8.2Motor settings (Control panel: Menu PAR -> P1)74
8.3Start / stop setup (Control panel: Menu PAR -> P2)76
8.4Frequency references (Control panel: Menu PAR -> P3)77
8.5Ramps and brakes setup (Control panel: Menu PAR -> P4)78
8.6Digital inputs (Control panel: Menu PAR -> P5)80
8.7Analogue inputs (Control panel: Menu PAR -> P6)81
8.8Pulse train / Encoder (Control panel: Menu PAR -> P7)81
8.9Digital outputs (Control panel: Menu PAR -> P8)82
8.10Analogue outputs (Control panel: Menu PAR -> P9)84
8.11Fieldbus Data-Mapping (Control panel: Menu PAR -> P10)85
8.12Prohibited Frequencies (Control panel: Menu PAR -> P11)86
8.13Limit Supervisions (Control panel: Menu PAR -> P12)87
8.14Protections (Control panel: Menu PAR -> P13)88
8.15Fault autoreset parameters (Control panel: Menu PAR -> P14) 90
8.16PID control parameters (Control panel: Menu PAR -> P15)90
8.17Motor Pre-heat (Control panel: Menu PAR -> P16)93
8.18Easy usage menu (Control panel: Menu PAR -> P17)93
8.19System parameters94
9.Parameter descriptions99
9.1Motor settings (Control panel: Menu PAR -> P1)99
9.2Start / stop setup (Control panel: Menu PAR -> P2)104
9.3Frequency references (Control panel: Menu PAR -> P3)112
9.4Ramps & brakes setup (Control panel: Menu PAR -> P4)114
9.5Digital inputs (Control panel: Menu PAR -> P5)119
9.6Analogue inputs (Control panel: Menu PAR -> P6)120
9.7Pulse train / Encoder (Control panel: Menu PAR -> P7)121
9.8Digital outputs (Control panel: Menu PAR -> P8)122
9.9Analogue outputs (Control panel: Menu PAR -> P9)123
9.10Fieldbus Data-Mapping (Control panel: Menu PAR -> P10)124
9.11Prohibited Frequencies (Control panel: Menu PAR -> P11)125
9.12Protections (Control panel:Menu Par->P13)126
9.13Automatic reset (Control panel: Menu PAR -> P14)133
9.14PID control parameters (Control panel: Menu PAR -> P15)134
1
9.15Application setting (Control panel: Menu PAR->P17)137
9.16System parameter139
9.17Modbus RTU141
9.17.1Termination resistor141
9.17.2Modbus address area141
9.17.3Modbus process data142
10.Technical data147
10.1Vacon 20 technical data147
10.2Power ratings149
10.2.1Vacon 20 – Mains voltage 208-240 V149
10.2.2Vacon 20 – Mains voltage 115 V150
10.2.3Vacon 20 – Mains voltage 380-480 V150
10.2.4Vacon 20 – Mains voltage 600 V151
10.3Brake resistors151
1
1
safetyvacon • 1
1. SAFETY
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY
OUT THE ELECTRICAL INSTALLATION!
This manual contains clearly marked cautions and warnings which are intended for
your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully:
=Dangerous voltage
Risk of death or severe injury
=General warning
Risk of damage to the product or
connected appliances
1.1 Warnings
The components of the power unit of the frequency converter
are live when Vacon 20 is connected to mains. Coming into
contact with this voltage is extremely dangerous and may
cause death or severe injury. The control unit is isolated from
the mains potential.
The motor terminals U, V, W (T1, T2, T3) and the possible brake
resistor terminals - / + are live when Vacon 20 is connected to
mains, even if the motor is not running.
The control I / O-terminals are isolated from the mains potential. However, the relay output terminals may have a dangerous control voltage present even when Vacon 20 is
isconnected from mains.
d
The earth leakage current of Vacon 20 frequency converters
exceeds 3.5 mA AC. According to standard EN61800-5-1, a
reinforced protective ground connection must be ensured.
If the frequency converter is used as a part of a ma chine, the
machine manufacturer is responsible for providing the
machine with a main switch (EN 60204-1).
If Vacon 20 is disconnected from mains while running the
motor, it remains live if the motor is energized by the process.
In this case the motor functions as a generator feeding energy
to the frequency converter.
1
2
vaconsafety
•
After disconnecting the frequency converter from the mains,
wait until the fan stops and the indicators on the display go
out. Wait 5 more minutes before doing any work on Vacon 20
connections.
The motor can start automatically after a fault situation, if the
autoreset function has been activated.
1
safetyvacon • 3
1.2 Safety instructions
The Vacon 20 frequency converter has been designed for fixed
installations only.
Do not perform any measurements when the frequency converter is connected to the mains.
Do not perform any voltage withstand tests on any part of
Vacon 20. The product safety is fully tested at factory.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the frequency converter.
Do not open the cover of Vacon 20. Static voltage discharge
from your fingers may damage the components. Opening the
cover may also damage the device. If the cover of Vacon 20 is
opened, warranty becomes void.
1.3 Earthing and earth fault protection
The Vacon 20 frequency converter must always be earthed with an earthing conductor connected to the earthing terminal. See figure below:
MI1 - MI3
1
4
vaconsafety
•
MI4
MI5
•
The earth fault protection inside the frequency converter protects
only the converter itself against earth faults.
If fault current protective switches are used they must be tested
•
with the drive with earth fault currents that are possible to arise in
fault situations.
1
safetyvacon • 5
1.4 Before running the motor
Checklist:
Before starting the motor, check that the motor is mounted
properly and ensure that the machine connected to the motor
allows the motor to be started.
Set the maximum motor speed (frequency) according to the
motor and the machine connected to it.
Before reversing the motor shaft rotation direction make sure
that this can be done safely.
Make sure that no power correction capacitors are connected
to the motor cable.
1
6
vaconsafety
•
1
receipt of deliveryvacon
VACON0020- 1L- 0001-1+OPTIONS
Vacon20
1L = Singlephase
3L = Threephases
1=115V
2 =208 - 230V
4 =380 - 480V
7 = 600V
Output Current
InputVoltage
+Options
EMC2
QPES
QFLG
+DLNL = Dutch
+DLNO = Norwegian
+DLPT = Portuguese
+DLRU = Russian
+DLSE =Swedish
+DLTR =Turkis h
+DLUS = US English
empty = English
Language of the documentation
+DLCN = Chinese
+DLCZ= Czech
+DLDE = German
+DLDK = Danish
+DLES= Spanish
+DLFI = Finnish
+DLFR = French
+DLIT = Italian
Inputphase
2. RECEIPT OF DELIVERY
After unpacking the product, check that no signs of transport damages are to be
found on the product and that the delivery is complete (compare the type designation
of the product to the code below).
Should the drive have been damaged during the shipping, please contact primarily
the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
2.1 Type designation code
2.2 Storage
If the frequency converter is to be kept in store before use make sure that the ambient conditions are acceptable:
Storing temperature -40…+70 °C
Relative humidity < 95%, no condensation
Figure 2.1: Vacon 20 type designation code
7
•
2
8
vaconreceipt of delivery
•
2.3 Maintenance
In normal operating conditions, Vacon 20 frequency converters are maintenancefree. However, regular maintenance is recommended to ensure a trouble-free operating and a long lifetime of the drive. We recommended to follow the table below for
maintenance intervals.
Maintenance intervalMaintenance action
Whenever necessary
Regular
12 months (If stored)
6 - 24 months (depending on environment)
* Only for frame 4 and frame 5
2.3.1 Capacitor recharge
After a longer storage time the capacitors need to be recharge in order to avoid capacitor damage. Possible high leakage current through the capacitors must be limited. The best way to achieve this is to use a DC-power supply with adjustable current
limit.
1) Set the current limit to 300…800 mA according to the size of the drive.
2) Then connect the DC-power supply to the input phase L1 and L2.
3) Then set the DC-voltage to the nominal DC-voltage level of the (1.35*Un AC) and
supply the converter for at least 1 h.
If DC-voltage is not available and the unit has been stored much longer than 12
months deenergized, consult the factory before connecting power.
• Clean headsink*
• Check tightening torques of terminals
• Check input and output terminals and control I / O terminals.
• Clean cooling tunnel.*
• Check operation of cooling fan, check for
corrosion on terminals, busbars and other
surfaces.*
• Check and clean and clean cooling fans:
*
Main fan
Interminal fan
*
2
receipt of deliveryvacon
2.4 Warranty
Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible
for damages and failures resulting from misuse, wrong installation, unacceptable
ambient temperature, dust, corrosive substances or operation outside the rated
specifications. Neither can the manufacturer be held responsible for consequential
damages.
The Manufacturer's time of warranty is 18 months from the delivery or 12 months
from the commissioning whichever expires first (Vacon Warranty Terms).
The local distributor may grant a warranty time different from the above. This warranty time shall be specified in the distributor's sales and warranty terms. Vacon assumes no responsibility for any other warranties than that granted by Vacon itself.
In all matters concerning the warranty, please contact first your distributor.
has been designed and manufactured in accordance w ith the following
standards:
Safety:
EN 60204 -1 (2009) (as relevant) ,
EN 61800-5-1 (2007)
EMC:
EN 61800-3 (2004)
and conforms to the rele vant safety provisions of the Low Voltage Directive
2006/95/EC and EMC Dir ective 2004/108 /EC.
It is ensured through internal me asures and quality control that the product
conforms at all times to the requireme nts of the curr ent Dire ctive and the
relevant standards.
In Vaasa, 30t h of July, 2010
Vesa Laisi
President
The year the CE marking was affixed:2011
vaconreceipt of delivery
•
2.5 Manufacturer’s declaration of conformity
2
=
M5
MI3
MI1
=M4
MI2
=M5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
MI4
=M 6
=M 6
MI5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
installationvacon
3. INSTALLATION
3.1 Mechanical installation
There are two possible ways to mount Vacon 20 in the wall. For MI1-MI3, either screw
or DIN-rail mounting; For MI4-MI5, screw or flange mounting.
Figure 3.1: Screw mounting, MI1 - MI3
Figure 3.2: Screw mounting, MI4 - MI5
Note! See the mounting dimensions on the back of the drive. More details in
Chapter
.
3.1.1
11
•
3
12
12
LOC
REM
BACK
RESET
OK
vacon
•
Figure 3.3: DIN-rail mounting, MI1 - MI3
Figure 3.4: Flange mounting, MI4 - MI5
installation
3
installationvacon
Figure 3.5: Flange mounting cutout dimensions for MI4 (Unit: mm)
13
•
Figure 3.6: Flange mounting cutout dimensions for MI5 (Unit: mm)
3
14
MI5
MI4
•
vacon
installation
Figure 3.7: Flange mounting depth dimensions for MI4 and MI5 (Unit: mm)
Enough free space shall be left above and below the frequency converter to ensure
sufficient air circulation and cooling. You will find the required dimensions for free
space in the table below.
If several units are mounted above each other the required free space equals C + D
(see figure below). Moreover, the outlet air used for cooling by the lower unit must
be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of
the converter.
*. Min clearance A and B for drives for
MI1 ~ MI3 can be 0 mm if the ambient
temperature is below 40 degrees.
A = clearance around the freq. converter (see also B)
B = distance from one frequency converter to another or distance to cabinet wall
C = free space above the frequency converter
D = free space underneath the frequency converter
NOTE! See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm), below (50 mm), and on the sides (20 mm)
of Vacon 20! (For MI1 - MI3, side-to-side installation allowed only if the ambient temperature is below 40 °C; For MI4-MI5, side-to-side installation is not allowed.
TypeCooling air required (m³/h)
MI110
Table 3.5: Required cooling air
MI210
MI330
MI445
MI575
Figure 3.12: Installation space
19
•
3
20
vacon
•
3.1.3 Power losses
If the operator wants to raise the switching frequency of the drive for some reason
(typically e.g. in order to reduce the motor noise), this inevitably affects the power
losses and cooling requirements, for different motor shaft power, operator can select the switching frequency according to the graphs below.
MI1 - MI5 3P 380 V POWER LOSS
installation
3
installationvacon
21
•
3
22
•
vacon
MI1 - MI5 3P 230 V POWER LOSS
installation
3
installationvacon
23
•
3
24
•
vacon
installation
3
Loading...
+ 130 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.