The Vacon AC drive contains a preloaded Vacon 100X Solar Pump application for instant use.
1.1Specific functions of Vacon Solar pump application
The Vacon 100X Solar Pump application allows flexible use of VACON® 100X frequency converters. This dedicated application SW was developed to drive a Solar Pump with an optimized
MPPT (Maximum Power Point Tracking) for 100X supplied by Solar Panels.
The MPPT is based on 4 parallel algorithms:
•Feed-Forward Controller (to follow the radiation variations)
•Correction Controller (to compensate the temperature variations)
•Oscillation Damping Regulator (to prevent the panel entering in the “current source”
branch of the characteristic)
•Local Maxima logic (to prevent the regulator from being trapped in a local maximum
lower than absolute maximum)
Features
•The MPP Tracker controls DC voltage reference in order to find the maximum power.
•Extensive wizards for start-up, PID-control used to facilitate commissioning
•‘Funct’ button for easy change between Local (keypad) and Remote control place. The
remote control place is selectable by parameter (I/O or Fieldbus)
•8 preset frequencies
•Motor pontentiometer functions
•2 programmable ramp times, 2 supervisions and 3 ranges of prohibited frequencies
•Control page for easy operation and monitoring of the most essential values.
•Fieldbus data mapping
•Automatic reset
•Different pre-heat modes used to avoid condensation problems
•Maximum output frequency 320Hz
•Real-time clock and timer functions available (optional battery required). Possible to
program 3 time channels to achieve different functions on the drive (e.g. Start/Stop and
Preset frequencies)
•External PID-controller available. Can be used to control e.g. a valve using the AC
drive's I/O
•Sleep mode function which automatically enables and disables drive running with user
defined levels to save energy.
•2-zone PID-controller (2 different feedback signals; minimum and maximum control)
•Two setpoint sources for the PID-control. Selectable with digital input
•PID setpoint boost function
•Feedforward function to improve the response to the process changes
•Process value supervision
•Maintenance counter
Service support: find your nearest Vacon service center at www.vacon.com
1
Page 6
vacon • 3Vacon 100X Solar Pump Application
1
Page 7
Safetyvacon • 4
2.SAFETY
This manual contains clearly marked warning information which is intended for your personal
safety and to avoid any unintentional damage to the product or connected appliances.
Before installing, commissioning or using the frequency converter, please read the warning
information contained in Vacon 100X Installation Manual.
Please read the following additional safety instructions carefully.
Only Vacon authorized, trained and qualified personnel are allowed to install, operate and
maintain the drive.
2.1Danger
These warnings are intended to personnel responsible for grounding the frequency converter.
Ignoring the following instructions can be extremely dangerous and may cause
death or severe injury.
Ground the frequency converter to ensure personnel safety and to reduce electromagnetic interference.
After disconnecting the AC drive from the mains or from the DC input supply,
wait until the indicators on the keypad go out (if no keypad is attached, see the
indicators on the cover). Wait an additional 30 seconds before starting any work
on the connections of Vacon 100X Drive. After expiration of this time, use measuring equipment to absolutely ensure that no
absence of voltage before starting any electrical work!
2.2Warnings
The touch current of VACON
dard EN61800-5-1, a reinforced protective ground connection must be ensured.
See Vacon 100X Installation Manual for further information.
Never work on the photovoltaic generator or frequency converter and its input/
output cables when the frequency converter is connected to the mains or to the
photovoltaic generator.
Before performing any measurement on the frequency converter, disconnect or
isolate the mains supply voltage or the DC input supply.
Do not touch the components on the frequency converter or on the string box
cabinet that have high DC voltage.
voltage is present.
®
100X drives exceeds 3.5mA AC. According to stan-
Always ensure
The photovoltaic generator cells exposed to light supply DC voltage even at low
light intensity.
Service support: find your nearest Vacon service center at www.vacon.com
2
Page 8
vacon • 5Safety
2
Page 9
Startupvacon • 6
OK
BACK
RESET
3.STARTUP
3.1First Start-up
In the Startup Wizard, you will be prompted for essential information needed by the drive so
that it can start controlling your process. In the Wizard, you will need the following keypad buttons:
Left/Right arrows. Use these to easily move between digits and decimals.
Up/Down arrows. Use these to move between options in menu and to change value.
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can return to the previous question in
the Wizard. If pressed at the first question, the Startup Wizard will be cancelled.
Once you have connected power to your Vacon 100 X AC drive, follow these instructions to easily set up your drive.
NOTE: You can have your AC drive equipped with a keypad with either a graphical or a text keypad.
1
2
3
4
Language selection (P6.1)Depends on language package
Russia
Daylight saving* (P5.5.5)
Time* (P5.5.2)hh:mm:ss
Year* (P5.5.4)yyyy
US
EU
OFF
5
* These questions appear if battery is installed
Service support: find your nearest Vacon service center at www.vacon.com
Date* (P5.5.3)dd.mm.
3
Page 10
vacon • 7Startup
6
Push the OK button unless you want to set all parameter values manually.
7
8
9
10
11
12
13
14
15
16
17
Run Startup Wizard?
Make a selection of an application
(P1.2 Application,ID212)
Set a value for P3.1.2.2 Motor
Type (so that it agrees with the
nameplate)
Set value for P3.1.1.1Motor Nom
Voltg
(according to nameplate)
Set value for P3.1.1.2Motor Nom
Freq
(according to nameplate)
Set value for P3.1.1.3Motor Nom
Speed
Set value for P3.1.1.4Motor Nom
Currnt
Set value for P3.1.1.5Motor Cos
Phi
Set value
frequency reference
Set
FreqReference
Set
1
Set
1
(according to nameplate)
(according to nameplate)
(according to nameplate)
for
P3.3.1.1 Minimum
value
for
P3.3.1.2 Max-
value
for
P3.4.1.2 Accel Time
value
for
P3.4.1.3 Decel Time
Yes
No
Standard
Local/Remote
Multi-step speed
PID control
Multi-purpose
Motor potentiometer
PM motor
Induction motor
Range: Varies
8.00...320.00 Hz
Range: 24...19.200 rpm
Range: Varies
Range: 0.30...1.00
Range:
Range:
Range:
Range:
0.00...50.00 Hz
0.00...320.00 Hz
0.1...300.0 s
0.1...300.0 s
3
If you set Motor Type to Induction Motor, you see the next question. If your selection is PM Motor, the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00 and the wizard goes directly to
question 18.
Page 11
Startupvacon • 8
18
19
20
21
22
To continue to the application wizard, set the selection to Yes and push the OK button.
After these selections, the Start-up wizard is completed. To start the Start-up wizard again,
you have 2 alternatives. Go to the parameter P6.5.1 Restore Factory Defaults or to the parameter B1.1.2 Start-up Wizard. Then set the value to Activate.
Set value
FreqReference
Set
value
FreqReference
Set
value
1
Set
value
1
Run the Application wizard?
for
P3.3.1.1 Min-
for
P3.3.1.2 Max-
for
P3.4.1.2 Accel Time
for
P3.4.1.3 Decel Time
Range:
Range:
Range:
Range:
Yes
No
0.00...50.00 Hz
0.00...320.00 Hz
0.1...300.0 s
0.1...300.0 s
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 12
vacon • 9Startup
3.2Description of the applications
Use the parameter P1.2 (Application) to make a selection of an application for the drive. Immediately when the parameter P1.2 changes, a group of parameters get their preset values.
3.2.0.1M1 Quick setup parameter group
In the Quick Setup parameter group you will find the different wizards of the Vacon 100 X Solar
Pump Application. The wizards help you to quickly set up your drive for use prompting you for
a number of essential data.
Table 1. Quick setup parameter group
CodeParameterMinMaxUnitDefaultIDDescription
0 = Do not activate
1 = Activate
B1.1Startup wizard0101170
P1.2Application050212
P1.3MinFreqReference0.00P1.4Hz0.00101
P1.4MaxFreqReferenceP1.3320.00Hz50.00102
P1.5Accel Time 10.1300.0s5.0103
P1.6Decel Time 10.1300.0s5.0104
P1.7Current limitVariesVariesAVaries107
P1.8Motor type010650
P1.9Motor Nom VoltgVariesVariesVVaries110
P1.10Motor Nom Freq8.00320.00HzVaries111
P1.11Motor Nom Speed2419200rpmVaries112
P1.12Motor Nom CurrntVariesVariesAVaries113
P1.13Motor Cos Phi0.301.000.74120
Choosing Activate initiates
the Startup Wizard (see
chapter 3.1).
0 = Standard
1 = Local/Remote
2 = Multi-Step Speed
3 = PID Control
4 = Multi-Purpose
5 = Motor
Potentiometer
Minimum allowed frequency reference
Maximum allowed frequency
reference
Defines the time required
for the output frequency to
increase from zero frequency to maximum frequency
Defines the time required
for the output frequency to
decrease from maximum
frequency to zero frequency
Maximum motor current
from AC drive
0 = Induction motor
1 = PM motor
Find this value U
rating plate of the motor.
Note also used connection
(Delta/Star).
Find this value f
ing plate of the motor.
Find this value n
ing plate of the motor.
Find this value I
ing plate of the motor.
Find this value on the rating
plate of the motor
on the
n
on the rat-
n
on the rat-
n
on the rat-
n
3
Page 13
Startupvacon • 10
Table 1. Quick setup parameter group
The drive searches for the
minimum motor current in
order to save energy and to
P1.14Energy optimization010666
P1.15Identification010631
P1.16Start function010505
P1.17Stop function010506
P1.18Automatic reset010731
P1.19External fault032701
P1.20AI Low Fault050700
P1.21Rem.Ctrl. Place010172
lower the motor noise. This
function can be used e.g. in
fan and pump applications
0 = Disabled
1 = Enabled
The identification run calculates or measures the motor
parameters that are necessary for a good control of the
motor and speed.
0 = No action
1 = At standstill
2 = With rotation
Before you do the identification run, you must set the
motor nameplate parameters.
0=Ramping
1=Flying start
0=Coasting
1=Ramping
0 = Disabled
1 = Enabled
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Response when an analogue
signal in use goes below
50% of the minimum signal
range. 0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to
stop mode)
5 = Fault (Stop by coasting)
Selection of remote control
place (start/stop). Can be
used to change back to
remote control from Vacon
Live e.g. in case of a broken
panel.
0=I/O control
1=Fieldbus control
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 14
vacon • 11Startup
Table 1. Quick setup parameter group
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
P1.22I/O A Ref sel195117
P1.23Keypad Ref sel192121
P1.24Fieldbus Ref sel193122
P1.25AI1 signal range010379
P1.26AI2 signal range011390
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
Selection of ref source when
control place is keypad:
See P1.22
Selection of ref source when
control place is Fieldbus:
See P1.22
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
3
Page 15
Startupvacon • 12
Table 1. Quick setup parameter group
Function selection for Basic
R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator active
10 = Start signal active
11 = Keypad control active
12 = I/O B control activated
13 = Limit supervision 1
14 = Limit supervision 2
15 = No fucntion
16 = No fucntion
17 = Preset speed active
18 = No fucntion
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID supervision limits
22 = Ext. PID superv. limits
23 = Input press. alarm/fault
24 = Frost prot. alarm/fault
25 - 30 = No fucntion
31 = RTC time chnl 1 control
1100
P1.27 RO1 function0512
32 = RTC time chnl 2 control
1
33 = RTC time chnl 3 control
34 = FB ControlWord B13
35 = FB ControlWord B14
36 = FB ControlWord B15
37 = FB ProcessData1.B0
38 = FB ProcessData1.B1
39 = FB ProcessData1.B2
40 = Maintenance alarm
41 = Maintenance fault
42 = No fucntion
43 = No fucntion
44 = Block Out.1
45 = Block Out.2
46 = Block Out.3
47 = Block Out.4
48 = Block Out.5
49 = Block Out.6
50 = Block Out.7
51 = Block Out.8
52 = Block Out.9
53 = Block Out.10
54 = No function
55 = No function
56 = Auto-cleaning
active
57 = Motor Switch
Open
58 = TEST (Always
Closed)
59 = No function
Service support: find your nearest Vacon service center at www.vacon.com
You can use the Standard application in speed-controlled processes where no special functions are necessary, for example pumps, fans, or conveyors.
It is possible to control the drive from the keypad, Fieldbus or I/O terminal.
When you control the drive with the I/O terminal, the frequency reference signal is connected
to AI1 (0…10V) or AI2 (4…20mA). The connection depends the type of the signal. There are also
3 preset frequency references available. You can activate the preset frequency references with
DI4 and DI5. The start/stop signals of the drive are connected to DI1 (start forward) and DI2
(start reverse).
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.1.1M1.31 Standard
Table 2. Standard start-up wizard menu
CodeParameterMinMaxUnitDefaultIDDescription
Make the selection of a
P1.31.1Preset Freq 1P1.3P1.4Hz10.0105
P1.31.2Preset Freq 2P1.3P1.4Hz15.0106
P1.31.3Preset Freq 3P1.3P1.4Hz20.0126
preset frequency with
the digital input DI4.
Make the selection of a
preset frequency with
the digital input DI5.
Make the selection of a
preset frequency with
the digital input DI4
and DI5.
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 18
vacon • 15Startup
3.2.2Local/Remote application
Use the Local/Remote application when, for example, it is necessary to switch between 2 different control places.
To change between the Local and the Remote control place, use DI6. When Remote control is
active, you can give the start/stop commands from Fieldbus or from I/O terminal (DI1 and DI2).
When Local control is active, you can give the start/stop commands from the keypad, Fieldbus
or I/O terminal (DI4 and DI5).
For each control place, you can make a selection of the frequency reference from the keypad,
Fieldbus or I/O terminal (AI1 or AI2).
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.2.1M1.33 Local/Remote
Table 3. Local/Remote start-up wizard menu
CodeParameterMinMaxUnitDefaultIDDescription
Selection of ref source when
control place is I/O B. See
P1.32.1I/O B Ref sel199131
P1.32.2I/O B Ctrl force
P1.32.3I/O B Ref force
P1.32.4Ctrl signal 1 B
P1.32.5Ctrl signal 2 B
P1.32.6Keypad Ctrl force
P1.32.7Fieldbus Ctrl force
P1.32.8Ext fault close
P1.32.9Ext fault open
DigIN
SlotA.6
DigIN
SlotA.6
DigIN
SlotA.4
DigIN
SlotA.5
DigIN
Slot0.1
DigIN
Slot0.1
DigIN
SlotA.3
DigIN
Slot0.2
above.
NOTE: I/O B control place
can only be forced active
with digital input (P3.5.1.7).
TRUE = Used frequency reference is specified by I/O
343
reference B parameter
(P3.3.1.6).
411Force control to fieldbus
Start signal 1 when control
423
place is I/O B
Start signal 2 when control
424
place is I/O B
410Force control to keypad
411Force control to fieldbus
FALSE = OK
405
TRUE = External fault
FALSE = External fault
406
TRUE = OK
3
Page 19
Startupvacon • 16
3.2.3Multi-step application
You can use the Multi-step speed application with processes where more than 1 fixed frequency reference is necessary (for example test benches).
It is possible to use 1 + 7 frequency references: 1 basic reference (AI1 or AI2) and 7 preset references.
Make a selection of the preset frequency references with digital signals DI4, DI5 and DI6. If
none of these inputs are active, the frequency reference is removed from the analogue input
(AI1 or AI2). Give the start/stop commands from the I/O terminal (DI1 and DI2).
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.3.1M1.33 Multi-step speed
Table 4. Multi-step speed start-up wizard menu
CodeParameterMinMaxUnitDefaultIDDescription
P1.33.1Preset Freq 1P1.3P1.4Hz10.0105
P1.33.2Preset Freq 2P1.3P1.4Hz15.0106
P1.33.3Preset Freq 3P1.3P1.4Hz20.0126
P1.33.4Preset Freq 4P1.3P1.4Hz25.0127
P1.33.5Preset Freq 5P1.3P1.4Hz30.0128
P1.33.6Preset Freq 6P1.3P1.4Hz40.0129
P1.33.7Preset Freq 7P1.3P1.4Hz50.0130
0 = Binary coded
1 = Number of inputs. Preset
P1.33.8PresetFreqMode010182
P1.33.9Ext fault close
P1.33.10Ext fault open
DigIN
SlotA.3
DigIN
Slot0.2
frequency is selected
according to how many of
preset speed digital inputs
are active
FALSE = OK
405
TRUE = External fault
FALSE = External fault
406
TRUE = OK
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 20
vacon • 17Startup
3.2.4PID Control application
You can use the PID control application with processes where you control the process variable
(for example pressure) through control of the speed of the motor.
In this application, the internal PID controller of the drive is configured for 1 setpoint and 1
feedback signal.
It is possible to use 2 control places. Make the selection of the control place A or B with DI6.
When control place A is active, the start/stop commands are given by DI1, and the PID controller gives the frequency reference. When control place B is active, start/stop commands are
given by DI4, and AI1 gives the frequency reference.
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.4.1M1.34 PID Control
Table 5. PID Control start-up wizard menu
CodeParameterMinMaxUnitDefaultIDDescription
If the value of the parameter
is set to 100% a change of
P1.34.1Gain0.001000.00%100.00118
P1.34.2Integration Time0.00600.00s1.00119
P1.34.3Derivation Time0.00100.00s0.00132
10% in the error value
causes the controller output
to change by 10%.
If this parameter is set to
1,00s a change of 10% in the
error value causes the controller output to change by
10.00%/s.
If this parameter is set to
1,00s a change of 10% in the
error value during 1.00 s
causes the controller output
to change by 10.00%.
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
AI’s and ProcessDataIn are
handled as % (0.00-
100.00%) and scaled according to Feedback min and
max.
NOTE: ProcessDataIn use
two decimals.
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input 1
18 = Temperature input 2
19 = Temperature input 3
20 = Temperature input 4
21 = Temperature input 5
22 = Temperature input 6
AI’s and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled according to Setpoint minimum
and maximum. NOTE: ProcessDataIn signals use 2
decimals.
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 22
vacon • 19Startup
Table 5. PID Control start-up wizard menu
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that
defined by parameter Sleep delay.
The minimum amount of
time the frequency has to
remain below the Sleep level
before the drive is stopped.
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
3
Page 23
Startupvacon • 20
3.2.5Multi-purpose application
You can use the Multi-purpose application for different processes (for example conveyors)
where a wide range of motor control functions is necessary.
It is possible to control the drive from the keypad, Fieldbus or I/O terminal. When you use I/O
terminal control, the start/stop commands are given through DI1 and DI2, and the frequency
reference from AI1 or AI2.
There are 2 acceleration/deceleration ramps available. The selection between Ramp1 and
Ramp2 is made by DI6.
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
0 = U/f Freq ctrl open loop
1 = Speed control open loop
Automatic torque boost can
be used in application where
starting torque due to starting friction is high.
0= Disabled
1= Enabled
Type of U/f curve between
zero frequency and the field
weakening point.
0=Linear
1=Squared
2=Programmable
The field weakening point is
the output frequency at
which the output voltage
reaches the field weakening
point voltage
Voltage at field weakening
point in % of motor nominal
voltage
Provided that the programmable U/f curve has been
selected (par. P3.1.4.1) , this
parameter defines the middle point frequency of the
curve.
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 24
vacon • 21Startup
Table 6. Multi-purpose start-up wizard menu
Provided that the programmable U/f curve has been
P1.35.10U/f Mid Voltg0.0100.0%100.0605
P1.35.11Zero Freq Voltg0.0040.00%Varies606
P1.35.12StartMagnCurrent0.00VariesAVaries517
P1.35.13StartMagnTime0,00600,00s0,00516
P1.35.14DC Brake CurrentVariesVariesAVaries507
P1.35.15DC BrakeTime0,00600,00s0,00508
P1.35.16DC Start Freq0,1010,00Hz1,50515
P1.35.17Load drooping0.0050.00%0.00620
P1.35.18Load drooping time0.002.00s0.00656
P1.35.19Load drooping mode0101534
selected (par. P3.1.4.1), this
parameter defines the middle point voltage of the
curve.
This parameter defines the
zero frequency voltage of the
U/f curve. The default value
varies according to unit size.
Defines the DC current fed
into motor at start. Disabled
if set to 0.
This parameter defines the
time for how long DC current is fed to motor before
acceleration starts.
Defines the current injected
into the motor during DCbraking.
0 = Disabled
Determines if braking is ON
or OFF and the braking time
of the DC-brake when the
motor is stopping.
The output frequency at
which the DC-braking is
applied.
The drooping function
enables speed drop as a
function of load. Drooping
will be defined in percent of
nominal speed at nominal
load.
Load drooping is used in
order to achieve a dynamic
speed drooping because of
changing load. This parameter defines the time during
which the speed is restored
to the level it was before the
load increase.
0 = Normal; Load drooping
factor is constant through
the whole frequency range
1 = Linear removal; Load
drooping is removed linearly from nominal frequency to zero frequency
3
Page 25
Startupvacon • 22
3.2.6Motor potentiometer application
Use the Motor potentiometer application for the processes where the frequency reference of
the motor is controlled (that is, increased and decreased) through digital inputs.
In this application, the I/O terminal is set to the default control place. the start/stop commands
are given with DI1 and DI2. The frequency reference of the motor is increased with DI5 and decreased with DI6.
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.6.1M1.36 Motor Potentiom
Table 7. Motor Potentiom start-up wizard menu
CodeParameterMinMaxUnitDefaultIDDescription
Rate of change in the motor
potentiometer reference
P1.36.1MotPot ramp time0.1500.0Hz/s10.0331
P1.36.2MotPot Reset021367
P1.36.3Preset Freq 1P1.3P1.4Hz20.0105
when increased or
decreased with parameters
P3.3.4.1 or P3.3.4.2.
Motor potentiometer frequency reference reset
logic.
0 = No reset
1 = Reset if stopped
2 = Reset if powered down
Make the selection of a
preset frequency with
the digital input DI4
and DI5.
Service support: find your nearest Vacon service center at www.vacon.com
3
Page 26
vacon • 23User Interfaces
9086.emf
FUNCT
Scroll menu up
Increase value
Scroll menu down
Decrease value
Move cursor leftMove cursor right
Move backward in menu
Exit edit mode
Reset faults with long press
Change control place
Access control page
Change direction
Stop buttonStart button
Enter active level/item
Confirm selection
4.USER INTERFACES
4.1Keypad of the drive
The control keypad is the interface between the Vacon 100 AC drive and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the AC drive's parameters.
There are two keypad types you can choose for your user interface:
play
and Text keypad.
4.1.1Buttons
The button section of the keypad is identical for both keypad types.
Keypad with graphical dis-
Figure 1. Keypad buttons
4.1.2Display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about the drive and
location in the menu structure and the item displayed.
4.1.3Navigation on keypad
The data on the control keypad are arranged in menus and submenus. Use the Up and Down
arrows to move between the menus. Enter the group/item by pressing the OK button and
to the former level by pressing the Back/Reset button.
The
Location field indicates your current location. The Status field gives information about
the present status of the drive. See Figure 1.
4
his present
return
Page 27
User Interfacesvacon • 24
9159.emf
Main Menu
Quick Setup
( 17 )
Parameters
( 12 )
STOPREADYI/O
ID:M1
( 5 )
Monitor
Status field
STOP/RUN
Direction
ALARM
Status field
READY/NOT READY/FAULT
Control place:
PC/IO/KEYPAD/FIELDBUS
Activated group/item:
Press OK to enter
Number of items
in the group
Location field
(Parameter ID number and
current menu location
4.1.4Vacon graphical keypad
Figure 2. Main menu
4.1.4.1
Using the graphical keypad
Editing values
The selectable values can be accessed and edited in two different ways on the graphical keypad.
Parameters with one valid value
Typically, one parameter is set one value. The value is selected either from a list of values (see
example below) or the parameter is given a numerical value from a defined range (e.g.
0.00...50.00 Hz).
Change value of a parameter following the procedure below:
1.Locate the parameter.
2.Enter the
Edit mode.
3.Set new value with the arrow buttons up/down. You can also move from digit to digit with
the arrow buttons left/right if the value is numerical and then change the value with the
arrow buttons up/down.
4.Confirm change with OK button or ignore change by returning to previous level with Back/
Reset button.
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 28
vacon • 25User Interfaces
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
STOPREADYI/O
ID:172M3.2.1
Edit
Help
Add to favorites
Rem Control Place
STOPREADYI/O
ID:M3.2.1
Rem Control Place
STOPREADYI/O
M3.2.1
I/O Control
FieldbusCTRL
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
STOPREADYI/O
ID:172M3.2.1
Rem Control Place
STOPREADYI/O
M3.2.1
I/O Control
FieldbusCTRL
OKOK
OK
BACK
RESET
OR:
9160.emf
9257.emf
OK
9256.emf
...
OK
Symbol for checkbox selection
Figure 3. Typical editing of values on graphical keypad (text value)
Figure 4. Typical editing of values on graphical keypad (numerical value)
Parameters with checkbox selection
Some parameters allow selecting several values. Make a checkbox selection at each value you
wish to activate as instructed below.
Figure 5. Applying the checkbox value selection on graphical keypad
4
Page 29
User Interfacesvacon • 26
Resetting fault
Instructions for how to reset a fault can be found in chapter 7 .
Function button
The FUNCT button is used for four functions:
1. to quickly access the Control page,
2. to easily change between the Local (Keypad) and Remote control places,
3. to change the rotation direction and
4. to quickly edit a parameter value.
Control places
The
control place is the source of control where the drive can be started and stopped. Every
control place has its own parameter for selecting the frequency reference source. The
control place
is always the keypad. The Remote control place is determined by parameter
Local
P3.2.1 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the
lowest priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again,
can bypass the remote control place selected with parameter P3.2.1 using a digital input. The
digital input is selected with parameter P3.5.1.7
(I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority
than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.7 through digital input while in
Remote, the control place will still switch to Keypad if Local is selected.
Switching between Local and Remote Control can be done by pressing the FUNCT-button on
the keypad or by using the "Local/Remote" (ID211) parameter.
Changing control places
Change of control place from
1. Anywhere in the menu structure, push the
2. Push the
OK button.
Arrow up or the Arrow down button to select Local/Remote and confirm with the
3. On the next display, select
4. The display will return to the same location as it was when the
Remote to Local (keypad).
FUNCT button.
Local or Remote and again confirm with the OK button.
FUNCT button was pushed.
However, if the Remote control place was changed to Local (Keypad) you will be prompted
for keypad reference.
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 30
vacon • 27User Interfaces
Main Menu
Parameters
( 15 )
Diagnostics
STOPREADYKeypad
ID:M1
( 7 )
Monitor
( 6 )
ID:
Choose action
STOPReadyKeypad
ID:1805
Local/Remote
Control page
Change direction
?
Remote
ID:
Local/Remote
STOPR EADYKeypad
ID:211
Remote
Local
Main Menu
Parameters
( 15 )
Diagnostics
STOPREADYI/O
ID:M1
( 7 )
Monitor
( 6 )
FUNCT
OK
OK
9161.emf
Main Menu
Parameters
( 15 )
Diagnostics
STOPREADYI/O
ID:M1
( 7 )
Monitor
( 6 )
ID:
Choose action
STOPReadyKeypad
ID:1805
Local/Remote
Control page
Change direction
STOPREADYKeypad
( 6 )
Keypad Reference
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
ID:184
Keypad
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
STOPREADYKeypad
( 6 )
ID:168
Keypad Reference
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
FUNCT
OK
OK
OK
9162.emf
Figure 6. Changing control places
Accessing the control page
Control page is meant for easy operation and monitoring of the most essential values.
The
1. Anywhere in the menu structure, push the
2. Push the
Arrow up or the Arrow down button to select Control page and confirm with the
FUNCT button.
OK button.
3. The control page appears
If keypad control place and keypad reference are selected to be used you can set the
pad Reference
after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable. The other
values on the page are Multimonitoring values. You can choose which values appear here
for monitoring (for this procedure, see page 37).
Key-
4
Figure 7. Accessing Control page
Page 31
User Interfacesvacon • 28
Main Menu
Parameters
( 15 )
Diagnostics
STOPREADYI/O
ID:M1
( 7 )
Monitor
( 6 )
ID:
Choose action
RUNReadyKeypad
ID:1805
Local/Remote
Control page
Change direction
ID:
Choose action
RUNReadyKeypad
ID:1805
Forward
Reverse
Main Menu
Parameters
( 15 )
Diagnostics
STOPREADYI/O
ID:M1
( 7 )
Monitor
( 6 )
FUNCT
OKOK
9163.ai
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT button.
NOTE!
Changing direction command is not visible in the menu unless the selected control place is
Local.
1. Anywhere in the menu structure, push the Funct button.
2. Push the Arrow up or the Arrow down button to select Change direction and confirm with
the OK button.
3. Then choose the direction you wish to run the motor to. The actual rotation direction is
blinking. Confirm with the OK button.
4. The rotation direction changes immediately and the arrow indication in the status field
changes.
Quick edit
Through the
the parameter’s ID number.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK
button.
3. Then enter the ID number of parameter or monitoring value you wish to access. Press OK
button to confirm.
4. Requested Parameter/Monitoring value appears on the display (in editing/monitoring
mode.)
Service support: find your nearest Vacon service center at www.vacon.com
Quick edit functionality you can quickly access the desired parameter by entering
4
Page 32
vacon • 29User Interfaces
STOPREADYKeypad
Main Menu
Favourites
( 0 )
( 4 )
ID:M6
User settings
I/O and Hardware
( 8 )
STOPREADYKeypad
Drive name
( 3 )
ID:
User settings
Application selection
HVAC
M6.5M6.5
Parameter backup
Drive
STOPREADYKeypad
Restore from keypad
ID:
Restore factory defaults
M6.5M6.5.1
Save to keypad
Parameter backup
OKOK
9164.emf
Copying parameters
NOTE: This feature is available in graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to
another drive. Finally the parameters are downloaded to the new drive restoring them from the
keypad.
Before any parameters can successfully be copied from the keypad to the drive, the drive has to be stopped before the parameters are uploaded.
•First go into
User settings menu and locate the Parameter backup submenu. In the
Parameter backup submenu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made at the
•
factory.
•By selecting
Restore from keypad will copy all parameters from keypad to a drive.
•
Figure 8. Parameter copy
NOTE: If the keypad is changed between drives of different sizes, the copied values of these pa-
Save to keypad you can copy all parameters to the keypad.
rameters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phii (P3.1.1.5)
Switching frequency (P3.1.2.3)
Motor current limit (P3.1.3.1)
Stall current limit (P3.9.3.2)
Stall time limit (P3.9.3.3)
Stall frequency (P3.9.3.4)
Maximum frequency (P3.3.1.2)
4
Page 33
User Interfacesvacon • 30
( 6 )
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 1 B
STOPREADYI/O
ID:403M3.5.1.1
Ctrl Signal 2 A
( 6 )
Add to favorites
STOPREADYI/O
ID:403M3.5.1.1
Ctrl signal 1 A
Edit
Help
Start Signal 1 for control Place
I/O A. Start Signal 1
functionality chosen with I/O A
Logic in Start/Stop Setup Menu.
STOPREADYI/O
Ctrl signal 1 A
ID:403
M3.5.1.1
OKOK
9165.emf
Basic Settings
Motor Nom Voltg
230.00 V
Motor Nom Speed
1430 rpm
STOPREADYI/O
Motor Nom Freq
50.00 Hz
Edit
Help
Motor Nom Freq
STOPREADYI/O
Add to favorites
Motor Nom Freq
was added to
favorites. Press OK
to continue.
STOPREADYI/O
OKOK
9166.emf
Help texts
The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the startup wizard.
Figure 9. Help text example
Adding item to favorites
You might need to refer to certain parameter values or other items often. Instead of locating
them one by one in the menu structure, you may want to add them to a folder called
Favorites
where they can easily be reached.
To remove an item from the Favorites, see chapter 4.3.7.
Figure 10. Adding item to Favorites
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 34
vacon • 31User Interfaces
9167.emf
Indicators:
Status
Indicators:
Alarm, Fault
Indicators:
Direction
Indicators:
Control place
Group or parameter
name
Menu location
4.1.5Vacon text keypad
You can also choose a so-called
Text keypad for your user interface. It has mainly the same
functionalities as the graphical keypad although some of these are somewhat limited.
4.1.5.1Keypad display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about the drive and
his present
location in the menu structure and the item displayed. If the text on the text line is too long to
fit in the display, the text will scroll from left to right to reveal the whole text string.
4
Page 35
User Interfacesvacon • 32
OKOKOK
BACK
RESET
9168.emf
4.1.5.2Using the text keypad
Editing values
Change value of a parameter following the procedure below:
1.Locate the parameter.
2.Enter the Edit mode by pressing OK.
3.Set new value with the arrow buttons up/down. You can also move from digit to digit with
the arrow buttons left/right if the value is numerical and change then the value with the
arrow buttons up/down.
4.Confirm change with OK button or ignore change by returning to previous level with Back/
Reset button.
Figure 11. Editing values
Resetting fault
Instructions for how to reset a fault can be found in chapter 7 on page 158.
Function button
The FUNCT button is used for four functions:
Control places
The
control place is the source of control where the drive can be started and stopped. Every
control place has its own parameter for selecting the frequency reference source. The
control place
is always the keypad. The Remote control place is determined by parameter
Local
P3.2.1 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the
lowest priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again,
can bypass the remote control place selected with parameter P3.2.1 using a digital input. The
digital input is selected with parameter P3.5.1.7
(I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority
than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.7 through digital input while in
Remote, the control place will still switch to Keypad if Local is selected.
Switching between Local and Remote Control can be done by pressing the FUNCT-button on
the keypad or by using the "Local/Remote" (ID211) parameter.
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 36
vacon • 33User Interfaces
FUNCT
OKOK
9169.emf
9170.emf
FUNCT
OK
OK
Changing control places
Change of control place from
Remote to Local (keypad).
1.Anywhere in the menu structure, push the FUNCT button.
2.Using the arrow buttons, select Local/Remote and confirm with the OK button.
3.On the next display, select Local or Remote and again confirm with the OK button.
4.The display will return to the same location as it was when the
FUNCT button was pushed.
However, if the Remote control place was changed to Local (Keypad) you will be prompted
for keypad reference.
Figure 12. Changing control places
Accessing the control page
Control page is meant for easy operation and monitoring of the most essential values.
The
1. Anywhere in the menu structure, push the
2. Push the
OK button.
Arrow up or the Arrow down button to select Control page and confirm with the
FUNCT button.
3. The control page appears
If keypad control place and keypad reference are selected to be used you can set the
pad Reference
after having pressed the OK button. If other control places or reference val-
ues are used the display will show Frequency reference which is not editable.
Figure 13. Accessing Control page
Key-
4
Page 37
User Interfacesvacon • 34
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT button.
Changing direction command is not visible in the menu unless the selected control place is
Local.
1. Anywhere in the menu structure, push the Funct button.
2. Push the Arrow up or the Arrow down button to select Change direction and confirm with
the OK button.
3. Then choose the direction you wish to run the motor to. The actual rotation direction is
blinking. Confirm with the OK button.
4. The rotation direction changes immediately and the arrow indication in the status field
changes.
Quick edit
Through the
the parameter’s ID number.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK
button.
3. Then enter the ID number of parameter or monitoring value you wish to access. Press OK
button to confirm.
4. Requested Parameter/Monitoring value appears on the display (in editing/monitoring
mode.)
Quick edit functionality you can quickly access the desired parameter by entering
NOTE!
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 38
vacon • 35User Interfaces
4.2Vacon live
Vacon Live is a PC tool for commissioning and maintenance of the Vacon® 10, Vacon® 20, and
Vacon® 100 AC drives). You can download Vacon Live from www.vacon.com.
The Vacon Live PC tool includes these functions.
• Parametrisation, monitoring, drive info, data logger, etc.
• The software download tool Vacon Loader
• RS-422 and Ethernet support
• Windows XP, Vista 7 and 8 support
• 17 languages: English, German, Spanish, Finnish, French, Italian, Russian, Swedish, Chinese, Czech, Danish, Dutch, Polish, Portuguese, Romanian, Slovak and Turkish You can make
the connection between the AC drive and the PC tool with the black USB/RS-422 cable from
Vacon or the Vacon 100 Ethernet cable. The RS-422 drivers are installed automatically during
the installation of Vacon Live. After you installed the cable, Vacon Live finds the connected drive
automatically.
See more on how to use Vacon Live in the help menu of the program.
4
Page 39
User Interfacesvacon • 36
4.3Menu structure
Click on and select the item you wish to receive more information about (electronic manual).
Table 8. Keypad menus
Quick setupSee chapter 3.
MonitorMulti-monitor*
Trend curve*
Basic
I/O
Extras/Advanced
Timer functions
PID Controller
ExtPID controller
Mainten. counters
Fieldbus data
Solar
ParametersSee chapter 6.
DiagnosticsActive faults
Reset faults
Fault history
Total counters
Trip counters
Software info
I/O and hardware
User settingsLanguage selections
Favorites
*
Basic I/O
Slot D
Slot E
Real time clock
Power unit settings
Keypad
RS-485
Ethernet
Application selection
Parameter backup*
Drive name
See chapter .
User levelsSee chapter 4.3.8.
*. Not available in text keypad
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 40
vacon • 37User Interfaces
Main Menu
Quick Setup
( 17 )
Parameters
( 12 )
ID:M1
STOPREADYI/O
( 5 )
Monitor
Monitor
Multimonitor
(13)
Basic
(13)
Timer functions
(10)
STOPREADYI/O
ID:M2.1
0.0rpm
STOPREADYI/O
Multimonitor
0.00 Hz
ID25FreqReference
Output Freq
0.00Hz
Motor Curre
0.00A
Motor Torque
0.00%
Motor Voltage
Motor Speed
Motor TemperaUnit TemperaDC-link volt
20.0 Hz
FreqReferenc
0.0V
0.0V81.9°C0.0%
ID:1M2.1.1.1
STOPReadyI/O
FreqReference
Output frequency
Motor Power
FreqReference
Motor Speed
Motor Current
Motor Torque
0.00 Hz
10.00 Hz
0.00 rpm
0.00 A
0.00 %
0.00 %
OKOK
OKOK
9171.emf
4.3.1Quick setup
In the Quick Setup parameter group you will find the different wizards of the Vacon 100 X Solar
Pump Application. More detailed information on the parameters of this group you will find in
chapter 3.
4.3.2Monitor
Multi-monitor
NOTE: This menu is not available in text keypad.
On the multi-monitor page, you can collect four to nine values that you wish to monitor.
Change the monitored value by activating the value cell (with arrow buttons left/right) and
clicking OK. Then choose a new item on the Monitoring values list and click OK again. More detailed information on the monitor items can be found in chapter 5.
Trend curve
Trend Curve feature is a graphical presentation of two monitor values at a time.
The
Basic
The basic monitoring values are the actual values of selected parameters and signals as well
as statuses and measurements.
I/O
Statuses and levels of various input and output signal values can be monitored here.
Extras/Advanced
Monitoring of different advanced values, e.g. fieldbus values.
Timer functions
Monitoring of timer functions and the Real Time Clock.
PID Controller
4
Monitoring of PID controller values.
Figure 14. Multi-monitoring page
Page 41
User Interfacesvacon • 38
External PID Controller
Monitoring of external PID controller values.
Maintenance counters
Monitoring of values related to Maintenance counters.
Fieldbus data
Fieldbus data shown as monitor values for debugging purposes at e.g. fieldbus commissioning.
Solar
Monitoring of values related to Solar specific application.
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 42
vacon • 39User Interfaces
4.3.3Parameters
Through this submenu, you can reach the application parameter groups and parameters. More
information on parameters in chapter 6.
4.3.4Diagnostics
Under this menu, you can find
info.
4.3.4.1Active faults
MenuFunctionNote
Active faultsWhen a fault/faults appear(s), the
display with the name of the fault
starts to blink. Press OK to return
to the Diagnostics menu. The
Active faults submenu shows the
number of faults. Select the fault
and push OK to see the fault-time
data.
4.3.4.2Reset faults
MenuFunctionNote
Reset faultsIn this menu you can reset faults.
For closer instructions, see chapter 7.
Active faults, Reset faults, Fault history, Counters and Software
Table 9.
The fault remains active until it is
cleared with the Reset button (push
for 2 s) or with a reset signal from the
I/O terminal or fieldbus or by choosing Reset faults (see below).
The memory of active faults can
store the maximum of 10 faults in
the order of appearance.
Table 10.
CAUTION! Remove external Control
signal before resetting the fault to
prevent unintentional restart of the
drive.
4.3.4.3Fault history
Table 11.
MenuFunctionNote
Fault history40 latest faults are stored in the
Fault history.
Entering the Fault history and clicking OK on the selected fault shows
the fault time data (details).
4
Page 43
User Interfacesvacon • 40
4.3.4.4Total counters
Table 12. Diagnostics menu, Total counters parameters
CodeParameterMinMaxUnitDefaultIDDescription
Amount of energy taken from
supply network. No reset.
NOTE FOR TEXT KEYPAD:
The highest energy unit
V4.4.1Energy counterVaries2291
V4.4.3
V4.4.4
V4.4.5
V4.4.6
V4.4.7
V4.4.8
V4.4.9
V4.4.10
V4.4.11
V4.4.12
V4.4.13
V4.4.14
V4.4.15
Operating time
(graphical keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Run time
(graphical keypad)
Run time
(text keypad)
Run time
(text keypad)
Run time
(text keypad)
Power on time
(graphical keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Start command
counter
a d hh:min2298 Control unit operating time
a
d
hh:min:ss
a d hh:min2293 Motor running time
a
d
hh:min:ss
a d hh:min2294
aPower on time in total years
dPower on time in total days
hh:min:ss
shown on the standard keypad is MW. Should the
counted energy exceed 999.9
MW, no unit is shown on the
keypad.
Control unit operating time in
total years
Control unit operating time in
total days
Control unit operating time in
hours, minutes and seconds
Motor running time in total
years
Motor running time in total
days
Motor running time in hours,
minutes and seconds
Amount of time the power
unit has been powered so far.
No reset.
Power on time in hours, minutes and seconds
The number of times the
2295
power unit has been started.
Service support: find your nearest Vacon service center at www.vacon.com
Resettable energy counter.
NOTE: The highest energy
unit shown on the standard
keypad is MW. Should the
counted energy exceed 999.9
MW, no unit is shown on the
keypad.
P4.5.1Energy trip counterVaries2296
P4.5.3
P4.5.4
P4.5.5
P4.5.6
Operating time
(graphical keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Operating time
(text keypad)
a d hh:min2299 Resettable. See P4.5.1.
aOperating time in total years
dOperating time in total days
hh:min:ss
To reset the counter:
Standard text keypad:
Apply a long (4 s) push on the
OK button.
Graphical k
Push OK once. Reset coun-ter page will appear. Push
OK once again.
Operating time in hours,
minutes and seconds
eypad:
4.3.4.6Software info
Table 14. Diagnostics menu, Software info parameters
CodeParameterMinMaxUnitDefaultIDDescription
V4.6.1
V4.6.2
V4.6.3
V4.6.4System load0100%2300 Load on control unit CPU.
V4.6.5
V4.6.6Application IDApplication code.
V4.6.7Application version
Software package
(graphical keypad)
Software package ID
(text keypad)
Software package
version
(text keypad)
Application name
(graphical keypad)
Code for software identification
Name of application.
4
Page 45
User Interfacesvacon • 42
4.3.5I/O and hardware
Various options-related settings are located in this menu. Note that the values in this menu are
raw values i.e. not scaled by the application.
4.3.5.1
Basic I/O
Monitor here the statuses of inputs and outputs.
Table 15. I/O and Hardware menu, Basic I/O parameters
CodeParameterMinMaxUnitDefaultIDDescription
V5.1.1Digital input 1010Status of digital input signal
V5.1.2Digital input 2010Status of digital input signal
V5.1.3Digital input 3010Status of digital input signal
V5.1.4Digital input 4010Status of digital input signal
V5.1.5Digital input 5010Status of digital input signal
V5.1.6Digital input 6010Status of digital input signal
Shows the selected (with
jumper) mode for Analogue
V5.1.7Analogue input 1 mode133
V5.1.8Analogue input 10100%0.00
V5.1.9Analogue input 2 mode133
V5.1.10Analogue input 20100%0.00
V5.1.11
V5.1.12Analogue output 10100%0.00
V5.1.13Relay output 1010Status of relay output signal
V5.1.14Relay output 2010Status of relay output signal
V5.1.15Relay output 3010Status of relay output signal
Analogue output 1
mode
131
input signal
1 = 0...20mA
3 = 0...10V
Status of analogue input signal
Shows the selected (with
jumper) mode for Analogue
input signal
1 = 0...20mA
3 = 0...10V
Status of analogue input signal
Shows the selected (with
jumper) mode for Analogue
output signal
1 = 0...20mA
3 = 0...10V
Status of analogue output
signal
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 46
vacon • 43User Interfaces
GRAPHICAL KEYPAD
Parameter name (= Function)
Parameter name (= Function)
Parameter value (= selected digital input)
Parameter value (= selected digital input)
4.3.5.2Option board slots
The parameters of this group depend on the option board installed. If no option board is placed
in slots D or E, no parameters are visible.
As an option board is removed, info text 39
Table 16. Option board-related parameters
MenuFunctionNote
Slot DSettingsOption board related settings.
MonitoringMonitor option board-related info.
Slot ESettingsOption board related settings.
MonitoringMonitor option board-related info.
4.3.5.3
The programming of inputs in the Vacon 100X Solar Pump Application is very flexible. The
available inputs on the standard and optional I/O can be used for various functions according
to the operator's choice.
The available I/O can be expanded with optional boards to be inserted in board slots D and E.
More information about the installation of optional boards you will find in the Vacon 100 X Installation manual.
4.3.5.4Digital inputs
The applicable functions for digital inputs are arranged as parameters in parameter group
M3.5.1. The value given to the parameter is a reference to the digital input you choose to use
for the function. The list of functions that you can assign to the available digital inputs is presented on Digital Inputs group.
Programming of digital and analogue inputs
Device removed will appear on the display.
Example
Figure 15.
4
Page 47
User Interfacesvacon • 44
OK
OK
9260.emf
BACK
RESET
BACK
RESET
Given the standard I/O board compilation on the Vacon 100 AC drive, there are 6 digital inputs
available (Slot A terminals 8, 9, 10, 14, 15 and 16). In the programming view, these inputs are
referred to as follows:
Table 17.
Input type
(Graphical keypad)
DigINdIA.1Digital input #1 (terminal 8) on board
DigINdIA.2Digital input #2 (terminal 9) on board
DigINdIA.3Digital input #3 (terminal 10) on
DigINdIA.4Digital input #4 (terminal 14) on
DigINdIA.5Digital input #5 (terminal 15) on
DigINdIA.6Digital input #6 (terminal 16) on
In the example Figure 15, the function
Input type
(Text keypad)
External fault close located in menu M3.5.1 as param-
eter P3.5.1.11, is by default given the value
keypad). This means that the function
External fault close is now controlled with a digital signal
to digital input DI3 (terminal 10).
This is what is shown in the parameter list.
SlotInput #Explanation
in Slot A (standard I/O board).
in Slot A (standard I/O board).
board in Slot A (standard I/O board).
board in Slot A (standard I/O board).
board in Slot A (standard I/O board).
board in Slot A (standard I/O board).
DigIN SlotA.3 (graphical keypad) or dI A.3 (text
CodeParameterDefaultIDDescription
P3.5.1.11External fault closeDigIN SlotA.3405
FALSE = OK
TRUE = External fault
Assume you need to change the selected input. Instead of DI3 you wish to use DI6 (terminal 16)
on the standard I/O. Do as instructed here:
Figure 16. Programming digital inputs with graphical keypad
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 48
vacon • 45User Interfaces
Figure 17. Programming digital inputs with text keypad
Table 18. Programming digital inputs
PROGRAMMING INSTRUCTIONS
Graphical keypadText keypad
1. Select the parameter and push the
right
button.
2. You are now in the
DigIN SlotA. is blinking and under-
value
Edit mode as the slot
Arrow
lined. (Should you have more digital inputs
available in your I/O, for example, through
inserted option boards in slots D or E, they
can also be selected here.).
3. Push the
vate the terminal value
4. Push the
change the terminal value to
Arrow right button again to acti-
3.
Arrow up button three times to
6. Confirm
with OK button.
5. NOTE! If the digital input DI6 was already
used for some other function a message is
displayed. You might then want to change
either of these selections.
1. Select the parameter and push the
OK but-
ton.
2. You are now in the
Edit mode as the letter d
is blinking. (Should you have more digital
inputs available in your I/O, for example,
through inserted option boards in slots D or
E, they can also be selected here.).
3. Push the
terminal value
4. Push the
change the terminal value to
Arrow right button to activate the
3. The letter d stops blinking.
Arrow up button three times to
6. Confirm with
OK button.
5. NOTE! If the digital input DI6 was already
used for some other function a message will
scroll through the display. You might then
want to change either of these selections.
4
Now, the function External fault close is controlled with a digital signal to digital input DI6 (terminal 16).
Page 49
User Interfacesvacon • 46
GRAPHICAL KEYPAD
Parameter name
Parameter name
Parameter value (= selected analogue input)
TEXT KEYPAD
Parameter value (= selected analogue input)
The function is not assigned to any terminal, or, the the input is set to be always
DigIN Slot0.1 (graphical keypad) or dI 0.1 (text keypad). This
NOTE!
FALSE, if its value is
is the default value of the majority of parameters in group M3.5.1.
On the other hand, some inputs have been by default set to be always TRUE. Their
value shows
Also
NOTE!
4.3.5.5Analogue inputs
Time Channels can be assigned to digital inputs. See more information on
page 95.
DigIN Slot0.2 (graphical keypad) or dI 0.2 (text keypad).
The target input for the analogue frequency reference signal can also be chosen from the available analogue inputs.
Given the standard I/O terminals on the Vacon 100 X AC drive, there are 2 analogue inputs available. In the programming view, these inputs are referred to as follows:
Input type
(Graphical keypad)
In the example Figure 18, the parameter
parameter code P3.5.2.1.1, is by default given the value
Service support: find your nearest Vacon service center at www.vacon.com
Figure 18.
Table 19. Programming analogue inputs
Input type
(Text keypad)
AnINAIA.1Analogue input #1 (terminals 2/3) on
AnINAIA.2Analogue input #2 (terminals 4/5) on
SlotInput #Explanation
board in Slot A (standard I/O termi-
AI1 signal selection located in menu M3.5.2.1 with
nals).
board in Slot A (standard I/O terminals).
AnIN SlotA.1 (graphical keypad) or AI
4
Page 50
vacon • 47User Interfaces
9264 emf
A.1 (text keypad). This means that the target input for the analogue frequency reference signal
AI1 is now the analogue input in terminals 2/3. Whether the signal is voltage or current, must
be determined with the
dip switches. See the Installation manual for more information.
This is what is shown in the parameter list on page 81:
CodeParameterMinMaxUnitDefaultIDDescription
Connect the AI1 signal to the
P3.5.2.1.1AI1 signal selection
AnIN
SlotA.1
analogue input of your choice
377
with this parameter.
Programmable. See page 81.
Assume you need to change the selected input. Instead of AI1 you wish to use the analogue input on your option board in slot D. Do as instructed here:
Figure 19. Programming analogue inputs with graphical keypad
Figure 20. Programming analogue inputs with text keypad
PROGRAMMING INSTRUCTIONS
Graphical keypadText keypad
1. Select the parameter and push the
right
button.
2. You are now in the
AnIN SlotA. is blinking and under-
value
Edit mode as the slot
lined.
3. Push the
the slot value to
Arrow up button once to change
AnIN SlotC. Confirm with
OK button.
Arrow
1. Select the parameter and push the
ton.
2. You are now in the
Edit mode as the letter A
is blinking.
3. Push the
the slot value to
Arrow up button once to change
C. Confirm with OK button.
OK but-
4
Page 51
User Interfacesvacon • 48
4.3.5.6Descriptions of signal sources
Table 20. Descriptions of signal sources
SourceFunction
Digital inputs:
A digital signal can be forced to a constant FALSE or TRUE
state using this functionality.
For example, some signals have been set to be always in
TRUE state by manufacturer, e.g parameter P3.5.1.15 (Run
enable). Unless changed, Run enable signal is always on.
Slot0.#
SlotA.#
SlotD.#Number (#) corresponds to digital input in slot D.
# = 1: Always FALSE
# = 2-10: Always TRUE
Analogue inputs (used for testing purposes):
# = 1: Analogue input = 0% signal strength
# = 2: Analogue input = 20% signal strength
# = 3: Analogue input = 30% signal strength
etc.
# = 10: Analogue input = 100% signal strength
Number (#) corresponds to digital input in slot A(Standard
terminals).
SlotE.#Number (#) corresponds to digital input in slot E.
TimeChannel.#
Fieldbus CW.#Number (#) refers to Control Word bit number.
FieldbusPD.#Number (#) refers to Process Data 1 bit number.
Number (#) corresponds to: 1=Time Channel1, 2=Time
Channel2, 3=Time Channel3
4.3.5.7Default assignments of digital and analogue inputs in Vacon 100 application
Digital and analogue inputs are assigned certain functions by the factory. In this application,
the default assignments are:
Table 21. Default assignments of inputs
InputTer mina l( s)ReferenceAssigned functionParameter code
DI18A.1Control signal 1 AP3.5.1.1
DI29A.2Control signal 2 AP3.5.1.2
DI310A.3External fault closeP3.5.1.11
DI414A.4Preset Freq Sel0P3.5.1.21
DI515A.5Preset Freq Sel1P3.5.1.22
DI616A.6External fault closeP3.5.1.13
AI12/3A.1AI1 signal selectionP3.5.2.1.1
AI24/5A.2AI2 signal selectionP3.5.2.2.1
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 52
vacon • 49User Interfaces
4.3.5.8Real time clock
Table 22. I/O and Hardware menu, Real time clock parameters
Daylight saving rule
1 = Off
2 = EU; Starts on last Sunday
in March, ends last Sunday in
October
3 = US; Start on 2nd Sunday
in March, ends on 1st Sunday
in November
4 = Russia (permanent)
4.3.5.9Power unit settings
Fan control
The fan operates in speed-controlled mode. The speed is controlled according to the drive’s
internal logic that receives data from temperature measurements.
Table 23. Power unit settings, Fan control
CodeParameterMinMaxUnitDefaultIDDescription
If enabled, the fan will stop in
5 minutes when the drive is
Table 26. I/O and Hardware menu, Keypad parameters
CodeParameterMinMaxUnitDefaultIDDescription
Time after which the display
P5.7.1Timeout time060min0
P5.7.2Default page040
P5.7.3Menu index
P5.7.4
P5.7.5Backlight time060min5
Contrast
*
3070%50
returns to page defined with
parameter P5.7.2.
0 = Not used
The page the keypad shows
when the drive is powered on
or when the time defined
with P5.7.1 has expired. If the
value is set to 0 the page last
visited is shown.
0 = None
1 = Enter menu index
2 = Main menu
3 = Control page
4 = Multimonitor
Set menu index for desired
page and activate with
parameter P5.7.2 = 1.
Set contrast of the display
(30...70%).
Set the time until the backlight of the display turns off
(0...60 min). If set to 0 s,
backlight is always on.
*. Only available with graphical keypad
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 54
vacon • 51User Interfaces
4.3.5.11Fieldbus
Parameters related to different fieldbus boards can also be found in the I/O and Hardware
menu. These parameters are explained in more detail in the respective fieldbus manual.
IP address
Subnet mask
Default gateway
MAC address
Modbus/TCPCommon settingsConnection limit
BacNet IPSettingsInstance number
NA
NA
NA
NA
NA
NA
Slave address
Communication timeout
Communication timeout
Protocol in use
BBMD IP
BBMD port
Time to live
MonitoringFB protocol status
Communication status
Actual instance
Control Word
Status Word
4
Page 55
User Interfacesvacon • 52
4.3.6User settings
Table 28. User settings menu, General settings
CodeParameterMinMaxUnitDefaultIDDescription
P6.1Language selectionsVariesVariesVaries802
P6.2Application selection801
M6.5Parameter backupSee chapter 4.3.6.1 below.
P6.7Drive nameGive name of drive if needed.
Depends on language package.
4.3.6.1
Parameter backup
Table 29. User settings menu, Parameter backup parameters
CodeParameterMinMaxUnitDefaultIDDescription
Restores default parameter
P6.5.1
P6.5.2
P6.5.3Restore from keypad*
B6.5.4Save to Set 1
B6.5.5Restore from Set 1
B6.5.6Save to Set 2
B6.5.7Restore from Set 2
Restore factory
defaults
Save to keypad
*
010
values and initiates the
831
Startup Wizard when activated
Save parameter values to
keypad to e.g. copy them to
another drive.
0 = No
1 = Yes
Load parameter values from
keypad to the drive.
Store a customised parameter set (all parameters
included in the application)
Load the customised parameter set to the drive.
Store another customised
parameter set (all parameters included in the application)
Load the customised parameter set 2 to the drive.
*. Only available with graphical keypad
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 56
vacon • 53User Interfaces
Motor Nom Freq
50.00 Hz
Favorites
STOPREADYI/O
Help
Motor Nom Freq
STOPREADYI/O
Monitor
Rem from favorites
OKOK
9172.emf
STOPREADYKeypadALARM
ID:2362P8.2
User levels
User level
Normal
Access code
00000
STOPREADYI/OALARM
00000
Min:0
Max:9
ID:2362P8.2
Access code
OK
9173.emf
4.3.7Favorites
NOTE: This menu is not available in text keypad.
Favorites are typically used to collect a set of parameters or monitoring signals from any of the
keypad menus. You can add items or parameters to the Favorites folder, see chapter .
To remove an item or a parameter from the Favorites folder, do the following:
4.3.8User levels
User level parameters are intended to restrict the visibility of parameters and to prevent unauthorized and inadvertent parameterization on the keypad.
Table 30. User level parameters
CodeParameterMinMaxUnitDefaultIDDescription
1 = Normal; All menus visible
in the Main menu
2 = Monitoring; Only Monitor,
Favorites and User Levels
P8.1User level1311194
P8.2Access code09999902362
menus are visible in the main
menu
3 = Favorites; Only Favorites
and User Levels menus are
visible in the Main menu
If set to other value than 0
before switching to monitoring when e.g. user level Nor-mal is active, the access
code will be asked when trying to switch back to Nor-mal. Can therefore be used
to prevent unauthorized
parameterization on the keypad.
4
Page 57
User Interfacesvacon • 54
Reference
potentiometer 1...10 k
Ω
Remote reference
4...20mA/0...10V
mA
4.4Example of control connections
The terminals of the Standard I/Os and the Relays are described below. The terminals shown
on shadowed background are assigned for signals with optional functions selectable with DIP
switches. See more information in Vacon 100X Installation Manual.
Table 31. Control I/O terminal signals and connection example.
Standard I/O
TerminalSignal
1+10 VrefReference output
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
30+24 Vin
ARS485Serial bus, negative
BRS485Serial bus, positive
AI1+
AI1-
AI2+
AI2-
24Vout24V aux. voltage
GNDI/O ground
DI1Digital input 1
DI2Digital input 2
DI3Digital input 3
CM
24Vout24V aux. voltage
GNDI/O ground
DI4Digital input 4
DI5Digital input 5
DI6Digital input 6
CMCommon for DI1-DI6*
AO1+
AO-/GND
Analogue input,
voltage or current
Analogue input common
Analogue input,
voltage or current
Analogue input common
Common for DI1-DI6
Analogue output,
voltage or current
Analogue output common
24V auxiliary input
voltage
*
Service support: find your nearest Vacon service center at www.vacon.com
*. Can be isolated from ground, see Vacon
100X Installation Manual.
4
Page 58
vacon • 55User Interfaces
From
standard I/O
From term.
#13
From term.
#6
RUN
4.4.1Relay and thermistor input terminals
Table 32. I/O terminal signals for relay and thermistor terminals and connection example.
Relays and thermistor
TerminalSignal
21
22
23
24
25
26
28
29
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
TI1+
TI1-
Relay output 1
Relay output 2
Thermistor input
4.4.2Safe Torque off (STO) terminals
For more information on the functionalities of the Safe Torque Off (STO), see Vacon 100X Installation Manual.
Table 33. I/O terminal signals for the STO functions.
Safe Torque Off terminals
Term inalSignal
S1
G1
S2
G2
F+
F-
Isolated digital input 1 (interchangeable polarity);
+24V ±20% 10...15mA
Isolated digital input 2 (interchangeable polarity);
+24V ±20% 10...15mA
Isolated feedback (CAUTION!
Polarity to be respected);
+24V ±20%
Isolated feedback (CAUTION!
Polarity to be respected);
GND
4
Page 59
User Interfacesvacon • 56
Service support: find your nearest Vacon service center at www.vacon.com
4
Page 60
vacon • 57Monitoring Menu
OK
OK
OK
OK
9250.emf
5.MONITORING MENU
5.1Monitor group
Vacon 100 X AC drive provides you with a possibility to monitor the actual values of parameters
and signals as well as statuses and measurements. Some of the values to be monitored are
customizable.
5.1.1Multimonitor
On the multi-monitor page, you can collect four to nine values that you wish to monitor.
5.1.2Trend curve
The
Trend Curve feature is a graphical presentation of two monitor values at a time.
Selecting values to monitor starts logging the values. In the Trend curve submenu, you can
view the trend curve, make the signal selections, give the minimum and maximum settings,
Sampling interval and choose whether to use Autoscaling or not.
Change values to monitor following the procedure below:
1. Locate the
2. Further enter the menu
3. The current selections to monitor are
Trend curve menu in the Monitor menu and press OK.
View trend curve by pressing OK again.
FreqReference and Motor speed visible at the bottom
of the display.
4. Only two values can be monitored as trend curves simultaneously. Select the one of the
current values you wish to change with the arrow buttons and press OK.
5. Browse the list of given monitoring values with the arrow buttons, select the one you wish
and press OK.
6. The trend curve of the changed value can be seen on the display.
5
The
Trend Curve feature also allows you to halt the progression of the curve and read the exact
invidual values.
1. In Trend curve view, select the display with the arrow button up (the frame of the display
turns bold) and press OK at the desired point of the progressing curve. A vertical hairline
appears on the display.
2. The display freezes and the values at the bottom of the display correspond to the location of
the hairline.
3. Use the arrow buttons left and right to move the hairline to see the exact values of some
other location.
Page 61
Monitoring Menuvacon • 58
9251.emf
OK
Table 34. Trend curve parameters
CodeParameterMinMaxUnitDefaultIDDescription
Enter this menu to select and
M2.2.1View Trend curve
P2.2.2Sampling interval100432000ms1002368
P2.2.3Channel 1 min-2147481000-10002369
P2.2.4Channel 1 max-100021474810002370
P2.2.5Channel 2 min-2147481000-10002371
P2.2.6Channel 2 max-100021474810002372
P2.2.7Autoscale0102373
monitor values for viewing in
curve form.
Set here the sampling interval.
Used by default for scaling.
Adjustments might be necessary.
Used by default for scaling.
Adjustments might be necessary.
Used by default for scaling.
Adjustments might be necessary.
Used by default for scaling.
Adjustments might be necessary.
The selected signal is automatically scaled between
min and max values if this
parameter is given value 1.
Service support: find your nearest Vacon service center at www.vacon.com
5
Page 62
vacon • 59Monitoring Menu
5.1.3Basic
See Table 35 in which the basic monitoring values are presented.
NOTE!
Only standard I/O board statuses are available in the Monitor menu. Statuses for all I/O board
signals can be found as raw data in the I/O and Hardware system menu.
Check expander I/O board statuses when required in the I/O and Hardware system menu.
Table 35. Basic monitoring menu items
CodeMonitoring valueUnitScaleIDDescription
V2.3.1Output frequencyHz0.011Output frequency to motor
V2.3.2FreqReferenceHz0.0125Frequency reference to motor control
V2.3.3Motor speedrpm12Motor actual speed in rpm
V2.3.4Motor currentAVaries3
V2.3.5Motor torque%0.14Calculated shaft torque
V2.3.7Motor shaft power%0.15Calculated motor shaft power in %
Calculated motor shaft power in kW or hp.
V2.3.8Motor shaft powerkW/hpVaries73
V2.3.9Motor voltageV0.16Output voltage to motor
V2.3.10DC link voltageV17Measured voltage in the drive’s DC-link
V2.3.11Unit temperature°C0.18Heatsink temperature in °C or °F
V2.3.12Motor temperature%0.19
V2.3.13Motor Preheat11228
Units depends on the unit selection parameter.
Calculated motor temperature in percent
of nominal working temperature.
Status of Motor preheat function.
0 = OFF
1 = Heating (feeding DC-current)
5
Page 63
Monitoring Menuvacon • 60
5.1.4I/O
Table 36. I/O signal monitoring
CodeMonitoring valueUnitScaleIDDescription
V2.4.1Slot A DIN 1, 2, 3115
V2.4.2Slot A DIN 4, 5, 6116
V2.4.3Slot B RO 1, 2, 3117Shows the status of relay inputs 1-3 in slot B
V2.4.4Analogue input 1%0.0159
V2.4.5Analogue input 2%0.0160
V2.4.6Analogue input 3%0.0161
V2.4.7Analogue input 4%0.0162
V2.4.8Analogue input 5%0.0175
V2.4.9Analogue input 6%0.0176
V2.4.10Slot A AO1%0.0181
Shows the status of digital inputs 1-3 in slot
A (standard I/O)
Shows the status of digital inputs 4-6 in slot
A (standard I/O)
Input signal in percent of used range. Slot
A.1 as default.
Input signal in percent of used range. Slot
A.2 as default.
Input signal in percent of used range. Slot
D.1 as default.
Input signal in percent of used range. Slot
D.2 as default.
Input signal in percent of used range. Slot
E.1 as default.
Input signal in percent of used range. Slot
E.2 as default.
Analog output signal in percent of used
range. Slot A (standard I/O)
Service support: find your nearest Vacon service center at www.vacon.com
5
Page 64
vacon • 61Monitoring Menu
5.1.5Extras & advanced
Table 37. Advanced values monitoring
CodeMonitoring valueUnitScaleIDDescription
Bit coded word
B1=Ready
B2=Run
B3=Fault
V2.6.1DriveStatusWord143
V2.6.2Ready status178
V2.6.3Appl.StatusWord1189
V2.6.4Appl.StatusWord2190
B6=RunEnable
B7=AlarmActive
B10=DC Current in stop
B11=DC Brake Active
B12=RunRequest
B13=MotorRegulatorActive
Bit coded information about ready criteria.
Useful for debugging when the drive is not in
ready status.
Values are visible as checkboxes on graphical keypad. If checked (), the value is
active.
B0: RunEnable high
B1: No fault active
B2: Charge switch closed
B3: DC voltage within limits
B4: Power manager initialized
B5: Power unit is not blocking start
B6: System software is not blocking start
Bit coded statuses of application.
Values are visible as checkboxes on graphical keypad. If checked (), the value is
active.
B0=Interlock 1
B1=Interlock 2
B2=Reserved
B3=Ramp 2 active
B4=Mechanical brake control
B5=I/O A control active
B6=I/O B control active
B7=Fieldbus Control Active
B8=Local control active
B9=PC control active
B10=Preset frequencies active
B11=Inching active
B12=Fire Mode active
B13=Motor Preheat active
B14=Forced stop active
B15=Drive stopped from keypad
Bit coded status of application.
Values are visible as checkboxes on graphical keypad. If checked (), the value is
active.
B0=Acc/Dec prohibited
B1=Motor switch open
B5=Jockey pump active
B6=Priming pump active
B7=Input pressure supervision (Alarm/Fault)
B8=Frost protection (Alarm/Fault)
B9=Autocleaning active
5
Page 65
Monitoring Menuvacon • 62
Table 37. Advanced values monitoring
CodeMonitoring valueUnitScaleIDDescription
16-bit word where each bit represents the
status of one digital input. 6 digital inputs
V2.6.5DIN StatusWord1156
V2.6.6DIN StatusWord2157
V2.6.7MotCurrent1 deci.0.145
V2.6.8FreqRef Source11495
V2.6.9LastActiveFaultCode137
V2.6.10LastActiveFault ID195
V2.6.11LastActiveAlarmCode174
V2.6.12LastActiveAlarm ID194
V2.6.13MotorRegulat.Status177
from every slot are read. Word 1 starts from
input 1 in slot A (bit0) and goes all the way to
input 4 in slot C (bit15).
16-bit word where each bit represents the
status of one digital input. 6 digital inputs
from every slot are read. Word 1 starts from
input 5 in slot C (bit0) and goes all the way to
input 6 in slot E (bit13).
Motor current monitor value with fixed number of decimals and less filtering. Can be
used e.g. for fieldbus purposes to always get
the right value regardless of frame size, or
for monitoring when less filtering time is
needed for the motor current.
Shows the momentary frequency reference
source.
0=PC
1=Preset Freqs
2=Keypad Reference
3=Fieldbus
4=AI1
5=AI2
6=AI1+AI2
7=PID Controller
8=Motor Potentiom.
9=Joystick
10=Inching
100=Not defined
101=Alarm,PresetFreq
102=Autocleaning
The fault code of latest activated fault that
has not been reset.
The fault ID of latest activated fault that has
not been reset.
The alarm code of latest activated alarm that
has not been reset.
The alarm ID of latest activated alarm that
has not been reset.
Motor limit controller status. Checked = limit
controller is active, Unchecked = limit controller is not active
Service support: find your nearest Vacon service center at www.vacon.com
5
Page 66
vacon • 63Monitoring Menu
5.1.6Timer functions
Here you can monitor values of timer functions and the Real Time Clock.
Table 38. Monitoring of timer functions
CodeMonitoring valueUnitScaleIDDescription
V2.7.1TC 1, TC 2, TC 311441
V2.7.2Interval 111442Status of timer interval
V2.7.3Interval 211443Status of timer interval
V2.7.4Interval 311444Status of timer interval
V2.7.5Interval 411445Status of timer interval
V2.7.6Interval 511446Status of timer interval
V2.7.7Timer 1s11447Remaining time on timer if active
V2.7.8Timer 2s11448Remaining time on timer if active
V2.7.9Timer 3s11449Remaining time on timer if active
V2.7.10Real time clock1450hh:mm:ss
Possible to monitor the statuses of the
three Time Channels (TC)
5.1.7PID Controller
Table 39. PID Controller value monitoring
CodeMonitoring valueUnitScaleIDDescription
V2.8.1PID setpointVaries
V2.8.2PID feedbackVaries
V2.8.3PID error Varies
V2.8.4PID output%0.0123
V2.8.5PID status124
According to
P3.13.1.7
According to
P3.13.1.7
According to
P3.13.1.7
PID controller setpoint value in process
20
units. Process unit is selected with a
parameter.
PID controller feedback value in process
21
units. Process unit is selected with a
parameter.
PID controller error value. Deviation of
22
feedback from setpoint in process units.
Process unit is selected with a parameter.
PID output in percent (0..100%). This value
can be fed e.g. to Motor Control (Frequency
reference) or Analogue output
0=Stopped
1=Running
3=Sleep mode
4=In dead band
5
Page 67
Monitoring Menuvacon • 64
5.1.8ExtPID Controller
Table 40. External PID Controller value monitoring
CodeMonitoring valueUnitScaleIDDescription
V2.9.1ExtPID setpointVaries
V2.9.2ExtPID feedbackVaries
V2.9.3ExtPID error Varies
V2.9.4ExtPID output%0.0186
V2.9.5ExtPID status187
According to
P3.14.1.10
According to
P3.14.1.10
According to
P3.14.1.10
External PID controller setpoint value in
83
process units. Process unit is selected with
a parameter.
External PID controller feedback value in
84
process units. Process unit is selected with
a parameter.
External PID controller Error value. Deviation of feedback from setpoint in process
85
units. Process unit is selected with a
parameter.
External PID controller outputin percent
(0..100%). This value can be fed e.g. to Analogue output.
0=Stopped
1=Running
4=In dead band
5.1.9Mainten. counters
Table 41. Maintenance counter monitoring
CodeMonitoring valueUnitScaleIDDescription
Status of maintenance counter in revolutions
multiplied by 1000, or hours.
V2.11.1MaintenCounter 1h/ kRevVaries1101
For configuration and activation of this counter, see chapter Group 3.16: Maintenance
counters.
5.1.10Fieldbus data
Table 42. Fieldbus data monitoring
Code
V2.12.1FB Control Word 1874
V2.12.2
V2.12.3FB data in 11876Raw value of process data in 32-bit signed format
V2.12.4FB data in 21877Raw value of process data in 32-bit signed format
V2.12.5FB data in 31878Raw value of process data in 32-bit signed format
V2.12.6FB data in 41879Raw value of process data in 32-bit signed format
Service support: find your nearest Vacon service center at www.vacon.com
Monitoring
value
FB Speed Refer-
ence
UnitScaleIDDescription
Fieldbus control word used by application in
bypass mode/format. Depending on the fieldbus
type or profile the data can be modified before
sent to application.
Speed reference scaled between minimum and
maximum frequency at the moment it was
Varies875
received by the application. Minimum and maximum frequencies can be changed after the reference was received without affecting the reference.
5
Page 68
vacon • 65Monitoring Menu
Table 42. Fieldbus data monitoring
Code
V2.12.7FB data in 51880Raw value of process data in 32-bit signed format
V2.12.8FB data in 61881Raw value of process data in 32-bit signed format
V2.12.9FB data in 71882Raw value of process data in 32-bit signed format
V2.12.10FB data in 81883Raw value of process data in 32-bit signed format
V2.12.11FB Status Word1864
V2.12.12FB Speed Actual0.01865
V2.12.13FB data out 11866Raw value of process data in 32-bit signed format
V2.12.14FB data out 21867Raw value of process data in 32-bit signed format
V2.12.15FB data out 31868Raw value of process data in 32-bit signed format
V2.12.16FB data out 41869Raw value of process data in 32-bit signed format
V2.12.17FB data out 51870Raw value of process data in 32-bit signed format
V2.12.18FB data out 61871Raw value of process data in 32-bit signed format
V2.12.19FB data out 71872Raw value of process data in 32-bit signed format
V2.12.20FB data out 81873Raw value of process data in 32-bit signed format
Monitoring
value
UnitScaleIDDescription
Fieldbus status word sent by application in bypass
mode/format. Depending on the FB type or profile
the data can be modified before sent to the FB.
Actual speed in %. 0 and 100% correspond to minimum and maximum frequencies respectively.
This is continuously updated depending on the
momentary min and max frequencies and the output frequency.
5.1.11Solar
Table 43. Solar monitoring items
Code
Monitoring
value
UnitScaleIDDescription
V2.15.1Vmp refV1914DC voltage reference for MPP regulation
V2.15.2Vmp ref correctV1942
Present correction on DC voltage reference
(P&O + oscillation)
V2.15.3Motor PowerkW1938Motor shaft power
V2.15.4Energy counterMWh1937Counter of energy taken by the supply
B2.15.5
Energy counter
reset
1932To reset V2.15.4
5
Page 69
Parametersvacon • 66
Main Menu
Quick Setup
( 17 )
( 6 )
Monitor
ID:M3
STOPREADYKeypad
Parameters
( 13 )
STOPREADYKeypad
Motor Settings
( 2 )
Start/Stop Setup
( 7 )
References
( 18 )
Parameters
ID:M3.1
OK
9147.emf
OK
9151.emf
6.PARAMETERS
The Vacon AC drive contains a preloaded Vacon 100X Solar Pump application for instant use.
The parameters of this application are listed in this chapter.
6.1Application parameter lists
Find the parameter menu and the parameter groups as guided below.
The Vacon 100 X Solar Pump Application embodies the following parameter groups:
Table 44. Parameter groups
Menu and Parameter groupDescription
Group 3.1: Motor settingsBasic and advanced motor settings
Group 3.2: Start/Stop setupStart and stop functions
Group 3.3: ReferencesParameters for setting references and preset speeds.
Group 3.4: Ramps And BrakesAcceleration/Deceleration setup
Group 3.5: I/O ConfigI/O programming
Group 3.6: Fieldbus DataMapProcess data in/out mapping
Group 3.7: Prohibit FreqProhibit frequencies programming
Group 3.8: SupervisionsProgrammable limit controllers
Group 3.9: ProtectionsProtections configuration
Group 3.10: Automatic resetAuto reset after fault configuration
Group 3.11: Appl. SettingsApplication settings
Group 3.12: Timer functionsConfiguration of 3 timers based on Real Time Clock.
Group 3.13: PID ControllerParameters for PID Controller 1.
Group 3.14: ExtPID ControllerParameters for external PID Controller.
Group 3.16: Mainten. CountersParameters related to Maintenance counters.
Group 3.21: Pump ControlPump function parameters
Group 3.22: SolarSolar specific function parameters
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 70
vacon • 67Parameters
6.1.1Column explanations
Code=Location indication on the keypad; Shows the operator the parameter num-
ber.
Parameter= Name of parameter
Min=Minimum value of parameter
Max=Maximum value of parameter
Unit=Unit of parameter value; Given if available
Default=Value preset by factory
ID=ID number of the parameter
Description= Short description of parameter values or its function
=More information on this parameter available; Click the parameter name
6.1.2Group 3.1: Motor settings
6.1.2.1Group 3.1.1: Motor nameplate
Table 45. Motor nameplate parameters
CodeParameterMinMaxUnitDefaultIDDescription
P3.1.1.1Motor Nom VoltgVariesVariesVVaries110
P3.1.1.2Motor Nom Freq8.00320.00HzVaries111
P3.1.1.3Motor Nom Speed2419200rpmVaries112
P3.1.1.4Motor Nom CurrntVariesVariesAVaries113
P3.1.1.5Motor Cos Phi0.301.000.74120
P3.1.1.6Motor Nom PowerVariesVarieskWVaries116
Find this value U
rating plate of the motor.
Note also used connection
(Delta/Star).
Find this value f
ing plate of the motor.
Find this value n
ing plate of the motor.
Find this value I
ing plate of the motor.
Find this value on the rating
plate of the motor
Find this value In on the rating plate of the motor.
on the
n
on the rat-
n
on the rat-
n
on the rat-
n
6
6.1.2.2Group 3.1.2: Motor Control
Table 46. Motor control
CodeParameterMinMaxUnitDefaultIDDescription
P3.1.2.1Control mode010600
P3.1.2.2Motor type010650
0 = U/f Freq ctrl open loop
1 = Speed control open loop
0 = Induction motor
1 = PM motor
Page 71
Parametersvacon • 68
Table 46. Motor control
CodeParameterMinMaxUnitDefaultIDDescription
Increasing the switching
frequency reduces the
capacity of the AC drive. It is
recommended to use a
lower frequency when the
P3.1.2.3Switching Freq1.5VarieskHzVaries601
P3.1.2.4Identification010631
P3.1.2.5Magnetizing current0.02*IHA0.0612
P3.1.2.6Motor switch010653
P3.1.2.7Load drooping0.0050.00%0.00620
P3.1.2.8Load drooping time0.002.00s0.00656
P3.1.2.9Load drooping mode0101534
motor cable is long in order
to minimize capacitive currents in the cable. Motor
noise can also be minimised
using a high switching frequency.
The automatic motor identification calculates or measures the motor parameters
that are needed for optimum motor and speed control.
0 = No action
1 = At standstill
Motor magnetizing current
(no-load current). The values of the U/f parameters
are identified by the magnetizing current if given before
the identification run. If this
value is set to zero, magnetizing current will be internally calculated.
Enabling this function prevents the drive from tripping
when the motor switch is
closed and opened e.g.
using flying start.
0 = Disabled
1 = Enabled
The drooping function
enables speed drop as a
function of load. Drooping
will be defined in percent of
nominal speed at nominal
load.
Load drooping is used in
order to achieve a dynamic
speed drooping because of
changing load. This parameter defines the time during
which the speed is restored
to the level it was before the
load increase.
0 = Normal; Load drooping
factor is constant through
the whole frequency range
1 = Linear removal; Load
drooping is removed linearly
from nominal frequency to
zero frequency
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 72
vacon • 69Parameters
Table 46. Motor control
CodeParameterMinMaxUnitDefaultIDDescription
P3.1.2.11Under Volt. Control011608
P3.1.2.12Energy optimization010666
P3.1.2.13StatorVoltAdjust50.0150.0%100.0659
P3.1.2.14Overmodulation011
0 = Disabled
1 = Enabled
The drive searches for the
minimum motor current in
order to save energy and to
lower the motor noise. This
function can be used e.g. in
fan and pump applications
0 = Disabled
1 = Enabled
Parameter for adjusting the
stator voltage in permanent
magnet motors.
Maximizes drive output voltage, but increases motor
current harmonics.
0= Disabled
1= Enabled
6.1.2.3Group 3.1.3: Limits
Table 47. Motor limit settings
CodeParameterMinMaxUnitDefaultIDDescription
P3.1.3.1Current limitVariesVariesAVaries107
P3.1.3.2MotorTorqueLimit0.0300.0%300.01287
P3.1.3.3GenerTorqueLimit0.0300.0%300.01288
P3.1.3.4MotorPowerLimit0.0300.0%300.01290
P3.1.3.5GenerPowerLimit0.0300.0%300.01289
Maximum motor current
from AC drive
Maximum motoring side
torque limit
Maximum generating side
torque limit
Maximum motoring side
power limit
Maximum generating side
power limit
6.1.2.4Group 3.1.4: Open loop
Table 48. Open loop settings
CodeParameterMinMaxUnitDefaultIDDescription
6
P3.1.4.1U/f ratio020108
P3.1.4.2Field WeakngPnt8.00P3.3.1.2HzVaries602
Type of U/f curve between
zero frequency and the field
weakening point.
0=Linear
1=Squared
2=Programmable
The field weakening point is
the output frequency at
which the output voltage
reaches the field weakening
point voltage
Page 73
Parametersvacon • 70
Table 48. Open loop settings
CodeParameterMinMaxUnitDefaultIDDescription
Voltage at field weakening
P3.1.4.3Voltage at FWP10.00200.00%100.00603
P3.1.4.4U/f Mid Freq0.00P3.1.4.2HzVaries604
P3.1.4.5U/f Mid Voltg0.0100.0%100.0605
P3.1.4.6Zero Freq Voltg0.0040.00%Varies606
P3.1.4.7Flying Start Options0101590
P3.1.4.8FlyStartScanCurrent0.0100.0%45.01610
P3.1.4.9Auto TorqueBoost010109
P3.1.4.10
P3.1.4.11
Torq u e b o o st m o t o r
gain
Torque boost genera-
tor gain
0.0100.0%100.0667
0.0100.0%0.0665
point in % of motor nominal
voltage
Provided that the programmable U/f curve has been
selected (par. P3.1.4.1) , this
parameter defines the middle point frequency of the
curve.
Provided that the programmable U/f curve has been
selected (par. P3.1.4.1), this
parameter defines the middle point voltage of the
curve.
This parameter defines the
zero frequency voltage of
the U/f curve. The default
value varies according to
unit size.
Checkbox selection:
B0 = Search shaft frequency
from same direction as frequency reference.
B1 = Disable AC scanning
B4 = Use frequency reference for initial guess
B5 = Disable DC pulses
Defined in percentage of
motor nominal current.
Automatic torque boost can
be used in application where
starting torque due to starting friction is high.
0= Disabled
1= Enabled
Scaling factor for motoring
side IR-compensation when
torque boost is used.
Scaling factor for generating
side IR-compensation when
torque boost is used.
6.1.2.5Group 3.1.4.12: I/f start
The I/f Start function is typically used with permanent magnet synchronous motors (PMSM) to
start the motor with constant current control. This is useful with high power motors in which
the resistance is low and the tuning of the U/f curve difficult.
The
I/f Start function can be used with induction motors (IM), too, e.g. if the tuning of the U/f
curve is difficult at low frequencies.
Applying the I/f Start function may also prove useful in providing sufficient torque for the motor
at startup.
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 74
vacon • 71Parameters
Motor Current
Time
[s]
I/
f Start
Frequency
I/
f Start Current
Output Frequency
9240.emf
Figure 21. I/f start
Table 49. I/f start parameters
CodeParameterMinMaxUnitDefaultIDDescription
P3.1.4.12.1I/f start010534
P3.1.4.12.2I/f start frequency0.0P3.1.1.2%15.0535
P3.1.4.12.3I/f start current0.0100.0%80.0536
6.1.2.6
CodeParameterMinMaxUnitDefaultIDDescription
P3.1.4.13.1TorqStabGain0.0500.0%50.01412
P3.1.4.13.2TorqStabGainFWP0.0500.0%50.01414
P3.1.4.13.3TorqStabDampTC0.00051.0000s0.00501413
P3.1.4.13.4
Group 3.1.4.13: Stabilators
Tor qSta bD ampTC
PMM
0.00051.0000s0.05001735
0 = Disabled
1 = Enabled
Output frequency limit
below which the defined I/f
start current is fed to motor.
The current fed to the motor
when the I/f start function is
activated.
Gain of the torque stabilator
in open loop motor control
operation.
Gain of the torque stabilator
at field weakening point in
open loop motor control
operation.
Damping time of torque stabilizer
Damping time constant of
torque stabilizer for PMmotor.
6
Page 75
Parametersvacon • 72
6.1.3Group 3.2: Start/Stop setup
Start/Stop commands are given differently depending on the control place.
Remote control place (I/O A): Start, stop and reverse commands are controlled by 2 digital inputs chosen with parameters P3.5.1.1 and P3.5.1.2. The functionality/logic for these inputs is
then selected with parameter P3.2.6 (in this group).
Remote control place (I/O B): Start, stop and reverse commands are controlled by 2 digital inputs chosen with parameters P3.5.1.4 and P3.5.1.5. The functionality/logic for these inputs is
then selected with parameter P3.2.7 (in this group).
Local control place (Keypad): Start and stop commands come from the keypad buttons, while
the direction of rotation is selected by the parameter P3.3.1.9.
Remote control place (Fieldbus): Start, stop and reverse commands come from fieldbus.
Table 50. Start/Stop Setup menu
CodeParameterMinMaxUnitDefaultIDDescription
Selection of remote control
place (start/stop). Can be
used to change back to
P3.2.1Rem.Ctrl. Place010172
P3.2.2Local/Remote010211
P3.2.3Keypad stop button010114
P3.2.4Start function010505
P3.2.5Stop function020506
P3.2.6I/O A logic041300
P3.2.7I/O B logic041363See above.
P3.2.8FB Start logic010889
remote control from Vacon
Live e.g. in case of a broken
panel.
0=I/O control
1=Fieldbus control
Switch between local and
remote control places
0=Remote
1=Local
0=Stop button always
enabled (Yes)
1=Limited function of Stop
button (No)
0=Ramping
1=Flying start
0: coasting
1: ramp to min frequency
2: ramp to zero frequency
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 76
vacon • 73Parameters
Table 50. Start/Stop Setup menu
CodeParameterMinMaxUnitDefaultIDDescription
Choose whether to copy the
Run state and Reference
when changing from
P3.2.10Rem to Loc Funct022181
P3.2.11 Start Analogue Signal0101810
P3.2.12Start Analogue Level0.00100.00%10.001857
P3.2.13Stop Analogue Level0.00100.00%80.001856
Remote to Local (keypad)
control:
0 = Keep Run
1 = Keep Run & Reference
2 = Stop
0= AI1
1= AI2
Start is set below this level
(unscaled signal). Startstop logic is reversed if >
P3.2.13
Start is set above this level
(unscaled signal). Startstop logic is reversed if <
P3.2.12
6
Page 77
Parametersvacon • 74
6.1.4Group 3.3: References
6.1.4.1Frequency reference
The requency reference source is programmable for all control places except PC, which always takes the reference from the PC tool.
Remote control place (I/O A): The source of frequency reference can be selected with parameter P3.3.1.5.
Remote control place (I/O B): The source of frequency reference can be selected with parameter P3.3.1.6.
Local control place (Keypad): If the default selection for parameter P3.3.1.7 is used the reference set with parameter P3.3.1.8 applies.
Remote control place (Fieldbus): The frequency reference comes from fieldbus if the default
value for parameter P3.3.1.10 is kept.
Table 51. Frequency reference parameters
CodeParameterMinMaxUnitDefaultIDDescription
P3.3.1.1MinFreqReference0.00P3.3.1.2Hz0.00101
P3.3.1.2MaxFreqReferenceP3.3.1.1320.00Hz50.00102
P3.3.1.3PosFreqRefLimit-320.0320.0Hz320.001285
P3.3.1.4NegFreqRefLimit-320.0320.0Hz-320.00 1286
P3.3.1.5I/O A Ref sel195117
P3.3.1.6I/O B Ref sel199131
Minimum allowed frequency
reference
Maximum allowed frequency
reference
Final frequency reference
limit for positive direction.
Final frequency reference
limit for negative direction.
NOTE: This parameter can
be used e.g. to prevent motor
from running in reverse
direction.
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
Selection of ref source when
control place is I/O B. See
above.
NOTE: I/O B control place can
only be forced active with digital input (P3.5.1.7).
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 78
vacon • 75Parameters
Table 51. Frequency reference parameters
CodeParameterMinMaxUnitDefaultIDDescription
Selection of ref source when
control place is keypad:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
P3.3.1.7Keypad Ref Sel192121
P3.3.1.8Keypad Reference0.00P3.3.1.2Hz0.00184
P3.3.1.9Keypad Direction010123
P3.3.1.10Fieldbus Ref Sel193122
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
The frequency reference can
be adjusted on the keypad
with this parameter.
Motor rotation when control
place is keypad
0 = Forward
1 = Reverse
Selection of ref source when
control place is Fieldbus:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
6
Page 79
Parametersvacon • 76
6.1.4.2Group 3.3.3: Preset Freqs
Table 52. Preset frequencies parameters
CodeParameterMinMaxUnitDefaultIDDescription
0 = Binary coded
1 = Number of inputs. Preset
P3.3.3.1PresetFreqMode010182
P3.3.3.2Preset Freq 0P3.3.1.1P3.3.1.2Hz5.00180
P3.3.3.3Preset Freq 1P3.3.1.1P3.3.1.2Hz10.00105
P3.3.3.4Preset Freq 2P3.3.1.1P3.3.1.2Hz15.00106
P3.3.3.5Preset Freq 3P3.3.1.1P3.3.1.2Hz20.00126
P3.3.3.6Preset Freq 4P3.3.1.1P3.3.1.2Hz25.00127
P3.3.3.7Preset Freq 5P3.3.1.1P3.3.1.2Hz30.00128
P3.3.3.8Preset Freq 6P3.3.1.1P3.3.1.2Hz40.00129
P3.3.3.9Preset Freq 7P3.3.1.1P3.3.1.2Hz50.00130
P3.3.3.10Preset Freq Sel0
P3.3.3.11Preset Freq Sel1
P3.3.3.12Preset Freq Sel2
DigIN
SlotA.4
DigIN
SlotA.5
DigIN
Slot0.1
frequency is selected according
to how many of preset speed
digital inputs are active
Basic preset frequency 0 when
selected by Control reference
parameter (P3.3.1.5).
Select with digital input:
Preset frequency selection 0
(P3.3.3.10)
Select with digital input:
Preset frequency selection 1
(P3.3.3.11)
Select with digital inputs: Preset
frequency selection 0 & 1
Select with digital input:
Preset frequency selection 2
(P3.3.3.12)
Select with digital inputs: Preset
frequency selection 0 & 2
Select with digital inputs: Preset
frequency selection 1 & 2
Select with digital inputs: Preset
frequency selection 0 & 1 & 2
Binary selector for Preset
419
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
Binary selector for Preset
420
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
Binary selector for Preset
421
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 80
vacon • 77Parameters
6.1.4.3Group 3.3.4: Motor Potentiom
With a motor potentiometer function, the user can increase and decrease the output frequency. By connecting a digital input to parameter P3.3.4.1 (
MotPot UP) and having the digital input
signal active, the output frequency will rise as long as the signal is active. The parameter
P3.3.4.2 (
MotPot DOWN) works vice versa, decreasing the output frequency.
The rate how the output frequency either rises or falls when Motor Potentiometer Up or Down
is activated is determined by the
Motor potentiometer ramp time (P3.3.4.3)
The Motor potentiometer reset parameter (P3.3.4.4) is used to choose whether to reset (set to
MinFreq) the Motor Potentiometer frequency reference when stopped or when powered down.
Motor potentiometer frequency reference is available in all control places in menu Group 3.3:
References. The motor potentiometer reference can be changed only when the drive is in run
state.
Table 53. Motor potentiometer parameters
CodeParameterMinMaxUnitDefaultIDDescription
FALSE = Not active
P3.3.4.1MotPot UP
P3.3.4.2MotPot DOWN
P3.3.4.3MotPot Ramp Time0.1500.0Hz/s10.0331
P3.3.4.4MotPot Reset021367
DigIN
Slot0.1
DigIN
Slot0.1
TRUE = Active (Motor poten-
418
tiometer reference
INCREASES until the contact
is opened)
FALSE = Not active
TRUE = Active (Motor poten-
417
tiometer reference
DECREASES until the contact
is opened)
Rate of change in the motor
potentiometer reference
when increased or decreased
with parameters P3.3.4.1 or
P3.3.4.2.
Motor potentiometer frequency reference reset logic.
0 = No reset
1 = Reset if stopped
2 = Reset if powered down
6
Page 81
Parametersvacon • 78
6.1.5Group 3.4: Ramps And Brakes
6.1.5.1Group 3.4.1: Ramp 1
Table 54. Ramp 1 setup
CodeParameterMinMaxUnitDefaultIDDescription
Defines the time required for
P3.4.1.2Accel Time 10.13000.0s5.0103
P3.4.1.3Decel Time 10.13000.0s5.0104
P3.4.1.4
Start Acceleration
Time
0.13000.0s2.0502Time from 0 to min frequency
6.1.5.2Group 3.4.3: Start Magnetizat
Table 55. Start magnetization parameters
the output frequency to
increase from zero frequency
to maximum frequency
Defines the time required for
the output frequency to
decrease from maximum frequency to zero frequency
CodeParameterMinMaxUnitDefaultIDDescription
Defines the DC current fed
P3.4.3.1StartMagnCurrent0.00VariesAVaries517
P3.4.3.2StartMagnTime0,00600,00s0,00516
into motor at start. Disabled
if set to 0.
This parameter defines the
time for how long DC current
is fed to motor before acceleration starts.
6.1.5.3Group 3.4.3: DC brake
Table 56. DC-brake parameters
CodeParameterMinMaxUnitDefaultIDDescription
Defines the current injected
P3.4.4.1DC Brake CurrentVariesVariesAVaries507
P3.4.4.2DC BrakeTime0,00600,00s0,00508
P3.4.4.3DC Start Freq0,1010,00Hz1,50515
into the motor during DCbraking.
0 = Disabled
Determines if braking is ON
or OFF and the braking time
of the DC-brake when the
motor is stopping.
The output frequency at
which the DC-braking is
applied.
6.1.5.4Group 3.4.5: Flux Braking
Table 57. Flux braking parameters
CodeParameterMinMaxUnitDefaultIDDescription
P3.4.5.1Flux Braking010520
P3.4.5.2Braking Current0VariesAVaries519
Service support: find your nearest Vacon service center at www.vacon.com
0=Disabled
1=Enabled
Defines the current level for
flux braking.
6
Page 82
vacon • 79Parameters
6.1.6Group 3.5: I/O Config
6.1.6.1Default assignments of programmable inputs
Table 58 below presents the default assignments of programmable digital and analogue inputs
in Vacon 100 X Solar Pump application.
Table 58. Default assignments of inputs
InputTer mina l( s)ReferenceAssigned functionParameter code
DI18A.1Ctrl signal 1 AP3.5.1.1
DI29A.2Ctrl signal 2 AP3.5.1.2
DI310A.3External fault closeP3.5.1.11
DI414A.4Preset frequency selection 0 P3.5.1.21
DI515A.5Preset frequency selection 1 P3.5.1.22
DI616A.6External fault closeP3.5.1.13
AI12/3A.1AI1 signal selectionP3.5.2.1.1
AI24/5A.2AI2 signal selectionP3.5.2.2.1
6.1.6.2Group 3.5.1: Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the required digital input terminal (see chapter 4). The digital inputs are represented as, for example,
DigIN Slot A.2, meaning the second input on slot A.
It is also possible to connect the digital inputs to time channels which are also represented as
terminals.
NOTE! The statuses of digital inputs and the digital output can be monitored in the Multimonitoring view.
Table 59. Digital input settings
CodeParameterDefaultIDDescription
P3.5.1.1Ctrl signal 1 ADigIN SlotA.1403 Ctrl signal 1 when control place is I/O A (FWD)
P3.5.1.2Ctrl signal 2 ADigIN SlotA.2404 Ctrl signal 2 when control place is I/O A (REV)
P3.5.1.4Ctrl signal 1 BDigIN Slot0.1423 Start signal 1 when control place is I/O B
P3.5.1.5Ctrl signal 2 BDigIN Slot0.1424 Start signal 2 when control place is I/O B
P3.5.1.7I/O B Ctrl ForceDigIN Slot0.1425TRUE = Force the control place to I/O B
P3.5.1.8I/O B Ref ForceDigIN Slot0.1343
P3.5.1.9Fieldbus Ctrl ForceDigIN Slot0.1411Force control to fieldbus
P3.5.1.10Keypad Ctrl ForceDigIN Slot0.1410 Force control to keypad
P3.5.1.11Ext Fault CloseDigIN SlotA.3405
P3.5.1.12Ext Fault OpenDigIN Slot0.2406
P3.5.1.13Fault Reset CloseDigIN SlotA.6414 Resets all active faults when TRUE
P3.5.1.14Fault Reset OpenDigIN Slot0.1213Resets all active faults when FALSE
TRUE = Used frequency reference is specified
by I/O reference B parameter (P3.3.1.6).
FALSE = OK
TRUE = External fault
FALSE = External fault
TRUE = OK
6
Page 83
Parametersvacon • 80
Table 59. Digital input settings
CodeParameterDefaultIDDescription
P3.5.1.15Run EnableDigIN Slot0.2407Must be on to set drive in Ready state
P3.5.1.16Run Interlock 1DigIN Slot0.21041
P3.5.1.17Run Interlock 2DigIN Slot0.21042 As above.
P3.5.1.21Preset Freq Sel0DigIN SlotA.4419
P3.5.1.22Preset Freq Sel1DigIN SlotA.5420
P3.5.1.23Preset Freq Sel2DigIN Slot0.1421
P3.5.1.24MotPot UPDigIN Slot0.1418
P3.5.1.25MotPot DOWNDigIN Slot0.1417
P3.5.1.27Timer 1DigIN Slot0.1447
P3.5.1.28Timer 2DigIN Slot0.1448 See above
P3.5.1.29Timer 3DigIN Slot0.1449 See above
P3.5.1.30PID SP BoostDigIN Slot0.1 1046
P3.5.1.31PID SP SelectionDigIN Slot0.1 1047
P3.5.1.32ExtPID StartSignalDigIN Slot0.21049
P3.5.1.33ExtPID SP SelectDigIN Slot0.11048
P3.5.1.40MainCounter1ResetDigIN Slot0.1490
P3.5.1.48AutoClean Activ.DigIN Slot0.11715
Drive may be ready but start is blocked as long
as interlock is on (Damper interlock).
Binary selector for Preset speeds (0-7). See
page 76.
Binary selector for Preset speeds (0-7). See
page 76.
Binary selector for Preset speeds (0-7). See
page 76.
FALSE = Not active
TRUE = Active (Motor potentiometer reference
INCREASES until the contact is opened)
FALSE = Not active
TRUE = Active (Motor potentiometer reference
DECREASES until the contact is opened)
Rising edge starts Timer 1 programmed in
Group 3.12: Timer functions parameter group
FALSE = No boost
TRUE = Boost
FALSE = Setpoint 1
TRUE = Setpoint 2
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect if the external PID-controller is not enabled in Group 3.14:
ExtPID Controller.
FALSE = Setpoint 1
TRUE = Setpoint 2
Reset the counter from digital input.
TRUE = Reset
Start the Auto-cleaning sequence.
The sequence will be aborted if activation signal is removed before the sequence has been
completed.
NOTE! The drive will start if the input is acti-
vated!
Parameter set 1/2 selection.
P3.5.1.49Param. Set 1/2 Sel.DigIN Slot0.1496
P3.5.1.50User Defined Fault 1DigIN Slot0.1
P3.5.1.51User Defined Fault 2DigIN Slot0.1
P3.5.1.52Energy Counter resetDigIN Slot0.11933 Energy Counter reset
P3.5.1.53Mains supply onDigIN Slot0.11934 Mains supply on
Open= Parameter Set 1
Closed= Parameter Set 2
Digital input selection for activating User
1552
Defined Fault (1 or 2).
3
Open= No operation
Closed= Fault Activated
Digital input selection for activating User
1552
Defined Fault (1 or 2).
4
Open= No operation
Closed= Fault Activated
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 84
vacon • 81Parameters
6.1.6.3Group 3.5.2: Analog inputs
NOTE! The number of usable analogue inputs depends on your (option) board setup. The standard I/O board embodies 2 analogue inputs.
Group 3.5.2.1: Analog Input 1
Table 60. Analogue input 1 settings
CodeParameterMinMaxUnitDefaultIDDescription
Connect the AI1 signal to the
P3.5.2.1.1AI1 signal selection
P3.5.2.1.2AI1 signal filter time0.00300.00s0.1378
P3.5.2.1.3AI1 signal range010379
P3.5.2.1.4AI1 custom. min-160.00160.00%0.00380
P3.5.2.1.5AI1 custom. max-160.00160.00%100.00381Custom range max setting
P3.5.2.1.6AI1 signal inversion010387
AnIN
SlotA.1
analogue input of your choice
377
with this parameter.
Programmable. See page 67.
Filter time for analogue
input.
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
Custom range min setting
20% = 4-20 mA/2-10 V
0 = Normal
1 = Signal inverted
Group 3.5.2.2: Analog Input 2
Table 61. Analogue input 2 settings
CodeParameterMinMaxUnitDefaultIDDescription
P3.5.2.2.1AI2 signal selection
P3.5.2.2.2AI2 signal filter time0.00300.00s0.1389See P3.5.2.1.2.
P3.5.2.6.6AI6 signal inversion010209See P3.5.2.1.6.
AnIN
SlotE.2
199See P3.5.2.1.1.
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 86
vacon • 83Parameters
6.1.6.4Group 3.5.3: Digital outputs
Group 3.5.3.2: Slot B Basic
Table 66. Digital output settings on standard I/O board
CodeParameterMinMaxUnitDefaultIDDescription
Function selection for Basic
R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator active
10 = Start signal active
11 = Keypad control active
12 = I/O B control activated
13 = Limit supervision 1
14 = Limit supervision 2
15 = No fucntion
16 = No fucntion
17 = Preset speed active
18 = No fucntion
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID supervision limits
P3.5.3.2.1 RO1 function0592
M3.5.3.2.2Basic R01 ON delay0.00320.00s0.00
M3.5.3.2.3Basic R01 OFF delay0.00320.00s0.00
M3.5.3.2.4Basic R02 function0593
1100
22 = Ext. PID superv. limits
1
23 = Input press. alarm/fault
24 = Frost prot. alarm/fault
25 - 30 = No fucntion
31 = RTC time chnl 1 control
32 = RTC time chnl 2 control
33 = RTC time chnl 3 control
34 = FB ControlWord B13
35 = FB ControlWord B14
36 = FB ControlWord B15
37 = FB ProcessData1.B0
38 = FB ProcessData1.B1
39 = FB ProcessData1.B2
40 = Maintenance alarm
41 = Maintenance fault
42 = No fucntion
43 = No fucntion
54 -55 = No function
56 = Auto-cleaning
active
57 = Motor Switch
Open
58 = TEST (Always
Closed)
59 = No function
1100
ON delay for relay
2
1100
OFF delay for relay
3
1100
See P3.5.3.2.1
4
6
Page 87
Parametersvacon • 84
Table 66. Digital output settings on standard I/O board
CodeParameterMinMaxUnitDefaultIDDescription
M3.5.3.2.5Basic R02 ON delay0.00320.00s0.00
M3.5.3.2.6Basic R02 OFF delay0.00320.00s0.00
1100
See M3.5.3.2.2.
5
1100
See M3.5.3.2.3.
6
6.1.6.5Expander slots D and E digital outputs
Shows only parameters for existing outputs on option boards placed in slots D and E. Selections as in Standard RO1 (P3.5.3.2.1).
This group or these parameters are not visible if no digital outputs exist in slots D or E.
6.1.6.6Group 3.5.4: Analogue outputs
Group 3.5.4.1: Slot A Basic
Table 67. Standard I/O board analogue output settings
Filtering time of analogue output signal. See P3.5.2.1.2
0 = No filtering
0 = 0 mA / 0V
1 = 4 mA / 2V
Signal type (current/voltage)
selected with dip switches.
Note the difference in analogue output scaling in parameter P3.5.4.1.4.
See also parameter P3.5.2.1.3.
Min scale in process unit
(depends on selection of AO1
function).
Max scale in process unit
(depends on selection of AO1
function)
nMotor
nMotor
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 88
vacon • 85Parameters
6.1.6.7Expander slots D to E analogue outputs
Shows only parameters for existing outputs on option boards placed in slots D and E. Selections as in Standard AO1 (P3.5.4.1.1).
This group or these parameters are not visible if no digital outputs exist in slots D or E.
6.1.7Group 3.6: Fieldbus DataMap
Table 68. Fieldbus data mapping
CodeParameterMinMaxUnitDefaultIDDescription
Data sent to fieldbus can be
chosen with parameter and
monitor value ID numbers.
P3.6.1FB DataOut 1 Sel0350001852
P3.6.2FB DataOut 2 Sel0350002853
P3.6.3FB DataOut 3 Sel0350003854
P3.6.4FB DataOut 4 Sel0350004855
P3.6.5FB DataOut 5 Sel0350005856
P3.6.6FB DataOut 6 Sel0350006857
P3.6.7FB DataOut 7 Sel0350007858
P3.6.8FB DataOut 8 Sel03500037859
The data is scaled to unsigned
16-bit format according to the
format on keypad. E.g. 25.5 on
keypad equals 255.
Select Process Data Out with
parameter ID
Select Process Data Out with
parameter ID
Select Process Data Out with
parameter ID
Select Process Data Out with
parameter ID
Select Process Data Out with
parameter ID
Select Process Data Out with
parameter ID
Select Process Data Out with
parameter ID
Fieldbus process data out
Default values for Process Data Out to monitor through fieldbus are listed in Table 69.
Table 69. Fieldbus Process Data Out
DataValueScale
Process Data Out 1 Output frequency0.01 Hz
Process Data Out 2 Motor speed1 rpm
Process Data Out 3 Motor current0.1 A
Process Data Out 4 Motor torque0.1 %
Process Data Out 5 Motor power0.1 %
Process Data Out 6 Motor voltage0.1 V
Process Data Out 7 DC-link voltage1 V
Process Data Out 8 Last active fault code1
Example: Value ‘2500’ for
Output Frequency corresponds to ‘25.00 Hz’ (scaling value is 0.01).
All monitoring values listed in chapter 5 are given the scaling value.
6
Page 89
Parametersvacon • 86
6.1.8Group 3.7: Prohibit Freq
In some systems it may be necessary to avoid certain frequencies due to mechanical resonance problems. By setting up prohibit frequencies it is possible to skip these ranges. When
the (input) frequency reference is increased, the internal frequency reference is kept at the low
limit until the (input) reference is above the high limit.
Table 70. Prohibit frequencies
CodeParameterMinMaxUnitDefaultIDDescription
P3.7.1Range 1 Low Lim-1,00320,00Hz0,005090 = Not used
P3.7.2Range 1 High Lim0,00320,00Hz0,005100 = Not used
P3.7.3Range 2 Low Lim0,00320,00Hz0,005110 = Not used
P3.7.4Range 2 High Lim0,00320,00Hz0,005120 = Not used
P3.7.5Range 3 Low Lim0,00320,00Hz0,005130 = Not used
P3.7.6Range 3 High Lim0,00320,00Hz0,005140 = Not used
Multiplier of the currently
P3.7.7Ramp TimeFactor0,110,0Times1,0518
selected ramp time between
prohibit frequency limits.
6.1.9Group 3.8: Supervisions
Choose here:
1.one or two (P3.8.1/P3.8.5) signal values for supervision.
2.whether the low or high limits are supervised (P3.8.2/P3.8.6)
3.the actual limit values (P3.8.3/P3.8.7).
4.the hystereses for the set limit values (P3.8.4/P3.8.8).
Table 71. Supervision settings
CodeParameterMinMaxUnitDefaultIDDescription
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
4 = Motor power
0 = Fault stored in history
1 = Fault not stored in history
0 = No action
1 = Alarm
2 = Alarm, PresetFreq
3 = Fault (Stop according to
stop mode)
4 = Fault (Stop by coasting)
This frequency used when
fault response (in Group 3.9:
Protections) is Alarm+preset
frequency
Defines drive operation when
STO function has been activated (eg. Emergency stop
button has been pressed).
6
Page 91
Parametersvacon • 88
13006.emf
13006.emf
6.1.10.2Group 3.9.2: Motor Therm Prot
The motor thermal protection is to protect the motor from overheating. The AC drive is capable
of supplying higher than nominal current to the motor. If the load requires this high current
there is a risk that the motor will be thermally overloaded. This is the case especially at low
frequencies. At low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of
the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the load current above which the motor is overloaded. This current limit is a function of
the output frequency.
The thermal stage of the motor can be monitored on the control keypad display. See chapter
6.1.
NOTE! If you use long motor cables (max. 100m) together with small drives (≤1.5
kW) the motor current measured by the drive can be much higher than the actual
motor current due to capacitive currents in the motor cable. Consider this when
setting up the motor thermal protection functions.
CAUTION! The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill. The model starts from zero if the
control board is powered off.
Table 73. Motor thermal protection settings
CodeParameterMinMaxUnitDefaultIDDescription
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
P3.9.2.1Motor Therm Prot032704
P3.9.2.2MotAmbient Temp -20.0100.0°C40.0705Ambient temperature in °C
P3.9.2.3ZeroSpeedCooling5.0150.0%Varies706
P3.9.2.4ThermTimeConst1200minVaries707
P3.9.2.5MotThermLoadbil10150%100708
3 = Fault (Stop by coasting)
If available, use the motor
thermistor to protect the
motor. Choose then value 0
for this parameter.
Defines the cooling factor at
zero speed in relation to the
point where the motor is running at nominal speed without external cooling.
The time constant is the time
within which the calculated
thermal stage has reached
63% of its final value.
Motor thermal Loadability
states how much the motor
can be thermally loaded. E.g.
90% means that the motor
temperature will settle
around 100% when continuosly running at 90% of nominal load.
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 92
vacon • 89Parameters
13006.emf
6.1.10.3Group 3.9.3: Motor Stall
The motor stall protection protects the motor from short time overload situations such as one
caused by a stalled shaft. The reaction time of the stall protection can be set shorter than that
of motor thermal protection. The stall state is defined with two parameters, P3.9.3.2 (
rent
) and P3.9.3.4 (Stall Freq. Limit). If the current is higher than the set limit and the output
Stall Cur-
frequency is lower than the set limit the stall state is true. There is actually no real indication
of the shaft rotation. Stall protection is a type of overcurrent protection.
NOTE! If you use long motor cables (max. 100m) together with small drives (≤1.5
kW) the motor current measured by the drive can be much higher than the actual
motor current due to capacitive currents in the motor cable. Consider this when
setting up the stall protection functions.
Table 74. Motor stall protection settings
CodeParameterMinMaxUnitDefaultIDDescription
0 = No action
1 = Alarm
P3.9.3.1MotorStall Flt030709
P3.9.3.2Stall Current0.005.2A
P3.9.3.3Stall Time Limit1.00120.00s15.00711
P3.9.3.4Stall Freq. Limit1.00P3.3.1.2Hz25.00712
3.7
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
For a stall stage to occur, the
710
current must have exceeded
this limit.
This is the maximum time
allowed for a stall stage.
For a stall state to occur, the
output frequency must have
remained below this limit for
a certain time.
6
Page 93
Parametersvacon • 90
13006.emf
6.1.10.4Group 3.9.4: Motor Underload
The purpose of the motor underload protection is to ensure that there is load on the motor
when the drive is running. If the motor loses its load there might be a problem in the process,
e.g. a broken belt or a dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters
P3.9.4.2 (
load
Underload protection: Field weakening area load) and P3.9.4.3 (Zero frequency
). The underload curve is a squared curve set between the zero frequency and the field
weakening point. The protection is not active below 5Hz (the underload time counter is
stopped).
The torque values for setting the underload curve are set in percentage which refers to the
nominal torque of the motor. The motor's name plate data, parameter motor nominal current
and the drive's nominal current IH are used to find the scaling ratio for the internal torque value. If other than nominal motor is used with the drive, the accuracy of the torque calculation
decreases.
NOTE! If you use long motor cables (max. 100m) together with small drives (≤1.5
kW) the motor current measured by the drive can be much higher than the actual
motor current due to capacitive currents in the motor cable. Consider this when
setting up the motor underload protection functions.
Table 75. Motor underload protection settings
CodeParameterMinMaxUnitDefaultIDDescription
0 = No action
1 = Alarm
P3.9.4.1Underload Flt030713
P3.9.4.2Fieldweak. Load10.0150.0%50.0714
P3.9.4.3Zero Freq. Load5.0150.0%10.0715
P3.9.4.4 Time Limit2.00600.00s20.00716
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
This parameter gives the
value for the minimum
torque allowed when the output frequency is above the
field weakening point.
This parameter gives value
for the minimum torque
allowed with zero frequency.
If you change the value of
parameter P3.1.1.4 this
parameter is automatically
restored to the default value.
This is the maximum time
allowed for an underload
state to exist.
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 94
vacon • 91Parameters
6.1.10.5Group 3.9.6: Temperature input fault 1
NOTE! This parameter group is visible only with an option board for temperature measurement (OPT-BH) installed.
Table 76. Temperature input fault 1 settings
CodeParameterMinMaxUnitDefaultIDDescription
Selection of signals to use for
alarm and fault triggering.
B0 = Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
P3.9.6.1Temperature signal 10630739
B5 = Temperature Signal 6
Max value is taken of the
chosen signals and used for
alarm/fault triggering.
NOTE! Only 6 first tempera-
ture inputs are supported
(counting boards from slot A
to slot E).
Temperature limit for trig-
P3.9.6.2Alarm limit 1-30.0200.0°C120.0741
P3.9.6.3Fault limit 1-30.0200.0°C120.0742
P3.9.6.4Fault limit response 1032740
ging alarm.
inputs chosen with parameter P3.9.6.1 are compared.
Temperature limit for trigging alarm.
inputs chosen with parame-
ter P3.9.6.1 are compared.
0 = No response
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
NOTE! Only
NOTE! Only
6
Page 95
Parametersvacon • 92
6.1.10.6Group 3.9.6: Temperature input fault 2
NOTE! This parameter group is visible only with an option board for temperature measurement (OPT-BH) installed.
Table 77. Temperature input fault 2 settings
CodeParameterMinMaxUnitDefaultIDDescription
Selection of signals to use for
alarm and fault triggering.
B0 = Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
P3.9.6.5Temperature signal 20630763
B5 = Temperature Signal 6
Max value is taken of the
chosen signals and used for
alarm/fault triggering.
NOTE! Only 6 first tempera-
ture inputs are supported
(counting boards from slot A
to slot E).
Temperature limit for trig-
P3.9.6.6Alarm limit 2-30.0200.0°C120.0764
P3.9.6.7Fault limit 2-30.0200.0°C120.0765
P3.9.6.8Fault limit response 2032766
ging alarm.
inputs chosen with parameter P3.9.6.5 are compared.
Temperature limit for trigging alarm.
inputs chosen with parame-
ter P3.9.6.5 are compared.
0 = No response
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
NOTE! Only
NOTE! Only
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 96
vacon • 93Parameters
6.1.10.7Group 3.9.8: AI Low Protection
Table 78. AI Low Protection settings
CodeParameterMinMaxUnitDefaultIDDescription
This parameter defines if the
AI Low protection is enabled
or disabled.
P3.9.8.1AI Low Protection022767
P3.9.8.2AI Low Fault050700
0 = Disabled
1 = Enabled in Run State
2 = Enabled in Run&Stop
States
Response when an analogue
signal in use goes below 50%
of the minimum signal range.
0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to
stop mode)
5 = Fault (Stop by coasting)
6.1.10.8Group 3.9.9: User Defined Fault 1
Table 79. User Defined Fault 1 settings
CodeParameterMinMaxUnitDefaultIDDescription
DigIN
P3.9.9.1User Defined Fault 1
P3.9.9.2UserDef. Fault1 Resp.033
Slot0.1
Digital input selection for
1552
activating User Defined Fault
3
(1 or 2)
0 = No action
1 = Alarm
1552
2 = Fault (Stop according to
5
stop mode)
3 = Fault (Stop by coasting)
6.1.10.9Group 3.9.10: User Defined Fault 2
Table 80. User Defined Fault 2 settings
CodeParameterMinMaxUnitDefaultIDDescription
DigIN
P3.9.10.1User Defined Fault 2
P3.9.10.2 UserDef. Fault2 Resp.033
Slot0.1
Digital input selection for
1552
activating User Defined Fault
4
(1 or 2)
0 = No action
1 = Alarm
1552
2 = Fault (Stop according to
6
stop mode)
3 = Fault (Stop by coasting)
6
Page 97
Parametersvacon • 94
6.1.11Group 3.10: Automatic reset
Table 81. Autoreset settings
CodeParameterMinMaxUnitDefaultIDDescription
P3.10.1Automatic reset010731
P3.10.2Wait time0.1010.0m1.0717
P3.10.3Automatic reset tries1105759
P3.10.4Restart Function011719
P3.10.5
P3.10.6
P3.10.7
P3.10.8Underload Tries T1,T211021930
Underload reset Time
1
Underload reset Time
2
Underload reset Time
3
0.11200.0m2.01927
0.11200.0m30.01928
0.11200.0m300.01929
0 = Disabled
1 = Enabled
Wait time before the first
reset is executed.
NOTE: Total number of trials
(irrespective of fault type)
We can choose what kind of
start function we want to use
when doing an autorest of the
drive.
0 = Flying start
1 = Start Function
6.1.12Group 3.11: Appl. Settings
Table 82. Application Settings
CodeParameterMinMaxUnitDefaultIDDescription
P3.11.1Parameter Password0999901806
P3.11.2C/F selection0101197
P3.11.3kW/hp selection0101198
P3.11.4Multimonitor View0211196
P3.11.5FunctButtonConfig015151195
0 = Celsius
1 = Fahrenheit
0 = kW
1 = hp
Division of keypad display
into sections in Multimonitor view.
0 = 2x2 sections
1 = 3x2 sections
2 = 3x3 sections
With this parameter it’s
possible to configure what
alternatives are visible
when pressing the function
button.
Service support: find your nearest Vacon service center at www.vacon.com
6
Page 98
vacon • 95Parameters
P Assign ToChannel
Interval 1
Interval 2
Interval 3
Interval 4
Timer 1
Timer 2
Timer 3
Interval 5
TimeChannel 1
TimeChannel 2
TimeChannel 3
9146.emf
6.1.13Group 3.12: Timer functions
The time functions (Time Channels) in the Vacon 100 X give you the possibility to program functions to be controlled by the internal RTC (Real Time Clock). Practically every function that can
be controlled by a digital input can also be controlled by a Time Channel. Instead of having an
external PLC controlling a digital input you can program the "closed" and "opened" intervals
of the input internally.
NOTE! The functions of this parameter group can be made the fullest advantage of only if the
battery (option) has been installed and the Real Time Clock settings have been properly made
during the Startup Wizard (see page 6 and page 7). It is not recommended to use these function without battery backup because the drive’s time and date settings will be reset at every
power down if no battery for the RTC is installed.
Time channels
The on/off logic for the
them. One
Time channel can be controlled by many Intervals or Timers by assigning as many
of these as needed to the
Time channels is configured by assigning Intervals or/and Timers to
Time channel.
Figure 22. The intervals and timers can be assigned to time channels in a flexible way. Ev-
ery interval and timer has its own parameter for assigning to a time channel.
6
Intervals
Every interval is given an "ON Time" and "OFF Time" with parameters. This is the daily time
that the interval will be active during the days set with "From Day" and “To Day” parameters.
E.g. the parameter setting below means that the interval is active from 7 am to 9 am every
weekday (Monday to Friday). The Time Channel to which this Interval is assigned will be seen
as a closed "virtual digital input" during that period.
ON Time: 07:00:00
OFF Time: 09:00:00
From Day: Monday
To Day: Friday
Page 99
Parametersvacon • 96
Duration
Remaining
time
Activation
Time
OUT
9137.emf
Timers
Timers can be used to set a Time Channel active during a certain time by a command from a
digital input (or a Time Channel).
Figure 23. Activation signal comes from a digital input or " a virtual digital input" such as a
Time channel. The Timer counts down from falling edge.
The below parameters will set the Timer active when Digital Input 1 on Slot A is closed and
keep it active for 30s after it is opened.
Duration: 30s
Timer: DigIn SlotA.1
Tip: A duration of 0 seconds can be used for simply overriding a Time channel activated from
a digital input without any off delay after the falling edge.
EXAMPLE
Problem:
We have an AC drive for air conditioning in a warehouse. It needs to run between 7am - 5pm
on weekdays and 9am - 1pm on weekends. Additionally, we need to be able to manually force
the drive to run outside working hours if there are people in the building and to leave it running
for 30 min afterwards.
Solution:
We need to set up two intervals, one for weekdays and one for weekends. A Timer is also needed for activation outside the office hours. An example of configuration below.
Interval 1:
P3.12.1.1:
P3.12.1.2:
P3.12.1.3:
P3.12.1.4:
Service support: find your nearest Vacon service center at www.vacon.com
ON Time: 07:00:00
OFF Time: 17:00:00
Days: Monday, Tuesday, Wednesday, Thursday, Friday
Assign to channel: Time channel 1
6
Page 100
vacon • 97Parameters
OKOKOK
Interval 1DaysDays
Monday
Sunday
Tuesday
Wednesday
Thursday
Friday
ON Time
Days
Edit
Help
Add to favorites
STOPREADYI/OSTOPREADYI/OSTOPREADYI/O
ID:1466M3.12.1.3
07:00:00
17:00:00
0
ID:M3.12.1.3ID:M3.12.1.3.1
OFF Time
9158.emf
Interval 2:
P3.12.2.1:
P3.12.2.2:
P3.12.2.3:
ON Time: 09:00:00
OFF Time: 13:00:00
Days: Saturday,
Sunday
P3.12.2.4: AssignToChannel: Time channel 1
Timer 1
The manual bypassing can be handled by a digital input 1 on slot A (by a different switch or connection to lighting).
P3.12.6.1:
P3.12.6.3:
P3.12.6.2:
Duration: 1800s (30min)
Assign to channel: Time channel 1
Timer 1: DigIn SlotA.1 (Parameter located in digital inputs menu.)
Finally select the Channel 1 for the I/O Run command.
P3.5.1.1:
Control signal 1 A: Time Channel 1
Figure 24. Final configuration where Time channel 1 is used as control signal for start com-
mand instead of a digital input.
6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.