Vacon 100 Applications Manual

vacon 100
®
hvac drives
application manual
vacon • 0
TABLE OF CONTENTS
Order code: DOC-APP02456+DLUK
Corresponds to application package FW0065V021.vcx
1. Vacon 100 - Startup ......................................................................................... 2
1.1 Startup Wizard................................................................................................................... 2
1.2 PID Mini-Wizard ................................................................................................................ 3
1.3 Multi-pump mini-wizard ................................................................................................... 4
1.4 Fire Mode wizard............................................................................................................... 5
2. Keypad of the drive .......................................................................................... 6
2.1 Vacon keypad with graphical display ................................................................................ 7
2.1.1 Keypad display................................................................................................................... 7
2.1.2 Using the graphical keypad............................................................................................... 7
2.2 Vacon keypad with text segment display ........................................................................ 12
2.2.1 Keypad display................................................................................................................. 12
2.2.2 Using the keypad ............................................................................................................. 13
2.3 Menu structure................................................................................................................ 15
2.3.1 Quick setup...................................................................................................................... 16
2.3.2 Monitor ............................................................................................................................ 16
2.3.3 Parameters...................................................................................................................... 17
2.3.4 Diagnostics ...................................................................................................................... 17
2.3.5 I/O and hardware............................................................................................................. 20
2.3.6 User settings ................................................................................................................... 28
2.3.7 Favourites........................................................................................................................ 29
2.3.8 User levels....................................................................................................................... 29
3. Vacon HVAC Application................................................................................. 30
3.1 Specific functions of Vacon HVAC application ................................................................ 30
3.2 Example of control connections ..................................................................................... 31
3.3 Isolating digital inputs from ground ............................................................................... 33
3.4 HVAC Application - Quick setup parameter group ......................................................... 34
3.5 Monitor group.................................................................................................................. 36
3.5.1 Multimonitor.................................................................................................................... 36
3.5.2 Basic ................................................................................................................................ 36
3.5.3 Timer functions monitoring ............................................................................................ 38
3.5.4 PID1 controller monitoring ............................................................................................. 39
3.5.5 PID2 controller monitoring ............................................................................................. 39
3.5.6 Multi-pump monitoring................................................................................................... 39
3.5.7 Fieldbus data monitoring ................................................................................................ 40
3.5.8 Temperature inputs monitoring ..................................................................................... 41
3.6 Vacon HVAC Application - Application parameter lists.................................................. 42
3.6.1 Column explanations ...................................................................................................... 43
3.6.2 Parameter programming................................................................................................ 44
3.6.3 Group 3.1: Motor settings ............................................................................................... 48
3.6.4 Group 3.2: Start/Stop setup ............................................................................................ 51
3.6.5 Group 3.3: Control reference settings ............................................................................ 52
3.6.6 Group 3.4: Ramp & Brakes Setup................................................................................... 55
3.6.7 Group 3.5: I/O Configuration ........................................................................................... 56
3.6.8 Group 3.6: Fieldbus Data Mapping.................................................................................. 63
3.6.9 Group 3.7: Prohibit Frequencies..................................................................................... 64
3.6.10 Group 3.8: Limit supervisions ......................................................................................... 65
Rev. H
Revision release date: 7.5.13
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
vacon • 1
3.6.11 Group 3.9: Protections ....................................................................................................66
3.6.12 Group 3.10: Automatic reset ........................................................................................... 69
3.6.13 Group 3.11: Timer functions ........................................................................................... 70
3.6.14 Group 3.12: PID-controller 1........................................................................................... 74
3.6.15 Group 3.13: PID-controller 2........................................................................................... 80
3.6.16 Group 3.14: Multi-pump.................................................................................................. 82
3.6.17 Group 3.16: Fire mode.....................................................................................................83
3.6.18 Group 3.17: Application settings..................................................................................... 84
3.6.19 Group 3.18: kWh pulse output settings........................................................................... 84
3.7 HVAC Application - Additional parameter information .................................................. 85
3.8 HVAC Application - Fault tracing .................................................................................. 111
3.8.1 Fault appears ................................................................................................................ 111
3.8.2 Fault history .................................................................................................................. 112
3.8.3 Fault codes .................................................................................................................... 113
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 - Startup vacon • 2
OK
BACK
RESET

1. VACON 100 - STARTUP

1.1 Startup Wizard

In the Startup Wizard, you will be prompted for essential information needed by the drive so that it can start controlling your process. In the Wizard, you will need the following keypad buttons:
Left/Right arrows. Use these to easily move between digits and decimals.
Up/Down arrows. Use these to move between options in menu and to change value.
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can return to the previous question in the Wizard. If pressed at the first question, the Startup Wizard will be cancelled.
Once you have connected power to your Vacon 100 frequency converter, follow these instructions to easily set up your drive.
NOTE! You can have your AC drive equipped with a keypad with either a graphical or an LCD display.
1
2
3 4
Language selection Depends on language package
Russia
Daylight saving
Time* hh:mm:ss
Day* dd.mm.
*
US EU OFF
5
* These questions appear if battery is installed
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Year* yyyy
1
vacon • 3 Vacon 100 - Startup
6
Push the OK button unless you want to set all parameter values manually.
7
8 9
10 11
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by activating the parameter Restore factory defaults (parameter P6.5.1) in the Parameter backup submenu (M6.5) OR with parameter P1.19 in the Quick setup menu.
Run Startup Wizard?
Choose your process
Set value for Motor nominal speed (according to nameplate)
Set value for Motor nominal current (according to nameplate)
Set value
Set
value
for
Minimum frequency Range: 0.00...50.00 Hz
for
Maximum frequency Range: 0.00...320.00 Hz
Yes No
Pump Fan
Range: 24...19,200 rpm
Range: Varies

1.2 PID Mini-Wizard

The PID mini wizard is activated in the Quick Setup menu. This wizard presupposes that you are going to use the PID controller in the "one feedback / one setpoint" mode. The control place will be I/O A and the default process unit ‘%’.
The PID mini wizard asks for the following values to be set:
1
If any other process unit than ‘%’ is selected the following questions appear: If not the Wizard will directly jump to step 5
2 3 4
5
If one of the analogue input signals is selected the question 6 appears. Otherwise you will be taken to question 7.
Process unit selection (Several selections. See par. P3.12.1.4).
.
Process unit min
Process unit max
Process unit decimals 0...4
Feedback 1 source selection
See Chapter 3.6.14.3 on page 71 for selections.
1
6
Analogue input signal range
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA See page 58.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 - Startup vacon • 4
7 8
If one of the analogue input signals is selected the question 9 appears. Otherwise you will be taken to question
If either of the options Keypad Setpoint 1 or 2 is chosen the question 10
9
10
11
If option ‘Yes’ is selected you will be prompted for three more values:
12 13
Error inversion
Setpoint source selection See page 75 for selections.
11.
Analogue input signal range
Keypad setpoint
Sleep function?
Sleep frequency limit 1 0.00...320.00 Hz
Sleep delay 1 0...3000 s
0 = Normal 1 = Inverted
will appear.
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA See page 58.
No Yes
14

1.3 Multi-pump mini-wizard

The Multi-Pump mini-wizard asks the most important questions for setting up a Multi-Pump system. The PID mini-wizard always precedes the Multi-Pump mini-wizard. The keypad will guide you through the questions as in Chapter 1.2 then to be followed by the set of questions below:
15 16
17
If Autochange function is enabled the following three questions will appear. If Autochange will not be used the Wizard jumps directly to question 21.
18 19
Wake-up level 1
Number of motors 1...4
Interlock function
Autochange
Include FC
Autochange interval 0.0...3000.0 h
Range depends on selected process unit.
0 = Not used 1 = Enabled
0 = Disabled 1 = Enabled
0 = Disabled 1 = Enabled
20
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Autochange: Frequency limit 0.00...50.00 Hz
1
vacon • 5 Vacon 100 - Startup
Start Fire Moode
Wizard
Fire Mode already
Enabled ?
Ask: Continue
Wizard?
Continue Wizard?
Ask parameter:
Fire Mode Freq Reference
Source
FireModeFrequency
selected to Frequency
Reference ?
Ask parameter:
Fire Mode Frequency
Ask parameter:
Activation Signal Type
Activation signal type?
(Open / Close)
Ask parameter:
Fire Mode Activ. Close
Ask parameter:
Fire Mode Activ. Open
Ask parameter:
Fire Mode Reverse
Ask parameter:
Fire Mode Password
Finished!
YES
NO
NO
YES
OPEN
CLOSE
NO
YES
7073.emf
21 22
Bandwidth 0...100%
Bandwidth delay 0...3600 s
After this, the keypad will show the digital input and relay output configuration done by the application (graphical keypad only). Write these values down for future reference.

1.4 Fire Mode wizard

The Fire Mode wizard is intended for easy commissioning of the Fire Mode function. The Fire Mode wizard can be initiated by choosing Activate for parameter P1.20 in the Quick setup menu. Fire Mode wizard asks the most important questions for setting up a Fire Mode function.
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 6
LOC REM
9086.emf
Scroll menu up Increase value
Scroll menu down Decrease value
Move cursor left Move cursor right
Move backward in menu Exit edit mode Reset faults with long press
Change control place
Access control page Change direction See ch. 2.2.1.3 for more information
Stop button Start button
Enter active level/item Confirm selection
Enter edit mode Bypass property page

2. KEYPAD OF THE DRIVE

The control keypad is the interface between the Vacon 100 frequency converter and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter's parameters.
There are two keypad types you can choose for your user interface: Keypad with graphical display and keypad with text segment display (text keypad).
The button section of the keypad is identical for both keypad types.
Figure 1. Keypad buttons
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 7 Keypad of the drive
9159.emf
( 17 )
( 12 )
STOP READY I/O
ID: M1
( 5 )
Main Menu
Quick Setup
Parameters
Monitor
Status field STOP/RUN
Direction
ALARM
Status field READY/NOT READY/FAULT
Control place: PC/IO/KEYPAD/FIELDBUS
Activated group/item: Press OK to enter
Number of items in the group
Location field (Parameter ID number and current menu location

2.1 Vacon keypad with graphical display

The graphical keypad features an LCD display and 9 buttons.

2.1.1 Keypad display

The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about the menu structure and the item displayed.
See the attached Keypad Navigation Map to get a comprehensive idea of the menu structure.
his present
location in
2.1.1.1 The data on the control keypad are arranged in menus and submenus. Use the Up and Down
arrows to move between the menus. Enter the group/item by pressing the OK button and to the former level by pressing the Back/Reset button.
The Location field indicates your current location. The Status field gives information about the present status of the drive. See Figure 1.
Main menu
return

2.1.2 Using the graphical keypad

2.1.2.1 Change value of a parameter following the procedure below:
1. Locate the parameter.
2
2. Enter the Edit mode.
3. Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and change then the value with the arrow buttons up/down.
4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Editing values
Figure 2. Main menu
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 8
STOP READY I/O
ID:172 M3.2.1
STOP READY I/O
ID: M3.2.1
STOP READY I/O
M3.2.1
STOP READY I/O
ID:172 M3.2.1
STOP READY I/O
M3.2.1
9160.emf
BACK
RESET
OR:
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
Edit
Help
Add to favorites
Rem Control Place Rem Control Place
I/O Control
FieldbusCTRL
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
Rem Control Place
I/O Control
FieldbusCTRL
Figure 3. Editing values on graphical keypad
2.1.2.2 Resetting fault
Instructions for how to reset a fault can be found in Chapter 3.8.1 on page 111.
2.1.2.3
The LOC/REM button is used for two functions: to quickly access the Control page and to easily change between the Local (Keypad) and Remote control places.
Control places
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the Local control place is always the keypad. The Remote control place is determined by parameter P1.15 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again, can bypass the remote control place selected with parameter P3.2.1 using a digital input. The digital input is selected with parameter P3.5.1.5 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.5 through digital input while in Remote, the control place will still switch to Keypad if Local is selected. Switching between Local and Remote Control can be done by pressing the Loc/Rem-button on the keypad or by using the "Local/Remote" (ID211) parameter.
Changing control places
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Local/Remote and confirm with
the OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Local/Remote control button
2
vacon • 9 Keypad of the drive
( 21 )
STOP READY Keypad
ID: M1
( 12 )
( 6 )
ID:
STOP Ready Keypad
ID:1805
?
ID:
STOP READY Keypad
ID:211
( 21 )
STOP READY I/O
ID: M1
( 12 )
( 6 )
11114.emf
Remote
Main Menu
Parameters
Diagnostics
Monitor
Choose action
Local/Remote
Control page
Local/Remote
Remote
Local
Main Menu
Parameters
Diagnostics
Monitor
( 21 )
STOP READY I/O
ID: M1
( 12 )
( 6 )
ID:
STOP Ready Keypad
ID:1805
STOP READY Keypad
( 6 )
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
ID:184
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
STOP READY Keypad
( 6 )
ID:168
0.00 Hz
0.00Hz
0.00A
0.00%
0.00%
11115.emf
Keypad Reference
Main Menu
Parameters
Diagnostics
Monitor
Choose action
Local/Remote
Control page
Output Frequency
Motor Current
Motor Torque
Motor Power
Keypad Reference
Output Frequency
Motor Current
Motor Torque
Motor Power
4. The display will return to the same location as it was when the Loc/Rem button was
pushed. However, if the Remote control place was changed to Local (Keypad) you will be prompted for keypad reference.
Figure 4. Changing control places
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Control page and confirm with
the OK button.
3. The control page appears.
If keypad control place and keypad reference are selected to be used you can set the Keypad reference after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring (for this procedure, see page 16).
2
Figure 5. Accessing Control page
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 10
STOP READY Keypad
( 0 )
( 4 )
ID: M6
( 8 )
STOP READY Keypad
( 3 )
ID: M6.5M6.5
STOP READY Keypad
ID: P6.5.2
11088.emf
Main Menu
Favourites
User settings
I/O and Hardware
Parameter compare ( 4 )
User settings
Language selection
English
Parameter backup
Restore from keypad
Restore factory defaults
Save to keypad
Parameter backup
2.1.2.4 Copying parameters
NOTE! This feature is available in graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to another drive. Finally the parameters are downloaded to the new drive restoring them from the keypad.
Before any parameters can successfully be copied from one drive to another the drive has to be stopped when the parameters are downloaded.
• First go into User settings menu and locate the Parameter backup submenu. In the Parameter backup submenu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made at the factory.
•By selecting Save to keypad you can copy all parameters to the keypad.
Restore from keypad will copy all parameters from keypad to a drive.
Figure 6. Parameter copy
NOTE! If the keypad is changed between drives of different sizes, the copied values of these parameters will not be used:
Motor nominal current (P3.1.1.4) Motor nominal voltage (P3.1.1.1) Motor nominal speed (P3.1.1.3) Motor nominal power (P3.1.1.6) Motor nominal frequency (P3.1.1.2) Motor cos phii (P3.1.1.5) Switching frequency (P3.1.2.1) Motor current limit (P3.1.1.7) Stall current limit (P3.9.5) Stall time limit (P3.9.13) Stall frequency (P3.9.14) Maximum frequency (P3.3.2)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 11 Keypad of the drive
( 6 )
STOP READY I/O
ID:403 P3.5.1.1
( 6 )
STOP READY I/O
ID:403 P3.5.1.1
STOP READY I/O
ID:403
P3.5.1.1
9165.emf
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 1 B
Ctrl Signal 2 A
Add to favorites
Ctrl signal 1 A
Edit
Help
Start Signal 1 for control Place I/O A. Start Signal 1 functionality chosen with I/O A Logic in Start/Stop Setup Menu.
Ctrl signal 1 A
230.00 V
1430 rpm
STOP READY I/O
50.00 Hz
STOP READY I/O STOP READY I/O
9166.emf
Basic Settings
Motor Nom Voltg
Motor Nom Speed
Motor Nom Freq
Edit
Help
Motor Nom Freq
Add to favorites
Motor Nom Freq
was added to favorites. Press OK to continue.
2.1.2.5 Help texts The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the startup wizard.
Figure 7. Help text example
2.1.2.6 Adding item to favourites You might need to refer to certain parameter values or other items often. Instead of locating
them one by one in the menu structure, you may want to add them to a folder called Favourites where they can easily be reached.
To remove an item from the Favourites, see Chapter 2.3.7.
Figure 8. Adding item to Favourites
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 12
9167.emf
READY RUN STOP ALARM FAULT
FWD REV I/O BUSKEYPAD
Indicators:
Status
Indicators:
Alarm, Fault
Indicators:
Direction
Indicators:
Control place
Group or parameter name
Menu location

2.2 Vacon keypad with text segment display

You can also choose a Keypad with text segment display (Text keypad) for your user interface. It has mainly the same functionalities as the keypad with graphical display although some of these are somewhat limited.

2.2.1 Keypad display

The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about his present location in the menu structure and the item displayed. If the text on the text line is too long to fit in the display, the text will scroll from left to right to reveal the whole text string.
2.2.1.1
Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up and Down arrows to move between the menus. Enter the group/item by pressing the OK button and return to the former level by pressing the Back/Reset button.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 13 Keypad of the drive
9168.emf
BACK
RESET

2.2.2 Using the keypad

2.2.2.1
Editing values
Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the Edit mode by pressing OK.
3. Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and change then the value with the arrow buttons up/down.
4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Figure 9. Editing values
2.2.2.2 Resetting fault
Instructions for how to reset a fault can be found in Chapter 3.8.1 on page 111.
2.2.2.3
Local/Remote control button
The LOC/REM button is used for two functions: to quickly access the Control page and to easily change between the Local (Keypad) and Remote control places.
Control places
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the Local control place is always the keypad. The Remote control place is determined by parameter P1.15 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again, can bypass the remote control place selected with parameter P3.2.1 using a digital input. The digital input is selected with parameter P3.5.1.5 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.5 through digital input while in Remote, the control place will still switch to Keypad if Local is selected. Switching between Local and Remote Control can be done by pressing the Loc/Rem-button on the keypad or by using the "Local/Remote" (P3.2.2) parameter.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 14
11089.emf
11090.emf
Changing control places
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Using the arrow buttons, select Local/Remote and confirm with the OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the Loc/Rem button was pushed. However, if the Remote control place was changed to Local (Keypad) you will be prompted for keypad reference.
Figure 10. Changing control places
Accessing the control page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the Loc/Rem button.
2. Push the Arrow up or the Arrow down button to select Control page and confirm with
the OK button.
3. The control page appears.
If keypad control place and keypad reference are selected to be used you can set the Keypad reference after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable.
Figure 11. Accessing Control page
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 15 Keypad of the drive

2.3 Menu structure

Click on and select the item you wish to receive more information about (electronic manual).
Table 1. Keypad menus
Quick setup See Chapter 3.4. Monitor Multi-monitor*
Basic Timer functions PID Controller 1 PID Controller 2 Multi-Pump Fieldbus data Temperature inputs
Parameters See Chapter 3. Diagnostics Active faults
Reset faults Fault history Total counters Trip counters Software info
I/O and hardware
User settings Language selections
Favourites
*
Basic I/O Slot D Slot E Real time clock Power unit settings Keypad RS-485 Ethernet
Application selection Parameter backup* Drive name
See Chapter 2.1.2.6.
2
User levels See Chapter 2.3.8.
* Not available in text keypad
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 16
( 4 )
( 12 )
ID: M1
STOP READY I/O
( 5 )
 
(13)
(10)
STOP READY I/O
ID: M2.1
0.0rpm
STOP READY I/O
0.00 Hz
ID25
0.00Hz
0.00A
0.00%
20.0 Hz
0.0V
0.0V 81.9°C 0.0%
ID:1 M2.1.1.1
STOP Ready I/O
0.00 Hz
10.00 Hz
0.00 rpm
0.00 A
0.00 %
0.00 %
11116.emf
(13)
Main Menu
Quick Setup
Parameters
Monitor
Monitor
Multimonitor
Basic
Timer functions
Multimonitor
FreqReference
Output Freq
Motor Curre
Motor Torque
Motor Voltage
Motor Speed
Motor TemperaUnit TemperaDC-link volt
FreqReferenc
FreqReference
Output frequency
Motor Power
FreqReference
Motor Speed
Motor Current
Motor Torque

2.3.1 Quick setup

The Quick Setup Menu includes the minimum set of most commonly used parameters during installation and commissioning. More detailed information on the parameters of this group you will find in Chapter 3.4.

2.3.2 Monitor

Multi-monitor
NOTE!This menu is not available in text keypad.
On the multi-monitor page, you can collect nine values that you wish to monitor.
Change the monitored value by activating the value cell (with arrow buttons left/right) and clicking OK. Then choose a new item on the Monitoring values list and click OK again.
Basic
The basic monitoring values are the actual values of selected parameters and signals as well as statuses and measurements. Different applications may have different and different number of monitoring values.
Timer functions
Monitoring of timer functions and the Real Time Clock. See Chapter 3.5.3.
PID Controller 1
Monitoring of PID controller values. See Chapter and Chapter 3.5.5.
PID Controller 2
Monitoring of PID controller values. See Chapter and Chapter 3.5.5.
Multi-Pump
Monitoring of values related to the use of several drives. See Chapter 3.5.6.
Fieldbus data
Fieldbus data shown as monitor values for debugging purposes at e.g. fieldbus commissioning. See Chapter 3.5.7.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Figure 12. Multi-monitoring page
2
vacon • 17 Keypad of the drive

2.3.3 Parameters

Through this submenu, you can reach the application parameter groups and parameters. More information on parameters in Chapter 3.

2.3.4 Diagnostics

Under this menu, you can find Active faults, Reset faults, Fault history, Counters and Software info.
2.3.4.1
Menu Function Note Active faults When a fault/faults appear(s), the
2.3.4.2 Reset faults
Menu Function Note Reset faults
Active faults
display with the name of the fault starts to blink. Press OK to return to the Diagnostics menu. The Active faults submenu shows the number of faults. Select the fault and push OK to see the fault-time data.
In this menu you can reset faults. For closer instructions, see Chapter 3.8.1.
The fault remains active until it is cleared with the Reset button (push for 2 s) or with a reset signal from the I/O terminal or fieldbus or by choosing Reset faults (see below). The memory of active faults can store the maximum of 10 faults in the order of appearance.
Control signal before resetting the fault to prevent unintentional restart of the drive.
CAUTION! Remove external
2.3.4.3 Fault history
Menu Function Note Fault history
40 latest faults are stored in the Fault history.
Entering the Fault history and clicking OK on the selected fault shows the fault time data (details).
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 18
2.3.4.4 Total counters
Table 2: Diagnostics menu, Total counters parameters
Index Parameter Min Max Unit Default ID Description
Amount of energy taken from supply network. No reset.
NOTE FOR TEXT KEYPAD:
The highest energy unit
V4.4.1 Energy counter Varies 2291
V4.4.3
V4.4.4
V4.4.5
V4.4.6
V4.4.7
V4.4.8
V4.4.9
V4.4.10
V4.4.11
V4.4.12
V4.4.13
V4.4.14
V4.4.15
Operating time
(graphical keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Run time
(graphical keypad)
Run time
(text keypad)
Run time
(text keypad)
Run time
(text keypad)
Power on time
(graphical keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Start command
counter
a d hh:min 2298 Control unit operating time.
a
d
hh:min:ss
a d hh:min 2293 Motor running time.
a
d
hh:min:ss
a d hh:min 2294
a Power on time in total years.
d Power on time in total days.
hh:min:ss
shown on the standard key­pad is MW. Should the counted energy exceed 999.9 MW, no unit is shown on the keypad.
Control unit operating time in total years.
Control unit operating time in total days.
Control unit operating time in hours, minutes and seconds.
Motor running time in total years.
Motor running time in total days.
Motor running time in hours, minutes and seconds
Amount of time the power unit has been powered so far. No reset.
Power on time in hours, minutes and seconds.
The number of times the
2295
power unit has been started.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 19 Keypad of the drive
2.3.4.5 Trip counters
Table 3: Diagnostics menu, Trip counters parameters
Index Parameter Min Max Unit Default ID Description
Resettable energy counter. NOTE FOR TEXT KEYPAD: The highest energy unit shown on the standard keypad is MW. Should the counted energy exceed 999.9 MW, no unit is shown on the
P4.5.1 Energy trip counter Varies 2296
P4.5.3
P4.5.4
P4.5.5
P4.5.6
Operating time
(graphical keypad)
Operating time
(standard keypad)
Operating time
(standard keypad)
Operating time
(standard keypad)
a d hh:min 2299 Resettable. See P4.5.1.
a Operating time in total years.
d Operating time in total days.
hh:min:ss
keypad.
To reset the counter:
Standard text keypad: Apply a long (4 s) push on the OK button. Graphical keypad: Push OK once.
counter
Push OK once again.
Operating time in hours, minutes and seconds.
Reset
page will appear.
2.3.4.6 Software info
Table 4: Diagnostics menu, Software info parameters
Index Parameter Min Max Unit Default ID Description
V4.6.1
V4.6.2
V4.6.3
V4.6.4 System load 0 100 % 2300 Load on control unit CPU.
V4.6.5
V4.6.6 Application ID 837 Application code.
V4.6.7 Application version 838
Software package
(graphical keypad)
Software package ID
(text keypad)
Software package
version
(text keypad)
Application name
(graphical keypad)
2524
Code for software identification.
2525 Name of application.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 20

2.3.5 I/O and hardware

Various options-related settings are located in this menu.
2.3.5.1
Basic I/O
Monitor here the statuses of inputs and outputs.
Table 5: I/O and Hardware menu, Basic I/O parameters
Index Parameter Min Max Unit Default ID Description
V5.1.1 Digital input 1 0 1 2502 Status of digital input signal
V5.1.2 Digital input 2 0 1 2503 Status of digital input signal
V5.1.3 Digital input 3 0 1 2504 Status of digital input signal
V5.1.4 Digital input 4 0 1 2505 Status of digital input signal
V5.1.5 Digital input 5 0 1 2506 Status of digital input signal
V5.1.6 Digital input 6 0 1 2507 Status of digital input signal
Shows the selected (with
V5.1.7 Analogue input 1 mode 1
V5.1.8 Analogue input 1 0 100 % 2509
V5.1.9 Analogue input 2 mode 1
V5.1.10 Analogue input 2 0 100 % 2511
V5.1.11
V5.1.12 Analogue output 1 0 100 % 2513
Analogue output 1
mode
-30...
+200°C
-30...
+200°C 2510
-30...
1
+200°C 2512
jumper) mode for Analogue
2508
input signal 1 = 0...20 mA
3 = 0...10 V
Status of analogue input signal
Shows the selected (with jumper) mode for Analogue input signal 1 = 0...20 mA
3 = 0...10 V
Status of analogue input signal
Shows the selected (with jumper) mode for Analogue otuput signal 1 = 0...20 mA
3 = 0...10 V
Status of analogue output signal
2.3.5.2
Option board slots
The parameters of this group depend on the option board installed. If no option board is placed in slots D or E, no parameters are visible. See Chapter 3.6.2 for the location of the slots.
As an option board is removed, info text F39 Device removed will appear on the display. See Table 74.
Menu Function Note Slot D Settings Option board related settings.
Monitoring Monitor option board-related info.
Slot E Settings Option board related settings.
Monitoring Monitor option board-related info.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 21 Keypad of the drive
2.3.5.3 Real time clock
Table 6: I/O and Hardware menu, Real time clock parameters
Index Parameter Min Max Unit Default ID Description
Status of battery.
M5.5.1 Battery state 1 3 2 2205
M5.5.2 Time hh:mm:ss 2201 Current time of day
M5.5.3 Date mm.dd. 2202 Current date
M5.5.4 Year yyyy 2203 Current year
M5.5.5 Daylight saving 1 4 1 2204
1 = Not installed 2 = Installed 3 = Change battery
Daylight saving rule 1 = Off 2 = EU 3 = US 4 = Russia
2.3.5.4 Power unit settings
Fan
The fan operates in optimized or always-on mode. In the optimized mode, fan speed is controlled according to the drive‘s internal logic that receives data from temperature measurements (if supported by the power unit) and the fan stops within 5 minutes when the drive is in Stop state. In always-on mode, the fan runs at full speed, without stopping.
Table 7: Power unit settings, Fan
Index Parameter Min Max Unit Default ID Description
V5.5.1.1 Fan control mode 0 1 1 2377
M5.6.1.5 Fan lifetime N/A N/A 0 849 Fan lifetime
M5.6.1.6
M5.6.1.7 Fan lifetime reset N/A N/A 0 823 Fan lifetime reset
Fan lifetime alarm
limit
0 200 000 h 50 000 824 Fan lifetime alarm limit
0 = Always on 1 = Optimized
Brake chopper
Table 8: Power unit settings, Brake chopper
Index Parameter Min Max Unit Default ID Description
0 = Disabled
P5.6.2.1 Brake chopper mode 0 3 0 2526
1 = Enabled (Run) 2 = Enabled (Run & Stop) 3 = Enabled (Run, no testing)
2
Sine filter
Sine filter support restricts overmodulation depth and prevents thermal management functions from decreasing switching frequency.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 22
Table 9: Power unit settings, Sine filter
Index Parameter Min Max Unit Default ID Description
P5.6.4.1 Sine filter 0 1 0 2507
0 = Disabled 1 = Enabled
2.3.5.5 Keypad
Table 10: I/O and Hardware menu, Keypad parameters
Index Parameter Min Max Unit Default ID Description
Time after which the display
P5.7.1 Timeout time 0 60 min 0 804
P5.7.2 Default page 0 4 0 2318
P5.7.3 Menu index 2499
P5.7.4 Contrast* 30 70 % 50 830
P5.7.5 Backlight time 0 60 min 5 818
returns to page defined with parameter P5.7.2. 0 = Not used
0 = None 1 = Enter menu index 2 = Main menu 3 = Control page 4 = Multimonitor
Set menu index for desired page and activate with parameter P5.7.2 = 1.
Set contrast of the display (30...70%).
Set the time until the backlight of the display turns off (0...60 min). If set to 0 s, backlight is always on.
* Only available with graphical keypad
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 23 Keypad of the drive
2.3.5.6 Fieldbus
Parameters related to different fieldbus boards can also be found in the I/O and Hardware menu. These parameters are explained in more detail in the respective fieldbus manual.
Submenu level 1 Submenu level 2 Submenu level 3 Submenu level 4 RS-485 Common settings Protocol Modbus/RTU
N2 BACnet MS/TP
Modbus/RTU Parameters Slave address
Baud rate Parity type Stop bits Communication timeout Operate mode
Monitoring Fieldbus protocol status
Communication status Illegal functions Illegal data addresses Illegal data values Slave device busy Memory parity error Slave device failure Last fault response Control word Status word
N2 Parameters Device address
Communication timeout
Monitoring Fieldbus protocol status
Communication status Invalid data Invalid commands Command not accepted Control word Status word
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 24
RS-485 BACnet MS/TP Parameters Baud rate
Autobauding MAC address Instance number Communication timeout
Monitoring Fieldbus protocol status
Communication status Actual instance number Fault code Control word Status word
Ethernet Common settings IP address mode
Fixed IP
IP address Subnet mask Default gateway
Modbus/TCP Common settings Connection limit
Monitoring* Fieldbus protocol status
BACnet/IP Settings Instance number
Monitoring Fieldbus protocol status
IP address Subnet mask Default gateway
Slave address Communication timeout
Communication status Illegal functions Illegal data addresses Illegal data values Slave device busy Memory parity error Slave device failure Last fault response Control word Status word
Communication timeout Protocol in use BBMD IP BBMD Port Time to live
Communication status Actual instance number Control word Status word
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 25 Keypad of the drive
* Will appear only after connection has been established
Table 11: RS-485 common settings
Index Parameter Min Max Unit Default ID Description
0 = No protocol
P5.8.1.1 Protocol 0 9 0 2208
4 = Modbus RTU 5 = N2 9 = BACnet MSTP
Table 12: ModBus RTU parameters (This table is only visible when P5.8.1.1 Protocol = 4/
Modbus RTU)
Index Parameter Min Max Unit Default ID Description
P5.8.3.1.1 Slave address 1 247 1 2320 Slave address
P5.8.3.1.2 Baud rate 300 230 400 bps 9600 2378 Baud rate
P5.8.3.1.3 Parity type Even None None 2379 Parity type
P5.8.3.1.4 Stop bits 1 2 2 2380 Stop bits
P5.8.3.1.5
P5.8.3.1.6 Operate mode Slave Master Slave 2374 Operate mode
Communication
timeout
0 65 535 s 10 2321
Communication timeout
Table 13: ModBus RTU monitoring (This table is only visible when P5.8.1.1 Protocol = 4/
Modbus RTU)
Index Parameter Min Max Unit Default ID Description
M5.8.3.2.1
P5.8.3.2.2
M5.8.3.2.3 Illegal functions 0 2383 Illegal functions
M5.8.3.2.4 Illegal data addresses 0 2384 Illegal data addresses
M5.8.3.2.5 Illegal data values 0 2385 Illegal data values
M5.8.3.2.6 Slave device busy 0 2386 Slave device busy
M5.8.3.2.7 Memory parity error 0 2387 Memory parity error
M5.8.3.2.8 Slave device failure 0 2388 Slave device failure
M5.8.3.2.9 Last fault response 0 2389 Last fault response
M5.8.3.2.10 Control word 16#0 2390 Control word
M5.8.3.2.11 Status word 16#0 2391 Status word
Fieldbus protocol
status
Communication
status
0 2381 Fieldbus protocol status
0 0 0 2382 Communication status
Table 14: N2 parameters (This table is only visible when P5.8.1.1 Protocol = 5/N2)
2
Index Parameter Min Max Unit
P 5.8.3.1.1 Device address 1 255 1 2350 Device address
P 5.8.3.1.2
Communication
timeout
0 255 10 2351
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Defaul
t
ID Description
Communication
timeout
Keypad of the drive vacon • 26
Table 15: N2 monitoring (This table is only visible when P5.8.1.1 Protocol = 5/N2)
Index Parameter Min Max Unit Default ID Description
M5.8.3.2.1
M5.8.3.2.2
M5.8.3.2.3 Invalid data 0 2401 Invalid data
M5.8.3.2.4 Invalid commands 0 2402 Invalid commands
M5.8.3.2.5 Command NACK 0 2403 Command NACK
M5.8.3.2.6 Control word 16#0 2404 Control word
M5.8.3.2.7 Status word 16#0 2405 Status word
Fieldbus protocol
status
Communication
status
0 2399 Fieldbus protocol status
0 0 0 2400 Communication status
Table 16: BACnet MSTP parameters (This table is only visible when P5.8.1.1 Protocol = 9/
BACNetMSTP)
Index Parameter Min Max Unit Default ID Description
P5.8.3.1.1 Baud rate 9600 76 800 bps 9600 2392 Baud rate
P5.8.3.1.2 Autobauding 0 1 0 2330 Autobauding
P5.8.3.1.3 MAC address 1 127 1 2331 MAC address
P5.8.3.1.4 Instance number 0 4 194 303 0 2332 Instance number
P5.8.3.1.5
Communication
timeout
0 65 535 10 2333
Communication timeout
Table 17: BACnet MSTP monitoring (This table is only visible when P5.8.1.1 Protocol = 9/
BACNetMSTP)
Index Parameter Min Max Unit Default ID Description
M5.8.3.2.1
M5.8.3.2.2
M5.8.3.2.3 Actual instance 0 2395 Actual instance
M5.8.3.2.4 Fault code 0 2396 Fault code
M5.8.3.2.5 Control word 16#0 2397 Control word
M5.8.3.2.6 Status word 16#0 2398 Status word
Fieldbus protocol
status
Communication
status
0 2393
0 2394
Fieldbus protocol status
Communication status
Table 18: Ethernet common settings
Index Parameter Min Max Unit Default ID Description
P5.9.1.1 IP address mode 0 1 1 2482
0 = Fixed IP 1 = DHCP with AutoIP
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
vacon • 27 Keypad of the drive
Table 19: Fixed IP
Index Parameter Min Max Unit Default ID Description
P5.9.1.2.1 IP address 192.168.0.10 2529
P5.9.1.2.2 Subnet mask 255.255.0.0 2530
P5.9.1.2.3 Default gateway 192.168.0.1 2531
M5.9.1.3 IP address 0 2483 IP address
M5.9.1.4 Subnet mask 0 2484 Subnet mask
M5.9.1.5 Default gateway 0 2485 Default gateway
M5.9.1.6 MAC address 2486 MAC address
The parameter is in use if P5.9.1.1 = 0/Fixed IP
The parameter is in use if P5.9.1.1 = 0/Fixed IP
The parameter is in use if P5.9.1.1 = 0/Fixed IP
Table 20: ModBus TCP common settings
Index Parameter Min Max Unit Default ID Description
P5.9.2.1.1 Connection limit 0 3 3 2446 Connection limit
P5.9.2.1.2 Slave address 0 255 255 2447 Slave address
P5.9.2.1.3
Communication
timeout
0 65 535 s 10 2448
Communication timeout
Table 21: BACnet IP settings
Index Parameter Min Max Unit Default ID Description
P5.9.3.1.1 Instance number 0 4 194 303 0 2406 Instance number
P5.9.3.1.2
P5.9.3.1.3 Protocol in use 0 1 0 2408 Protocol in use
P5.9.3.1.4 BBMD IP 192.168.0.1 2409 BBMD IP
P5.9.3.1.5 BBMD Port 1 65 535 47 808 2410 BBMD Port
P5.9.3.1.6 Time to live 0 255 0 2411 Time to live
Communication
timeout
0 65 535 0 2407
Communication timeout
Table 22: BACnet IP monitoring
Index Parameter Min Max Unit Default ID Description
M5.9.3.2.1
P5.9.3.2.2
M5.9.3.2.3 Actual instance 0 2414 Invalid data
M5.9.3.2.4 Control word 16#0 2415 Control word
M5.9.3.2.5 Status word 16#0 2416 Status word
Fieldbus protocol
status
Communication
status
0 2412 Fieldbus protocol status
0 0 0 2413 Communication status
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Keypad of the drive vacon • 28

2.3.6 User settings

Table 23: User settings menu, General settings
Index Parameter Min Max Unit Default ID Description
P6.1 Language selections Varies Varies Varies 802
M6.5 Parameter backup See Table 24 below.
M6.6 Parameter compare See Table 25 below.
P6.7 Drive name Give name of drive if needed.
Depends on language package.
2.3.6.1
Parameter backup
Table 24: User settings menu, Parameter backup parameters
Index Parameter Min Max Unit Default ID Description
P6.5.1
P6.5.2
P6.5.3 Restore from keypad* 2488
P6.5.4 Save to set 1 2489
P6.5.5 Restore from set 1 2490
P6.5.6 Save to set 2 2491
P6.5.7 Restore from set 2 2492
Restore factory
defaults
Save to keypad
*
Restores default parameter
831
values and initiates the Startup Wizard
Save parameter values to
2487
keypad to e.g. copy them to another drive.
Load parameter values from keypad to the drive.
Save parameter values to parameter set 1.
Load parameter values from parameter set 1.
Save parameter values to parameter set 2.
Load parameter values from parameter set 2.
* Only available with graphical keypad
Table 25: Parameter compare
Index Parameter Min Max Unit Default ID Description
Starts comparing
P6.6.1 Active set-Set 1 2493
P6.6.2 Active set-Set 2 2494
P6.6.3 Active set-Defaults 2495
P6.6.4 Active set-Keypad set 2496
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
parameters to the selected set.
Starts comparing parameters to the selected set.
Starts comparing parameters to the selected set.
Starts comparing parameters to the selected set.
2
vacon • 29 Keypad of the drive
50.00 Hz
STOP READY I/O
STOP READY I/O
9172.emf
Motor Nom Freq
Favorites
Help
Motor Nom Freq
Monitor
Rem from favorites
STOP READY KeypadALARM
ID:2362 P8.2
User levels
User level
Normal
Access code
00000
STOP READY I/OALARM
00000
Min:0
Max:9
ID:2362 P8.2
Access code
9173.emf

2.3.7 Favourites

NOTE! This menu is not available in text keypad.
Favourites are typically used to collect a set of parameters or monitoring signals from any of the keypad menus. You can add items or parameters to the Favourites folder, see Chapter 2.1.2.6.
To remove an item or a parameter from the Favourites folder, do the following:

2.3.8 User levels

User level parameters are intended to restrict the visibility of parameters and to prevent unauthorized and inadvertent parameterization on the keypad.
Table 26: User level parameters
Index Parameter Min Max Unit Default ID Description
0 = Normal 1 = Monitoring
P8.1 User level 0 1 0 1194
P8.2 Access code 0 9 0 2362
In monitoring level only the Monitor, Favourites and User Levels menus are visible in the main menu.
If set to other value than 0 before switching to monitoring when e.g. user level Normal is active, the access code will be asked when trying to switch back to Normal. Can therefore be used to prevent unauthorized parameterization on the keypad.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 30

3. VACON HVAC APPLICATION

The Vacon HVAC drive contains a preloaded application for instant use.
The parameters of this application are listed in Chapter 3.6 of this manual and explained in more detail in Chapter 3.7.

3.1 Specific functions of Vacon HVAC application

The Vacon HVAC application is an easy-to-use application for not only basic Pump and Fan applications where only one motor and one drive is needed but also offers extensive possibilities for PID control.
Features
Start-Up Wizard for extremely fast setup for basic pump or fan applications.
Mini-Wizards to ease the setup of applications.
Loc/Rem button for easy change between Local (keypad) and Remote control place.
The remote control place is selectable by parameter. (I/O or Fieldbus)
Control page for easy operation and monitoring of the most essential values.
Run interlock input (Damper interlock). Drive will not start before this input is
activated.
•Different pre-heat modes used to avoid condensation problems.
Maximum output frequency 320 Hz
Real-time clock and timer functions available (optional battery required). Possible to
program 3 time channels to achieve different functions on the drive (e.g. Start/Stop and Preset frequencies).
External PID-controller available.
Sleep mode function which automatically enables and disables drive running with user
defined levels to save energy.
2-zone PID-controller (2 different feedback signals; minimum and maximum control).
Two setpoint sources for the PID-control. Selectable with digital input.
PID setpoint boost function
Feedforward function to improve the response to the process changes.
Process value supervision
Multi-Pump control
Pressure loss compensation for compensating pressure losses in the pipework e.g.
when sensor is incorrectly placed near the pump or fan.
Can be used to control e.g. a valve using the drive’s I/O.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 31 Vacon HVAC Application

3.2 Example of control connections

Table 27. Connection example, standard I/O board
Standard I/O board
Termina l Signal Default
Reference potentiometer
1...10 kΩ
Remote reference
4...20mA/0...10V
(programmable)
+10 V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ref
AI1+
AI1-
AI2+
AI2-
24 V
out
GND I/O ground
DI1 Digital input 1 Start FWD
DI2 Digital input 2 Start REV
DI3 Digital input 3 Fault
CM
24 V
out
GND I/O ground
DI4 Digital input 4
DI5 Digital input 5
DI6 Digital input 6
Reference output
Analogue input, voltage or current Analogue input common
(current) Analogue input,
voltage or current Analogue input common
(current)
24 V aux. voltage
Common A for DIN1-DIN6
24 V aux. voltage
*
**
Voltage
Current
Preset
freq select
1
Preset
freq select
2
Fault reset
3
mA
To Relay board
1 or 2
CM Common A for DIN1-DIN6**
17
AO1+ Analogue signal (+output)
18
AO-/GND Analogue output common
19
+24 V
30
A
B
*
Selectable with DIP switches, see Vacon 100
Installation Manual.
**
Digital inputs can be isolated from ground. See
Chapter 3.3.
in
RS485 Serial bus, negative
RS485 Serial bus, positive
24 V auxiliary input voltage
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Output
frequency
Vacon HVAC Application vacon • 32
From
Standard I/O board
From term.
#6 or 12
From
Standard I/O board
From term.
#12
From term.
RUN
From term.
RUN
#13
#13
Table 28. Connection example, Relay board 1
Relay board 1
Termina l Signal
21 RO1/1 NC 22 RO1/2 CM
Relay output 1 RUN
23 RO1/3 NO 24 RO2/1 NC 25 RO2/2 CM
Relay output 2 FAULT
26 RO2/3 NO 32 RO3/1 CM
Relay output 3 READY
33 RO3/2 NO
Table 29. Connection example, Relay board 2
Relay board 2
Termina l Signal
21 RO1/1 NC 22 RO1/2 CM
Relay output 1 RUN
23 RO1/3 NO 24 RO2/1 NC 25 RO2/2 CM
Relay output 2 FAULT
26 RO2/3 NO 28 TI1+
Thermistor input
29 TI1-
Default
Default
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 33 Vacon HVAC Application
AO1
AI2
AI1
RS485*
DGND
9054.emf
OFFOFF
ONON
AC V AC V AC V

3.3 Isolating digital inputs from ground

The digital inputs (terminals 8-10 and 14-16) on the standard I/O board can also be isolated from ground by setting the dip switch on the control board to position OFF.
See Figure 13 to locate the switches and make appropriate selections for your requirements.
Figure 13. Dip switches and their default positions. * Bus terminator resistor
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 34

3.4 HVAC Application - Quick setup parameter group

The Quick Setup parameter group is a collection of parameters that are most commonly used during installation and commissioning. They are collected in the first parameter group so that they can be found fast and easily. They can, however, be also reached and edited in their actual parameter groups. Changing a parameter value in the Quick setup group also changes the value of this parameter in its actual group.
Table 30: Quick setup parameter group
Index Parameter Min Max Unit Default ID Description
on the
n
on the
n
on the
n
on the
n
on the
n
P1.1 Motor nominal voltage Varies Varies V Varies 110
P1.2
P1.3 Motor nominal speed 24 19200 rpm Varies 112
P1.4 Motor nominal current Varies Varies A Varies 113
P1.5 Motor Cos Phi 0.30 1.00 Varies 120
P1.6 Motor nominal power Varies Varies kW Varies 116
P1.7 Motor current limit Varies Varies A Varies 107
P1.8 Minimum frequency 0.00 P1.9 Hz Varies 101
P1.9 Maximum frequency P1.8 320.00 Hz 50.00 102
P1.10
P1.11 Preset frequency 1 P3.3.1 300.00 Hz 10.00 105
P1.12 Preset frequency 2 P3.3.1 300.00 Hz 15.00 106
P1.13 Acceleration time 1 0.1 3000.0 s 20.0 103
P1.14 Deceleration time 1 0.1 3000.0 s 20.0 104
P1.15 Remote control place 1 2 1 172
P1.16 Automatic reset 0 1 0 731
Motor nominal
frequency
I/O control reference A
selection
8.00 320.00 Hz 50.00 111
18 6117
Find this value U rating plate of the motor.
See page 48.
Find this value f rating plate of the motor.
See page 48.
Find this value n rating plate of the motor.
Find this value I rating plate of the motor.
Find this value on the rating plate of the motor.
Find this value I rating plate of the motor.
Maximum motor current from AC drive.
Minimum allowed frequency reference.
Maximum allowed frequency reference.
Selection of ref source when control place is I/O A. See page 52 for selections.
Select with digital input: Preset frequency selection 0 (P3.5.1.15) (Default = Digital Input 4)
Select with digital input: Preset frequency selection 1 (P3.5.1.16) (Default = Digital Input 5)
Time to accelerate from zero to maximum frequency.
Time to decelerate from minimum to zero frequency.
Selection of remote control place (start/stop) 1 = I/O 2 = Fieldbus
0 = Disabled 1 = Enabled
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 35 Vacon HVAC Application
Table 30: Quick setup parameter group
0 = Inactive
P1.17 PID Mini-Wizard * 0 1 0 1803
P1.18 Multi-Pump Wizard * 0 1 0
P1.19 Startup Wizard ** 0 1 0 1171
P1.20 Fire Mode Wizard * 0 1 0 1672
1 = Activate See Chapter 1.2.
0 = Inactive 1 = Activate See Chapter 1.3.
0 = Inactive 1 = Activate See Chapter 1.1.
0 = Inactive 1 = Activate
* = The parameter is only visible on the graphical keypad. ** = The parameter is only visible on the graphical and the text keypad.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 36

3.5 Monitor group

Vacon 100 AC drive provides you with a possibility to monitor the actual values of parameters and signals as well as statuses and measurements. Some of the values to be monitored are customizable.

3.5.1 Multimonitor

On the multi-monitor page, you can collect nine values that you wish to monitor. See page 16 for more information.

3.5.2 Basic

See Table 31 in which the basic monitoring values are presented.
NOTE!
Only Standard I/O board statuses are available in the Monitor menu. Statuses for all I/O board signals can be found as raw data in the I/O and Hardware system menu.
Check expander I/O board statuses when required in the I/O and Hardware system menu.
Table 31: Monitoring menu items
Code Monitoring value Unit ID Description
V2.2.1 Output frequency Hz 1 Output frequency to motor V2.2.2 Frequency reference Hz 25 Frequency reference to motor control V2.2.3 Motor speed rpm 2 Motor speed in rpm V2.2.4 Motor current A 3 V2.2.5 Motor torque % 4 Calculated shaft torque V2.2.7 Motor shaft power % 5 Total power consumption of AC drive V2.2.8 Motor shaft power kW/hp 73
V2.2.9 Motor voltage V 6 V2.2.10 DC link voltage V 7 V2.2.11 Unit temperature °C 8 Heatsink temperature V2.2.12 Motor temperature % 9 Calculated motor temperature V2.2.13 Analogue input 1 % 59 Signal in percent of used range V2.2.14 Analogue input 2 % 60 Signal in percent of used range V2.2.15 Analogue output 1 % 81 Signal in percent of used range
V2.2.16 Motor Preheat 1228
V2.2.17 Drive Status Word 43
0 = OFF 1 = Heating (feeding DC-current)
Bit coded status of drive B1 = Ready B2 = Run B3 = Fault B6 = RunEnable B7 = AlarmActive B10 = DC Current in stop B11 = DC Brake Active B12 = RunRequest B13 = MotorRegulatorActive
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 37 Vacon HVAC Application
Table 31: Monitoring menu items
Code Monitoring value Unit ID Description
V2.2.18 Last active fault 37
V2.2.19 Fire mode status 1597
V2.2.20 DIN Status Word 1 56
V2.2.21 DIN Status Word 2 57
V2.2.22
V2.2.23 Appl.StatusWord 1 89
V2.2.24 Appl.StatusWord 2 90
V2.2.25 kWhTripCounter Low 1054
V2.2.26 kWhTripCounter High 1067
Motor current with 1 decimal
45
The fault code of latest activated fault that has not been reset.
0 = Disabled 1 = Enabled 2 = Activated (Enabled + DI open) 3 = Test mode
16-bit word where each bit represents the status of one digital input. 6 digital inputs at every slot are read. Word 1 starts from input 1 in slot A (bit0) and goes to input 4 in slot C (bit15).
16-bit word where each bit represents the status of one digital input. 6 digital inputs at every slot are read. Word 2 starts from input 5 in slot C (bit0) and goes to input 6 in slot E (bit13).
Motor current monitor value with a fixed number of decimals and less filtering. Can be used e.g. for fieldbus purposes to always get the right value regardless of frame size, or monitoring when less filtering time is needed for the motor current.
Bit coded Application Status Word 1. B0 = Interlock1, B1 = Interlock2, B5 = I/O A Control Act., B6 = I/O B Control Act., B7 = Fieldbus Control Act., B8 = Local Control Act., B9 = PC Control Act., B10 = Preset Frequencies Act., B12 = FireMode Act., B13 = PreHeat Act.
Bit coded Application Status Word 2. B0 = Acc/Dec Prohibited, B1 = MotorSwitch Act.
Energy counter with kWh output. (Low Word)
Determines how many times energy counter has spinned around. (High Word)
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 38

3.5.3 Timer functions monitoring

Here you can monitor values of timer functions and the Real Time Clock.
Table 32: Monitoring of timer functions
Code Monitoring value Unit ID Description
V2.3.1 TC 1, TC 2, TC 3 1441
V2.3.2 Interval 1 1442 Status of timer interval V2.3.3 Interval 2 1443 Status of timer interval V2.3.4 Interval 3 1444 Status of timer interval V2.3.5 Interval 4 1445 Status of timer interval V2.3.6 Interval 5 1446 Status of timer interval V2.3.7 Timer 1 s 1447 Remaining time on timer if active V2.3.8 Timer 2 s 1448 Remaining time on timer if active V2.3.9 Timer 3 s 1449 Remaining time on timer if active
V2.3.10 Real time clock 1450
Possible to monitor the statuses of the three Time Channels (TC)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 39 Vacon HVAC Application

3.5.4 PID1 controller monitoring

Table 33: PID1-controller value monitoring
Code Monitoring value Unit ID Description
V2.4.1 PID1 setpoint Varies 20 Process units selected with parameter V2.4.2 PID1 feedback Varies 21 Process units selected with parameter V2.4.3 PID1 error value Varies 22 Process units selected with parameter
V2.4.4 PID1 output % 23
V2.4.5 PID1 status 24

3.5.5 PID2 controller monitoring

Table 34: PID2-controller value monitoring
Output to motor control or external control (AO)
0 = Stopped 1 = Running 3 = Sleep mode 4 = In dead band (see page 74)
Code Monitoring value Unit ID Description
V2.5.1 PID2 setpoint Varies 83 Process units selected with parameter V2.5.2 PID2 feedback Varies 84 Process units selected with parameter V2.5.3 PID2 error value Varies 85 Process units selected with parameter V2.5.4 PID2 output % 86 Output to external control (AO)
0 = Stopped
V2.5.5 PID2 status 87

3.5.6 Multi-pump monitoring

Table 35: Multi-pump monitoring
Code Monitoring value Unit ID Description
V2.6.1 Motors running 30
V2.6.2 Autochange 1114
1 = Running 2 = In dead band (see page 74)
The number of motors running when Multi-Pump function is used.
Informs the user if autochange is requested.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 40

3.5.7 Fieldbus data monitoring

Table 36: Fieldbus data monitoring
Code Monitoring value Unit ID Description
Fieldbus control word used by application in
V2.8.1 FB Control Word 874
V2.8.2
V2.8.3 FB data in 1 876 Raw value of process data in 32-bit signed format V2.8.4 FB data in 2 877 Raw value of process data in 32-bit signed format V2.8.5 FB data in 3 878 Raw value of process data in 32-bit signed format V2.8.6 FB data in 4 879 Raw value of process data in 32-bit signed format V2.8.7 FB data in 5 880 Raw value of process data in 32-bit signed format V2.8.8 FB data in 6 881 Raw value of process data in 32-bit signed format V2.8.9 FB data in 7 882 Raw value of process data in 32-bit signed format
V2.8.10 FB data in 8 883 Raw value of process data in 32-bit signed format
V2.8.11 FB Status Word 864
V2.8.12 FB speed actual 865
V2.8.13 FB data out 1 866 Raw value of process data in 32-bit signed format V2.8.14 FB data out 2 867 Raw value of process data in 32-bit signed format V2.8.15 FB data out 3 868 Raw value of process data in 32-bit signed format V2.8.16 FB data out 4 869 Raw value of process data in 32-bit signed format V2.8.17 FB data out 5 870 Raw value of process data in 32-bit signed format V2.8.18 FB data out 6 871 Raw value of process data in 32-bit signed format V2.8.19 FB data out 7 872 Raw value of process data in 32-bit signed format V2.8.20 FB data out 8 873 Raw value of process data in 32-bit signed format
FB speed
reference
bypass mode/format. Depending on the fieldbus type or profile the data can be modified before sent to application.
Speed reference scaled between minimum and maximum frequency at the moment it was received by the application. Minimum and
875
maximum frequencies can changed after the refe-rence was received without affecting the refe-rence.
Fieldbus status word sent by application in bypass mode/format. Depending on the FB type or profile the data can be modified before sent to the FB.
Actual speed in %. 0 and 100% correspond to minimum and maximum frequencies respectively. This is continuously updated depending on the momentary min and max frequencies and the output frequency.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 41 Vacon HVAC Application

3.5.8 Temperature inputs monitoring

This menu is only visible if there is an option card installed having temperature measurement inputs, such as the OPT-BJ option cards.
Table 37: Temperature inputs monitoring
Index Parameter Min Max Unit Default ID Description
Measured value of Temperature Input 1. If input is available but no sensor is
P2.9.1 Temp.Input 1 -50.0 200.0 °C 200.0 50
P2.9.2 Temp.Input 2 -50.0 200.0 °C 200.0 51
P2.9.3 Temp.Input 3 -50.0 200.0 °C 200.0 52
connected the maximum value is shown because measured resistance is endless.
Measured value of Temperature Input 2. If input is available but no sensor is connected the maximum value is shown because measured resistance is endless.
Measured value of Temperature Input 3. If input is available but no sensor is connected the maximum value is shown because measured resistance is endless.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 42
( 17 )
( 6 )
ID: M3
STOP READY Keypad
( 13 )
STOP READY Keypad
 
( 2 )
( 7 )
( 18 )
ID: M3.1
11091.emf
Main Menu
Quick Setup
Monitor
Parameters
Motor Settings
Start/Stop Setup
References
Parameters
9151.emf

3.6 Vacon HVAC Application - Application parameter lists

Find the parameter menu and the parameter groups as guided below.
The HVAC Application embodies the following parameter groups:
Table 38. Parameter groups
Menu and Parameter group Description
Group 3.1: Motor settings Basic and advanced motor settings. Group 3.2: Start/Stop setup Start and stop functions. Group 3.3: Control reference settings Frequency reference setup. Group 3.4: Ramp & Brakes Setup Acceleration/Deceleration setup. Group 3.5: I/O Configuration I/O programming. Group 3.6: Fieldbus Data Mapping Fieldbus data out parameters. Group 3.7: Prohibit Frequencies Prohibit frequencies programming. Group 3.8: Limit supervisions Programmable limit controllers. Group 3.9: Protections Protections configuration. Group 3.10: Automatic reset Auto reset after fault configuration. Group 3.11: Timer functions Configuration of 3 timers based on Real Time Clock.
Group 3.12: PID-controller 1
Parameters for PID Controller 1. Motor control or
external usage. Group 3.13: PID-controller 2 Parameters for PID Controller 2. External usage. Group 3.14: Multi-pump Parameters for multi-pump usage. Group 3.16: Fire mode Parameters for Fire Mode. Group 3.17 Application Settings
Group 3.18 kWh Pulse Output
Parameters for configuring an digital output giving
pulses corresponding to the kWh counter.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 43 Vacon HVAC Application

3.6.1 Column explanations

Code = Location indication on the keypad; Shows the operator the parameter
number. Parameter = Name of parameter Min = Minimum value of parameter Max = Maximum value of parameter Unit = Unit of parameter value; Given if available Default = Value preset by factory ID = ID number of the parameter Description = Short description of parameter values or its function
= More information on this parameter available; Click the parameter name.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 44
11071.emf

3.6.2 Parameter programming

The programming of digital inputs in Vacon HVAC Application is very flexible. There are no digital terminals assigned only for certain function. You can choose the terminal of your choice for the certain function, in other words, functions appear as parameters which the operator defines a certain input for. For a list of functions for the digital inputs, see Table 45 on page 56.
Also
Time Channels can be assigned to digital inputs. See more information on page 70.
The selectable values of the programmable parameters are of type
DigIN SlotA.1 (graphical keypad) or
dI A.1 (text keypad)
in which
‘DigIN / dI’ stand for digital input. ‘Slot_’ refers to the board; A and B are Vacon AC drive standard boards, D and E are option boards (see Figure 14). See
Chapter 3.6.2.3. The number after the board letter refers to the respective terminal on the selected board. Hence, SlotA.1 / A.1 means terminal DIN1 on the standard board in board slot A. The parameter (signal) is not connected to any terminal, i.e. it is not used, if, instead of a letter, the final number is preceded by a ‘0’ (for example DigIN Slot0.1 / dI 0.1).
Figure 14. Option board slots
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 45 Vacon HVAC Application
STOP READY Keypad
( 17 )
( 5 )
ID: M3
( 12 )
STOP READY Keypad
 
( 18 )
( 4 )
( 7 )
ID: M3.5
STOP READY Keypad
 
( 26 )
( 36 )
( 1 )
ID: M3.5.1
STOP READY Keypad
DigIn Slot0.1
DigIn Slot0.1
DigIn SlotA.1
ID:404 M3.5.1.2
9149.emf
Main Menu
Quick Setup
Monitor
Parameters
References
Parameters
I/O Config
Ramps and Brakes
I/O Config
Digital Inputs
Analog Inputs
Digital Outputs
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 2 A
Ctrl Signal 1 B
OK OK OK
STOP READY Keypad
DigIn Slot0.1
DigIn Slot0.1
DigIn SlotA.1
ID:404 M3.5.1.2
STOP READY Keypad
ID: M3.5.1.2
STOP READY Keypad
Min:
Max:
ID:404 M3.5.1.2
9150.emf
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 2 A
Ctrl Signal 1 B
Ctrl signal 2 A
Edit
Help
Add to favorites
Ctrl signal 2 A
DigIN SlotA.2
DigIN Slot0 DigIN SlotA DigIN SlotB DigIN SlotC DigIN SlotD DigIN SlotE TimeChannel Fieldbus CW LLP signal
0-10 Varies Varies Varies Varies Varies 1-3 0-31 1-5
OK OK
EXAMPLE:
You want to connect the
Control signal 2 A (parameter P3.5.1.2) to digital input DI2 on
Standard I/O board.
3.6.2.1 Example programming with graphical keypad
1
Locate the parameter Control signal 2 A (P3.5.1.2) on the keypad.
2
3
3
Enter the Edit mode.
Change the value: The editable part of the value (DigIN Slot0) is underlined and blinking. Change the slot to DigIN SlotA or assign the signal to Time Channel with the arrow keys up and down. Make the terminal value (.1) editable by pressing the right key once and change the value to ‘2’ with arrow keys up and down.
Accept the change with OK button or return to previous menu level with BACK/ RESET button.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 46
9156.emf
OK OK
OK
9157.emf
OK
OK
3.6.2.2 Example programming with text keypad
1
2
Locate the parameter Control signal 2 A (P3.5.1.2) on the keypad.
Enter the Edit mode by pressing OK. The initial character starts to blink. Change the value of signal source to ‘A’ with the arrow buttons. Then press the arrow button right. Now the terminal number blinks. Connect the parameter
Control signal 2 A (P3.5.1.2) to terminal DI2 by setting the terminal
number to ‘2’.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 47 Vacon HVAC Application
3.6.2.3 Descriptions of signal sources:
Table 39. Descriptions of signal sources
Source Function
Slot0 1 = Always FALSE, 2-9 = Always TRUE
SlotA Number corresponds to digital input in the slot.
SlotB Number corresponds to digital input in the slot.
SlotC Number corresponds to digital input in the slot.
SlotD Number corresponds to digital input in the slot.
SlotE Number corresponds to digital input in the slot.
TimeChannel (tCh) 1 = Time Channel 1, 2 = Time Channel 2, 3 = Time Channel 3
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 48

3.6.3 Group 3.1: Motor settings

3.6.3.1 Basic Settings
Table 40: Basic motor settings
Index Parameter Min Max Unit Default ID Description
P3.1.1.1 Motor nominal voltage Varies Varies V Varies 110
P3.1.1.2
P3.1.1.3 Motor nominal speed 24 19200 rpm Varies 112
P3.1.1.4 Motor nominal current Varies Varies A Varies 113
P3.1.1.5 Motor Cos Phi 0.30 1.00 Varies 120
P3.1.1.6 Motor nominal power Varies Varies kW Varies 116
P3.1.1.7 Motor current limit Varies Varies A Varies 107
P3.1.1.8 Motor type 0 1 0 650
Motor nominal
frequency
8.00 320.00 Hz Varies 111
Find this value U rating plate of the motor.
This parameter sets the voltage at the field weakening point to 100% * U
connection (Delta/Star).
Find this value f rating plate of the motor.
Find this value n rating plate of the motor.
Find this value I rating plate of the motor.
Find this value on the rating plate of the motor
Find this value In on the rating plate of the motor.
Maximum motor current from AC drive.
Select what motor type is used. 0 = asynchronous induction motor, 1 = PM synchronous motor.
. Note also used
nMotor
on the
n
on the
n
on the
n
on the
n
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 49 Vacon HVAC Application
3.6.3.2 Motor Control Settings
Table 41: Advanced motor settings
Index Parameter Min Max Unit Default ID Description
Motor noise can be minimised using a high switching frequency. Increasing the switching frequency reduces the
P3.1.2.1 Switching frequency 1.5 Varies kHz Varies 601
P3.1.2.2 Motor switch 0 1 0 653
P3.1.2.4
P3.1.2.5
P3.1.2.6
P3.1.2.7
P3.1.2.9 U/f ratio selection 0 1 Varies 108
P3.1.2.15
P3.1.2.16
P3.1.2.17 StatorVoltAdjust 50.0% 150.0% 100.0 659
Zero frequency
voltage
Motor preheat
function
Motor preheat
temperature limit
Motor preheat
current
Overvoltage
controller
Undervoltage
controller
0.00 40.00 % Varies 606
0 3 0 1225
-20 80 °C 0 1226
0
0 1 1 607
0 1 1 608
0.5*I
A Varies 1227
L
capacity of the drive. It is recommended to use a lower frequency when the motor cable is long in order to minimize capacitive currents in the cable.
Enabling this function prevents the drive from tripping when the motor switch is closed and opened e.g. using flying start. 0 = Disabled 1 = Enabled
This parameter defines the zero frequency voltage of the U/f curve. The default value varies according to unit size.
0 = Not used 1 = Always in stop state 2 = Controlled by DI 3 = Temp limit (heatsink)
NOTE! Virtual digital input
can be activated by Real Time Clock
Motor preheat is switched on when the heatsink temperature goes below this level (if par. P3.1.2.5 is set to
Temperature limit.
If limit is e.g. 10 °C feeding current starts at 10 °C and stops at 11 °C (1-degree hysteresis).
DC current for pre-heating of motor and drive in stop state. Activated by digital input or by temperature limit.
Type of U/f curve between zero frequency and the field weakening point. 0 = Linear 1 = Squared
0 = Disabled 1 = Enabled
0 = Disabled 1 = Enabled
Parameter for adjusting stator voltage in permanent magnet motors.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 50
Table 41: Advanced motor settings
Index Parameter Min Max Unit Default ID Description
The drive searches for the minimum motor current in order to save energy and to
P3.1.2.18 Energy Optimization 0 1 0 666
P3.1.2.19 Flying Start Options 0 1
P3.1.2.20 I/f Start 0 1 0 534
P3.1.2.21 I/f Start Frequency 5 25 Hz
P3.1.2.22 I/f Start Currency 0 100 % 80 536
0.2 x
P3.1.1.2
lower the motor noise. This function can be used e.g. in fan and pump applications 0 = Disabled 1 = Enabled
0 = Shaft direction is searched from both directions.
1590
1 = Shaft direction is searched only from the same direction as the frequency reference.
This parameter enables/ disables the I/f Start function. 0 = Disabled 1 = Enabled
Output frequency limit, below
535
which the I/f Start function is activated.
Defines the current that is fed to the motor when I/f start function is activated, in percentage of the nominal current.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 51 Vacon HVAC Application

3.6.4 Group 3.2: Start/Stop setup

Start/Stop commands are given differently depending on the control place.
Remote control place (I/O A): Start, stop and reverse commands are controlled by 2 digital inputs chosen with parameters P3.5.1.1 and P3.5.1.2. The functionality/logic for these inputs is then selected with parameter P3.2.6 (in this group).
Remote control place (I/O B): Start, stop and reverse commands are controlled by 2 digital inputs chosen with parameters P3.5.1.3 and P3.5.1.4. The functionality/logic for these inputs is then selected with parameter P3.2.7 (in this group).
Local control place (Keypad): Start and stop commands come from the keypad buttons, while the direction of rotation is selected by the parameter P3.3.7.
Remote control place (Fieldbus): Start, stop and reverse commands come from fieldbus.
Table 42. Start/Stop Setup menu
Index Parameter Min Max Unit Default ID Description
Selection of remote control place (start/stop). Can be used to change back to
P3.2.1
P3.2.2 Local/Remote 0 1 0 211
P3.2.3 Keypad stop button 0 1 0 114
P3.2.4 Start function 0 1 Varies 505
P3.2.5 Stop function 0 1 0 506
P3.2.6
P3.2.7
P3.2.8 Fieldbus start logic 0 1 0 889
Remote control
place
I/O A start/stop
logic
I/O B start/stop
logic
0 1 0 172
0 4 0 300
0 4 0 363 See above.
remote control from Vacon Live e.g. in case of a broken panel. 0 = I/O control 1 = Fieldbus control
Switch between local and remote control places 0 = Remote 1 = Local
0 = Stop button always enabled (Yes) 1 = Limited function of Stop button (No)
0 = Ramping 1 = Flying start
0 = Coasting 1 = Ramping
Logic = 0:
Ctrl sgn 1 = Forward Ctrl sgn 2 = Backward
Logic = 1:
Ctrl sgn 1 = Forward (edge) Ctrl sgn 2 = Inverted Stop
Logic = 2:
Ctrl sgn 1 = Forward (edge) Ctrl sgn 2 = Bckwrd (edge)
Logic = 3:
Ctrl sgn 1 = Start Ctrl sgn 2 = Reverse
Logic = 4:
Ctrl sgn 1 = Start (edge) Ctrl sgn 2 = Reverse
0 = Rising edge required 1 = State
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 52

3.6.5 Group 3.3: Control reference settings

The requency reference source is programmable for all control places except
PC, which
always takes the reference from the PC tool.
Remote control place (I/O A): The source of frequency reference can be selected with parameter P3.3.3.
Remote control place (I/O B): The source of frequency reference can be selected with parameter P3.3.4.
Local control place (Keypad): If the default selection for parameter P3.3.5 is used the reference set with parameter P3.3.6 applies.
Remote control place (Fieldbus): The frequency reference comes from fieldbus if the default value for parameter P3.3.9 is kept.
Table 43: Control reference settings
Index Parameter Min Max Unit Default ID Description
P3.3.1
P3.3.2
P3.3.3
P3.3.4
P3.3.5
P3.3.6 Keypad reference 0.00 P3.3.2 Hz 0.00 184
P3.3.7 Keypad direction 0 1 0 123
Minimum frequency
Maximum frequency
I/O control
reference
selection
A
I/O control
reference
selection
B
Keypad Ctrl
Reference selection
0.00 P3.3.2 Hz 0.00 101
P3.3.1 320.00 Hz 50.00 102
18 6117
18 4131
18 2121
Minimum allowed frequency reference
Maximum allowed frequency reference
Selection of ref source when control place is I/O A 1 = Preset Frequency 0 2 = Keypad reference 3 = Fieldbus 4 = AI1 5 = AI2 6 = AI1+AI2 7 = PID 1 reference 8 = Motor potentiometer
Selection of ref source when control place is I/O B. See above. NOTE! I/O B control place can only be forced active with digital input (P3.5.1.5).
Selection of ref source when control place is keypad: 1 = Preset Frequency 0 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = AI1+AI2 7 = PID 1 reference 8 = Motor potentiometer
The frequency reference can be adjusted on the keypad with this parameter.
Motor rotation when control place is keypad 0 = Forward 1 = Reverse
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 53 Vacon HVAC Application
Table 43: Control reference settings
Selects function for Run state & Reference copy when changing
P3.3.8
P3.3.9
P3.3.10
P3.3.11 Preset frequency 0 P3.3.1 P3.3.2 Hz 5.00 180
P3.3.12 Preset frequency 1 P3.3.1 P3.3.2 Hz 10.00 105
P3.3.13 Preset frequency 2 P3.3.1 P3.3.2 Hz 15.00 106
P3.3.14 Preset frequency 3 P3.3.1 P3.3.2 Hz 20.00 126
P3.3.15 Preset frequency 4 P3.3.1 P3.3.2 Hz 25.00 127
P3.3.16 Preset frequency 5 P3.3.1 P3.3.2 Hz 30.00 128
P3.3.17 Preset frequency 6 P3.3.1 P3.3.2 Hz 40.00 129
P3.3.18 Preset frequency 7 P3.3.1 P3.3.2 Hz 50.00 130
P3.3.19
P3.3.20
P3.3.21
Keypad reference
copy
Fieldbus control
reference selection
Preset frequency
mode
Preset alarm
frequency
Motor
potentiometer
ramp time
Motor
potentiometer reset 0 2 1 367
02 1181
18 3122
01 0182
P3.3.1 P3.3.2 Hz 25.00 183
0.1 500.0 Hz/s 10.0 331
to Keypad control: 0 = Copy reference 1 = Copy ref & Run State 2 = No copying
Selection of ref source when control place is Fieldbus: 1 = Preset frequency 0 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = AI1+AI2 7 = PID 1 reference 8 = Motor potentiometer
0 = Binary coded 1 = Number of inputs. Preset frequency is selected according to how many of preset speed digital inputs are active.
Basic preset frequency 0 when selected by Control reference parameter (P3.3.3).
Select with digital input: Preset frequency selection 0 (P3.5.1.15)
Select with digital input: Preset frequency selection 1 (P3.5.1.16)
Select with digital inputs: Preset frequency selection 0 & 1.
Select with digital input: Preset frequency selection 2 (P3.5.1.17)
Select with digital inputs: Preset frequency selection 0 & 2.
Select with digital inputs: Preset frequency selection 1 & 2.
Select with digital inputs: Preset frequency selection 0 & 1 & 2.
This frequency used when fault response (in Group 3.9: Protections) is Alarm+preset frequency.
Rate of change in the motor potentiometer reference when increased or decreased.
Motor potentiometer frequency reference reset logic. 0 = No reset 1 = Reset if stopped 2 = Reset if powered down
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 54
Table 43: Control reference settings
This parameter enables or disables the function to run the motor in reverse direction. This parameter shall be set to
P3.3.22 Reverse direction 0 1 0 15530
reverse prevented if there is a risk of causing damage to the process by running in reverse. 0 = Reverse allowed 1 = Reverse prevented
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 55 Vacon HVAC Application

3.6.6 Group 3.4: Ramp & Brakes Setup

Two ramps are available (two sets of acceleration time, deceleration time and ramp shape). The second ramp can be activated by a digital input. NOTE! Ramp 2 always has higher priority and is used if a digital input for ramp selection is activated or Ramp 2 threshold is smaller than RampFreqOut.
Table 44: Ramp and brakes setup
Index Parameter Min Max Unit Default ID Description
P3.4.1 Ramp 1 shape 0.0 10.0 s 0.0 500 S-curve time ramp 1.
Defines the time required for
P3.4.2 Acceleration time 1 0.1 3000.0 s 20.0 103
P3.4.3 Deceleration time 1 0.1 3000.0 s 20.0 104
P3.4.4 Ramp 2 shape 0.0 10.0 s 0.0 501
P3.4.5 Acceleration time 2 0.1 3000.0 s 20.0 502 See P3.4.2.
P3.4.6 Deceleration time 2 0.1 3000.0 s 20.0 503 See P3.4.3.
P3.4.7 Start magnetizing time 0.00 600.00 s 0.00 516
P3.4.8
P3.4.9
P3.4.10 DC brake current Varies Varies A Varies 507
P3.4.11
P3.4.12 Flux braking 0 1 0 520
P3.4.13 Flux braking current 0 Varies A Varies 519
Start magnetizing
current
DC braking time at
stop
Frequency to start DC
braking at ramp stop
Varies Varies A Varies 517
0.00 600.00 s 0.00 508
0.10 10.00 Hz 1.50 515
the output frequency to increase from zero frequency to maximum frequency.
Defines the time required for the output frequency to decrease from maximum frequency to zero frequency.
S-curve time ramp 2. See P3.4.1.
This parameter defines the time for how long DC current is fed to motor before acceleration starts.
Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping.
Defines the current injected into the motor during DC­braking. 0 = Disabled
The output frequency at which the DC-braking is applied.
0 = Disabled 1 = Enabled
Defines the current level for flux braking.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 56

3.6.7 Group 3.5: I/O Configuration

3.6.7.1 Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the required digital input terminal. The digital inputs are represented as, for example,
A.2,
meaning the second input on slot A.
DigIN Slot
It is also possible to connect the digital inputs to time channels which are also represented as terminals.
NOTE! The statuses of digital inputs and the digital output can be monitored in the Multimonitoring view, see Chapter 3.5.1.
Table 45: Digital input settings
Index Parameter Default ID Description
P3.5.1.1 Control signal 1 A DigIN SlotA.1 403 Start signal 1 when control place is I/O 1 (FWD)
P3.5.1.2 Control signal 2 A DigIN Slot0.1 404 Start signal 2 when control place is I/O 1 (REV)
P3.5.1.3 Control signal 1 B DigIN Slot0.1 423 Start signal 1 when control place is I/O B
P3.5.1.4 Control signal 2 B DigIN Slot0.1 424 Start signal 2 when control place is I/O B
P3.5.1.5 I/O B control force DigIN Slot0.1 425 TRUE = Force the control place to I/O B
P3.5.1.6 I/O B reference force DigIN Slot0.1 343
P3.5.1.7 External fault close DigIN SlotA.3 405
P3.5.1.8 External fault open DigIN Slot0.2 406
P3.5.1.9 Fault reset DigIN SlotA.6 414 Resets all active faults
P3.5.1.10 Run enable DigIN Slot0.2 407 Must be on to set drive in Ready state
P3.5.1.11 Run interlock 1 DigIN Slot0.1 1041
P3.5.1.12 Run interlock 2 DigIN Slot0.1 1042 As above.
P3.5.1.13 Motor preheat ON DigIN Slot0.1 1044
P3.5.1.14 Fire Mode activation DigIN Slot0.2 1596
P3.5.1.15
P3.5.1.16
P3.5.1.17
P3.5.1.18 Timer 1 DigIN Slot0.1 447
P3.5.1.19 Timer 2 DigIN Slot0.1 448 See above
P3.5.1.20 Timer 3 DigIN Slot0.1 449 See above
P3.5.1.21 PID1 setpoint boost DigIN Slot0.1 1047
P3.5.1.22 PID1 select setpoint DigIN Slot0.1 1046
Preset frequency
selection 0
Preset frequency
selection 1
Preset frequency
selection 2
DigIN SlotA.4 419
DigIN SlotA.5 420
DigIN Slot0.1 421
TRUE = Used frequency reference is specified by I/O reference B parameter (P3.3.4).
FALSE = OK TRUE = External fault
FALSE = External fault TRUE = OK
Drive will not start before this input is activated (Damper interlock).
FALSE = No acti on TRUE = Uses the motor preheat DC-Current in Stop state Used when parameter P3.1.2.5 is set to 2.
FALSE = Fire Mode active TRUE = No action
Binary selector for Preset speeds (0-7). See page 52.
Binary selector for Preset speeds (0-7). See page 52.
Binary selector for Preset speeds (0-7). See page 52.
Rising edge starts Timer 1 programmed in Group
3.11: Timer functions parameter group
FALSE = No boost TRUE = Boost
FALSE = Setpoint 1 TRUE = Setpoint 2
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 57 Vacon HVAC Application
Table 45: Digital input settings
FALSE = PID2 in stop mode TRUE = PID2 regulating
P3.5.1.23 PID2 start signal DigIN Slot0.2 1049
P3.5.1.24 PID2 select setpoint DigIN Slot0.1 1048
P3.5.1.25 Motor 1 interlock DigIN Slot0.1 426
P3.5.1.26 Motor 2 interlock DigIN Slot0.1 427
P3.5.1.27 Motor 3 interlock DigIN Slot0.1 428
P3.5.1.28
P3.5.1.29 Motor 5 interlock DigIN Slot0.1 430
P3.5.1.30 Motor potentiometer UP DigIN Slot0.1 418
P3.5.1.31
P3.5.1.32 Ramp 2 selection DigIN Slot0.1 408
P3.5.1.33 Fieldbus control DigIN Slot0.1 441 TRUE = Forces control place to fieldbus.
P3.5.1.39
P3.5.1.40
P3.5.1.41 Fire mode reverse DigIn Slot0.1 1618
P3.5.1.42 Keypad CTRL DigIn Slot0.1 410 Force control place to keypad.
Motor 4 interlock DigIN Slot0.1 429
Motor potentiometer
DOWN
Fire mode activation
open
Fire mode activation
close
DigIN Slot0.1 417
DigIn Slot0.2 1596
DigIn Slot0.1 1619
This parameter will have no effect if PID2 controller is not enabled in the Basic menu for PID2
FALSE = Setpoint 1 TRUE = Setpoint 2
FALSE = Not active TRUE = Active
FALSE = Not active TRUE = Active
FALSE = Not active TRUE = Active
FALSE = Not active TRUE = Active
FALSE = Not active TRUE = Active
FALSE = Not active TRUE = Active (Motor potentiometer reference INCREASES until the contact is opened)
FALSE = Not active TRUE = Active (Motor potentiometer reference DECREASES until the contact is opened)
Used for switching between ramp 1 and 2. OPEN = Ramp1 shape, acceleration time 1 and deceleration time 1. CLOSED = Ramp2 shape, acceleration time 2 and deceleration time 2.
Activates fire mode, if fire mode is enabled by correct password. FALSE = A ctive TRUE = Inactive
Activates fire mode, if fire mode is enabled by correct password. FALSE = A ctive TRUE = Inactive
Reverse command of rotation direction while running in Fire Mode. This DI has no effect in normal operation.
3
P3.5.1.43 ResetkWhTripCounter DigIN Slot0.1 1053 Reset kWh Trip Counter
P3.5.1.44
P3.5.1.45
Fire mode preset
frequency selection 0
Fire mode preset
frequency selection 1
DigIN Slot0.1 15531
DigIN Slot0.1 15532
Fire Mode frequency source has to be Fire Mode frequency before the selection can be activated.
Fire Mode frequency source has to be Fire Mode frequency before the selection can be activated.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 58
3.6.7.2 Analogue inputs
Table 46: Analogue input settings
Index Parameter Min Max Unit Default ID Description
Connect the AI1 signal to the
P3.5.2.1 AI1 signal selection
P3.5.2.2 AI1 signal filter time 0.00 300.00 s 1.0 378 Filter time for analogue input
P3.5.2.3 AI1 signal range 0 1 0 379
P3.5.2.4 AI1 custom. min -160.00 160.00 % 0.00 380
P3.5.2.5 AI1 custom. max -160.00 160.00 % 100.00 381 Custom range max setting
P3.5.2.6 AI1 signal inversion 0 1 0 387
P3.5.2.7 AI2 signal selection
P3.5.2.8 AI2 signal filter time 0.00 300.00 s 1.0 389 See P3.5.2.2.
P3.5.2.9 AI2 signal range 0 1 1 390
P3.5.2.10 AI2 custom. min -160.00 160.00 % 0.00 391 See P3.5.2.4.
P3.5.2.11 AI2 custom. max -160.00 160.00 % 100.00 392 See P3.5.2.5.
P3.5.2.12 AI2 signal inversion 0 1 0 398 See P3.5.2.6.
P3.5.2.13 AI3 signal selection
P3.5.2.14 AI3 signal filter time 0.00 300.00 s 1.0 142 Filter time for analogue input
P3.5.2.15 AI3 signal range 0 1 0 143
P3.5.2.16 AI3 custom. min -160.00 160.00 % 0.00 144 20% = 4-20 mA / 2-10 V
P3.5.2.17 AI3 custom. max -160.00 160.00 % 100.00 145 Custom range max setting
P3.5.2.18 AI3 signal inversion 0 1 0 151
P3.5.2.19 AI4 signal selection
P3.5.2.20 AI4 signal filter time 0.00 300.00 s 1.0 153 See P3.5.2.14.
P3.5.2.21 AI4 signal range 0 1 0 154
P3.5.2.22 AI4 custom. min -160.00 160.00 % 0.00 155 See P3.5.2.16.
P3.5.2.23 AI4 custom. max -160.00 160.00 % 100.00 156 See P3.5.2.17.
P3.5.2.24 AI4 signal inversion 0 1 0 162 See P3.5.2.18.
P3.5.2.25 AI5 signal selection
P3.5.2.26 AI5 signal filter time 0.00 300.00 s 1.0 189 Filter time for analogue input
P3.5.2.27 AI5 signal range 0 1 0 190
P3.5.2.28 AI5 custom. min -160.00 160.00 % 0.00 191 20% = 4-20 mA / 2-10 V
AnIN
SlotA.1
AnIN
SlotA.2
AnIN
Slot0.1
AnIN
Slot0.1
AnIN
Slot0.1
analogue input of your choice
377
with this parameter. Programmable
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA
Custom range min setting 20% = 4-20 mA / 2-10 V
0 = Normal 1 = Signal inverted
388 See P3.5.2.1.
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA
Connect the AI3 signal to the analogue input of your choice
141
with this parameter. Programmable
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA
0 = Normal 1 = Signal inverted
See P3.5.2.13.
152
Programmable
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA
Connect the AI5 signal to the analogue input of your choice
188
with this parameter. Programmable.
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 59 Vacon HVAC Application
Table 46: Analogue input settings
P3.5.2.29 AI5 custom. max -160.00 160.00 % 100.00 192 Custom range max setting
P3.5.2.30 AI5 signal inversion 0 1 0 198
P3.5.2.31 AI6 signal selection
P3.5.2.32 AI6 signal filter time 0.00 300.00 s 1.0 200 See P3.5.2.14.
P3.5.2.33 AI6 signal range 0 1 0 201
P3.5.2.34 AI6 custom. min -160.00 160.00 % 0.00 202 See P3.5.2.16.
P3.5.2.35 AI6 custom. max -160.00 160.00 % 100.00 203 See P3.5.2.17.
P3.5.2.36 AI6 signal inversion 0 1 0 209 See P3.5.2.18.
AnIN
Slot0.1
0 = Normal 1 = Signal inverted
See P3.5.2.13.
199
Programmable
0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 60
3.6.7.3 Digital outputs, slot B (Basic)
Table 47: Digital output settings on standard I/O board
Index Parameter Min Max Unit Default ID Description
Function selection for Basic R01: 0 = None 1 = Ready 2 = Run 3 = General fault 4 = General fault inverted 5 = General alarm 6 = Reversed 7 = At speed 8 = Motor regulator active 9 = Preset speed active 10 = Keypad control active 11 = I/O B control activated 12 = Limit supervision 1 13 = Limit supervision 2 14 = Start signal active 15 = Reserved 16 = Fire Mode activation 17 = RTC time chnl 1 control
P3.5.3.2.1 Basic R01 function 0 39 2 11001
P3.5.3.2.2 Basic R01 ON delay 0.00 320.00 s 0.00 11002 ON delay for relay
P3.5.3.2.3 Basic R01 OFF delay 0.00 320.00 s 0.00 11003 OFF delay for relay
P3.5.3.2.4 Basic R02 function 0 39 3 11004 See P3.5.3.2.1
P3.5.3.2.5 Basic R02 ON delay 0.00 320.00 s 0.00 11005 See P3.5.3.2.2.
P3.5.3.2.6 Basic R02 OFF delay 0.00 320.00 s 0.00 11006 See P3.5.3.2.3.
P3.5.3.2.7 Basic R03 function 0 39 1 11007
18 = RTC time chnl 2 control 19 = RTC time chnl 3 control 20 = FB ControlWord B13 21 = FB ControlWord B14 22 = FB ControlWord B15 23 = PID1 in Sleep mode 24 = Reserved 25 = PID1 supervision limits 26 = PID2 supervision limits 27 = Motor 1 control 28 = Motor 2 control 29 = Motor 3 control 30 = Motor 4 control 31 = Reserved (Always open) 32 = Reserved (Always open) 33 = Reserved (Always open) 34 = Maintenance alarm 35 = Maintenance fault 36 = Thermistor fault 37 = Motor switch 38 = PreHeat 39 = kWh pulse output
See P3.5.3.2.1. Not visible if only 2 output relays are installed
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 61 Vacon HVAC Application
3.6.7.4 Expander slots D and E digital outputs
Table 48: Slot D/E digital outputs
Index Parameter Min Max Unit Default ID Description
Shows only parameters for
Application dynamic
output list
existing outputs in slot D/E. Selections as in Basic R01 Not visible if no digital output exists in slot D/E.
3.6.7.5 Analogue outputs, Slot A (Standard)
Table 49: Standard I/O board analogue output settings
Index Parameter Min Max Unit Default ID Description
0 = TEST 0% (Not used) 1 = TEST 100% 2 = Output freq (0 -fmax) 3 = Freq reference (0-fmax) 4 = Motor speed (0 - Motor nominal speed)
nMotor
nMotor
) ) )
)
P3.5.4.1.1 AO1 function 0
PID
feed-
back
2 10050
5 = Output current (0-I 6 = Motor torque (0-T 7 = Motor power (0-P 8 = Motor voltage (0-U 9 = DC link voltage (0-1000V)
10 = PID1 output (0-100%) 11 = PID2 output (0-100%) 12 = ProcessDataIn1 13 = ProcessDataIn2 14 = ProcessDataIn3 15 = ProcessDataIn4 16 = ProcessDataIn5 17 = ProcessDataIn6 18 = ProcessDataIn7 19 = ProcessDataIn8
nMotor nMotor
NOTE! For ProcessDataIn,
e.g. value 5000 = 50.00%
Filtering time of analogue
P3.5.4.1.2 AO1 filter time 0.00 300.00 s 1.00 10051
P3.5.4.1.3 AO1 minimum 0 1 0 10052
P3.5.4.1.4 AO1 minimum scale Varies Varies Varies 0.0 10053
P3.5.4.1.5 AO1 maximum scale Varies Varies Varies 0.0 10054
output signal. See P3.5.2.2 0 = No filtering
0 = 0 mA / 0 V 1 = 4 mA / 2 V Note the difference in analogue output scaling in parameter P3.5.4.1.4.
Min scale in process unit (depends on selection of AO1 function)
Max scale in process unit (depends on selection of AO1 function)
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 62
3.6.7.6 Expander slots D to E analogue outputs
Table 50: Slot D/E analogue outputs
Index Parameter Min Max Unit Default ID Description
Shows only parameters for
Application dynamic
output list
existing outputs in slot D/E. Selections as in Basic AO1 Not visible if no analogue output exists in slot D/E.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 63 Vacon HVAC Application

3.6.8 Group 3.6: Fieldbus Data Mapping

Table 51: Fieldbus data mapping
Index Parameter Min Max Unit Default ID Description
Data sent to fieldbus can be chosen with parameter and monitor value ID numbers. The data is scaled to unsigned 16-bit format according to the format on keypad. E.g. 25.5 on keypad equals 255.
Select Process Data Out with parameter ID.
Select Process Data Out with parameter ID.
Select Process Data Out with parameter ID.
Select Process Data Out with parameter ID.
Select Process Data Out with parameter ID.
Select Process Data Out with parameter ID.
Select Process Data Out with parameter ID.
P3.6.1
P3.6.2
P3.6.3
P3.6.4
P3.6.5
P3.6.6
P3.6.7
P3.6.8
Fieldbus data out 1
selection
Fieldbus data out 2
selection
Fieldbus data out 3
selection
Fieldbus data out 4
selection
Fieldbus data out 5
selection
Fieldbus data out 6
selection
Fieldbus data out 7
selection
Fieldbus data out 8
selection
0 35000 1 852
0 35000 2 853
0 35000 45 854
0 35000 4 855
0 35000 5 856
0 35000 6 857
0 35000 7 858
0 35000 37 859
Fieldbus process data out
Values to monitor through fieldbus are:
Table 52. Fieldbus Process Data Out
Data Value Scale
Process Data Out 1 Output frequency 0.01 Hz Process Data Out 2 Motor speed 1 rpm Process Data Out 3 Motor current 0.1 A Process Data Out 4 Motor torque 0.1 % Process Data Out 5 Motor power 0.1 % Process Data Out 6 Motor voltage 0.1 V Process Data Out 7 DC-link voltage 1 V Process Data Out 8 Last active fault code
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 64

3.6.9 Group 3.7: Prohibit Frequencies

In some systems it may be necessary to avoid certain frequencies due to mechanical resonance problems. By setting up prohibit frequencies it is possible to skip these ranges.
Table 53: Prohibit frequencies
Index Parameter Min Max Unit Default ID Description
P3.7.1
P3.7.2
P3.7.3
P3.7.4
P3.7.5
P3.7.6
P3.7.7 Ramp time factor 0,1 10,0 Times 1,0 518
Prohibit frequency
range 1 low limit
Prohibit frequency
range 1 high limit
Prohibit frequency
range 2 low limit
Prohibit frequency
range 2 high limit
Prohibit frequency
range 3 low limit
Prohibit frequency
range 3 high limit
-1,00 320,00 Hz 0,00 509 0 = Not used
0,00 320,00 Hz 0,00 510 0 = Not used
0,00 320,00 Hz 0,00 511 0 = Not used
0,00 320,00 Hz 0,00 512 0 = Not used
0,00 320,00 Hz 0,00 513 0 = Not used
0,00 320,00 Hz 0,00 514 0 = Not used
Multiplier of the currently selected ramp time between prohibit frequency limits.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 65 Vacon HVAC Application

3.6.10 Group 3.8: Limit supervisions

Choose here:
1. One or two (P3.8.1/P3.8.5) signal values for supervision.
2. Whether the low or high limits are supervised (P3.8.2/P3.8.6)
3. The actual limit values (P3.8.3/P3.8.7).
4. The hystereses for the set limit values (P3.8.4/P3.8.8).
Table 54: Limits supervision settings
Index Parameter Min Max Unit Default ID Description
0 = Output frequency 1 = Frequency reference 2 = Motor current
P3.8.1
P3.8.2 Supervision #1 mode 0 2 0 1432
P3.8.3 Supervision #1 limit -200.000 200.000 Varies 25.00 1433
P3.8.4
P3.8.5
P3.8.6 Supervision #2 mode 0 2 0 1436 See P3.8.2
P3.8.7 Supervision #2 limit -200.000 200.000 Varies 40.00 1437 See P3.8.3
P3.8.8
Supervision #1 item
selection
Supervision #1 limit
hysteresis
Supervision #2 item
selection
Supervision #2 limit
hysteresis
07 01431
-200.000 200.000 Varies 5.00 1434
0 7 1 1435 See P3.8.1
-200 000 200.000 Varies 5.00 1438 See P3.8.4
3 = Motor torque 4 = Motor power 5 = DC-link voltage 6 = Analogue input 1 7 = Analogue input 2
0 = Not used 1 = Low limit supervision (output active over limit) 2 = High limit supervision (output active under limit)
Supervision limit for selected
Unit appears
item. automatically.
Supervision limit hysteresis for selected item. Unit is set automatically.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 66
13006.emf
13006.emf
13006.emf

3.6.11 Group 3.9: Protections

Parameters of Motor thermal protection (P3.9.6 to P3.9.10)
The motor thermal protection is to protect the motor from overheating. The drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current I
T
specifies the load current above which the motor is overloaded. This current limit is a function of the output frequency.
The thermal stage of the motor can be monitored on the control keypad display. See Chapter 3.5.
If you use long motor cables (max. 100 m) together with small drives (1.5 kW) the motor current measured by the drive can be much higher than the actual motor current due to capacitive currents in the motor cable. Consider this when setting up the motor thermal protection functions.
The calculated model does not protect the motor if the airflow to the motor is reduced by blocked air intake grill. If the control board is powered off, the model is initialised based on the value which had been calculated before the power off (memory functionality).
Parameters of Stall protection (P3.9.11 to P3.9.14)
The motor stall protection protects the motor from short time overload situations such as one caused by a stalled shaft. The reaction time of the stall protection can be set shorter than that of motor thermal protection. The stall state is defined with two parameters, P3.9.12 (
current
) and P3.9.14 (Stall frequency limit). If the current is higher than the set limit and the
Stall
output frequency is lower than the set limit the stall state is true. There is actually no real indication of the shaft rotation. Stall protection is a type of overcurrent protection.
If you use long motor cables (max. 100 m) together with small drives (≤ 1.5 kW) the motor current measured by the drive can be much higher than the actual motor current due to capacitive currents in the motor cable. Consider this when setting up the motor thermal protection functions.
Parameters of Underload protection (P3.9.15 to P3.9.18)
The purpose of the motor underload protection is to ensure that there is load on the motor when the drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken belt or a dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters P3.9.16 (Underload protection: Field weakening area load) and P3.9.17 (
Zero frequency load
), see below. The underload curve is a squared curve set between the zero
Underload protection:
frequency and the field weakening point. The protection is not active below 5Hz (the underload time counter is stopped).
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 67 Vacon HVAC Application
13006.emf
The torque values for setting the underload curve are set in percentage which refers to the nominal torque of the motor. The motor's name plate data, parameter motor nominal current and the drive's nominal current I
are used to find the scaling ratio for the internal torque
L
value. If other than nominal motor is used with the drive, the accuracy of the torque calculation decreases.
If you use long motor cables (max. 100 m) together with small drives (1.5 kW) the motor current measured by the drive can be much higher than the actual motor current due to capacitive currents in the motor cable. Consider this when setting up the motor thermal protection functions.
Table 55: Protections settings
Index Parameter Min Max Unit Default ID Description
0 = No action 1 = Alarm
P3.9.1
P3.9.2
P3.9.3
P3.9.4 Undervoltage fault 0 1 0 727
P3.9.5
P3.9.6
P3.9.7
P3.9.8
P3.9.9
P3.9.10
P3.9.11 Motor stall fault 0 3 0 709 See P3.9.2
Response to Analogue
input low fault
Response to external
fault
Response to Input
phase fault
Response to output
phase fault
Motor thermal
protection
Motor ambient
temperature factor
Motor thermal zero
speed cooling
Motor thermal time
constant
Motor thermal
loadability
04 0700
03 2701
01 0730
0 3 2 702 See P3.9.2
0 3 2 704 See P3.9.2
-20.0 100.0 °C 40.0 705 Ambient temperature in °C
5.0 150.0 % 60.0 706
1 200 min Varies 707
0 150 % 100 708
2 = Alarm, set preset fault frequency (par. P3.3.19) 3 = Fault (Stop according to stop mode) 4 = Fault (Stop by coasting)
0 = No action 1 = Alarm 2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Select the supply phase configuration. The input phase supervision ensures that the input phases of the frequency converter have an approximately equal current. 0 = 3 Phase Support 1 = 1 Phase Support
0 = Fault stored in history 1 = Fault not stored in history
Defines the cooling factor at zero speed in relation to the point where the motor is running at nominal speed without external cooling.
The time constant is the time within which the calculated thermal stage has reached 63% of its final value.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 68
Table 55: Protections settings
P3.9.12 Stall current 0.00
P3.9.13 Stall time limit 1.00 120.00 s 15.00 711
P3.9.14 Stall frequency limit 1.00 P3.3.2 Hz 25.00 712
P3.9.15
P3.9.16
P3.9.17
P3.9.18
P3.9.19
P3.9.20
P3.9.21 Thermistor fault 0 3 0 732 See P3.9.2
P3.9.22
P3.9.23
P3.9.25 TempFault Signal 0 3
P3.9.26 TempAlarm Limit -30.0 200.0 130.0 741
P3.9.27 TempFault Limit -30.0 200.0 155.0 742
P3.9.28 TempFault Response 0 3 Fault 740
Underload fault
(broken belt/dry pump)
Underload protection: Field weakening area
load
Underload protection:
Zero frequency load
Underload protection:
Time limit
Response to Fieldbus
communication fault
Slot communication
fault
Response to PID1
supervision fault
Response to PID2
supervision fault
0 3 0 713 See P3.9.2
10.0 150.0 % 50.0 714
5.0 150.0 % 10.0 715
2.00 600.00 s 20.00 716
0 4 3 733 See P3.9.1
0 3 2 734 See P3.9.2
0 3 2 749 See P3.9.2
0 3 2 757 See P3.9.2
2*I
H
A
I
H
Not
Used
For a stall stage to occur, the
710
current must have exceeded this limit.
This is the maximum time allowed for a stall stage.
For a stall state to occur, the output frequency must have remained below this limit for a certain time.
This parameter gives the value for the minimum torque allowed when the output frequency is above the field weakening point.
This parameter gives value for the minimum torque allowed with zero frequency. If you change the value of parameter P3.1.1.4 this parameter is automatically restored to the default value.
This is the maximum time allowed for an underload state to exist.
Selection for which signals to
739
use for alarm and fault triggering.
Temperature for trigging an alarm.
Temperature for trigging a fault.
Fault response for Temperature Fault. 0 = No response 1 = Alarm 2 = Fault (Stop according to stop mode) 3 = Fault (Stop by coasting)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 69 Vacon HVAC Application

3.6.12 Group 3.10: Automatic reset

Table 56: Autoreset settings
Index Parameter Min Max Unit Default ID Description
P3.10.1 Automatic reset 0 1 0 731
P3.10.2 Restart function 0 1 1 719
P3.10.3 Wait time 0,10 10000,0 s 0,50 717
P3.10.4 Trial time 0,00 10000,0 s 60,00 718
P3.10.5 Number of trials 1 10 4 759
P3.10.6
P3.10.7
P3.10.8
P3.10.9 Autoreset: AI low 0 1 1 723
P3.10.10
P3.10.11
P3.10.12
P3.10.13
P3.10.14 PID Supervision No Yes No 15538
Autoreset:
Undervoltage
Autoreset:
Overvoltage
Autoreset:
Overcurrent
Autoreset: Unit
overtemperature
Autoreset: Motor overtemperature
Autoreset:
External fault
Autoreset:
Underload fault
0 1 1 720
0 1 1 721
0 1 1 722
0 1 1 724
0 1 1 725
0 1 0 726
0 1 0 738
0 = Disabled 1 = Enabled
The start mode for Automatic reset is selected with this parameter: 0 = Flying start 1 = According to par. P3.2.4
Wait time before the first reset is executed.
When the trial time has elapsed, and the fault is still active, the drive will trip to fault.
NOTE! Total number of trials (irrespective of fault type)
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Autoreset permitted? 0 = No 1 = Yes
Include fault in the automatic reset function.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 70
P
9146.emf
AssignToChannel
Interval 1
Interval 2
Interval 3
Interval 4
Timer 1
Timer 2
Timer 3
Interval 5
TimeChannel 1
TimeChannel 2
TimeChannel 3

3.6.13 Group 3.11: Timer functions

The time functions (Time Channels) in the Vacon 100 give you the possibility to program functions to be controlled by the internal RTC (Real Time Clock). Practically every function that can be controlled by a digital input can also be controlled by a Time Channel. Instead of having an external PLC controlling a digital input you can program the "closed" and "opened" intervals of the input internally.
NOTE! The functions of this parameter group can be made the fullest advantage of only if the battery (option) has been installed and the Real Time Clock settings have been properly made during the Startup Wizard (see page 2 and page 3). It is not recommended to use these function without battery backup because the drive’s time and date settings will be reset at every power down if no battery for the RTC is installed.
Time channels
The on/off logic for the them. One
Time channel can be controlled by many Intervals or Timers by assigning as many
of these as needed to the
Time channels is configured by assigning Intervals or/and Timers to
Time channel.
Figure 15. The intervals and timers can be assigned to time channels in a flexible way.
Every interval and timer has its own parameter for assigning to a time channel.
Intervals
Every interval is given an "ON Time" and "OFF Time" with parameters. This is the daily time that the interval will be active during the days set with "From Day" and “To Day” parameters. E.g. the parameter setting below means that the interval is active from 7 am to 9 am every weekday (Monday to Friday). The Time Channel to which this Interval is assigned will be seen as a closed "virtual digital input" during that period.
ON Time: 07:00:00 OFF Time: 09:00:00 From Day: Monday To Day: Friday
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 71 Vacon HVAC Application
9137.emf
Duration
Remaining time
Activation
Time
OUT
9137.emf
Timers
Timers can be used to set a Time Channel active during a certain time by command from a digital input (or a Time Channel).
Figure 16. Activation signal comes from a digital input or " a virtual digital input" such as a
Time channel. The Timer counts down from falling edge.
The below parameters will set the Timer active when Digital Input 1 on Slot A is closed and keep it active for 30 s after it is opened.
Duration: 30 s Timer: DigIn SlotA.1
Tip: A duration of 0 seconds can be used for simply overriding a Time channel activated from
a digital input without any off delay after the falling edge.
EXAMPLE
Problem:
We have a frequency converter for air conditioning in a warehouse. It needs to run between 7 am - 5 pm on weekdays and 9 am - 1 pm on weekends. Additionally, we need to be able to manually force the drive to run outside working hours if there are people in the building and to leave it running for 30 min afterwards.
Solution:
We need to set up two intervals, one for weekdays and one for weekends. A Timer is also needed for activation outside the office hours. An example of configuration below.
3
Interval 1:
P3.11.1.1: P3.11.1.2: P3.11.1.3: P3.11.1.4: P3.11.1.5:
Interval 2:
P3.11.2.1: P3.11.2.2:
ON Time: 07:00:00 OFF Time: 17:00:00 From Day: ‘1’ (= Monday) To Day: ‘5’ (= Friday) Assign to channel: Time channel 1
ON Time: 09:00:00 OFF Time: 13:00:00
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 72
P
11092.emf
Interval 2
To = S und a yFrom = S aturday
Digital input 1 on Slot A
Interval 1
Timer 1
Duration = 1800 s
To = Fr ida yFrom = M onday
Ctrl Signal 1A
Time channel 1
Start/Stop
ON = 07:00:00 hs OFF = 17:00:00 hs
ON = 09:00:00 hs OFF = 13:00:00 hs
P3.11.2.3: From Day: Saturday P3.11.2.4: P3.11.2.5:
To Day: Sunday AssignToChannel: Time channel 1
Timer 1
The manual bypassing can be handled by a digital input 1 on slot A (by a different switch or connection to lighting).
P3.11.6.1: P3.11.6.2:
P3.5.1.18:
Duration: 1800 s (30 min) Assign to channel: Time channel 1
Timer 1: DigIn SlotA.1 (Parameter located in digital inputs menu.)
Figure 17. Final configuration where Time channel 1 is used as control signal for
start command instead of a digital input.
Table 57: Timer functions
Index Parameter Min Max Unit Default ID Description
3.11.1 INTERVAL 1
P3.11.1.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1464 ON time
P3.11.1.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1465 OFF time
ON day of week 0 = Sunday 1 = Monday
P3.11.1.3 From day 0 6 0 1466
P3.11.1.4 To day 0 6 0 1467 See above
P3.11.1.5 Assign to channel 0 3 0 1468
2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday
Select affected time channel (1-3) 0 = Not used 1 = Time channel 1 2 = Time channel 2 3 = Time channel 3
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 73 Vacon HVAC Application
Table 57: Timer functions
3.11.2 INTERVAL 2
P3.11.2.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1469 See Interval 1
P3.11.2.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1470 See Interval 1
P3.11.2.3 From day 0 6 0 1471 See Interval 1
P3.11.2.4 To day 0 6 0 1472 See Interval 1
P3.11.2.5 Assign to channel 0 3 0 1473 See Interval 1
3.11.3 INTERVAL 3
P3.11.3.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1474 See Interval 1
P3.11.3.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1475 See Interval 1
P3.11.3.3 From day 0 6 0 1476 See Interval 1
P3.11.3.4 To day 0 6 0 1477 See Interval 1
P3.11.3.5 Assign to channel 0 3 0 1478 See Interval 1
3.11.4 INTERVAL 4
P3.11.4.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1479 See Interval 1
P3.11.4.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1480 See Interval 1
P3.11.4.3 From day 0 6 0 1481 See Interval 1
P3.11.4.4 To day 0 6 0 1482 See Interval 1
P3.11.4.5 Assign to channel 0 3 0 1483 See Interval 1
3.11.5 INTERVAL 5
P3.11.5.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1484 See Interval 1
P3.11.5.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1485 See Interval 1
P3.11.5.3 From day 0 6 0 1486 See Interval 1
P3.11.5.4 To day 0 6 0 1487 See Interval 1
P3.11.5.5 Assign to channel 0 3 0 1488 See Interval 1
3.11.6 TIMER 1
P3.11.6.1 Duration 0 72000 s 0 1489
P3.11.6.2 Assign to channel 0 3 0 1490
P3.11.6.3 Mode TOFF TON TOFF 15527
The time the timer will run when activated. (Activated by DI)
Select affected time channel (1-3) 0 = Not used 1 = Time channel 1 2 = Time channel 2 3 = Time channel 3
Select if the timer works with on delay or off delay.
3.11.7 TIMER 2
P3.11.7.1 Duration 0 72000 s 0 1491 See Timer 1
P3.11.7.2 Assign to channel 0 3 0 1492 See Timer 1
P3.11.7.3 Mode TOFF TON TOFF 15528
Select if the timer works with on delay or off delay.
3
3.11.8 TIMER 3
P3.11.8.1 Duration 0 72000 s 0 1493 See Timer 1
P3.11.8.2 Assign to channel 0 3 1494 See Timer 1
P3.11.8.3 Mode TOFF TON TOFF 15523
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Select if the timer works with on delay or off delay.
Vacon HVAC Application vacon • 74

3.6.14 Group 3.12: PID-controller 1

3.6.14.1 Basic settings
Table 58:
Index Parameter Min Max Unit Default ID Description
If the value of the parameter is set to 100% a change of 10% in
P3.12.1.1 PID gain 0.00 1000.00 % 100.00 118
P3.12.1.2 PID integration time 0.00 600.00 s 1.00 119
P3.12.1.3 PID derivation time 0.00 100.00 s 0.00 132
P3.12.1.4
P3.12.1.5 Process unit min Varies Varies Varies 0 1033
P3.12.1.6 Process unit max Varies Varies Varies 100 1034
P3.12.1.7
P3.12.1.8 Error inversion 0 1 0 340
P3.12.1.9 Dead band hysteresis Varies Varies Varies 0 1056
P3.12.1.10 Dead band delay 0.00 320.00 s 0.00 1057
Process unit
selection
Process unit
decimals
1 38 1 1036 Select unit for actual value.
04 21035
the error value causes the controller output to change by 10%.
If this parameter is set to 1,00 second a change of 10% in the error value causes the controller output to change by
10.00%/s.
If this parameter is set to 1,00 second a change of 10% in the error value during 1.00 s causes the controller output to change by 10.00%.
Number of decimals for process unit value
0 = Normal (Feedback < Setpoint -> Increase PID output) 1 = Inverted (Feedback < Setpoint ->
Dead band area around the setpoint in process units.The PID output is locked if the feedback stays within the deadband area for a predefined time.
If the feedback stays within the dead band area for a predefined time, the output is locked.
Decrease PID output
)
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 75 Vacon HVAC Application
3.6.14.2 Setpoints
Table 59:
Index Parameter Min Max Unit Default ID Description
P3.12.2.1 Keypad setpoint 1 Varies Varies Varies 0 167
P3.12.2.2 Keypad setpoint 2 Varies Varies Varies 0 168
Defines the rising and falling
P3.12.2.3 Setpoint ramp time 0.00 300.0 s 0.00 1068
P3.12.2.4
P3.12.2.5
P3.12.2.6
P3.12.2.7
P3.12.2.8 Sleep delay 1 0 3000 s 0 1017
P3.12.2.9 Wake-up level 1 0,01 100 x 0 1018
Setpoint source 1
selection
Setpoint 1 mini-
mum
Setpoint 1 maxi-
mum
Sleep frequency
limit 1
016 1332
-200.00 200.00 % 0.00 1069
-200.00 200.00 % 100.00 1070
0.00 320.00 Hz 0.00 1016
ramp times for setpoint changes. (Time to change from minimum to maximum)
0 = Not used 1 = Keypad setpoint 1 2 = Keypad setpoint 2 3 = AI1 4 = AI2 5 = AI3 6 = AI4 7 = AI5 8 = AI6 9 = ProcessDataIn1 10 = ProcessDataIn2 11 = ProcessDataIn3 12 = ProcessDataIn4 13 = ProcessDataIn5 14 = ProcessDataIn6 15 = ProcessDataIn7 16 = ProcessDataIn8 AI’s and ProcessDataIn are handled as percent (0.00-
100.00%) and scaled according to Setpoint minimum and maximum. NOTE! ProcessDataIn use two decimals.
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
Drive goes to sleep mode when the output frequency stays below this limit for a time greater than that defined by parameter Sleep delay.
The minimum amount of time the frequency has to remain below the Sleep level before the drive is stopped.
If it is in sleep mode, the PID controller will start the drive and regulate when going below this level. Absolute level or relative to setpoint based on WakeUpMode parameter.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 76
Table 59:
Select if wake up level should
P3.12.2.10
P3.12.2.11 Setpoint 1 boost -2.0 2.0 x 1.0 1071
P3.12.2.12
P3.12.2.13
P3.12.2.14
P3.12.2.15
P3.12.2.16 Sleep delay 2 0 3000 s 0 1076 See P3.12.2.8.
P3.12.2.17 Wake-up level 2 Varies 0.0000 1077 See P3.12.2.9.
P3.12.2.18
P3.12.2.19 Setpoint 2 boost -2.0 2.0 Varies 1.0 1078 See P3.12.2.11.
Setpoint 1 wake-up
mode
Setpoint source 2
selection
Setpoint 2 mini-
mum
Setpoint 2 maxi-
mum
Sleep frequency
limit 2
Setpoint 2 wake-up
mode
0 1 0 15539
0 16 2 431 See par. P3.12.2.4
-200.00 200.00 % 0.00 1073
-200.00 200.00 % 100.00 1074
0.00 320.00 Hz 0.00 1075 See P3.12.2.7.
0 1 0 15540
work as absolute level or as relative setpoint. 0 = Absolute level 1 = Relative setpoint
The setpoint can be boosted with a digital input.
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
Select if the wake-up level works as the absolute level or as the relative setpoint. 0 = Absolute level 1 = Relative setpoint
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 77 Vacon HVAC Application
3.6.14.3 Feedbacks
Table 60:
Index Parameter Min Max Unit Default ID Description
1 = Only Source1 in use 2 = SQRT(Source1);(Flow=Constan t x SQRT(Pressure)) 3 = SQRT(Source1- Source 2)
P3.12.3.1 Feedback function 1 9 1 333
P3.12.3.2
P3.12.3.3
P3.12.3.4
P3.12.3.5
P3.12.3.6
P3.12.3.7
P3.12.3.8
Feedback function
gain
Feedback 1 source
selection
Feedback 1
minimum
Feedback 1
maximum
Feedback 2
source selection
Feedback 2
minimum
Feedback 2
maximum
-1000.0 1000.0 % 100.0 1058
0 14 2 334
-200.00 200.00 % 0.00 336
-200.00 200.00 % 100.00 337
0 14 0 335 See P3.12.3.3
-200.00 200.00 % 0.00 338
-200.00 200.00 % 100.00 339
4 = SQRT(Source 1) + SQRT (Source 2) 5 = Source 1 + Source 2 6 = Source 1 - Source 2 7 = MIN (Source 1, Source 2) 8 = MAX (Source 1, Source 2) 9 = MEAN (Source 1, Source 2)
Used e.g. with selection 2 in
Feedback function
0 = Not used 1 = AI1 2 = AI2 3 = AI3 4 = AI4 5 = AI5 6 = AI6 7 = ProcessDataIn1 8 = ProcessDataIn2 9 = ProcessDataIn3 10 = ProcessDataIn4 11 = ProcessDataIn5 12 = ProcessDataIn6 13 = ProcessDataIn7 14 = ProcessDataIn8 AI’s and ProcessDataIn are handled as % (0.00-100.00%) and scaled according to Feedback min and max. NOTE! ProcessDataIn use two decimals.
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 78
3.6.14.4 Feedforward
Feedforward usually needs accurate process models, but in some simple cases a gain + offset type of feedforward is enough. The feedforward part does not use any feedback measurements of the actual controlled process value (water level in the example on page 103). Vacon feedforward control uses other measurements which are indirectly affecting the controlled process value.
Table 61:
Index Parameter Min Max Unit Default ID Description
P3.12.4.1 Feedforward function 1 9 1 1059 See Table 60, P3.12.3.1.
P3.12.4.2
P3.12.4.3
P3.12.4.4
P3.12.4.5
P3.12.4.6
P3.12.4.7 Feedforward 2 min -200.00 200.00 % 0.00 1065 See Table 60, P3.12.3.7.
P3.12.4.8 Feedforward 2 max -200.00 200.00 % 100.00 1066 See Table 60, P3.12.3.8.
Feedforward function
gain
Feedforward 1
source selection
Feedforward 1
minimum
Feedforward 1
maximum
Feedforward 2
source selection
-1000 1000 % 100.0 1060 See Table 60, P3.12.3.2.
0 14 0 1061 See Table 60, P3.12.3.3.
-200.00 200.00 % 0.00 1062 See Table 60, P3.12.3.4.
-200.00 200.00 % 100.00 1063 See Table 60, P3.12.3.5.
0 14 0 1064 See Table 60, P3.12.3.6.
3.6.14.5 Process supervision
Process supervision is used to control that the actual value stays within predefined limits. With this function you can e.g. detect a major pipe burst and stop unnecessary flooding. See more on page 103.
Table 62:
Index Parameter Min Max Unit Default ID Description
P3.12.5.1
P3.12.5.2 Upper limit Varies Varies Varies Varies 736
P3.12.5.3 Lower limit Varies Varies Varies Varies 758
P3.12.5.4 Delay 0 30000 s 0 737
Enable process
supervision
0 1 0 735
0 = Disabled 1 = Enabled
Upper actual/process value supervision.
Lower actual/process value supervision.
If the desired value is not reached within this time a fault or alarm is created.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 79 Vacon HVAC Application
3.6.14.6 Pressure loss compensation
Table 63:
Index Parameter Min Max Unit Default ID Description
Enables pressure loss
P3.12.6.1 Enable setpoint 1 0 1 0 1189
P3.12.6.2
P3.12.6.3 Enable setpoint 2 0 1 0 1191 See P3.12.6.1 above.
P3.12.6.4
Setpoint 1 max
compensation
Setpoint 2 max
compensation
Varies Varies Varies Varies 1190
Varies Varies Varies Varies 1192 See P3.12.6.2 above.
compensation for setpoint 1. 0 = Disabled 1 = Enabled
Value added proportionally to the frequency. Setpoint compensation = Max compensation * (FreqOut-MinFreq)/ (MaxFreq-MinFreq)
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 80

3.6.15 Group 3.13: PID-controller 2

3.6.15.1 Basic settings
For more detailed information, see Chapter 3.6.14.
Table 64:
Index Parameter Min Max Unit Default ID Description
P3.13.1.1 Enable PID 0 1 0 1630
P3.13.1.2 Output in Stop 0.0 100.0 % 0.0 1100
P3.13.1.3 PID gain 0.00 1000.00 % 100.00 1631
P3.13.1.4 PID integration time 0.00 600.00 s 1.00 1632
P3.13.1.5 PID derivation time 0.00 100.00 s 0.00 1633
P3.13.1.6 Process unit selection 1 38 1 1635
P3.13.1.7 Process unit min Varies Varies Varies 0 1664
P3.13.1.8 Process unit max Varies Varies Varies 100 1665
P3.13.1.9 Process unit decimals 0 4 2 1666
P3.13.1.10 Error inversion 0 1 0 1636
P3.13.1.11 Dead band hysteresis Varies Varies Varies 0.0 1637
P3.13.1.12 Dead band delay 0.00 320.00 s 0.00 1638
3.6.15.2 Setpoints
Table 65:
0 = Disabled 1 = Enabled
The output value of the PID controller in % of its maximum output value while it is stopped from digital input.
Index Parameter Min Max Unit Default ID Description
P3.13.2.1 Keypad setpoint 1 0.00 100.00 Varies 0.00 1640
P3.13.2.2 Keypad setpoint 2 0.00 100.00 Varies 0.00 1641
P3.13.2.3 Setpoint ramp time 0.00 300.00 s 0.00 1642
P3.13.2.4
P3.13.2.5 Setpoint 1 minimum -200.00 200.00 % 0.00 1644
P3.13.2.6 Setpoint 1 maximum -200.00 200.00 % 100.00 1645
P3.13.2.7
P3.13.2.8 Setpoint 2 minimum -200.00 200.00 % 0.00 1647
P3.13.2.9 Setpoint 2 maximum -200.00 200.00 % 100.00 1648
Setpoint source 1
selection
Setpoint source 2
selection
0 16 1 1643
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
0 16 0 1646 See P3.13.2.4.
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 81 Vacon HVAC Application
3.6.15.3 Feedbacks
For more detailed information, see Chapter 3.6.14.
Table 66:
Index Parameter Min Max Unit Default ID Description
P3.13.3.1 Feedback function 1 9 1 1650
P3.13.3.2 Feedback function gain -1000.0 1000.0 % 100.0 1651
P3.13.3.3
P3.13.3.4 Feedback 1 minimum -200.00 200.00 % 0.00 1653
P3.13.3.5 Feedback 1 maximum -200.00 200.00 % 100.00 1654
P3.13.3.6
P3.13.3.7 Feedback 2 minimum -200.00 200.00 % 0.00 1656
P3.13.3.8 Feedback 2 maximum -200.00 200.00 % 100.00 1657
Feedback 1
source selection
Feedback 2
source selection
0 14 1 1652
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
0 14 2 1655
Minimum value at analogue signal minimum.
Maximum value at analogue signal maximum.
3.6.15.4 Process supervision
For more detailed information, see Chapter 3.6.14.
Table 67:
Index Parameter Min Max Unit Default ID Description
P3.13.4.1 Enable supervision 0 1 0 1659
P3.13.4.2 Upper limit Varies Varies Varies Varies 1660
P3.13.4.3 Lower limit Varies Varies Varies Varies 1661
P3.13.4.4 Delay 0 30000 s 0 1662
0 = Disabled 1 = Enabled
If the desired value is not reached within this time a fault or alarm is activated.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 82

3.6.16 Group 3.14: Multi-pump

The
Multi-pump functionality allows you to control up to 4 motors (pumps, fans) with PID
controller 1. The AC drive is connected to one motor which is the "regulating" motor connecting and disconnecting the other motors to/from the mains, by means of contactors controlled with relays when needed in order to maintain the right setpoint. The
Autochange
function controls the order/priority in which the motors are started in order to guarantee their equal wear. The controlling motor can be included in the autochange and interlocks logic, or, it may be selected to always functions as Motor 1. Motors can be taken out of use momentarily, e.g. for service, using the motor
Index Parameter Min Max Unit Default ID Description
P3.14.1 Number of motors 1 5 1 1001
P3.14.2 Interlock function 0 1 1 1032
P3.14.3 Include FC 0 1 1 1028
P3.14.4 Autochange 0 1 0 1027
P3.14.5 Autochange interval 0.0 3000.0 h 48.0 1029
P3.14.6
P3.14.7
P3.14.8 Bandwidth 0 100 % 10 1097
P3.14.9 Bandwidth delay 0 3600 s 10 1098
Autochange:
Frequency limit
Autochange: Motor
limit
Interlock function. See page 106.
Table 68: Multi-pump parameters
0.00 50.00 Hz 25.00 1031
0 4 1 1030
Total number of motors (pumps/fans) used in multipump system.
Enable/Disable use of interlocks. Interlocks are used to tell the system if a motor is connected or not. 0 = Disabled 1 = Enabled
Include the frequency converter in the autochange and interlocking system. 0 = Disabled 1 = Enabled
Disable/enable rotation of starting order and priority of motors. 0 = Disabled 1 = Enabled
After the expiry of the time defined with this parameter, the autochange function takes place if the capacity used lies below the level defined with parameters P3.14.6 and P3.14.7.
These parameters define the level below which the capacity used must remain so that the autochange can take place.
Percentage of the setpoint. E.g.: Setpoint = 5 bar, Bandwidth = 10%: As long as the feedback value stays within 4.5...5.5 bar motor disconnection or removal will not take place.
With feedback outside the bandwidth, this time must pass before pumps are added or removed.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 83 Vacon HVAC Application

3.6.17 Group 3.16: Fire mode

Drive ignores all commands from keypad, fieldbuses and PC tool and runs at preset frequency when activated. If activated, alarm sign is shown on the keypad and warranty is void. In order to enable the function, you need to set a password in the description field for parameter
Mode password
. Please note the NC (normally closed) type of this input!
Fire
NOTE! THE WARRANTY IS VOID IF THIS FUNCTION IS ACTIVATED! There is also a different password for test mode to be used for testing the Fire Mode without the warranty becoming void.
Table 69: Fire mode parameters
Index Parameter Min Max Unit Default ID Description
P3.16.1 Fire Mode password 0 9999 0 1599
P3.16.2
P3.16.3
P3.16.4 Fire Mode frequency 8.00 P3.3.2 Hz 0.00 1598
P3.16.5
P3.16.6 Fire Mode reverse DigIN Slot0.1 1618
P3.16.7
P3.16.8
P3.16.9
M
3.16.10
Fire Mode Activ.
Open
Fire Mode Activ.
Close
Fire Mode frequency
source
Fire Mode preset
frequency 1
Fire Mode preset
frequency 2
Fire Mode preset
frequency 3
Fire Mode status 0 3 0 1597
0 8 0 1617
0 50 10 15535
0 50 20 15536 See above.
0 50 30 15537 See above.
DigIN Slot0.2 1596
DigIN Slot0.1 1619
1001 = Enabled 1234 = Test mode
FALSE = Fire Mode active TRUE = Inactive
FALSE = Inactive TRUE = Fire Mode Active
Frequency used when Fire Mode is activated.
Selection of reference source when Fire Mode is active. This enables selection of e.g. AI1 or PID controller as reference source also while operating in Fire Mode. 0 = Fire Mode frequency 1 = Preset speeds 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = AI1 + AI2 7 = PID1 8 = Motor potentiometer
Reverse command of rotation direction while running in Fire Mode. This function has no effect in normal operation. FALSE = Forward TRUE = Reverse
Preset frequency for Fire Mode
Monitoring value (see also Tab le 3 1) 0 = Disabled 1 = Enabled 2 = Activated (Enabled + DI Open) 3 = Test Mode
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 84
Table 69: Fire mode parameters
Fire Mode counter tells how many times Fire Mode has been activated. The counter cannot be reset.
M
3.16.11
Fire Mode counter 0
4 294
967 295
0 1679

3.6.18 Group 3.17: Application settings

Table 70: Application settings
Index Parameter Min Max Unit Default ID Description
P3.17.1 Password 0 9999 0 1806

3.6.19 Group 3.18: kWh pulse output settings

Table 71: kWh pulse output settings
Index Parameter Min Max Unit Default ID Description
P3.18.1 kWh pulse length 50 200 ms 50 15534
P3.18.2 kWh pulse resolution 1 100 kWh 1 15533
Length of kWh pulse in milliseconds
Indicates how often the kWh pulse must be triggered.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 85 Vacon HVAC Application
U[V]
f[Hz]
11117.emf
Default: Nominal voltage of the motor
Linear
Squared
Field weakening point
Default: Nominal frequency of the motor

3.7 HVAC Application - Additional parameter information

Due to its user-friendliness and simplicity of use, the most parameters of the Vacon HVAC Application only require a basic description which is given in the parameter tables in Chapter 3.6.
In this ch apter, yo u will fi nd addit ional inf ormation on certain most advanced parameters of the Vacon HVAC Application. Should you not find the information you need contact your distributor.
P3.1.1.7 MOTOR CURRENT LIMIT
This parameter determines the maximum motor current from the AC drive. The parameter value range differs from size to size.
When the current limit is active the drive output frequency is decreased.
NOTE! This is not an overcurrent trip limit.
P3.1.2.9 U/F RATIO SELECTION
Selection
number
Selection name Description
0Linear
1Squared
The voltage of the motor changes linearly as a function of output frequency from zero frequency voltage (P3.1.2.4) to the field weakening point (FWP) voltage at FWP frequency. This default setting should be used if there is no special need for another setting.
The voltage of the motor changes from zero point voltage (P3.1.2.4) following a squared curve form from zero to the field weakening point. The motor runs undermagnetised below the field weakening point and produces less torque. Squared U/f ratio can be used in applications where torque demand is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
3
Figure 18. Linear and squared change of motor voltage
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 86
P3.1.2.15 OVERVOLTAGE CONTROLLER P3.1.2.16 UNDERVOLTAGE CONTROLLER
These parameters allow the under-/overvoltage controllers to be switched out of operation. This may be useful, for example, if the mains supply voltage varies more than -15% to +10% and the application will not tolerate this over-/undervoltage. In this case, the regulator controls the output frequency taking the supply fluctuations into account.
P3.1.2.17 STATOR VOLTAGE ADJUST
Stator voltage adjust parameter is used only when Permanent magnet motor (PM motor) has been selected for parameter P3.1.1.8. This parameter has no affect if Induction motor has been selected. With an induction motor in use, the value has been internally forced to 100% and it cannot be changed.
When the value of parameter P3.1.1.8 (Motor type) parameter is changed to PM Motor, the U/f curve will be automatically extended up to the limits of the drive's full output voltage, retaining the defined U/f-ratio. This internal extension is done to avoid running the PM motor in the field weakening area because the PM motor nominal voltage is typically much lower than the full output voltage capability of the drive.
PM motor nominal voltage typically represents the motor’s back-EMF voltage at nominal frequency, but depending on the motor manufacturer, it may represent e.g. the stator voltage at nominal load.
This parameter gives an easy way to adjust the drive’s U/f curve near to the motor’s back­EMF-curve without needing to change several U/f curve parameters.
The Stator voltage adjust parameter defines the drive’s output voltage in percent of the motor’snominal voltage at the motor’s nominal frequency.
The U/f curve of the drive is typically tuned slightly above the back-EMF curve of the motor. Themotor current increases the more the drive’s U/f-curve differs from the motor’s back-EMF
-curve.
P3.2.5 STOP FUNCTION
Selection
number
0Coasting
1Ramp
P3.2.6 I/O START/STOP LOGIC
Values 0...4 offer possibilities to control the starting and stopping of the AC drive with digital signal connected to digital inputs. CS = Control signal.
Selection name Description
The motor is allowed to stop on its own inertia. The control by the drive is discontinued and the drive current drops to zero as soon as the stop command is given.
After the Stop command, the speed of the motor is decelerated according to the set deceleration parameters to zero speed.
The selections including the text 'edge' shall be used to exclude the possibility of an unintentional start when, for example, power is connected, re-connected after a power failure, after a fault reset, after the drive is stopped by Run Enable (Run Enable = False) or when the control place is changed to I/O control. The Start/Stop contact must be opened before the
motor can be started.
The used stop mode is
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Coasting in all examples.
3
vacon • 87 Vacon HVAC Application
t
Output frequency
FWD
REV
Ctrl signal 2
Ctrl signal 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
Keypad start
button
1 2 3 4 5 6 7 8 9 10 11 12 13
9135.emf
Selection
number
0
Selection name Note
CS1: Forward
CS2: Backward
The functions take place when the contacts are closed.
Explanations:
1
2
3
4
5
6
7
Figure 19. I/O A Start/Stop logic = 0
Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward.
CS2 activates which, however, has no effect on the output frequency because the first selected direction has the highest priority.
CS1 is inactivated which causes the direction to start changing (FWD to REV) because CS2 is still active.
CS2 inactivates and the frequency fed to the motor drops to 0.
CS2 activates again causing the motor to accelerate (REV) towards the set frequency.
CS2 inactivates and the frequency fed to the motor drops to 0.
CS1 activates and the motor accelerates (FWD) towards the set frequency.
Run enable signal is set to FALSE, which drops
8
the frequency to 0. The run enable signal is configured with parameter P3.5.1.10.
Run enable signal is set to TRUE, which causes
9
the frequency to rise towards the set frequency because CS1 is still active.
Keypad stop button is pressed and the frequency
10
fed to the motor drops to 0. (This signal only works if P3.2.3 Keypad stop button = Yes)
The drive starts through pushing the Start
11
button on the keypad.
The keypad stop button is pushed again to stop
12
the drive.
The attempt to start the drive through pushing
13
the Start button is not successful because CS1 is inactive.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 88
t
9176.emf
Output frequency
FWD
REV
Ctrl signal 2
Ctrl signal 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
71 2 3 4 5 6 98
Selection
number
1
Selection name Note
CS1: Forward (edge)
CS2: Inverted stop
Explanations:
1
2
3
4
5
Figure 20. I/O A Start/Stop logic = 1
Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward.
CS2 inactivates causing the frequency to drop to
0.
CS1 activates causing the output frequency to rise again. The motor runs forward.
Run enable signal is set to FALSE, which drops the frequency to 0. The run enable signal is configured with parameter P3.5.1.10.
Start attempt with CS1 is not successful because Run enable signal is still FALSE.
CS1 activates and the motor accelerates (FWD)
6
towards the set frequency because the Run enable signal has been set to TRUE.
Keypad stop button is pressed and the frequency
7
fed to the motor drops to 0. (This signal only works if P3.2.3 Keypad stop button = Yes)
CS1 activates causing the output frequency to
8
rise again. The motor runs forward.
CS2 inactivates causing the frequency to drop to
9
0.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 89 Vacon HVAC Application
t
Output frequency
FWD
REV
Ctrl signal 2
Ctrl signal 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
1 2 3 4 5 6 7 8 9
11093.emf
11 1210
Selection
number
2
Selection name Note
CS1: Forward (edge)
CS2: Backward (edge)
Shall be used to exclude the possibility of an unintentional start. The Start/Stop contact must be opened before the motor can be restarted.
Explanations:
1
2
3
4
5
6
Figure 21. I/O A Start/Stop logic = 2
Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward.
CS2 activates which, however, has no effect on the output frequency because the first selected direction has the highest priority.
CS1 is inactivated which causes the direction to start changing (FWD to REV) because CS2 is still active.
CS2 inactivates and the frequency fed to the motor drops to 0.
CS2 activates again causing the motor to accelerate (REV) towards the set frequency.
CS2 inactivates and the frequency fed to the motor drops to 0.
CS1 activates and the motor accelerates (FWD)
7
towards the set frequency.
Run enable signal is set to FALSE, which drops
8
the frequency to 0. The run enable signal is configured with parameter P3.5.1.10.
Run enable signal is set to TRUE, which, unlike if value 0 is selected for this parameter, has no
9
effect because rising edge is required to start even if CS1 is active.
Keypad stop button is pressed and the frequency
10
fed to the motor drops to 0. (This signal only works if P3.2.3 Keypad stop button = Yes)
CS1 is opened and closed again which causes
11
the motor to start.
CS1 inactivates and the frequency fed to the
12
motor drops to 0.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 90
t
Output frequency
FWD
REV
Ctrl signal 2
Ctrl signal 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
Keypad start
button
1 2 3 4 6 7 8 9
11094.emf
5
1210 11
Selection
number
3
Selection name Note
CS1: Start
CS2: Reverse
Explanations:
1
2
3
4
5
6
Figure 22. I/O A Start/Stop logic = 3
Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward.
CS2 activates which causes the direction to start changing (FWD to REV).
CS2 is inactivated which causes the direction to start changing (REV to FWD) because CS1 is still active.
Also CS1 inactivates and the frequency drops to
0.
Despite the activation of CS2, the motor does not start because CS1 is inactive.
CS1 activates causing the output frequency to rise again. The motor runs forward because CS2 is inactive.
Run enable signal is set to FALSE, which drops
7
the frequency to 0. The run enable signal is configured with parameter P3.5.1.10.
Run enable signal is set to TRUE, which causes
8
the frequency to rise towards the set frequency because CS1 is still active.
Keypad stop button is pressed and the frequency
9
fed to the motor drops to 0. (This signal only works if P3.2.3 Keypad stop button = Yes)
The drive starts through pushing the Start
10
button on the keypad.
The drive is stopped again with the stop button
11
on the keypad.
The attempt to start the drive through pushing
12
the Start button is not successful because CS1 is inactive.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 91 Vacon HVAC Application
t
Output frequency
FWD
REV
Ctrl signal 2
Ctrl signal 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
1 2 3 4
5
6 7 8 9
1110
11095.emf
10 11
Selection
number
4
Selection name Note
CS1: Start (edge)
CS2: Reverse
Shall be used to exclude the possibility of an unintentional start. The Start/Stop contact must be opened before the motor can be restarted.
Explanations:
1
2
3
4
5
6
Figure 23. I/O A Start/Stop logic = 4
Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward because CS2 is inactive.
CS2 activates which causes the direction to start changing (FWD to REV).
CS2 is inactivated which causes the direction to start changing (REV to FWD) because CS1 is still active.
Also CS1 inactivates and the frequency drops to
0.
Despite the activation of CS2, the motor does not start because CS1 is inactive.
CS1 activates causing the output frequency to rise again. The motor runs forward because CS2 is inactive.
Run enable signal is set to FALSE, which drops
7
the frequency to 0. The run enable signal is configured with parameter P3.5.1.10.
Before a successful start can take place, CS1
8
must be opened and closed again.
Keypad stop button is pressed and the frequency
9
fed to the motor drops to 0. (This signal only works if P3.2.3 Keypad stop button = Yes)
Before a successful start can take place, CS1
10
must be opened and closed again.
11 CS1 inactivates and the frequency drops to 0.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 92
P3.3.10 PRESET FREQUENCY MODE
You can use the preset frequency parameters to define certain frequency references in advance. These references are then applied by activating/inactivating digital inputs connected to parameters P3.5.1.15, P3.5.1.16 and P3.5.1.17 (
frequency selection 1
and Preset frequency selection 2). Two different logics can be selected:
Preset frequency selection 0, Preset
Selection
number
0Binary coded
1
P3.3.12 PRESET FREQUENCIES 1 P3.3.18
Selection name Note
Combine activated inputs according to Table 72 to choose the Preset frequency needed.
Number (of inputs
used)
TO 7
According to how many of the inputs assigned for
frequency selections frequencies
1 to 3.
are active you can apply the Preset
Preset
The values of the preset frequencies are automatically limited between the minimum and maximum frequencies (P3.3.1 and P3.3.2). See table below.
Table 72. Selection of preset
frequencies; = input activated
Required action Activated frequency Choose value 1 for
parameter P3.3.3
Preset frequency 0
B2 B1 B0 Preset frequency 1 B2 B1 B0 Preset frequency 2 B2 B1 B0 Preset frequency 3
B2 B1 B0 Preset frequency 4 B2 B1 B0 Preset frequency 5 B2 B1 B0 Preset frequency 6 B2 B1 B0 Preset frequency 7
P3.4.1 RAMP 1 SHAPE
The start and end of acceleration and deceleration ramps can be smoothed with this parameter. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped acceleration/ deceleration. The acceleration time is determined with parameters P3.4.2 and P3.4.3. See Figure 24.
These parameters are used to reduce mechanical erosion and current spikes when the reference is changed.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 93 Vacon HVAC Application
P3.4.2, P3.4.3
[Hz]
[t]
P3.4.1
P3.4.1
11096.emf
Figure 24. Acceleration/Deceleration (S-shaped)
P3.4.12 F
LUX BRAKING
Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases where additional brake resistors are not needed.
When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains controlled during braking.
The flux braking can be set ON or OFF.
NOTE! Flux braking converts the energy into heat at the motor, and should be used intermittently to avoid motor damage.
P3.5.1.10 RUN ENABLE
Contact open: Start of motor disabled Contact closed: Start of motor enabled
The frequency converter is stopped according to the selected function at P3.2.5. The follower drive will always coast to stop.
P3.5.1.11 RUN INTERLOCK 1 P3.5.1.12 R
UN INTERLOCK 2
The drive cannot be started if any of the interlocks are open.
3
The function could be used for a damper interlock, preventing the drive to start with damper closed.
P3.5.1.15 PRESET FREQUENCY SELECTION 0 P3.5.1.16 P P3.5.1.17 P
RESET FREQUENCY SELECTION 1 RESET FREQUENCY SELECTION 2
Connect a digital input to these functions with the programming method presented in Chapter 3.6.2 to be able to apply Preset frequencies 1 to 7 (see Table 72 and pages 53, 56 and
92).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 94
%
100%
63%
P3.5.2.2
t [s]
11097.emf
Filtered signal
Unfiltered signal
P3.5.2.2 AI1 SIGNAL FILTER TIME
When this parameter is given a value greater than 0 the function that filters out disturbances from the incoming analogue signal is activated.
NOTE! Long filtering time makes the regulation response slower!
Figure 25. AI1 signal filtering
P3.5.3.2.1 B
ASIC R01 FUNCTION
Table 73. Output signals via RO1
Selection Selection name Description
0 Not used 1 Ready The frequency converter is ready to operate 2 Run The frequency converter operates (motor is running) 3 General fault A fault trip has occurred 4 General fault inverted A fault trip has not occurred 5 General alarm 6 Reversed The reverse command has been selected 7 At speed The output frequency has reached the set reference
8 Motor regulator activated
9 Preset frequency active
10 Keypad control active Keypad control mode selected 11 I/O control B active I/O control place B selected
One of the limit regulators (e.g. current limit, torque limit) is activated
The preset
frequency
has been selected with digital
input
12 Limit supervision 1 Activates if the signal value falls below or exceeds the
set supervision limit (P3.8.3 or P3.8.7) depending on
13 Limit supervision 2
the selected function. 14 Start command active Start command is active. 15 Reserved
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 95 Vacon HVAC Application
Table 73. Output signals via RO1
Selection Selection name Description
16 Fire mode ON 17 RTC timer 1 control Time channel 1 is used. 18 RTC timer 2 control Time channel 2 is used. 19 RTC timer 3 control Time channel 3 is used. 20 FB Control WordB.13 21 FB Control WordB.14 22 FB Control WordB.15 23 PID1 in Sleep mode 24 Reserved 25 PID1 supervision limits PID1 feedback value is beyond supervision limits. 26 PID2 supervision limits PID2 feedback value is beyond supervision limits. 27 Motor 1 control Contactor control for 28 Motor 2 control Contactor control for 29 Motor 3 control Contactor control for 30 Motor 4 control Contactor control for
31 Reserved (Always open)
32 Reserved (Always open) 33 Reserved (Always open) 34 Maintenance warning 35 Maintenance fault
Multi-pump function Multi-pump function Multi-pump function Multi-pump function
P3.9.2 RESPONSE TO EXTERNAL FAULT
An alarm message or a fault action and message is generated by an external fault external fault signal in one of the programmable digital inputs (DI3 by default) using parameters P3.5.1.7 and P3.5.1.8. The information can also be programmed into any of the relay outputs.
P3.9.8 MOTOR THERMAL ZERO SPEED COOLING
Defines the cooling factor at zero speed in relation to the point where the motor is running at nominal speed without external cooling. See Table 55.
The default value is set assuming that there is no external fan cooling the motor. If an external fan is used this parameter can be set to 90% (or even higher).
If you change the parameter P3.1.1.4 restored to the default value.
Setting this parameter does not affect the maximum output current of the drive which is determined by parameter P3.1.1.7 alone.
The corner frequency for the thermal protection is 70% of the motor nominal frequency (P3.1.1.2).
(Motor nominal current), this parameter is automatically
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon HVAC Application vacon • 96
f
f
n
Par. P3.9.8=40%
0
11098.emf
I
T
100%
Overload area
P
cooling
Corner freq
Figure 26. Motor thermal current IT curve
P3.9.9 M
OTOR THERMAL TIME CONSTANT
The time constant is the time within which the calculated thermal stage has reached 63% of its final value. The bigger the frame and/or slower the speed of the motor, the longer the time constant.
The motor thermal time is specific to the motor design and it varies between different motor manufacturers. The default value of the parameter varies from size to size.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate at six times the rated current) is known (given by the motor manufacturer) the time constant parameter can be set basing on it. As a rule of thumb, the motor thermal time constant in minutes equals to 2*t6. If the drive is in stop stage the time constant is internally increased to three times the set parameter value. The cooling in stop stage is based on convection and the time constant is increased.
See Figure 27.
P3.9.10 MOTOR THERMAL LOADABILITY
Setting value to 130% means that the nominal temperature will be reached with 130% of motor nominal current.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
3
vacon • 97 Vacon HVAC Application
105%
Q = (I/IT)2 x (1-e
-t/T )
I/I
T
11099.emf
Trip area
Motor temperature
Time
Motor temperature
Time constant T
*)
*)
Changes by motor size and
adjusted with P3.9.9
Fault/alarm
P3.9.6
Motor• current
f
I
Par. P3.9.12
Par. P3.9.14
11100.emf
Stall area
Figure 27. Motor temperature calculation
P3.9.12 S
TALL CURRENT
The current can be set to 0.0…2*IL. For a stall stage to occur, the current must have exceeded this limit. See Figure 28. If parameter P3.1.1.7
Motor current limit is changed, this parameter
is automatically calculated to 90% of the current limit. See page 66.
NOTE! In order to guarantee desired operation, this limit must be set below the current limit.
3
P3.9.13 S
TALL TIME LIMIT
Figure 28. Stall characteristics settings
This time can be set between 1.0 and 120.0 s.
This is the maximum time allowed for a stall stage. The stall time is counted by an internal up/ down counter.
If the stall time counter value goes above this limit the protection will cause a trip (see P3.9.11). See page 66.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Loading...