8.2 Motor settings (Control panel: Menu PAR -> P1) 52
8.3 Start / stop setup (Control panel: Menu PAR -> P2) 53
8.4 Frequency references (Control panel: Menu PAR -> P3) 54
8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4) 55
8.6 Digital inputs (Control panel: Menu PAR -> P5) 56
8.7 Analogue inputs (Control panel: Menu PAR -> P6) 56
8.8 Digital outputs (Control panel: Menu PAR -> P8) 57
8.9 Analogue outputs (Control panel: Menu PAR -> P9) 57
8.10 Protections (Control panel: Menu PAR -> P13) 58
8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14) 58
8.12 PI control parameters (Control panel: Menu PAR -> P15) 59
8.13 Application Setting (Control panel: Menu PAR -> P17) 59
8.14 System parameters 60
9. Parameter descriptions 62
9.1 Motor settings (Control panel: Menu PAR -> P1) 62
9.2 Start / stop setup (Control panel: Menu PAR -> P2) 67
9.3 Frequency references (Control panel: Menu PAR -> P3) 74
9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4) 75
9.5 Digital inputs (Control panel: Menu PAR -> P5) 79
9.6 Analogue inputs (Control panel: Menu PAR -> P6) 80
9.7 Digital outputs (Control panel: Menu PAR -> P8) 81
9.8 Analogue outputs (Control panel: Menu PAR -> P9) 82
9.9 Protections (Control panel:Menu Par->P13) 83
9.10 Automatic reset (Control panel: Menu PAR -> P14) 87
9.11 PI control parameters (Control panel: Menu PAR -> P15) 88
9.12 Application setting (Control panel: Menu PAR->P17) 89
9.13 Modbus RTU 91
9.13.1 Termination resistor 91
9.13.2 Modbus address area 91
9.13.3 Modbus process data 92
10. Technical data 94
10.1 Vacon 10 technical data 94
10.2 Power ratings 96
10.2.1 Vacon 10 – Mains voltage 208-240 V 96
10.2.2 Vacon 10 – Mains voltage 115 V 97
10.2.3 Vacon 10 – Mains voltage 380-480 V 97
10.2.4 Vacon 10 – Mains voltage 575 V 98
10.3 Brake resistors 98
safetyvacon • 1
1. SAFETY
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY
OUT THE ELECTRICAL INSTALLATION!
This manual contains clearly marked cautions and warnings which are intended for
your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully:
=Dangerous voltage
Risk of death or severe injury
=General warning
Risk of damage to the product or
connected appliances
1.1 Warnings
The components of the power unit of the frequency converter
are live when Vacon 10 is connected to mains. Coming into
contact with this voltage is extremely dangerous and may
cause death or severe injury. The control unit is isolated from
the mains potential.
The motor terminals U, V, W (T1, T2, T3) and the possible brake
resistor terminals - / + are live when Vacon 10 is connected to
mains, even if the motor is not running.
The control I / O-terminals are isolated from the mains potential. However, the relay output terminals may have a dangerous control voltage present even when Vacon 10 is
connected from mains.
dis
The earth leakage current of Vacon 10 frequency converters
exceeds 3.5 mA AC. According to standard EN61800-5-1, a
reinforced protective ground connection must be ensured.
If the frequency converter is used as a part of a ma chine, the
machine manufacturer is responsible for providing the
machine with a main switch (EN 60204-1).
If Vacon 10 is disconnected from mains while running the
motor, it remains live if the motor is energized by the process.
In this case the motor functions as a generator feeding energy
to the frequency converter.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
2 •vaconsafety
After disconnecting the frequency converter from the mains,
wait until the fan stops and the indicators on the display go
out. Wait 5 more minutes before doing any work on Vacon 10
connections.
The motor can start automatically after a fault situation, if the
autoreset function has been activated.
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
safetyvacon • 3
1.2 Safety instructions
The Vacon 10 frequency converter has been designed for fixed
installations only.
Do not perform any measurements when the frequency converter is connected to the mains.
Do not perform any voltage withstand tests on any part of
Vacon 10. The product safety is fully tested at factory.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the frequency converter.
Do not open the cover of Vacon 10. Static voltage discharge
from your fingers may damage the components. Opening the
cover may also damage the device. If the cover of Vacon 10 is
opened, warranty becomes void.
1.3 Earthing and earth fault protection
The Vacon 10 frequency converter must always be earthed with an earthing conductor connected to the earthing terminal. See figure below:
MI1 - MI3
• The earth fault protection inside the frequency converter protects
only the converter itself against earth faults.
• If fault current protective switches are used they must be tested
with the drive with earth fault currents that are possible to arise in
fault situations.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
4 • vaconsafety
1.4 Before running the motor
Checklist:
Before starting the motor, check that the motor is mounted
properly and ensure that the machine connected to the motor
allows the motor to be started.
Set the maximum motor speed (frequency) according to the
motor and the machine connected to it.
Before reversing the motor shaft rotation direction make sure
that this can be done safely.
Make sure that no power correction capacitors are connected
to the motor cable.
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
receipt of deliveryvacon • 5
2. RECEIPT OF DELIVERY
After unpacking the product, check that no signs of transport damages are to be
found on the product and that the delivery is complete (compare the type designation
of the product to the code below).
Should the drive have been damaged during the shipping, please contact primarily
the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
2.1 Type designation code
VACON0010- 1L- 0001- 1+OPTIONS
Vacon 10
Input phase
1L = Single phase
3L = Three phases
Output Current
Input Voltage
1 =115V
2 = 208 - 230V
4 = 380 - 480V
7 = 575V
+Options
EMC2
QPES
Language of the documentation
+DLCN = Chinese
+DLCZ = Czech
+DLDE = German
+DLDK = Danish
+DLES = Spanish
+DLFI = Finnish
+DLFR = French
+DLIT = Italian
Figure 2.1: Vacon 10 type designation code
2.2 Storage
If the frequency converter is to be kept in store before use make sure that the ambient conditions are acceptable:
Storing temperature -40…+70°C
Relative humidity < 95%, no condensation
+DLNL = Dutch
+DLNO = Norwegian
+DLPT = Portuguese
+DLRU = Russian
+DLSE = Swedish
+DLTR = Turkish
+DLUS = US English
empt y = Engli sh
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
6 • vaconreceipt of delivery
2.3 Maintenance
In normal operating conditions, Vacon 10 frequency converters are maintenancefree. However, regular maintenance is recommended to ensure a trouble-free operating and a long lifetime of the drive. We recommended to follow the table below for
maintenance intervals.
Maintenance intervalMaintenance action
Whenever necessary
Regular
12 months (If stored)
6 - 24 months (depending on environment)
5 - 7 years
2.3.1 Capacitor recharge
After a longer storage time the capacitors need to be recharge in order to avoid capacitor damage. Possible high leakage current through the capacitors must be limited. The best way to achieve this is to use a DC-power supply with adjustable current
limit.
1) Set the current limit to 300…800 mA according to the size of the drive.
2) Then connect the DC-power supply to the input phase L1 and L2.
3) Then set the DC-voltage to the nominal DC-voltage level of the (1.35*Un AC) and
supply the converter for at least 1 h.
If DC-voltage is not available and the unit has been stored much longer than 12
months deenergized, consult the factory before connecting power.
• Clean headsink
• Check tightening torques of terminals
• Check input and output terminals and control I / O terminals.
• Clean cooling tunnel.
• Check operation of cooling fan, check for
corrosion on terminals, busbars and other
surfaces.
• Chang cooling fans:
• Main fan
• Interminal fan
• The motor cables should cross other cables
at an angle of 90 degrees.
2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
receipt of deliveryvacon • 7
2.4 Warranty
Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible
for damages and failures resulting from misuse, wrong installation, unacceptable
ambient temperature, dust, corrosive substances or operation outside the rated
specifications. Neither can the manufacturer be held responsible for consequential
damages.
The Manufacturer's time of warranty is 18 months from the delivery or 12 months
from the commissioning whichever expires first (Vacon Warranty Terms).
The local distributor may grant a warranty time different from the above. This warranty time shall be specified in the distributor's sales and warranty terms. Vacon assumes no responsibility for any other warranties than that granted by Vacon itself.
In all matters concerning the warranty, please contact first your distributor.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
2
8 • vaconreceipt of delivery
EU DECLARATION OF CONFORMITY
We
Manufacture r's nam e:Vacon Oyj
Manufacturer' s address:P.O.Box 2 5
Runsorintie 7
FIN-65381 Vaasa
Finland
hereby declare that the product
Product name:Vacon 10 Frequency Converter
Model d esignation:Vacon101L00012…to 00092
Vacon103L00012…to 00112
Vacon103L00014…to 00124
has been designed and manufactured in accordance with the following
standards:
Safety:
EN 60204 -1 (2009) (as relevant) ,
EN 61800-5-1 (2007)
EMC:EN 61800-3 (2004)
and conforms to the relevant safety provisions of the Low Voltage Directive
2006/95/E C and EMC Dir ective 2004/108/EC .
It is ensured through internal measures and quality control that the product
conforms at all times to the requi rements of the current Direct ive an d the
relevant standards.
In Vaasa, 30th of July, 2010
Vesa Laisi
President
The year the CE marking was affixed:2011
2.5 Manufacturer’s declaration of conformity
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
=
M5
MI3
MI1
=M4
MI2
=M5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
12
installationvacon • 9
3 INSTALLATION
3.1 Mechanical installation
There are two possible ways to mount Vacon 10 in the wall. For MI1-MI3, either screw
or DIN-rail mounting. The mounting dimensions are given on the back of the drive
and on the following page.
Figure 3.1: Screw mounting, MI1 - MI3
Figure 3.2: DIN-rail mounting, MI1 - MI3
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Table 2: Vacon 10 frame dimensions (mm) and weights (kg)
*without shipping package
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 11
Frame Dimensions(Inches)Weig ht*
MI12.66.23.91.2
MI23.59.941.5
MI33.910.34.32.2
Table 3: Vacon 10 frame dimensions (Inch) and weights (Ibs)
WHD(Ibs.)
*without shipping package
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
12 • vacon installation
3.1.2 Cooling
Enough free space shall be left above and below the frequency converter to ensure
sufficient air circulation and cooling. You will find the required dimensions for free
space in the table below.
If several units are mounted above each other the required free space equals C + D
(see Installation space). Moreover, the outlet air used for cooling by the lower unit
must be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of
the converter.
Min clearance (mm)
TypeA*B*CD
MI1202010050
MI2202010050
MI3202010050
Table 3.1: Min. clearances around AC drive
*. Min clearance A and B for drives for
MI1 ~ MI3 can be 0 mm if the ambient
temperature is below 40 degrees.
A = clearance around the freq. converter (see also B)
B = distance from one frequency converter to another or distance to cabinet wall
C = free space above the frequency converter
D = free space underneath the frequency converter
NOTE! See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm), below (50 mm), and on the sides
(20 mm) of Vacon 10! For MI1 - MI3, side-to-side installation allowed only if the ambient temperature is below 40 °C.
TypeCooling air required (m³/h)
MI110
MI210
MI330
Table 3.2: Required cooling air
C
A
Figure3.4:Installation space
B
A
D
B
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 13
3.1.3 Power losses
If the operator wants to raise the switching frequency of the drive for some reason
(typically e.g. in order to reduce the motor noise), this inevitably affects the power
losses and cooling requirements, for different motor shaft power, operator can select the switching frequency according to the graphs below.
MI1 - MI3 3P 380 V POWER LOSS
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
14 • vacon installation
MI1 - MI3 3P 230 V POWER LOSS
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 15
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
16 • vacon installation
MI1 - MI3 1P 230 V POWER LOSS
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 17
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
18 • vacon installation
3.1.4 EMC levels
EN61800-3 defines the division of frequency converters into five classes according to
the level of electromagnetic disturbances emitted, the requirements of a power system network and the installation environment (see below). The EMC class of each
product is defined in the type designation code.
Category C1: Frequency converters of this class comply with the requirements of
category C1 of the product standard EN 61800-3 (2004). Category C1 ensures the
best EMC characteristics and it includes converters the rated voltage of which is less
than 1000 V and which are intended for use in the 1st environment.
NOTE: The requirements of class C are fulfilled only as far as the conducted emissions are concerned.
Category C2: Frequency converters of this class comply with the requirements of
category C2 of the product standard EN 61800-3 (2004). Category C2 includes converters in fixed installations and the rated voltage of which is less than 1000 V. The
class C2 frequency converters can be used both in the 1st and the 2nd environment.
Category C3: Frequency converters of this class comply with the requirements of
category C3 of the product standard EN 61800-3 (2004). Category C3 includes converters the rated voltage of which is less than 1000 V and which are intended for use
in the second environment only.
Category C4: The drives of this class do not provide EMC emission protection. These
kinds of drives are mounted in enclosures.
Environments in product standard EN 61800-3 (2004)
First environment: Environment that includes domestic premises. It also includes
establishments directly connected without intermediate transformers to a low-voltage power supply network which supplies buildings used for domestic purposes.
NOTE: houses, apartments, commercial premises or offices in a residential building
are examples of first environment locations.
Second environment: Environment that includes all establishments other than
those directly connected to a low-voltage power supply network which supplies
buildings used for domestic purposes.
NOTE: industrial areas, technical areas of any building fed from a dedicated transformer are examples of second environment locations.
3.1.5 Changing the EMC protection class from C2 or C3 to C4
The EMC protection class of MI1-3 frequency converters can be changed from class
C2 or C3 to class C4 by removing the EMC-capacitor disconnecting screw, see figure below.
Note! Do not attempt to change the EMC level back to class C2 or C3. Even if the procedure above is reversed, the frequency converter will no longer fulfil the EMC requirements of class C2 / C3!
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 19
Figure 3.5: EMC protection class, MI1 - MI3
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
20 • vacon installation
1~ (230V)
3~ (230V, 400V)
Motor out
MAINS
MOTOR
Strip the
plastic cable
coating for
360° earthing
L1 L 2/N L3U/ T1 V/T2 W /T3R+ R-
1~ (230V)
3~(230V, 400V, 575V)
1~ (115V)
MAINS
MOTOR
BRAKE
RESISTOR
External brake resistor
Motor out
Strip the
plastic
cable
coating
for 360°
earthing
3~(230V, 400V, 575V)
3.2 Cabling and connections
3.2.1 Power cabling
Note! Tightening torque for power cables is 0.5 - 0.6 Nm
Figure 3.6: Vacon 10 power connections, MI1
3
Figure 3.7: Vacon 10 power connections, MI2 - MI3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 21
Attach this plate
BEFORE i nsta lling
the pow er ca bl es
Attach the support
AFTER i nstal ling
the po wer cables
3.2.2 Control cabling
Figure 3.8: Mount the PE-plate and API cable support, MI1 - MI3
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
22 • vacon installation
Strip the plastic
cable coating for
360°earthing
Control cable
tightening
torque: 0.4 Nm
Figure 3.9: Open the lid, MI1 - MI3
3
Figure 3.10: Install the control cables. MI1 - MI3. See Chapter 6.2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 23
M4*8 - 12 Pcs
M4-8 Screws 14 Pcs
3.2.3 Screw of cables
Figure 3.11: MI1 screws
Figure 3.12: MI2 screws
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
24 • vacon installation
M4-8 Screws 10 Pcs
M4-10 Screws 4 Pcs
Figure 3.13: MI3 screws
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installationvacon • 25
3.2.4 Cable and fuse specifications
Use cables with heat resistance of at least +70°C. The cables and the fuses must be
dimensioned according to the tables below. Installation of cables according to UL
regulations is presented in Chapter Cable installation and the UL standards.
The fuses function also as cable overload protection.
These instructions apply only to cases with one motor and one cable connection from
the frequency converter to the motor. In any other case, ask the factory for more information.
EMC categorycat. C2cat. C3 cat. C4
Mains cable types111
Motor cable types321
Control cable types444
Table 3.3: Cable types required to meet standards. EMC categories are
described in Chapter EMC levels
Cable typeDescription
Power cable intended for fixed installation and the specific mains voltage.
1
Shielded cable not required.
(NKCABLES / MCMK or similar recommended)
Power cable equipped with concentric protection wire and intended for
2
the specific mains voltage.
(NKCABLES / MCMK or similar recommended).
Power cable equipped with compact low-impedance shield and intended
for the specific mains voltage.
3
(NKCABLES / MCCMK, SAB / ÖZCUY-J or similar recommended).
*360º earthing of both motor and FC connection required to meet the standard
Screened cable equipped with compact low-impedance shield (NKCA-
4
Table 3.4: Cable type descriptions
BLES /Jamak, SAB / ÖZCuY-O or similar).
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Table 3.9: Cable and fuse sizes for Vacon 10, 575 V
Note! To fulfil standard EN61800-5-1, the protective co nductor should be at least
10 mm2 Cu or 16 mm2 Al. Another possibility is to use an additional protective con-
ductor of at least the same size as the original one.
Fuse
[A]
[mm2]
Cu
cable
Cu [mm2]
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
2
[mm
]
terminal
[mm
2
]
Relay
2
[mm
Relay
terminal
2
[mm
]
]
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
28 • vacon installation
3.2.5 General cabling rules
Before starting the installation, check that none of the components of the fre-
1
quency converter is live.
Place the motor cables sufficiently far from other cables:
• Avoid placing the motor cables in long parallel lines with other cables.
• If the motor cable runs in parallel with other cables, the minimum distance
between the motor cable and other cables is 0.3 m.
• The given distance also applies between the motor cables and signal cables
2
3
4
of other systems.
• The maximum length of the motor cables for MI1-3 is 30 m. If use longer
cable, current accuracy will be decreased.
• The motor cables should cross other cables at an angle of 90 degrees.
If cable insulation checks are needed, see Chapter Cable and motor insulation
checks.
Connecting the cables:
• Strip the motor and mains cables as advised in Figure Stripping of cables.
• Connect the mains, motor and control cables into their respective terminals, see Figures Vacon 10 power connections, MI1 - Install the control
cables.
• Note the tightening torques of power cables andcontrol cables given in
Vacon 10 power connections, MI1 and Install t he control cables. MI1 - MI3.
See Chapter6.2.
• For information on cable installation according to UL regulations see Chapter Cable installation and the UL standards.
• Make sure that the control cable wires do not come in contact with th e electronic components of the unit.
• If an external brake resistor (option) is used, connect its cable to the appropriate term inal.
• Check the connection of the earth cable to the motor and the frequency
converter terminals marked with.
• Connect the separate shield of the motor cable to the earth plate of the
frequency converter, motor and the supply centre.
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
20 mm
35 mm
8 mm
Earth conductor
8 mm
installationvacon • 29
3.2.6 Stripping lengths of motor a nd mains cables
Figure 3.14: Stripping of cables
Note! Strip also the plastic cover of the cables for 360 degree earthing. See Figures
Vacon 10 power connections, MI1, Vacon 10 power connections, MI2 - MI3 and Install
the control cables. MI1 - MI3. See Chapter 6.2
3.2.7 Cable installation and the UL standards
To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper cable with a minimum heat-resistance of +60 / 75°C must be used.
3.2.8 Cable and motor insulation checks
These checks can be performed as follows if motor or cable insulations are suspected to be faulty.
1. Motor cable insulation checks
Disconnect the motor cable from terminals U / T1, V / T2 and W / T3 of the frequency
converter and from the motor. Measure the insulation resistance of the motor cable
between each phase conductor as well as between each phase conductor and the
protective ground conductor.
The insulation resistance must be >1 MOhm.
2. Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 / N and L3 of the frequency converter and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the
protective ground conductor. The insulation resistance must be >1 MOhm.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the
motor connection box. Measure the insulation resistance of each motor winding. The
measurement voltage must equal at least the motor nominal voltage but not exceed
1000 V. The insulation resistance must be >1 MOhm.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
30 • vaconcommissioning
4. COMMISSIONING
Before commissioning, read the warnings and instructions listed in
Chapter 1!
4.1 Commissioning steps of Vacon 10
Read carefully the safety instructions in Chapter 1 and follow them.
1
After the installation, make sure that:
• both the frequency converter and the motor are grounded.
• the mains and motor cables comply with the requirements given in Chapter 3.2.4.
• the control cables are located as far as possible from the power. cables
2
3
4
5
6
ee C
hapter 3.2.5, step 2) and the shields of the shielded cables are con-
(s
nected to protective earth
Check the quality and quantity of cooling air (Chapter 3.1.2).
Check that all Start / Stop switches connected to the I / O terminals are in Stop-
position.
Connect the frequency converter to mains.
Set the parameters of group 1 according to the requirements of your application.
At least the following parameters should be set:
• motor nominal speed (par. 1.3)
• motor nominal current (par. 1.4)
• application type (par. 17.1)
You will find the values needed for the parameters on the motor rating plate.
.
4
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
commissioningvacon • 31
Perform test run without motor. Perform either Test A or Test B:
A) Control from the I / O terminals:
Turn the Start / Stop switch to ON position.
•
• Change the frequency reference (potentiometer).
• Check the Monitoring Menu and make sure that the value of Output frequency changes according to the change of frequency reference.
7
8
9
10
• Turn the Start / Stop switch to OFF position.
ntrol from the keypad:
B) Co
•
Select the keypad as the control place with par 2.1. You can also move to
ypad control by pressing Loc / Rem button or select Local control with
ke
par 2.5.
• Push the Start button on the keypad.
• Check the Monitoring Menu and make sure that the value of Output frequency. changes according to the change of frequency reference.
• Push the Stop button on the keypad.
Run the no-load tests without the motor b eing connected to the process, if possible. If this is impossible, secure the safety of each test prior to running it. Inform
ur co-workers of the tests.
yo
• Switch off the supply voltage and wait up until the drive has stopped.
• Connect the motor cable to the motor and to the motor cable terminals of
he
frequency converter.
t
• See to that all Start / Stop switches are in Stop positions.
• Switch the mains ON.
• Repeat test 7A or 7B.
Perform an identification run (see par. 1.18), especially if the application requires
a high startup torque or a high torque with low speed.
Connect the motor to the process (if the no-load test was running without the
motor being connected).
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
4
32 • vaconfault tracing
Fault code (02 = overvoltage)
FT. 02
5. FAULT TRACING
Note: The fault codes listed in this chapter are visible if the Application Interface has
a display, like e.g. in control board or if a personal computer has been connected to
the drive.
When a fatal fault is detected by the frequency converter control electronics, the
drive will stop and the symbol FT and the fault code blinked on the display are in the
following format, e.g.:
The active fault can be reset by pressing BACK / RESET button when the API is in active fault menu level (FT XX), or pressing BACK / RESET button with long time (> 2 s)
when the API is in active fault submenu level (F5.x ), or via the I / O terminal or field
bus. Reset fault history (long push > 5 s), when the API is in fault history submenu
level (F6.x). The faults with subcode and time labels are stored in the Fault history
submenu which can be browsed. The different fault codes, their causes and correcting actions are presented in the table below.
5
Fault
Table 5.1: Fault codes
Fault namePossible causeCorrecting actions
code
Overcurrent
1
Overvoltage
2
Earth fault
3
Frequency converter has
detected too high a current
) in the motor cable:
(>4*I
N
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
The DC-link voltage has
exceeded the internal safety
limit:
• deceleration time is too
short
• high overvoltage spikes in
mains
Current measurement has
detected extra leakage current at
start:
• insulation failure in cables or
motor
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
Check loading.
Check motor size.
Check cables.
Increase the deceleration
time (Par.4.3)
Check motor cables and
motor
fault tracingvacon • 33
Fault
Table 5.1: Fault codes
Fault namePossible causeCorrecting actions
code
System fault
8
Undervoltage
9
Output phase fault
11
Frequency converter
13
undertemperature
Frequency converter
14
overtemperature
Motor stalled
15
Motor overtempera-
16
ture
Motor underload
17
• component failure
• faulty operation
The DC-link voltage has gone
below the internal safety limit:
• most probable cause: supp ly
voltage is too low
• frequency converter internal
fault
• Power outages
Current measurement has
detected that there is no current
in one motor phase.
Heat sink temperature is under
°C
-10
Heat sink is overheated.
Motor stall protection has
tripped.
Motor overheating has been
detected by frequency converter
motor temperature model. Motor
is overloaded.
Motor underload protection has
tripped.
Reset the fault and
restart .
If the fault re-occurs, contact the distributor near to
you.
NOTE! If fault F8 occurs,
find out the subcode of the
fault from the Fault History menu under Id xxx!
In case of temporary supply voltage break reset the
fault and restart the frequency converter. Check
the supply voltage. If it is
adequate, an internal failure has occurred.
Contact the distributor
near to you.
Check motor cable and
motor.
Check the ambient temperature.
Check that the cooling air
flow is not blocked.
Check the ambient temperature.
Make sure that the
switching frequency is not
too high in relation to
ambient temperature and
motor load.
Check that the motor is
able to rotate freely.
Decrease the motor load.
If no motor overload
exists, check the temperature model parameters.
Check motor and load,
e.g. for broken belts or dry
pumps.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
5
34 • vaconfault tracing
Fault
Table 5.1: Fault codes
Fault namePossible causeCorrecting actions
code
EEPROM checksum
22
fault
Microcontroller
25
watchdog fault
Back EMF protection
27
Internal bus commu-
34
nication
Application fault
35
IGBT Overtemperature
41
Analog input select
20% - 100% (selected
50
signal range 4 to
20 mA or 2 to 10 V)
External fault
51
Fieldbus fault
53
Idenfication faultIdentification run has failed.
57
Parameter save fault
• faulty operation
• component failure
• faulty operation
• component failure
Drive has detected that the magnetized motor is running in start
situation.
• A rotating PM-motor
Ambient interference or defective
hard ware
Application is not working properly.
Overtemperature alarm is issued
when the IGBT switch temperature exceeds 110 °C.
Current at the analogue input is <
4mA; Voltage at the analogue
input is < 2 V.
• control cable is broken or
loose.
• signal source has failed.
Digital input fault. Digital input
has been programmed as external fault input and this input is
active.
The data connection between the
fieldbus Master and the fieldbus
of the drive has broken.
Contact the distributor
near to you.
Reset the fault and
resta rt.
If the fault re-occur, contact the distributor near to
you.
Make sure that there is no
rotating PM-motor when
the start command is
given.
If the fault re-occur, contact the distributor near to
you.
Contact the distributor
near to you.
Check loading.
Check motor size.
Make identification run.
Check the current loop
circuitry.
Check installation.
If installation is correct,
contact the nearest Vacon
distributor.
Run command was
removed before completion of identification run.
Motor is not connected to
frequency converter.
There is load on motor
shaft.
5
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 apivacon • 35
6. VACON 10 APPLICATION INTERFACE
6.1 Introduction
There is only one version of Control Board available for the Vacon 10 drive:
Vers ion Composition
6 Digital inputs
2 Analogue inputs
Vacon 10
Table 6.1: Available Control Board
This section provides you with a description of the I / O-signals f or these versions and
instructions for using the Vacon 10 general purpose application.
The frequency reference can be selected from Preset Speed 0-7, Keypad, Fieldbus,
AI1, AI2, PI.
Basic properties:
• Digital inputs DI1…DI6 are freely programmable. The user can assign a
single input to many functions.
• Digital-, relay- and analogue outputs are freely programmable.
• Analog output can be set as current output.
• Analog input 1 can be set as voltage input and Analog input 2
can be set as current input.
Special features:
• Programmable Start / Stop and Reverse signal logic
• Reference scaling
• DC-brake at start and stop
• Programmable U / f curve
• Adjustable switching frequency
• Autoreset function after fault
1 Analogue output
1 Digital output
2 Relay outputs
RS-485 Interface
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
36 • vaconvacon 10 api
• Protections and supervisions (all fully programmable; off, alarm, fault):
• Analog input low fault
• Undervoltage fault
• Earth fault
• Output phase fault
• Motor thermal, stall and underload protection
• 8 preset speeds
• Analogue input range selection, signal scaling and filtering
6
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 apivacon • 37
20
ON
OFF
6.2 Control I/O
TerminalSignalFactory presetDescription
1 +10Vre Ref. voltage outMaximum load 10 mA
2 AI1Analog signal in 1
3 GNDI/O signal ground
6 24Vout 24V output for DI's
7 GNDI/O signal ground
8 DI1Digital input 1
9 DI2Digital input 2
10 DI3Digital input 3
A ARS485 signal AFB Communication Negative
B BRS485 signal BFB Communication Positive
4 AI2Analog signal in 2
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
38 • vaconcontrol panel
7. CONTROL PANEL
7.1 General
The panel is an irremovable part of the drive consisting of corresponding control
board; The overlay with display status on the cover and the button are in clarifications in the user language.
The User Panel consists o f an alphanumeric LCD display with back light and a keypad
with the 9 push buttons (see Figure 7.1).
7.2 Display
The display includes 14-segment and 7-segment blocks, arrowheads and clear text
unit symbols. The arrowheads, when visible, indicate some information about the
drive, which is printed in clear text in user language on the overlay (numbers 1…14
in the figure below). The arrowheads are grouped in 3 groups with the following
meanings and English overlay texts (see Figure 7.1):
Group 1 - 5; Drive status
1= Drive is ready to start (READY)
2= Drive is running (RUN)
3= Drive has stopped (STOP)
4= Alarm condition is active (ALARM)
5= Drive has stopped due to a fault (FAULT)
Group 6 - 10; Control selections
When API is operated by PC control, there are no arrowhead at I / O, KEYPAD and
BUS.
6= Motor is rotating forward (FWD)
7= Motor is rotating reverse (REV)
8= I/O terminal block is the selected control place (I / O)
9= Keypad is the selected control place (KEYPAD)
10= Fieldbus is the selected control place (BUS)
Group 11 - 14; Navigation main menu
11= Reference main menu (REF)
12= Monitoring main menu (MON)
13= Parameter main menu (PAR)
14= System main menu (SYS)
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panelvacon • 39
1 2 3 4 5
6 7 8 9 10
11
13
14
12
READY RUN STOP ALARM FAULT
FWD REV I/O KEYPAD BUS
SYS
PAR
REF
MON
BACK
RESET
LOC
REM
OK
7.3 Keypad
The keypad section of the control panel consists of 9 buttons (see Figure 7.1). The
buttons and their functions are described as Table 7.1.
The drive stops by pressing the keypad STOP button.
The drive starts by pressing the keypad START button when the selected control
place is KEYPAD.
Figure 7.1: Vacon 10 Control panel
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
40 • vaconcontrol panel
OK
SymbolButton NameFunction Description
StartMotor START from the panel
STOPMotor STOP from the panel
OKUsed for confirmation
BACK
RESET
LOC
Back / Reset
Up and Down
Left and Right
Loc / RemChange control place
Cancels edited parameter
Move backwards in menu levels
Reset fault indication
Navigation button:
Select root parameter number on rootparameter list, Up decrease / Down
increase parameter number,
Up increase / Down decrease parameter value change
Available in MON, PAR and SYS menuparameter, navigation and parameter
digit setting
MON can also use left and right button
to navigate the menu from V1.x to V2.1
to V3.1
REM
Table 7.1: Keypad Function
NOTE! The status of all the 9 buttons are available for application program!
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
control panelvacon • 41
7.4 Navigation on the Vacon 10 control panel
This chapter provides you with information on na vigating the menus on Vacon 10 and
editing the values of the parameters.
7.4.1 Main menu
The menu structure of Vacon 10 control software consists of a main menu and several submenus. Navigation in the main menu is shown below:
REFERENCE
MENU
Dispalysthe
keypad reference
value
regardless of
theselected
contron place.
REF
MON
PAR
SYSSYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RU N
Hz
REF
MON
OK
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
PRESS
MONI TO RING
MENU
In this me nu
you can
browsethe
monitoring
values.
REF
MON
PA R
SYSSYS
FWD REV I/O KEYPAD BU S
FAUL TALARMSTOPREADY RUN
REF
MON
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
PRESS
PAR A M E T E R
MENU
In this me nu
you can
browseand
edit the
parameters.
REF
MON
PAR
SYSSYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RUN
REF
MON
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
PRESS
SYSTEM
MENU
Here youwill be
able tobrowse
systemparameter
and fault
submenu.
REF
MON
PAR
SYSSYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPRE ADY RUN
REF
MON
OK
PAR
PRESS
FWD REV I/O KEYPAD BUS
Figure 7.2: The main menu of Vacon 10
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
FAULTALARMSTOPREADY RUN
Hz
FAUL TALARMSTO PREADY RUN
FAULTALARMSTOPREADY RUN
FAU LTALARMSTO PREAD Y RUN
7
42 • vaconcontrol panel
Press to enter
edit mode
Change
value
Press to
confirm
OKOK
SYS
FWD REV I/O KEYPAD BUS
REF
MON
PA R
FAU LTALARMSTOPREADY R UN
Hz
7.4.2 Reference menu
Figure 7.3: Reference menu display
Move to the reference menu with the UP / DOWN button (see Figure 7.2). The reference value can be changed by 0.01 every time with UP / DOWN button as shown in
Figure 7.3.
If the value has big change, first press Left and Right buttons to select the dig it which
has to be changed, then press Up button to increase and Down button to decreases
the value in the selected digit . In the end, press OK button to take the setting value
effective.
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panelvacon • 43
7.4.3 Monitoring menu
REF
MON
PAR
SYS
FW D R EV I /O K EY PA D B USF W D RE V I/ O K EY PA D B US
FAULTALARMSTOPREADY RUN
MON
REF
PAR
SYS
OK
1
Press OK to enter
Monitoring menu
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
Prsess Down to
3
browse V4.4
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RUN
FAULTALARMSTOPRE ADY RUN
OK
Press Left/Right t o browse
2
other Monitor ing groups
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
Preess OK the value is
4
displayed
5
Press OK V4.4 is display
Figure 7.4: Monitoring menu display
Monitoring values are actual values of measured signals as well as status of some
control settings. It is visible in Vacon 10 display, but it can not be edited. The monitoring values are listed in Table 7.2.
Pressing Left/Right button to change the actual parameter to the first parameter of
the next group, to browse monitor menu from V1.x to V2.1 to V4.1. After entering the
desired group, the monitoring values can be browsed b y pressing UP /DOWN button,
as shown in Figure 7.4.
In MON menu the selected signal and its value are alternateing in the display by
pressing OK button.
Note! Turn on drive power, arrowhead of main menu is at MON, V x. x
is displayed in Panel.
The value of “x” is determined by the last show before power
shut down. E.g., it was V4.4, and it is also V4.4 when restart.
FAULTALARMSTOPREADY RUN
FAULTALARMSTOPRE ADY RUN
OK
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
44 • vaconcontrol panel
Code Monitoring signalUnitID Description
V1.1Output frequencyHz1 Outpu t frequency to motor
V1.2Frequency referenceHz25
V1.3Motor speedrpm2 Calculated motor speed
V1.4Motor currentA3 Measured motor current
V1.5Motor torque%4
V1.6Output PowerKW79 Output power from drive to motor
V1.7Motor voltage V6 Motor voltage
V1.8DC-link voltageV7 Measured DC-link voltage
V1.9Drive temperature°C8 Heatsink temperature
V1.10 Motor temperature%9 Calculated motor temperature
V2.1Analog input 1%13
V2.2Analog input 2%14
V2.3Analog output %26
Digital input status DI1,
V2.4
DI2, DI3
Digital input status DI4,
V2.5
DI5, DI6
V2.6RO1, RO2, DO17 Relay / digital output status
V4.1PI setpoint%20 Regulator setpoint
V4.2PI feedback value%21 Regulator actual value
V4.3PI error%22 Re gulato r error
V4.4PI output%23 Regulator output
Table 7.2: Vacon 10 monitoring signals
Frequency reference to motor control
Calculated actual / nominal torque
of the motor
AI1 signal range in percent of used
range
AI2 signal range in percent of used
range
AO signal range in percent of used
range
15 Digital input status
16 Digital input status
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panelvacon • 45
7.4.4 Parameter menu
In Parameter menu only the Quick setup parameter list is shown as default. By giving
the value 0 to the parameter 17.2, it is possible to open other advanced parameter
groups. The parameter lists and descriptions can be found in chapters 8 and 9.
The following figure shows the parameter menu view:
REF
MON
PAR
SYS
FW D R EV I/O KE Y PAD B USFWD R E V I/ O K EY PA D B U S
FAULTALARMSTOPREADY RU N
REF
MON
PAR
SYS
OK
Press Right to browse
OK
REF
MON
PAR
SYS
2
4
6
otherPa r. group
FWD R EV I/O KEYPAD BUS
Press OK button to enter
edit mode
Press OK to confirm
Press OK to enter Par. menu
1
REF
MON
PAR
SYS
FWD R EV I/O KEYPAD BUS
Press down button to
3
browse P3.4
REF
MON
PAR
SYS
FWD R EV I/O KEYPAD BUS
Press Up / Down to change value
5
FAULTALARMSTOPREADY RU N
FAULTALARMSTOPREADY RUN
Figure 7.5: Parameter menu
The parameter can be changed as the Figure 7.5.
Left / Right button is available inside Parameter menu. Pressing Left / Right button
to change the actual parameter to the first parameter of the next group (Example:
any parameter of P1… is displayed -> RIGHT button -> P2.1 is displayed -> RIGHT button -> P3.1 is displayed …). After entering the desired group, pressing UP / DOWN
button to select root parameter number, and then press OK button to display the value of the parameter and also enter edit mode.
FAULTALARMSTOPREADY RU N
FAULTALARMSTOPREADY RUN
OK
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
46 • vaconcontrol panel
In edit mode, Left and Right buttons are used to select the digit which has to be
changed, and Up increases / Down decreases parameter value.
In edit mode, the value of Px.x is displayed blinkingly in the panel. After about 10 s,
Px.x is displayed in the panel again if you don't press any button.
Note! In edit mode, if you edit the value and don't press OK button, the
value isn't changed successfully.
In edit mode, if you don't edit the value, you can press Reset /
SYS menu including fault submenu and system parameter submenu, and the display
and operation of the system parameter submenu is similar to PAR menu or MON
menu.In system parameter submenu, there are some editable parameter (P) and
some uneditable parameter (V).
The Fault submenu of SYS menu includes active fault submenu and fault history sub menu.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
In active fault situation, FAULT arrow is blinking and the display is blinking active
fault menu item with fault code. If there are several active faults, you can check it by
entering the active fault submenu F5.x. F5.1 is always the latest active fault code. The
active faults can be reset by pressing BACK / RESET button with long time (>2 s),
when the API is in active fault submenu level (F5.x). If the fault cannot be reset, the
blinking continues. It is possible to select other display menus durin g active fault, but
in this case the display returns automatically to the fault menu if no button is pressed
in 10 seconds. The fault code, subcode and the operating day, hour and minute values at the fault instant are shown in the value menu (operating hours = displayed
reading).
Figure 7.6: Fault menu
7
48 • vaconcontrol panel
Note! Fault History can be reset by long pressing the BACK / RESET
button for 5 second time,when the API is in fault history submenu level (F6.x), it will also clear all active faults.
See Chapters for fault descriptions
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parametersvacon • 49
i
8. STANDARD APPLICATION PARAMETERS
On the next pages you can find the lists of parameters within the respective parameter groups. The parameter descriptions are given in Chapter 9 .
Explanations:
Code: Location indication on the keypad; Shows the operator the present
Parameter: Name of monitoring value or parameter
Min: Minimum value of parameter
Max: Maximum value of parameter
Unit: Unit of parameter value; given if available
Default: Factory preset value
ID: ID number of the parameter (used with fieldbus control)
NOTE: On parameter code: Parameter value can only be changed after the FC ha s
been stopped. This manual is for Vacon 10 standard application only. If you are using a special application, please download the appropriate user manual on http://
www.vacon.com -> Support & Downloads.
Monitoring value number or Parameter number
More information on this parameter available in chapter 9: ‘Param-
eter descriptions’ click on the parameter name.
Modifiable only in stop state
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
CodeParameterMin Max Unit Default IDNote
Ramp S-shape0,010,0s0,0500
Acceleration time 1 0,1 3000,0 s3,0103
Deceleration time 1 0,1 3000,0 s3,0104
Ramp S-shape 20,010,0s0,0501
Acceleration time 2 0,1 3000,0 s10,0502
Deceleration time 2 0,1 3000,0 s10,0503
Flux Braking030520
0,5 x
Flux Braking Cur-
rent
DC Braking Current
Stop DC current
time
Stop DC current
frequency
Start DC current
time
Table 8.5: Ramps and brakes setup
2,0 x
I
Nunit
2,0 x
I
Nunit
A
A
I
Nunit
0,3 x
I
Nunit
0,00 600,00 s0,00508
0,10 10,00 Hz1,50515
0,00 600,00 s0,00516 0 = Not active
I
Nunit
I
Nunit
0 = Linear
>0 = S-curve ramp time
0 = Off
1 = Deceleration
2 = Chopper
3 = Full Mode
519
Defines the current
injected into the motor
507
during DC brakeing.
Determines if braking is
ON or OFF and the braking time of the DC-brake
when the motor is stopping.
0 = Not active
The output frequency at
which the DC-braking is
applied.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
56 • vaconparameters
iii
i
i
i
i
i
8.6 Digital inputs (Control panel: Menu PAR -> P5)
CodeParameterMin Max Unit Default IDNote
0 = Not used
1 = DI1
I / O control signal 1 061403
P5.1
P5.2 I / O control signal 2 062404 As parameter 5.1
P5.3Reverse060412 As parameter 5.1
P5.4 Ext. fault Close066405 As parameter 5.1
P5.5Ext. fault Open060406 As parameter 5.1
P5.6Fault reset063414 As parameter 5.1
P5.7Run enable060407 As parameter 5.1
P5.8 Preset speed B0064419 As parameter 5.1
P5.9 Preset speed B1065420 As parameter 5.1
P5.10 Preset speed B2060421 As parameter 5.1
Ramp time 2 selec-
P5.11
P5.12Disable PI0601020 As parameter 5.1
P5.13Force to I/O060409 As parameter 5.1
Table 8.6: Digital inputs
tion
060408 As parameter 5.1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
6 = DI6
8.7 Analogue inputs (Control panel: Menu PAR -> P6)
Code Parame terMin Max Unit Default IDNote
AI1 Signal range010379
P6.1
-100,00
P6.2 AI1 Custom min
P6.3 AI1 Custom max
P6.4 AI1 filter time0,010,0s0,1378 0 = no filtering
P6.5 AI2 signal range010390
P6.6 AI2 Custom min
P6.7 AI2 Custom max
P6.8 AI2 filter time0,010,0s0,1389 0 = no filtering
8.8 Digital outputs (Control panel: Menu PAR -> P8)
Code ParameterMin Max Unit Default IDSelections
0 = Not used
1 = Ready
2 = Run
3 = Fault
RO1 signal
P8.1
selection
RO2 signal sel-
P8.2
cetion
DO1 signal sel-
P8.3
cetion
P8.4 RO2 inversion010489
Table 8.8: Digital outputs
0112313
0113314 As parameter 8.1
0111312 As parameter 8.1
4 = Fault Inverted
5 = Warning
6 = Reversed
7 = At Speed
8 = Motor regula tor active
9 = FB C ontrol Wo rd.B13
10 = FB C ontrol Wo rd.B14
11 = FB C ontrol Wo rd.B15
0 = No inversion
1 = Inverted
8.9 Analogue outputs (Control panel: Menu PAR -> P9)
Code ParameterMin Max Unit Default IDSelections
0 = Not used
Analog output
P9.1
signal selection
Analog output
P9.2
minimum
Table 8.9: Analogue output s
041307
010310
1 = Output freq. (0-f
2 = Output current (0-I
3 = Motor torque (0-T
4 = PI output (0 - 100%)
0 = 0 mA
1 = 4 mA
max
)
nMotor
nMotor
)
)
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
58 • vaconparameters
P13.2
P13.3
P13.4
i
iiiii
P13.5
P13.6
P13.7
P13.8
P13.9
P13.10
P14.1
P14.2
i
i
P14.3
P14.5
8.10 Protections (Control panel: Menu PAR -> P13)
CodeParam eterMin Max Unit Default IDNote
Analog Input low
P13.1
Table 8.10: Protections
fault
Under voltage
fault
Earth fault
Output Phase
Faul t
Stall protection
Under load pro-
tection
Motor thermal
protection
Mtp:Ambient
temperature
Mtp:Zero speed
cooling
Mtp:Thermal time
constant
021700
122727
0
22703 As parameter 13.1
0
22702 As parameter 13.1
0
20709 As parameter 13.1
0
20713 As parameter 13.1
0
22704 As parameter 13.1
-20
100
0,0
150,0%40,0 706 Cooling as % at 0 speed
1
200min45707
40705
°C
0 = No action
1 = Alarm
2 = Fault: Coast
1 = No response (no fault
generated but drive still
stops modulation)
2 = Faul t:Coa st
Environment temperation
Motor thermal time constant
NOTE! These parameters are shown, when P17.2 = 0.
8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14)
Code Paramete rMinMax Unit Default IDNote
Automatic Reset 010731
Wait time0,10 10,00s0,50 717 Waiting time after fault
Trial time0,00 60,00s30,00 718 Maximum time for trials
Restart Function 022719
Table 8.11: Fault autoreset parameters
0 = Disabled
1 = Enable
0 = Ramping
1 = Flying
2 = From Start Function
NOTE! These parameters are shown, when P17.2 = 0.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parametersvacon • 59
i
i
i
i
i
P17.1
8.12
PI control parameters (Control panel: Menu PAR -> P15)
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
62 • vaconparameter descriptions
9. PARAMETER DESCRIPTIONS
On the next pages you can find the descriptions of certain parameters. The descriptions have been arranged according to parameter group and number.
9.1 Motor settings (Control panel: Menu PAR -> P1)
1.7 CURRENTLIMIT
This parameter determines the maximum motor current from the frequency
converter. To avoid motor overload, set this parameter according to the rated
current of the motor. The current limit is equal to the rated converter current
(In) by default.
1.8 MOTORCONTROLMODE
With this parameter the user can select the motor control mode. The selections are:
0= Frequency control:
Drive frequency reference is set to output frequency without s lip com-
pensation. Motor actual speed is finally defined by motor load.
1= Open loop speed control:
Drive frequency reference is set to motor speed reference. The motor
speed remains the same regardless of motor load. Slip is compensated.
1.9 U / FRATIO
There are three selections for this parameter:
0 = Linear:
The voltage of the motor changes linearly with the frequency in the
constant flux area from 0 Hz to the field weakening point where the
field weakening point voltage is supplied to the motor. Linear U / f ratio
should be used in constant torque applications. See Figure 9.1.
This default setting should be used if there is no special need for another setting.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
U[V]
f[Hz]
Un
Par. 1.11
Par. 1.14
Par. 1.10
Default: Nominal
voltage of the m otor
Linear
Squared
Field weakening
point
Default: Nominal
frequency of t he
motor
parameter descriptionsvacon • 63
1 = Quadratic:
The voltage of the motor changes following a squared curve form with
the frequency in the area from 0 Hz to the field weakening poin t where
the field weakening point voltage is also supplied to the motor. The
motor runs under magnetised below the field weakening point and
produces less torque, power losses and electromechanical noise.
Squared U / f ratio can be used in applications where torque demand
of the load is proportional to the square of the speed, e.g. in centrifugal
fans and pumps.
Figure 9.1: Linear and squared change of motor voltage
2 = Programmable U / f curve:
The U / f curve can be programmed with three different points. Programmable U / f curve can be used if the other settings do not satisfy
the needs of the application.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
Un
Par. 1.11
U[V]
f[Hz]
Par. 1.13
(Def. 50%)
Par. 1.14
(Def. 0.0%)
Default: Nominal
voltage of the m otor
Field weakening
point
Default: Nominal
frequency of t he
motor
Par. 1.12 (Def. 10%)Pa r. 1.10
64 • vaconparameter descriptions
Figure 9.2: Programmable U / f curve
1.10 FIE LDWEAKENINGPOINT
The field weakening point is the output frequency at which the output voltage
reaches the value set with par. 1.11.
1.11 FIE LDWEAKENINGPOINTVOLTAGE
Above the frequency at the field weakening point, the output voltage remains
at the value set with this parameter. Below the frequency at the field weakening point, the output voltage depends on the setting of the U / f curve parameters. See parameters 1.9-1.14 and Figures 9.1 and 9.2.
When the parameters 1.1 and 1.2 (nominal voltage and nominal frequency of
the motor) are set, the parameters 1.10 and 1.11 are automatically given the
corresponding values. If you need different values for the field weakening
point and the voltage, change these parameters after setting the parameters
1.1 and 1.2.
1.12 U / FMIDDLE POINTFREQUENCY
If the programmable U / f curve has been selected with the parameter 1.9, this
parameter defines the middle point frequency of the curve. See Figure 9.2.
1.13 U / FMIDDLE POINTVOLTAGE
If the programmable U / f curve has been selected with the parameter 1.9, this
parameter defines the middle point voltage of the curve. See Figure 9.2.
1.14 ZEROFREQUENCYVOLTAGE
This parameter defines the zero frequency voltage of the curve. See Figures
9.1 and 9.2.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 65
1.15 TORQUEBOOST
When this parameter has been activated, the voltage to the motor changes automatically with high load torque which makes the motor produce sufficient
torque to start and run at low frequencies. The voltage increase depends on
the motor type and power. Automatic torque boost can be used in applications
with high load torque, e.g. in conveyors.
0 = Disabled
1 = Enabled
Note: In high torque - low speed applications - it is likely that the motor will
overheat. If the motor has to run a prolonged time under these conditions,
special attention must be paid to cooling the motor. Use external cooling for
the motor if the temperature tends to rise too high.
Note: The best performance can be reached by running motor identification,
see par. 1.18.
1.16 SWI TCHINGFREQUENCY
Motor noise can be minimised using a high switching frequency. Increasing
the switching frequency reduces the capacity of the frequency converter unit.
Switching frequency for Vacon 10: 1.5…16 kHz.
1.17 BRAKECHOPPER
Note! An internal brake chopper is installed in three phase supply MI2 and MI3
size drives.
0 = Disable (No brake chopper used)
1 = Enable: Always (Used in Run and Stop state)
2 = Enable: Run state (Brake chopper used in Run state)
When the frequency converter is decelerating the motor, the energy stored to the inertia of the motor and the load are fed into an external brake resistor, if the brake
chopper has been activated. This enables the frequency converter to decelerate the
load with a torque equal to that of acceleration (provided that the correct brake resistor has been selected). See separate Brake resistor installation manual.
1.18 MOTORIDENTIFICATION
0 = Not active
1 = Standstill identification
When Standstill identification is selected, the drive will perform an ID-run
when it is started from selected control place. Drive has to be started within
20 seconds, otherwise identification is aborted.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
66 • vaconparameter descriptions
The drive does not rotate the motor during Standstill identification. When ID
run is ready the drive is stopped. Drive will start normally, when the next start
command is given.
After end the identification, the drive need stop the start command. If control
place is Keypad, user need press stop button. If control place is IO,user need
put DI(Control signal) inactivate. If control place is fieldbus, user need set the
control bit to 0.
The ID run improves the torque calculations and the automatic torque boost
function. It will also result in a better slip compensation in speed control
(more accurate RPM).
The parameters below will change after ID run successfully,
a. P1.9 U / f ratio
b. P1.12 U / f mid point frequency
c. P1.13 U / f mid point voltage
d. P1.14 Zero freq voltage
e. P1.18 Motor identification (1->0)
f. P1.19 Rs voltage drop
Note!The nameplate data of the motor has to be set BEFORE doing ID run.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 67
9.2 Start / stop setup (Control panel: Menu PAR -> P2)
2.1 REMOTECONTROLPLACE 1 SELECTION
With this parameter, the user can select the active control place. The selections are:
0 = I / O terminal (frequency reference can be selected with P3.3)
1 = Fieldbus
The priority order of selecting the control place is:
1. Force to I/O when the digital input of P5.13 (Force to I/O) is active.
2. Loc/Rem button or P2.5 (Local/Remote) =1.
3. Determined by P2.1 (Remote Control Place Selection).
Note: You can select control place by pressing Loc / Rem button or with par.
2.5, P2.1 will have no effect in local mode.
Local = Keypad is the control place
Remote = I / O terminal or FieldBus
2.2 STARTFUNCTION
The user can select two start functions for Vacon 10 with this parameter:
0 = Ramp start
The frequency converter starts from 0 Hz and accelerates to the set
frequency reference within the set acceleration time (See detailed description: ID103). (Load inertia, torque or starting friction may cause
prolonged acceleration times).
1 = Flying start
With this function the drive identifies the speed of the motor and starts
to the corresponding frequency immediately.
Use this mode if the motor is rotating when the start command is given. With the flying start, it is possible to ri de through short mains voltage interruptions.
2.3 STOPFUNCTION
Two stop functions can be selected in this application:
0 = Coasting
The motor coasts to a halt without control from the frequency converter after the Stop command.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
68 • vaconparameter descriptions
1 = Ramping
After the Stop command, the speed of the motor is decelerated according to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an external braking resistor for to be able to decelerate the motor in acceptable time.
2.4 I / O STARTSTOPLOGIC
Values 0...3 offer possibilities to control the starting and stopping of the AC
drive with digital signal connected to digital inputs. CS = Control signal.
The selections including the text 'edge' shall be used to exclude the possibility
of an unintentional start when, for example, power is connected, re-connected
after a power failure, after a fault reset, after the drive is stopped by Run Enable (Run Enable = False) or when the control place is changed to I / O control.
The Start / Stop contact must be opened before the motor can be started.
Accurate stop mode is that the stop time is fixed from falling edge of DI to motor stop.
Selection
Selection nameNote
number
CS1:Forward
0
CS2:Backward
Output
FWD
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start butt on
Keypad
stop button
12 34 56 78 9
The functions take place when the contacts are closed.
Figure 9.3: Start/Stop logic, selection 0
t
10 11 12 13
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 69
Explanations
1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs
forward.
2 CS2 activates which, however, has no
effect on the output frequency because
the first selected direction has the highest priority.
3 CS1 is inactivated which caused the
direction to start changing (FWD to REV)
because CS2 is still active.
4 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
5 CS2 actives again causing the motor to
accelerate (REV) towards the set frequency.
6 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
7 CS1 actives and the motor accelerates
(FWD) towards the set frequency.
8 Run enable signal is set to FALSE, which
drops the frequency to 0.The run enable
signal is configured with par. 5.7.
9 Run enable signal is set to TRUE, wh ich
causes the frequency to rise towards the
set frequency because CS1 is still active.
10 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
11 The drive starts through pushing the
Start button on the keypad.
12 The keypad stop button is pushed again
to stop the drive.
13 The attempt to start the drive through
pushing the Start button is not successful because CS1 is inactive.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
70 • vaconparameter descriptions
Selection
number
Selection nameNote
CS1:Forward(edge)
1
CS2:Inverted stop
Output
FWD
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
stop button
1234 5 6789
Figure 9.4: Start/Stop logic, selection 1
Explanations
1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs
forward.
2 CS2 inactivates causing the frequency to
drop to 0.
3 CS1 inactivates causing the output fre-
quency to rise again. The motor runs
forward.
4 Run enable signal is set to FALSE, which
drops the frequency to 0. The run enable
signal is configured with par. 5.7.
5 Start attempt with CS1 is not successful
because Run enable signal is still
FAL SE.
t
6 CS1 ac tivates and the motor accelerates
(FWD) towards the set frequency
because the Run enable signal has been
set to TRUE.
7 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
8 CS1 activates causing the output fre-
quency to rise again. The motor runs
forward.
9 CS2 in activates causing the frequency to
drop to 0.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
FWD
REV
Set
frequency
Set
frequency
0 Hz
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
stop button
12 356 78 9
10 11 12
Output
frequency
t
`
4
parameter descriptionsvacon • 71
Selection
number
2
Explanations:
1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs
forward.
2 CS2 activates which, however, has no
effect on the output frequency because
the first selected direction has the highest priority.
3 CS1 is inactivated which causes the
direction to start changing (FWD to REV)
because CS2 is still active.
4 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
5 CS2 ac tivates again causing the motor to
accelerate (REV) towards the set frequency.
6 CS2 ina ctivates and the frequency fed to
the motor drops to 0.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Selection nameNote
CS1:Forward(edge)
CS2:Backward(edge)
Shall be used to exclude the possibility of an
unintentional start. The Start / Stop contact must
be opened before the motor can be restarted.
Figure 9.5: Start/Stop logic, selection 2
7 CS1 ac tivates and the motor accelerates
(FWD) towards the set frequency.
8 Run enable signal is set to FALSE, which
drops the frequency to 0.The run enable
signal is configured with par. 5.7.
9 CS1 act ivates again causing the motor to
accelerate (REV) towards the set frequency.
10 CS1 activates again causing the motor to
accelerate (REV) towards the set frequency.
11 CS1 inactivates and the frequency fed to
the motor drops to 0.
9
72 • vaconparameter descriptions
Selection
number
Selection nameNote
CS1:Start
3
CS2:Reverse
Output
FWD
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start butt on
Keypad
stop button
123 4 567 89
Figure 9.6: Start/Stop logic, selection 3
Explanations:
1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs
forward.
2 CS2 activates which causes the direction
to start changing (FWD to REV).
3 CS2 is inactivated which causes the
direction to start changing (REV to FWD)
because CS1 is still active.
4 Also CS1 inactivates and the frequency
drops to 0.
5 Despite the activates of CS2,the motor
does not start because CS1 is inactive.
6 CS1 activates causing the output fre-
quency to rise again. The motor runs
forward because CS2 is inactive.
t
1011 12
7 R un enable signal i s set to FA LSE, whi ch
drops the frequency to 0.The run enable
signal is configured with par. 5.7.
8 Run enable signal is set to TRUE, which
causes the frequency to rise towards the
set frequency because CS1 is still active.
9 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
10 The drive starts through pushing the
Start button on the keypad.
11 The drive is stopped again with the Stop
button on the Keypad.
12 The attempt to start the drive through
pushing the Start button is not successful because CS1 is inactive.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 73
2.5 LOCAL / REMOTE
This parameter defines whether the control place of the drive is remote (I / O
or FieldBus) or local.
0 = Remote Control
1 = Local Control
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
74 • vaconparameter descriptions
9.3 Frequency references (Control panel: Menu PAR -> P3)
Preset speeds 0 - 7 can be used to determine frequency references that are
applied when appropriate combinations of digital inputs are activated. Preset
speeds can be activated from digital inputs inputs when Par.3.3 (Remote control place frequency reference selection) =1.
Parameter values are automatically limited between the minimum and maximum frequencies. (par. 3.1, 3.2).
9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
4.1 RAMP S-SHAPE
The start and end of the acceleration and deceleration ramp can be smoothed
with this parameter. Setting value 0 gives a linear ramp shape which causes
acceleration and deceleration to act immediately to the changes in the reference signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped acceleration/deceleration. The acceleration and deceleration times are determined
with parameters 4.2 and 4.3.
Figure 9.7: S-shaped acceleration/deceleration
4.2 ACCELERAT IONTIME 1
4.3 DECELERATIONTIME 1
4.4 RAMP S-SHAPE 2
4.5 ACCELERATIO NTIME 2
4.6 DECELERATIONTIME 2
These limits correspond to the time required for the output frequency to accelerate from the zero frequency to the set maximum frequency, or to decelerate from the set maximum frequency to zero frequency.
The user can set two different acceleration/deceleration time and set two different ramp s-shape for one application.The active set can be selected with
the selected digital input (par. 5.11).
4.7 FLUXBRAKING
Instead of DC braking, flux braking is a useful form of braking with motors of
max. 15 kW.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
76 • vaconparameter descriptions
When braking is needed, the frequency is reduced and the flux in the motor is
increased, which in turn increases the motor's capability to brake. Unlike DC
braking, the motor speed remains controlled during braking.
0 = Off
1 = Deceleration
2 = Chopper
3 = Full Mode
Note: Flux braking converts the energy into heat at the motor, and should be
used intermittently to avoid motor damage.
4.10 STO P DC CURRENTTIME
Determines if braking is ON or OFF and the braking time of the DC-brake
when the motor is stopping. The function of the DC-brake depends on the stop
function, par. 2.3.
0 = DC brake is not active
>0 = DC brake is active and its function depends on the Stop function,
(par. 2.3). The DC braking time is determined with this parameter.
Par. 2.3 = 0 (Stop function = Coasting):
After the stop command, the motor coasts to a stop without control from the
frequency converter.
With the DC injection, the motor can be electrically stopped in the shortest
possible time, without using an optional external braking resistor.
The braking time is scaled by the frequency when the DC-braking starts. If the
frequency is greater, or equal to the nominal frequency of the motor, the set
value of parameter 4.10 determines the braking time. For example, when the
frequency is 10% of the nominal, the braking time is 10% of the set value of
parameter 4.10.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
f
n
f
n
t
t
t=1xpar. 4.10
t=0,1x par.4.10
0,1 x f
n
RUN
STOP
RUN
STOP
Outputf requency
Motorspeed
Output frequency
Motor speed
DC-brakingO N
DC-braking ON
f
out
f
out
t=par.4.
t
Par. 4.1
Motorspeed
Output frequ
ency
DC- brak in g
RUN
STOP
f
out
1
10
parameter descriptionsvacon • 77
Figure 9.8: DC-braking time when Stop mode = Coasting
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the
set deceleration parameters, if the inertia of the motor and load allows that,
to the speed defined with parameter 4.11, where the DC-braking starts.
The braking time is defined with parameter 4.10. See Figure 9.9.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Figure 9.9: DC-braking time when Stop mode = Ramp
9
78 • vaconparameter descriptions
t
Pa r4.12
Par 4.9
RUN
STO P
Output
frequency
DC-bra king
current
4.11 STO P DC CURRENTFREQUENCY
It is the output frequency at which the DC-braking is applied.
4.12 STAR T DC CURRENTTIME
DC-brake is activated when the start command is given. This parameter defines the time of the DC-braking. After the brake is released, the output frequency increases according to the set start function by par. 2.2.
Figure 9.10: DC braking time at start
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 79
9.5 Digital inputs (Control panel: Menu PAR -> P5)
These parameters are programmed using the FTT-method (Function To Terminal), where you have a fixed input or output that you define a certain function for. You can also define more than one function to a digital input, e.g. Start
al 1 and Preset Speed B1 to DI1.
sign
The selections for these parameters are:
0 = Not used
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
6 = DI6
5.1 I / O CTRLSIGNAL 1
5.2 I / O CTRLSIGNAL 2
5.3 REVERSE
The digital input only active when P2.4 (I/O Start stop logic) =1
The motor will run in reverse when the rising edge of P5.3 is happened.
5.4 EXTERNALFAULTCLOSE
5.5 EXTERNALFAULTOPEN
5.6 FAULTRESET
5.7 RUNENABLE
5.8 PRESETSPEED B0
5.9 PRESETSPEED B1
5.10 PRESETSPEED B2
5.11 RAMPTI ME 2 SELECTION
Contact open: Acceleration / Deceleration time 1 and Ramp S-shape
selected
Contact closed: Acceleration / Deceleration time 2 and Ramp S-shape2
selected
Set Acceleration / Deceleration times with parameters 4.2 and 4.3 and the alternative ramp times with 4.4 and 4.5.
Set Ramp S-shape with Par. 4.1 and the alternative Ramp S-shape2 with
Par. 4.4
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
80 • vaconparameter descriptions
%
100%
63%
Par. 6 .4
Par. 6 .8
t[s]
Filtered signal
Unfiltered signal
9.6 Analogue inputs (Control panel: Menu PAR -> P6)
6.4 AI1 FILTERTIME
6.8 AI2 FILTERTIME
This parameter, given a value greater than 0, activates the function that filters
out disturbances from the incoming analogue signal.
Long filtering time makes the regulation responseslower. See
6.2 AI1 CUSTOMMINI MUM
6.3 AI1 CUSTOMMAXI MUM
6.6 AI2 CUSTOMMINI MUM
6.7 AI2 CUSTOMMAXI MUM
These parameters set the analogue input signal for any input signal span from
-100 to 100%.
Figure 9.11: AI1 and AI2 signal filtering
Figure 9.11.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 81
9.7 Digital outputs (Control panel: Menu PAR -> P8)
8.1 RO1 SIGNALSELECTION
8.2 RO2 SIGNALSELCETION
8.3 DO1 SIGNALSELCETION
SettingSignal content
0 = Not used
1 = ReadyThe frequency converter is ready to operate.
2 = Run
3 = Faul tA fault trip has occurred.
4 = Faul t inver ted
5 = Warn ingA warning is active.
6 = Reversed
7 = At speedThe output frequency has reached the set reference.
8 = Motor regulator active
9 = FB Con trol Word.B13
10 = FB C ontrol Word.B 14
11 = FB C ontrol Word.B 15
Table 9.2: Output signals via RO1, RO2 and DO1
Output is not in operation.
The frequency converter operates (motor is running).
A fault trip has not occurred.
everse command has been selected, output fre-
The r
quency to the motor is negative.
Each of motoring current regulator,generating current
reg. ,over voltage reg. ,under voltage reg. is active.
Output can be controlled with B13 in the fie ldbus control
Output can be controlled with B14 in the fie ldbus control
Output can be controlled with B15 in the fie ldbus control
word.
word.
word.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
82 • vaconparameter descriptions
9.8 Analogue outputs (Control panel: Menu PAR -> P9)
9.1 ANALOGOUTPUTSIGNALSELECTION
9.2 ANALOGOUTPUTMINIMUM
0 = Not used
1 = Output frequency (0 - f
2 = Output current (0 - I
3 = Motor torque (0 - T
4 = PID output (0 - 100%)
0 = 0 mA
1 = 4 mA
nMotor
max
nMotor
)
)
)
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 83
f
I
Inmotor *1.3
25Hz
Stall ar ea
9.9 Protections (Control panel:Menu Par->P13)
13.5 STA LLPROTECTION
13.6 UNDERLOADPROTECTION
0 = No action
1 = Alarm
2 = Fault, coast
The motor stall protection protects the motor from short time overload situations such as one caused by a stalled shaft. The stall current is I
stall time 15 seconds and stall frequency limit 25 Hz . If the current is higher
than the limit and output frequency is lower than the limit, the stall state is
true and the drive reacts according to this parameter. There is actually no real
indication of the shaft rotation.
Figure 9.12: Stall characteristics
nMotor
0 = No action
1 = Alarm
2 = Fault, coast
The purpose of the motor underload protection is to ensure that there is load
on the motor when the drive is running. If the motor loses its load there might
be a problem in the process, e.g. a broken belt or a dry pump.
The underload protection time limit is 20 seconds, which is the maximum time
allowed for an underload state to exist before causing a trip according to this
parameter.
*1.3,
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
Underload curve at
zero freq. = 10%
f
5 Hz
Underl oad curve a t
nominal freq. = 50 %
Field we akening
point, P1.11
Underload area
To rq ue
84 • vaconparameter descriptions
Figure 9.13: Underload protection
13.7 MOTORTHERM ALPROTECTION
The motor thermal protection is to protect the motor from overheating. The drive is
capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that the motor will be thermally overloaded. This is
the case especially at low frequencies. At low frequencies the cooling effect of the
motor is reduced as well as its capacity. If the motor is equipped with an external fan
the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output
current of the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current
IT specifies the load current above which the motor is overloaded. This current limit
is a function of the output frequency.
0 = No action
1 = Alarm
2 = Fault, coast
If tripping is selected the drive will stop and activate the fa ult stage, if the temperature of the motor becomes too high. Deactivating the protection, i.e. setting parameter to 0, will reset the thermal model of the motor to 0%.
CAUTION! The calculated model does not protect the motor if
the airflow to the motor is reduced by blocked air intake grill.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 85
f
f
n
par.= 40%
0
I
100%
Overload area
cooling
.913
13.8 MTP:AMBIENT TEMPERATURE
When the motor ambient temperature must be taken into consideration, it is
recommended to set a value for this parameter. The value can be set between
-20 and 100 degrees Celsius.
13.9 MTP:ZEROSPEEDCOOLING
The cooling power can be set between 0 - 150.0% x cooling power at nominal
frequency. See Figure 9.14.
P
T
Figure 9.14: Motor cooling power
13.10 MTP:THERMALTIMECONSTANT
This time can be set between 1 and 200 minutes.
This is the thermal time constant of the motor. The bigger the motor, the longer the time constants. The time constant is the time within which the calculated thermal model has reached 63% of its final value.
The motor thermal time is specific to the motor design and it varies between
different motor manufacturers.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate
at six times the rated current) is known (given by the motor manufacturer) the
time constant parameter can be set basing on it. As a rule of thumb, the motor
thermal time constant in minutes equals to 2 x t6. If the drive is in stop state
the time constant is internally increased to three times the set parameter value. See also Figure 9.15.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
86 • vaconparameter descriptions
Mot or t empera ture
105%
Moto r
current
I/I
T
Tri p ar ea
Time cons tant T
Motor te mperat ure
*)
Changesby motor size and
adjusted with parameter
*)
Q=(I/IT)2x(1-e
Figure 9.15: Motor temperature calculation
-t/T
)
.1013
/warning
Fault
activ ation point,
with
if selec ted
par.
.713
Time
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 87
Fault t rigger
Motor stop signal
Mot or
start signal
Su perv isio n
Restart 1Restart 2
Trial time
par.14.3
Fa ul t act i ve
RESET/
Fault reset
Autoreset function: (Trials = 2)
Wait time
par.14.2
Wait t ime
par.1 4.2
Wait ti me
par.14. 2
9.10 Automatic reset (Control panel: Menu PAR -> P14)
14.1 AUT OMATICRESET
Activate the Automatic reset after fault with this parameter.
NOTE: Automatic reset is allowed for certain faults only.
Fault: 1. Under voltage
2. Over voltage
3. Over current
4. Motor temperature
5. Under load
14.3 TRIALTIME
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first autoreset. If the number of faults occurring during the trial time exceeds three, the fault state becomes active. Otherwise the fault is cleared after the trial time has elapsed and the next fault
starts the trial time count again. See Figure 9.16.
If a single fault remains during the trial time, a fault state is true.
Figure 9.16: Example of Automatic restarts with two restarts
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
88 • vaconparameter descriptions
Analogue input
9.11 PI control parameters (Control panel: Menu PAR -> P15)
15.7 P GAIN
This paramete r defines the gain of the PI controller. If the value of the pa rameter is set to 100%, a change of 10% in the error value caus es the controller
output to change by 10%.
15.8 I-TIME
This para meter defines the integrati on time of the PI cont roller. If this parameter is set to 1,00 second, the controller output is changed b y a value corre sponding to th e output caused from the gain every second. (G ain*Error)/s.
15.5 FEEDBACK VALUE MINIMUM
15.6 FEEDBACK VALUE MAXIMUM
This parameter sets the minimum and maximum scaling points for feedback
value.
Controller
feedback(%)
par. 15.6
9
par. 15.5
0V
Custom min
par.6.2/6.6
0mA
Figure 9.17: Feedback minimum and maximum
Cus tom max
par.6.3 /6.7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
10V
20mA
with custom
min and max
scaling (%)
parameter descriptionsvacon • 89
9.12 Application setting (Control panel: Menu PAR->P17)
17.1 DRIVESETUP
With this parameter you can easily set up your drive for four different applications.
Note! This parameter is only visible when the Startup Wizard is active. The
startup wizard will start in first power-up. It can also be started as follows.
See the figures below.
NOTE! Running the startup wizard will always re turn all parameter
settings to their factory defaults!
RUN
REF
MON
PAR
SYS
FWD R EV I/O K EY PAD BUS
FAULTALARMSTOPREADY
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
OK
1
Enter Pa r. menu, select
P1.3 motor nominal speed
REF
MON
PAR
SYS
FWD R EV I/O KEY PA D BUS
FAULTALARMSTOPREADY RUN
2
Press OK ent er
edit mode
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
OK
P1.3
Change
3
with Up/Down button
and press OK to
comfirm
value
Perform the same
4
procedure for P1.4,
motor nomi nal current
Figure 9.18: Startup wizard
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
*Same as drive voltage,
except in 115V drives
this value is 230V
Parameters
affected:
Figure 9.19: Drive setup
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
BUSFWD REV I/O KEYPAD
OK
Press OK to enter
2
edit mode.
0=
0=
1,5 x
I
1,1 x
I
1,1 x
I
1,5 x
I
NMOT
NMOT
NMOT
NMOT
Not
Frequecny
used
control
0=
0=
Not
Frequecny
used
control
0=
0=
Not
Frequecny
control
used
1=Open
1=
loop speed
used
ontrol
P1.1 Motor Un (V)
P1.2 Motor fn (Hz)
P1.7 Current limit (A)
P1.8 Motor control mode
P1.15 Torque boost
P2.1 Control place
P2.2 Start function
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
I/O
I/O
I/O
I/O
OK
Press OK to
4
confirm
drive setup
REF
MON
PAR
SYS
BUSFWD
0=
0=
0 Hz
Ramp
Coast
0=
20 Hz
Ramp1=Ramp
1=
0=
20 Hz
Flying
Coast
0=
0=
0 Hz
Ramp
Coast
P2.3 Stop function
P3.1 Min frequency
P3.2 Max frequency
P3.3 I/O reference
P4.2 Acc. time (s)
P4.3 Dec time (s)
READY RUN STOP ALARM FAULT
REV I/O KEYPAD BUS
Select between
3
0-3, see below!
50/60
4=AI1
3s 3s
Hz
0-10V
50/60
4=AI1
5s 5s
Hz
0-10V
4=AI1
50/60
Hz
50/60
Hz
0-10V
4=AI1
0-10V
20s20s
1s 1s
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 91
ON
OFF
9.13 Modbus RTU
Vacon 10 has a built-in Modbus RTU bus interface. The signal level of the interface
is in accordance with the RS-485 standard.
The built-in Modbus connection of Vacon 10 supports the following function codes:
Funct ion
code
Table 9.3: Modbus RTU
9.13.1 Termination resistor
The RS-485 bus is terminated with termination resistors of 120 ohms in both ends.
Vacon 10 has a built-in termination resistor which is switched off as a default (presented below). The termination resistor can be switched on and off with the right
hand dip switch located above IO-terminals in the front of the drive (see below).
9.13.2 Modbus address area
The Modbus interface of Vacon 10 uses the ID numbers of the application parameters
as addresses. The ID numbers can be found in the parameter tables in chapter 8.
When several parameters / monitoring values are read at a time, they must be consecutive. 11 addresses can be read and the addresses can be parameters or monitoring values.
Function nameAddress
03Read Holding Registers Al l ID numbersNo
04Read Input RegistersAll ID numbersNo
06Write Single RegistersAll ID numbersYes
16Write multiple registers All ID numbersYes
Figure 9.20: Vacon 10 I/O
Broadcast
messages
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
92 • vaconparameter descriptions
9.13.3 Modbus process data
Process data is an address area for fieldbus control. Fieldbus control is active when
the value of parameter 2.1 (Control place) is 3 (= fieldbus). The content of the process
data has been determined in the application. The following tables present the process data contents in the General Purpose Application.
IDModbus register NameScaleTy pe
210132101, 42101FB Status Word-Binary coded
210232102, 42102FB General Status Word -Binary coded
210332103, 42103FB Actual Speed0,01%
210432104, 42104Output frequency0.01+/- Hz
210532105, 42105Motor speed1+/- Rpm
210632106, 42106Motor current0.01A
200132001, 42001FB Control Word-Binary coded
200232002, 42002FB General Control Word -Binary coded
200332003, 42003FB Speed Reference0,01%
200432004, 42004Programmable by P15.1
200532005, 42005Programmable by P15.4
200632006, 42006--200732007, 42007--200832008, 42008--200932009, 42009--201032010, 42010--201132011, 42011---
Table 9.5: Input process data
Note! 2004 can set as PI Control Reference by setting P15.1(Setpoint se-
lection) or 2005 can be set as PI Actual value by setti ng P15.4(Feedback value selection)!
+/- % (of nominal)
+/- % (of nominal)
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptionsvacon • 93
Status word (output process data)
Information about the status of the device and messages is indicated in the Status
word. The Status word is composed of 16 bits the meanings of which are described
in the table below:
Bit
B0, RDYDrive not readyDrive ready
B1, RUNStopRun
B2, DIRClockwiseCounter-clockwise
B3, FLTNo faultFault active
B4, WNo alarmAlarm active
B5, AREFRampingSpeed reference reached
B6, Z-Drive is running at zero speed
B7 - B15--
Table 9.6: Status word (output process data)
Value = 0Valu e = 1
Actual speed (output process data)
This is actual speed of the frequency converter. The scaling is -10000...10000. The
value is scaled in percentage of the frequency area between set minimum and maximum frequency.
Control word (input process data)
The three first bits of the control word are used to control the frequency converter.
By using control word it is possible to control the operation of the drive. The meanings of the bits of control word are explained in the table below:
Bit
B0, RUNStopRun
B1, DIRClockwiseCounter-clockwise
B2, RSTRising edge of this bit will reset active fault
Table 9.7: Control word (input process data)
Valu e = 0Value = 1
Description
Description
Speed reference (input process data)
This is the Reference 1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 0...10000. The value is scaled in percentage of the frequency area between the set minimum and maximum frequencies.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
94 • vacontechnical data
10. TECHNICAL DATA
10.1 Vacon 10 technical data
Mains
connection
Supply network
Motor
connection
Control
characteristics
Table 10.1: Vacon 10 technical data
Input voltage U
Input frequency45…66 Hz
Line current THD> 120%
Connection to mains
Networks
Short circuit current
Output voltage
Output current
Starting current /
que
tor
Output frequency0…320 Hz
Frequency resolution
Control method
Switching frequency1...16 kHz; Factory default 4 kHz
Frequency referenceResolution 0.01 Hz
Field weakening point 30…320 Hz
Acceleration time0.1…3000 sec
Deceleration time0.1…3000 sec
Once per minute or less (normal case)
Vacon 10 (400 V) cannot be used with corner grounded
s
network
Maximum short circuit current has to be < 50 kA.
0 - U
in
Continuous rated current I
max. +50 ºC (depends on the unit size), overload
1.5 x I
max.
N
1 min / 10 min
Current 2 x I
depends on motor
0,01 Hz
Frequency Control U / f
Open Loop Sensorless Vector Control
100%*T
) 30%*T
for 2 sec in every 20 sec period. Torque
N
with brake option (only in 3~ drives sizes MI2-5
N
without brake option
N
at ambient temperature
N
10
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
technical datavacon • 95
-10 °C (no frost)…+40 / 50°C (depends on the unit size):
a
ted loadability I
Ambient operating
temperature
Storage temperature -40°C…+70°C
Relative humidity
Air quality:
Ambient
conditions
EMC
- chemical vapours
- mech. particles
Altitude
Vibration:
EN60068-2-6
Shock
IEC 68-2-27
Enclosure classIP20 / IP21 / Nema1 for MI1-3.
Pollution degree
ImmunityComplies with EN50082-1, -2, EN61800-3
Emissions
Standards
Certificates
and manufacturer’s declarations o f
con
formity
Table 10.1: Vacon 10 technical data
r
Side by side installation for MI1-3 it is always 40°C; For
IP21/Nema1 option in MI1-3 the maximum temparture
is also 40 °C.
0…95% RH, non-condensing, non-corrosive, no dripping
er
wat
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1000 m. 1% derating for each 100 m above 1000 m; max. 2000 m
3...150 Hz
Displacement amplitude 1(peak) mm at 3...15.8 Hz Max
e
acc
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
PD2
230V : Complies with EMC cate gory C2; With an internal
RFI fi
400V: Complies with EMC category C2; With an internal
RFI fi
Both: No EMC emission protection (Vacon level N):
Without RFI filter
For EMC: EN61800-3,
For safety: UL508C, EN61800-5
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed approvals)
N
leration amplitude 1 G at 15.8...150 Hz
lter.
lter
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com