NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from www.vacon.com/downloads
.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde
applicables sur le site www.vacon.com/downloads
.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 - Startupvacon • 2
OK
BACK
RESET
1.VACON 100 - STARTUP
1.1Startup Wizard
In the Startup Wizard, you will be prompted for essential information needed by the drive so that
it can start controlling your process. In the Wizard, you will need the following keypad buttons:
Left/Right arrows. Use these to easily move between digits and decimals.
Up/Down arrows. Use these to move between options in menu and to change value.
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can return to the previous question in the
Wizard. If pressed at the first question, the Startup Wizard will be cancelled.
Once you have connected power to your Vacon 100 frequency converter, follow these instructions
to easily set up your drive.
NOTE! You can have your AC drive equipped with a keypad with either a graphical or an LCD display.
1
2
3
4
5
Language selectionDepends on language package
Russia
Daylight saving
Time*hh:mm:ss
Day*dd.mm.
Year*yyyy
*
US
EU
OFF
* These questions appear if battery is installed
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
vacon • 3Vacon 100 - Startup
6
Push the OK button unless you want to set all parameter values manually.
7
8
9
10
11
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by activating the parameter Restore factory defaults (pa-
rameter P6.5.1) in the Parameter backup submenu (M6.5) OR with parameter P1.19 in the Quick
setup menu.
Run Startup Wizard?
Choose your process
Set value for Motor nominal speed
(according to nameplate)
Set value for Motor nominal current
(according to nameplate)
Set value
Set
value
for
Minimum frequencyRange: 0.00...50.00 Hz
for
Maximum frequencyRange: 0.00...320.00 Hz
Yes
No
Pump
Fan
Range: 24...19,200 rpm
Range: Varies
1.2PID Mini-Wizard
The PID mini wizard is activated in the Quick Setup menu. This wizard presupposes that you are
going to use the PID controller in the "one feedback / one setpoint" mode. The control place will be
I/O A and the default process unit ‘%’.
The PID mini wizard asks for the following values to be set:
1
If any other process unit than ‘%’ is selected the following questions appear: If not the Wizard will
directly jump to step 5
2
3
4
5
If one of the analogue input signals is selected the question 6 appears. Otherwise you will be taken
to question 7.
Process unit selection(Several selections. See par. P3.12.1.4).
.
Process unit min
Process unit max
Process unit decimals0...4
Feedback 1 source selection
See Chapter 3.6.14.3 on page 71 for
selections.
1
6
Analogue input signal range
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
See page 57.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 - Startupvacon • 4
7
8
If one of the analogue input signals is selected the question 9 appears. Otherwise you will be taken
to question
If either of the options Keypad Setpoint 1 or 2 is chosen the question 10
9
10
11
If option ‘Yes’ is selected you will be prompted for three more values:
12
13
Error inversion
Setpoint source selectionSee page 74 for selections.
11.
Analogue input signal range
Keypad setpoint
Sleep function?
Sleep frequency limit 10.00...320.00 Hz
Sleep delay 10...3000 s
0 = Normal
1 = Inverted
will appear.
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
See page 57.
No
Yes
14
1.3Multi-pump mini-wizard
The Multi-Pump mini-wizard asks the most important questions for setting up a Multi-Pump system. The PID mini-wizard always precedes the Multi-Pump mini-wizard. The keypad will guide you
through the questions as in Chapter 1.2 then to be followed by the set of questions below:
15
16
17
If Autochange function is enabled the following three questions will appear. If Autochange will not
be used the Wizard jumps directly to question 21.
18
19
Wake-up level 1
Number of motors1...4
Interlock function
Autochange
Include FC
Autochange interval0.0...3000.0 h
Range depends on selected process
unit.
0 = Not used
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
20
21
22
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Autochange: Frequency limit0.00...50.00 Hz
Bandwidth0...100%
Bandwidth delay0...3600 s
1
vacon • 5Vacon 100 - Startup
Start Fire Moode
Wizard
Fire Mode already
Enabled ?
Ask: Continue
Wizard?
Continue Wizard?
Ask parameter:
Fire Mode Freq Reference
Source
FireModeFrequency
selected to Frequency
Reference ?
Ask parameter:
Fire Mode Frequency
Ask parameter:
Activation Signal Type
Activation signal type?
(Open / Close)
Ask parameter:
Fire Mode Activ. Close
Ask parameter:
Fire Mode Activ. Open
Ask parameter:
Fire Mode Reverse
Ask parameter:
Fire Mode Password
Finished!
YES
NO
NO
YES
OPEN
CLOSE
NO
YES
7073.emf
After this, the keypad will show the digital input and relay output configuration done by the
application (graphical keypad only). Write these values down for future reference.
1.4Fire Mode wizard
The Fire Mode wizard is intended for easy commissioning of the Fire Mode function. The Fire Mode
wizard can be initiated by choosing Activate for parameter P1.20 in the Quick setup menu. Fire Mode
wizard asks the most important questions for setting up a Fire Mode function.
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 6
LOC
REM
9086.emf
Scroll menu up
Increase value
Scroll menu down
Decrease value
Move cursor leftMove cursor right
Move backward in menu
Exit edit mode
Reset faults with long press
Change control place
Access control page
Change direction
See ch. 2.2.1.3 for
more information
Stop buttonStart button
Enter active level/item
Confirm selection
Enter edit mode
Bypass property page
2.KEYPADOFTHEDRIVE
The control keypad is the interface between the Vacon 100 frequency converter and the user. With
the control keypad it is possible to control the speed of a motor, to supervise the state of the
equipment and to set the frequency converter's parameters.
There are two keypad types you can choose for your user interface: Keypad with graphical display
and keypad with text segment display (text keypad).
The button section of the keypad is identical for both keypad types.
Figure 1. Keypad buttons
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 7Keypad of the drive
9159.emf
( 17 )
( 12 )
STOPREADYI/O
ID:M1
( 5 )
Main Menu
Quick Setup
Parameters
Monitor
Status field
STOP/RUN
Direction
ALARM
Status field
READY/NOT READY/FAULT
Control place:
PC/IO/KEYPAD/FIELDBUS
Activated group/item:
Press OK to enter
Number of items
in the group
Location field
(Parameter ID number and
current menu location
2.1Vacon keypad with graphical display
The graphical keypad features an LCD display and 9 buttons.
2.1.1Keypad display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or
drive functions. On the display, the user sees information about
structure and the item displayed.
See the attached Keypad Navigation Map to get a comprehensive idea of the menu structure.
his present
location in the menu
2.1.1.1
The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows
to move between the menus. Enter the group/item by pressing the OK button and
mer level by pressing the Back/Reset button.
The Location field indicates your current location. The Status field gives information about the
present status of the drive. See Figure 1.
Main menu
return
to the for-
2.1.2Using the graphical keypad
2.1.2.1
Change value of a parameter following the procedure below:
1.Locate the parameter.
2.Enter the Edit mode.
2
3.Set new value with the arrow buttons up/down. You can also move from digit to digit with the
arrow buttons left/right if the value is numerical and change then the value with the arrow buttons up/down.
4.Confirm change with OK button or ignore change by returning to previous level with Back/
Reset button.
Editing values
Figure 2. Main menu
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 8
STOPREADYI/O
ID:172M3.2.1
STOPREADYI/O
ID:M3.2.1
STOPREADYI/O
M3.2.1
STOPREADYI/O
ID:172M3.2.1
STOPREADYI/O
M3.2.1
9160.emf
BACK
RESET
OR:
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
Edit
Help
Add to favorites
Rem Control PlaceRem Control Place
I/O Control
FieldbusCTRL
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
Rem Control Place
I/O Control
FieldbusCTRL
Figure 3. Editing values on graphical keypad
2.1.2.2Resetting fault
Instructions for how to reset a fault can be found in Chapter 3.8.1 on page 110.
2.1.2.3
Local/Remote control button
The LOC/REM button is used for two functions: to quickly access the Control page and to easily
change between the Local (Keypad) and Remote control places.
Control places
The control place is the source of control where the drive can be started and stopped. Every
control place has its own parameter for selecting the frequency reference source. In the HVAC
drive, the Local control place is always the keypad. The Remote control place is determined by
parameter P1.15 (I/O or Fieldbus). The selected control place can be seen on the status bar of the
keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest
priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again, can bypass
the remote control place selected with parameter P3.2.1 using a digital input. The digital input is
selected with parameter P3.5.1.5 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than
remote control. Therefore, if, for example, bypassed by parameter P3.5.1.5 through digital input
while in Remote, the control place will still switch to Keypad if Local is selected. Switching
between Local and Remote Control can be done by pressing the Loc/Rem-button on the keypad or
by using the "Local/Remote" (ID211) parameter.
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Local/Remote and confirm with the
OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the Loc/Rem button was pushed.
Changing control places
However, if the Remote control place was changed to Local (Keypad) you will be prompted for
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 9Keypad of the drive
( 21 )
STOPREADYKeypad
ID:M1
( 12 )
( 6 )
ID:
STOPReadyKeypad
ID:1805
?
ID:
STOPREADYKeypad
ID:211
( 21 )
STOPREADYI/O
ID:M1
( 12 )
( 6 )
11114.emf
Remote
Main Menu
Parameters
Diagnostics
Monitor
Choose action
Local/Remote
Control page
Local/Remote
Remote
Local
Main Menu
Parameters
Diagnostics
Monitor
( 21 )
STOPREADYI/O
ID:M1
( 12 )
( 6 )
ID:
STOPReadyKeypad
ID:1805
STOPREADYKeypad
( 6 )
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
ID:184
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
STOPREADYKeypad
( 6 )
ID:168
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
11115.emf
Keypad Reference
Main Menu
Parameters
Diagnostics
Monitor
Choose action
Local/Remote
Control page
Output Frequency
Motor Current
Motor Torque
Motor Power
Keypad Reference
Output Frequency
Motor Current
Motor Torque
Motor Power
keypad reference.
Figure 4. Changing control places
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Control page and confirm with the
OK button.
3. The control page appears.
If keypad control place and keypad reference are selected to be used you can set the Keypad reference after having pressed the OK button. If other control places or reference values are
used the display will show Frequency reference which is not editable. The other values on the
page are Multimonitoring values. You can choose which values appear here for monitoring (for
this procedure, see page 16).
2
Figure 5. Accessing Control page
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 10
STOPREADYKeypad
( 0 )
( 4 )
ID:M6
( 8 )
STOPREADYKeypad
( 3 )
ID:M6. 5M6.5
STOPREADYKeypad
ID:P6.5.2
11088.emf
Main Menu
Favourites
User settings
I/O and Hardware
Parameter compare
( 4 )
User settings
Language selection
English
Parameter backup
Restore from keypad
Restore factory defaults
Save to keypad
Parameter backup
2.1.2.4Copying parameters
NOTE! This feature is available in graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to another
drive. Finally the parameters are downloaded to the new drive restoring them from the keypad.
Before any parameters can successfully be copied from one drive to another the drive has to be
stopped when the parameters are downloaded.
• First go into User settings menu and locate the Parameter backup submenu.
In the Parameter backup submenu, there are three possible functions to be selected:
• Restore factory defaults will re-establish the parameter settings originally made
at the factory.
•By selecting Save to keypad you can copy all parameters to the keypad.
• Restore from keypad will copy all parameters from keypad to a drive.
Figure 6. Parameter copy
NOTE! If the keypad is changed between drives of different sizes, the copied values of these
parameters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phii (P3.1.1.5)
Switching frequency (P3.1.2.1)
Motor current limit (P3.1.1.7)
Stall current limit (P3.9.5)
Stall time limit (P3.9.13)
Stall frequency (P3.9.14)
Maximum frequency (P3.3.2)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 11Keypad of the drive
( 6 )
STOPREADYI/O
ID:403P3.5.1.1
( 6 )
STOPREADYI/O
ID:403P3.5.1.1
STOPREADYI/O
ID:403
P3.5.1.1
9165.emf
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 1 B
Ctrl Signal 2 A
Add to favorites
Ctrl signal 1 A
Edit
Help
Start Signal 1 for control Place
I/O A. Start Signal 1
functionality chosen with I/O A
Logic in Start/Stop Setup Menu.
Ctrl signal 1 A
230.00 V
1430 rpm
STOPREADYI/O
50.00 Hz
STOPREADYI/OSTOPREADYI/O
9166.emf
Basic Settings
Motor Nom Voltg
Motor Nom Speed
Motor Nom Freq
Edit
Help
Motor Nom Freq
Add to favorites
Motor Nom Freq
was added to
favorites. Press OK
to continue.
2.1.2.5Help texts
The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the startup wizard.
Figure 7. Help text example
2.1.2.6Adding item to favourites
You might need to refer to certain parameter values or other items often. Instead of locating them
one by one in the menu structure, you may want to add them to a folder called Favourites where
they can easily be reached.
To remove an item from the Favourites, see Chapter 2.3.7.
Figure 8. Adding item to Favourites
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 12
9167.emf
READYRUNSTOPALARMFAULT
FWDREVI/OBUSKEYPAD
Indicators:
Status
Indicators:
Alarm, Fault
Indicators:
Direction
Indicators:
Control place
Group or parameter name
Menu location
2.2Vacon keypad with text segment display
You can also choose a Keypad with text segment display (Text keypad) for your user interface.
It has mainly the same functionalities as the keypad with graphical display although some of these
are somewhat limited.
2.2.1Keypad display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or
drive functions. On the display, the user sees information about
structure and the item displayed. If the text on the text line is too long to fit in the display, the text
will scroll from left to right to reveal the whole text string.
his present
location in the menu
2.2.1.1
Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows
return
to move between the menus. Enter the group/item by pressing the OK button and
to the
former level by pressing the Back/Reset button.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 13Keypad of the drive
9168.emf
BACK
RESET
2.2.2Using the keypad
2.2.2.1
Editing values
Change value of a parameter following the procedure below:
1.Locate the parameter.
2.Enter the Edit mode by pressing OK.
3.Set new value with the arrow buttons up/down. You can also move from digit to digit with the
arrow buttons left/right if the value is numerical and change then the value with the arrow buttons up/down.
4.Confirm change with OK button or ignore change by returning to previous level with Back/
Reset button.
Figure 9. Editing values
2.2.2.2Resetting fault
Instructions for how to reset a fault can be found in Chapter 3.8.1 on page 110.
2.2.2.3
Local/Remote control button
The LOC/REM button is used for two functions: to quickly access the Control page and to easily
change between the Local (Keypad) and Remote control places.
Control places
The control place is the source of control where the drive can be started and stopped. Every
control place has its own parameter for selecting the frequency reference source. In the HVAC
drive, the Local control place is always the keypad. The Remote control place is determined by
parameter P1.15 (I/O or Fieldbus). The selected control place can be seen on the status bar of the
keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest
priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again, can bypass
the remote control place selected with parameter P3.2.1 using a digital input. The digital input is
selected with parameter P3.5.1.5 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than
remote control. Therefore, if, for example, bypassed by parameter P3.5.1.5 through digital input
while in Remote, the control place will still switch to Keypad if Local is selected. Switching
between Local and Remote Control can be done by pressing the Loc/Rem-button on the keypad or
by using the "Local/Remote" (P3.2.2) parameter.
2
Changing control places
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 14
11089.emf
11090.emf
Change of control place from Remote to Local (keypad).
1.Anywhere in the menu structure, push the Loc/Rem button.
2.Using the arrow buttons, select Local/Remote and confirm with the OK button.
3.On the next display, select Local or Remote and again confirm with the OK button.
4.The display will return to the same location as it was when the Loc/Rem button was pushed.
However, if the Remote control place was changed to Local (Keypad) you will be prompted for
keypad reference.
Figure 10. Changing control places
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Control page and confirm with the
OK button.
3. The control page appears.
If keypad control place and keypad reference are selected to be used you can set the Keypad reference after having pressed the OK button. If other control places or reference values are
used the display will show Frequency reference which is not editable.
Figure 11. Accessing Control page
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 15Keypad of the drive
2.3Menu structure
Click on and select the item you wish to receive more information about (electronic manual).
Table 1. Keypad menus
Quick setupSee Chapter 3.4.
MonitorMulti-monitor*
Basic
Timer functions
PID Controller 1
PID Controller 2
Multi-Pump
Fieldbus data
Temperature inputs
ParametersSee Chapter 3.
DiagnosticsActive faults
Reset faults
Fault history
Total counters
Trip counters
Software info
I/O and
hardware
User settingsLanguage selections
Favourites
*
Basic I/O
Slot D
Slot E
Real time clock
Power unit settings
Keypad
RS-485
Ethernet
Application selection
Parameter backup*
Drive name
See Chapter 2.1.2.6.
2
User levelsSee Chapter 2.3.8.
* Not available in text keypad
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 16
( 4 )
( 12 )
ID:M1
STOPREADYI/O
( 5 )
(13)
(10)
STOPREADYI/O
ID:M2.1
0.0rpm
STOPREADYI/O
0.00 Hz
ID25
0.00Hz
0.00A
0.00%
20.0 Hz
0.0V
0.0V81.9°C0.0%
ID:1M2.1.1.1
STOPReadyI/O
0.00 Hz
10.00 Hz
0.00 rpm
0.00 A
0.00 %
0.00 %
11116.emf
(13)
Main Menu
Quick Setup
Parameters
Monitor
Monitor
Multimonitor
Basic
Timer functions
Multimonitor
FreqReference
Output Freq
Motor Curre
Motor Torque
Motor Voltage
Motor Speed
Motor TemperaUnit TemperaDC-link volt
FreqReferenc
FreqReference
Output frequency
Motor Power
FreqReference
Motor Speed
Motor Current
Motor Torque
2.3.1Quick setup
The Quick Setup Menu includes the minimum set of most commonly used parameters during installation and commissioning. More detailed information on the parameters of this group you will
find in Chapter 3.4.
2.3.2Monitor
Multi-monitor
NOTE!This menu is not available in text keypad.
On the multi-monitor page, you can collect nine values that you wish to monitor.
Change the monitored value by activating the value cell (with arrow buttons left/right) and clicking
OK. Then choose a new item on the Monitoring values list and click OK again.
Basic
The basic monitoring values are the actual values of selected parameters and signals as well as
statuses and measurements. Different applications may have different and different number of
monitoring values.
Timer functions
Monitoring of timer functions and the Real Time Clock. See Chapter 3.5.3.
PID Controller 1
Monitoring of PID controller values. See Chapter and Chapter 3.5.5.
PID Controller 2
Monitoring of PID controller values. See Chapter and Chapter 3.5.5.
Multi-Pump
Monitoring of values related to the use of several drives. See Chapter 3.5.6.
Fieldbus data
Fieldbus data shown as monitor values for debugging purposes at e.g. fieldbus commissioning. See
Chapter 3.5.7.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 12. Multi-monitoring page
2
vacon • 17Keypad of the drive
2.3.3Parameters
Through this submenu, you can reach the application parameter groups and parameters. More information on parameters in Chapter 3.
2.3.4Diagnostics
Under this menu, you can find Active faults, Reset faults, Fault history, Counters and Software info.
2.3.4.1
MenuFunctionNote
Active faultsWhen a fault/faults appear(s), the
2.3.4.2Reset faults
MenuFunctionNote
Reset faults
Active faults
display with the name of the fault
starts to blink. Press OK to return
to the Diagnostics menu. The
Active faults submenu shows the
number of faults. Select the fault
and push OK to see the fault-time
data.
In this menu you can reset faults.
For closer instructions, see
Chapter 3.8.1.
The fault remains active until it is
cleared with the Reset button (push
for 2 s) or with a reset signal from the
I/O terminal or fieldbus or by
choosing Reset faults (see below).
The memory of active faults can store
the maximum of 10 faults in the order
of appearance.
Control signal before resetting the
fault to prevent unintentional restart
of the drive.
CAUTION! Remove external
2.3.4.3Fault history
MenuFunctionNote
Fault history
40 latest faults are stored in the
Fault history.
Entering the Fault history and clicking
OK on the selected fault shows the
fault time data (details).
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 18
2.3.4.4Total counters
Table 2: Diagnostics menu, Total counters parameters
IndexParameterMinMaxUnitDefaultIDDescription
Amount of energy taken from
supply network. No reset.
NOTE FOR TEXT KEYPAD:
The highest energy unit
V4.4.1Energy counterVaries2291
V4.4.3
V4.4.4
V4.4.5
V4.4.6
V4.4.7
V4.4.8
V4.4.9
V4.4.10
V4.4.11
V4.4.12
V4.4.13
V4.4.14
V4.4.15
Operating time
(graphical keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Run time
(graphical keypad)
Run time
(text keypad)
Run time
(text keypad)
Run time
(text keypad)
Power on time
(graphical keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Start command
counter
a d hh:min2298 Control unit operating time.
a
d
hh:min:ss
a d hh:min2293 Motor running time.
a
d
hh:min:ss
a d hh:min2294
aPower on time in total years.
dPower on time in total days.
hh:min:ss
shown on the standard keypad is MW. Should the
counted energy exceed 999.9
MW, no unit is shown on the
keypad.
Control unit operating time in
total years.
Control unit operating time in
total days.
Control unit operating time in
hours, minutes and seconds.
Motor running time in total
years.
Motor running time in total
days.
Motor running time in hours,
minutes and seconds
Amount of time the power
unit has been powered so far.
No reset.
Power on time in hours,
minutes and seconds.
The number of times the
2295
power unit has been started.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Resettable energy counter.
NOTE FOR TEXT KEYPAD:
The highest energy unit
shown on the standard
keypad is MW. Should the
counted energy exceed 999.9
MW, no unit is shown on the
P4.5.1Energy trip counterVaries2296
P4.5.3
P4.5.4
P4.5.5
P4.5.6
Operating time
(graphical keypad)
Operating time
(standard keypad)
Operating time
(standard keypad)
Operating time
(standard keypad)
a d hh:min2299 Resettable. See P4.5.1.
aOperating time in total years.
dOperating time in total days.
hh:min:ss
keypad.
To reset the counter:
Standard text keypad:
Apply a long (4 s) push on the
OK button.
Graphical keypad:
Push OK once.
counter
Push OK once again.
Operating time in hours,
minutes and seconds.
Reset
page will appear.
2.3.4.6Software info
Table 4: Diagnostics menu, Software info parameters
IndexParameterMinMaxUnitDefaultIDDescription
V4.6.1
V4.6.2
V4.6.3
V4.6.4System load0100%2300 Load on control unit CPU.
V4.6.5
V4.6.6Application ID837 Application code.
V4.6.7Application version838
Software package
(graphical keypad)
Software package ID
(text keypad)
Software package
version
(text keypad)
Application name
(graphical keypad)
2524
Code for software
identification.
2525 Name of application.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 20
2.3.5I/O and hardware
Various options-related settings are located in this menu.
2.3.5.1
Basic I/O
Monitor here the statuses of inputs and outputs.
Table 5: I/O and Hardware menu, Basic I/O parameters
IndexParameterMinMaxUnitDefaultIDDescription
V5.1.1Digital input 1012502 Status of digital input signal
V5.1.2Digital input 2012503 Status of digital input signal
V5.1.3Digital input 3012504 Status of digital input signal
V5.1.4Digital input 4012505 Status of digital input signal
V5.1.5Digital input 5012506 Status of digital input signal
V5.1.6Digital input 6012507 Status of digital input signal
Shows the selected (with
V5.1.7Analogue input 1 mode1
V5.1.8Analogue input 10100%2509
V5.1.9Analogue input 2 mode1
V5.1.10Analogue input 20100%2511
V5.1.11
V5.1.12Analogue output 10100%2513
Analogue output 1
mode
-30...
+200°C
-30...
+200°C2510
-30...
1
+200°C2512
jumper) mode for Analogue
2508
input signal
1 = 0...20 mA
3 = 0...10 V
Status of analogue input
signal
Shows the selected (with
jumper) mode for Analogue
input signal
1 = 0...20 mA
3 = 0...10 V
Status of analogue input
signal
Shows the selected (with
jumper) mode for Analogue
otuput signal
1 = 0...20 mA
3 = 0...10 V
Status of analogue output
signal
2.3.5.2
Option board slots
The parameters of this group depend on the option board installed. If no option board is placed in
slots D or E, no parameters are visible. See Chapter 3.6.2 for the location of the slots.
As an option board is removed, info text F39 Device removed will appear on the display. See
Table 74.
MenuFunctionNote
Slot DSettingsOption board related settings.
MonitoringMonitor option board-related info.
Slot ESettingsOption board related settings.
MonitoringMonitor option board-related info.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 21Keypad of the drive
2.3.5.3Real time clock
Table 6: I/O and Hardware menu, Real time clock parameters
Daylight saving rule
1 = Off
2 = EU
3 = US
4 = Russia
2.3.5.4Power unit settings
Fan
The fan operates in optimized or always-on mode. In the optimized mode, fan speed is controlled
according to the drive‘s internal logic that receives data from temperature measurements (if
supported by the power unit) and the fan stops within 5 minutes when the drive is in Stop state. In
always-on mode, the fan runs at full speed, without stopping.
Table 7: Power unit settings, Fan
IndexParameterMinMaxUnitDefaultIDDescription
V5.5.1.1Fan control mode0112377
M5.6.1.5Fan lifetimeN/AN/A0849 Fan lifetime
M5.6.1.6
M5.6.1.7Fan lifetime resetN/AN/A0823 Fan lifetime reset
Sine filter support restricts overmodulation depth and prevents thermal management functions
from decreasing switching frequency.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 22
Table 9: Power unit settings, Sine filter
IndexParameterMinMaxUnitDefaultIDDescription
P5.6.4.1Sine filter0102507
0 = Disabled
1 = Enabled
2.3.5.5Keypad
Table 10: I/O and Hardware menu, Keypad parameters
IndexParameterMinMaxUnitDefaultIDDescription
Time after which the display
P5.7.1Timeout time060min0804
P5.7.2Default page0402318
P5.7.3Menu index2499
P5.7.4Contrast* 3070%50830
P5.7.5Backlight time060min5818
returns to page defined with
parameter P5.7.2.
0 = Not used
0 = None
1 = Enter menu index
2 = Main menu
3 = Control page
4 = Multimonitor
Set menu index for desired
page and activate with
parameter P5.7.2 = 1.
Set contrast of the display
(30...70%).
Set the time until the
backlight of the display turns
off (0...60 min). If set to 0 s,
backlight is always on.
* Only available with graphical keypad
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 23Keypad of the drive
2.3.5.6Fieldbus
Parameters related to different fieldbus boards can also be found in the I/O and Hardware menu.
These parameters are explained in more detail in the respective fieldbus manual.
Baud rate
Parity type
Stop bits
Communication timeout
Operate mode
MonitoringFieldbus protocol status
Communication status
Illegal functions
Illegal data addresses
Illegal data values
Slave device busy
Memory parity error
Slave device failure
Last fault response
Control word
Status word
N2ParametersDevice address
Communication timeout
MonitoringFieldbus protocol status
Communication status
Invalid data
Invalid commands
Command not accepted
Control word
Status word
RS-485BACnet MS/TPParametersBaud rate
Autobauding
MAC address
Instance number
Communication timeout
MonitoringFieldbus protocol status
Communication status
Actual instance number
Fault code
Control word
Status word
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drivevacon • 24
EthernetCommon settingsIP address mode
Fixed IP
IP address
Subnet mask
Default gateway
Modbus/TCPCommon settingsConnection limit
Monitoring*Fieldbus protocol status
BACnet/IPSettingsInstance number
MonitoringFieldbus protocol status
* Will appear only after connection has been established
IP address
Subnet mask
Default gateway
Slave address
Communication timeout
Communication status
Illegal functions
Illegal data addresses
Illegal data values
Slave device busy
Memory parity error
Slave device failure
Last fault response
Control word
Status word
Communication timeout
Protocol in use
BBMD IP
BBMD Port
Time to live
Communication status
Actual instance number
Control word
Status word
Table 11: RS-485 common settings
IndexParameterMinMaxUnitDefaultIDDescription
0 = No protocol
P5.8.1.1Protocol0902208
Table 12: ModBus RTU parameters (This table is only visible when P5.8.1.1 Protocol = 4/
Modbus RTU)
IndexParameterMinMaxUnitDefaultIDDescription
P5.8.3.1.1Slave address124712320 Slave address
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4 = Modbus RTU
5 = N2
9 = BACnet MSTP
2
vacon • 25Keypad of the drive
Table 12: ModBus RTU parameters (This table is only visible when P5.8.1.1 Protocol = 4/