Vacon 100 hvac ac drives application manual

vacon 100 hvac
®
ac drives
application manual
vacon • 0
TABLE OF CONTENTS
Order code: DOC-APP02456+DLUK
Revision release date: 19.11.13
Corresponds to application package FW0065V021.vcx
1. Vacon 100 - Startup..........................................................................................2
1.1 Startup Wizard ...................................................................................................................2
1.2 PID Mini-Wizard .................................................................................................................3
1.3 Multi-pump mini-wizard ....................................................................................................4
1.4 Fire Mode wizard................................................................................................................5
2. Keypad of the drive ..........................................................................................6
2.1 Vacon keypad with graphical display .................................................................................7
2.1.1 Keypad display ...................................................................................................................7
2.1.2 Using the graphical keypad ...............................................................................................7
2.2 Vacon keypad with text segment display.........................................................................12
2.2.1 Keypad display .................................................................................................................12
2.2.2 Using the keypad..............................................................................................................13
2.3 Menu structure ................................................................................................................15
2.3.1 Quick setup.......................................................................................................................16
2.3.2 Monitor .............................................................................................................................16
2.3.3 Parameters ......................................................................................................................17
2.3.4 Diagnostics.......................................................................................................................17
2.3.5 I/O and hardware..............................................................................................................20
2.3.6 User settings ....................................................................................................................28
2.3.7 Favourites.........................................................................................................................29
2.3.8 User levels .......................................................................................................................29
3. Vacon HVAC Application .................................................................................30
3.1 Specific functions of Vacon HVAC application .................................................................30
3.2 Example of control connections ......................................................................................31
3.3 Isolating digital inputs from ground ................................................................................33
3.4 HVAC Application - Quick setup parameter group ..........................................................34
3.5 Monitor group...................................................................................................................36
3.5.1 Multimonitor.....................................................................................................................36
3.5.2 Basic.................................................................................................................................36
3.5.3 Timer functions monitoring .............................................................................................38
3.5.4 PID1 controller monitoring..............................................................................................39
3.5.5 PID2 controller monitoring..............................................................................................39
3.5.6 Multi-pump monitoring....................................................................................................39
3.5.7 Fieldbus data monitoring.................................................................................................40
3.5.8 Temperature inputs monitoring ......................................................................................41
3.6 Vacon HVAC Application - Application parameter lists...................................................42
3.6.1 Column explanations .......................................................................................................43
3.6.2 Parameter programming.................................................................................................44
3.6.3 Group 3.1: Motor settings ................................................................................................48
3.6.4 Group 3.2: Start/Stop setup .............................................................................................51
3.6.5 Group 3.3: Control reference settings.............................................................................52
3.6.6 Group 3.4: Ramp & Brakes Setup....................................................................................54
3.6.7 Group 3.5: I/O Configuration ............................................................................................55
3.6.8 Group 3.6: Fieldbus Data Mapping ..................................................................................62
3.6.9 Group 3.7: Prohibit Frequencies......................................................................................63
3.6.10 Group 3.8: Limit supervisions..........................................................................................64
3.6.11 Group 3.9: Protections .....................................................................................................65
3.6.12 Group 3.10: Automatic reset............................................................................................68
Rev. H
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
vacon • 1
3.6.13 Group 3.11: Timer functions ............................................................................................69
3.6.14 Group 3.12: PID-controller 1............................................................................................73
3.6.15 Group 3.13: PID-controller 2............................................................................................79
3.6.16 Group 3.14: Multi-pump...................................................................................................81
3.6.17 Group 3.16: Fire mode .....................................................................................................81
3.6.18 Group 3.17: Application settings......................................................................................83
3.6.19 Group 3.18: kWh pulse output settings ...........................................................................83
3.7 HVAC Application - Additional parameter information ...................................................84
3.8 HVAC Application - Fault tracing ...................................................................................110
3.8.1 Fault appears .................................................................................................................110
3.8.2 Fault history ...................................................................................................................111
3.8.3 Fault codes.....................................................................................................................112
NOTE! You can download the English and French product manuals with applicable safety, warning and caution information from www.vacon.com/downloads
.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l’ensemble des informations de sécurité, avertissements et mises en garde applicables sur le site www.vacon.com/downloads
.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 - Startup vacon • 2
OK
BACK
RESET

1. VACON 100 - STARTUP

1.1 Startup Wizard

In the Startup Wizard, you will be prompted for essential information needed by the drive so that it can start controlling your process. In the Wizard, you will need the following keypad buttons:
Left/Right arrows. Use these to easily move between digits and decimals.
Up/Down arrows. Use these to move between options in menu and to change value.
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can return to the previous question in the Wizard. If pressed at the first question, the Startup Wizard will be cancelled.
Once you have connected power to your Vacon 100 frequency converter, follow these instructions to easily set up your drive.
NOTE! You can have your AC drive equipped with a keypad with either a graphical or an LCD display.
1
2
3 4 5
Language selection Depends on language package
Russia
Daylight saving
Time* hh:mm:ss
Day* dd.mm.
Year* yyyy
*
US EU OFF
* These questions appear if battery is installed
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
vacon • 3 Vacon 100 - Startup
6
Push the OK button unless you want to set all parameter values manually.
7
8 9
10 11
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by activating the parameter Restore factory defaults (pa- rameter P6.5.1) in the Parameter backup submenu (M6.5) OR with parameter P1.19 in the Quick setup menu.
Run Startup Wizard?
Choose your process
Set value for Motor nominal speed (according to nameplate)
Set value for Motor nominal current (according to nameplate)
Set value
Set
value
for
Minimum frequency Range: 0.00...50.00 Hz
for
Maximum frequency Range: 0.00...320.00 Hz
Yes No
Pump Fan
Range: 24...19,200 rpm
Range: Varies

1.2 PID Mini-Wizard

The PID mini wizard is activated in the Quick Setup menu. This wizard presupposes that you are going to use the PID controller in the "one feedback / one setpoint" mode. The control place will be I/O A and the default process unit ‘%’.
The PID mini wizard asks for the following values to be set:
1
If any other process unit than ‘%’ is selected the following questions appear: If not the Wizard will directly jump to step 5
2 3 4
5
If one of the analogue input signals is selected the question 6 appears. Otherwise you will be taken to question 7.
Process unit selection (Several selections. See par. P3.12.1.4).
.
Process unit min
Process unit max
Process unit decimals 0...4
Feedback 1 source selection
See Chapter 3.6.14.3 on page 71 for selections.
1
6
Analogue input signal range
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA See page 57.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 - Startup vacon • 4
7 8
If one of the analogue input signals is selected the question 9 appears. Otherwise you will be taken to question
If either of the options Keypad Setpoint 1 or 2 is chosen the question 10
9
10
11
If option ‘Yes’ is selected you will be prompted for three more values:
12 13
Error inversion
Setpoint source selection See page 74 for selections.
11.
Analogue input signal range
Keypad setpoint
Sleep function?
Sleep frequency limit 1 0.00...320.00 Hz
Sleep delay 1 0...3000 s
0 = Normal 1 = Inverted
will appear.
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA See page 57.
No Yes
14

1.3 Multi-pump mini-wizard

The Multi-Pump mini-wizard asks the most important questions for setting up a Multi-Pump sys­tem. The PID mini-wizard always precedes the Multi-Pump mini-wizard. The keypad will guide you through the questions as in Chapter 1.2 then to be followed by the set of questions below:
15 16 17
If Autochange function is enabled the following three questions will appear. If Autochange will not be used the Wizard jumps directly to question 21.
18 19
Wake-up level 1
Number of motors 1...4
Interlock function
Autochange
Include FC
Autochange interval 0.0...3000.0 h
Range depends on selected process unit.
0 = Not used 1 = Enabled
0 = Disabled 1 = Enabled
0 = Disabled 1 = Enabled
20
21 22
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Autochange: Frequency limit 0.00...50.00 Hz
Bandwidth 0...100%
Bandwidth delay 0...3600 s
1
vacon • 5 Vacon 100 - Startup
Start Fire Moode
Wizard
Fire Mode already
Enabled ?
Ask: Continue
Wizard?
Continue Wizard?
Ask parameter:
Fire Mode Freq Reference
Source
FireModeFrequency
selected to Frequency
Reference ?
Ask parameter:
Fire Mode Frequency
Ask parameter:
Activation Signal Type
Activation signal type?
(Open / Close)
Ask parameter:
Fire Mode Activ. Close
Ask parameter:
Fire Mode Activ. Open
Ask parameter:
Fire Mode Reverse
Ask parameter:
Fire Mode Password
Finished!
YES
NO
NO
YES
OPEN
CLOSE
NO
YES
7073.emf
After this, the keypad will show the digital input and relay output configuration done by the application (graphical keypad only). Write these values down for future reference.

1.4 Fire Mode wizard

The Fire Mode wizard is intended for easy commissioning of the Fire Mode function. The Fire Mode wizard can be initiated by choosing Activate for parameter P1.20 in the Quick setup menu. Fire Mode wizard asks the most important questions for setting up a Fire Mode function.
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 6
LOC REM
9086.emf
Scroll menu up Increase value
Scroll menu down Decrease value
Move cursor left Move cursor right
Move backward in menu Exit edit mode Reset faults with long press
Change control place
Access control page Change direction See ch. 2.2.1.3 for more information
Stop button Start button
Enter active level/item Confirm selection
Enter edit mode Bypass property page

2. KEYPAD OF THE DRIVE

The control keypad is the interface between the Vacon 100 frequency converter and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter's parameters.
There are two keypad types you can choose for your user interface: Keypad with graphical display and keypad with text segment display (text keypad).
The button section of the keypad is identical for both keypad types.
Figure 1. Keypad buttons
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 7 Keypad of the drive
9159.emf
( 17 )
( 12 )
STOP READY I/O
ID: M1
( 5 )
Main Menu
Quick Setup
Parameters
Monitor
Status field STOP/RUN
Direction
ALARM
Status field READY/NOT READY/FAULT
Control place: PC/IO/KEYPAD/FIELDBUS
Activated group/item: Press OK to enter
Number of items in the group
Location field (Parameter ID number and current menu location

2.1 Vacon keypad with graphical display

The graphical keypad features an LCD display and 9 buttons.

2.1.1 Keypad display

The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about structure and the item displayed.
See the attached Keypad Navigation Map to get a comprehensive idea of the menu structure.
his present
location in the menu
2.1.1.1 The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows
to move between the menus. Enter the group/item by pressing the OK button and mer level by pressing the Back/Reset button.
The Location field indicates your current location. The Status field gives information about the present status of the drive. See Figure 1.
Main menu
return
to the for-

2.1.2 Using the graphical keypad

2.1.2.1 Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the Edit mode.
2
3. Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and change then the value with the arrow but­tons up/down.
4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Editing values
Figure 2. Main menu
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 8
STOP READY I/O
ID:172 M3.2.1
STOP READY I/O
ID: M3.2.1
STOP READY I/O
M3.2.1
STOP READY I/O
ID:172 M3.2.1
STOP READY I/O
M3.2.1
9160.emf
BACK
RESET
OR:
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
Edit
Help
Add to favorites
Rem Control Place Rem Control Place
I/O Control
FieldbusCTRL
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
Rem Control Place
I/O Control
FieldbusCTRL
Figure 3. Editing values on graphical keypad
2.1.2.2 Resetting fault
Instructions for how to reset a fault can be found in Chapter 3.8.1 on page 110.
2.1.2.3
Local/Remote control button
The LOC/REM button is used for two functions: to quickly access the Control page and to easily change between the Local (Keypad) and Remote control places.
Control places
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the Local control place is always the keypad. The Remote control place is determined by parameter P1.15 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again, can bypass the remote control place selected with parameter P3.2.1 using a digital input. The digital input is selected with parameter P3.5.1.5 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.5 through digital input while in Remote, the control place will still switch to Keypad if Local is selected. Switching between Local and Remote Control can be done by pressing the Loc/Rem-button on the keypad or by using the "Local/Remote" (ID211) parameter.
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Local/Remote and confirm with the
OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the Loc/Rem button was pushed.
Changing control places
However, if the Remote control place was changed to Local (Keypad) you will be prompted for
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 9 Keypad of the drive
( 21 )
STOP READY Keypad
ID: M1
( 12 )
( 6 )
ID:
STOP Ready Keypad
ID:1805
?
ID:
STOP READY Keypad
ID:211
( 21 )
STOP READY I/O
ID: M1
( 12 )
( 6 )
11114.emf
Remote
Main Menu
Parameters
Diagnostics
Monitor
Choose action
Local/Remote
Control page
Local/Remote
Remote
Local
Main Menu
Parameters
Diagnostics
Monitor
( 21 )
STOP READY I/O
ID: M1
( 12 )
( 6 )
ID:
STOP Ready Keypad
ID:1805
STOP READY Keypad
( 6 )
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
ID:184
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
STOP READY Keypad
( 6 )
ID:168
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
11115.emf
Keypad Reference
Main Menu
Parameters
Diagnostics
Monitor
Choose action
Local/Remote
Control page
Output Frequency
Motor Current
Motor Torque
Motor Power
Keypad Reference
Output Frequency
Motor Current
Motor Torque
Motor Power
keypad reference.
Figure 4. Changing control places
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Control page and confirm with the
OK button.
3. The control page appears.
If keypad control place and keypad reference are selected to be used you can set the Keypad reference after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring (for this procedure, see page 16).
2
Figure 5. Accessing Control page
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 10
STOP READY Keypad
( 0 )
( 4 )
ID: M6
( 8 )
STOP READY Keypad
( 3 )
ID: M6. 5M6.5
STOP READY Keypad
ID: P6.5.2
11088.emf
Main Menu
Favourites
User settings
I/O and Hardware
Parameter compare ( 4 )
User settings
Language selection
English
Parameter backup
Restore from keypad
Restore factory defaults
Save to keypad
Parameter backup
2.1.2.4 Copying parameters
NOTE! This feature is available in graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to another drive. Finally the parameters are downloaded to the new drive restoring them from the keypad.
Before any parameters can successfully be copied from one drive to another the drive has to be stopped when the parameters are downloaded.
• First go into User settings menu and locate the Parameter backup submenu. In the Parameter backup submenu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made at the factory.
•By selecting Save to keypad you can copy all parameters to the keypad.
Restore from keypad will copy all parameters from keypad to a drive.
Figure 6. Parameter copy
NOTE! If the keypad is changed between drives of different sizes, the copied values of these parameters will not be used:
Motor nominal current (P3.1.1.4) Motor nominal voltage (P3.1.1.1) Motor nominal speed (P3.1.1.3) Motor nominal power (P3.1.1.6) Motor nominal frequency (P3.1.1.2) Motor cos phii (P3.1.1.5) Switching frequency (P3.1.2.1) Motor current limit (P3.1.1.7) Stall current limit (P3.9.5) Stall time limit (P3.9.13) Stall frequency (P3.9.14) Maximum frequency (P3.3.2)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 11 Keypad of the drive
( 6 )
STOP READY I/O
ID:403 P3.5.1.1
( 6 )
STOP READY I/O
ID:403 P3.5.1.1
STOP READY I/O
ID:403
P3.5.1.1
9165.emf
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 1 B
Ctrl Signal 2 A
Add to favorites
Ctrl signal 1 A
Edit
Help
Start Signal 1 for control Place I/O A. Start Signal 1 functionality chosen with I/O A Logic in Start/Stop Setup Menu.
Ctrl signal 1 A
230.00 V
1430 rpm
STOP READY I/O
50.00 Hz
STOP READY I/O STOP READY I/O
9166.emf
Basic Settings
Motor Nom Voltg
Motor Nom Speed
Motor Nom Freq
Edit
Help
Motor Nom Freq
Add to favorites
Motor Nom Freq
was added to favorites. Press OK to continue.
2.1.2.5 Help texts The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the startup wizard.
Figure 7. Help text example
2.1.2.6 Adding item to favourites You might need to refer to certain parameter values or other items often. Instead of locating them
one by one in the menu structure, you may want to add them to a folder called Favourites where they can easily be reached.
To remove an item from the Favourites, see Chapter 2.3.7.
Figure 8. Adding item to Favourites
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 12
9167.emf
READY RUN STOP ALARM FAULT
FWD REV I/O BUSKEYPAD
Indicators:
Status
Indicators:
Alarm, Fault
Indicators:
Direction
Indicators:
Control place
Group or parameter name
Menu location

2.2 Vacon keypad with text segment display

You can also choose a Keypad with text segment display (Text keypad) for your user interface. It has mainly the same functionalities as the keypad with graphical display although some of these are somewhat limited.

2.2.1 Keypad display

The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about structure and the item displayed. If the text on the text line is too long to fit in the display, the text will scroll from left to right to reveal the whole text string.
his present
location in the menu
2.2.1.1
Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows
return
to move between the menus. Enter the group/item by pressing the OK button and
to the
former level by pressing the Back/Reset button.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 13 Keypad of the drive
9168.emf
BACK
RESET

2.2.2 Using the keypad

2.2.2.1
Editing values
Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the Edit mode by pressing OK.
3. Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and change then the value with the arrow but­tons up/down.
4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Figure 9. Editing values
2.2.2.2 Resetting fault
Instructions for how to reset a fault can be found in Chapter 3.8.1 on page 110.
2.2.2.3
Local/Remote control button
The LOC/REM button is used for two functions: to quickly access the Control page and to easily change between the Local (Keypad) and Remote control places.
Control places
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the Local control place is always the keypad. The Remote control place is determined by parameter P1.15 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again, can bypass the remote control place selected with parameter P3.2.1 using a digital input. The digital input is selected with parameter P3.5.1.5 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.5 through digital input while in Remote, the control place will still switch to Keypad if Local is selected. Switching between Local and Remote Control can be done by pressing the Loc/Rem-button on the keypad or by using the "Local/Remote" (P3.2.2) parameter.
2
Changing control places
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 14
11089.emf
11090.emf
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Using the arrow buttons, select Local/Remote and confirm with the OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the Loc/Rem button was pushed. However, if the Remote control place was changed to Local (Keypad) you will be prompted for keypad reference.
Figure 10. Changing control places
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Control page and confirm with the
OK button.
3. The control page appears.
If keypad control place and keypad reference are selected to be used you can set the Keypad reference after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable.
Figure 11. Accessing Control page
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 15 Keypad of the drive

2.3 Menu structure

Click on and select the item you wish to receive more information about (electronic manual).
Table 1. Keypad menus
Quick setup See Chapter 3.4. Monitor Multi-monitor*
Basic Timer functions PID Controller 1 PID Controller 2 Multi-Pump Fieldbus data Temperature inputs
Parameters See Chapter 3. Diagnostics Active faults
Reset faults Fault history Total counters Trip counters Software info
I/O and hardware
User settings Language selections
Favourites
*
Basic I/O Slot D Slot E Real time clock Power unit settings Keypad RS-485 Ethernet
Application selection Parameter backup* Drive name
See Chapter 2.1.2.6.
2
User levels See Chapter 2.3.8.
* Not available in text keypad
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 16
( 4 )
( 12 )
ID: M1
STOP READY I/O
( 5 )
 
(13)
(10)
STOP READY I/O
ID: M2.1
0.0rpm
STOP READY I/O
0.00 Hz
ID25
0.00Hz
0.00A
0.00%
20.0 Hz
0.0V
0.0V 81.9°C 0.0%
ID:1 M2.1.1.1
STOP Ready I/O
0.00 Hz
10.00 Hz
0.00 rpm
0.00 A
0.00 %
0.00 %
11116.emf
(13)
Main Menu
Quick Setup
Parameters
Monitor
Monitor
Multimonitor
Basic
Timer functions
Multimonitor
FreqReference
Output Freq
Motor Curre
Motor Torque
Motor Voltage
Motor Speed
Motor TemperaUnit TemperaDC-link volt
FreqReferenc
FreqReference
Output frequency
Motor Power
FreqReference
Motor Speed
Motor Current
Motor Torque

2.3.1 Quick setup

The Quick Setup Menu includes the minimum set of most commonly used parameters during in­stallation and commissioning. More detailed information on the parameters of this group you will find in Chapter 3.4.

2.3.2 Monitor

Multi-monitor
NOTE!This menu is not available in text keypad.
On the multi-monitor page, you can collect nine values that you wish to monitor.
Change the monitored value by activating the value cell (with arrow buttons left/right) and clicking OK. Then choose a new item on the Monitoring values list and click OK again.
Basic
The basic monitoring values are the actual values of selected parameters and signals as well as statuses and measurements. Different applications may have different and different number of monitoring values.
Timer functions
Monitoring of timer functions and the Real Time Clock. See Chapter 3.5.3.
PID Controller 1
Monitoring of PID controller values. See Chapter and Chapter 3.5.5.
PID Controller 2
Monitoring of PID controller values. See Chapter and Chapter 3.5.5.
Multi-Pump
Monitoring of values related to the use of several drives. See Chapter 3.5.6.
Fieldbus data
Fieldbus data shown as monitor values for debugging purposes at e.g. fieldbus commissioning. See Chapter 3.5.7.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 12. Multi-monitoring page
2
vacon • 17 Keypad of the drive

2.3.3 Parameters

Through this submenu, you can reach the application parameter groups and parameters. More in­formation on parameters in Chapter 3.

2.3.4 Diagnostics

Under this menu, you can find Active faults, Reset faults, Fault history, Counters and Soft­ware info.
2.3.4.1
Menu Function Note Active faults When a fault/faults appear(s), the
2.3.4.2 Reset faults
Menu Function Note Reset faults
Active faults
display with the name of the fault starts to blink. Press OK to return to the Diagnostics menu. The Active faults submenu shows the number of faults. Select the fault and push OK to see the fault-time data.
In this menu you can reset faults. For closer instructions, see Chapter 3.8.1.
The fault remains active until it is cleared with the Reset button (push for 2 s) or with a reset signal from the I/O terminal or fieldbus or by choosing Reset faults (see below). The memory of active faults can store the maximum of 10 faults in the order of appearance.
Control signal before resetting the fault to prevent unintentional restart of the drive.
CAUTION! Remove external
2.3.4.3 Fault history
Menu Function Note Fault history
40 latest faults are stored in the Fault history.
Entering the Fault history and clicking OK on the selected fault shows the fault time data (details).
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 18
2.3.4.4 Total counters
Table 2: Diagnostics menu, Total counters parameters
Index Parameter Min Max Unit Default ID Description
Amount of energy taken from supply network. No reset.
NOTE FOR TEXT KEYPAD:
The highest energy unit
V4.4.1 Energy counter Varies 2291
V4.4.3
V4.4.4
V4.4.5
V4.4.6
V4.4.7
V4.4.8
V4.4.9
V4.4.10
V4.4.11
V4.4.12
V4.4.13
V4.4.14
V4.4.15
Operating time
(graphical keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Run time
(graphical keypad)
Run time
(text keypad)
Run time
(text keypad)
Run time
(text keypad)
Power on time
(graphical keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Start command
counter
a d hh:min 2298 Control unit operating time.
a
d
hh:min:ss
a d hh:min 2293 Motor running time.
a
d
hh:min:ss
a d hh:min 2294
a Power on time in total years.
d Power on time in total days.
hh:min:ss
shown on the standard key­pad is MW. Should the counted energy exceed 999.9 MW, no unit is shown on the keypad.
Control unit operating time in total years.
Control unit operating time in total days.
Control unit operating time in hours, minutes and seconds.
Motor running time in total years.
Motor running time in total days.
Motor running time in hours, minutes and seconds
Amount of time the power unit has been powered so far. No reset.
Power on time in hours, minutes and seconds.
The number of times the
2295
power unit has been started.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 19 Keypad of the drive
2.3.4.5 Trip counters
Table 3: Diagnostics menu, Trip counters parameters
Index Parameter Min Max Unit Default ID Description
Resettable energy counter. NOTE FOR TEXT KEYPAD: The highest energy unit shown on the standard keypad is MW. Should the counted energy exceed 999.9 MW, no unit is shown on the
P4.5.1 Energy trip counter Varies 2296
P4.5.3
P4.5.4
P4.5.5
P4.5.6
Operating time
(graphical keypad)
Operating time
(standard keypad)
Operating time
(standard keypad)
Operating time
(standard keypad)
a d hh:min 2299 Resettable. See P4.5.1.
a Operating time in total years.
d Operating time in total days.
hh:min:ss
keypad.
To reset the counter:
Standard text keypad: Apply a long (4 s) push on the OK button. Graphical keypad: Push OK once.
counter
Push OK once again.
Operating time in hours, minutes and seconds.
Reset
page will appear.
2.3.4.6 Software info
Table 4: Diagnostics menu, Software info parameters
Index Parameter Min Max Unit Default ID Description
V4.6.1
V4.6.2
V4.6.3
V4.6.4 System load 0 100 % 2300 Load on control unit CPU.
V4.6.5
V4.6.6 Application ID 837 Application code.
V4.6.7 Application version 838
Software package
(graphical keypad)
Software package ID
(text keypad)
Software package
version
(text keypad)
Application name
(graphical keypad)
2524
Code for software identification.
2525 Name of application.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 20

2.3.5 I/O and hardware

Various options-related settings are located in this menu.
2.3.5.1
Basic I/O
Monitor here the statuses of inputs and outputs.
Table 5: I/O and Hardware menu, Basic I/O parameters
Index Parameter Min Max Unit Default ID Description
V5.1.1 Digital input 1 0 1 2502 Status of digital input signal
V5.1.2 Digital input 2 0 1 2503 Status of digital input signal
V5.1.3 Digital input 3 0 1 2504 Status of digital input signal
V5.1.4 Digital input 4 0 1 2505 Status of digital input signal
V5.1.5 Digital input 5 0 1 2506 Status of digital input signal
V5.1.6 Digital input 6 0 1 2507 Status of digital input signal
Shows the selected (with
V5.1.7 Analogue input 1 mode 1
V5.1.8 Analogue input 1 0 100 % 2509
V5.1.9 Analogue input 2 mode 1
V5.1.10 Analogue input 2 0 100 % 2511
V5.1.11
V5.1.12 Analogue output 1 0 100 % 2513
Analogue output 1
mode
-30...
+200°C
-30...
+200°C 2510
-30...
1
+200°C 2512
jumper) mode for Analogue
2508
input signal 1 = 0...20 mA 3 = 0...10 V
Status of analogue input signal
Shows the selected (with jumper) mode for Analogue input signal 1 = 0...20 mA 3 = 0...10 V
Status of analogue input signal
Shows the selected (with jumper) mode for Analogue otuput signal 1 = 0...20 mA 3 = 0...10 V
Status of analogue output signal
2.3.5.2
Option board slots
The parameters of this group depend on the option board installed. If no option board is placed in slots D or E, no parameters are visible. See Chapter 3.6.2 for the location of the slots.
As an option board is removed, info text F39 Device removed will appear on the display. See Table 74.
Menu Function Note Slot D Settings Option board related settings.
Monitoring Monitor option board-related info.
Slot E Settings Option board related settings.
Monitoring Monitor option board-related info.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 21 Keypad of the drive
2.3.5.3 Real time clock
Table 6: I/O and Hardware menu, Real time clock parameters
Index Parameter Min Max Unit Default ID Description
Status of battery.
M5.5.1 Battery state 1 3 2 2205
M5.5.2 Time hh:mm:ss 2201 Current time of day
M5.5.3 Date mm.dd. 2202 Current date
M5.5.4 Year yyyy 2203 Current year
M5.5.5 Daylight saving 1 4 1 2204
1 = Not installed 2 = Installed 3 = Change battery
Daylight saving rule 1 = Off 2 = EU 3 = US 4 = Russia
2.3.5.4 Power unit settings
Fan
The fan operates in optimized or always-on mode. In the optimized mode, fan speed is controlled according to the drive‘s internal logic that receives data from temperature measurements (if supported by the power unit) and the fan stops within 5 minutes when the drive is in Stop state. In always-on mode, the fan runs at full speed, without stopping.
Table 7: Power unit settings, Fan
Index Parameter Min Max Unit Default ID Description
V5.5.1.1 Fan control mode 0 1 1 2377
M5.6.1.5 Fan lifetime N/A N/A 0 849 Fan lifetime
M5.6.1.6
M5.6.1.7 Fan lifetime reset N/A N/A 0 823 Fan lifetime reset
Fan lifetime alarm
limit
0 200 000 h 50 000 824 Fan lifetime alarm limit
0 = Always on 1 = Optimized
Brake chopper
Table 8: Power unit settings, Brake chopper
Index Parameter Min Max Unit Default ID Description
0 = Disabled
P5.6.2.1 Brake chopper mode 0 3 0 2526
1 = Enabled (Run) 2 = Enabled (Run & Stop) 3 = Enabled (Run, no testing)
2
Sine filter
Sine filter support restricts overmodulation depth and prevents thermal management functions from decreasing switching frequency.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 22
Table 9: Power unit settings, Sine filter
Index Parameter Min Max Unit Default ID Description
P5.6.4.1 Sine filter 0 1 0 2507
0 = Disabled 1 = Enabled
2.3.5.5 Keypad
Table 10: I/O and Hardware menu, Keypad parameters
Index Parameter Min Max Unit Default ID Description
Time after which the display
P5.7.1 Timeout time 0 60 min 0 804
P5.7.2 Default page 0 4 0 2318
P5.7.3 Menu index 2499
P5.7.4 Contrast* 30 70 % 50 830
P5.7.5 Backlight time 0 60 min 5 818
returns to page defined with parameter P5.7.2. 0 = Not used
0 = None 1 = Enter menu index 2 = Main menu 3 = Control page 4 = Multimonitor
Set menu index for desired page and activate with parameter P5.7.2 = 1.
Set contrast of the display (30...70%).
Set the time until the backlight of the display turns off (0...60 min). If set to 0 s, backlight is always on.
* Only available with graphical keypad
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 23 Keypad of the drive
2.3.5.6 Fieldbus
Parameters related to different fieldbus boards can also be found in the I/O and Hardware menu. These parameters are explained in more detail in the respective fieldbus manual.
Submenu level 1 Submenu level 2 Submenu level 3 Submenu level 4 RS-485 Common settings Protocol Modbus/RTU
N2 BACnet MS/TP
Modbus/RTU Parameters Slave address
Baud rate Parity type Stop bits Communication timeout Operate mode
Monitoring Fieldbus protocol status
Communication status Illegal functions Illegal data addresses Illegal data values Slave device busy Memory parity error Slave device failure Last fault response Control word Status word
N2 Parameters Device address
Communication timeout
Monitoring Fieldbus protocol status
Communication status Invalid data Invalid commands Command not accepted Control word Status word
RS-485 BACnet MS/TP Parameters Baud rate
Autobauding MAC address Instance number Communication timeout
Monitoring Fieldbus protocol status
Communication status Actual instance number Fault code Control word Status word
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 24
Ethernet Common settings IP address mode
Fixed IP
IP address Subnet mask Default gateway
Modbus/TCP Common settings Connection limit
Monitoring* Fieldbus protocol status
BACnet/IP Settings Instance number
Monitoring Fieldbus protocol status
* Will appear only after connection has been established
IP address Subnet mask Default gateway
Slave address Communication timeout
Communication status Illegal functions Illegal data addresses Illegal data values Slave device busy Memory parity error Slave device failure Last fault response Control word Status word
Communication timeout Protocol in use BBMD IP BBMD Port Time to live
Communication status Actual instance number Control word Status word
Table 11: RS-485 common settings
Index Parameter Min Max Unit Default ID Description
0 = No protocol
P5.8.1.1 Protocol 0 9 0 2208
Table 12: ModBus RTU parameters (This table is only visible when P5.8.1.1 Protocol = 4/
Modbus RTU)
Index Parameter Min Max Unit Default ID Description
P5.8.3.1.1 Slave address 1 247 1 2320 Slave address
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4 = Modbus RTU 5 = N2 9 = BACnet MSTP
2
vacon • 25 Keypad of the drive
Table 12: ModBus RTU parameters (This table is only visible when P5.8.1.1 Protocol = 4/
Modbus RTU)
P5.8.3.1.2 Baud rate 300 230 400 bps 9600 2378 Baud rate
P5.8.3.1.3 Parity type Even None None 2379 Parity type
P5.8.3.1.4 Stop bits 1 2 2 2380 Stop bits
P5.8.3.1.5
P5.8.3.1.6 Operate mode Slave Master Slave 2374 Operate mode
Communication
timeout
0 65 535 s 10 2321
Communication timeout
Table 13: ModBus RTU monitoring (This table is only visible when P5.8.1.1 Protocol = 4/
Modbus RTU)
Index Parameter Min Max Unit Default ID Description
M5.8.3.2.1
P5.8.3.2.2
M5.8.3.2.3 Illegal functions 0 2383 Illegal functions
M5.8.3.2.4 Illegal data addresses 0 2384 Illegal data addresses
M5.8.3.2.5 Illegal data values 0 2385 Illegal data values
M5.8.3.2.6 Slave device busy 0 2386 Slave device busy
M5.8.3.2.7 Memory parity error 0 2387 Memory parity error
M5.8.3.2.8 Slave device failure 0 2388 Slave device failure
M5.8.3.2.9 Last fault response 0 2389 Last fault response
M5.8.3.2.10 Control word 16#0 2390 Control word
M5.8.3.2.11 Status word 16#0 2391 Status word
Fieldbus protocol
status
Communication
status
0 2381 Fieldbus protocol status
0 0 0 2382 Communication status
Table 14: N2 parameters (This table is only visible when P5.8.1.1 Protocol = 5/N2)
Index Parameter Min Max Unit
P 5.8.3.1.1 Device address 1 255 1 2350 Device address
P 5.8.3.1.2
Communication
timeout
0 255 10 2351
Defaul
t
ID Description
Communication
timeout
Table 15: N2 monitoring (This table is only visible when P5.8.1.1 Protocol = 5/N2)
Index Parameter Min Max Unit Default ID Description
M5.8.3.2.1
M5.8.3.2.2
M5.8.3.2.3 Invalid data 0 2401 Invalid data
M5.8.3.2.4 Invalid commands 0 2402 Invalid commands
M5.8.3.2.5 Command NACK 0 2403 Command NACK
M5.8.3.2.6 Control word 16#0 2404 Control word
M5.8.3.2.7 Status word 16#0 2405 Status word
Fieldbus protocol
status
Communication
status
0 2399 Fieldbus protocol status
0 0 0 2400 Communication status
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 26
Table 16: BACnet MSTP parameters (This table is only visible when P5.8.1.1 Protocol = 9/
BACNetMSTP)
Index Parameter Min Max Unit Default ID Description
P5.8.3.1.1 Baud rate 9600 76 800 bps 9600 2392 Baud rate
P5.8.3.1.2 Autobauding 0 1 0 2330 Autobauding
P5.8.3.1.3 MAC address 1 127 1 2331 MAC address
P5.8.3.1.4 Instance number 0 4 194 303 0 2332 Instance number
P5.8.3.1.5
Communication
timeout
0 65 535 10 2333
Communication timeout
Table 17: BACnet MSTP monitoring (This table is only visible when P5.8.1.1 Protocol = 9/
BACNetMSTP)
Index Parameter Min Max Unit Default ID Description
M5.8.3.2.1
M5.8.3.2.2
M5.8.3.2.3 Actual instance 0 2395 Actual instance
M5.8.3.2.4 Fault code 0 2396 Fault code
M5.8.3.2.5 Control word 16#0 2397 Control word
M5.8.3.2.6 Status word 16#0 2398 Status word
Fieldbus protocol
status
Communication
status
0 2393
0 2394
Fieldbus protocol status
Communication status
Table 18: Ethernet common settings
Index Parameter Min Max Unit Default ID Description
P5.9.1.1 IP address mode 0 1 1 2482
0 = Fixed IP 1 = DHCP with AutoIP
Table 19: Fixed IP
Index Parameter Min Max Unit Default ID Description
P5.9.1.2.1 IP address 192.168.0.10 2529
P5.9.1.2.2 Subnet mask 255.255.0.0 2530
P5.9.1.2.3 Default gateway 192.168.0.1 2531
M5.9.1.3 IP address 0 2483 IP address
M5.9.1.4 Subnet mask 0 2484 Subnet mask
M5.9.1.5 Default gateway 0 2485 Default gateway
M5.9.1.6 MAC address 2486 MAC address
The parameter is in use if P5.9.1.1 = 0/Fixed IP
The parameter is in use if P5.9.1.1 = 0/Fixed IP
The parameter is in use if P5.9.1.1 = 0/Fixed IP
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 27 Keypad of the drive
Table 20: ModBus TCP common settings
Index Parameter Min Max Unit Default ID Description
P5.9.2.1.1 Connection limit 0 3 3 2446 Connection limit
P5.9.2.1.2 Slave address 0 255 255 2447 Slave address
P5.9.2.1.3
Communication
timeout
0 65 535 s 10 2448
Communication timeout
Table 21: BACnet IP settings
Index Parameter Min Max Unit Default ID Description
P5.9.3.1.1 Instance number 0 4 194 303 0 2406 Instance number
P5.9.3.1.2
P5.9.3.1.3 Protocol in use 0 1 0 2408 Protocol in use
P5.9.3.1.4 BBMD IP 192.168.0.1 2409 BBMD IP
P5.9.3.1.5 BBMD Port 1 65 535 47 808 2410 BBMD Port
P5.9.3.1.6 Time to live 0 255 0 2411 Time to live
Communication
timeout
0 65 535 0 2407
Communication timeout
Table 22: BACnet IP monitoring
Index Parameter Min Max Unit Default ID Description
M5.9.3.2.1
P5.9.3.2.2
M5.9.3.2.3 Actual instance 0 2414 Invalid data
M5.9.3.2.4 Control word 16#0 2415 Control word
M5.9.3.2.5 Status word 16#0 2416 Status word
Fieldbus protocol
status
Communication
status
0 2412 Fieldbus protocol status
0 0 0 2413 Communication status
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Loading...
+ 91 hidden pages