Boiler installation shall be completed by qualied agency.
Become familiar with symbols identifying potential
hazards.
This is the safety alert symbol. Symbol alerts you to
potential personal injury hazards. Obey all safety messages
following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not
avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal
injury.
!
WARNING
All boiler and venting installations shall be done
by qualied agency and in accordance with
and Maintenance Manual. Installing or venting boiler
or any other appliance with improper methods or
materials could result in serious injury or death due
to re or to asphyxiation from poisonous gases such
as carbon monoxide which is odorless and invisible.
!
WARNING
Modication, substitution or elimination of factory
equipped, supplied or specied components could
result in death or serious injury.
Keep boiler area clear and free from combustible
materials, gasoline and other ammable vapors and
liquids.
DO NOT obstruct air openings to boiler room.
To the owner: Installation and service of this boiler must
be performed by qualied installer.
To the installer: Leave all instructions with boiler for
future reference.
Installation in Commonwealth of Massachusetts must be
performed by Licensed Plumber or Licensed Gas Fitter.
2
DIMENSIONAL DATA
DIMENSIONS
A
BOILER
SECTION
317 ⅞"11 ¼"6"
421 ½"12 ⅝"6"
525 ⅛"14 ¼"7"
629¼15 ¹⁵/16”8”
DEPTH
OF
FLUSH
JACKET
TO CENTER LINE
FLUE OUTLET
B
FRONT OF
CASING
OF
C
DIA.
OF
FLUE
OUTLET
3
BOILER RATINGS & CAPACITIES
BOILER RATINGS
(2)
NET
RATINGS
WATER
(3)
A.F.U.E.
CHIMNEY
BOILER
MODEL
NUMBER
(1)
OIL BURNER
INPUT
(3)
HEATING
CAPACITY
gph*Mbh*Mbh*Mbh
SFH-3085WSFH-3085WT0.851191039085.0%8X8X15
SFH-3100WSFH-3100WT1.0014011910384.0%8X8X15
SFH-4100WSFH-4100WT1.0014012210686.0%8X8X15
SFH-4125WSFH-4125WT1.2517515113185.0%8X8X15
SFH-4145WSFH-4145WT1.4520317315084.0%8X8X15
SFH-5160WSFH-5160WT1.6022419316885.0%8X8X15
SFH-5185WSFH-5185WT1.8525922119284.0%8X8X15
SFH-6175WSFH-6175WT1.7524521218485.0%8X8X15
SFH-6210WSFH-6210WT2.1029425221984.0%8X8X15
*
Mbh = 1,000 Btu per hour [Btu = British Thermal Unit]
1
Oil burner input based on 140,000 Btu per gallon.
2
Net AHRI water ratings shown are based on a piping and pickup allowance of 1.15. Consult manufacturer
before selecting a boiler for installation having unusual piping and pickup requirements, such as intermittent
system operation, extensive piping systems, etc.
3
Heating Capacity and AFUE based on 13.0% CO2 with -0.02” W. C. draft over re and #1 smoke or less.
Tested in accordance with U.S. Department of Energy test procedures.
Relief Valve, Temperature Pressure Gauge, Drain Valve, Wiring Harness, Burner Electrical Disconnect, Plastic
Cover, Supply Tapping-2”, Return Tapping-1 1/2”, High Limit and Circulator Control, Primary Control. For
Tankless Heater Units add Tankless Hot Water Coil and Triple Combination High Limit/Low Limit/Circulator
Control.
TANKLESS WATER HEATER CAPACITIES
BOILER
MODEL
NUMBER
INPUT
RATE
G.P.H.
TANKLESS
HEATER
NUMBER
INTERMITTENT DRAW
SFH-3085WT0.85T3310.5
SFH-3100WT1.00T33¼10.5
SFH-4100WT1.00T43¼13.5
SFH-4125WT1.25T43¾13.5
SFH-4145WT1.45T4413.5
SFH-5160WT1.60T4416.5
SFH-5185WT1.85T44¼16.5
SFH-6175WT1.75T44¼19.5
SFH-6210WT2.10T44½19.5
TANKLESS
HEATER CAPACITY
G.P.M.
BOILER
WATER CONTENT
GALS.
4
INTRODUCTION
!
WARNING
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious
injury.
• Installation must conform to requirements of the
authority having jurisdiction. Such applicable
requirements take precedence over the general
instructions of this manual.
• Install boiler in accordance with requirements of
authority having jurisdiction, or in the absence of such
requirements, CSA B139: Installation Code for Oil
Burning Equipment.
• Where required by the authority having jurisdiction,
the installation must conform to the American Society
of Mechanical Engineers Safety Code for Controls and
Safety Devices for Automatically Fired Boilers, ANSI/
ASME No. CSD-1.
• LOCATE BOILERS in front of nal position before
removing crate. Provide level solid base as near the
chimney as possible, and centrally located with respect
to heat distribution system as practical.
• Allow 24 inches in the front and top for servicing and
cleaning, or removing tankless water heating coil.
• When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to permit
replacement of another appliance such as water heater.
!
WARNING
Fire hazard. Do not install boiler on combustible
ooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
Boiler must not be installed on carpeting or vinyl ooring.
Minimum clearances to combustible construction are:
TOP .......................................... 24 IN.
FRONT ...................................... 24 IN.
FLUE CONNECTOR ........................ 9 IN.
REAR .......................................... 6 IN.
SIDES ......................................... 6 IN.
NOTICE
Clearance for access should exceed re protection
clearance.
REMOVE CRATE and plastic protective wrapper, inspect for
damage.
Move boiler to permanent position by sliding or walking.
5
VENTILATION & COMBUSTION AIR
!
WARNING
Asphyxiation, re hazard. Do not obstruct air
openings to combustion area. Follow instructions
below, to maintain adequate combustion air.
COMBUSTION AIR REQUIREMENTS
(MINIMUM OPENING IN SQUARE INCHES)
*UNCONFINED AREA**CONFINED AREA
OUTSIDE
INSIDE
OUTSIDE
INPUT
(Mbh)
119241193060
140281403570
175351754488
2034120351102
2244522456112
2454924562123
2595225965130
2945929774147
* Unconned area: A space whose volume is not less than 50 cubic feet per 1000 Btu per hour of all
appliances installed in that space (cubic feet of space = height x width x length).
** Conned area: A space whose volume is less than 50 cubic feet per 1000 Btu per hour of all appliances
installed in that space (cubic feet of space = height x width x length).
COMBUSTION AIR
1 IN2/5000Btu/HR
(PARAGRAPH 4)
COMBUSTION AIR
1 IN2/1000 Btu/HR
(MIN 100IN2) (Figure
1)
COMBUSTION AIR
1 IN2/4000 Btu/HR
(Figures 2&3)
1 IN2/2000 Btu/HR
(Figure 4)
1.
Ventilation of boiler room must be adequate enough to
provide sufcient air to properly support combustion.
2.
When boiler is located in an unconned space in a
building of conventional construction frame, masonry
or metal, inltration normally is adequate to provide
air for combustion and ventilation. However, in any
building which has been altered to conserve energy
or to minimize inltration, the boiler area should be
considered as a CONFINED SPACE. Provide combustion
air and ventilation air in accordance with the section
“Air for Combustion and Ventilation,” of NFPA 31:
Standard for the Installation of Oil-Burning Equipment.
3.
When a boiler is installed in an unconned space,
in a building of unusually tight construction, air for
combustion and room ventilation must be obtained
from outdoors or from spaces freely communicating
with the outdoors. A permanent opening or openings
having a total free area of not less than 1 square
inch per 5,000 Btu per hour of total input rating of all
appliances shall be provided. Ducts may be used to
convey make-up air from the outdoors and shall have
the same cross-sectional area of the openings to which
they are connected.
6
VENTILATION & COMBUSTION AIR
4.
When air for combustion and room ventilation is from
inside buildings, conned space shall be provided with
two permanent openings, one starting 12 inches from
the top and one 12 inches from the bottom of the
enclosed space. Each opening shall have a minimum
free area of 1 square inch per one thousand (1,000)
Btu per hour of the total input rating of all appliances
in the enclosed space, but must not be less than one
hundred (100) square inches. These openings must
freely communicate with the interior areas having
adequate inltration from the outside. See Figure #1.
5.
When the boiler is installed in a conned space and
all air is provided from the outdoors, the conned
space shall be provided with two permanent openings,
one commencing within 12 inches from the top and
one commencing 12 inches from the bottom of the
enclosure. The openings shall communicate directly, or
by ducts, with the outdoors or spaces (crawl or attic)
that freely communicate with the outdoors. One of the
following methods must be used to provide adequate
air for ventilation and combustion.
A. When directly communicating with the outdoors,
each opening shall have a minimum free area
of 1 square inch per 4,000 Btu per hour of total
input rating of all equipment in the enclosure. See
Figure #2.
B. When communicating with the outdoors by means
of vertical ducts, each opening shall have a
minimum free area 1 square inch per 4,000 Btu per
hour of total input rating of all appliances in the
enclosed space. See Figure #3.
C. If horizontal ducts are used, each opening shall
have a minimum free area 1 square inch per 2,000
Btu per hour total input rating of all appliances in
the enclosed space. See Figure #4.
D. When ducts are used, they shall be of the same
cross sectional area as the free area of the area of
the openings to which they connect. The minimum
dimension of rectangular air ducts shall not be less
than 3 inches.
6.
In calculating free area using louvers, grills or screens
for the above, consideration shall be given to their
blocking effect. Screens used shall not be smaller than
¼ inch mesh. If the free area through a design of
louver or grill is known, it should be used in calculating
the size opening required to provide the free area
specied. If the design and free area is not known,
it may be assumed that wood louvers will have 2025% free area and metal louvers and grills will have
60-75% free area. Louvers and grills shall be xed in
the open position or interlocked with the boiler so that
they are opened automatically during boiler operation.
Refer to the Combustion Air Requirements chart on
previous page for combustion air minimum opening
requirements.
Figure #1
7
Figure #2
VENTILATION & COMBUSTION AIR
Figure #3 Figure #4
8
CONNECTING SUPPLY AND RETURN PIPING
1.
Connect supply and return piping as suggested in
Figure #5, below. When boiler is used in connection
with refrigerated systems:
A. Chilled medium MUST BE IN PARALLEL with boiler.
B. Use appropriate valves to prevent chilled medium
from entering heating boiler.
2.
During heating cycle open valves A and B, close valves
C and D.
3.
During heating cooling cycle open valves C and D, close
valves A and B.
A. Maintain minimum clearance of one inch to hot
water pipes.
In air handling units where they may be exposed to
refrigerated air circulation, boiler piping system MUST be
supplied with ow control valves or other automatic means
to prevent gravity circulation of boiler water during cooling
cycle.
4.
Hot water boilers installed above radiation level must
be provided with low water device either as part of
boiler or at time of boiler installation.
5.
When boiler is connected to heating system utilizing
multiple zoned circulators, each circulator must be
supplied with ow control valve to prevent gravity
circulation.
* Reduced pressure back ow preventer must be used
under provisions required by the Environmental
Protection Agency, (EPA).
6.
Bypass piping is an option which gives ability to
adjust supply boiler water temperature to t system
or condition of installation. Although, this method of
piping is not typically required for baseboard heating
systems.
Figure #5 Typical Piping Conguration
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.