UTICA BOILERS MGB75, MGB100, MGB125, MGB150, MGB175 Installation, Operation & Maintanance Manual

...
P/N 37611601, Rev. B [02/09]
R
An I SO 9001 -2000 Ce rtifie d Company
MGB SERIES
Cast Iron Gas Fired Boilers
For Forced Hot Water
MAINTANANCE MANUAL
UTICA BOILERS
P.O. Box 4729 Utica, NY 13504-4729
MEMBER: The Hydronics Institute
MODEL NUMBERS:
MGB50 MGB75 MGB100 MGB125 MGB150 MGB175 MGB200 MGB250 MGB300
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS
H
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
TABLE OF CONTENTS
Ratings & Data - Natural Gas & Propane Gas ... 3
Installation Procedure .........................................4
Ventilation & Combustion Air ..............................5
IMPORTANT: Read the following instruc-
tions COMPLETELY before installing!!
Connecting Supply & Return Piping ...................7
Vent Installation ................................................ 11
Vent System Modification ................................. 11
Vent Damper Installation & Instructions............ 12
Connecting Gas Service ...................................13
Electrical Section ..............................................13
Wiring Diagram - 24V Standing Pilot ................14
Wiring Diagram - Intermittent Ignition ...............15
Lighting Instructions..........................................16
Normal Sequence of Operation ........................18
General Instructions ......................................... 18
Checking Gas Input Rate To Boiler .................. 20
Replacement Parts......................................22-27
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
SAFETY SYMBOLS & WARNINGS
WARNING
!
1. Keep boiler area clear and free from combustible
materials, gasoline and other flammable vapors
and liquids.
2. DO NOT obstruct air openings to the boiler room.
3. Modification, substitution or elimination of fac­tory equipped, supplied or specified components
may result in property damage, personal injury or the loss of life.
4. TO THE OWNER - Installation and service of this
boiler must be performed by a qualified installer.
5. TO THE INSTALLER - Leave all instructions with the boiler for future reference.
6. When this product is installed in the Common­wealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
The following defined symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
DANGER
!
Indicates an imminently hazardous situation
Which, if not avoided, will result in death, serious
injury or substantial property damage.
WARNING
!
Indicates a potentially hazardous situation which,
if not avoided, could result in death, serious injury
or substantial property damage.
CAUTION
!
Indicates a potentially hazardous situation which,
if not avoided, could result in minor or moderate
injury or property damage.
WARNING
!
All installations of boilers and venting should be
done only by a qualified expert and in accordance
with the appropriate manual. Installing or venting a boiler or any other gas appliance with improper methods or materials may result in serious injury or
death due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless
and invisible.
C.S.A. Certified
For Natural Gas Or Propane
2
Tested For 100 LBS.
ASME
Working Pressure
RATINGS & DATA - NATURAL GAS & PROPANE GAS
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
(1) **
I
=B=R
NetOutput
Btu/Hr
37,000 243
55,000 365
72,000 481
Boiler
No.
(1)
A
.G.
Btu/Hr.
50 50,000
75 75,000
100 100,000
A
.
I
nput
(1)
Heating
C
apacity Btu/Hr.
42,000
63,000
83,000
125 125,000 104,000 90,000 603
150 150,000 124,000 108,000
175 175,000 143,000 124,000 829
200 200,000 165,000 143,000 957
250 250,000 205,000 178,000
300 299,999 243,000 214,000 1368
EXPLANATORY NOTES
--All boilers are design certified for installation on noncombustible floor.
--For installation on combustible floors use combustible floor kit.
--Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be reduced to 10 feet. Refer to the latest
revision of NFGC part 11.
--Electric service to be 120 Volts, 15 Amps, 60 Hz.
--The MEA number for the this boiler is 19-79-E. (1) For elevations above 2000 feet, ratings should be reduced at a rate of 4% for each 1000 feet above sea
level.
(2) Base on 170° temperature in radiators. (3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and radiation.
--Net I=B=R ratings include 15% allowance for normal piping and pick-up load. Manufacturer should be consulted on installations having other than normal piping and pick-up requirements. ** For equivalent square feet of radiation, divide I=B=R output by 150.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler
Battery, High Limit Control, Vent Damper Relay, Theraltimeter Gauge, Circulator With Return Piping To Boiler, Main Gas Burners, Combination 24 Volt Gas Control (Includes Automatic Gas Valve, Gas Pressure Regulator, Automatic Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Cock, Spill Switch, Rollout Switch, Automatic Vent Damper. Not Shown Are: Wiring Harness, Thermocouple, Non-linting Safety Pilot.
OPTIONAL EQUIPMENT: Intermittent Electric Ignition Pilot System.
(2)
NetRating
Sq. Ft. HW
@ 170
o
719
1189
No.
of
Burners
1
2
2
3
3
4
4
5
6
(3)
Recommended
A
ir
C
ushion
T
ank
15 2.4
15
30 4.0
30 5.6
30 5.6
30 7.2
30 7.2
30
60 10.4
Water
C
ontent
(Gals.)
4.0
8.8
Boiler No.
50
75
100
125
150
175
Natural Gas
I
nlet*
½"
A
11"
½" 15 7
½" 15 7
½"
½"
18"
18"
½" 22¾
200 ½" 22¾" 11 ½" 8" 30¾" 38¾" 8" 1¼"
250 ¾"
265
13
300 ¾" 30½" 15¼" 9" 30¾" 42¾" 10" 1¼"
* Propane gas inlet, all units, 1/2"
" 11
"
16
Dimensions
B
5
½
" 4" 30¾" 36¼" 6"
½
" 5" 30¾" 37¾" 6"
½
" 6" 30¾" 37¼" 6½"
9
½
" 6" 30¾" 37¼" 6½"
9
½
" 7" 30¾" 37¾" 7"
½
" 7" 30¾" 38¾" 7" 1¼"
C DE
F
Pump size Supply &
Return
13¼" 8" 30¾" 40¾" 8"
3
T
appings
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
INSTALLATION PROCEDURE
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
WARNING
!
Improper installation, adjustment, alteration, service or maintenance can cause
injury or property damage.
The installation must conform to the requirements of the
1.
authority having jurisdiction or, in the absence of such requirements, to the latest revision of the National Fuel Gas Code, ANSI Z223. (Available from the American Gas Association, 8501 E. Pleasant Valley Road, Cleveland, Ohio 44134). Reference should also be made to local gas utility regulations and other codes in effect in the area in which the installation is to be made. When installed in Canada: The latest revision of the CAN1-B149.1 and/ or B149.2 Installation Codes for Gas-Burning Equipment and/or local codes.
2.
Where required by the authority having jurisdiction, the installation must conform to American Society of Me­chanical Engineers Safety Code for Controls and Safety Devices For Automatically Fired Boilers, ANSI/ASME
No.CSD-1.
3.
This boiler series is classified as a Category 1 and the vent installation shall be in accordance with Part 7 of the National Fuel Gas Code noted above when installed in the United States. In Canada refer to the CAN1-B149.1 and or B149.2 Installation Codes for Gas-Burning Equip­ment. Also refer to applicable provisions of the local build­ing codes.
4.
This boiler has met safe lighting and other performance criteria with the gas manifold and control assembly on the boiler per the latest revision of ANSI Z21.13/CGA 4.9. The boiler shall be installed such that the gas ignition
5.
system components are protected from water (drip­ping, spraying, rain, etc.) during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.). Locate boiler on level, solid base as near the chimney
6.
as possible and centrally located with respect to the heat distribution system as practical. Allow 24 inches at the front and right side for servicing
7.
and cleaning. When installed in a utility room, the door should be wide
8.
enough to allow the largest boiler part to enter, or to permit replacement of another appliance such as a water heater.
FOR INSTALLATION ON NON-COMBUSTIBLE
9.
FLOORS ONLY - For installation on combustible flooring special base must be used. (See Replacement Parts Sec­tion.) The boiler can not be installed on carpeting. Mini­mum clearances to combustible construction are:
TOP ........................................................... 18 IN.
FRONT ...............................................ALCOVE *
FLUE CONNECTOR ................................... 6 IN.
REAR ...........................................................4 IN.
CONTROL SIDE .......................................... 9 IN.
OTHER SIDE ............................................... 3 IN.
NOTE: Greater clearances for access should supersede
fire protection clearances.
* The definition of an Alcove is a three sided space with no wall in front of the boiler. The ANSI standard for an alcove is 18 inches from the front of an appliance to the leading edge of the side walls as shown below.
Minimum Clearances to Combustible Construction (as
seen from above)
4"
9"
BOILER
18"
3"
4
VENTILATION & COMBUSTION AIR
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
WARNING
!
Air openings to combustion area must not be obstructed. By following the instructions below,
adequate combustion air can be maintained.
COMBUSTION AIR REQUIREMENTS
(Minimum Square Inches Requirement)
Unconfined Area* Confined Area**
Inside
Model
* A space whose volume is not less than 50 cubic feet per 1000 BTU per hour of all appliances installed in that space (cubic feet of space = height x width x length) ** A space whose volume is less than 50 cubic feet per 1000 BTU per hour of all appliances installed in that space (cubic feet of space = height x width x length)
1.
Combustion Air
No.
1 Sq. In./1000
Btu/Hr.
(Fig. #3)
50 100 10 13 25
75 100 15 19 38
100 100 20 25 50
125 125 25 32 63
150 150 30 38 75
175 175 35 44 88
200 200 40 50 100
250 250 50 63 125
300 300 60 75 150
Ventilation of the boiler room must be adequate to provide
Outside
Combustion Air
1 Sq. In./5000
Btu/Hr.
(Fig. #4)
Outside Combustion Air
Vertical Ducts
1 Sq. In./4000
BTU/Hr.
Horizontal Ducts
1 Sq. In./2000
BTU/Hr.
sufficient air to properly support combustion per the latest revision of the National Fuel Gas Code, ANSI Z223.1.
Figure #1
CHIMNEY OR
TYPE B VENT PIPE
When a boiler is located in an unconfined space in a
2.
building or conventional construction frame, masonry or metal building, infiltration normally is adequate to provide air for combustion and ventilation. However, if the equip­ment is located in a building of tight construction (See the National Fuel Gas Code, ANSI Z223.1 latest revision), the boiler area should be considered as a confined space.
In this case air for combustion and ventilation shall be provided according to Step 5. If there is any doubt, install air supply provisions in accordance with the latest revision of the National Fuel Gas Code. When a boiler is installed in an unconfined space in a
3.
building of tight construction, air for combustion and ven­tilation must be obtained from outdoors or from spaces freely communicating with the outdoors. A permanent opening or openings having a total free area of not less than 1 square inch per 5000 Btu per hour of total input rating of all appliances shall be provided. Ducts may be used to convey makeup air from the outdoors and shall have the same cross-sectional area of the openings to which they are connected.
4.
When air for combustion and ventilation is from inside buildings, the confined space shall be provided with two permanent openings, one starting 12 inches from the top and one 12 inches from the bottom of the enclosed space. Each opening shall have a minimum free area of 1 square inch per 1000 Btu per hour of the total input rating of all appliances in the enclosed space, but must not be less than 100 square inches. These openings must freely communicate directly with other spaces of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. (Figure #1)
5.
When the boiler is installed in a confined space and all air is provided from the outdoors the confined space shall be provided with one or two permanent openings according to methods A or B. When ducts are used, they shall be of the same cross sectional area as the free area of the area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 x 3 inches or 9 square inches.
When installing two openings, one must commence with-A. in 12 inches from the top and the other within 12 inches from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. One of the following methods must be used to provide adequate air for ventilation and combustion.
5
VENTILATION AND COMBUSTION AIR
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
When directly communicating with the outdoors, each
1.
opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour of total input rating of all equip­ment in the enclosure. (Figure #2)
Figure #2
CHIMNEY OR TYPE B VENT PIPE
If horizontal ducts are used, each opening and duct shall
3.
have a minimum free area 1 square inch per 2,000 Btu per hour of total input rating of all appliances in the en­closed space. (Figure #4)
Figure #4
CHIMNEY OR TYPE B VENT PIPE
When communicating with the outdoors by means of
2.
vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour of total input rating of all appliances in the enclosed space. (Figure #3)
Figure #3
CHIMNEY OR TYPE B VENT PIPE
(DUCT ENDS 1 FT. ABOVE THE FLOOR)
One permanent opening, commencing within 12 inches A. of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides, 1 inch from the back, and 6 inches from the front of the boiler. The opening shall directly communicate with the outdoors or shall communicate through a verti­cal or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. The openings must have a minimum free area of 1 square inch per 3000 Btu per hour of the total input rating of all equipment located in the enclosure. The free area must be no less than the sum of the areas of all vent connec­tors in the confined space.
In calculating free area using louvers, grilles or screens
4.
for the above, consideration shall be given to their block­ing effect. Screens used shall not be smaller than 1/4 inch mesh. If the free area through a design of louver or grill is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will have 20-25% free area and metal louvers and grilles will have 60-75% free area. Louvers and grilles should be fixed in the open position or interlocked with the boiler so they are opened automatically during the boiler
operation.
6
CONNECTING SUPPLY & RETURN PIPING
EXPANSION
TANK
CHECK VALVE
B
D
FEED
WATER
C
RETURN PIPING
FROM HEATING AND COOLING ELEMENT
WATER CHILLER
SUPPLY PIPING
TO HEATING
AND COOLING
ELEMENT
CIRCULATOR
A
PRESSURE REDUCING VALVE
PROPER BACKFLOW PROTECTION DEVICE
GATE VALVE
PURGE VALVE
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
IMPORTANT: Circulators in the following illustrations are mounted on the system supply side, but
mounting on the system return side is also acceptable practice.
Figure #5
Connect supply and return piping as suggested in Figure
1.
#5 when the boiler is used in connection with refrigerated systems.
The chilled medium MUST BE PIPED IN PARALLEL A. with the boiler. Use appropriate valves to prevent the chilled medium B. from entering the heating boiler.
Maintain a minimum clearance of one inch to hot water C.
pipes.
2.
When the boiler is connected to heating coils located in air
- During heating cycle open valves A and B, close valves C and D.
- During cooling cycle, open valves C and D, close valves A and B.
handling units where they may be exposed to refrigerated air circulation, the boiler piping system MUST BE sup­plied with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. Hot water boilers installed above radiation level must be
3.
provided with a low water cut-off device. When a boiler is connected to a heating system that
4.
utilizes multiple zoned circulators, each circulator must be supplied with a flow control valve to prevent gravity
circulation.
Hot water boilers and system must be filled with water
5.
and maintained to a minimum pressure of 12 pounds per square inch.
7
CONNECTING SUPPLY AND RETURN PIPING
BOILER
WATER INLET
ALTERNATE
CIRCULATOR
LOCATION
TO SYSTEM
FROM SYSTEM
CIRCULATOR
SHUT-OFF VALVE
PRESSURE REDUCER VALVE
CHECK VALVE
BALL VALVE
3 WAY MIXING VALVE
AIR SEPARATOR
HOSE BIB
EXPANSION
TANK
BOILER
ALTERNATE
CIRCULATOR
LOCATION
TO SYSTEM
FROM SYSTEM
V2V1
CIRCULATOR
SHUT-OFF VALVE
PRESSURE REDUCER VALVE
CHECK VALVE
BALL VALVE
AIR SEPARATOR
ZONE VALVE
EXPANSION
TANK
WATER INLET
SYSTEM
CIRCULATOR
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
Figure #6
BYPASS PIPING -
AUTOMATIC MIXING VALVE
Bypass piping is an option which gives the ability to adjust
6.
the supply boiler water temperature to fit the system or the condition of the installation. This method of piping, however, is not typically required for baseboard heat­ing systems. Typical installations where bypass piping is used are as follows:
This method is used to protect boilers from condensation A. forming due to low temperature return water. Generally noticed in large converted gravity systems or other large water volume systems. (Figure #6) These methods are used to protect systems using radi-B. ant panels and the material they are encased in from
8
BYPASS PIPING -
FIXED LOW TEMP ONLY
high temperature supply water from the boiler and pro­tect the boiler from condensation.
NOTE#1: When using bypass piping, adjust valves V1 & V2 until desired system temperature is obtained.
NOTE#2: Bypass loop must be same size piping as the supply and return piping.
7. Installation using circulators and zone valves are shown in Figures #7-#10. For further piping information refer to the I=B=R Installation and Piping Guide.
ZONE 3
ZONE 2
ZONE 1 (PRIORITY ZONE)
BOILER
ZONE 4
DHW CIRCULATOR
WATER INLET
CIRC 2
CIRC 3
CIRC 4
CIRCULATOR
SHUT-OFF VALVE
PRESSURE REDUCER VALVE
CHECK VALVE
BALL VALVE
AIR SEPARATOR
ZONE VALVE
HOSE BIB
FLOW CONTROL VALVE
EXPANSION
TANK
BOILER
DHW
CIRCULATOR
CH CIRCULATOR
PRIORITY ZONE
CIRCULATOR
EXPANSION
TANK
WATER INLET
FLOW CONTROL VAVLE
SHUT-OFF VALVE
PRESSURE REDUCER VALVE
CHECK VALVE
BALL VALVE
AIR SEPARATOR
ZONE VALVE
HOSE BIB
CONNECTING SUPPLY AND RETURN PIPING
National Excelsior Company www.excelsiorhvac.com
Subject to change without notice.
Figure #7
SINGLE ZONE SYSTEM WITH
DHW PRIORITY
MULTIZONE SYSTEM WITH CIRCU-
LATORS AND DHW PRIORITY
Figure #8
9
Loading...
+ 19 hidden pages