Vacon 100 x Installation And Maintenance Manual

Page 1
vacon®100 x
ac drives
Installation, Technical and Maintenance
Manual
Page 2
Page 3
Service support: find your nearest Vacon service center at www.vacon.com
INDEX
Document code (Original Instructions): DPD00534G
Order code: DOC-INS03985+DLUK
Rev. G
Revision release date: 11.7.14
1. Safety................................................................................................................2
1.1 Signs....................................................................................................................................2
1.2 Units ....................................................................................................................................2
1.3 Danger.................................................................................................................................3
1.4 Warnings .............................................................................................................................4
1.5 Earthing and earth fault protection ....................................................................................5
1.6 Insulation system................................................................................................................8
1.7 Compatibility with RCDs .....................................................................................................9
1.8 Extended temperature range .............................................................................................9
1.9 Electro-magnetic compatibility (EMC)................................................................................9
1.10 Declaration of conformity .................................................................................................10
2. Receipt of delivery ..........................................................................................14
2.1 Type designation code.......................................................................................................15
2.2 Unpacking and lifting the AC drive ...................................................................................16
2.3 Accessories .......................................................................................................................16
2.3.1 Frame MM4 .......................................................................................................................16
2.3.2 Frame MM5 .......................................................................................................................17
2.3.3 Frame MM6 .......................................................................................................................17
2.3.4 STO terminal connector....................................................................................................18
2.3.5 ‘Product modified’ sticker.................................................................................................18
2.3.6 Disposal.............................................................................................................................18
3. Mounting.........................................................................................................20
3.1 Dimensions .......................................................................................................................20
3.2 Introduction of modules....................................................................................................23
3.3 Mounting ...........................................................................................................................24
3.3.1 Wall-mounting ..................................................................................................................25
3.3.2 Motor-mounting................................................................................................................25
3.3.3 Segregated modules.........................................................................................................25
3.4 Cooling ..............................................................................................................................26
4. Power cabling .................................................................................................28
4.1 Circuit breaker ..................................................................................................................29
4.2 UL standards on cabling ...................................................................................................30
4.3 Description of the terminals .............................................................................................31
4.4 Cable dimensioning and selection....................................................................................34
4.4.1 Cable and fuse sizes, frames MM4 to MM6......................................................................34
4.4.2 Cable and fuse sizes, frames MM4 to MM6, North America............................................35
4.4.3 Brake resistor cables........................................................................................................36
4.4.4 Control cables ...................................................................................................................36
4.5 Cable installation ..............................................................................................................37
5. Control unit.....................................................................................................44
5.1 Control unit cabling...........................................................................................................45
5.1.1 Control cable sizing ..........................................................................................................45
5.1.2 Standard I/O terminals .....................................................................................................46
5.1.3 Relay and thermistor input terminals ..............................................................................47
5.1.4 Safe Torque off (STO) terminals .......................................................................................47
5.1.5 Selection of terminal functions with dip switches ...........................................................48
5.1.6 Isolating digital inputs from ground .................................................................................48
5.1.7 Bus termination of the RS485 connection........................................................................49
Page 4
vacon • 1
5.2 I/O cabling and Fieldbus connection ................................................................................50
5.2.1 Prepare for use through Ethernet....................................................................................50
5.2.2 Prepare for use through RS485........................................................................................51
5.2.3 RS485 cable data...............................................................................................................52
5.3 Battery installation for Real Time Clock (RTC) ................................................................53
6. Commissioning ...............................................................................................56
6.1 Commissioning of the drive ..............................................................................................57
6.2 Changing EMC protection class........................................................................................58
6.3 Running the motor ............................................................................................................60
6.3.1 Cable and motor insulation checks ..................................................................................60
6.4 Maintenance......................................................................................................................61
7. Technical data.................................................................................................62
7.1 AC drive power ratings......................................................................................................62
7.1.1 Mains voltage 3AC 208-240V.............................................................................................62
7.1.2 Mains voltage 3AC 380-480V.............................................................................................63
7.1.3 Definitions of overloadability ............................................................................................64
7.2 Brake resistor ratings.......................................................................................................65
7.3 VACON® 100 X - technical data........................................................................................66
7.3.1 Technical information on control connections.................................................................69
8. Options............................................................................................................72
8.1 Mains switch......................................................................................................................72
8.1.1 Installation ........................................................................................................................72
8.2 Control Keypad..................................................................................................................76
8.2.1 Mounting onto the drive ....................................................................................................76
8.2.2 Installation ........................................................................................................................77
8.2.3 Wall-mounting ..................................................................................................................79
8.2.4 Graphical and Text keypad................................................................................................81
8.2.5 VACON® keypad with graphical display...........................................................................82
8.2.6 VACON® keypad with text segment display.....................................................................89
8.2.7 Fault Tracing .....................................................................................................................93
8.3 Heater (arctic option) ......................................................................................................101
8.3.1 Safety...............................................................................................................................101
8.3.2 Dangers ...........................................................................................................................101
8.3.3 Technical data .................................................................................................................101
8.3.4 Mounting instructions: MM4 Example............................................................................102
8.4 Option boards..................................................................................................................105
8.5 Flange adapter ................................................................................................................106
8.5.1 Mounting instructions: MM4 Example............................................................................109
9. Safe Torque Off .............................................................................................112
9.1 General description.........................................................................................................112
9.2 Warnings .........................................................................................................................112
9.3 Standards ........................................................................................................................113
9.4 The principle of STO........................................................................................................114
9.4.1 Technical details .............................................................................................................115
9.5 Connections.....................................................................................................................116
9.5.1 Safety Capability Cat. 4 / PL e / SIL 3 .............................................................................117
9.5.2 Safety Capability Cat. 3 / PL e / SIL 3 .............................................................................119
9.5.3 Safety Capability Cat. 2 / PL d / SIL 2 .............................................................................119
9.5.4 Safety Capability Cat. 1 / PL c / SIL 1..............................................................................120
9.6 Commissioning ...............................................................................................................121
9.6.1 General wiring instructions ............................................................................................121
9.6.2 Checklist for commissioning ..........................................................................................121
9.7 Parameters and fault tracing .........................................................................................122
9.8 Maintenance and diagnostics .........................................................................................123
Page 5
Safety vacon • 2
Service support: find your nearest Vacon service center at www.vacon.com
1
1. SAFETY
This manual contains clearly marked warning information which is intended for your personal safe­ty and to avoid any unintentional damage to the product or connected appliances.
Please read the warning information carefully.
VACON
®
100 X is a drive designed to control asynchronous AC motors and permanent magnet motors. The product is intended to be installed in a restricted access location and for a general purpose use.
Only VACON
®
authorized, trained and qualified personnel are allowed to install, operate and
maintain the drive.
1.1 Signs
The cautions and warnings are marked as follows:
Table 1. Warning signs.
1.2 Units
The dimensions used in this manual conform to International Metric System units, otherwise known as SI (Système International d’Unités) units. For the purpose of the equipment's UL certification, some of these dimensions are accompanied by their imperial equivalents.
= DANGEROUS VOLTAGE!
= HOT SURFACE
= WARNING or CAUTION
Physical
dimension
SI value US value Conversion factor US designation
length 1 mm 0.0394 inch 25.4 inch
Weight 1 kg 2.205 lb 0.4536 pound
Speed
1 min
-1
1 rpm 1
revolution per minute
Temperature 1 °C (T1) 33.8 °F (T2) T2 = T1 x 9/5 + 32 Fahrenheit
Torque 1 Nm 8.851 lbf in 0.113
pound-force inches
Power 1 kW 1.341 HP 0.7457 horsepower
Table 2. Unit conversion table.
Page 6
1
vacon • 3 Safety
1.3 Danger
The components of the power unit of VACON® 100 X drives are live when the drive is con­nected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals (U, V, W), the brake resistor terminals and the DC-terminals are live when VACON® 100 X Drive is connected to the mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait until the indicators on the keypad go out (if no keypad is connected, see the indicators on the cover). Wait an additional 30 seconds
before doing any work on the connections of VACON
®
100 X Drive. Do not open the unit before this time has expired. After expiration of this time, use measuring equipment to absolutely ensure that no
voltage is present.
Always ensure absence of voltage before starting any elec-
trical work! The control I/O-terminals are isolated from the mains potential. However, the relay outputs
and other I/O-terminals may have a dangerous control voltage present even when VACON
®
100 X drive is disconnected from the mains.
Before connecting the AC drive to mains make sure that the powerhead of VACON
®
100 X
Drive is mounted firmly on the terminal box.
During a coast stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped and wait until the indicators on the keypad go out (if no keypad is connected, see the indicators on the cover). Wait an additional 30 seconds before starting any work on the drive.
Page 7
Safety vacon • 4
Service support: find your nearest Vacon service center at www.vacon.com
1
1.4 Warnings
VACON® 100 X AC drive is meant for fixed installations (on the motor or on the wall) only.
Only DVC A circuits (Decisive Voltage Class A, according to IEC 61800-5-1) are allowed to be connected to the control unit. This advice aims to protect both the drive
and the client-application. VACON
®
is not responsible for direct or consequential damages resulting from unsafe connections of external circuits to the drive. See para­graph 1.6 for more details.
Do not perform any measurements when the AC drive is connected to the mains.
The touch current of VACON
®
100 X AC drives exceeds 3.5mA AC. According to stan­dard EN61800-5-1, a reinforced protective ground connection must be ensured. See paragraph 1.5 for more details.
If the AC drive is used as a part of a machine, the machine manufacturer is responsi- ble for providing the machine with a supply disconnecting device (EN 60204-1). See paragraph 4.1 for more details.
Only spare parts delivered by VACON
®
can be used.
At power-up or fault reset, the motor will start immediately if the start signal is active, unless the pulse control for
Start/Stop logic has been selected
) and the STO inputs are ready to be used (normal operation). The I/O functionalities (including start inputs) may change if parameters, applications or software are changed. Disconnect, there­fore, the motor if an unexpected start can cause danger. This is valid only if STO inputs are energized. For prevention on unexpected restart, use appropriate safety relay con­nected to the STO inputs.
The motor starts automatically after automatic fault reset if the autoreset function is activated. See the Application Manual for more detailed information. This is valid only if STO inputs are energized. For prevention on unexpected restart, use appropriate safety relay connected to the STO inputs.
Before performing any measurement on the motor or on the motor cable, discon­nect the motor cable from the AC drive.
Do not perform any voltage withstand test on any part of VACON
®
100 X. The tests shall be performed according to a specific procedure. Ignoring this procedure may damage the product.
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of your supply network. See paragraph 6.2 for more details.
In a domestic environment, this product may cause radio interference in which case supplementary mitigation measures may be required.
Page 8
1
vacon • 5 Safety
1.5 Earthing and earth fault protection
The VACON® 100 X AC drive must always be earthed with an earthing conductor connected to the earthing terminal marked with .
See Table 12 and Table 13 for the required cross-section of phase conductor and protective earth­ing conductor (both made of copper).
Since the touch current exceeds 3.5 mA AC, according to EN61800-5-1, the MM4 and MM5 shall have a fixed connection and provision of an additional terminal for a second protective earthing conductor of the same cross-sectional area as the original protective earthing conductor. MM6 shall have a fixed installation and a cross-section of the protective earthing conductor of at least 10 mm
2
Cu.
On the terminal-box, three screws (for MM4 and MM5) and two screws (for MM6)are provided for ORIGINAL and MOTOR protective earthing conductors: the customer can choose the screw for each one.
The cross-sectional area of every protective earthing conductor which does not form a part of the supply cable or cable enclosure shall, in any case, be not less than:
•2.5 mm
2
if mechanical protection is provided or
•4 mm
2
if mechanical protection is not provided. For cord-connected equipment, provisions shall be made so that the protective earthing conductor in the cord shall, in the case of fail­ure of the strain-relief mechanism, be the last conductor to be interrupted.
The power-head is earthed through metal aglets, located on the terminal-box, which fit into spring baskets on the powerhead. See Figure 1, Figure 2 and Figure 3 for the location of the screws (three for MM4 and MM5, two for MM6) and the metal aglets (one for MM4 and MM5, two for MM6). Please, pay attention not to damage or remove these aglets.
CAUTION!
Page 9
Safety vacon • 6
Service support: find your nearest Vacon service center at www.vacon.com
1
Figure 1. Earth connections and metal aglet in MM4.
Figure 2. Earth connections and metal aglet in MM5.
Earth connection
Metal aglet
Earth connection
Earth connection
Earth connections
Metal aglet
Earth connection
Page 10
1
vacon • 7 Safety
Figure 3. Earth connections and metal aglet in MM6.
However, always follow the local regulations for the minimum size of the protective earthing conductor.
NOTE: Due to the high capacitive currents present in the AC drive, fault current protective switches
may not function properly.
Earth connection Earth connection
Metal aglet
Metal aglet
Page 11
Safety vacon • 8
Service support: find your nearest Vacon service center at www.vacon.com
1
1.6 Insulation system
A distinction has to be made for the following three groups of terminals, according the insulation system of VACON
®
100 X:
Mains and motor connections (L1, L2, L3, U, V, W)
Relays (R01, R02)
(*)
Thermistor-input
Control terminals (I/Os, RS485, Ethernet, STO)
The Control terminals (I/Os, RS485, Ethernet, STO) are isolated from the Mains (the insulation is re­inforced, according to IEC 61800-5-1) and the GND terminals are referred to PE.
This is important when you need to connect other circuits to the drive and test the complete assem­bly. Should you have any doubt or question, please contact your local VACON
®
distributor.
Figure 4. Insulation system.
Please, consider carefully the insulation system depicted in Figure 4 before connect­ing any circuit to the unit.
(*)
The relays may be used also with DVC A circuits. This is possible only if both relays
are used with DVC A circuit: to mix Mains and DVC A is not allowed.
POWER UNIT
L1 L2 L3
U V
W
R01 __
R02 __
DC- DC+/R+ R-
10Vref __
Analog Inputs __
Digital Inputs__
Digital Outputs__
24V __
Ethernet __
RS485 _ _
STO __
___Thermistor
Keypad
CONTROL UNIT
Reinforced
Mains
Mains
DVC A
DVC A or Mains
(*)
Page 12
1
vacon • 9 Safety
1.7 Compatibility with RCDs
1.8 Extended temperature range
VACON® 100 X has an integrated cooling system, independent from the motor fan. Under maxi­mum operating conditions, the ambient temperature cannot exceed 40 °C. See Table 24 and Table 25 for the output rated current. Higher temperatures are allowed only with derating of the output current. With derating the unit can operate up to 60°C. See the Figure 5.
Figure 5. Temperature-output current derating curve.
NOTE: the maximum allowed switching frequency above 50°C is 1.5 kHz. The AC drive is cooled down by air-ventilation. Therefore, make sure that enough free space is left
around the AC drive to ensure sufficient air circulation (see for more details the mounting instruc­tions on chapter 3).
1.9 Electro-magnetic compatibility (EMC)
The VACON® 100 X complies with IEC 61000-3-12, provided that the short circuit power (SSC) is greater than or equal to 120 at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power SSC greater than or equal to 120.
This product can cause a d.c. current in the protective earthing conductor. Where a re­sidual current-operated protective (RCD) or monitoring (RCM) device is used for pro­tection in case of direct or indirect contact, only an RCD or RCM of Type B is allowed on the supply side of this product.
Ambient temperature (°C)
Percent rated output current (% I
N
)
10 20 30 40 50
100
75
50
25
0-10
150
60
Temperature - Output Current Derating Curve
Page 13
Safety vacon • 10
Service support: find your nearest Vacon service center at www.vacon.com
1
1.10 Declaration of conformity
Figure 6. Declaration of conformity.
Page 14
1
vacon • 11 Safety
Figure 7. STO certificate.
Page 15
Safety vacon • 12
Service support: find your nearest Vacon service center at www.vacon.com
1
NOTE! You can download the English and French product manuals with applicable safety, warn­ing and caution information from www.vacon.com/downloads.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l’ensemble des informations de sécurité, avertissements et mises en garde applica­bles sur le site www.vacon.com/downloads.
Page 16
1
vacon • 13 Safety
Page 17
Receipt of delivery vacon • 14
Service support: find your nearest Vacon service center at www.vacon.com
2
2. RECEIPT OF DELIVERY
Check the correctness of delivery by comparing your order data to the drive information found on the package label. If the delivery does not correspond to your order, contact the supplier immedi­ately. See chapter 2.3.
Figure 8. VACON® package label.
Marks:
3234500378
Cust. Ord. No:
Application:
FW0065V008
Firmware:
EMC level C2
380-480 V IP66 / Type 4X
31 A
Rated current:
122245
B.ID:
V0789012245
S/N:
223456789012345678901234567 29012345
20-AB3L00315A02B5H1MB1C-12345678
Code:
VACON0100-3L-0031-4-X
Type:
0022345628AC DRIVE
223456789012245
Vacon type code
Rated current
Supply voltage
Application code
IP class EMC level
Serial number
CUSTOMER NAME
Customer’s order number
Vacon order number
Batch ID
Page 18
2
vacon • 15 Receipt of delivery
2.1 Type designation code
VACON® type designation code is formed of a nine-segment code and optional +codes. Each seg­ment of the type designation code uniquely corresponds to the product and options you have or­dered. The code is of the following format:
VACON0100-3L-0061-4-X +xxxx +yyyy
VACON
This segment is common for all products.
0100
Product range: 0100 = VACON
®
100
3L
Input/Function: 3L = Three-phase input
0061
Drive rating in ampere; e.g. 0061 = 61 A See Table 24 and Table 25 for all the drive rat-
ings.
4
Supply voltage: 2 = 208-240 V
4 = 380-480 V
X
-IP66/ Type 4X
-EMC-level C2
-Two relay outputs
-One thermistor input
+xxxx +yyyy
Additional codes (Several options possible). Examples of additional codes: +HMGR Graphical keypad IP66 +F0065 HVAC Application installed +F0159 FLOW application installed +SRBT Integrated battery for real time clock +FBIE Onboard fieldbus protocols activated
Page 19
Receipt of delivery vacon • 16
Service support: find your nearest Vacon service center at www.vacon.com
2
2.2 Unpacking and lifting the AC drive
The weights of the AC drives vary according to frame size. You may need to use a piece of special lifting equipment to move the converter from its package. Note the weights of each individual frame size in Table 3 below.
Table 3. Frame weights.
VACON® 100 X drives have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of trans­port damage are to be found on the product and that the delivery is complete.
Should the drive have been damaged during shipping, please contact the cargo insurance company or the carrier in the first instance.
2.3 Accessories
After having opened the transport package and lifted the drive out, check immediately that these various accessories were included in the delivery. The contents of the accessories bag differ by drive size:
2.3.1 Frame MM4
Frame
Weight
[kg] [lb]
MM4 8.8 19.4 MM5 14.9 32.8 MM6 31.5 69.4
Item Quantity Purpose
STO terminal connector 1
Six pin black connector (see Figure 9) to use STO function
M4 x 12 DIN6900-3-Combi-Delta-Tx screw
10 Screws for control cable clamps
M1-3 Cable clamp 5 Clamping control cables
M4 x 12 DIN6900-3-Combi-Delta-Tx screw
6 Screws for power cable clamps
M25 Cable clamp 3 Clamping power cables
‘Product modified’ sticker 1 Information about modifications
HMI cap
*
*. Provided only if the drive is delivered with the keypad.
1 Closing cap for the HMI connector
Table 4. Content of accessory bag, MM4.
Page 20
2
vacon • 17 Receipt of delivery
2.3.2 Frame MM5
2.3.3 Frame MM6
Item Quantity Purpose
STO terminal connector 1
Six pin black connector (see Figure 9) to use STO function
M4 x 12 DIN6900-3-Combi-Delta-Tx screw
10 Screws for control cable clamps
M1-3 Cable clamp 5 Clamping control cables
M4 x 12 DIN6900-3-Combi-Delta-Tx screw
6 Screws for power cable clamps
M32 Cable clamp 3 Clamping power cables
‘Product modified’ sticker 1 Information about modifications
HMI cap
*
*. Provided only if the drive is delivered with the keypad.
1 Closing cap for the HMI connector
Table 5. Content of accessory bag, MM5.
Item Quantity Purpose
STO terminal connector 1
Six pin black connector (see Figure 9) to use STO function
M4 x 12 DIN6900-3-Combi-Delta-Tx screw
10 Screws for control cable clamps
M1-3 Cable clamp 5 Clamping control cables
M4 x 25 DIN6900-3-Combi-Delta-Tx screw
6 Screws for power cable clamps
M40 Cable clamp 3 Clamping power cables
‘Product modified’ sticker 1 Information about modifications
HMI cap
*
*. Provided only if the drive is delivered with the keypad mounted.
1 Closing cap for the HMI connector
Table 6. Content of accessory bag, MM6.
Page 21
Receipt of delivery vacon • 18
Service support: find your nearest Vacon service center at www.vacon.com
2
2.3.4 STO terminal connector
Figure 9. STO connector.
2.3.5 ‘Product modified’ sticker
In the small plastic bag included in the delivery you will find a silver
Product modified sticker. The
purpose of the sticker is to notify the service personnel about the modifications made in the AC drive. Attach the sticker on the side of the AC drive to avoid losing it. Should the AC drive be later modified mark the change on the sticker.
Figure 10. ‘Product modified’ sticker.
2.3.6 Disposal
When the device reaches the end of its operating life do not dispose of it as a part of standard household garbage. Main components of the product can be recycled, but some need to be fragmented to separate different types of materials and components that need to be treated as special waste from electrical and electronic components. To ensure environmentally sound and safe recycling treatment, the product can be taken to appropriate recycling center or returned to the manufacturer. Observe local and other applicable laws as they may mandate special treatment for specific components or special treatment may be ecologically sensible.
Product modified
Date:
Date:
Date:
13064.emf
Page 22
2
vacon • 19 Receipt of delivery
Page 23
Mounting vacon • 20
Service support: find your nearest Vacon service center at www.vacon.com
3
3. MOUNTING
VACON® 100 X is the ideal solution for a decentralised installation. It is conceived to be mounted on a wall or directly on the motor, saving space and reducing the cabling complexity. In both of the cas­es, it must be ensured that the mounting plane is even.
3.1 Dimensions
Figure 11. VACON® 100 X drive dimensions, MM4.
Frame
Dimensions W x H x D
[mm] [in]
MM4 190.7 x 315.3 x 196.4 7.51 x 12.41 x 7.73
MM4 +HMGR 190.7 x 315.3 x 213.8 7.51 x 12.41 x 8.42
315,3
190,7
187,8
213,8
293,0
296,5
5
,
9
143,5
196,4
Page 24
3
vacon • 21 Mounting
Figure 12. VACON® 100 X drive dimensions, MM5.
Frame
Dimensions W x H x D
[mm] [in]
MM5 232.6 x 367.4 x 213.5 9.16 x 14.46 x 8.41
MM5 +HMGR 232.6 x 367.4 x 230.8 9.16 x 14.46 x 9.08
367,4
203,7
230,8
180,0
345,2
349,2
6
,
1
232,6
213,5
Page 25
Mounting vacon • 22
Service support: find your nearest Vacon service center at www.vacon.com
3
Figure 13. VACON® 100 X drive dimensions, MM6.
Frame
Dimensions W x H x D
[mm] [in]
MM6 349.5 x 499.8 x 235.4 13.76 x 19.68 x 9.27
MM6 +HMGR 349.5 x 499.8 x 254.2 13.76 x 19.68 x 10.00
229,6
254,2
322,0
349,5
382,8
385,3
499,8
8
,
2
235,4
Page 26
3
vacon • 23 Mounting
3.2 Introduction of modules
The mechanical concept of VACON® 100 X drive is based on two segregated parts, power and con­trol, connected to each other by pluggable terminals. The power unit, called powerhead, includes all the power electronics such as the EMC-filter, IGBTs, capacitors, choke or power boards while the control board and the control terminals are located in the terminal box.
Figure 14. VACON® 100 X drive modules.
Powerhead
Terminal box
Page 27
Mounting vacon • 24
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3 Mounting
The drive consists of two main elements:
1. The terminal box that includes the power terminals and control board with the control terminals and
2. The powerhead containing all the power electronics.
To install the drive, both parts need to be separated. The terminal box must be fixed first and all cabling done. After this, the powerhead will be plugged on the terminal box and fixed with 4 (MM4 and MM6) or 6 (MM5) dedicated screws located on top side of the powerhead (see Figure 15.). In or­der to guarantee specified IP protection, recommended fastening torque is 2-3 Nm. The screws should be tightened crosswise.
Figure 15. Separation of modules(MM5 example).
Page 28
3
vacon • 25 Mounting
3.3.1 Wall-mounting
The drive can be mounted in vertical or horizontal position on the wall or any other relatively even mounting plane or machine frame and fixed with the screws recommended in Table 7.
Recommended screw or bolt size for MM4 is M5, for MM5 M6 and MM6 is M8.
3.3.2 Motor-mounting
The drive can also be mounted on a motor (on top or on any side of the motor). The drive is equipped with a cooling system independent of the motor. Motor-mounting requires special adapting com­ponents. Contact your local VACON
®
distributor for additional information.
3.3.3 Segregated modules
In order to ease replacements in case of failure, the power and the control sub-systems are en­closed in two segregated parts, connected together through pluggable terminals:
• Power-head: heat-sink enclosing all power electronics
• Terminal-box: block containing unit control and power terminals
Firstly, the terminal-box has to be fixed and the cabling has to be done. Secondly, the power-head has to be plugged and fixed to the terminal-box with dedicated screws (see Table 8). In order to pre­serve the specified IP protection class, the recommended fastening torque is 2-3 Nm.
Frame Screw number Screw size
MM4 4 M5 MM5 4 M6 MM6 4 M8
Table 7. Screws for wall mounting.
Frame Screw number Screw size
MM4 4 M5 MM5 6 M5 MM6 4 M6
Table 8. Screws for fixing the powerhead to the terminal box.
Page 29
Mounting vacon • 26
Service support: find your nearest Vacon service center at www.vacon.com
3
3.4 Cooling
The AC drive produces heat in operation and is cooled down by air circulated by a fan. The cooling concept is independent of the motor fan.
Enough free space shall be left around the AC drive to ensure sufficient air circulation and cooling. Different acts of maintenance may also require a certain amount of free space.
The minimum clearances given in Table 9 must not be exceeded. It is also important to ensure that the temperature of the cooling air does not exceed the maximum ambient temperature of the con­verter.
Contact local VACON
®
distributor for more information on required clearances in different instal-
lations.
Table 9. Min. clearances around AC drive.
A = Clearance left and right from the drive B = Clearance above the drive C = Clearance underneath the AC drive
Figure 16. Installation space.
Table 10. Required cooling air.
Should you need further details on the cooling system of the VACON® 100 X, please contact your local VACON
®
distributor.
Min clearance [mm]
Type A B C
All types 80 160 60
Type
Cooling air required
[m
3
/h]
MM4 140 MM5 140 MM6 280
B
C
AAA
Page 30
3
vacon • 27 Mounting
Page 31
Power cabling vacon • 28
Service support: find your nearest Vacon service center at www.vacon.com
4
4. POWER CABLING
The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals marked with U, V and W. See principal connection diagram in Figure 17. See also Table 11 for the cable recommendations for different EMC levels.
Figure 17. Principal connection diagram.
Use cables with heat resistance in accordance with the application requirements. The cables and the fuses must be dimensioned according to the AC drive nominal OUTPUT current which you can find on the rating plate.
Keypad
Control
U/T1
V/T2
W/T3
M
L1
L2
L3
Power unit
Page 32
4
vacon • 29 Power cabling
Table 11. Cable types required to meet standards.
1 = Power cable intended for fixed installation and the specific mains voltage. Shielded cable not
required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and intended for the spe-
cific mains voltage. (MCMK or similar recommended). See Figure 18.
3 = Symmetrical power cable equipped with compact low-impedance shield and intended for
the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recommended cable transfer impedance (1...30MHz) max. 100 mOhm/m]. See Figure 18. *360º earthing of the shield with cable glands in motor end needed for EMC level C2.
4 = Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-O or
similar).
Figure 18.
NOTE: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames). NOTE: If safety switch is connected the EMC protection shall be continuous over the whole cable
installation.
4.1 Circuit breaker
Please disconnect the drive via an external circuit breaker. You have to provide a switching device between supply and main connection terminals.
When connecting the input terminals to the power supply using a circuit breaker, observe that this is of type B or type C and ensure it has a capacity of 1.5 to 2 times of the inverter’s rated current (see Table 24 and Table 25).
NOTE: circuit breaker is not allowed in installations where C-UL is required. Only fuses are recom­mended.
EMC levels
Cable type
1st environment 2nd environment
Category C2 Category C3 Category C4
Mains cable 1 1 1 Motor cable 3* 2 2 Control cable 4 4 4
Shield
PE conductors
Shield
PE conductor
Page 33
Power cabling vacon • 30
Service support: find your nearest Vacon service center at www.vacon.com
4
4.2 UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with a minimum heat-resistance of +70/75°C. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmet­rical amperes, 600V AC maximum, when protected by T or J class fuses.
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.
Page 34
4
vacon • 31 Power cabling
4.3 Description of the terminals
The following pictures describe the power terminals and the typical connections in Vacon® 100X drives.
Figure 19. Power connections, MM4.
PES
AC power supply
Three phases
PE
3AC
Motor
PE
brake
resistor
Page 35
Power cabling vacon • 32
Service support: find your nearest Vacon service center at www.vacon.com
4
Figure 20. Power connections, MM5.
PES
AC power supply
Three phases
PE
3AC
Motor
PE
brake
resistor
Page 36
4
vacon • 33 Power cabling
Figure 21. Power connections, MM6.
PES
AC power supply
Three phases
PE
3AC
Motor
PE
brake
resistor
Page 37
Power cabling vacon • 34
Service support: find your nearest Vacon service center at www.vacon.com
4
4.4 Cable dimensioning and selection
Table 12 shows the minimum dimensions of the Cu-cables and the corresponding fuse sizes. These instructions apply only to cases with one motor and one cable connection from the AC drive
to the motor. In any other case, ask the factory for more information.
4.4.1 Cable and fuse sizes, frames MM4 to MM6
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specification. Bigger fuses than those recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. VACON
®
also rec­ommends high speed J (UL & CSA), aR (UL recognized, IEC 60269-4) and gS (IEC 60269-4) fuse ranges.
Table 12. Cable and fuse sizes for VACON® 100 X.
The terminal sizes are intended for 1 conductor. For MM6, the max. diameter of the ring terminal is 14 mm. The cable dimensioning is based on the criteria of the International Standard IEC60364-5-52: Cables must be PVC-isolated; Max number of parallel cables is 9.
When using cables in parallel,
NOTE HOWEVER that the requirements of both the cross-sectional area and
the max number of cables must be observed. For important information on the requirements of the earthing conductor, see chapter Earthing and earth fault protection of the standard. For the correction factors for each temperature, see International Standard IEC60364-5-52.
Frame Type
I
INPUT
[A]
Fuse
(gG/gL)
[A]
Mains and
motor cable
Cu [mm
2
]
Ter minal ca ble size
Main terminal
[mm
2
]
Earth terminal
[mm
2
]
MM4
0003 4 - 0004 4 3.4 - 4.6 6 3*1.5+1.5
0.5—10
solid
0.5—6 stranded
M4 ring terminal
or 1—6
0007 2 - 0008 2 0005 4 - 0008 4
6.0 - 7.2
5.4 - 8.1
10 3*1.5+1.5
0.5—10
solid
0.5—6 stranded
M4 ring terminal
or
1—6
0011 2 - 0012 2 0009 4 - 0012 4
9.7 - 10.9
9.3 - 11.3
16 3*2.5+2.5
0.5—10
solid
0.5—6 stranded
M4 ring terminal or 1—6
MM5
0018 2 0016 4
16.1
15.4
20 3*6+6
0.5—16
solid
or stranded
M5 ring terminal or 1—10
0024 2 0023 4
21.7
21.3
25 3*6+6
0.5—16
solid
or stranded
M5 ring terminal or 1—10
0031 2 0031 4
27.7
28.4
32 3*10+10
0.5—16
solid or
stranded
M5 ring terminal or 1—10
MM6
0038 4 36.7 40 3*10+10 M6
ring terminal M6 ring terminal
0048 2 0046 4
43.8
43.6
50 3*16+16 M6
ring terminal M6 ring terminal
0062 2 0061 4
57.0 58,2
63 3*25+16 M6
ring terminal M6 ring terminal
0072 4 67.5 80 3*35+16 M6 ring terminal M6 ring terminal
Page 38
4
vacon • 35 Power cabling
4.4.2 Cable and fuse sizes, frames MM4 to MM6, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specification. Bigger fuses than those recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. VACON
®
also rec­ommends high speed J (UL & CSA), aR (UL recognized, IEC 60269-4) and gS (IEC 60269-4) fuse ranges.
Table 13. Cable and fuse sizes for VACON® 100 X.
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must be PVC-isolated; Max ambient temperature +40 °C (104 °F), max temperature of cable surface +70/+75 °C (158/ 167 °F); Use only cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel, NOTE HOWEVER that the requirements of both the cross-sectional area and the max number of cables must be observed. For important information on the requirements of the earthing conductor, see standard Underwriters’ Labo­ratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Laboratories UL508C.
Frame Type
I
INPUT
[A]
Fuse
(class T)
[A]
Mains and
motor cable
Cu
Terminal cable size
Main terminal Earth terminal
MM4
0003 4 - 0004 4 3.4 - 4.6 6
AWG14 AWG24-AWG10
AWG17-AWG10 M4
ring terminal
0007 2 - 0008 2 0005 4 - 0008 4
6.0 - 7.2
5.4 - 8.1
10
AWG14 AWG24-AWG10
AWG17-AWG10 M4
ring terminal
0011 2 0009 4
9.7
9.3
15
AWG14 AWG24-AWG10
AWG17-AWG10 M4
ring terminal
0012 2 0012 4
10.9
11.3
20
AWG14 AWG24-AWG10
AWG17-AWG10 M4
ring terminal
MM5
0018 2 0016 4
16.1
15.4
25
AWG10 AWG20-AWG5
AWG17-AWG8 M5
ring terminal
0024 2 0023 4
21.7
21.3
30
AWG10 AWG20-AWG5
AWG17-AWG8 M5
ring terminal
0031 2 0031 4
27.7
28.4
40
AWG8 AWG20-AWG5
AWG17-AWG8 M5
ring terminal
MM6
0038 4 36.7 50
AWG4
AWG13-AWG0
M6 ring terminal
AWG13-AWG2 M6
ring terminal
0048 2 0046 4
43.8
43.6
60
AWG4
AWG13-AWG0 M6
ring terminal
AWG13-AWG2 M6 ring terminal
0062 2 0061 4
57.0 58,2
80
AWG4
AWG13-AWG0 M6
ring terminal
AWG13-AWG2 M6 ring terminal
0072 4 67.5 100
AWG2
AWG9-AWG2/0 M6
ring terminal
AWG9-AWG2/0 M6 ring terminal
Page 39
Power cabling vacon • 36
Service support: find your nearest Vacon service center at www.vacon.com
4
4.4.3 Brake resistor cables
VACON
®
100 X AC drives are equipped with terminals for an optional external brake resistor. These
terminals are marked with DC+/R+ and R-. See Table 27 and Table 28 for the resistor ratings.
4.4.4 Control cables
For information on control cables see chapter Control unit.
Page 40
4
vacon • 37 Power cabling
4.5 Cable installation
Before starting, check that none of the components of the AC drive is live. Read carefully the warnings in chapter 1.
Place the motor cables sufficiently far from other cables
Avoid placing the motor cables in long parallel lines with other cables.
If the motor cables run in parallel with other cables note the minimum distances between the motor cables and other cables given in table below.
The given distances also apply between the motor cables and signal cables of other systems.
•The maximum lengths of motor cables (shielded) are 100 m (MM4) and 150 m (MM5 and MM6).
The motor cables should cross other cables at an angle of 90 degrees.
If cable insulation checks are needed, see chapter Cable and motor insulation checks.
Start the cable installation according to the instructions below:
Figure 22. Stripping of cables.
Distance between
cables, [m]
Shielded
cable, [m]
0.3 50
1.0 200
1
Strip the motor and mains cables as recommended below.
D1
B1
C1
A1
D2
C2
Earth conductor
MAINS MOTOR
Shield
E
Earth conductor
Page 41
Power cabling vacon • 38
Service support: find your nearest Vacon service center at www.vacon.com
4
Table 14. Cables stripping lengths [mm].
IEC installation:
Figure 23. Cable entry plate, MM4.
Figure 24.Cable entry plate, MM5.
Frame A1 B1 C1 D1 C2 D2 E
MM4 15 70 10 30 7 30
as short as possibleMM5 20 70 10 40 10 40
MM6 20 90 15 60 15 60
2
Remove the cable entry plate. The cable entry system is a combination of a cable entry plate (see the figure below) and cable glands. In the cable entry plate there are several openings available for the cables with ISO metric thread.
Open only the inlet holes where you need to run the cables.
3
Choose the correct cable glands according to drive and cable size as shown in the following pictures.
Page 42
4
vacon • 39 Power cabling
Figure 25.Cable entry plate, MM6.
Figure 26.Cable gland.
4
Cable glands must be made of plastic materials. They are used for sealing cables passing through cable entries to ensure the characteristics of the enclosure.
Plastic cable glands are recommend. If metal cable glands are needed, all insula­tion system requirements and all protective earthing requirements have to be ful­filled in accordance with the national electrical regulations and IEC 61800-5-1.
5
Screw the cable glands on the cable entry holes using the proper tightening torque as shown in Table 15.
Page 43
Power cabling vacon • 40
Service support: find your nearest Vacon service center at www.vacon.com
4
Tightening torques of cable glands:
UL installation:
Figure 27.Cable entry plate, MM4 UL installation.
Frame
Gland screw
type [metric]
Tightening torque [Nm]/[lb-in.]
[Nm] lb-in.
MM4
M16 1.0 8.9 M25 4.0 35.5
MM5
M16 1.0 8.9 M25 4.0 35.5 M32 7.0 62.1
MM6
M16 1.0 8.9 M25 4.0 35.5 M40 10.0 88.7
Table 15. Tightening torque and dimension of cable glands.
6
To connect NPT pipes to Vacon®100X, use the optional metal cable entry plate (included in -R02 option) to meet UL installation rules.
One metal conduit plate with accessories (screws and gasket) is delivered in a separate bag together with the drive. See the following figures for more details.
Page 44
4
vacon • 41 Power cabling
Figure 28.Cable entry plate, MM5 UL installation.
Figure 29.Cable entry plate, MM6 UL installation.
Page 45
Power cabling vacon • 42
Service support: find your nearest Vacon service center at www.vacon.com
4
Cable installation:
Tightening torques of cable terminals:
Table 16. Tightening torques of terminals.
7
All the (3) terminal box openings are closed with the standard plastic plates with the metric threads.
8
The metal cable entry plate for UL installation has to be installed in place of one of standard plastic cable entries provided with the default package. The metal cable entry plate has three not-threaded openings: input line, motor and I/Os and can be mounted only on left or right-hand side of the drive.
9
Flexible or rigid cable conduit can be used.
Use proper fittings to join and terminate rigid conduit tubing, and protect it from damage too.
The proper selection of electrical conduit materials, fittings, and installation are important for safe electrical wiring.
10
Setscrew fittings are commonly used with conduit; they provide weather tight joints that are firm to keep the IP degree of the drive.
11
Pass the cables (supply cable, motor cable, brake cable and I/O cables) through the conduits (UL connections) or through the cable glands (IEC connections) and cable entries.
12
Detach the cable clamps and the grounding clamps.
13
Connect the stripped cables:
Expose the shield of both cables in order to make a 360-degree connection with the cable clamp (reverse the shield over the plastic cover of the cable and fix all together).
Connect the phase conductors of the supply and motor cables into their respective terminals.
Form the rest of the cable shield of both cables into “pigtails” and make a grounding connection with the clamp. Make the pigtails just long enough to reach and be fixed to the terminal - no longer.
Frame Type
Tightening torque
[Nm]/[lb-in.]
Power and motor
terminals
Tightening torque
[Nm]/[lb-in.]
EMC grounding
clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
[Nm] lb-in. [Nm] lb-in. [Nm] lb-in.
MM4
0007 2 - 0012 2 0003 4 - 0012 4
1.2—1.5 10.6—13.3 1.5 13.3 2.0 17.7
MM5
0018 2 - 0031 2 0016 4 - 0031 4
1.2—1.5 10.6—13.3 1.5 13.3 2.0 17.7
MM6
0048 2 - 0062 2 0038 4 - 0072 4
4—5 35.4—44.3 1.5 13.3 2.0 17.7
14
Check the connection of the earth cable to the motor and the AC drive termi­nals marked with .
Page 46
4
vacon • 43 Power cabling
Page 47
Control unit vacon • 44
Service support: find your nearest Vacon service center at www.vacon.com
5
5. CONTROL UNIT
Remove the powerhead of the drive to reveal the terminal box with the control terminals. The control unit of the AC drive consists of the control board and additional boards (option boards)
connected to the slot connectors of the control board. The locations of boards, terminals and switches are presented in Figure 30 below.
Figure 30. Locations of components in control unit.
When delivered from the factory, the control unit of the AC drive contains the standard controlling interface - the control and relay terminals of the control unit - unless otherwise specifically or­dered. On the next pages you will find the arrangement of the control I/O and the relay terminals, the general wiring diagram and the control signal descriptions.
Number Meaning
1 Control terminals 1-11 (see chapter 5.1.2) 2 Control terminals 12-30, A-B (see chapter 5.1.2) 3 Relay terminals (see chapter 5.1.2) 4 Thermistor input (see chapter 5.1.2) 5STO terminals 6Dip switches 7 Ethernet terminal (see chapter chapter 5.2.1) 8 Option boards
Table 17. Locations of components in control unit.
8
8
4
7
5
3
1 2
6
Page 48
5
vacon • 45 Control unit
The control board can be powered externally (+24VDC, max. 1000mA, ±10%) by connecting the ex­ternal power source to terminal #30, see chapter 5.1.2. This voltage is sufficient for parameter set­ting and for keeping the control unit active. Note however that the measurements of the main circuit (e.g. DC-link voltage, unit temperature) are not available when the mains is not connected.
5.1 Control unit cabling
The principal terminal block placement is presented in Figure 31 below. The control board is equipped with 22 fixed control I/O terminals and the relay board with 6+2. Additionally, the termi­nals for the Safe Torque Off (STO) function (see chapter chapter 9.) can be seen in the picture below. All signal descriptions are also given in Table 19.
Figure 31. Control terminals.
5.1.1 Control cable sizing
The control cables shall be at least 0.5 mm
2
screened multicore cables, see Table 18. The maxi-
mum terminal wire size is 2.5 mm
2
for the relay terminals and 1.5 mm2 for other terminals.
Find the tightening torques of the control and relay board terminals in Table 18.
Terminal screw
Tightening torque
Nm lb-in.
I/O terminals and STO terminals (screw M2)
0.5 4.5
Relay terminals (screw M3) 0.5 4.5
Table 18. Control cable tightening torques.
Page 49
Control unit vacon • 46
Service support: find your nearest Vacon service center at www.vacon.com
5
5.1.2 Standard I/O terminals
The terminals of the
Standard I/Os and the Relays are described below. For more information on
the connections, see chapter 7. The terminals shown on shadowed background are assigned for signals with optional functions se-
lectable with DIP switches. See more information in chapter 5.1.5 and in chapter 5.1.6.
Table 19. Control I/O terminal signals and connection example.
Standard I/O
Term inal Signal
1 +10 Vref Reference output
2
AI1+
Analogue input, voltage or current
3
AI1-
Analogue input com­mon
4
AI2+
Analogue input, voltage or current
5
AI2-
Analogue input com­mon
6
24Vout 24V aux. voltage
7
GND I/O ground
8
DI1 Digital input 1
9
DI2 Digital input 2
10
DI3 Digital input 3
11
CM
Common for DI1-DI6
*
*. Can be isolated from ground, see chap-
ter chapter 5.1.6.
12
24Vout 24V aux. voltage
13
GND I/O ground
14
DI4 Digital input 4
15
DI5 Digital input 5
16
DI6 Digital input 6
17
CM Common for DI1-DI6*
18
AO1+
Analogue output, voltage or current
19
AO-/GND
Analogue output com­mon
30 +24 Vin
24V auxiliary input voltage
A RS485 Serial bus, negative B RS485 Serial bus, positive
Reference
potentiometer 1...10 kΩ
Remote reference
4...20mA/0...10V
mA
Page 50
5
vacon • 47 Control unit
5.1.3 Relay and thermistor input terminals
5.1.4 Safe Torque off (STO) terminals
For more information on the functionalities of the Safe Torque Off (STO), see chapter 9.
Table 20. I/O terminal signals for relay and thermistor terminals and connection example.
Relays and thermistor
Term inal Signal
21
RO1/1
Relay output 1
22
RO1/2
23
RO1/3
24
RO2/1
Relay output 2
25
RO2/2
26
RO2/3
28
TI1+
Thermistor input
29
TI1-
Table 21. I/O terminal signals for the STO functions.
Safe Torque Off terminals
Ter mina l Signal
S1
Isolated digital input 1 (inter­changeable polarity); +24V ±20% 10...15mA
G1
S2
Isolated digital input 2 (inter­changeable polarity); +24V ±20% 10...15mA
G2
F+
Isolated feedback (CAUTION! Polarity to be respected); +24V ±20%
F-
Isolated feedback (CAUTION! Polarity to be respected); GND
From
standard I/O
From term.
#13
From term.
#6
RUN
Page 51
Control unit vacon • 48
Service support: find your nearest Vacon service center at www.vacon.com
5
5.1.5 Selection of terminal functions with dip switches
The VACON
®
100 X drive embodies five so-called dip switches that allow for three functional selec­tions each. The shadowed terminals in Table 19 can be functionally modified with the dip switches. The switches have three positions: C, 0 and V. The switch in the position “C” means that the input or the output has been set in current mode. The switch in the position “V” means voltage mode.The middle position ”0” is for
Test mode. See Figure 32 to locate the switches and make appropriate
selections for your requirements. Factory defaults are: AI1 = V; AI2 = C, AO = C.
Figure 32. Dip switches for analogue inputs and analogue output.
5.1.6 Isolating digital inputs from ground
The digital inputs (terminals 8-10 and 14-16) on the standard I/O board can be isolated from ground by setting the
dip switch to position ‘0’. The switch in the position “1” means that the common of
digital input has been connected to 24 V (negative logic). The switch in the position “2” means that the common of digital inputs has been connected to ground (positive logic). See Figure 33. Locate the switch and set it in desired position. Factory default is 2.
Figure 33. Digital inputs dip switch.
Page 52
5
vacon • 49 Control unit
5.1.7 Bus termination of the RS485 connection
This dip switch is related to the RS485 connection. It’s used for bus termination. The bus termina­tion must be set to the first and to the last device on the network. This switch in position “0” means that a termination resistor of 120 ohm is connected and the termination of the bus has been set. This switch in the position “1” means that a pull-up and a pull-down resistors of 10 kOhm have been connected for biasing purpose. The switch in the position “2” means no termination and no biasing resistors have been connected. Factory default is 2. See Figure 34.
Figure 34. RS485 dip switch.
Page 53
Control unit vacon • 50
Service support: find your nearest Vacon service center at www.vacon.com
5
5.2 I/O cabling and Fieldbus connection
The AC drive can be connected to fieldbus either through RS485 or Ethernet. The connection for RS485 is on the standard I/O terminals (A and B) and the connection for Ethernet is left to the con­trol terminals. See Figure 35.
Figure 35.
5.2.1 Prepare for use through Ethernet
For more detailed information, see the user’s manual of the fieldbus you are using.
5.2.1.1 Ethernet cable data
Table 22. Ethernet cable data.
1
Connect the Ethernet cable (see specification on page 50) to its terminal and run the cable through the conduit plate.
2
Remount the powerhead. NOTE: When planning the cable runs, remember to keep the distance between the Ethernet cable and the motor cable at a minimum of 30 cm.
Connector
Shielded RJ45 connector. Note: max
length of the connector 40 mm. Cable type CAT5e STP Cable length Max. 100m
1234567891011
12 13 14 15 16 17 18 19 30
BA
RS485
terminals
Ethernet connection
Page 54
5
vacon • 51 Control unit
5.2.2 Prepare for use through RS485
1
Strip about 15 mm of the RS485 cable (see specification on page 52) and cut off the grey cable shield. Remember to do this for both bus cables (except for the last device). Leave no more than 10 mm of the cable outside the terminal block and strip the cables at about 5 mm to fit in the terminals. See picture below.
Also strip the cable now at such a distance from the terminal that you can fix it to the frame with the grounding clamp. Strip the cable at a maximum length of 15 mm. Do
not strip the aluminum cable shield!
2
Then connect the cable to its appropriate terminals on VACON® 100 X AC drive stan­dard terminal block, terminals A and B (A = negative, B = positive). See Figure 35.
3
Using the cable clamp included in the delivery of the drive, ground the shield of the RS485 cable to the frame of the AC drive.
4
If VACON® 100 X AC drive is the last device on the bus, the
bus termination must be set. Locate the DIP switches to the top of the control unit (see Figure 32) and turn the right most switch to position “1”. Biasing is built in the termination resistor. See also step 6.
5
NOTE: When planning the cable runs, remember to keep the distance between the
fieldbus cable and the motor cable at a minimum of 30 cm.
10
5
Page 55
Control unit vacon • 52
Service support: find your nearest Vacon service center at www.vacon.com
5
5.2.3 RS485 cable data
Table 23. RS485 cable data.
6
The bus termination must be set for the first and the last device of the fieldbus line. See picture below and step 4. We recommend that the first device on the bus and, thus, terminated, was the Master device.
Connector
2.5 mm
2
Cable type
STP (Shielded Twisted Pair), type Belden
9841 or similar
Cable length
Depends on the used fieldbus. See
respective bus manual.
Fieldbus
= Bus termination
Resistor = 220 ohm
Ter mi nat io n
activated
Ter mi na ti on
activated with
DIP switch
Termination
deactivated
Vacon 100X Vacon 100X Vacon 100X Vacon 100X Vacon 100X
Page 56
5
vacon • 53 Control unit
5.3 Battery installation for Real Time Clock (RTC)
Enabling the functions of the Real Time Clock (RTC) requires that an optional battery is installed in the VACON
®
100 X drive.
Detailed information on the functions of the
Real Time Clock (RTC) can be found in the Application
Manual. See the following figures to install the battery on the control box of Vacon
®
100X frequency
converter.
Figure 36. Remove the three screws on the control box.
1
Remove the three screws on the control box as shown in Figure 36.
2
Rotate and open the cover of the control box as shown in Figure 37.
Page 57
Control unit vacon • 54
Service support: find your nearest Vacon service center at www.vacon.com
5
Figure 37. Open the cover of control box.
3
Install the battery in the correct place and connect it to the control box. See Figure 38 for battery location and connector.
Page 58
5
vacon • 55 Control unit
Figure 38. Location and connector for the battery on the control box.
Location for battery
Connector for battery
Page 59
Commissioning vacon • 56
Service support: find your nearest Vacon service center at www.vacon.com
6
6. COMMISSIONING
Before commissioning, note the following directions and warnings:
Internal components and circuit boards of VACON® 100 X drive (except for the galvan­ically isolated I/O terminals) are live when it is connected to the mains potential.
Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals R-/R+ are live when VACON
®
100 X drive is connected to the mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present
even when VACON
®
100 X drive is disconnected from the mains.
Do not make any connections to or from the frequency converter when it is connected to the mains.
After disconnecting the AC drive from the mains, wait until the fan stops and the indicators on the powerhead go out. Wait an additional 30 seconds before doing any
work on the connections of VACON
®
100 X Drive. Do not open the unit before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no
voltage is present.
Always ensure absence of voltage before starting
any electrical work!
Before connecting the AC drive to mains make sure that the powerhead VACON
®
100
X Drive is mounted firmly on the terminal box.
Page 60
6
vacon • 57 Commissioning
6.1 Commissioning of the drive
Read carefully the safety instructions in Chapter 1 and above and follow them. After the installation:
Check that both the frequency converter and the motor are grounded.
Check that the mains and motor cables comply with the requirements given in chapter 5.
Check that the control cables are located as far as possible from the power cables.
Check that the shields of the shielded cables are connected to protective earth marked with .
Check the tightening torques of all terminals.
Check that the wires do not touch the electrical components of the drive.
Check that the common inputs of digital input groups are connected to +24V or ground of the I/O terminal.
Check the quality and quantity of cooling air.
Check the inside of the frequency converter for condensation.
Check that all Start/Stop switches connected to the I/O terminals are in the Stop­position.
Before connecting the frequency converter to mains: Check mounting and condi­tion of all fuses and other protective devices.
Run the Startup Wizard (see the Application Manual).
Page 61
Commissioning vacon • 58
Service support: find your nearest Vacon service center at www.vacon.com
6
6.2 Changing EMC protection class
If your supply network is an IT (impedance-grounded) system but your AC drive is EMC-protected according to class C1 or C2 you need to modify the EMC protection of the AC drive to EMC-level T (C4). This is done by removing the EMC screws as described below:
Figure 39. Locations of EMC screws in MM4.
Figure 40. Locations of EMC screws in MM5.
Warning! Do not perform any modifications on the AC drive when it is connected to mains.
1
Separate the powerhead and the terminal box. Turn the powerhead upside down and remove the two screws marked in Figure 39 (for MM4), Figure 40 (for MM5) and in Figure 42(for MM6).
Page 62
6
vacon • 59 Commissioning
Figure 41. Powerhead separated from the terminal box in MM6.
Figure 42.Locations of EMC screws in MM6.
2
CAUTION! Before connecting the AC drive to mains make sure that the EMC protec-
tion class settings of the drive are appropriately made.
3
NOTE! After having performed the change write ‘EMC level modified’ on the sticker
included in the VACON
®
100 X delivery (see below) and note the date. Unless already
done, attach the sticker close to the name plate of the AC drive.
Product modified
Date:
Date:
Date:
EMC-level modified C1->C4
DDMMYY
Page 63
Commissioning vacon • 60
Service support: find your nearest Vacon service center at www.vacon.com
6
6.3 Running the motor
MOTOR RUN CHECK LIST
6.3.1 Cable and motor insulation checks
1. Motor cable insulation checks Disconnect the motor cable from terminals U, V and W of the AC drive and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1MΩ at ambient temperature of 20°C.
2. Mains cable insulation checks Disconnect the mains cable from terminals L1, L2 and L3 of the AC drive and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1MΩ at ambient temperature of 20°C.
3. Motor insulation checks Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1MΩ at ambient temperature of 20°C.
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
Make sure that the motor terminals are not connected to mains potential.
Page 64
6
vacon • 61 Commissioning
6.4 Maintenance
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is recom­mended to ensure trouble-free operation and longevity of the drive. We recommend the table below is followed for maintenance intervals.
NOTE: Because of capacitor type (thin film capacitors), reforming of capacitors is not necessary.
Maintenance interval Maintenance action
Regularly and according to general maintenance interval
Check tightening torques of terminals
6...24 months (depending on environment)
Check input and output terminals and control I/O terminals.
Check operation of cooling fan
Check the heatsink for dust and clean if necessary
6...10 years Change main fan 10 years Replace the battery of the RTC.
Page 65
Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
7. TECHNICAL DATA
7.1 AC drive power ratings
7.1.1 Mains voltage 3AC 208-240V
Table 24. Power ratings of VACON® 100 X, supply voltage 3AC 208-240V.
NOTE: The rated currents in given ambient temperatures (in Table 24) are achieved only when the switching frequency is equal to or less than the factory default.
Mains voltage 3AC 208-240V, 50/60 Hz
Converter
type
Input
current
[A]
Loadability
Motor shaft power
230V supply
Rated continuous
current I
N
[A]
50% overload
current
[A]
Max current
I
S
[kW] [HP]
MM4
0007 6.0 6.6 9.9 13.2 1.1 1.5 0008 7.2 8.0 12.0 16.0 1.5 2.0 0011 9.7 11.0 16.5 22.0 2.2 3.0 0012 10.9 12.5 18.8 25.0 3.0 4.0
MM5
0018 16.1 18.0 27.0 36.0 4.0 5.0 0024 21.7 24.2 36.3 48.4 5.5 7.5 0031 27.7 31.0 46.5 62.0 7.5 10.0
MM6
0048 43.8 48.0 72.0 96.0 11.0 15.0
0062 57.0 62.0 93.0 124.0 15.0 20.0
Page 66
7
vacon • 63 Technical data
7.1.2 Mains voltage 3AC 380-480V
NOTE: The rated currents in given ambient temperatures (in Table 25) are achieved only when the switching frequency is equal to or less than the factory default.
Mains voltage 3AC 380-480V, 50/60 Hz
Converter
type
Input
current
[A]
Loadability
Motor shaft power
400V 480V
Rated continuous
current I
N
[A]
50% overload
current
[A]
Max current
I
S
[kW] [HP]
MM4
0003 3.4 3.4 5.1 6.8 1.1 1.5 0004 4.6 4.8 7.2 9.6 1.5 2.0 0005 5.4 5.6 8.4 11.2 2.2 3.0 0008 8.1 8.0 12.0 16.0 3.0 5.0 0009 9.3 9.6 14.4 19.2 4.0 5.0 0012 11.3 12.0 18.0 24.0 5.5 7.5
MM5
0016 15.4 16.0 24.0 32.0 7.5 10.0 0023 21.3 23.0 34.5 46.0 11.0 15.0 0031 28.4 31.0 46.5 62.0 15.0 20.0
MM6
0038 36.7 38.0 57.0 76.0 18.5 25.0 0046 43.6 46.0 69.0 92.0 22.0 30.0 0061 58,2 61.0 91.5 122.0 30.0 40.0
Table 25. Power ratings of VACON® 100 X, supply voltage 3AC 380-480V, high overload.
Mains voltage 3AC 380-480V, 50/60 Hz
Converter
type
Input
current
[A]
Loadability
Motor shaft power
400V 480V
Rated continuous
current I
N
[A]
10% overload
current
[A]
Max current
I
S
[kW] [HP]
MM6
0072 67.5 72.0 80.0 108.0 37.0 50.0
Table 26. Power ratings of VACON® 100 X, supply voltage 3AC 380-480V, low overload.
Page 67
Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
7.1.3 Definitions of overloadability
High overload= Following continuous operation at rated output current IN, the converter supplies 150% * IN
for 1 min, followed by a period of at least 9 min at I
N
or below.
Example: If the duty cycle requires 150% rated current for 1 min in every 10 min, the remaining 9 min
must be at rated current I
N
or less.
Figure 43. High overload.
Low overload= Following continuous operation at rated output current I
N
, the converter supplies 110% * IN
for 1 min, followed by a period of at least 9 min at I
N
or below.
Example: If the duty cycle requires 110% rated current for 1 min in every 10 min, the remaining 9 min
must be at rated current I
N
or less.
Figure 44. Low overload.
NOTE! For more information, please refer to IEC61800-2 (IEC:1998) Standard.
I
N
I
N*150%
1 min 9 min
I
N*150%
Current
Time
I
N
I
N*110%
1 min 9 min
I
N*110%
Current
Time
Page 68
7
vacon • 65 Technical data
7.2 Brake resistor ratings
Make sure that the resistance is higher than the minimum resistance defined. The power handling capacity must be sufficient for the application.
Recommended minimum brake resistor values for VACON
®
100 X AC drives:
Mains Voltage 3AC 208-240V, 50/60 Hz
Frame Type
Minimum Resistance
recommended
[ohm]
Brake power @405
VDC
[kW]
MM4
0007 25 6.6 0008 25 6.6 0011 25 6.6 0012 25 6.6
MM5
0018 15 10.9 0024 15 10.9 0031 10 16.4
MM6
0048 8 20.5 0062 8 20.5
Table 27. Brake resistor ratings, 208-240V.
Mains Voltage 3AC 380-480V, 50/60 Hz
Frame Type
Minimum Resistance
recommended
[ohm]
Brake power @845
VDC
[kW]
MM4
0003 50 14.3 0004 50 14.3 0005 50 14.3 0008 50 14.3 0009 50 14.3 0012 50 14.3
MM5
0016 30 23.8 0023 30 23.8 0031 20 35.7
MM6
0038 15 47.6 0046 15 47.6 0061 15 47.6 0072 15 47.6
Table 28. Brake resistor ratings, 380-480V.
Page 69
Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
7.3 VACON® 100 X - technical data
Mains connection
Input voltage U
in
3AC 208…240V 3AC 380...480V
Input voltage tolerance
-15%...+10% continuously
Input frequency 50/60 Hz Protection class I Input frequency
tolerance
47.5...66 Hz
Connection to mains Once per minute or less Starting delay <7 s
Supply network
TN- and IT-network (cannot be used with corner earthed network)
Short-circuit current Max. short-circuit current has to be < 100kA
Motor connection
Output voltage
3AC 0... U
in
Rated output current
IN: Ambient temperature max. +40°C. See Table 24 and Table 25.
Overload output current
1.5 x IN (1 min/10 min);
1.1 x I
N
(1 min/10 min) only for MM6 0072.
See Table 24 and Table 25.
Starting output current
IS for 2 s every 20 s. See Table 24 and Table 25.
Output frequency 0…320 Hz (standard) Frequency resolution 0.01 Hz Protection class I
Motor characteristics
AC squirrel cage motors
Permanent magnet motors Cable type Screened motor cable Cable maximum length
(full EMC compliance)
C2: 15m
Control characteristics
Switching frequency
Programmable 1.5…16 kHz;
Default: 6 kHz (MM4 and MM5); 4 kHz (MM6)
Automatic switching frequency derating in case of
overheating Frequency reference
Analogue input Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz Field weakening point 8…320 Hz Acceleration time 0.1…3000 sec Deceleration time 0.1…3000 sec
Braking
Brake chopper standard in all frames
External brake resistor optional
Control connections
See chapter 5.
Page 70
7
vacon • 67 Technical data
Communication interface
Fieldbus
Standard: Serial communication (RS485/Mod-
bus); Ethernet IP, Profinet IO, Modbus TCP, Bac-
net IP
Optional: CanOpen; Profibus DP, DeviceNet, Lon-
works
Status indicators
Drive status indicators (LED) on top side (POWER,
RUN, FAULT, READY)
Ambient conditions
Ambient operating tem­perature
-10°C …+40°C
Extended temperature range
up to 60°C with current derating (see chapter 1.8)
Storage temperature -40°C…+70°C Relative humidity
0 to 100% R
H
Pollution degree
PD2 used for PCB design.
However the drives are suitable for outdoor use
because of dust-tight enclosure to numeral 6
[acc. to IEC 60529].
Altitude
100% load capacity (no derating) up to 1,000m;
derating 1%/100m at 1,000...3,000m
Stationary vibration: sinusoidal
3 Hz f 8,72 Hz: 10 mm
8,72 Hz
f 200 Hz: 3g
[3M7 acc. to IEC 60721-3-3]
Shock/Bump
25g / 6 ms
[3M7 acc. to IEC 60721-3-3] Degree of protection IP66/Type 4X
Noise Level
Average noise level (min­max) in dB (A)
The sound pressure depends on the cooling fan
speed, which is controlled in accordance with the
drive temperature.
MM4: 45-56
MM5: 57-65
MM6: 63-72
Directives
EMC 2004/108/EC Low Voltage Directive 2006/95/EC RoHS 2002/95/EC WEEE 2012/19/EC
Standards
Immunity
EN61800-3 (2004), 1st and 2nd environment
Emissions
EN61800-3 (2004), Category C2
The drive can be modified for IT-networks. THD EN61000-3-12 (see chapter 1.9) Safety EN 61800-5-1
Production quality ISO 9001
Approvals
Functional Safety TÜV (Rheinland) - Tested Electrical Safety TÜV (SÜD) - Tested EMC TÜV - Tested USA, Canada cULus approval, file number E171278
Page 71
Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
Table 29. VACON® 100 X technical data.
Declaration of Con­formity
Korea KC mark Australia C-tick Declaration of Conformity Europe EC Declaration of Conformity
Protections
Undervoltage trip limit
Depends on supply voltage (0,8775*supply volt-
age):
Supply voltage 400 V: Trip limit
351 V
Supply voltage 480 V: Trip limit 421 V
Supply voltage 240 V: Trip limit 211 V Overvoltage fault protec-
tion
Yes
Earth fault protection Ye s Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Ye s Unit overtemperature
protection
Yes
Motor overload protec­tion
Yes. These devices provide motor overeload pro-
tection at 105% of full load amperes. Motor stall protection Yes Motor underload protec-
tion
Yes
Short-circuit protection of +24V and +10V refer­ence voltages
Yes
Thermal motor protec­tion
Yes (by PTC)
Page 72
7
vacon • 69 Technical data
7.3.1 Technical information on control connections
Standard I/O
Terminal Signal Technical information
1 Reference output +10V, +3%; Maximum current 10 mA
2
Analogue input, voltage or current
Analogue input channel 1 0-20 mA (Ri =250
Ω)
0-10 V (Ri=200k
Ω)
Resolution 0.1%, accuracy ±1% Selection V/mA with dip-switches (see chapter 5). Default 0-10V Short-circuited protected.
3
Analogue input common
Differential input if not connected to ground; Allows ±20V differential mode voltage to GND
4
Analogue input, voltage or current
Analogue input channel 2 0-20 mA (Ri =250
Ω)
0-10 V (Ri=200k
Ω)
Resolution 0.1%, accuracy ±1% Selection V/mA with dip-switches (see chapter 5). Default 0-20mA Short-circuited protected.
5
Analogue input common
Differential input if not connected to ground; Allows 20V differential mode voltage to GND
6
24V aux. voltage
+24V, ±10%, max volt. ripple < 100mVrms; max. 250mA Short-circuit protected
7
I/O ground
Ground for reference and controls (connected internally to frame earth through 1M
Ω)
8
Digital input 1
Positive or negative logic Ri = min. 5k
Ω
18…30V = "1"
0...5V = “0”
9
Digital input 2
10
Digital input 3
11
Common A for DIN1-DIN6.
Digital inputs can be isolated from ground, see chapter 5. Default: connected to ground.
12
24V aux. voltage Same as terminal 6.
13
I/O ground
Ground for reference and controls (connected internally to frame earth through 1M
Ω)
14
Digital input 4
Positive or negative logic Ri = min. 5k
Ω
18…30V = "1"
0...5V = “0”
15
Digital input 5
16
Digital input 6
17
Common A for DIN1-DIN6.
Digital inputs can be isolated from ground, see chapter 5. Default: connected to ground.
18
Analogue output, voltage or current
Analogue output channel 1 0-20 mA (R
L
<500 Ω)
0-10 V (R
L
>1kΩ)
Resolution 0.1%, accuracy ±2% Selection V/mA with dip-switches (see chapter 5). Default 0-20mA Short-circuited protected.
19
Analogue output common
30 24V auxiliary input voltage
Can be used with an external power supply (with a current limiter or fuse protected) to supply the control unit and fieldbus for backup purposes. Dimensioning: max. 1000mA/control unit.
Table 30. Technical information on standard I/O terminals.
Page 73
Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
A RS485 Differential receiver/transmitter
Set bus termination with dip switches (see page 48). Default: but termination disconnected.
B RS485
Relays
Relays with two change-over contact (SPDT) and a PTC thermistor input. 5,5 mm isolation between channels.
Terminal Signal Technical information
21
Relay output 1
*
*
If 230VAC is used as control voltage from the output relays, the control circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent welding on the relay contacts. Refer to standard EN 60204-1, section 7.2.9
Switching capacity 24VDC/8A
250VAC/8A 125VDC/0.4A
Min.switching load 5V/10mA
22 23 24
Relay output 2*
Switching capacity 24VDC/8A
250VAC/8A 125VDC/0.4A
Min.switching load 5V/10mA
25 26 28
Thermistor input
Rtrip = 4.7 kΩ (PTC); Measuring voltage 3.5V
29
Table 31. Technical information on Relay and thermistor terminals.
Standard I/O
Terminal Signal Technical information
Table 30. Technical information on standard I/O terminals.
Page 74
7
vacon • 71 Technical data
Page 75
Options vacon • 72
Service support: find your nearest Vacon service center at www.vacon.com
8
8. OPTIONS
The options available for VACON® 100 X are described below.
8.1 Mains switch
The purpose of the Mains switch is to disconnect the VACON® 100 X from the mains when, for ex­ample, service actions are needed. The mains switch is available as option and it can be integrated in the drive. The switch can be mounted on either side of the drive. See Figure 45.
Figure 45. The mains switch mounted on either side of the drive, MM4 example.
8.1.1 Installation
Figure 46. Disconnect the cable entry plate: example for MM5.
1
Remove the cable entry plate from the drive on the left-hand-side if the mains switch must be mounted on this side. Otherwise remove the cable entry plate from the right-hand-side. See the Figure 46.
Page 76
8
vacon • 73 Options
Figure 47. Cable entry plate from the bottom side of the drive.
Figure 48. Powerhead separated from the terminal box.
2
Remove the cable entry plate from the bottom side of the terminal box by loos­ing the six screws. Cables pass through this inlet hole.
3
Remove the powerhead from the terminal box by loosing the screws on the top side of the drive.
Page 77
Options vacon • 74
Service support: find your nearest Vacon service center at www.vacon.com
8
Figure 49. Connection of the supply cable to the Mains switch (right-hand-side example).
4
Connect the supply cable to the Mains switch passing through the cable entry plate of the bottom side (use the cable gland for sealing the cable to the gland plate) and then through the terminal box as shown in the figure below.
5
Connect the cables from the Mains switch to the terminal box. The cables have to be connected to the terminals L1, L2 and L3.
6
Place the Mains switch plate with the cables in the groove and fix it with its screws.
7
Place the cable entry plate with the other cables (motor cable, brake cable, I/O cables) in the groove on the bottom side of the drive and fix it with its screws.
Page 78
8
vacon • 75 Options
Figure 50. Mains switch, cable entry and cables connected.
Figure 51. Mount the powerhead on the terminal box.
8
Mount the powerhead on the terminal box with its screws: the installation pro­cess has been completed. See Figure 51.
Page 79
Options vacon • 76
Service support: find your nearest Vacon service center at www.vacon.com
8
8.2 Control Keypad
The control keypad is the interface between the VACON® 100 X frequency converter and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter's parameters.
The keypad is an option and can be delivered separately. The option includes the keypad, the keypad holder and three screws. You can use one screw to fix the keypad holder to the drive or three screws to fix the keypad holder to an enclosure/cabinet or any special housing for the drive in which you want to have a remote keypad control available.
8.2.1 Mounting onto the drive
Figure 52. Drive and the optional keypad kit.
Page 80
8
vacon • 77 Options
8.2.2 Installation
Figure 53. Disconnection of the HMI cap from the drive.
Figure 54. Installation of the keypad holder on the powerhead.
1
Remove the HMI cap from the drive as shown in the Figure 53.
2
Install the keypad holder with a screw as shown in the Figure 54. The metal sheets of the keypad holder have to be mounted under the fan holder as shown in the following figures.
Page 81
Options vacon • 78
Service support: find your nearest Vacon service center at www.vacon.com
8
Figure 55. Mounting of the keypad.
Figure 56. Keypad mounted onto the drive. Tighten the fixing screws of the cable connector to
the enclosure of the drive. This is to keep the high IP66 protection degree of the drive.
3
Connect the keypad to the drive and plug the cable on the HMI connector as shown in the Figure 55 and in the Figure 56.
Page 82
8
vacon • 79 Options
8.2.3 Wall-mounting
The keypad can be mounted on the wall in a convenient location by using the same keypad holder and three screws provided with the keypad option kit.
Figure 57. Fix the keypad holder with three screws to the wall.
1
Fix the keypad holder with three screws to the wall.
Page 83
Options vacon • 80
Service support: find your nearest Vacon service center at www.vacon.com
8
Figure 58. Keypad connected to the drive.
2
Connect and fix the cable to the enclosure of the drive and hold the keypad to the wall.
Page 84
8
vacon • 81 Options
8.2.4 Graphical and Text keypad
There are two keypad types you can choose for your user interface: keypad with graphical display and keypad with text segment display (text keypad).
The button section of the keypad is identical for both keypad types.
Figure 59. Keypad buttons.
9086.emf
FUNCT
Scroll menu up Increase value
Scroll menu down Decrease value
Move cursor left Move cursor right
Move backward in menu Exit edit mode Reset faults with long press
Change control place
Access control page Change direction
Stop button Start button
Enter active level/item Confirm selection
Page 85
Options vacon • 82
Service support: find your nearest Vacon service center at www.vacon.com
8
8.2.5 VACON® keypad with graphical display
The graphical keypad features an LCD display and 9 buttons.
8.2.5.1 Keypad display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about
his present
location in the menu
structure and the item displayed.
8.2.5.2
Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows to move between the menus. Enter the group/item by pressing the OK button and
return
to the for-
mer level by pressing the Back/Reset button. The
Location field indicates your current location. The Status field gives information about the
present status of the drive. See Figure 60.
Figure 60. Main menu.
8.2.5.3
Using the graphical keypad
Editing values
The selectable values can be accessed and edited in two different ways on the graphical keypad.
Parameters with one valid value
Typically, one parameter is set one value. The value is selected either from a list of values (see ex­ample below) or the parameter is given a numerical value from a defined range (e.g. 0.00...50.00 Hz).
Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the
Edit mode.
3. Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and then change the value with the arrow but­tons up/down.
4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Location field
Status field
(Parameter ID number
Main Menu
Quick Setup
( 17 )
Parameters
( 12 )
STOP READY I/O
ID: M1
( 5 )
Monitor
Activated group/item. Press OK to enter.
Number of items in the group
STOP/RUN
Status field READY/NOT READY/FAULT
Control place: PC/IO/KEYPAD/FIELDBUS
ALARM
and current menu location)
Direction
Page 86
8
vacon • 83 Options
Figure 61. Typical editing of values on graphical keypad (text value).
Figure 62. Typical editing of values on graphical keypad (numerical value).
Parameters with checkbox selection
Some parameters allow selecting several values. Make a checkbox selection at each value you wish to activate as instructed below.
Figure 63. Applying the checkbox value selection on graphical keypad
Start/St op Setup
Rem Control Place
I/O Control
KeypadStopB utton
Yes
Start Funct ion
Ramping
STOP READY I/O
ID:172 M3.2.1
Edit
Help
Add to favo rites
Rem Cont rol Place
STOP READY I/O
ID: M3.2.1
Rem Cont rol Place
STOP READY I/O
M3. 2. 1
I/O Con trol
Fieldbu sCTRL
Start/St op Setup
Rem Control Place
I/O Control
KeypadStopB utton
Yes
Start Funct ion
Ramping
STOP READY I/O
ID:172 M3.2.1
Rem Cont rol Place
STOP READY I/O
M3.2.1
I/O Con trol
Fieldbu sCTRL
OR:
OKOKOK
BACK
RESET
9257.emf
OK
9256.emf
...
OK
Symbol for checkbox selection
Page 87
Options vacon • 84
Service support: find your nearest Vacon service center at www.vacon.com
8
Resetting fault
Instructions for how to reset a fault can be found in chapter 8.2.7.
Function button
The FUNCT button is used for four functions:
1. to quickly access the Control page,
2. to easily change between the Local (Keypad) and Remote control places,
3. to change the rotation direction and
4. to quickly edit a parameter value.
Control places
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. The Local control place is always the keypad. The
Remote control place is determined by parameter P3.2.1 (I/O or Field-
bus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again, can bypass the
remote control place selected with parameter P3.2.1 using a digital input. The digital input is se­lected with parameter P3.5.1.7
(I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.7 through digital input while in
Remote, the control place will still switch to Keypad if Local is selected. Switching between
Local and Remote Control can be done by pressing the FUNCT-button on the keypad or by using the "Local/Remote" (ID211) parameter.
Changing control places
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the
Arrow up or the Arrow down button to select Local/Remote and confirm with the OK
button.
3. On the next display, select
Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the
FUNCT button was pushed. How-
ever, if the Remote control place was changed to Local (Keypad) you will be prompted for key­pad reference.
Page 88
8
vacon • 85 Options
Figure 64. Changing control places.
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the
Arrow up or the Arrow down button to select Control page and confirm with the OK
button.
3. The control page appears
If keypad control place and keypad reference are selected to be used you can set the
Keypad
Reference
after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring.
Figure 65. Accessing Control page.
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY Keypad
ID: M1
( 7 )
Monitor
( 6 )
ID:
Choose action
STOP Ready Keypad
ID:1805
Local/Remote
Control page
Change direction
?
Remote
ID:
Local/Remote
STOP READY Keypad
ID:211
Remote
Local
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY I/O
ID: M1
( 7 )
Monitor
( 6 )
FUNCT
OK
OK
9161.emf
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY I/O
ID: M1
( 7 )
Monitor
( 6 )
ID:
Choose action
STOP Ready Keypad
ID:1805
Local/Remote
Control page
Change direction
STOP READY Keypad
( 6 )
Keypad Reference
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
ID:184
Keypad
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
STOP READY Keypad
( 6 )
ID:168
Keypad Reference
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
FUNCT
OK
OK
OK
9162.emf
Page 89
Options vacon • 86
Service support: find your nearest Vacon service center at www.vacon.com
8
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT button. NOTE! Chang-
ing direction
command is not visible in the menu unless the selected control place is Local.
1. Anywhere in the menu structure, push the Funct button.
2. Push the Arrow up or the Arrow down button to select Change direction and confirm with the OK button.
3. Then choose the direction you wish to run the motor to. The actual rotation direction is blinking. Confirm with the OK button.
4. The rotation direction changes immediately and the arrow indication in the status field changes.
Quick edit
Through the Quick edit functionality you can quickly access the desired parameter by entering the parameter’s ID number.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK but­ton.
3. Then enter the ID number of parameter or monitoring value you wish to access. Press OK but­ton to confirm.
4. Requested Parameter/Monitoring value appears on the display (in editing/monitoring mode.)
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY I/O
ID: M1
( 7 )
Monitor
( 6 )
ID:
Choose action
RUN Ready Keypad
ID:1805
Local/Remote
Control page
Change direction
ID:
Choose action
RUN Ready Keypad
ID:1805
Forward
Reverse
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY I/O
ID: M1
( 7 )
Monitor
( 6 )
FUNCT
OK OK
9163.ai
Page 90
8
vacon • 87 Options
Copying parameters
NOTE:
This feature is available with graphical keypad only. The parameter copy function can be used to copy parameters from one drive to another. The parameters are first saved to the keypad, then the keypad is detached and connected to another
drive. Finally the parameters are downloaded to the new drive restoring them from the keypad. Before any parameters can successfully be copied from one drive to another the drive has to be
stopped when the parameters are downloaded.
First go into
User settings menu and locate the Parameter backup submenu. In the Param-
eter backup
submenu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made at the fac-
tory.
By selecting
Save to keypad you can copy all parameters to the keypad.
Restore from keypad will copy all parameters from keypad to a drive.
Figure 66. Parameter copy.
NOTE: If the keypad is changed between drives of different sizes, the copied values of these param-
eters will not be used:
Motor nominal current (P3.1.1.4) Motor nominal voltage (P3.1.1.1) Motor nominal speed (P3.1.1.3) Motor nominal power (P3.1.1.6) Motor nominal frequency (P3.1.1.2) Motor cos phi (P3.1.1.5) Switching frequency (P3.1.2.3) Motor current limit (P3.1.3.1) Stall current limit (P3.9.3.2) Stall time limit (P3.9.3.3) Stall frequency (P3.9.3.4) Maximum frequency (P3.3.1.2)
STOP READY Keypad
 
Application selection
HVAC
User settings
Drive name
Drive
Parameter backup
( 3 )
ID: M6.5
STOP READY Keypad
Restore factory defaults
Parameter backup
Restore from keypad
Save to keypad
ID: M6.5.1
STOP READY Keypad
  
 
I/O and Hardware
( 8 )
Main Menu
Favourites
( 0 )
User settings
( 4 )
ID: M6
OK OK
Page 91
Options vacon • 88
Service support: find your nearest Vacon service center at www.vacon.com
8
Help texts
The graphical keypad features instant help and information displays for various items. All parameters offer an instant help display. Select Help and press the OK button. Text information is also available for faults, alarms and the startup wizard.
Figure 67. Help text example.
Adding item to favourites
You might need to refer to certain parameter values or other items often. Instead of locating them one by one in the menu structure, you may want to add them to a folder called
Favorites where they
can easily be reached. To add an item to the Favorites.
Figure 68. Adding item to Favorites.
( 6 )
Digital Inp uts
Ctrl Signal 1 A
Ctrl Signal 1 B
STOP READY I/O
ID:403 M3.5.1.1
Ctrl Signal 2 A
( 6 )
Add to favo rites
STOP READY I/O
ID:403 M3.5.1.1
Ctrl signal 1 A
Edit
Help
Start Sign al 1 for cont rol P lace I/O A . Sta rt Si gnal 1 funct ional ity chos en wi th I/ O A Logic in S tart/Sto p Set up Me nu.
STOP READY I/O
Ctrl si gnal 1 A
ID:403 M3.5.1.1
OK
OK
Basic Setti ngs
Motor Nom V oltg
230.00 V
Motor Nom S peed
1430 rpm
STOP READY I/O
Motor Nom F req
50.00 Hz
Edit
Help
Motor N om Freq
STOP READY I/O
Add to favor ites
Motor N om Freq
was added to favorites. Press OK to continue.
STOP READY I/O
OK
OK
Page 92
8
vacon • 89 Options
8.2.6 VACON® keypad with text segment display
You can also choose a Keypad with text segment display (Text keypad) for your user interface. It has mainly the same functionalities as the keypad with graphical display although some of these are somewhat limited.
8.2.6.1 Keypad display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about
his present
location in the menu structure and the item displayed. If the text on the text line is too long to fit in the display, the text will scroll from left to right to reveal the whole text string.
8.2.6.2
Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows to move between the menus. Enter the group/item by pressing the OK button and
return
to the for-
mer level by pressing the Back/Reset button.
Indicators: Status
Indicators: Alarm, Fault
Indicators: Direction
Indicators: Control place
Group or parameter name
Menu location
Page 93
Options vacon • 90
Service support: find your nearest Vacon service center at www.vacon.com
8
8.2.6.3 Using the keypad
Editing values
Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the Edit mode by pressing OK.
3. Set new value with the arrow buttons up/down. You can also move from digit to digit with the
arrow buttons left/right if the value is numerical and change then the value with the arrow but­tons up/down.
4. Confirm change with OK button or ignore change by returning to previous level with Back/
Reset button.
Figure 69. Editing values.
Resetting fault
Instructions for how to reset a fault can be found in chapter 8.2.7.
Function button
The FUNCT button is used for four functions:
1. to quickly access the Control page,
2. to easily change between the Local (Keypad) and Remote control places,
3. to change the rotation direction and
4. to quickly edit a parameter value.
Control places
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. The
Local control place
is always the keypad. The
Remote control place is determined by parameter P3.2.1 (I/O or Field-
bus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again, can bypass the
remote control place selected with parameter P3.2.1 using a digital input. The digital input is se­lected with parameter P3.5.1.7
(I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.7 through digital input while in
Remote, the control place will still switch to Keypad if Local is selected. Switching between
Local and Remote Control can be done by pressing the FUNCT-button on the keypad or by using the "Local/Remote" (ID211) parameter.
BACK
RESET
OKOKOK
Page 94
8
vacon • 91 Options
Changing control places
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the FUNCT button.
2. Using the arrow buttons, select Local/Remote and confirm with the OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the
FUNCT button was pushed.
However, if the Remote control place was changed to Local (Keypad) you will be prompted for keypad reference.
Figure 70. Changing control places.
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the
Arrow up or the Arrow down button to select Control page and confirm with the OK
button.
3. The control page appears
If keypad control place and keypad reference are selected to be used you can set the
Keypad
Reference
after having pressed the OK button. If other control places or reference values are
used the display will show Frequency reference which is not editable.
Figure 71. Accessing Control page.
FUNCT
OK OK
9169.emf
9170.emf
FUNCT
OK
OK
Page 95
Options vacon • 92
Service support: find your nearest Vacon service center at www.vacon.com
8
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT button.NOTE! Chang-
ing direction
command is not visible in the menu unless the selected control place is Local.
1. Anywhere in the menu structure, push the Funct button.
2. Push the Arrow up or the Arrow down button to select Change direction and confirm with the OK
button.
3. Then choose the direction you wish to run the motor to. The actual rotation direction is blinking.
Confirm with the OK button.
4. The rotation direction changes immediately and the arrow indication in the status field changes.
Quick edit
Through the Quick edit functionality you can quickly access the desired parameter by entering the parameter’s ID number.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK but-
ton.
3. Then enter the ID number of parameter or monitoring value you wish to access. Press OK but-
ton to confirm.
4. Requested Parameter/Monitoring value appears on the display (in editing/monitoring mode.)
Page 96
8
vacon • 93 Options
8.2.7 Fault Tracing
When an unusual operating condition is detected by the AC drive control diagnostics, the drive ini­tiates a notification visible, for example, on the keypad. The keypad will show the code, the name and a short description of the fault or alarm.
The notifications vary in consequence and required action.
Faults make the drive stop and require
reset of the drive.
Alarms inform of unusual operating conditions but the drive will continue run-
ning.
Info may require resetting but do not affect the functioning of the drive.
For some faults you can program different responses in the application. See parameter group Pro­tections.
The fault can be reset with the
Reset button on the control keypad or via the I/O terminal. The faults
are stored in the Fault history menu which can be browsed. The different fault codes you will find in the table below.
NOTE: When contacting distributor or factory because of a fault condition, always write down all
texts and codes on the keypad display.
Fault appears
When a fault appears and the drive stops examine the cause of fault, perform the actions advised here and reset the fault as instructed below.
1. With a long (1 s) press on the
Reset button on the keypad or
2. By entering the
Diagnostics Menu (M4), entering Reset faults (M4.2) and selecting Reset faults
parameter.
3.
For keypad with LCD display only: By selecting value Yes for the parameter and clicking OK.
Figure 72. Diagnostic menu with graphical keypad.
Figure 73. Diagnostic menu with text keypad.
Main Menu
( 5 )
Monito r
Parame ters
( 12 )
Diagno stics
( 6 )
ID: M4
STOP READY I/O
Diagnostics
Active faul ts
( 0 )
Fault histo ry
( 39 )
ID: M4.1
STOP READY I/O
Reset fa ults
Reset faults
Reset fault s
Help
ID: M4 .2
STOP READY I/O
OK
OK
OK
OK
Page 97
Options vacon • 94
Service support: find your nearest Vacon service center at www.vacon.com
8
8.2.7.1 Fault History
In menu M4.3 Fault history you find the maximum number of 40 occurred faults. On each fault in the memory you will also find additional information, see below.
Figure 74. Fault history menu with graphical keypad.
Figure 75. Fault history menu with text keypad.
Diagnostics
Active faul ts
( 0 )
Reset faults
Fault history
( 39 )
ID: M4.1
STOP READY I/O
 
!
!
!
Fault history
External Fault
Fault old
51
891384s
External Fault
Fault old
51
871061s
Device removed
Info old
39
862537s
ID:
STOP READY I/O
!
Device remo ved
ID: M4.3.3.2
Code 39
ID 380
State Info old
Date 7.12.2009
Time 04:46:33
Operating time 862537s
STOP READY I/O
OKOKOK
Page 98
8
vacon • 95 Options
8.2.7.2 Fault codes
Fault
code
Fault
ID
Fault name Possible cause Remedy
1
1
Overcurrent (hardware fault)
AC drive has detected too high a cur­rent (>4*I
H
) in the motor cable:
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
Check loading. Check motor. Check cables and connections. Make identification run. Check ramp times.
2
Overcurrent (software fault)
2
10
Overvoltage (hardware fault)
The DC-link voltage has exceeded the limits defined.
• too short a deceleration time
• brake chopper is disabled
• high overvoltage spikes in supply
• Start/Stop sequence too fast
Make deceleration time longer. Use brake chopper or brake resistor (available as options). Activate overvoltage controller. Check input voltage.
11
Overvoltage (soft­ware fault)
3
20
Earth fault (hard­ware fault)
Current measurement has detected that the sum of motor phase current is not zero.
• insulation failure in cables or motor
Check motor cables and motor.
21
Earth fault (soft­ware fault)
540
Charging switch
The charging switch is open, when the START command has been given.
• faulty operation
• component failure
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
760
Saturation
Various causes:
• defective component
• brake resistor short-circuit or overload
Cannot be reset from keypad. Switch off power. DO NOT RE-CONNECT POWER! Contact factory. If this fault appears simultane­ously with F1, check motor cables and motor.
Table 32. Fault codes and descriptions.
Page 99
Options vacon • 96
Service support: find your nearest Vacon service center at www.vacon.com
8
8
600
System fault
Communication between control board and power unit has failed.
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
601
Communication between control board and power unit has interference, but it is still working.
602
Watchdog has reset the CPU
603
Voltage of auxiliary power in power unit is too low.
604
Phase fault: Voltage of an output phase does not follow the reference
605
CPLD has faulted but there is no detailed information about the fault
606
Control and power unit software are incompatible
Update software. Should the fault re-occur, contact the dis­tributor near to you.
607
Software version cannot be read. There is no software in power unit.
Update power unit software. Should the fault re-occur, con­tact the distributor near to you.
608
CPU overload. Some part of the soft­ware (for example application) has caused an overload situation. The source of fault has been suspended
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
609
Memory access has failed. For exam­ple, retain variables could not be restored.
610
Necessary device properties cannot be read.
614
Configuration error.
647
Software error
Update software. Should the fault re-occur, contact the dis­tributor near to you.
648
Invalid function block used in applica­tion. System software and application are not compatible.
649
Resource overload. Error when loading parameter initial values. Error when restoring parameters. Error when saving parameters.
9
80
Undervoltage (fault)
DC-link voltage is under the voltage limits defined.
• most probable cause: too low a supply voltage
• AC drive internal fault
• defect input fuse
• external charge switch not closed
NOTE! This fault is activated only if the
drive is in Run state.
In case of temporary supply voltage break reset the fault and restart the AC drive. Check the supply voltage. If it is ade­quate, an internal failure has occurred. Contact the distributor near to you.
81
Undervoltage (alarm)
10 91
Input phase Input line phase is missing.
Check supply voltage, fuses and cable.
Fault
code
Fault
ID
Fault name Possible cause Remedy
Table 32. Fault codes and descriptions.
Page 100
8
vacon • 97 Options
11 100
Output phase supervision
Current measurement has detected that there is no current in one motor phase.
Check motor cable and motor.
12
110
Brake chopper supervision (hardware fault)
No brake resistor installed. Brake resistor is broken. Brake chopper failure.
Check brake resistor and cabling. If these are ok, the chopper is faulty. Contact the distributor near to you.
111
Brake chopper saturation alarm
13 120
AC drive under­temperature (fault)
Too low temperature measured in power unit’s heatsink or board. Heat­sink temperature is under -10°C.
Check the ambient tempera­ture
14
130
AC drive over­temperature (fault, heatsink)
Too high temperature measured in power unit’s heatsink or board. Heat­sink temperature is over 100°C.
Check the correct amount and flow of cooling air. Check the heatsink for dust. Check the ambient tempera­ture. Make sure that the switching frequency is not too high in relation to ambient tempera­ture and motor load.
131
AC drive over­temperature (alarm, heatsink)
132
AC drive over­temperature (fault, board)
133
AC drive over­temperature (alarm, board)
15 140
Motor stalled Motor is stalled. Check motor and load.
16 150
Motor overtem­perature
Motor is overloaded.
Decrease motor load. If no motor overload exists, check the temperature model parameters.
17 160
Motor underload Motor is underloaded. Check load.
19
180
Power overload (short-time supervision)
Drive power is too high. Decrease load.
181
Power overload (long-time super­vision)
25
240
Motor control fault
Start angle identification has failed.
Reset the fault and restart. Should the fault re-occur, con­tact the distributor near to you.
241
Generic motor control fault.
26 250
Start-up pre­vented
Start-up of the drive has been pre­vented. Run request is ON when a new software (firmware or application), parameter setting or any other file, which has affects the operation of the drive, has been loaded to drive.
Reset the fault and stop the AC drive. Load the software and start the AC drive.
30 530
STO fault
Emergency stop button has been con­nected or some other STO operation has been activated.
When the STO function is acti­vated, the drive is in safe state.
32 312
Fan cooling Fan life time is up.
Change fan and reset fan life time counter.
Fault
code
Fault
ID
Fault name Possible cause Remedy
Table 32. Fault codes and descriptions.
Loading...