.10 MAX REFERENCE/ACTUAL TEMPERATURE
Temperature corresponding to maximum reference/actual.
Page 80
vacon • 77 Parameter description
3
Page 81
Fault tracing vacon • 78
Service support: find your nearest Vacon service center at www.vacon.com
4
4. FAULT TRACING
Fault
code
Fault name Subcode Possible cause Remedy
1
Overcurrent
AC drive has detected too high a current (>4*I
H
) in the motor cable:
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
Check loading. Check motor. Check cables and connections. Make identification run. Check ramp times.
2
Overvoltage
The DC-link voltage has exceeded the limits defined.
• too short a deceleration time
• brake chopper is disabled
• high overvoltage spikes in supply
• Start/Stop sequence too fast
Make deceleration time longer. Use brake chopper or brake resistor (available as options). Activate overvoltage controller. Check input voltage.
3
Earth fault
Current measurement has detected that the sum of motor phase current is not zero.
• insulation failure in cables or motor
Check motor cables and motor.
84 MPI communication crc error
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
89 HMI receives buffer overflow
Check PC-drive cable. Try to reduce ambient noise
90 Modbus receives buffer overflow
Check Modbus specifications for time-out. Check cable length. Reduce ambient noise. Check baudrate.
8
System Fault 93 Power identification error
Try to reduce ambient noise. Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
97 MPI off line error
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
98 MPI driver error
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
99 Option board driver error
Check contact in option board slot Try to reduce ambient noise; Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
Table 27. Fault codes and descriptions.
Page 82
vacon • 79 Fault tracing
4
100 Option board configuration error
Check contact in option board slot Try to reduce ambient noise; Should the fault re-occur, con­tact the distributor near to you.
101 Modbus buffer overflow
Check Modbus specifications for time-out. Check cable length. Reduce ambient noise. Check baudrate.
104 Option board channel full
Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, con­tact the distributor near to you.
105
Option board memory allocation fail
Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, con­tact the distributor near to you.
8
System Fault 106 Option board Object queue full
Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, con­tact the distributor near to you.
107 Option board HMI queue full
Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, con­tact the distributor near to you.
108 Option board SPI queue full
Check contacts in option board slot. Try to reduce ambient noise. Should the fault re-occur, con­tact the distributor near to you.
111 Parameter copy error
Check if parameter set is com­patible with drive. Do not remove Keypad until copy is finished.
113
Frequency detective timer over­flow
Check keypad contacts. Try to reduce ambient noise. Should the fault re-occur, con­tact the distributor near to you.
114 PC control time out fault
Do not close Vacon Live when PC control is active. Check PC-Drive cable. Try to reduce ambient noise.
115 DeviceProperty data format
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
Fault
code
Fault name Subcode Possible cause Remedy
Table 27. Fault codes and descriptions.
Page 83
Fault tracing vacon • 80
Service support: find your nearest Vacon service center at www.vacon.com
4
8
System Fault 120 Task stack overflow
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
9
Undervoltage
DC-link voltage is under the volt­age limits defined.
• most probable cause: too low a supply voltage
• AC drive internal fault
• defect input fuse
• external charge switch not closed
NOTE! This fault is activated only
if the drive is in Run state.
In case of temporary supply voltage break reset the fault and restart the AC drive. Check the supply voltage. If it is adequate, an internal failure has occurred. Contact the distributor near to you.
10
Input phase Input line phase is missing.
Check supply voltage, fuses and cable.
11
Output phase
Current measurement has detected that there is no current in one motor phase.
Check motor cables and motor.
13
AC drive undertemperature
Too low temperature measured in power unit’s heatsink or board. Heatsink temperature is under ­10°C.
Check the ambient tempera­ture.
14
AC drive overtemperature
Too high temperature measured in power unit’s heatsink or board. Heatsink temperature is over 100°C.
Check the correct amount and flow of cooling air. Check the heatsink for dust. Check the ambient tempera­ture. Make sure that the switching frequency is not too high in rela­tion to ambient temperature and motor load.
15
Motor stalled Motor is stalled.
Check motor and load. Insufficient motor power, check motor stall protection parame­trization.
16
Motor overtemperature
Motor is overloaded.
Decrease motor load. If no motor overload exists, check the temperature model parameters.
17
Motor underload Motor is under loaded
Check load. Check underload protection parametrization.
19
Power overload Supervision for drive power
Drive power is to high: decrease load.
25
Watchdog
Error in the microprocessor moni­toring Malfunction Component fault
Reset the fault and restart. If the fault occurs again, please contact your closest Vacon rep­resentative.
27
Back EMF
Protection of unit when starting with rotating motor
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
Fault
code
Fault name Subcode Possible cause Remedy
Table 27. Fault codes and descriptions.
Page 84
vacon • 81 Fault tracing
4
30
STO fault
Safe torque off signal does not allow drive to be set as ready
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
35
Application error
0
Firmware Interface version between Application and Control not matching
Load a compatible application. Please contact your closest Vacon representative.
1 Application software flash error Reload Application
2 Application header error
Load a compatible application. Please contact your closest Vacon representative.
41
IGBT temp
IGBT temperature (UnitTempera­ture + I2T) too high
Check loading. Check motor size. Make identification run.
50
4 mA fault (Analog input)
Selected signal range: 4...20 mA (see Application Manual) Current less than 4 mA Signal line broken detached The signal source is faulty
Check the analog input’s current source and circuit.
51
External fault
Error message on digital input. The digital input was programmed as an input for external error mes­sages. The input is active.
Check the programming and check the device indicated by the error message. Check the cabling for the respective device as well.
52
Keypad Communication fault
The connection between the con­trol keypad and the frequency con­verter is broken.
Check keypad connection and keypad cable.
53
Fieldbus communication fault
The data connection between the fieldbus master and fieldbus board is broken
Check installation and fieldbus master.
54
Fieldbus Interface error Defective option board or slot Check board and slot.
55
Wrong run command
Wrong run alarm and stop com­mand
Run forward and backward are activated at the same time
56
Temperature Temperature fault
Board OPTBH is installed and measured temperature is above (or below) the limit
57
Identification Identification alarm
Motor identification has not been successfully completed
63
Quick Stop Quick Stop activated
The drive has been stopped with Quick Stop digital input or Quick Stop command by fieldbus
Fault
code
Fault name Subcode Possible cause Remedy
Table 27. Fault codes and descriptions.
Page 85
Page 86
Page 87
Page 88
Document ID:
Order code:
Rev. H
Manual authoring: documentation@vacon.com
Vacon Plc. Runsorintie 7 65380 Vaasa Finland
Subject to change without prior notice © 2015 Vacon Plc.
Find your nearest Vacon office
on the Internet at:
www.vacon.com
Loading...