Vacon 10 Complete User's Manual

Document: DPD00717C
Version release date: 20.11.2011
1. Safety 1
1.1 Warnings 1
1.2 Safety instructions 3
1.4 Before running the motor 4
2. Receipt of delivery 5
2.3.1 Capacitor recharge 6
2.4 Warranty 7
2.5 Manufacturer’s declaration of conformity 8
3. Installation 9
3.1 Mechanical installation 9
3.1.1 Vacon 10 dimensions 10
3.1.2 Cooling 12
3.1.3 Power losses 13
3.1.4 EMC levels 18
3.1.5 Changing the EMC protection class from C2 or C3 to C4 18
3.2 Cabling and connections 20
3.2.1 Power cabling 20
3.2.2 Control ca bling 21
3.2.3 Screw of cables 23
3.2.4 Cable and fuse specifications 25
3.2.5 General cabling rules 28
3.2.6 Stripping lengths of motor and mains cables 29
3.2.7 Cable installation and the UL standards 29
3.2.8 Cable and motor insulation checks 29
4. Commissioning 30
4.1 Commissioning steps of Vacon 10 30
5. Fault tracing 32
6. Vacon 10 application Interface 35
6.1 Introduction 35
6.2 Control I/O 37
7. Control panel 38
7.1 General 38
7.2 Display 38
7.3 Keypad 39
7.4 Navigation on the Vacon 10 control panel 41
7.4.1 Main menu 41
INDEX
8. Standard application parameters 49
8.1 Quick setup par. (Virtual menu, shows when par. 17.2 = 1) 50
8.2 Motor settings (Control panel: Menu PAR -> P1) 52
8.3 Start / stop setup (Control panel: Menu PAR -> P2) 53
8.4 Frequency references (Control panel: Menu PAR -> P3) 54
8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4) 55
8.6 Digital inputs (Control panel: Menu PAR -> P5) 56
8.7 Analogue inputs (Control panel: Menu PAR -> P6) 56
8.8 Digital outputs (Control panel: Menu PAR -> P8) 57
8.9 Analogue outputs (Control panel: Menu PAR -> P9) 57
8.10 Protections (Control panel: Menu PAR -> P13) 58
8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14) 58
8.12 PI control parameters (Control panel: Menu PAR -> P15) 59
8.13 Application Setting (Control panel: Menu PAR -> P17) 59
8.14 System parameters 60
9. Parameter descriptions 62
9.1 Motor settings (Control panel: Menu PAR -> P1) 62
9.2 Start / stop setup (Control panel: Menu PAR -> P2) 67
9.3 Frequency references (Control panel: Menu PAR -> P3) 74
9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4) 75
9.5 Digital inputs (Control panel: Menu PAR -> P5) 79
9.6 Analogue inputs (Control panel: Menu PAR -> P6) 80
9.7 Digital outputs (Control panel: Menu PAR -> P8) 81
9.8 Analogue outputs (Control panel: Menu PAR -> P9) 82
9.9 Protections (Control panel:Menu Par->P13) 83
9.10 Automatic reset (Control panel: Menu PAR -> P14) 87
9.11 PI control parameters (Control panel: Menu PAR -> P15) 88
9.12 Application setting (Control panel: Menu PAR->P17) 89
9.13 Modbus RTU 91
9.13.1 Termination resistor 91
9.13.2 Modbus address area 91
9.13.3 Modbus process data 92
10. Technical data 94
10.1 Vacon 10 technical data 94
10.2 Power ratings 96
10.2.1 Vacon 10 – Mains voltage 208-240 V 96
10.2.2 Vacon 10 – Mains voltage 115 V 97
10.2.3 Vacon 10 – Mains voltage 380-480 V 97
10.2.4 Vacon 10 – Mains voltage 575 V 98
10.3 Brake resistors 98
safety vacon 1

1. SAFETY

ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY OUT THE ELECTRICAL INSTALLATION!
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or con­nected appliances.
Please read the information included in cautions and warnings carefully:
=Dangerous voltage
Risk of death or severe injury
=General warning
Risk of damage to the product or connected appliances

1.1 Warnings

The components of the power unit of the frequency converter are live when Vacon 10 is connected to mains. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is isolated from the mains potential.
The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor terminals - / + are live when Vacon 10 is connected to mains, even if the motor is not running.
The control I / O-terminals are isolated from the mains poten­tial. However, the relay output terminals may have a danger­ous control voltage present even when Vacon 10 is
connected from mains.
dis
The earth leakage current of Vacon 10 frequency converters exceeds 3.5 mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
If the frequency converter is used as a part of a ma chine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1).
If Vacon 10 is disconnected from mains while running the motor, it remains live if the motor is energized by the process. In this case the motor functions as a generator feeding energy to the frequency converter.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
2 vacon safety
After disconnecting the frequency converter from the mains, wait until the fan stops and the indicators on the display go out. Wait 5 more minutes before doing any work on Vacon 10 connections.
The motor can start automatically after a fault situation, if the autoreset function has been activated.
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
safety vacon 3

1.2 Safety instructions

The Vacon 10 frequency converter has been designed for fixed installations only.
Do not perform any measurements when the frequency con­verter is connected to the mains.
Do not perform any voltage withstand tests on any part of Vacon 10. The product safety is fully tested at factory.
Prior to measurements on the motor or the motor cable, dis­connect the motor cable from the frequency converter.
Do not open the cover of Vacon 10. Static voltage discharge from your fingers may damage the components. Opening the cover may also damage the device. If the cover of Vacon 10 is opened, warranty becomes void.

1.3 Earthing and earth fault protection

The Vacon 10 frequency converter must always be earthed with an earthing conduc­tor connected to the earthing terminal. See figure below:
MI1 - MI3
The earth fault protection inside the frequency converter protects
only the converter itself against earth faults.
If fault current protective switches are used they must be tested
with the drive with earth fault currents that are possible to arise in fault situations.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
4 vacon safety

1.4 Before running the motor

Checklist:
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor shaft rotation direction make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
receipt of delivery vacon 5

2. RECEIPT OF DELIVERY

After unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below).
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.

2.1 Type designation code

VACON0010- 1L- 0001- 1 +OPTIONS
Vacon 10
Input phase
1L = Single phase 3L = Three phases
Output Current
Input Voltage
1 =115V 2 = 208 - 230V 4 = 380 - 480V 7 = 575V
+Options
EMC2 QPES
Language of the documentation
+DLCN = Chinese +DLCZ = Czech +DLDE = German +DLDK = Danish +DLES = Spanish +DLFI = Finnish +DLFR = French +DLIT = Italian
Figure 2.1: Vacon 10 type designation code

2.2 Storage

If the frequency converter is to be kept in store before use make sure that the ambi­ent conditions are acceptable:
Storing temperature -40…+70°C
Relative humidity < 95%, no condensation
+DLNL = Dutch +DLNO = Norwegian +DLPT = Portuguese +DLRU = Russian +DLSE = Swedish +DLTR = Turkish +DLUS = US English empt y = Engli sh
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
6 vacon receipt of delivery

2.3 Maintenance

In normal operating conditions, Vacon 10 frequency converters are maintenance­free. However, regular maintenance is recommended to ensure a trouble-free oper­ating and a long lifetime of the drive. We recommended to follow the table below for maintenance intervals.
Maintenance interval Maintenance action
Whenever necessary Regular
12 months (If stored)
6 - 24 months (depending on environment)
5 - 7 years

2.3.1 Capacitor recharge

After a longer storage time the capacitors need to be recharge in order to avoid ca­pacitor damage. Possible high leakage current through the capacitors must be lim­ited. The best way to achieve this is to use a DC-power supply with adjustable current limit.
1) Set the current limit to 300…800 mA according to the size of the drive.
2) Then connect the DC-power supply to the input phase L1 and L2.
3) Then set the DC-voltage to the nominal DC-voltage level of the (1.35*Un AC) and supply the converter for at least 1 h.
If DC-voltage is not available and the unit has been stored much longer than 12 months deenergized, consult the factory before connecting power.
• Clean headsink
• Check tightening torques of terminals
• Check input and output terminals and con­trol I / O terminals.
• Clean cooling tunnel.
• Check operation of cooling fan, check for corrosion on terminals, busbars and other surfaces.
• Chang cooling fans:
• Main fan
• Interminal fan
• The motor cables should cross other cables at an angle of 90 degrees.
2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
receipt of delivery vacon 7

2.4 Warranty

Only manufacturing defects are covered by the warranty. The manufacturer as­sumes no responsibility for damages caused during or resulting from transport, re­ceipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible for damages and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust, corrosive substances or operation outside the rated specifications. Neither can the manufacturer be held responsible for consequential damages.
The Manufacturer's time of warranty is 18 months from the delivery or 12 months from the commissioning whichever expires first (Vacon Warranty Terms).
The local distributor may grant a warranty time different from the above. This war­ranty time shall be specified in the distributor's sales and warranty terms. Vacon as­sumes no responsibility for any other warranties than that granted by Vacon itself.
In all matters concerning the warranty, please contact first your distributor.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
8 vacon receipt of delivery
EU DECLARATION OF CONFORMITY
We
Manufacture r's nam e: Vacon Oyj
Manufacturer' s address: P.O.Box 2 5
Runsorintie 7 FIN-65381 Vaasa Finland
hereby declare that the product
Product name: Vacon 10 Frequency Converter
Model d esignation: Vacon101L00012…to 00092
Vacon103L00012…to 00112 Vacon103L00014…to 00124
has been designed and manufactured in accordance with the following standards:
Safety:
EN 60204 -1 (2009) (as relevant) , EN 61800-5-1 (2007)
EMC: EN 61800-3 (2004)
and conforms to the relevant safety provisions of the Low Voltage Directive 2006/95/E C and EMC Dir ective 2004/108/EC .
It is ensured through internal measures and quality control that the product conforms at all times to the requi rements of the current Direct ive an d the relevant standards.
In Vaasa, 30th of July, 2010
Vesa Laisi President
The year the CE marking was affixed: 2011

2.5 Manufacturer’s declaration of conformity

Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
=
M5
MI3
MI1
=M4
MI2
=M5
LOC REM
BACK RESET
OK
LOC REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
12
installation vacon 9

3 INSTALLATION

3.1 Mechanical installation

There are two possible ways to mount Vacon 10 in the wall. For MI1-MI3, either screw or DIN-rail mounting. The mounting dimensions are given on the back of the drive and on the following page.
Figure 3.1: Screw mounting, MI1 - MI3
Figure 3.2: DIN-rail mounting, MI1 - MI3
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
10 vacon installation
D1
H3
D2
H1
W2
W3
H2
LOC REM
BACK
RESET
OK

3.1.1 Vacon 10 dimensions

Figure 3.3: Vacon 10 dimensions, MI1 - MI3
Type H1 H2 H3 W1 W2 W3 D1 D2
MI1 160.1 147 137.3 65.5 37.8 4.5 98.5 7 MI2 195 183 170 90 62.5 5.5 101.5 7 MI3 254.3 244 229.3 100 75 5.5 108.5 7
Table 1: Vacon 10 dimensions in millimetres
Frame Dimensions(mm) Weig ht*
W H D (kg.)
MI1 66 157 98 0.5 MI2 90 195 102 0.7 MI3 100 262 109 1
Table 2: Vacon 10 frame dimensions (mm) and weights (kg)
*without shipping package
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 11
Frame Dimensions(Inches) Weig ht*
MI1 2.6 6.2 3.9 1.2 MI2 3.5 9.9 4 1.5 MI3 3.9 10.3 4.3 2.2
Table 3: Vacon 10 frame dimensions (Inch) and weights (Ibs)
W H D (Ibs.)
*without shipping package
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
12 vacon installation

3.1.2 Cooling

Enough free space shall be left above and below the frequency converter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table below.
If several units are mounted above each other the required free space equals C + D (see Installation space). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the tem­perature of the cooling air does not exceed the maximum ambient temperature of the converter.
Min clearance (mm)
Type A* B* C D
MI1 20 20 100 50 MI2 20 20 100 50 MI3 20 20 100 50
Table 3.1: Min. clearances around AC drive
*. Min clearance A and B for drives for MI1 ~ MI3 can be 0 mm if the ambient temperature is below 40 degrees.
A = clearance around the freq. converter (see also B) B = distance from one frequency converter to another or distance to cabinet wall C = free space above the frequency converter D = free space underneath the frequency converter
NOTE! See the mounting dimensions on the back of the drive. Leave free space for cooling above (100 mm), below (50 mm), and on the sides (20 mm) of Vacon 10! For MI1 - MI3, side-to-side installation allowed only if the am­bient temperature is below 40 °C.
Type Cooling air required (m³/h)
MI1 10 MI2 10 MI3 30
Table 3.2: Required cooling air
C
A
F ig ur e 3 .4 : I ns t al la ti on sp ac e
B
A
D
B
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 13

3.1.3 Power losses

If the operator wants to raise the switching frequency of the drive for some reason (typically e.g. in order to reduce the motor noise), this inevitably affects the power losses and cooling requirements, for different motor shaft power, operator can se­lect the switching frequency according to the graphs below.
MI1 - MI3 3P 380 V POWER LOSS
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
14 vacon installation
MI1 - MI3 3P 230 V POWER LOSS
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 15
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
16 vacon installation
MI1 - MI3 1P 230 V POWER LOSS
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 17
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
18 vacon installation

3.1.4 EMC levels

EN61800-3 defines the division of frequency converters into five classes according to the level of electromagnetic disturbances emitted, the requirements of a power sys­tem network and the installation environment (see below). The EMC class of each product is defined in the type designation code.
Category C1: Frequency converters of this class comply with the requirements of category C1 of the product standard EN 61800-3 (2004). Category C1 ensures the best EMC characteristics and it includes converters the rated voltage of which is less than 1000 V and which are intended for use in the 1st environment. NOTE: The requirements of class C are fulfilled only as far as the conducted emis­sions are concerned.
Category C2: Frequency converters of this class comply with the requirements of category C2 of the product standard EN 61800-3 (2004). Category C2 includes con­verters in fixed installations and the rated voltage of which is less than 1000 V. The class C2 frequency converters can be used both in the 1st and the 2nd environment.
Category C3: Frequency converters of this class comply with the requirements of category C3 of the product standard EN 61800-3 (2004). Category C3 includes con­verters the rated voltage of which is less than 1000 V and which are intended for use in the second environment only.
Category C4: The drives of this class do not provide EMC emission protection. These kinds of drives are mounted in enclosures.
Environments in product standard EN 61800-3 (2004)
First environment: Environment that includes domestic premises. It also includes establishments directly connected without intermediate transformers to a low-volt­age power supply network which supplies buildings used for domestic purposes.
NOTE: houses, apartments, commercial premises or offices in a residential building are examples of first environment locations.
Second environment: Environment that includes all establishments other than those directly connected to a low-voltage power supply network which supplies buildings used for domestic purposes. NOTE: industrial areas, technical areas of any building fed from a dedicated trans­former are examples of second environment locations.

3.1.5 Changing the EMC protection class from C2 or C3 to C4

The EMC protection class of MI1-3 frequency converters can be changed from class C2 or C3 to class C4 by removing the EMC-capacitor disconnecting screw, see fig­ure below.
Note! Do not attempt to change the EMC level back to class C2 or C3. Even if the pro­cedure above is reversed, the frequency converter will no longer fulfil the EMC re­quirements of class C2 / C3!
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 19
Figure 3.5: EMC protection class, MI1 - MI3
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
20 vacon installation
1~ (230V)
3~ (230V, 400V)
Motor out
MAINS
MOTOR
Strip the plastic cable coating for 360° earthing
L1 L 2/N L3 U/ T1 V/T2 W /T3R+ R-
1~ (230V)
3~(230V, 400V, 575V)
1~ (115V)
MAINS
MOTOR
BRAKE RESISTOR
External brake resistor
Motor out
Strip the plastic cable coating for 360° earthing
3~(230V, 400V, 575V)

3.2 Cabling and connections

3.2.1 Power cabling

Note! Tightening torque for power cables is 0.5 - 0.6 Nm
Figure 3.6: Vacon 10 power connections, MI1
3
Figure 3.7: Vacon 10 power connections, MI2 - MI3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 21
Attach this plate BEFORE i nsta lling the pow er ca bl es
Attach the support AFTER i nstal ling the po wer cables

3.2.2 Control cabling

Figure 3.8: Mount the PE-plate and API cable support, MI1 - MI3
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
22 vacon installation
Strip the plastic cable coating for 360°earthing
Control cable tightening torque: 0.4 Nm
Figure 3.9: Open the lid, MI1 - MI3
3
Figure 3.10: Install the control cables. MI1 - MI3. See Chapter 6.2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 23
M4*8 - 12 Pcs
M4-8 Screws 14 Pcs

3.2.3 Screw of cables

Figure 3.11: MI1 screws
Figure 3.12: MI2 screws
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
24 vacon installation
M4-8 Screws 10 Pcs
M4-10 Screws 4 Pcs
Figure 3.13: MI3 screws
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 25

3.2.4 Cable and fuse specifications

Use cables with heat resistance of at least +70°C. The cables and the fuses must be dimensioned according to the tables below. Installation of cables according to UL regulations is presented in Chapter Cable installation and the UL standards.
The fuses function also as cable overload protection. These instructions apply only to cases with one motor and one cable connection from the frequency converter to the motor. In any other case, ask the factory for more in­formation.
EMC category cat. C2 cat. C3 cat. C4
Mains cable types 1 1 1 Motor cable types 3 2 1 Control cable types 4 4 4
Table 3.3: Cable types required to meet standards. EMC categories are described in Chapter EMC levels
Cable type Description
Power cable intended for fixed installation and the specific mains voltage.
1
Shielded cable not required. (NKCABLES / MCMK or similar recommended)
Power cable equipped with concentric protection wire and intended for
2
the specific mains voltage. (NKCABLES / MCMK or similar recommended).
Power cable equipped with compact low-impedance shield and intended for the specific mains voltage.
3
(NKCABLES / MCCMK, SAB / ÖZCUY-J or similar recommended).
*360º earthing of both motor and FC connection required to meet the standard
Screened cable equipped with compact low-impedance shield (NKCA-
4
Table 3.4: Cable type descriptions
BLES /Jamak, SAB / ÖZCuY-O or similar).
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
26 vacon installation
Mains
cable
2
]
Motor
cable
Cu [mm
Frame Ty pe
MI2 0001-0004 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0005 32 2*6+6 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
Fuse
[A]
Cu [mm
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
terminal
[mm
2
]
2
]
Control
terminal
[mm
2
]
Table 3.5: Cable and fuse sizes for Vacon 10, 115 V, 1~
Mains
cable
Mains
cable
Motor
cable
Cu [mm2]
Motor
cable
Cu [mm2]
Frame Ty pe
MI1 0001-0003 10 2*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI2 0004-0007 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0009 32 2*6+6 3*1.5+1.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.6: Cable and fuse sizes for Vacon 10, 208 - 240 V, 1~
Frame Ty pe
MI1 0001-0003 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI2 0004-0007 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0011 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Fuse
[A]
Fuse
[A]
Cu [mm2]
Cu [mm2]
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
terminal
[mm
2
]
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
terminal
[mm
2
]
Table 3.7: Cable and fuse sizes for Vacon 10, 208 - 240 V, 3~
Relay
terminal
[mm
Relay
terminal
[mm
Relay
terminal
[mm
2
]
2
]
2
]
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 27
Mains
Motor
cable
Frame Typ e
MI1 0001-0003 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI2 0004-0006 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0008-0012 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Fuse
[A]
[mm2]
Cu
cable
Cu [mm
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
terminal
[mm
2
]
2
]
Control
terminal
[mm
2
]
terminal
Table 3.8: Cable and fuse sizes for Vacon 10, 380 - 480 V, 3~
Mains
Motor
cable
Fram e Ty pe
MI3 0002-0004 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0005-0006 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0009 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.9: Cable and fuse sizes for Vacon 10, 575 V
Note! To fulfil standard EN61800-5-1, the protective co nductor should be at least 10 mm2 Cu or 16 mm2 Al. Another possibility is to use an additional protective con-
ductor of at least the same size as the original one.
Fuse
[A]
[mm2]
Cu
cable
Cu [mm2]
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
2
[mm
]
terminal
[mm
2
]
Relay
2
[mm
Relay
terminal
2
[mm
]
]
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
28 vacon installation

3.2.5 General cabling rules

Before starting the installation, check that none of the components of the fre-
1
quency converter is live. Place the motor cables sufficiently far from other cables:
Avoid placing the motor cables in long parallel lines with other cables.
• If the motor cable runs in parallel with other cables, the minimum distance between the motor cable and other cables is 0.3 m.
• The given distance also applies between the motor cables and signal cables
2
3
4
of other systems.
• The maximum length of the motor cables for MI1-3 is 30 m. If use longer cable, current accuracy will be decreased.
• The motor cables should cross other cables at an angle of 90 degrees.
If cable insulation checks are needed, see Chapter Cable and motor insulation checks.
Connecting the cables:
• Strip the motor and mains cables as advised in Figure Stripping of cables.
• Connect the mains, motor and control cables into their respective termi­nals, see Figures Vacon 10 power connections, MI1 - Install the control cables.
• Note the tightening torques of power cables and control cables given in Vacon 10 power connections, MI1 and Install t he control cables. MI1 - MI3. See Chapter6.2.
• For information on cable installation according to UL regulations see Chap­ter Cable installation and the UL standards.
• Make sure that the control cable wires do not come in contact with th e elec­tronic components of the unit.
• If an external brake resistor (option) is used, connect its cable to the appro­priate term inal.
Check the connection of the earth cable to the motor and the frequency converter terminals marked with.
• Connect the separate shield of the motor cable to the earth plate of the frequency converter, motor and the supply centre.
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
20 mm
35 mm
8 mm
Earth conductor
8 mm
installation vacon 29

3.2.6 Stripping lengths of motor a nd mains cables

Figure 3.14: Stripping of cables
Note! Strip also the plastic cover of the cables for 360 degree earthing. See Figures Vacon 10 power connections, MI1, Vacon 10 power connections, MI2 - MI3 and Install the control cables. MI1 - MI3. See Chapter 6.2

3.2.7 Cable installation and the UL standards

To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper ca­ble with a minimum heat-resistance of +60 / 75°C must be used.

3.2.8 Cable and motor insulation checks

These checks can be performed as follows if motor or cable insulations are suspect­ed to be faulty.
1. Motor cable insulation checks
Disconnect the motor cable from terminals U / T1, V / T2 and W / T3 of the frequency converter and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor.
The insulation resistance must be >1 MOhm.
2. Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 / N and L3 of the frequency con­verter and from the mains. Measure the insulation resistance of the mains cable be­tween each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1 MOhm.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1 MOhm.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
30 vacon commissioning

4. COMMISSIONING

Before commissioning, read the warnings and instructions listed in Chapter 1!

4.1 Commissioning steps of Vacon 10

Read carefully the safety instructions in Chapter 1 and follow them.
1
After the installation, make sure that:
• both the frequency converter and the motor are grounded.
• the mains and motor cables comply with the requirements given in Chap­ter 3.2.4.
• the control cables are located as far as possible from the power. cables
2
3 4 5
6
ee C
hapter 3.2.5, step 2) and the shields of the shielded cables are con-
(s nected to protective earth
Check the quality and quantity of cooling air (Chapter 3.1.2).
Check that all Start / Stop switches connected to the I / O terminals are in Stop- position.
Connect the frequency converter to mains.
Set the parameters of group 1 according to the requirements of your application. At least the following parameters should be set:
• motor nominal speed (par. 1.3)
• motor nominal current (par. 1.4)
• application type (par. 17.1)
You will find the values needed for the parameters on the motor rating plate.
.
4
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
commissioning vacon 31
Perform test run without motor. Perform either Test A or Test B:
A) Control from the I / O terminals:
Turn the Start / Stop switch to ON position.
• Change the frequency reference (potentiometer).
• Check the Monitoring Menu and make sure that the value of Output fre­quency changes according to the change of frequency reference.
7
8
9
10
• Turn the Start / Stop switch to OFF position.
ntrol from the keypad:
B) Co
Select the keypad as the control place with par 2.1. You can also move to
ypad control by pressing Loc / Rem button or select Local control with
ke par 2.5.
• Push the Start button on the keypad.
• Check the Monitoring Menu and make sure that the value of Output fre­quency. changes according to the change of frequency reference.
• Push the Stop button on the keypad.
Run the no-load tests without the motor b eing connected to the process, if possi­ble. If this is impossible, secure the safety of each test prior to running it. Inform
ur co-workers of the tests.
yo
• Switch off the supply voltage and wait up until the drive has stopped.
• Connect the motor cable to the motor and to the motor cable terminals of
he
frequency converter.
t
• See to that all Start / Stop switches are in Stop positions.
• Switch the mains ON.
• Repeat test 7A or 7B.
Perform an identification run (see par. 1.18), especially if the application requires a high startup torque or a high torque with low speed.
Connect the motor to the process (if the no-load test was running without the motor being connected).
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
4
32 vacon fault tracing
Fault code (02 = overvoltage)
FT. 02

5. FAULT TRACING

Note: The fault codes listed in this chapter are visible if the Application Interface has
a display, like e.g. in control board or if a personal computer has been connected to the drive.
When a fatal fault is detected by the frequency converter control electronics, the drive will stop and the symbol FT and the fault code blinked on the display are in the following format, e.g.:
The active fault can be reset by pressing BACK / RESET button when the API is in ac­tive fault menu level (FT XX), or pressing BACK / RESET button with long time (> 2 s) when the API is in active fault submenu level (F5.x ), or via the I / O terminal or field bus. Reset fault history (long push > 5 s), when the API is in fault history submenu level (F6.x). The faults with subcode and time labels are stored in the Fault history submenu which can be browsed. The different fault codes, their causes and correct­ing actions are presented in the table below.
5
Fault
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
Overcurrent
1
Overvoltage
2
Earth fault
3
Frequency converter has detected too high a current
) in the motor cable:
(>4*I
N
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
The DC-link voltage has exceeded the internal safety limit:
• deceleration time is too short
• high overvoltage spikes in mains
Current measurement has detected extra leakage current at start:
• insulation failure in cables or motor
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
Check loading. Check motor size. Check cables.
Increase the deceleration time (Par.4.3)
Check motor cables and motor
fault tracing vacon 33
Fault
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
System fault
8
Undervoltage
9
Output phase fault
11
Frequency converter
13
undertemperature
Frequency converter
14
overtemperature
Motor stalled
15
Motor overtempera-
16
ture
Motor underload
17
• component failure
• faulty operation
The DC-link voltage has gone below the internal safety limit:
• most probable cause: supp ly voltage is too low
• frequency converter internal fault
• Power outages
Current measurement has detected that there is no current in one motor phase.
Heat sink temperature is under
°C
-10
Heat sink is overheated.
Motor stall protection has tripped.
Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded.
Motor underload protection has tripped.
Reset the fault and restart . If the fault re-occurs, con­tact the distributor near to you. NOTE! If fault F8 occurs, find out the subcode of the fault from the Fault His­tory menu under Id xxx!
In case of temporary sup­ply voltage break reset the fault and restart the fre­quency converter. Check the supply voltage. If it is adequate, an internal fail­ure has occurred. Contact the distributor near to you.
Check motor cable and motor.
Check the ambient tem­perature.
Check that the cooling air flow is not blocked. Check the ambient tem­perature. Make sure that the switching frequency is not too high in relation to ambient temperature and motor load.
Check that the motor is able to rotate freely.
Decrease the motor load. If no motor overload exists, check the temper­ature model parameters.
Check motor and load, e.g. for broken belts or dry pumps.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
5
34 vacon fault tracing
Fault
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
EEPROM checksum
22
fault
Microcontroller
25
watchdog fault
Back EMF protection
27
Internal bus commu-
34
nication
Application fault
35
IGBT Overtemperature
41
Analog input select 20% - 100% (selected
50
signal range 4 to 20 mA or 2 to 10 V)
External fault
51
Fieldbus fault
53
Idenfication fault Identification run has failed.
57
Parameter save fault
• faulty operation
• component failure
• faulty operation
• component failure
Drive has detected that the mag­netized motor is running in start situation.
• A rotating PM-motor
Ambient interference or defective hard ware
Application is not working prop­erly.
Overtemperature alarm is issued when the IGBT switch tempera­ture exceeds 110 °C.
Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V.
• control cable is broken or loose.
• signal source has failed.
Digital input fault. Digital input has been programmed as exter­nal fault input and this input is active.
The data connection between the fieldbus Master and the fieldbus of the drive has broken.
Contact the distributor near to you.
Reset the fault and resta rt. If the fault re-occur, con­tact the distributor near to you.
Make sure that there is no rotating PM-motor when the start command is given.
If the fault re-occur, con­tact the distributor near to you.
Contact the distributor near to you.
Check loading. Check motor size. Make identification run.
Check the current loop circuitry.
Check installation. If installation is correct, contact the nearest Vacon distributor.
Run command was removed before comple­tion of identification run. Motor is not connected to frequency converter. There is load on motor shaft.
5
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 api vacon 35

6. VACON 10 APPLICATION INTERFACE

6.1 Introduction

There is only one version of Control Board available for the Vacon 10 drive:
Vers ion Composition
6 Digital inputs 2 Analogue inputs
Vacon 10
Table 6.1: Available Control Board
This section provides you with a description of the I / O-signals f or these versions and instructions for using the Vacon 10 general purpose application.
The frequency reference can be selected from Preset Speed 0-7, Keypad, Fieldbus, AI1, AI2, PI.
Basic properties:
• Digital inputs DI1…DI6 are freely programmable. The user can assign a single input to many functions.
• Digital-, relay- and analogue outputs are freely programmable.
• Analog output can be set as current output.
• Analog input 1 can be set as voltage input and Analog input 2 can be set as current input.
Special features:
• Programmable Start / Stop and Reverse signal logic
• Reference scaling
• DC-brake at start and stop
• Programmable U / f curve
• Adjustable switching frequency
• Autoreset function after fault
1 Analogue output 1 Digital output 2 Relay outputs
RS-485 Interface
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
36 vacon vacon 10 api
• Protections and supervisions (all fully programmable; off, alarm, fault):
• Analog input low fault
• Undervoltage fault
• Earth fault
• Output phase fault
• Motor thermal, stall and underload protection
• 8 preset speeds
• Analogue input range selection, signal scaling and filtering
6
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 api vacon 37
20

ON
OFF

6.2 Control I/O

Terminal Signal Factory preset Description
1 +10Vre Ref. voltage out Maximum load 10 mA 2 AI1 Analog signal in 1
3 GND I/O signal ground 6 24Vout 24V output for DI's
7 GND I/O signal ground 8 DI1 Digital input 1
9 DI2 Digital input 2 10 DI3 Digital input 3 A A RS485 signal A FB Communication Negative B B RS485 signal B FB Communication Positive 4 AI2 Analog signal in 2
mA
5 GND I/O signal ground 13 GND I/O signal ground 14 DI4 Digital input 4 15 DI5 Digital input 5 16 DI6 Digital input 6 18 AO Analog Output
20 DO Digital signal out
22 RO 13 Relay out 1 23 RO 14
24 RO 22 Relay out 2 25 RO 21 26 RO 24
Table 6.2: Vacon 10 default I/O configuration and connections P) = Programmable function, see parameter lists and descriptions, chapters 8 and 9.
Freq. reference
Start forward P) Start reverse P) Fault reset P)
PI actual value P)
Preset speed B0 P) Preset speed B1 External fault Output frequency P) Active = READY P)
Active = RUN P)
Active = FAULT
P)
0 - 10 V Ri = 200 k (min)
%, max. load 50 mA
0 - +30 V Ri = 12 k min
0(4) - 20 mA, Ri = 200
0 - +30 V Ri = 12 k
P)
(min)
P)
0(4) - 20 mA, RL = 500 Open collector, max. load 48V/50mA Max. switching load:
250Vac/2A or 250Vdc/ 0,4A
P)
Max. switching load: 250Vac/2A or 250Vdc/ 0,4A
Figure 6.1: Vacon 10 I/O
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
38 vacon control panel

7. CONTROL PANEL

7.1 General

The panel is an irremovable part of the drive consisting of corresponding control board; The overlay with display status on the cover and the button are in clarifica­tions in the user language.
The User Panel consists o f an alphanumeric LCD display with back light and a keypad with the 9 push buttons (see Figure 7.1).

7.2 Display

The display includes 14-segment and 7-segment blocks, arrowheads and clear text unit symbols. The arrowheads, when visible, indicate some information about the drive, which is printed in clear text in user language on the overlay (numbers 1…14 in the figure below). The arrowheads are grouped in 3 groups with the following meanings and English overlay texts (see Figure 7.1):
Group 1 - 5; Drive status
1= Drive is ready to start (READY) 2= Drive is running (RUN) 3= Drive has stopped (STOP) 4= Alarm condition is active (ALARM) 5= Drive has stopped due to a fault (FAULT)
Group 6 - 10; Control selections
When API is operated by PC control, there are no arrowhead at I / O, KEYPAD and BUS.
6= Motor is rotating forward (FWD) 7= Motor is rotating reverse (REV) 8= I/O terminal block is the selected control place (I / O) 9= Keypad is the selected control place (KEYPAD) 10= Fieldbus is the selected control place (BUS)
Group 11 - 14; Navigation main menu
11= Reference main menu (REF) 12= Monitoring main menu (MON) 13= Parameter main menu (PAR) 14= System main menu (SYS)
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 39
1 2 3 4 5
6 7 8 9 10
11
13
14
12
READY RUN STOP ALARM FAULT
FWD REV I/O KEYPAD BUS
SYS
PAR
REF
MON
BACK
RESET
LOC
REM
OK

7.3 Keypad

The keypad section of the control panel consists of 9 buttons (see Figure 7.1). The buttons and their functions are described as Table 7.1.
The drive stops by pressing the keypad STOP button. The drive starts by pressing the keypad START button when the selected control
place is KEYPAD.
Figure 7.1: Vacon 10 Control panel
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
40 vacon control panel
OK
Symbol Button Name Function Description
Start Motor START from the panel
STOP Motor STOP from the panel
OK Used for confirmation
BACK
RESET
LOC
Back / Reset
Up and Down
Left and Right
Loc / Rem Change control place
Cancels edited parameter Move backwards in menu levels Reset fault indication
Navigation button: Select root parameter number on root­parameter list, Up decrease / Down increase parameter number, Up increase / Down decrease parame­ter value change
Available in MON, PAR and SYS men­uparameter, navigation and parameter digit setting MON can also use left and right button to navigate the menu from V1.x to V2.1 to V3.1
REM
Table 7.1: Keypad Function
NOTE! The status of all the 9 buttons are available for application program!
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
control panel vacon 41

7.4 Navigation on the Vacon 10 control panel

This chapter provides you with information on na vigating the menus on Vacon 10 and editing the values of the parameters.

7.4.1 Main menu

The menu structure of Vacon 10 control software consists of a main menu and sev­eral submenus. Navigation in the main menu is shown below:
REFERENCE MENU
Dispalysthe keypad reference value regardless of theselected contron place.
REF
MON
PAR
SYS SYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RU N
Hz
REF
MON
OK
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
PRESS
MONI TO RING MENU
In this me nu you can browsethe monitoring values.
REF
MON
PA R
SYS SYS
FWD REV I/O KEYPAD BU S
FAUL TALARMSTOPREADY RUN
REF
MON
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
PRESS
PAR A M E T E R MENU
In this me nu you can browseand edit the parameters.
REF
MON
PAR
SYS SYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RUN
REF
MON
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
PRESS
SYSTEM MENU
Here youwill be able tobrowse systemparameter and fault submenu.
REF
MON
PAR
SYS SYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPRE ADY RUN
REF
MON
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
Figure 7.2: The main menu of Vacon 10
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
FAULTALARMSTOPREADY RUN
Hz
FAUL TALARMSTO PREADY RUN
FAULTALARMSTOPREADY RUN
FAU LTALARMSTO PREAD Y RUN
7
42 vacon control panel
Press to enter edit mode
Change value
Press to confirm
OK OK
SYS
FWD REV I/O KEYPAD BUS
REF
MON
PA R
FAU LTALARMSTOPREADY R UN
Hz

7.4.2 Reference menu

Figure 7.3: Reference menu display
Move to the reference menu with the UP / DOWN button (see Figure 7.2). The refer­ence value can be changed by 0.01 every time with UP / DOWN button as shown in Figure 7.3.
If the value has big change, first press Left and Right buttons to select the dig it which has to be changed, then press Up button to increase and Down button to decreases the value in the selected digit . In the end, press OK button to take the setting value effective.
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 43

7.4.3 Monitoring menu

REF
MON
PAR
SYS
FW D R EV I /O K EY PA D B US F W D RE V I/ O K EY PA D B US
FAULTALARMSTOPREADY RUN
MON
REF
PAR
SYS
OK
1
Press OK to enter
Monitoring menu
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
Prsess Down to
3
browse V4.4
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RUN
FAULTALARMSTOPRE ADY RUN
OK
Press Left/Right t o browse
2
other Monitor ing groups
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
Preess OK the value is
4
displayed
5
Press OK V4.4 is display
Figure 7.4: Monitoring menu display
Monitoring values are actual values of measured signals as well as status of some control settings. It is visible in Vacon 10 display, but it can not be edited. The moni­toring values are listed in Table 7.2.
Pressing Left/Right button to change the actual parameter to the first parameter of the next group, to browse monitor menu from V1.x to V2.1 to V4.1. After entering the desired group, the monitoring values can be browsed b y pressing UP /DOWN button, as shown in Figure 7.4.
In MON menu the selected signal and its value are alternateing in the display by pressing OK button.
Note! Turn on drive power, arrowhead of main menu is at MON, V x. x
is displayed in Panel. The value of “x” is determined by the last show before power
shut down. E.g., it was V4.4, and it is also V4.4 when restart.
FAULTALARMSTOPREADY RUN
FAULTALARMSTOPRE ADY RUN
OK
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
44 vacon control panel
Code Monitoring signal Unit ID Description
V1.1 Output frequency Hz 1 Outpu t frequency to motor
V1.2 Frequency reference Hz 25
V1.3 Motor speed rpm 2 Calculated motor speed V1.4 Motor current A 3 Measured motor current
V1.5 Motor torque % 4
V1.6 Output Power KW 79 Output power from drive to motor V1.7 Motor voltage V 6 Motor voltage V1.8 DC-link voltage V 7 Measured DC-link voltage V1.9 Drive temperature °C 8 Heatsink temperature V1.10 Motor temperature % 9 Calculated motor temperature
V2.1 Analog input 1 % 13
V2.2 Analog input 2 % 14
V2.3 Analog output % 26
Digital input status DI1,
V2.4
DI2, DI3 Digital input status DI4,
V2.5
DI5, DI6 V2.6 RO1, RO2, DO 17 Relay / digital output status V4.1 PI setpoint % 20 Regulator setpoint V4.2 PI feedback value % 21 Regulator actual value V4.3 PI error % 22 Re gulato r error V4.4 PI output % 23 Regulator output
Table 7.2: Vacon 10 monitoring signals
Frequency reference to motor con­trol
Calculated actual / nominal torque of the motor
AI1 signal range in percent of used range
AI2 signal range in percent of used range
AO signal range in percent of used range
15 Digital input status
16 Digital input status
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 45

7.4.4 Parameter menu

In Parameter menu only the Quick setup parameter list is shown as default. By giving the value 0 to the parameter 17.2, it is possible to open other advanced parameter
groups. The parameter lists and descriptions can be found in chapters 8 and 9. The following figure shows the parameter menu view:
REF
MON
PAR
SYS
FW D R EV I/O KE Y PAD B US FWD R E V I/ O K EY PA D B U S
FAULTALARMSTOPREADY RU N
REF
MON
PAR
SYS
OK
Press Right to browse
OK
REF
MON
PAR
SYS
2
4
6
otherPa r. group
FWD R EV I/O KEYPAD BUS
Press OK button to enter edit mode
Press OK to confirm
Press OK to enter Par. menu
1
REF
MON
PAR
SYS
FWD R EV I/O KEYPAD BUS
Press down button to
3
browse P3.4
REF
MON
PAR
SYS
FWD R EV I/O KEYPAD BUS
Press Up / Down to change value
5
FAULTALARMSTOPREADY RU N
FAULTALARMSTOPREADY RUN
Figure 7.5: Parameter menu
The parameter can be changed as the Figure 7.5. Left / Right button is available inside Parameter menu. Pressing Left / Right button
to change the actual parameter to the first parameter of the next group (Example: any parameter of P1… is displayed -> RIGHT button -> P2.1 is displayed -> RIGHT but­ton -> P3.1 is displayed …). After entering the desired group, pressing UP / DOWN button to select root parameter number, and then press OK button to display the val­ue of the parameter and also enter edit mode.
FAULTALARMSTOPREADY RU N
FAULTALARMSTOPREADY RUN
OK
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
46 vacon control panel
In edit mode, Left and Right buttons are used to select the digit which has to be changed, and Up increases / Down decreases parameter value.
In edit mode, the value of Px.x is displayed blinkingly in the panel. After about 10 s, Px.x is displayed in the panel again if you don't press any button.
Note! In edit mode, if you edit the value and don't press OK button, the
value isn't changed successfully. In edit mode, if you don't edit the value, you can press Reset /
Back button to display Px.x again.
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 47
OK
Press OK to enter V1 .1
1
Press Left/Right button to browse other groups
2
Press down to browse other active faults
3
REF
MON
PAR
SYS
FAULTALA RMSTOP
FWD REV I/O KEYPAD BUS
READY RUN
OK
Press OK to select one fault to browse its time
4
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RU N
FWD REV I/O KEYPAD BUS
Browse for fault code(C xx), subcode(Id xx), days(dxx), hours(H xx), minutes(M xx)
5
REF
MON
PAR
SYS
FAULTALA RMSTOPREADY RU N
FWD REV I/O KEYPAD BUS
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS

7.4.5 System menu

SYS menu including fault submenu and system parameter submenu, and the display and operation of the system parameter submenu is similar to PAR menu or MON menu.In system parameter submenu, there are some editable parameter (P) and some uneditable parameter (V).
The Fault submenu of SYS menu includes active fault submenu and fault history sub ­menu.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
In active fault situation, FAULT arrow is blinking and the display is blinking active fault menu item with fault code. If there are several active faults, you can check it by entering the active fault submenu F5.x. F5.1 is always the latest active fault code. The active faults can be reset by pressing BACK / RESET button with long time (>2 s), when the API is in active fault submenu level (F5.x). If the fault cannot be reset, the blinking continues. It is possible to select other display menus durin g active fault, but in this case the display returns automatically to the fault menu if no button is pressed in 10 seconds. The fault code, subcode and the operating day, hour and minute val­ues at the fault instant are shown in the value menu (operating hours = displayed reading).
Figure 7.6: Fault menu
7
48 vacon control panel
Note! Fault History can be reset by long pressing the BACK / RESET
button for 5 second time,when the API is in fault history sub­menu level (F6.x), it will also clear all active faults.
See Chapters for fault descriptions
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameters vacon 49
i

8. STANDARD APPLICATION PARAMETERS

On the next pages you can find the lists of parameters within the respective param­eter groups. The parameter descriptions are given in Chapter 9 .
Explanations:
Code: Location indication on the keypad; Shows the operator the present
Parameter: Name of monitoring value or parameter Min: Minimum value of parameter Max: Maximum value of parameter Unit: Unit of parameter value; given if available Default: Factory preset value ID: ID number of the parameter (used with fieldbus control)
NOTE: On parameter code: Parameter value can only be changed after the FC ha s been stopped. This manual is for Vacon 10 standard application only. If you are us­ing a special application, please download the appropriate user manual on http:// www.vacon.com -> Support & Downloads.
Monitoring value number or Parameter number
More information on this parameter available in chapter 9: ‘Param-
eter descriptions’ click on the parameter name.
Modifiable only in stop state
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
50 vacon parameters
P1.1
P1.2
P1.3
P1.4
P1.5
i
i
i
i
iiiii
i
P1.7
P1.15
P2.2
P2.3
P3.1
P3.2

8.1 Quick setup parameters (Virtual menu, shows when par. 17.2 = 1)

Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage
Motor nominal
frequency
Motor nominal
speed
Motor nominal
current
Motor cos
(Power Factor)
Current limit
Torque boost 0 1 0 109
Remote control
P2.1
place 1 selection
Start function
Stop function
Min frequency 0,00 P3. 2 Hz 0,0 0 101 Minimum freq reference
Max frequency P3.1 320,00 Hz
Remote Control
Place 1 frequency
P3.3
refere nce selec-
tion
P3.4 P reset speed 0 P3.1 P3.2 Hz 5,00 124
P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105
P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106
P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126
Table 8.1: Quick setup parameters
180 690 V Varies 110
30,00 320,00 Hz
30 20000 rpm
2,0 x
0,2 x
I
I
Nunit
Nunit
0,30 1,00 0,85 120
2.0 x
0,2 x
I
I
Nunit
Nunit
0 1 0 172
0
1 0 505
0
1 0 506
1 6 4 117
50,00 /
60,00
1440 /
1720
I
A
Nunit
1.5 x
A
I
Nunit
50,00 /
60,00
Check rating plate on the motor.
Check rating plate on the
111
motor.
Default a pplies for a 4-
112
pole motor.
Check rating plate on the
113
motor.
Check rating plate on the motor.
107 Maximum motor current
0 = Not used 1 = Used
0 = I / O terminal 1 = Fieldbus
0 = Ramp 1 = Flying start
0 = Coasting 1 = Ramp
Maximum freq refer-
102
ence
1 = Preset Speeds 0-7 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = PI
Activated by digital inputs
Activated by digital inputs
Activated by digital inputs
Activated by digital inputs
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 51
P4.2
P4.3
P14.1
Code Paramete r Min Max Unit Default ID Note
Acceleration time
1
Deceleration time
1
P6.1 AI1 Signal range 0 1 0 379
P6.5 AI2 Signal range 0 1 0 390
Automatic reset 0 1 0 731
Parameter
P17.2
Table 8.1: Quick setup parameters
conceal
0,1 3000,0 s 3,0 103
0,1 3000,0 s 3,0 104
01 1 115
Acceleration time from 0 Hz to maximum fre­quency.
Deceleration time from maximum frequency to 0 Hz.
0 = 0 - 100% 1 = 20% - 100%
20% is the same as 2 V minimum signal level.
0 = 0 - 100% 1 = 20% - 100%
20% is the same as 4 mA minimum signal level.
0 = Disable 1 = Enable
0 = All parameters visi-
ble 1 = Only quick setup parameter group visible
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
52 vacon parameters
P1.1
P1.2
P1.3
i
i
i
iii
i
i
i
i
i
P1.4
P1.5P1.6
P1.7
P1.8
P1.9
P1.10
P1.11
P1.12
P1.13
P1.14
P1.15
P1.16
P1.17

8.2 Motor settings (Control panel: Menu PAR -> P1)

Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage
Motor nominal fre-
quency
Motor nominal
speed
Motor nominal
current
Motor cos
(Power Factor)
Motor type 0 1 0 650
Current limit
Motor control
mode
U / f ratio 0 2 0 108
Field weakening
point
Field weakening
point voltage
U / f mid point
frequency
U / f mid point
voltage
Zero freq voltage 0,00 40,00 % Varies 606
Torqu e Bo ost 0 1 0 109
Switching fre-
quency
Brake Chopper 0 2 0 504
Table 8.2: Motor settings
180 690 V Varies 110
30,00 320,00 Hz
30 20000 rpm
2,0 x
0,2 x
I
I
Nunit
Nunit
0,30 1,00 0,85 120
2.0 x
0,2 x
I
I
Nunit
Nunit
01 0600
8,00
320,00 Hz
10,00 200,00 % 100,00 603
0,00 P1.10 Hz
0,00 P1.11 % 100,00 605
1,5 16,0 kHz 4,0 / 2,0 601
50,00 /
60,00
1440 /
1720
I
A
Nunit
1.5 x
A
I
Nunit
50,00 /
60,00
50,00 /
60,00
Check rating plate on the motor
Check rating plate on the
111
motor
Default applie s for a 4-pole
112
motor.
Check rating plate on the
113
motor
Check rating plate on the motor
0 = Induction 1 = Permanent magnet
107 Maximum motor current
0 = Frequency control 1 = Open loop speed control
0 = Linear 1 = Quadratic 2 = Programmable
Field weakening point fre-
602
quency Voltage at field weakening
point as % of U Mid point frequency for
604
programmable U / f Mid point voltage for pro-
grammable U / f as % of U
nmot
Voltage at 0 Hz as % of U
nmot
0 = Disabled 1 = Enabled
PWM frequency. If values are higher than default, reduce the current capacity
0 = Disabled 1 = Enabled: Always 2 = Run state
nmot
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 53
iiiii
P2.2
P2.3
i
P1.18
P1.19
P1.20
P1.21
Code Parameter Min Max Unit Default ID Note
Motor identifica-
tion
Rs voltage drop 0,00 100,00 % 0,00 675
Overvoltage con-
troller
Undervoltage
controller
Table 8.2: Motor settings
01 0631
02 1607
01 1608
0 = Not active 1 = Standstill identification
(need run command within 20 s to activate)
Voltage drop over motor windings as % of U
nominal current.
0 = Disabled 1 = Enabled, Standard
mode 2 = Enable d, Shock load mode
0 = Disable 1 = Enable
NOTE! These parameters are shown, when P17.2 = 0.
8.3

Start / stop setup (Control panel: Menu PAR -> P2)

Code Para meter Min Max Unit Default ID Note
Remote Control
P2.1
Place 1 Selection
Start function
Stop function
I
/ O Start / Stop
4
P2.
P2.
P2.6
Table 8.3: Start / stop setup
logic
5 Lo
cal / Remote 0 1 0 211
Ke
ypad control
ectio
dir
0
1 0 172
0
1 0 505
0
1 0 506
0 3 2 300
0 1 0 123
n
0 = I / O terminals 1 = Fieldbus
0 = Ramp 1 = Flying start
0 = Coasting 1 = Ramp
I / O control I / O control signal 1 signal 2
orward Backward
0 F 1 Fwd (edge ) Inve rted S top 2 Fwd(edge) Bwd(edge) 3 Start Reverse
Remote control
0 = 1 = Local control
Forward
0 = 1 = Backward
nmot
at
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
54 vacon parameters
P3.1
P3.2
i
iiiiiii
i

8.4 Frequency references (Control panel: Menu PAR -> P3)

Code Parameter Min Max Unit Default ID Note
Min frequency 0,00 P3.2 Hz 0,00 101
Max frequency P3.1 320,00 Hz
Remote Control
Place 1 fre-
P3.3
quency refer-
ence selection
P3.4 Preset speed 0 P3.1 P3.2 Hz 5,00 124 Activated by digital inputs P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105 Activated by digital inputs P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106 Activated by digital inputs P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126 Activated by digital inputs P3.8 Preset speed 4 P3.1 P3.2 Hz 25,00 127 Activated by digital inputs
P3.9 Preset speed 5 P3.1 P3.2 Hz 30,00 128 Activated by digital inputs P3.10 Preset speed 6 P3.1 P3.2 Hz 40,00 129 Activated by digital inputs P3.11 Preset speed 7 P3.1 P3.2 Hz 50,00 130 Activated by digital inputs
Table 8.4: Frequency references
NOTE! These parameters are shown, when P17.2 = 0.
16 4117
50,00 /
60,00
102
1 = Preset Speeds 0 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = PI
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 55
iiiiiiiii
i
P4.1
P4.2
P4.3
P4.4
P4.5
P4.6
P4.7
P4.8
P4.9
P4.10
P4.11
P4.12

8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)

Code Parameter Min Max Unit Default ID Note
Ramp S-shape 0,0 10,0 s 0,0 500
Acceleration time 1 0,1 3000,0 s 3,0 103
Deceleration time 1 0,1 3000,0 s 3,0 104
Ramp S-shape 2 0,0 10,0 s 0,0 501
Acceleration time 2 0,1 3000,0 s 10,0 502
Deceleration time 2 0,1 3000,0 s 10,0 503
Flux Braking 0 3 0 520
0,5 x
Flux Braking Cur-
rent
DC Braking Current
Stop DC current
time
Stop DC current
frequency
Start DC current
time
Table 8.5: Ramps and brakes setup
2,0 x
I
Nunit
2,0 x
I
Nunit
A
A
I
Nunit
0,3 x
I
Nunit
0,00 600,00 s 0,00 508
0,10 10,00 Hz 1,50 515
0,00 600,00 s 0,00 516 0 = Not active
I
Nunit
I
Nunit
0 = Linear >0 = S-curve ramp time
0 = Off 1 = Deceleration 2 = Chopper 3 = Full Mode
519
Defines the current injected into the motor
507
during DC brakeing.
Determines if braking is ON or OFF and the brak­ing time of the DC-brake when the motor is stop­ping. 0 = Not active
The output frequency at which the DC-braking is applied.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
56 vacon parameters
iii
i
i
i
i
i

8.6 Digital inputs (Control panel: Menu PAR -> P5)

Code Parameter Min Max Unit Default ID Note
0 = Not used 1 = DI1
I / O control signal 1 0 6 1 403
P5.1
P5.2 I / O control signal 2 0 6 2 404 As parameter 5.1 P5.3 Reverse 0 6 0 412 As parameter 5.1 P5.4 Ext. fault Close 0 6 6 405 As parameter 5.1 P5.5 Ext. fault Open 0 6 0 406 As parameter 5.1 P5.6 Fault reset 0 6 3 414 As parameter 5.1 P5.7 Run enable 0 6 0 407 As parameter 5.1 P5.8 Preset speed B0 0 6 4 419 As parameter 5.1 P5.9 Preset speed B1 0 6 5 420 As parameter 5.1
P5.10 Preset speed B2 0 6 0 421 As parameter 5.1
Ramp time 2 selec-
P5.11
P5.12 Disable PI 0 6 0 1020 As parameter 5.1 P5.13 Force to I/O 0 6 0 409 As parameter 5.1
Table 8.6: Digital inputs
tion
0 6 0 408 As parameter 5.1
2 = DI2 3 = DI3 4 = DI4 5 = DI5 6 = DI6

8.7 Analogue inputs (Control panel: Menu PAR -> P6)

Code Parame ter Min Max Unit Default ID Note
AI1 Signal range 0 1 0 379
P6.1
-100,00
P6.2 AI1 Custom min P6.3 AI1 Custom max P6.4 AI1 filter time 0,0 10,0 s 0,1 378 0 = no filtering
P6.5 AI2 signal range 0 1 0 390
P6.6 AI2 Custom min P6.7 AI2 Custom max P6.8 AI2 filter time 0,0 10,0 s 0,1 389 0 = no filtering
Table 8.7: Analogue inputs
100,00 % 0,00 380 0,00 = no min scaling
-100,00
300,00 % 100,00 381 100,00 = no max scaling
-100,00
100,00 % 0,00 391 0,00 = no min scaling
-100,00
300,00 % 100,00 392 100,00 = no max scaling
0 = 0 - 100% ( 0 - 10 V) 1 = 20% - 100% ( 2 - 10 V)
0 = 0 - 100% ( 0 - 20 mA) 1 = 20% - 100% (4 -20 mA)
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 57
i
i
iii

8.8 Digital outputs (Control panel: Menu PAR -> P8)

Code Parameter Min Max Unit Default ID Selections
0 = Not used 1 = Ready 2 = Run 3 = Fault
RO1 signal
P8.1
selection
RO2 signal sel-
P8.2
cetion
DO1 signal sel-
P8.3
cetion
P8.4 RO2 inversion 0 1 0 489
Table 8.8: Digital outputs
0 11 2 313
0 11 3 314 As parameter 8.1
0 11 1 312 As parameter 8.1
4 = Fault Inverted 5 = Warning 6 = Reversed 7 = At Speed 8 = Motor regula tor active 9 = FB C ontrol Wo rd.B13 10 = FB C ontrol Wo rd.B14 11 = FB C ontrol Wo rd.B15
0 = No inversion 1 = Inverted

8.9 Analogue outputs (Control panel: Menu PAR -> P9)

Code Parameter Min Max Unit Default ID Selections
0 = Not used
Analog output
P9.1
signal selection
Analog output
P9.2
minimum
Table 8.9: Analogue output s
0 4 1 307
0 1 0 310
1 = Output freq. (0-f 2 = Output current (0-I 3 = Motor torque (0-T 4 = PI output (0 - 100%)
0 = 0 mA 1 = 4 mA
max
)
nMotor
nMotor
)
)
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
58 vacon parameters
P13.2
P13.3
P13.4
i
iiiii
P13.5
P13.6
P13.7
P13.8
P13.9
P13.10
P14.1
P14.2
i
i
P14.3
P14.5

8.10 Protections (Control panel: Menu PAR -> P13)

Code Param eter Min Max Unit Default ID Note
Analog Input low
P13.1
Table 8.10: Protections
fault
Under voltage
fault
Earth fault
Output Phase
Faul t
Stall protection
Under load pro-
tection
Motor thermal
protection
Mtp:Ambient temperature
Mtp:Zero speed
cooling
Mtp:Thermal time
constant
0 2 1 700
1 2 2 727
0
2 2 703 As parameter 13.1
0
2 2 702 As parameter 13.1
0
2 0 709 As parameter 13.1
0
2 0 713 As parameter 13.1
0
2 2 704 As parameter 13.1
-20
100
0,0
150,0 % 40,0 706 Cooling as % at 0 speed
1
200 min 45 707
40 705
°C
0 = No action 1 = Alarm 2 = Fault: Coast
1 = No response (no fault
generated but drive still stops modulation) 2 = Faul t:Coa st
Environment tempera­tion
Motor thermal time con­stant
NOTE! These parameters are shown, when P17.2 = 0.

8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14)

Code Paramete r Min Max Unit Default ID Note
Automatic Reset 0 1 0 731
Wait time 0,10 10,00 s 0,50 717 Waiting time after fault
Trial time 0,00 60,00 s 30,00 718 Maximum time for trials
Restart Function 0 2 2 719
Table 8.11: Fault autoreset parameters
0 = Disabled 1 = Enable
0 = Ramping 1 = Flying 2 = From Start Function
NOTE! These parameters are shown, when P17.2 = 0.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 59
i
i
i
i
i
P17.1
8.12

PI control parameters (Control panel: Menu PAR -> P15)

Code Parameter Min Max Unit Default ID Note
Setpoint selec-
P15.1
P15.2 Fixed setpoint 0,0 100,0 % 50,0 167 Fixed setpoint
P15.4
P15.5
P15.6
P15.7 P gain 0,0 1000,0 % 10,00 118 Proportional gain P15.8 I time 0,00 320,00 s 10,00 119 Integ rative time
P15.10 Error inversion 0 1 0 340
Table 8.12: PI control parameters
tion
Feedback value
le
se
Feedback value
minumum
Feedback value
maximum
0 3 0 332
0 2 1 334
ction
0,0 50,0 % 0,0 336 Value at minimum signal
10,0 300,0 % 100,0 337 Value at maximum signal
NOTE! These parameters are shown, when P17.2 = 0.

8.13 Application Setting (Control panel: Menu PAR -> P17)

0 = Fixed setpoint % 1 = AI1 2 = AI2 3 = Fiel-bus (ProcessDataIn1)
0 = AI1 1 = AI2 2 = Field-bus (Process-
)
n2
DataI
irect (Feedback < Set-
0 = D po
int ->Increase PID out-
put)
nverted (Feedback >
1 = I Se
tpoint ->Decrease PID
output)
Code Parameter Min Max Unit Default ID Note
0 = Basic 1 = Pump
Application Type 0 3 0 540
Parameter
P17.2
conceal
Table 8.13: Application Setting parameters
0 1 1 115
2 = Fan dr ive 3 = High Torque NOTE! Visible only when
Startup wizard is active.
0 = All parameters visible 1 = Only quick setup
parameter group visible
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
60 vacon parameters

8.14 System parameters

Code Parameter Min Max Default ID Note
V1.1 API SW ID 2314
V1.2 API SW version 835
V1.3 Power SW ID 2315
V1.4 Power SW version 834
V1.5 Application ID 837
V1.6 Application revision 838
V1.7 System load 839
When Modbus and no Option board has been installed the comm. Parameters are as follows
V2.1 Communication status 808
P2.2 Fieldbus protocol 0 1 0 809
P2.3 Slave address 1 255 1 810
P2.4 Baud rate 0 8 5 811
P2.7 Communication time out 0 255 0 814
Reset communication
P2.8
Table 8.14: System parameters
Software information (MENU PAR -> V1)
status
0 1 0 815
Status of Modbus communication. Format: xx.yyy where xx = 0 - 64 (Number of error messages) yyy = 0 ­999 (Number of good messages)
0 = Not used 1 = Modbus used
0 = 300 1 = 600 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200 7 = 38400 8 = 57800
0 = Not used 1 = 1 sec 2 = 2 secs, etc
8
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameters vacon 61
Code Paramete r Min Max De fault ID Note
V3.1 MW h counter 827 Million Watt Hour V3.2 Power on days 828 V3.3 Power on hours 829
V3.4 Run counter: Days 840 V3.5 Run counter: Hours 841
V3.6 Fault counter 842
Panel parameter set sta-
V3.7
P4.2
F5.x Active Fault menu
F6.x Fault History menu
Table 8.14: System parameters
tus monitor
Restore factory defaults 010 831
Other informati on
1 = Restores factory
defaults for all param­eters
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
62 vacon parameter descriptions

9. PARAMETER DESCRIPTIONS

On the next pages you can find the descriptions of certain parameters. The descrip­tions have been arranged according to parameter group and number.

9.1 Motor settings (Control panel: Menu PAR -> P1)

1.7 CURRENT LIMIT

This parameter determines the maximum motor current from the frequency converter. To avoid motor overload, set this parameter according to the rated current of the motor. The current limit is equal to the rated converter current (In) by default.

1.8 MOTOR CONTROL MODE

With this parameter the user can select the motor control mode. The selec­tions are:
0 = Frequency control: Drive frequency reference is set to output frequency without s lip com-
pensation. Motor actual speed is finally defined by motor load.
1 = Open loop speed control: Drive frequency reference is set to motor speed reference. The motor
speed remains the same regardless of motor load. Slip is compensat­ed.

1.9 U / F RATIO

There are three selections for this parameter:
0 = Linear:
The voltage of the motor changes linearly with the frequency in the constant flux area from 0 Hz to the field weakening point where the field weakening point voltage is supplied to the motor. Linear U / f ratio should be used in constant torque applications. See Figure 9.1.
This default setting should be used if there is no special need for an­other setting.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
U[V]
f[Hz]
Un
Par. 1.11
Par. 1.14
Par. 1.10
Default: Nominal voltage of the m otor
Linear
Squared
Field weakening point
Default: Nominal frequency of t he motor
parameter descriptions vacon 63
1 = Quadratic:
The voltage of the motor changes following a squared curve form with the frequency in the area from 0 Hz to the field weakening poin t where the field weakening point voltage is also supplied to the motor. The motor runs under magnetised below the field weakening point and produces less torque, power losses and electromechanical noise. Squared U / f ratio can be used in applications where torque demand of the load is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
Figure 9.1: Linear and squared change of motor voltage
2 = Programmable U / f curve:
The U / f curve can be programmed with three different points. Pro­grammable U / f curve can be used if the other settings do not satisfy the needs of the application.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
Un
Par. 1.11
U[V]
f[Hz]
Par. 1.13
(Def. 50%)
Par. 1.14
(Def. 0.0%)
Default: Nominal voltage of the m otor
Field weakening point
Default: Nominal frequency of t he motor
Par. 1.12 (Def. 10%) Pa r. 1.10
64 vacon parameter descriptions
Figure 9.2: Programmable U / f curve

1.10 FIE LD WEAKENING POINT

The field weakening point is the output frequency at which the output voltage reaches the value set with par. 1.11.

1.11 FIE LD WEAKENING POINT VOLTAGE

Above the frequency at the field weakening point, the output voltage remains at the value set with this parameter. Below the frequency at the field weaken­ing point, the output voltage depends on the setting of the U / f curve param­eters. See parameters 1.9-1.14 and Figures 9.1 and 9.2.
When the parameters 1.1 and 1.2 (nominal voltage and nominal frequency of the motor) are set, the parameters 1.10 and 1.11 are automatically given the corresponding values. If you need different values for the field weakening point and the voltage, change these parameters after setting the parameters
1.1 and 1.2.

1.12 U / F MIDDLE POINT FREQUENCY

If the programmable U / f curve has been selected with the parameter 1.9, this parameter defines the middle point frequency of the curve. See Figure 9.2.

1.13 U / F MIDDLE POINT VOLTAGE

If the programmable U / f curve has been selected with the parameter 1.9, this parameter defines the middle point voltage of the curve. See Figure 9.2.

1.14 ZERO FREQUENCY VOLTAGE

This parameter defines the zero frequency voltage of the curve. See Figures
9.1 and 9.2.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 65

1.15 TORQUE BOOST

When this parameter has been activated, the voltage to the motor changes au­tomatically with high load torque which makes the motor produce sufficient torque to start and run at low frequencies. The voltage increase depends on the motor type and power. Automatic torque boost can be used in applications with high load torque, e.g. in conveyors.
0 = Disabled 1 = Enabled
Note: In high torque - low speed applications - it is likely that the motor will
overheat. If the motor has to run a prolonged time under these conditions, special attention must be paid to cooling the motor. Use external cooling for the motor if the temperature tends to rise too high.
Note: The best performance can be reached by running motor identification, see par. 1.18.

1.16 SWI TCHING FREQUENCY

Motor noise can be minimised using a high switching frequency. Increasing the switching frequency reduces the capacity of the frequency converter unit.
Switching frequency for Vacon 10: 1.5…16 kHz.

1.17 BRAKE CHOPPER

Note! An internal brake chopper is installed in three phase supply MI2 and MI3 size drives.
0 = Disable (No brake chopper used) 1 = Enable: Always (Used in Run and Stop state) 2 = Enable: Run state (Brake chopper used in Run state)
When the frequency converter is decelerating the motor, the energy stored to the in­ertia of the motor and the load are fed into an external brake resistor, if the brake chopper has been activated. This enables the frequency converter to decelerate the load with a torque equal to that of acceleration (provided that the correct brake re­sistor has been selected). See separate Brake resistor installation manual.

1.18 MOTOR IDENTIFICATION

0 = Not active 1 = Standstill identification
When Standstill identification is selected, the drive will perform an ID-run when it is started from selected control place. Drive has to be started within 20 seconds, otherwise identification is aborted.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
66 vacon parameter descriptions
The drive does not rotate the motor during Standstill identification. When ID run is ready the drive is stopped. Drive will start normally, when the next start command is given.
After end the identification, the drive need stop the start command. If control place is Keypad, user need press stop button. If control place is IO,user need put DI(Control signal) inactivate. If control place is fieldbus, user need set the control bit to 0.
The ID run improves the torque calculations and the automatic torque boost function. It will also result in a better slip compensation in speed control (more accurate RPM).
The parameters below will change after ID run successfully,
a. P1.9 U / f ratio
b. P1.12 U / f mid point frequency
c. P1.13 U / f mid point voltage
d. P1.14 Zero freq voltage
e. P1.18 Motor identification (1->0)
f. P1.19 Rs voltage drop
Note!The nameplate data of the motor has to be set BEFORE doing ID run.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 67

9.2 Start / stop setup (Control panel: Menu PAR -> P2)

2.1 REMOTE CONTROL PLACE 1 SELECTION

With this parameter, the user can select the active control place. The selec­tions are:
0 = I / O terminal (frequency reference can be selected with P3.3) 1 = Fieldbus
The priority order of selecting the control place is:
1. Force to I/O when the digital input of P5.13 (Force to I/O) is active.
2. Loc/Rem button or P2.5 (Local/Remote) =1.
3. Determined by P2.1 (Remote Control Place Selection).
Note: You can select control place by pressing Loc / Rem button or with par.
2.5, P2.1 will have no effect in local mode.
Local = Keypad is the control place Remote = I / O terminal or FieldBus

2.2 START FUNCTION

The user can select two start functions for Vacon 10 with this parameter:
0 = Ramp start
The frequency converter starts from 0 Hz and accelerates to the set frequency reference within the set acceleration time (See detailed de­scription: ID103). (Load inertia, torque or starting friction may cause prolonged acceleration times).
1 = Flying start
With this function the drive identifies the speed of the motor and starts to the corresponding frequency immediately.
Use this mode if the motor is rotating when the start command is giv­en. With the flying start, it is possible to ri de through short mains volt­age interruptions.

2.3 STOP FUNCTION

Two stop functions can be selected in this application:
0 = Coasting
The motor coasts to a halt without control from the frequency convert­er after the Stop command.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
68 vacon parameter descriptions
1 = Ramping
After the Stop command, the speed of the motor is decelerated ac­cording to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an exter­nal braking resistor for to be able to decelerate the motor in accepta­ble time.

2.4 I / O START STOP LOGIC

Values 0...3 offer possibilities to control the starting and stopping of the AC drive with digital signal connected to digital inputs. CS = Control signal.
The selections including the text 'edge' shall be used to exclude the possibility of an unintentional start when, for example, power is connected, re-connected after a power failure, after a fault reset, after the drive is stopped by Run En­able (Run Enable = False) or when the control place is changed to I / O control.
The Start / Stop contact must be opened before the motor can be started.
Accurate stop mode is that the stop time is fixed from falling edge of DI to mo­tor stop.
Selection
Selection name Note
number
CS1:Forward
0
CS2:Backward
Output
FWD
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start butt on
Keypad
stop button
1 2 3 4 5 6 7 8 9
The functions take place when the contacts are closed.
Figure 9.3: Start/Stop logic, selection 0
t
10 11 12 13
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 69
Explanations 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 activates which, however, has no
effect on the output frequency because the first selected direction has the high­est priority.
3 CS1 is inactivated which caused the
direction to start changing (FWD to REV) because CS2 is still active.
4 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
5 CS2 actives again causing the motor to
accelerate (REV) towards the set fre­quency.
6 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
7 CS1 actives and the motor accelerates
(FWD) towards the set frequency.
8 Run enable signal is set to FALSE, which
drops the frequency to 0.The run enable signal is configured with par. 5.7.
9 Run enable signal is set to TRUE, wh ich
causes the frequency to rise towards the set frequency because CS1 is still active.
10 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
11 The drive starts through pushing the
Start button on the keypad.
12 The keypad stop button is pushed again
to stop the drive.
13 The attempt to start the drive through
pushing the Start button is not success­ful because CS1 is inactive.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
70 vacon parameter descriptions
Selection
number
Selection name Note
CS1:Forward(edge)
1
CS2:Inverted stop
Output
FWD
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
stop button
1 2 3 4 5 6 7 8 9
Figure 9.4: Start/Stop logic, selection 1
Explanations 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 inactivates causing the frequency to
drop to 0.
3 CS1 inactivates causing the output fre-
quency to rise again. The motor runs forward.
4 Run enable signal is set to FALSE, which
drops the frequency to 0. The run enable signal is configured with par. 5.7.
5 Start attempt with CS1 is not successful
because Run enable signal is still FAL SE.
t
6 CS1 ac tivates and the motor accelerates
(FWD) towards the set frequency because the Run enable signal has been set to TRUE.
7 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
8 CS1 activates causing the output fre-
quency to rise again. The motor runs forward.
9 CS2 in activates causing the frequency to
drop to 0.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
FWD
REV
Set
frequency
Set
frequency
0 Hz
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
stop button
1 2 3 5 6 7 8 9
10 11 12
Output
frequency
t
`
4
parameter descriptions vacon 71
Selection
number
2
Explanations: 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 activates which, however, has no
effect on the output frequency because the first selected direction has the high­est priority.
3 CS1 is inactivated which causes the
direction to start changing (FWD to REV) because CS2 is still active.
4 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
5 CS2 ac tivates again causing the motor to
accelerate (REV) towards the set fre­quency.
6 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Selection name Note
CS1:Forward(edge) CS2:Backward(edge)
Shall be used to exclude the possibility of an unintentional start. The Start / Stop contact must be opened before the motor can be restarted.
Figure 9.5: Start/Stop logic, selection 2
7 CS1 ac tivates and the motor accelerates
(FWD) towards the set frequency.
8 Run enable signal is set to FALSE, which
drops the frequency to 0.The run enable signal is configured with par. 5.7.
9 CS1 act ivates again causing the motor to
accelerate (REV) towards the set fre­quency.
10 CS1 activates again causing the motor to
accelerate (REV) towards the set fre­quency.
11 CS1 inactivates and the frequency fed to
the motor drops to 0.
9
72 vacon parameter descriptions
Selection
number
Selection name Note
CS1:Start
3
CS2:Reverse
Output
FWD
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start butt on
Keypad
stop button
1 2 3 4 5 6 7 8 9
Figure 9.6: Start/Stop logic, selection 3
Explanations: 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 activates which causes the direction
to start changing (FWD to REV).
3 CS2 is inactivated which causes the
direction to start changing (REV to FWD) because CS1 is still active.
4 Also CS1 inactivates and the frequency
drops to 0.
5 Despite the activates of CS2,the motor
does not start because CS1 is inactive.
6 CS1 activates causing the output fre-
quency to rise again. The motor runs forward because CS2 is inactive.
t
10 11 12
7 R un enable signal i s set to FA LSE, whi ch
drops the frequency to 0.The run enable signal is configured with par. 5.7.
8 Run enable signal is set to TRUE, which
causes the frequency to rise towards the set frequency because CS1 is still active.
9 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
10 The drive starts through pushing the
Start button on the keypad.
11 The drive is stopped again with the Stop
button on the Keypad.
12 The attempt to start the drive through
pushing the Start button is not success­ful because CS1 is inactive.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 73

2.5 LOCAL / REMOTE

This parameter defines whether the control place of the drive is remote (I / O or FieldBus) or local.
0 = Remote Control 1 = Local Control
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
74 vacon parameter descriptions

9.3 Frequency references (Control panel: Menu PAR -> P3)

3.3 REMOTE CONTROL PLACE 1 FREQUENCY REFERENCE SELECTION

It defines the selected frequency reference source when the drive is control­led by the I / O terminal.
1 = Preset speed 0 2 = Keypad reference 3 = Fieldbus Reference 4 = AI1 5 = AI2 6 = PI

3.4 - 3.11 PRESET SPEEDS 0 - 7

Preset speeds 0 - 7 can be used to determine frequency references that are applied when appropriate combinations of digital inputs are activated. Preset speeds can be activated from digital inputs inputs when Par.3.3 (Remote con­trol place frequency reference selection) =1.
Parameter values are automatically limited between the minimum and maxi­mum frequencies. (par. 3.1, 3.2).
Speed
Preset speed 0 Preset speed 1 x Preset speed 2 x Preset speed 3 x x Preset speed 4 x Preset speed 5 x x Preset speed 6 x x Preset speed 7 x x x
Table 9.1: Preset speeds 0 - 7
Preset
speed B2
Preset
speed B1
Preset
speed B0
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
P4.2, 4.3
[Hz]
[t]
P4.1
P4.1
parameter descriptions vacon 75

9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)

4.1 RAMP S-SHAPE

The start and end of the acceleration and deceleration ramp can be smoothed with this parameter. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the refer­ence signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped accel­eration/deceleration. The acceleration and deceleration times are determined with parameters 4.2 and 4.3.
Figure 9.7: S-shaped acceleration/deceleration
4.2 ACCELERAT ION TIME 1
4.3 DECELERATION TIME 1
4.4 RAMP S-SHAPE 2
4.5 ACCELERATIO N TIME 2
4.6 DECELERATION TIME 2
These limits correspond to the time required for the output frequency to ac­celerate from the zero frequency to the set maximum frequency, or to decel­erate from the set maximum frequency to zero frequency.
The user can set two different acceleration/deceleration time and set two dif­ferent ramp s-shape for one application.The active set can be selected with the selected digital input (par. 5.11).

4.7 FLUX BRAKING

Instead of DC braking, flux braking is a useful form of braking with motors of max. 15 kW.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
76 vacon parameter descriptions
When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains controlled during braking.
0 = Off 1 = Deceleration 2 = Chopper 3 = Full Mode
Note: Flux braking converts the energy into heat at the motor, and should be
used intermittently to avoid motor damage.

4.10 STO P DC CURRENT TIME

Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping. The function of the DC-brake depends on the stop function, par. 2.3.
0 = DC brake is not active >0 = DC brake is active and its function depends on the Stop function,
(par. 2.3). The DC braking time is determined with this parameter.
Par. 2.3 = 0 (Stop function = Coasting):
After the stop command, the motor coasts to a stop without control from the frequency converter.
With the DC injection, the motor can be electrically stopped in the shortest possible time, without using an optional external braking resistor.
The braking time is scaled by the frequency when the DC-braking starts. If the frequency is greater, or equal to the nominal frequency of the motor, the set value of parameter 4.10 determines the braking time. For example, when the frequency is 10% of the nominal, the braking time is 10% of the set value of parameter 4.10.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
f
n
f
n
t
t
t=1xpar. 4.10
t=0,1x par.4.10
0,1 x f
n
RUN
STOP
RUN
STOP
Outputf requency
Motorspeed
Output frequency
Motor speed
DC-brakingO N
DC-braking ON
f
out
f
out
t=par.4.
t
Par. 4.1
Motorspeed
Output frequ
ency
DC- brak in g
RUN STOP
f
out
1
10
parameter descriptions vacon 77
Figure 9.8: DC-braking time when Stop mode = Coasting
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the set deceleration parameters, if the inertia of the motor and load allows that, to the speed defined with parameter 4.11, where the DC-braking starts.
The braking time is defined with parameter 4.10. See Figure 9.9.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Figure 9.9: DC-braking time when Stop mode = Ramp
9
78 vacon parameter descriptions
t
Pa r4.12
Par 4.9
RUN STO P
Output frequency
DC-bra king current

4.11 STO P DC CURRENT FREQUENCY

It is the output frequency at which the DC-braking is applied.

4.12 STAR T DC CURRENT TIME

DC-brake is activated when the start command is given. This parameter de­fines the time of the DC-braking. After the brake is released, the output fre­quency increases according to the set start function by par. 2.2.
Figure 9.10: DC braking time at start
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 79

9.5 Digital inputs (Control panel: Menu PAR -> P5)

These parameters are programmed using the FTT-method (Function To Ter­minal), where you have a fixed input or output that you define a certain func­tion for. You can also define more than one function to a digital input, e.g. Start
al 1 and Preset Speed B1 to DI1.
sign
The selections for these parameters are:
0 = Not used 1 = DI1 2 = DI2 3 = DI3 4 = DI4 5 = DI5
6 = DI6

5.1 I / O CTRL SIGNAL 1

5.2 I / O CTRL SIGNAL 2

5.3 REVERSE

The digital input only active when P2.4 (I/O Start stop logic) =1
The motor will run in reverse when the rising edge of P5.3 is happened.
5.4 EXTERNAL FAULT CLOSE
5.5 EXTERNAL FAULT OPEN
5.6 FAULT RESET
5.7 RUN ENABLE
5.8 PRESET SPEED B0
5.9 PRESET SPEED B1
5.10 PRESET SPEED B2
5.11 RAMP TI ME 2 SELECTION
Contact open: Acceleration / Deceleration time 1 and Ramp S-shape selected Contact closed: Acceleration / Deceleration time 2 and Ramp S-shape2 selected
Set Acceleration / Deceleration times with parameters 4.2 and 4.3 and the al­ternative ramp times with 4.4 and 4.5.
Set Ramp S-shape with Par. 4.1 and the alternative Ramp S-shape2 with Par. 4.4
  
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
80 vacon parameter descriptions
%
100%
63%
Par. 6 .4 Par. 6 .8
t[s]
Filtered signal
Unfiltered signal

9.6 Analogue inputs (Control panel: Menu PAR -> P6)

6.4 AI1 FILTER TIME
6.8 AI2 FILTER TIME
This parameter, given a value greater than 0, activates the function that filters out disturbances from the incoming analogue signal.
Long filtering time makes the regulation response slower. See
6.2 AI1 CUSTOM MINI MUM
6.3 AI1 CUSTOM MAXI MUM
6.6 AI2 CUSTOM MINI MUM
6.7 AI2 CUSTOM MAXI MUM
These parameters set the analogue input signal for any input signal span from
-100 to 100%.
Figure 9.11: AI1 and AI2 signal filtering
Figure 9.11.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 81

9.7 Digital outputs (Control panel: Menu PAR -> P8)

8.1 RO1 SIGNAL SELECTION
8.2 RO2 SIGNAL SELCETION
8.3 DO1 SIGNAL SELCETION
Setting Signal content
0 = Not used 1 = Ready The frequency converter is ready to operate. 2 = Run 3 = Faul t A fault trip has occurred. 4 = Faul t inver ted 5 = Warn ing A warning is active.
6 = Reversed
7 = At speed The output frequency has reached the set reference.
8 = Motor regulator active
9 = FB Con trol Word.B13
10 = FB C ontrol Word.B 14
11 = FB C ontrol Word.B 15
Table 9.2: Output signals via RO1, RO2 and DO1
 
Output is not in operation.
The frequency converter operates (motor is running).
A fault trip has not occurred.
everse command has been selected, output fre-
The r
quency to the motor is negative.
Each of motoring current regulator,generating current
reg. ,over voltage reg. ,under voltage reg. is active.
Output can be controlled with B13 in the fie ldbus control
Output can be controlled with B14 in the fie ldbus control
Output can be controlled with B15 in the fie ldbus control
word.
word.
word.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
82 vacon parameter descriptions

9.8 Analogue outputs (Control panel: Menu PAR -> P9)

9.1 ANALOG OUTPUT SIGNAL SELECTION

9.2 ANALOG OUTPUT MINIMUM

0 = Not used 1 = Output frequency (0 - f 2 = Output current (0 - I 3 = Motor torque (0 - T 4 = PID output (0 - 100%)
0 = 0 mA 1 = 4 mA
nMotor
max
nMotor
) )
)
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 83
f
I
Inmotor *1.3
25Hz
Stall ar ea

9.9 Protections (Control panel:Menu Par->P13)

13.5 STA LL PROTECTION

13.6 UNDER LOAD PROTECTION

0 = No action 1 = Alarm
2 = Fault, coast
The motor stall protection protects the motor from short time overload situa­tions such as one caused by a stalled shaft. The stall current is I stall time 15 seconds and stall frequency limit 25 Hz . If the current is higher than the limit and output frequency is lower than the limit, the stall state is true and the drive reacts according to this parameter. There is actually no real indication of the shaft rotation.
Figure 9.12: Stall characteristics
nMotor
0 = No action 1 = Alarm 2 = Fault, coast
The purpose of the motor underload protection is to ensure that there is load on the motor when the drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken belt or a dry pump.
The underload protection time limit is 20 seconds, which is the maximum time allowed for an underload state to exist before causing a trip according to this parameter.
*1.3,
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
Underload curve at zero freq. = 10%
f
5 Hz
Underl oad curve a t nominal freq. = 50 %
Field we akening point, P1.11
Underload area
To rq ue
84 vacon parameter descriptions
Figure 9.13: Underload protection

13.7 MOTOR THERM AL PROTECTION

The motor thermal protection is to protect the motor from overheating. The drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is equipped with an external fan the load reduction at low speeds is small. The motor thermal protection is based on a calculated model and it uses the output current of the drive to determine the load on the motor. The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the load current above which the motor is overloaded. This current limit is a function of the output frequency.
0 = No action 1 = Alarm 2 = Fault, coast
If tripping is selected the drive will stop and activate the fa ult stage, if the tem­perature of the motor becomes too high. Deactivating the protection, i.e. set­ting parameter to 0, will reset the thermal model of the motor to 0%.
CAUTION! The calculated model does not protect the motor if the airflow to the motor is reduced by blocked air intake grill.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 85
f
f
n
par. = 40%
0
I
100%
Overload area
cooling
.913

13.8 MTP:AMBIENT TEMPERATURE

When the motor ambient temperature must be taken into consideration, it is recommended to set a value for this parameter. The value can be set between
-20 and 100 degrees Celsius.

13.9 MTP:ZERO SPEED COOLING

The cooling power can be set between 0 - 150.0% x cooling power at nominal frequency. See Figure 9.14.
P
T
Figure 9.14: Motor cooling power

13.10 MTP:THERMAL TIME CONSTANT

This time can be set between 1 and 200 minutes.
This is the thermal time constant of the motor. The bigger the motor, the long­er the time constants. The time constant is the time within which the calculat­ed thermal model has reached 63% of its final value.
The motor thermal time is specific to the motor design and it varies between different motor manufacturers.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate at six times the rated current) is known (given by the motor manufacturer) the time constant parameter can be set basing on it. As a rule of thumb, the motor thermal time constant in minutes equals to 2 x t6. If the drive is in stop state the time constant is internally increased to three times the set parameter val­ue. See also Figure 9.15.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
86 vacon parameter descriptions
Mot or t empera ture
105%
Moto r current
I/I
T
Tri p ar ea
Time cons tant T
Motor te mperat ure
*)
Changesby motor size and adjusted with parameter
*)
Q=(I/IT)2x(1-e
Figure 9.15: Motor temperature calculation
-t/T )
.1013
/warning
Fault activ ation point,
with
if selec ted par.
.713
Time
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 87
Fault t rigger
Motor stop signal
Mot or
start signal
Su perv isio n
Restart 1 Restart 2
Trial time
par.14.3
Fa ul t act i ve
RESET/
Fault reset
Autoreset function: (Trials = 2)
Wait time
par.14.2
Wait t ime
par.1 4.2
Wait ti me
par.14. 2

9.10 Automatic reset (Control panel: Menu PAR -> P14)

14.1 AUT OMATIC RESET

Activate the Automatic reset after fault with this parameter.
NOTE: Automatic reset is allowed for certain faults only.
Fault: 1. Under voltage
2. Over voltage
3. Over current
4. Motor temperature
5. Under load

14.3 TRIAL TIME

The Automatic restart function restarts the frequency converter when the faults have disappeared and the waiting time has elapsed.
The time count starts from the first autoreset. If the number of faults occur­ring during the trial time exceeds three, the fault state becomes active. Oth­erwise the fault is cleared after the trial time has elapsed and the next fault starts the trial time count again. See Figure 9.16.
If a single fault remains during the trial time, a fault state is true.
Figure 9.16: Example of Automatic restarts with two restarts
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
88 vacon parameter descriptions
Analogue input

9.11 PI control parameters (Control panel: Menu PAR -> P15)

15.7 P GAIN

This paramete r defines the gain of the PI controller. If the value of the pa ram­eter is set to 100%, a change of 10% in the error value caus es the controller output to change by 10%.

15.8 I-TIME

This para meter defines the integrati on time of the PI cont roller. If this param­eter is set to 1,00 second, the controller output is changed b y a value corre ­sponding to th e output caused from the gain every second. (G ain*Error)/s.
15.5 FEEDBACK VALUE MINIMUM
15.6 FEEDBACK VALUE MAXIMUM
This parameter sets the minimum and maximum scaling points for feedback value.
Controller feedback(%)
par. 15.6
9
par. 15.5
0V
Custom min par.6.2/6.6
0mA
Figure 9.17: Feedback minimum and maximum
Cus tom max par.6.3 /6.7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
10V 20mA
with custom min and max scaling (%)
parameter descriptions vacon 89

9.12 Application setting (Control panel: Menu PAR->P17)

17.1 DRIVE SETUP

With this parameter you can easily set up your drive for four different applica­tions.
Note! This parameter is only visible when the Startup Wizard is active. The startup wizard will start in first power-up. It can also be started as follows. See the figures below.
NOTE! Running the startup wizard will always re turn all parameter
settings to their factory defaults!
RUN
REF
MON
PAR
SYS
FWD R EV I/O K EY PAD BUS
FAULTALARMSTOPREADY
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
OK
1
Enter Pa r. menu, select P1.3 motor nominal speed
REF
MON
PAR
SYS
FWD R EV I/O KEY PA D BUS
FAULTALARMSTOPREADY RUN
2
Press OK ent er edit mode
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
OK
P1.3
Change
3
with Up/Down button and press OK to comfirm
value
Perform the same
4
procedure for P1.4, motor nomi nal current
Figure 9.18: Startup wizard
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
FAULTALARMSTOPREADY RUN
rpm
FAULTALARMSTOPREADY RUN
A
9
90 vacon parameter descriptions
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
FWD REV I/O KEYPAD
Startup wizard
1
showns par 17.1 number.
Selections:
P1.1 P1.2 P1.7 P1.8 P1.15 P2.1 P2.2 P2.3 P3.1 P3.2 P3.3 P4.2 P4.3
50/60
0 = Basic
1 = Pump drive
2 = Fan drive
3 = High Torque drive
V*
Hz
50/60
V*
Hz
50/60
V*
Hz
50/60
V*
Hz
*Same as drive voltage, except in 115V drives this value is 230V
Parameters affected:
Figure 9.19: Drive setup
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
BUS FWD REV I/O KEYPAD
OK
Press OK to enter
2
edit mode.
0=
0=
1,5 x
I
1,1 x
I
1,1 x
I
1,5 x
I
NMOT
NMOT
NMOT
NMOT
Not
Frequecny
used
control
0=
0=
Not
Frequecny
used
control
0=
0=
Not
Frequecny control
used
1=Open
1=
loop speed
used
ontrol
P1.1 Motor Un (V) P1.2 Motor fn (Hz) P1.7 Current limit (A) P1.8 Motor control mode P1.15 Torque boost P2.1 Control place P2.2 Start function
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
I/O
I/O
I/O
I/O
OK
Press OK to
4
confirm drive setup
REF
MON
PAR
SYS
BUS FWD
0=
0=
0 Hz
Ramp
Coast
0=
20 Hz
Ramp1=Ramp
1=
0=
20 Hz
Flying
Coast
0=
0=
0 Hz
Ramp
Coast
P2.3 Stop function P3.1 Min frequency P3.2 Max frequency P3.3 I/O reference P4.2 Acc. time (s) P4.3 Dec time (s)
READY RUN STOP ALARM FAULT
REV I/O KEYPAD BUS
Select between
3
0-3, see below!
50/60
4=AI1
3s 3s
Hz
0-10V
50/60
4=AI1
5s 5s
Hz
0-10V
4=AI1
50/60 Hz
50/60 Hz
0-10V
4=AI1 0-10V
20s20s
1s 1s
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 91
ON
OFF

9.13 Modbus RTU

Vacon 10 has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with the RS-485 standard. The built-in Modbus connection of Vacon 10 supports the following function codes:
Funct ion code
Table 9.3: Modbus RTU

9.13.1 Termination resistor

The RS-485 bus is terminated with termination resistors of 120 ohms in both ends. Vacon 10 has a built-in termination resistor which is switched off as a default (pre­sented below). The termination resistor can be switched on and off with the right hand dip switch located above IO-terminals in the front of the drive (see below).

9.13.2 Modbus address area

The Modbus interface of Vacon 10 uses the ID numbers of the application parameters as addresses. The ID numbers can be found in the parameter tables in chapter 8. When several parameters / monitoring values are read at a time, they must be con­secutive. 11 addresses can be read and the addresses can be parameters or moni­toring values.
Function name Address
03 Read Holding Registers Al l ID numbers No 04 Read Input Registers All ID numbers No 06 Write Single Registers All ID numbers Yes 16 Write multiple registers All ID numbers Yes
Figure 9.20: Vacon 10 I/O
Broadcast messages
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
92 vacon parameter descriptions

9.13.3 Modbus process data

Process data is an address area for fieldbus control. Fieldbus control is active when the value of parameter 2.1 (Control place) is 3 (= fieldbus). The content of the process data has been determined in the application. The following tables present the proc­ess data contents in the General Purpose Application.
ID Modbus register Name Scale Ty pe
2101 32101, 42101 FB Status Word - Binary coded 2102 32102, 42102 FB General Status Word - Binary coded 2103 32103, 42103 FB Actual Speed 0,01 % 2104 32104, 42104 Output frequency 0.01 +/- Hz 2105 32105, 42105 Motor speed 1 +/- Rpm 2106 32106, 42106 Motor current 0.01 A
2107 32107, 42107 Motor torque 0,1
2108 32108, 42108 Motor power 0,1
2109 32109, 42109 Motor voltage 0,1 V 2110 32110, 42110 DC link voltage 1 V 2111 32111, 42111 Active fault code 1 -
Table 9.4: Output process data
ID Modbus register Name Scale Type
2001 32001, 42001 FB Control Word - Binary coded 2002 32002, 42002 FB General Control Word - Binary coded 2003 32003, 42003 FB Speed Reference 0,01 % 2004 32004, 42004 Programmable by P15.1 2005 32005, 42005 Programmable by P15.4 2006 32006, 42006 - - ­2007 32007, 42007 - - ­2008 32008, 42008 - - ­2009 32009, 42009 - - ­2010 32010, 42010 - - ­2011 32011, 42011 - - -
Table 9.5: Input process data
Note! 2004 can set as PI Control Reference by setting P15.1(Setpoint se-
lection) or 2005 can be set as PI Actual value by setti ng P15.4(Feed­back value selection)!
+/- % (of nomi­nal)
+/- % (of nomi­nal)
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 93
Status word (output process data)
Information about the status of the device and messages is indicated in the Status word. The Status word is composed of 16 bits the meanings of which are described in the table below:
Bit
B0, RDY Drive not ready Drive ready B1, RUN Stop Run B2, DIR Clockwise Counter-clockwise B3, FLT No fault Fault active B4, W No alarm Alarm active B5, AREF Ramping Speed reference reached B6, Z - Drive is running at zero speed B7 - B15 - -
Table 9.6: Status word (output process data)
Value = 0 Valu e = 1
Actual speed (output process data)
This is actual speed of the frequency converter. The scaling is -10000...10000. The value is scaled in percentage of the frequency area between set minimum and max­imum frequency.
Control word (input process data)
The three first bits of the control word are used to control the frequency converter. By using control word it is possible to control the operation of the drive. The mean­ings of the bits of control word are explained in the table below:
Bit
B0, RUN Stop Run B1, DIR Clockwise Counter-clockwise B2, RST Rising edge of this bit will reset active fault
Table 9.7: Control word (input process data)
Valu e = 0 Value = 1
Description
Description
Speed reference (input process data)
This is the Reference 1 to the frequency converter. Used normally as Speed refer­ence. The allowed scaling is 0...10000. The value is scaled in percentage of the fre­quency area between the set minimum and maximum frequencies.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
94 vacon technical data

10. TECHNICAL DATA

10.1 Vacon 10 technical data

Mains connection
Supply network
Motor connection
Control characteristics
Table 10.1: Vacon 10 technical data
Input voltage U
Input frequency 45…66 Hz Line current THD > 120% Connection to mains
Networks
Short circuit current Output voltage
Output current
Starting current /
que
tor Output frequency 0…320 Hz Frequency resolution
Control method
Switching frequency 1...16 kHz; Factory default 4 kHz Frequency reference Resolution 0.01 Hz Field weakening point 30…320 Hz Acceleration time 0.1…3000 sec Deceleration time 0.1…3000 sec
Braking torque
115 V, -15%...+10% 1~ 208…240 V, -15%...+10% 1~ 208…240 V, -15%...+10% 3~
in
380 - 480 V, -15%...+10% 3~ 575 V, -15%...+10% 3~
Once per minute or less (normal case) Vacon 10 (400 V) cannot be used with corner grounded
s
network Maximum short circuit current has to be < 50 kA. 0 - U
in
Continuous rated current I max. +50 ºC (depends on the unit size), overload
1.5 x I
max.
N
1 min / 10 min Current 2 x I depends on motor
0,01 Hz Frequency Control U / f
Open Loop Sensorless Vector Control
100%*T ) 30%*T
for 2 sec in every 20 sec period. Torque
N
with brake option (only in 3~ drives sizes MI2-5
N
without brake option
N
at ambient temperature
N
10
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
technical data vacon 95
-10 °C (no frost)…+40 / 50°C (depends on the unit size): a
ted loadability I
Ambient operating temperature
Storage temperature -40°C…+70°C
Relative humidity
Air quality:
Ambient conditions
EMC
- chemical vapours
- mech. particles
Altitude
Vibration: EN60068-2-6
Shock IEC 68-2-27
Enclosure class IP20 / IP21 / Nema1 for MI1-3. Pollution degree Immunity Complies with EN50082-1, -2, EN61800-3
Emissions
Standards
Certificates and manufac­turer’s decla­rations o f con
formity
Table 10.1: Vacon 10 technical data
r Side by side installation for MI1-3 it is always 40°C; For IP21/Nema1 option in MI1-3 the maximum temparture is also 40 °C.
0…95% RH, non-condensing, non-corrosive, no dripping
er
wat
IEC 721-3-3, unit in operation, class 3C2 IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1000 m. 1% der­ating for each 100 m above 1000 m; max. 2000 m
3...150 Hz
Displacement amplitude 1(peak) mm at 3...15.8 Hz Max
e
acc UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
PD2
230V : Complies with EMC cate gory C2; With an internal RFI fi 400V: Complies with EMC category C2; With an internal RFI fi Both: No EMC emission protection (Vacon level N): Without RFI filter
For EMC: EN61800-3, For safety: UL508C, EN61800-5
For safety: CB, CE, UL, cUL, For EMC: CE, CB, c-tick (see unit nameplate for more detailed approvals)
N
leration amplitude 1 G at 15.8...150 Hz
lter.
lter
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
10
96 vacon technical data

10.2 Power ratings

10.2.1 Vacon 10 – Mains voltage 208-240 V

Mains voltage 208-240 V, 50/60 Hz, 1~ series
Rated loadability
Freq.
converter
type
100% contin. current I
0001 1.7 2.6 0.33 0.25 4.2 MI1 0.55 0002 2.4 3.6 0.5 0.37 5.7 MI1 0.55 0003 2.8 4.2 0.75 0.55 6.6 MI1 0.55 0004 3.7 5.6 1 0.75 8.3 MI2 0.55 0005 4.8 7.2 1.5 1.1 11.2 MI2 0.7 0007 7 10.5 2 1.5 14.1 MI2 0.7
0009* 9.6 14.4 3 2.2 22.1 MI3 0.99
Table 10.2:Vacon 10 power ratings, 208-240 V
N
[ A ]
150% over­load current [ A ]
* The maximum ambient operating temperature of this drive is 40 °C!
Motor shaft power
P
[HP ]
[KW]
P
Nominal input current
[ A ]
Mechanical size
Weight (kg)
Mains voltage 208 - 240 V, 50/60 Hz, 3~ series
Rated loadability
Freq.
converter
type
100% contin. current I
0001 1.7 2.6 0.33 0.25 2.7 MI1 0.55 0002 2.4 3.6 0.5 0. 37 3.5 MI1 0.55 0003 2.8 4.2 0.75 0.55 3.8 MI1 0.55 0004 3.7 5.6 1 0.75 4.3 MI2 0. 7
0005 4.8 7.2 1.5 1.1 6.8 MI2 0.7 0007* 7 10.5 2 1.5 8.4 MI2 0.7 0011* 11 16.5 3 2.2 13.4 MI3 0.99
Table 10.3: Vacon 10 power ratings, 208-240 V, 3~
[ A ]
N
150% over­load current [ A ]
Motor shaft power
PHPP
[ KW ]
Nominal input current
[ A ]
* The maximum ambient operating temperature of these drives is +40 °C.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
10
Mechanical size
Weig ht (kg)
technical data vacon 97

10.2.2 Vacon 10 – Mains voltage 115 V

Mains voltage 115 V, 50/60 Hz, 1~ series
Rated loadability
Freq.
converter
type
100% contin. current I
0001 1.7 2.6 0.33 0.25 9.2 MI2 0.7 0002 2.4 3.6 0.5 0.37 11.6 MI2 0.7 0003 2.8 4.2 0.75 0.55 12.4 MI2 0.7 0004 3.7 5.6 1 0.75 15 MI2 0.7 0005 4.8 7.2 1.5 1.1 16.5 MI3 0.99
Table 10.4: Vacon 10 power ratings, 115 V, 1~

10.2.3 Vacon 10 – Mains voltage 380-480 V

[ A ]
N
150% over­load cu rrent [ A ]
Motor shaft power
P
[ HP ]P[ KW ]
Mains voltage 380-480 V, 50/60 Hz, 3~ series
Rated loadability
Freq.
converter
100% contin.
type
current I
] 0001 1.3 2 0.5 0.37 2.2 MI1 0.55 0002 1.9 2.9 0.75 0.55 2.8 MI1 0.55 0003 2.4 3.6 1 0.75 3.2 MI1 0.55 0004 3.3 5 1.5 1. 1 4 MI2 0.7 0005 4.3 6.5 2 1.5 5.6 MI2 0.7 0006 5.6 8.4 3 2.2 7.3 MI 2 0.7 0008 7.6 11.4 4 3 9.6 MI3 0,99 0009 9 13.5 5 4 11.5 MI3 0.99 0012 12 18 7.5 5.5 14.,9 MI3 0.99
Table 10.5: Vacon 10 power ratings, 380-480 V
[ A
N
150% over­load cu rrent [ A ]
* The maximum ambient operating temperature of these drives is +50 °C.
Motor shaft power
P
[ HP ]P[ KW ]
Nominal input current
[ A ]
Nominal input current
[ A ]
Mechanical size
Mechanical size
Weig ht (Kg)
Weig ht (kg)
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
10
Loading...