* Minimum acceptable height for Low Water Cutoff probe.
Table 1 - Dimensions
DIMENSIONS (INCH.)
BOILER
MODEL
NUMBER
MGC-8727½
MGC-9730¾
Add 5½” to height for vent Damper.
FLUE
DIAMETER
“A”
WIDTH
2
2 - BOILER RATINGS AND CAPACITIES
Table 2 - Ratings and Capacities
† NATURAL GAS† PROPANE GASAFUE
(2)
BOILER
MODEL
NUMBER
(1)
Input
Mbh
(3)
(1)
Heating
Capacity
(3)
Mbh
MGC-8262.522019124520617983.9
MGC-929925121828023520483.7
†
Input rating for sea level to 2,000 ft. (610m) above sea level. Over 2000 ft (610m) above sea level.
Reduce input rate 4% for every 1000 ft (304m) above sea level.
+ Heating Capacity based on D.O.E. (Department of Energy) test procedure.
(1)
Add model number sufce ‘P’ for Propane.
(2)
Net AHRI Water rating shown based on piping and pickup allowance of 1.15. Consult manufacturer before selecting
boiler for installations having unusual piping and pickup requirements, such as intermittent system operation,
extensive piping systems, etc.
(3)
MBH = 1,000 Btuh = British Thermal Unit Per Hour
NET AHRI
RATING
Water,
(3)
Mbh
INPUT
MBH
(3)
HEATING
CAPACITY
MBH
(3)
NET AHRI
RATING
INTERMITTENT
IGNITION WITH
VENT DAMPER
Ratings marked “Net AHRI Ratings” indicate amount of remaining heat input used to heat radiation or terminal units. Net
AHRI Ratings shown are based on allowance of 1.15 in accordance with factors shown on AHRI Standard as published by
The Hydronics Institute.
-Selection of boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated heat loss of the
building.
-Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements.
BOILERS FOR USE AT HIGH ALTITUDE
Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level.
For use at altitudes above 2,000 feet above sea level, input ratings are reduced by change in main burner orice size.
For altitudes above 2,000 feet above sea level, input ratings should be reduced at rate of 4% for each 1,000 feet above
sea level. Consult National Fuel Gas Code, ANSI Z223.1/NFPA 54 or manufacturer for correct orice sizing information.
14 - Operating Your Boiler .................................. 21
15 - Maintaining Your Boiler ................................ 23
16 - Service Hints .............................................. 24
17 - Equipment And Optional Accessories ............ 25
Appendix A - Control Module ............................... 27
SAFETY SYMBOLS & WARNINGS
The following dened symbols are used throughout
this manual to notify the reader of potential hazards
of varying risk levels.
!
DANGER
Indicates a hazardous situation which, if not
avoided, WILL result in death or serious injury
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions
COMPLETELY before installing!!
!
WARNING
Fire, explosion, asphyxiation and electrical
shock hazard. Improper installation could
result in death or serious injury. Read this
manual and understand all requirements
before beginning installation.
!
WARNING
Keep boiler area clear and free from
combustible materials, gasoline and other
ammable vapors and liquids.
DO NOT obstruct air openings to the boiler
room.
Modication, substitution or elimination
of factory equipped, supplied or specied
components may result in personal injury or
loss of life.
TO THE OWNER - Installation and service of
this boiler must be performed by a qualied
installer.
TO THE INSTALLER - Leave all instructions
with boiler for future reference.
When this product is installed in the
Commonwealth of Massachusetts the
installation must be performed by a Licensed
Plumber or Licensed Gas Fitter.
!
WARNING
Indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not
avoided, could result in minor or moderate
injury.
NOTICE
Used to address practices not related to
personal injury.
4
4 - INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration,
service or maintenance could result in death or
serious injury.
1.
Installation must conform to the requirements
of the authority having jurisdiction or, in the
absence of such requirements, to the National
Fuel Gas Code, ANSI Z223.1/NFPA 54.
2.
Where required by the authority having
jurisdiction, the installation must conform to the
Standard for Controls and Safety Devices for
Automatically red Boilers, ANSI/ASME CSD-1.
3.
Boiler series is classied as a Category I. Vent
installation shall be in accordance with "Venting of
Equipment ," of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or applicable provisions of the
local building codes.
4.
Boiler has met safe lighting and other
performance criteria with the gas manifold and
control assembly on the boiler per the latest
revision of ANSI Z21.13/CGA 4.9.
5.
Install boiler such that gas ignition system
components are protected from water (dripping,
spraying, rain, etc.) during appliance operation
and service, (circulator replacement, condensate
trap, control replacement, etc.).
6.
Locate boiler on level, solid base as near chimney
as possible and centrally located with respect to
heat distribution system as practical.
7.
Allow 24 inches (610mm ) at front and right side
for servicing and cleaning.
8.
When installed in utility room, door should be
wide enough to allow largest boiler part to enter,
or to permit replacement of another appliance
such as water heater.
!
WARNING
Fire hazard. Do not install boiler on
combustible ooring or carpeting. Failure to
follow these instructions could result in death
or serious injury.
1.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY - For installation on combustible
ooring special base must be used. (See
Replacement Parts Section.) Boiler can not be
installed on carpeting.
Table 3 -
Top6”(152mm)
Rear6”(152mm)
Control Side7”(178mm)
Opposite Side6”(152mm)
Front
Flue/Vent Connector6”(152mm)
Near Boiler Piping2”(51mm)
NOTE: Greater clearances for access should supersede fire
* Denition of Alcove is three sided space with no
wall in front of boiler. ANSI standard for alcove is 18
inches from front of appliance to leading edge of side
walls as shown below.
MINIMUM CLEARANCE DIMENSIONS
Inches(mm)
18”(457mm)
protection clearances.
Minimum Clearances to Combustible
Construction (as seen from above)
6"
6"
BOILER
Front
7"
Control
Side
18"
5
5 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,”
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or
applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes
dryers, and kitchen ventilation equipment interfere
with proper operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
• Engineered Installations. Must be approved by
authority having jurisdiction.
• Mechanical Air Supply. Provide minimum of
0.35 cfm per Mbh for all appliances located
within space. Additional requirements where
exhaust fans installed. Interlock each appliance
to mechanical air supply system to prevent main
burner operation when mechanical air supply
system not operating.
• All Indoor Air. Calculate minimum allowable room
volume for all appliances in space. Use a different
method if minimum volume not available.
A. Standard Method. Cannot be used if known
air inltration rate is less than 0.40 air
changes per hour. See Table 4 for space
with boiler only. Use equation for multiple
appliances.
• All Outdoor Air. Provide permanent opening(s)
communicating directly or by ducts with outdoors.
A. Two Permanent Opening Method. Provide
opening commencing within 12 inches of top
and second opening commencing within 12
inches of bottom of enclosure.
Direct communication with outdoors or
communicating through vertical ducts.
Provide minimum free area of 1 in² per 4
Mbh of total input rating of all appliances
in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in² per 2
Mbh of total input rating of all appliances
in enclosure.
B. One Permanent Opening Method. Provide
opening commencing within 12 inches of top
of enclosure. Provide minimum clearance of
1 inch on sides/back and 6 inches on front
of boiler (does not supersede clearance to
combustible materials).
• Refer to National Fuel Gas Code for additional
requirements for louvers, grilles, screens and air
ducts.
• Combination Indoor and Outdoor Air. Refer
to National Fuel Gas Code for application
information.
Volume ≥ 50 ft3 x Total Input [Mbh]
B. Known Air Inltration Rate. See Table 4
for space with boiler only. Use equation
for multiple appliances. Do not use an air
inltration rate (ACH) greater than 0.60.
Volume ≥ 21 ft3⁄ACH x Total Input [Mbh]
C. Refer to National Fuel Gas Code for opening
requirements between connected indoor
spaces.
Table 4 - Minimum Room Volume, Indoor Air Only*
Room Cubic Feet Volume
Input
Mbh
Standard
Method
Known Air Inltration Rate Method (Air Changes Per Hour)
* Table values based on boiler only. Add volume for any additional appliances.
6
6 - CONNECTING SUPPLY AND RETURN PIPING
!
WARNING
Burn and scald hazard. Safety relief valve
could discharge steam or hot water during
operation. Install discharge piping per these
instructions.
1.
Refer to local codes and appropriate ASME Boiler
and Pressure Vessel Code for additional installation requirements. Install safety relief valve using
pipe ttings provided with boiler. See Figure 2
2.
Install safety relief valve with spindle in vertical
position.
3.
Do not install shutoff valve between boiler and
safety relief valve.
4.
Install discharge piping from safety relief valve.
See Figure 2.
• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F
(191°C) or greater.
• Individual boiler discharge piping shall be independent of other discharge piping.
• Size and arrange discharge piping to avoid
reducing safety relief valve relieving capacity
below minimum relief valve capacity stated on
rating plate.
• Run pipe as short and straight as possible to
location protecting user from scalding and properly drain piping.
• Install union, if used, close to safety relief valve
outlet.
• Install elbow(s), if used, close to safety relief
valve outlet and downstream of union (if used).
Figure 2 - Safety Relief Valve
RELIEF VALVE
DISCHARGE
LINE
Check local
codes for
maximum
distance
from oor
or allowable
safe point of
discharge.
• Terminate pipe with plain end (not threaded).
7
6 - CONNECTING SUPPLY AND RETURN PIPING
!
WARNING
Burn and scald hazard. Safety relief valve
could discharge steam or hot water during
operation. Install discharge piping per these
instructions.
1.
Boiler is shipped assembled. Install discharge
piping from safety relief valve. See Warning, Page
7.
2.
Install temperature pressure gauge.
• Apply pipe sealant to threads on shaft of
gauge.
• Thread gauge into supply water tee. See Figure
3.
NOTICE
DO NOT TIGHTEN GAUGE BY HAND!! Gauge
should be tightened using crescent wrench or
9/16” open end wrench. See Figure 3.
3.
Connect supply and return lines to boiler.
Connections may require additional ttings and
parts, as shown on diagrams.
Verify clean water supply is available to water inlet
valve. Install sand strainer when water supply is from
a well or pump.
Install hot water boiler above radiation level or as
required by Authority having jurisdiction. Install low
water cutoff device at time of installation. See Figure
1 for minimum probe height. Use kit #550002998.
Follow instruction enclosed with kit. With other
LWCO’s use their manufacturer specic instructions.
Periodic inspection is necessary, as is ushing of oat
type devices, per manufacturers specic instruction.
FOR USE WITH COOLING UNITS
A. Boiler used in connection with refrigeration
system, must be installed so that chilled medium
is piped in parallel with heating boiler. Appropriate
valves must be used to prevent chilled medium
from entering heating boiler. See Figure 5 page 9.
B. Boiler connected to heating coils located in air
handling units where they may be exposed to
refrigerated air circulation, piping system shall
be equipped with ow control valves or other
automatic means to prevent gravity circulation of
boiler water during cooling cycle.
Figure 3 - Temperature Pressure Gauge
LOW WATER TEMPERATURE AND LARGE WATER
CONTENT SYSTEM (See Figures 6 and 7, Page 10.)
Signicant condensation may form in boiler and/or
venting system if boiler is operated for long period of
time with return temperatures of less than 120° F.
Condensate is corrosive and can cause severe
damage to boiler and venting system. Minimum
design return water temperature to prevent
condensation in boiler and venting is 120°F.
Minimum high limit setting is 140°F.
1.
Boiler used in heating system where design
water temperatures below 140°F are desired
(e.g. radiant oor heating), 4-way mixing valve
or suitable alternative is required to prevent low
temperature return water from entering boiler.
Follow mixing valve manufacturer’s instructions.
2.
Boiler connected to system having large water
content (such as former gravity system), install
system bypass. See Figures 6 and 7, page 10.
3.
If boiler water reset control is used to operate
boiler, minimum reset supply water temperature
setpoint must be at least 140°F, unless mixing
valve is used as in (1) above.
8
6 - CONNECTING SUPPLY AND RETURN PIPING
Figure 4 - Typical Hot Water Piping
Figure 5 - Chilled Water Piping
9
6 - CONNECTING SUPPLY AND RETURN PIPING
Bypass Piping Required For High Mass (Large Water Content) Systems
Figure 6 - BYPASS PIPING - CIRCULATOR ON SUPPLY
Figure 7 - BYPASS PIPING - CIRCULATOR ON RETURN
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.