Utica Boilers JE Operation and Installation Manual

Page 1
JE Series
Cast Iron Commercial
Natural Gas Steam Boiler
INSTALL ATION, OPER ATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certified Company
Manufactured by:
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
P/N# 240010349, Rev. B [02/2014]
Page 2
CAST IRON HOT WATER OR STEAM BOILER
Contents
Ratings And Capacities .................................................................................................... 3
Shipment Check List ....................................................................................................... 4
Accessory Carton Check List............................................................................................. 5
Safety Information ......................................................................................................... 6
Before Installing ............................................................................................................. 7
Ventilation And Combustion Air........................................................................................8
Vent Installation ........................................................................................................... 10
Boiler Dimensions ......................................................................................................... 13
Installation – Assembly ................................................................................................. 14
Tappings ..................................................................................................................... 24
Boiler Piping ............................................................................................................... 25
Connecting Gas Service ................................................................................................. 28
Electrical Wiring ........................................................................................................... 29
Wiring Diagrams ........................................................................................................... 30
Operation And Service ................................................................................................... 31
Checking And Adjusting ................................................................................................. 33
Cleaning And Maintenance ............................................................................................. 34
Pilot System Troubleshooting Table ................................................................................. 35
SAFETY SYMBOLS
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury.
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
KEEP THIS MANUAL NEAR BOILER.
RETAIN FOR FUTURE REFERENCE.
WARNING
!
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
2
Page 3
RATINGS AND CAPACITIES
Ratings and Capacities - Chart 1
Input/Size
(Mbh)
300
400
500
600
700
800
900
1000
1100
1200
1300
Output (1)
Gross
Output
Mbh
233
310
388
465
543
620
698
775
853
930
1008
Net AHRI
Ratings (2)
Steam
(Sq
Ft)
729
971
1213
1454
1696
1938
2183
2421
2667
2908
3150
Steam
Mbh
175
233
291
349
407
465
524
581
640
698
756
Flue Outlet No. &
8” 10” 12” I.D. x Ht.
Size
1
1
1
2
1 1
2
1 1
2
1
2
3
1
2
Chimney
Size (6)
8”x20’
10”x20’
12”x20’
12”x20’
12”x20’
14”x20’
14”x20’
14”x20’
16”x20’
16”x20’
16”x20’
Flue
Collector
Size to
Chimney
8
10
12
12
12
14
14
14
16
16
16
Horse-
power
Gross
Output
(4)
6.96
9.25
11.58
13.88
16.21
18.51
20.84
23.13
25.46
27.76
30.09
Therm.
Eff.
77.0
77.0
77.0
1400
1500
1085
1163
3392
3633
814
872
1
2
3
18”x20’
18”x20
18
18
32.39
34.72
1) Ratings are at sea level to 2,000 feet. For altitudes above 2,000 feet, reduce all ratings 4% for each 1,000 feet above sea level
2) Net steam ratings based on an allowance of 1.333 (300-1500). Contact Technical Support before selecting boiler for installations having unusual piping and pick-up factors, such as intermittent system operations, extensive piping systems, etc.
3) Ratings in square feet are computed at 240 Btuh/square foot for steam boilers.
4) Ratings based on 33,500 Btuh per horsepower.
5) Pressure drop based on given ow from single outlet and returning to single inlet at the opposite end of the boiler.
6) Chimney sizes shown are one option based on a typical venting system as shown in Figure 6, and sized according to the National Fuel Gas Code, assuming Type B double wall vent and vent connectors, Other venting system designs are acceptable as shown on Flue Connection And Venting section of this manual. For further chimney design and sizing information, consult the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision, or ASHRAE HVAC Systems and Equipment Handbook, Chimney, Gas Vent, and Fireplace Systems, or the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances. NFPA 211. Follow standard engineering practice.
3
Page 4
END
BASE
*****
END
****
JACKET
**
PANEL
CARTON
PANEL
CARTON
***
TRIM
STEAM
CARTON
LESS LOW
1
ITEM #
550002860
1
ITEM #
550002871
1
CARTON
ACCESSORY
WATER
CUTOFF
1
1
1
1
1
1
41200066
SHIPMENT CHECK LIST
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
41200067
41200068
1
1
1
1
1
1
41200069
1
1
1
1
1
1
**
TRIM
STEAM
CARTON
500
400
*COMPONENT CART.
300
MODEL
KIT #
550002863
KIT #
550002862
KIT #
550002861
RIGHT
41154050
INNER
SECTIONS
41154052
-
-
1
1
2
(SA-1)
41200061
-
1
-
1
-
-
1
1
3
4
(SA-2)
41200062
-
-
-
1
2
1
1
1
5
6
-
2
-
1
7
(SA-3)
41200063
1
1
-
1
8
(SA-4)
41200064
-
2
1
1
10
-
3
-
1
11
2
-
1
1
12
2
1
-
1
13
3
-
-
1
14
2
-
-
1
9
For further component information see Parts, Kits and Optional Accessories Manual provide
with your boiler see pages listed.
* SEE PAGE 8 - COMPONENT CARTON PARTS LIST
** SEE PAGE 7 - STEAM CARTON PARTS LIST
*** SEE PAGE 3 - ACCESSORY CARTON PARTS LIST
**** SEE PAGE 8 - JACKET END PANEL CARTON PARTS LIST
***** SEE PAGE 4 - BASE PANEL CARTON PARTS LIST
LEFT
41154051
Model
1
300
1
400
1
500
1
600
1
700
1
800
1
900
1
1000
1
1100
1
1200
1
1300
1
1400
1
1500
4
Page 5
ACCESSORY CARTON CHECK LIST
ACCESSORY CARTON
BOILER MODEL NUMBERS AND QUANTITIES
PARTS
DESCRIPTION PART NO.
COMPLETE ACCY CRTN #
4” Push Nipples 43300977 6 8 10 12 14 16 18 20 22 24 26 28 30
5/8” - 11NC x 7 Stud
5/8” - 11NC Hex Nut
5/8” Flat Washer 14695306 12 16 20 24 28 32 36 40 44
Non-Asbestos Furnace Cement
- Pint
FB-1 Fitting Bag 41200051 1 1 1 - - - - - - - - - -
FB-2 Fitting Bag 41200052 - - - 1 1 1 1 1 - - - - -
FB-3 Fitting Bag 41200053 - - - - - - - - 1 1 1 1 1
3/4” Drain Valve 14622001 1 1 1 1 1 1 1 1 1 1 1 1 1
Nipple Paste ­4oz.
14695304 6 8 10 12 14 16 18 20 22 24 26 28 30
1330005 12 16 20 24 28 32 36 40 44 48 52 56 60
1440001 2 2 2 2 2 2 2 2 2 2 2 2 2
14691302 1 1 1 1 1 1 1 1 1 1 1 1 1
300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
48 52 56 60
1” Sq. Head Plugs 1395004 4 4 4 4 4 4 4 4 4 4 4 4 4
Junction Box Assembly 1-3 Base
Hercules Grrip 1/4 Pint
550002870 1 1 1 1 1 1 1 1 1 1 1 1 1
14691302 1 1 1 1 1 1 1 2 2 2 2 2 2
5
Page 6
SAFETY INFORMATION
Safety Information
IMPORTANT: Read the following instructions COMPLETELY before installing!!
When Your Boiler Arrives
When boiler arrives be sure to save and refer to instructions.
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible
materials, gasoline and other ammable vapors
and liquids. DO NOT obstruct air openings to the boiler room.
Modication, substitution or elimination of factory equipped, supplied or specied components may
result in personal injury or loss of life. TO THE OWNER - Installation and service of this
boiler must be performed by a qualied installer.
TO THE INSTALLER - Leave all instructions with boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
1.
Never test for leaks with an open ame. Use soap suds
to check all connections. This will avoid any possibility
of re or explosion.
2.
Boiler is congured for operation with natural gas. Over-ring will result in premature failure of boiler
sections and cause dangerous operation. Verify there is adequate gas supply piping.
3.
Never vent this boiler into enclosed space. Always connect boiler to chimney and vent to outside. Never vent to another room or inside abuilding.
4.
Verify there is adequate air supply for complete combustion.
5.
Follow regular service and maintenance schedule for
efcient and safe operation.
Inspect each item received for visible damage. If any parts are damaged, report this to freight company immediately and request them to call and make inspection before you make any installation. Have inspector prepare a signed report. Send copy of report to manufacturer.
We must have the signed inspection report of the freight company to prove their liability.
Read these instructions carefully before beginning the installation to be sure all packages have been received. It is recommended that you follow the step-by-step instructions for best assembly results. Before discarding any packing material carefully examine for loose parts. Also store all parts received where they will not be lost or damaged.
Codes Governing Installation
Installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA54.
Where required by the authority having jurisdiction, the installation must conform to the standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Additional controls and safety devices are required for CSD-1.
Installation
Boiler is designed to provide wide heating capacity range with multiple burner modules, each equipped with its own set of controls. For purposes of orientation, gas manifold location is considered the front. Instructions are written for assembly of boiler starting with left side and working to right side.
!
WARNING
Fire hazard. Do not install boiler on non-combustible
ooring such as carpeting or wood ooring. Failure
to follow these instructions could result in death or serious injury.
6.
DO NOT install boiler on non-combustible ooring such as carpeting or wood ooring.
6
Page 7
BEFORE INSTALLING
Boiler Location
Locate boiler on level, non-combustible foundation as near
to chimney or ue as possible. Allow 24 inches at front and
sides of boiler for servicing and cleaning. When installed in utility room, the door should be wide enough to allow the largest boiler parts to enter, or permit replacement of any other appliance in the same room. Installing contractor must provide ventilated foundation for boiler when installing:
• Over a room
Over electrical wiring or cables of any kind
If concrete oor is not cured or water is channeled under concrete oor
Minimum Vent Pipe Clearance
If the vent pipe must go through a crawl space, double wall vent pipe should be used. Where vent passes through a combustible wall or partition, use a ventilated metal thimble. The thimble should be 4 inches larger in diameter than vent pipe. If boiler is installed with single wall galvanized type vent pipe, it must have 6 inches clearance between its surface and any combustible material. If
UL listed type B (insulated) vent pipe is used, clearance
between it and combustible material to be as listed by pipe manufacturer.
Fire hazard. Do not install boiler on combustible
ooring such as carpeting or wood ooring. Failure
to follow these instructions could result in death or
Combustion Air
Provide combustion and ventilation air in accordance with the section “Air for Combustion and Ventilation”, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of the local building codes.
Chimney And Vent Pipe Connection
This is a very important part of the heating system. It must be clean, the right size, properly constructed and in Good Condition. No boiler can function properly with a bad
chimney. See Pages 8-12 for specic venting instructions.
Flue pipe should be same size as draft hood outlet from boiler to ue collector. See Chart 1 for Typical Chimney Size. Maintain a minimum upward slope of 1/4 inch per linear foot from boiler to the chimney. Fasten joints together with sheet metal screws to prevent sagging.
serious injury.
!
WARNING
CHART 2
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY,
MINIMUM CLEARANCES TO
COMBUSTIBLE CONSTRUCTION
Inputs of
400 MBH or
less
Top 52” 52”
Front 18” 18”
Flue Collector 6 “ 6”
Rear 18” 24”
Sides 18” 24”
Steam/Water
Piping
Greater clearances (24”) for access should supersede
re protection clearances.
1” 1”
Inputs over
400 MBH
7
Page 8
VENTILATION AND COMBUSTION AIR
WARNING
!
Asphyxiation hazard. Ensure enough air is available for proper combustion, avoiding hazard due to lack of oxygen.
!
WARNING
Air openings to combustion area shall not be obstructed. Follow Chart 3 to insure adequate combustion air is maintained.
COMBUSTION AIR REQUIREMENTS –
(MINIMUM SQUARE INCHES OPENING)
*UNCONFINED AREA **CONFINED AREA
MODEL
NUMBER
300 1 75 300 75 150
400 1 100 400 100 200
500 1 125 500 125 250
600 2 150 600 150 300
700 2 175 700 175 350
800 2 200 800 200 400
900 2 225 900 225 450
1000 2 250 1000 250 500
1100 3 275 1100 275 550
1200 3 300 1200 300 600
1300 3 325 1300 325 650
1400 3 350 1400 350 700
1500 3 375 1500 375 750
* Unconned area: A space whose volume is not less than 50 cubic feet per 1000 Btu
per hour of all appliances installed in that space (cubic feet of space = height x width x length).
** Conned area: A space whose volume is less than 50 cubic feet per 1000 Btu per
hour of all appliances installed in that space (cubic feet of space = height x width x length).
BOILER
MODULES
OUTSIDE
COMBUSTION
AIR 1 SQ. IN
/4000 Btu/hr
(SEE FIG. 2)
INSIDE
COMBUSTION
AIR 1 SQ. IN.
/1000 Btu/hr
(SEE FIG. 1)
Chart #3
OUTSIDE COMBUSTION AIR
HORZ.
VERT. DUCTS
1 SQ. IN.
/4000 Btu/hr
DUCTS
1 SQ. IN.
/2000 Btu/
hr
8
Page 9
VENTILATION AND COMBUSTION AIR
Figure 1 Figure 2
Combustion
Air
Openings
Vent-Piping
Combustion Air supplied from
inside the building
Combustion Air
Openings with
Motorized Dampers
Vent-Piping
Combustion Air supplied from
outside the building
Important Vent-Piping Note: Sloped vent pipe at least 1/4” for every 1’ to the vent terminal.
1.
Provide combustion and ventilation air in accordance with the section “Air for Combustion and Ventilation”, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of the local building codes.
2.
Boiler is located in unconned space in building or
conventional construction frame, masonry or metal
building, inltration normally is adequate to provide air
for combustion and ventilation. However, if equipment is located in building of tight construction (See National Fuel Gas Code, ANSI Z223.1), boiler area should be
considered as conned space. If there is any doubt,
install air supply provisions in accordance with latest revision of National Fuel Gas Code.
3.
Boiler is installed in unconned space, in building of
tight construction, air for combustion and ventilation must be obtained from outdoors or from spaces freely communicating with outdoors. Permanent opening or openings having total free area of not less than 1 square inch per 5,000 Btu per hour of total input rating of all appliances shall be provided. Ducts may be used to convey makeup air from outdoors and shall have same cross-sectional area of openings to which they are connected.
4.
When air for combustion and ventilation is from inside
buildings, conned space shall be provided with two
permanent openings, one starting 12 inches from top and one 12 inches from bottom of enclosed space. Each opening shall have minimum free area of 1 square inch per one thousand (1000) Btu per hour of total input rating of all appliances in enclosed space, but must not be less than one hundred (100) square inches. Openings must freely communicate directly with other
spaces of sufcient volume so combined volume of all spaces meets criteria for unconned space. Figure 1.
5.
When boiler is installed in conned space and all air is provided from outdoors conned space shall
be provided with one or two permanent openings according to methods A or B (see page 10). When ducts are used, they shall be of same cross sectional area as free area of area of openings to which they connect. Minimum dimension of rectangular air ducts shall be not less than 3 x 3 inches or 9 square inches.
9
Page 10
VENTILATION AND COMBUSTION AIR
A. When installing two openings, one must commence
within 12 inches from top and other within 12 inches from bottom of enclosure. Openings shall communicate directly, or by ducts, with outdoors or spaces (crawl or attic) that freely communicate with outdoors. One of following methods must be used to provide adequate air for ventilation and combustion.
1) When directly communicating with outdoors, each opening shall have minimum free area of 1 square inch per 4,000 Btu per hour of total input rating of all equipment in enclosure. Refer to Figure 2 on previous page.
2) When communicating with outdoors by means of vertical ducts, each opening shall have minimum free area 1 square inch per 4,000 Btu per hour of total input rating of all appliances in the enclosed space.
3) If horizontal ducts are used, each opening and duct shall have minimum free area 1 square inch per 2,000 Btu per hour of total input rating of all appliances in the enclosed space.
6. In calculating free area using louvers, grilles or
B. One permanent opening, commencing within 12
inches of top of enclosure, shall be permitted where equipment has clearances of at least 1 inch from sides, 1 inch from back, and 6 inches from front of boiler. Opening shall directly communicate with outdoors or shall communicate through vertical or horizontal duct to outdoors or spaces (crawl or attic) that freely communicate with outdoors. Openings must have minimum free area of 1 square inch per 3000 Btu per hour of total input rating of all equipment located in enclosure. Free area must be no less than sum of areas of all vent
connectors in conned space.
screens for above, consideration shall be given to their blocking effect. Screens used shall not be smaller than 1/4 inch mesh. If free area through design of louver or grill is known, it should be used in calculating size opening required to provide free
area specied. If design and free area is not known,
it may be assumed that wood louvers will have 20­25% free area and metal louvers and grilles will have 60-75% free area. Louvers and grilles should
be xed in open position or interlocked with boiler
so they are opened automatically during boiler operation.
VENT INSTALLATION
WARNING
!
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
1.
The vent pipe must slope upward from the boiler not less than 1/4” for every 1’ to the vent terminal.
Figures 1 & 2.
2.
Horizontal portions of the venting system shall be supported rigidly every 5 feet and at the elbows. No portion of the vent pipe should have dips or sags.
Flue Connection And Venting
Vent installations shall be in accordance with “Venting of Equipment”, of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, or applicable provisions of the local building codes.
1.
Consult dimensional drawing for number and size of
ue pipes required for each size boiler.
2.
Maintain minimum upward slope of 1/4 inch per linear foot from the boiler to chimney.
3.
Run ue pipe directly as possible. Keep turns to a minimum. Insert ue pipe into, but not beyond, inside
wall of chimney. Do not connect into a chimney serving
an open replace.
4.
Insulate ue pipe where it passes near combustible
material.
5.
Rigidly support pipe with hangers and straps.
6.
Extend chimneys at least 2 feet above any object within radius of 15 feet, including roof.
7.
Install hood on all ue pipes which extend through roof.
In most locations, venting of boiler relies on natural draft. In as much as energy available from natural draft is quite low, serious thought should be given to vent system design, i.e., adequate size, use of gradual transitions, tees, elbows, etc., close proximity of boiler and chimney. On all boilers, vertical risers must be at least as large as vent openings on draft-hood.
manufacturer makes no specic recommendations
regarding application of draft inducers that may be used with this boiler. If draft inducer is used, it is up to installing contractor and draft inducer manufacturer to determine proper application.
Boiler
10
Page 11
VENT INSTALLATION
Flue Connection And Venting - Continued
Simple vent system consists of 6-foot minimum vertical
Figure 3
rise immediately off draft-hood, as shown in Figure 3.
Terminate this vertical ue above building roof with suitable
rain cap at least 2 feet above surrounding obstructions, i.e., parapets, adjacent buildings, penthouses, etc. This type of vent system applies to single draft-hood boilers ONLY, and has limited practical use, because it is restricted to single-story boiler rooms and because of problems
encountered in roof ashing.
Vertical venting system shown in Figure 3 cannot be used on multiple-base boilers because of physical interference of multiple rain caps.
IMPORTANT: Extend chimneys at least 2 feet above any
For multiple-base boilers, pant leg venting system shown in
object within radius of 15 feet, including roof.
Figure 4 can be applied, if desired.
Vent system shown in Figure 5 is commonly used. With
Figure 5
vent diameters sized to match ue outlets, minimum
vertical rise of 4 feet above draft-hood must be maintained for proper operation. Refer to Chart 1 for typical chimney sizes. Requirements for this type of system are: an adequately sized chimney, adequate combustion air, and outlet end of horizontal run must be no more than 6 feet from chimney with no more than one 90° elbow in this run as shown.
For installations where required minimum 4-foot vertical rise cannot be maintained, diameter of horizontal run must be increased one inch for each foot of riser reduction. This procedure will reduce resistance of system, and if chimney is adequate boiler will vent properly.
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
Figure 4
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
11
Page 12
VENT INSTALLATION
Figure 6
Bafe Size (Inches)
Riser 8 10 12
A 6 8 10
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
Shown is suggested size of xed bafe for different size risers.
Flue Connection And Venting - Continued In certain cases where these short rises of less than 4
feet have been used, spillage of combustion products has occurred at the draft-hoods farthest from the chimney. Assuming the chimney is adequately sized, one acceptable method to correct this spillage problem is to permanently
bafe the riser(s) closest to the chimney to reduce the
excess of room air entering those draft-hoods. DO NOT
BAFFLE ENOUGH TO CAUSE SPILLAGE. The use of xed bafes in the short risers above the boiler draft-hood are
acceptable as spelled out in American National Standard NFPA 54/ANSI Z223.1 National Fuel Gas Code, latest revision.
Fabricate these xed bafes, using 20-gauge steel. See Figure #6. Permanently attach the bafe to the inside of
the riser(s). Trial and error will dictate the degree to which each should be positioned to avoid draft-hood spillage at the far end of the boiler. Be careful to avoid bending
the xed bafe so it will obstruct the ue gas ow in the
horizontal collector.
Removing Existing Boiler From Common Venting System
When existing boiler is removed from common venting system, common venting system is likely to be too large for proper venting of appliances remaining connected to it.
At time of removal of existing boiler, following steps shall be followed with each appliance remaining connected to common venting system placed in operation, while other appliances remaining connected to common venting system are not in operation.
1.
Seal any unused openings in the common venting system.
2.
Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deciencies which
could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
4.
Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
5.
Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the ame of
a match or candle, or smoke from a cigarette, cigar or pipe.
6.
After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas-burning
appliance to their previous conditions of use.
7.
Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
12
Page 13
BOILER DIMENSIONS
Front View
Supply
1
2
3
AA
A
Top View
D E
C
Return
Supply Supply
Left Side View
Supply
Water Line
38”
29½
Floor Line
F
Flue Outlets
Return
ALL SUPPLY AND RETURN
CONNECTIONS ARE 4 INCH
Chart 4
Boiler
Model
No.
300 400
500
600 700 800 900
1000
1100 1200 1300 1400 1500
Water
Content in
Gallons
20 25 30
35 40 45 50 55
60 65 70 75 80
Shipping
Weight
Lbs.
922
1133
1344
1555 1766 1977 2188 2399
2610 2821 3032 3243 3454
A Jacket
Width L to R
20 3/4
25
29 1/4
33 1/2 37 3/4
42
46 1/2
50
54 3/4
59 63 1/4 67 1/2 71 3/4
* Note - See page 14 Base Assembly
AA
Base &
Battery
Length
16 3/4
21
25 1/4
29 1/2 34 3/4
38 42 1/4 46 1/2
50 3/4
55 59 1/4 63 1/2 67 3/4
C D E F
10 3/8 12 1/2 14 5/8
10 3/8 10 3/8 12 1/2 12 1/2 14 5/8
10 3/8 12 1/2 10 3/8 12 1/2 14 5/8
– – –
12 3/4 14 7/8
17 19 1/8 21 1/4
14 7/8
17
17 19 1/8 21 1/4
– – –
– – – – –
17
17 21 1/4 21 1/4 21 1/4
10 3/8 12 1/2 14 5/8
10 3/8 12 1/2 12 1/2 14 5/8 14 5/8
12 1/2 12 1/2 14 5/8 14 5/8 14 5/8
*Boiler Modules
*1 *2 *3
300 400 500
300 300 400 400 500
300 400 300 400 500
x x x
300 400 400 500 500
400 400 500 500 500
400 400 500 500 500
x x x
x x x x x
13
Page 14
INSTALLATION – ASSEMBLY
Base Assembly
300, 400 and 500 boilers are the basic models.
300 model has (6) burners
400 model has (8) burners
500 model has (10) burners
Combinations of basic models are used to assemble 600 through 1500 models.
Refer to Chart 3 for proper order of assembly. When two or more bases are used to assemble boiler, verify tops of bases are even.
1.
Fasten bases together with 5/16 cap bolts and nuts.
2.
Insert two bolts in front posts and two in rear posts as shown in Figure 7A .
3.
After bases are fastened, install base end panels. Install end panels before assembling sections. See
Figure 7B.
NOTICE
Figure 7A
Figure #7A
Figure 7B
Bolts with nuts in the front and rear posts
Verify bases are level after assembly.
Section Assembly
1.
Start sections from left or right end of base.
2.
Place end section on base with center-line of section directly over joint of base end closure.
3.
With boilers having two or more bases, as you progress be sure parting line (center-line of section) of intermediate
sections fall on junction of two bases. See Figure 8.
Figure 8
Alignment of section along side
Note: First
Section Alignment
is critical. Use side
of base to align
rst section. Do
not allow side to
overhang base.
14
Page 15
INSTALLATION – ASSEMBLY
1.
When starting section assembly, clean nipples and nipple ports.
2.
Coat nipples and nipple ports with Hercules Grrip or other good sealant. See Figure 9.
3.
Place nipples in ports. Take care to seat them squarely to prevent cocking. Figure 10.
4.
When pulling sections together with tie rods, insert tie rods in holes nearest to nipple ports. Move tie rods to proper location, if necessary, only after sections are fully pulled together. See insert Figure 11.
Figure 9
Figure 10
5.
Oil or lubricate threads, insert rods in lugs with washers under nuts and tighten uniformly and evenly so that sections are pulled parallel as they go together. When all sections are pulled up, locate tie rods in alternating pairs of upper and lower holes between adjacent sections. See Figure 11.
6.
Be sure both ends of completed section assembly are resting evenly on both ends of base.
7.
Apply furnace cement at joints of sections front, top and back. Apply furnace cement where sections join the base. See Figure 12.
8.
Place necessary plugs and control wells in correct locations. See Figure 31 page 24.
A. Plug all other tappings, leaving air vent in top of
one of end sections, and connect water.
B. Fill boiler with water until it runs out air vent. See
Figure 31 port D page 24.
C. Hydrostatically test boiler in accordance with
applicable codes. D. Check for leaks before continuing with assembly. E. Drain and remove unnecessary plugs.
Figure 11
Figure 12
Apply non-asbestos furnace cement to joints on all sides of boiler.
15
Page 16
INSTALLATION – ASSEMBLY
Attaching Draft Hoods
1.
Attach draft hoods to boiler sections after applying boiler Hercules Grrip to top of boiler sections where hoods and sections meet.
2.
Use J-bolts to attach front of draft hoods to slots in section anges. See Figure 13.
Figure 13
Draft Hood
Draft hood notched to t over sections
J-bolt & nut attach to front of hood
Draft hood clean-out covers
16
Page 17
INSTALLATION – ASSEMBLY
Installing Boiler Jacket Panels
NOTICE
Start jacket assembly at left side.
1.
Attach lower jacket end panel (left) to two Z-bars on base end closures through two slotted holes on bottom
of jacket end panel. Use (2) #10 x ½” screws. See
Figure 14.
2.
Attach middle jacket end panel (left) to lower jacket end panel with middle laying over lower. Line up holes.
Use (5) #10 x ½” screws. See Figure 15.
Figure 14
Figure 15
3.
Attach upper jacket end panel (left) to middle jacket end panel with upper behind middle. Line up holes.
Use (6) #10 x ½” screws. Ensure bare metal plate is
inserted between casting ridge and draft hood. This holds panel in place. See Figure 16.
Figure 16
17
Page 18
INSTALLATION – ASSEMBLY
4.
Position top/front intermediate panel so back edge of top hangs on adjustable clips on front of draft hood(s);
A. Left edge hangs on bracket on left upper jacket end
panel,
B. Right edge with integral bracket hangs on tie
rod(s).
See
Figure 17.
Figure 17
Adjustable Clips
Bracket
Installed
Front Jacket Panel
Front Jacket
Panel
Right Edge
Integral Bracket
5.
Attach top/front intermediate panel to lower base
brackets through four slotted holes in panel. Use (4)
#10 x ½” screws. See Figure 18.
6.
On multiple base boilers, each additional top/front intermediate panel attaches in same way (working your way from left to right). Figure 18.
Figure 18
18
Page 19
INSTALLATION – ASSEMBLY
NOTICE
Manufacture recommends assembling jacket panels after piping is completed. Skip step 7 proceed to step 8.
7.
Attach upper jacket end panel (right) so left edge hangs on bracket on top/front intermediate panel. Insert bare metal plate in same manner as left panel. See Figure 19.
A. Attach side panel to base bracket through to slotted
holes. See Figure 20
Figure 19
Figure 20
Figure 21
B. For added support attach side panel to draft hood.
A
B
19
Page 20
INSTALLATION – ASSEMBLY
See Figure 21.
If boiler piping is preassembled jacket can be assembled as follows. See Figures 22A and 22B.
8.
Attach middle jacket end panel (right) to upper jacket end panel with middle laying over upper. Line up holes.
Use (6) #10 x ½” screws. See Figure 22A.
9.
Attach lower jacket end panel (right) to middle jacket
end panel with lower behind middle. Line up holes. Use
(5) #10 x ½” screws.
10.
Attach lower jacket end panel to two Z-bars on base end closures through two slotted holes on bottom
of jacket end panel. Use (2) #10 x ½” screws. See
Figure 22B.
Figure 22A
Figure 22B
11.
Position top of rear jacket panel(s) to draft hood bafe ange. Secure with (2) #10 x ½” screws. Secure bottom
of rear jacket panel(s) to bracket(s) on boiler base using (2) #10 x ½” screws. See Figure 23.
Figure 23
20
Page 21
INSTALLATION – ASSEMBLY
12.
Attach burner door knobs with #8-32 x ¼” screws and #8-32 hex nuts.
13.
Slide bottom of lower access door(s) in slots on top of manifold brackets. See Figure 24.
14.
Position control access jacket panel(s) so tabs slide into slots on top/front intermediate jacket panel(s).
15.
Attach control access jacket panel to front jacket. Use
(2) #10 x ½” screws. See Figure 25.
16.
Each boiler base includes:
Factory installed lighting Instruction Labels.
Factory installed Data plate indicating required gas type, ring rate, and gas pressure for that base.
These plates are located on Jacket Top/Front Panels.
Field installed rating plate showing total Input and Output Ratings. Rating plate is shipped in AC Carton and is to be mounted on side Jacket End Panel by installing contractor.
Figure 24
Figure 25
17.
Attach any Local Code Label, not provided by manufacturer, to boiler.
Figure 26
NOTE: Attachment of control access jacket panel can wait until controls have been mounted to front jacket panel.
21
Page 22
INSTALLATION – ASSEMBLY
Control Mounting And Installation
Electrical controls, J-box, etc. can be mounted on either left or right jacket end panel.
Boiler safeties (LWCO, etc.) and respective piping must be mounted on opposite end of boiler electrical controls.
1.
Attach J-box assembly to jacket end panel. Align with
holes in end panel. Use (4) #10 x ½” screws. See
Figure 27.
2.
Attach control panel to front jacket panel align with
predrilled holes. Use (4) #10 x ½” screws. Secure
harness to control panel with zip-ties. Attach wire clips to side and front panels (3). Route wires through clips. See Figure 28A.
Figure 28A
Figure 27
CLIPCLIP
3.
Orient harness of control panel assembly so correct (female) plug is toward J-box and will connect to J-box harness. See Figure 28A.
4.
Connect plugs on harnesses. See Figure 28B.
Figure 28B
CLIP
22
Page 23
INSTALLATION – ASSEMBLY
5.
Connect plugs on harnesses. See Figure 29.
6.
On multiple base boilers, mount remaining control panels to intermediate jacket panels following steps 4 & 5.
7.
On each base, connect gas valve harness. Refer to Wiring Diagram page 30.
Figure 29
8.
Connect pilot spark wire after control panel installation. See Figure 30.
Figure 30
23
Page 24
TAPPINGS
Figure 31 shows end section and provided tappings. Tappings are same in both right and left end sections.
OPENING SIZE STEAM
A 4” Supply and Return
B ½”
C ¾” Drain, Left End
C ¾” Drain, Right End
D ½” Plugged
E 1” Accessories
*F 1” Safety Valve
G ¾”
*If using opening F for other than Safety Valve or Safety Relief Valve, or Safety/Relief valve is larger than 1”, Install Safety/Relief Valve in Header Piping as near boiler as possible.
BOILER TRIM
Following controls are supplied as standard equipment. Details of their function and operation will be found in section on Checking and Adjustments page 33.
Primary LWCO and Gauge Glass Set
Plugged or Electronic (Probe Type) LWCO
Figure 31
D
A
Figure 32
F
B
G
B
A
C
E
STEAM TRIM
1.
Low Water Cut-Off (mounted externally) with blow-off valve
2.
High Pressure Limit Control
3.
Pressure Gauge
4.
Water Gauge Glass Set
5.
Siphon Loop
6.
Safety Valve 15 psi. See page 27 for installation location.
STEAM TRIM ASSEMBLY
Field assemble Steam Trim, Low Water Cut-Off, High Pressure Limit Control, Pressure Gauge, Water Gauge Glass Set and Siphon Loop, as shown in Figure 32. See Figure 31 and Chart above for location of controls.
NOTICE
Do not place any shutoff between pressure relief valve and boiler, or on discharge pipes between such safety valves and atmosphere. Installation of pressure relief valve shall conform to requirements of ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
WATER LEVEL 29” TO FLOOR
Field Assembled
24
Page 25
TO RETURN
CITY WATER SUPPLY
CITY WATER SUPPLY
WATER
LINE
A
TO RETURN
WATER
LINE
A
1.1/2
67 SERIES
CUTOFF
WATER
LINE
NO. 150
OR
NO. 93
Figure 33 - Boiler Tappings
BOILER PIPING
STEAM BOILERS - SERIES S
NOTE: Mount electrical supply on opposite side.
AND ELECTRIC BOILER FEED PUMP
CUTOFF USED WITH CONDENSATE RECEIVER
McDONNELL PUMP CONTROL AND LOW-WATER
CUTOFF
SEPARATE McDONNEL FEEDER AND
SEPARATE McDONNEL LOW-WATER
No. 247 mechanical feeder or No.
101-24V electric feeder with transformer
- for use on closed heating systems only.
BOILER SIZE USE
300 THRU 1500
NOTE: For multiple installation with condensate tank and single boiler feed
pump, use No. 93 on each boiler to operate motorized valve in each boiler
feed line.
*These items available through your Distributor.
Gauge Glass Tappings
No. 47-2* Control Mounts in
DIMENSION A - 2 = 2 ½ inches
FOR CLOSED HEATING SYSTEMS
DIMENSION A - 1 = 1 ½ inches
FOR PROCESS OR PARTIAL PROCESS SYSTEMS
DIMENSION A = 2 • 2 ½
FOR CLOSED HEATING SYSTEMS
BOILER TAPPINGS ARE AVAILABLE FOR ALL CONNECTIONS SHOWN
COMBINATION
McDONNELL FEEDER CUTOFF
BOILER SIZE USE
300 THRU 1500
NOTE: For multiple boiler installation with gravity return, use feeder Cutoff
Combination or separate feeder and separate cutoff on each boiler.
25
Page 26
Figure 34
SKIM TEE
BOILER PIPING
STEAM BOILER PIPING
Optional Location
for Make-up
Water
Connections
29½”
Install Safety Valve As Close To Boiler As Possible
STEAM BOILER PIPING See Figure 34
Full size steam header is recommended by manufacture on all steam systems as shown above.
• Risers should be full 4” and at least 20” in height. Use
skimmer tee as shown.
Area of Main Steam Cross Header Pipe should be equal to or larger than total area of Steam Supply Mains leading from Header and should never be smaller than Supply tappings on Boiler. Return Header should be piped to both ends of Boiler. Area of Return Header should be equal to total area of Return Mains or larger.
Pipe steam cross headers with swing joints, or equipped with slip joint connector, to prevent expansion and contraction of steam header from damaging boiler.
Each installation has preferred piping arrangement according to system requirements. Installer’s heating engineer or using standard engineering practice choice of arrangements and sizes of headers should be decided.
WARNING
!
Do not install shut-off or steam valve between safety valve and boiler.
Steam Piping Size
Model Header Riser Equalizer
300 to 900 4” 4” 2”
1000 to 1200 4” 4” 2 ½”
1300 to 1500 4” 4” 3”
26
Page 27
BOILER PIPING
Figure 35 - High Steam Quality Drop Header Piping Arrangement
20” MIN
Note: Single
Main Riser May
Be Used.
27
Water
for Make-up
Connections
Optional Location
Page 28
CONNECTING GAS SERVICE
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
!
DANGER
Fire Hazard. Do not use matches, candles, open
ames, or other methods providing ignition source.
Failure to comply will result in death or serious injury.
Gas Supply Connection, Natural Gas Only
1.
Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements USA - National Fuel Gas Code, ANSI
Z223.1/NFPA 54
2.
On multiple base boilers, connect gas service with branch lines from common main.
3.
Install ground joint union in each branch line for easy servicing of gas controls.
4.
Provide sediment trap up stream of gas valve. Figure 36.
5.
Size and install gas piping system to provide sufcient
gas supply to meet maximum input at not less than minimum supply pressure. See Chart 6 for pipe sizes for gas mains.
6. Pressure test boiler and gas connection before
placing boiler in operation.
Pressure test over 1/2 psig (3.5 kPa). Disconnect boiler and its individual gas shutoff valve from gas supply system.
Pressure test at 1/2 psig (3.5 kPa) or less. Isolate boiler from gas supply system by closing manual gas shutoff valve.
Locate leakage using gas detector, noncorrosive
detection uid, or other leak detection method
acceptable to authority having jurisdiction. Do
not use matches, candles, open ames, or other
methods that can provide ignition source.
Correct leaks immediately and retest.
Chart 5
Minimum Operating Gas Supply Pressure
Models
300 500 600 1000 1300 1500
Models
400 700 800 900 1100 1200 1400
All
Models
All
Models
TABLE OF PIPE SIZES IN INCHES FOR GAS MAINS
Boiler
No
300 1¼ 1¼ 1¼ 1¼ 1¼
400 1¼ 1¼ 1¼ 1½ 1½ 2
500 1¼ 1¼ 1½ 1½ 1½ 2 2 2
600 1½ 1½ 1½ 2 2 2 2 2
700 1½ 1½ 2 2 2 2 2
800 2 2 2 2 2
900 2 2 2 2 2
1000 2 2 2 2
1100 2 2 2 2 2
1200 2 2 2 2 2½ 2½ 3
1300 2 2 2 2½ 2½ 2½ 3 3
1400 2 2 2 2½ 2½ 2½ 3 3 3
1500 2 2 2½ 2½ 2½ 2½ 3 3 3
Maximum Gas Supply Pressure
20’ 30’ 40’ 50’ 60’ 80’ 100’ 125’ 150’
5.0 inches w.c.
5.3 inches w.c.
13.5 inches w.c.
Manifold Pressure
3.5 inches w.c.
Chart 6
(NATURAL GAS)
Figure 36
28
Page 29
ELECTRICAL WIRING
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before making any line voltage connections. Failure to do so could result in death or serious injury.
!
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Electrical Wiring
1.
Electrically bond boiler to ground in accordance with requirements of authority having jurisdiction. Refer to National Electrical Code, ANSI/NFPA 70.
2.
Install fused disconnect switch between boiler and electrical panel in convenient location.
3.
Secure wiring from high temperature limit control to boiler jacket or gas piping to prevent accidental disconnect from controls.
4.
Tape all wiring to gas valves securely to gas supply lines or run in appropriate conduit.
Adjust Thermostat Heat Anticipator
1.
Set heat anticipator setting per thermostat manufacture instructions.
2.
Follow thermostat manufacture instructions for nal
adjustment.
3.
When set above temperature indicated on thermometer, boiler burners should ignite. Verify thermostat(s) turns boiler off when room temperature reaches selected setting and starts boiler when room temperature falls few degrees.
4.
Set thermostat for desired temperature.
MULTIPLE
BASE BOILERS
5.
Thermostat Installation
1.
Follow instructions included with your thermostat.
2.
Locate thermostat about 5 feet above oor on inside wall.
3.
Keep thermostat(s) at desired room temperature. If windows are opened or heat is not needed, set thermostat(s) to lower setting.
PLACES TO AVOID LOCATING THERMOSTAT
Dead Spots
Hot Spots
Cold Spots
Behind Doors
Corners and Alcoves
Concealed Pipes
Fireplaces
TV Sets
Lamps
Direct Sunlight
Kitchens
Concealed Pipes or Ducts
Stairwells
Drafts
Unheated Rooms on other side of Wall
29
Page 30
Commercial Boiler, 1, 2 & 3 Base
WIRING DIAGRAMS
LOW VOLTAGE WIRING
30
Page 31
OPERATION AND SERVICE
Control Functions And Operation
Control module performs following basic functions:
1.
Opens and closes rst (pilot) operator of gas valve.
2.
Provides spark for igniting pilot burner.
3.
Senses pilot burner ame.
4.
Shuts off spark after pilot ame is lit.
5.
Opens and closes second (main) operator.
Functions occur in two stages - trial for pilot ignition and main burner operation as described below.
Trial For Pilot Ignition
1.
On every call for heat (system start), control performs
internal safe-start check. If ame simulating condition is
present, system will not start.
2.
During normal start, control opens rst (pilot) valve operator of gas control, which allows gas to ow to
pilot burner. At same time, electronic spark generator in control produces 15,000 Volt spark pulse output (open circuit). Voltage produces spark at igniter sensor rod which ignites pilot burner.
3.
If pilot ame does not light or presence of pilot ame is not detected back through ame-rod, control will not
open second (Main) valve operator of gas control.
4.
Control will continue to try to ignite pilot burner until
either ame is detected or thermostat (controller) is set
below call for heat.
Main Burner Operation
1.
When pilot ame is established, ame rectication
circuit is completed to burner ground.
2.
Control ame sensing circuit detects ame current,
shuts off spark generator and opens second (Main)
valve operator to allow gas to ow to main burners.
3.
Pilot ame ignites main burner conventionally.
Electronic control module cannot be repaired. If troubleshooting procedure indicates malfunction in control, control must be replaced. Intermittent Pilot systems must be serviced by trained service technicians.
Preliminary Check
Make following visual checks before troubleshooting and after maintenance.
1.
Check power switch.
2.
Open manual shutoff valves in gas line to boiler.
3.
Verify all wiring connections are clean and tight.
4.
Review control’s normal sequence of operation.
System Troubleshooting
1.
Set thermostat or controller above room temperature and observe system response.
2.
Establish of system malfunction or deviation from normal operation by using Pilot System Troubleshooting Table, in following section.
3.
After any maintenance or repair, troubleshooting sequence should be repeated until procedure ends with normal system operation.
Component Verication
Verify Spark Ignition Circuit
Control electronic module and step-up transformer provides spark ignition at 15,000 V (open circuit). Check circuit at control module as follows:
1.
Turn off manual gas valve to prevent ow of gas.
!
WARNING
Electrical shock hazard. Do not touch either end of jumper or stud terminal, high voltage circuit. Failure to follow these instructions could result in death or serious injury.
2.
Disconnect ignition cable at control stud terminal to isolate circuit from pilot burner/igniter-sensor.
3.
Prepare short jumper lead using heavily insulated wire, such as ignition wire.
4.
Energize control.
5.
Touch one end of jumper rmly to control ground
terminal (GND).
6.
Do not disconnect existing ground lead.
7.
Move free end slowly toward stud terminal to establish spark.
8.
Pull lead wire slowly away from stud. Note length of gap at which arcing discontinues.
9.
Arc length of 1/8 inch (3.2 mm) or more indicates satisfactory voltage output.
10.
If no arc can be established or maximum gap is less than 1/8 inch (3.2 mm), replace control.
31
Page 32
OPERATION AND SERVICE
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do not use any
phone in your building. Immediately call your gas supplier from
a neighbor’s phone. Follow gas supplier’s instructions.
If you cannot reach your gas supplier, call the re
department.
Ignition Cable Verication
1.
Cable must not run in continuous contact with a metal surface or spark voltage will be greatly reduced.
2.
Connections to stud terminal on control and on igniter-sensor must be clean and tight.
3.
Loose connections may not conduct ame current even
though ignition spark is satisfactory.
4.
Check the cable electrical continuity.
Grounding Verication
Ground is required for pilot burner/igniter-sensor mounting bracket, and control GND terminal. If ground is poor or erratic, safety shutdown may occur even though operation is normal at checkout. If nuisance shutdowns occur, check grounding.
Startup And Checkout
If any failure of system component system will not operate. If system does not perform as outlined in Start System, below, refer to Pilot System Troubleshooting Table.
Start System
1.
Turn power to control(s) on. Turn off gas supply.
2.
Check control(s) operation as follows: A. Set Thermostat or controller above room
temperature to call for heat. B. Watch for spark at pilot burner(s). C. Turn on gas supply. D. Appliance is equipped with automatic ignition
device which automatically lights the pilot. Do not
try to light appliance by hand. E. Before operating, smell all around appliance area
for gas. Be sure to smell next to oor because
some gas is heavier than air and will settle on
oor. Read “What To Do If You Smell Gas” on front
page of this manual.above. F. Use only your hand to push in or turn gas control
knob. Never use tools. If knob will not push in or
turn by hand, don’t try to repair it, call qualied
service technician. Force or attempted repair may
result in a re or explosion.
32
G. Do not use this appliance if any part has been
under water. Immediately call a qualied service
technician to inspect the appliance and to replace any part of control system and any gas control which has been under water.
3.
System start: A. Spark will turn on and pilot gas valve will open at
once. Pilot burner(s) should ignite after gas reaches pilot burner(s).
B. Spark ignition should cut off when pilot ame is
established.
C. Main gas valve should open and main burners should
ignite after gas reaches burner ports.
Light-off may not be satisfactory until gas input and combustion air have been adjusted.
DANGER
Fire Hazard. Do not use matches, candles, open
ames, or other methods providing ignition source.
Failure to comply will result in death or serious injury.
Pilot Flame Adjustment
1.
Pilot ame should envelop 3/8 to 1/2 inch of tip of
insulated rod on igniter-sensor. See Figure 38.
2.
If adjustment is required, remove pilot adjustment cover screw and turn inner adjustment screw clockwise
to decrease or counterclockwise to increase pilot ame.
3.
Replace cover screw after adjustment to prevent possible gas leakage.
Test Ignition system safety shutoff device after placing boiler in operation. Disconnect sensor wire from ignition module. Burner operation should stop.
Figure 38 - Proper Flame Adjustment
Page 33
CHECKING AND ADJUSTING
Verify Burner Input
Check boiler for proper Btu input rate. Do not exceed Input rate stamped on nameplate of boiler located on end jacket panel. Verify primary air supply to main burners is properly
adjusted for complete combustion. If boiler is shut down for service, gas and electric must be off for 5 minutes before relighting.
Verify boiler for proper Btu Input proceed as follows:
1.
With main burners operating, measure gas Input to boiler by reading the gas meter.
2.
Verify all other appliances connected to same meter are shut off.
3.
Rate of gas ow (cu. ft. per hour) multiplied by Btu
value of gas should match Btu input shown on boiler nameplate.
4.
If it is not within +/- 2%, adjust Pressure Regulator
to obtain desired ow. Adjustment stem can be found
cap regulator top. Adjustment screw is plastic and may require slightly greater turning force than metal threads.
5.
Turn clockwise to increase input and counterclockwise to decrease input rate.
6.
Replace Regulator Cap.
High Limit Control
While boiler is operating, set high limit control below boiler water temperature and main burners should shut off. Return control to normal setting. Main burners should restart.
Burner And Pilot Flame
Manufacture recommends ue passages, burner
adjustments and operation of boiler controls be checked once a year by a service technician.
To clean ue passages:
BOILER FLUE PASSAGE
A. Remove burners and pilot(s) from boiler. B. Remove clean-cut cover panel on draft hood to
expose ue passages. See Figure 13 page 16.
C. Clean ue passageways between sections with
exible handle wire brush. Remove all dirt from
bottom of boiler and reassemble all parts.
D. Verify pilot connection(s), adjustment of pilot(s)
and burner ames after reassembly.
Figure 39 - Pilot and Flame
Outer Mantle
Outer Cone
Burner
Manifold
WARNING
!
Burn and scald hazard. Discharge of water, vapor and steam may scald. Failure to follow these instructions could result in death or serious injury.
Pressure Relief Valve
1.
Pressure relief valve on boiler is required.
2.
Run a pipe from pressure relief valve outlet to appropriate open drain.
3.
Pipe must be of same size as outlet on valve and open end must not be threaded.
4.
Run drain in area not subject to freezing. Failure to do so may cause water damage or injury should valve release.
5.
If valve discharge occurs, or valve fails to open as described above, contact service technician to replace relief valve and inspect heating system to determine cause, as this may indicate equipment malfunction.
6.
Follow valve manufacture instructions for testing and maintenance.
Burner And Pilot Flame
1.
Manufacture recommends visual check of burners and
pilot ame monthly during heating season by owner
and once year by service technician. See Figure 39.
2.
Look for deterioration from corrosion of burners, pilot burners and boiler base frame.
3.
Clean boiler base interior and exterior.
WARNING
!
Asphyxiation hazard. Improper installation could result in death or serious injury. Failure to follow these instructions could result in death or serious injury.
Venting System
1.
Check chimney for correct size, proper construction, clean and in good condition to ensure proper combustion.
2.
You must provide enough fresh air for combustion.
3.
If your building is of tight construction, it may be necessary to add fresh air duct to provide oxygen. See Chart 3, page 8.
4.
Monthly during heating season check that sections of
vent pipe are secure at all joints and ttings. There
should be at least two (2) sheet metal screws per joint.
5.
Check that vent pipe slopes at least 1/4” per foot up from boiler to chimney.
6.
Vent pipe should be securely fastened to prevent sagging.
7.
Check vent Pipe for any deterioration from corrosion or any other sources.
8.
Refer to Venting and Combustion Air instructions in this manual.
33
Page 34
CLEANING AND MAINTENANCE
Cleaning The Steam Boiler
Steam boilers must be cleaned prior to use in order to
ensure efcient operation.
Grease, oil, sand and dirt cause scum to form on the surface of water in new boilers. Heavier particles carried in grease may settle to bottom of boiler and form sludge. If permitted to remain in boiler it will prevent generation of steam, produces foaming and causes an unsteady water line. Remove accumulation of oil and grease by blowing off boiler as follows:
1.
Install surface skim connection of at least 1¼” nominal pipe size in boiler using skim tee. See Figure 35 page
27. Skim line should extend to within 18” of oor or
appropriate drain. A. Insert valve in line close to boiler.
2.
Bring water line to center of outlet. A. Raise temperature to just below steaming.
B. While burners are on, open the valve in skim line
and slowly feed clean water into boiler adjusting
inlet water so boiler water remains hot.
C. Continue skimming until water is clean.
3.
Close valves in boiler feed line and skim line.
4.
Bring boiler pressure to about 10 lbs. A. Turn burners off.
B. Open bottom drain valve permitting all water to
drain from boiler.
5.
After boiler has cooled, ll and ush out several times.
6.
Fill to proper water level and ready for normal service.
Do not use soda or any alkali, vinegar or acid for cleaning
heating boilers, it is difcult to completely remove them.
Injury may occur after cleaning process if these agents are used.
Boiler Water Treatment
In steam systems where system is tight, free from leaks, and all steam is returned to boiler as condensate, amount of make up water is small. Water treatment is not required.
On steam systems with less than 90% of steam being returned as condensate, or with very hard or corrosive make up water, treatment may be desirable. Follow recommendations of ASME (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code, Section VI, latest version.
Between Heating Seasons
Boilers should not be drained between heating seasons.
Steam boilers should be entirely lled with water during the
summer months to exclude air.
Low Water Cutoff(s)
Inspect low water cutoff(s) annually or as recommended
by low water cutoff manufacture. Flush oat types per
manufacturer’s instructions.
General Housekeeping
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and
liquids.
• Keep boiler area clear of obstructions to ow of
combustion and ventilation air.
34
Page 35
PILOT SYSTEM TROUBLESHOOTING TABLE
Turn gas supply OFF. Turn thermostat
(controller) to call for heat.
Power to module (24V module)
YES
Spark Across Igniter/Sensor Gap.
YES
Turn gas supply ON.
Pilot Burner Lights?
YES
NO
NO
NO
NOTE: Before troubleshooting, familiarize yourself with startup and check procedure.
Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring. Also, check air proving switch on combustion air blower system (if used) and that vent damper (if used) is open and end switch is made.
Pull ignition lead and check spark at module.
Spark okay?
NO
YES
Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
Check boot of the ignition cable for signs of melting or bucking. Take protective
action to shield cable and boot from excessive temperatures.
Check that all manual gas valves are open, supply tubing and pressures are
good, and pilot burner orice is not blocked.
Check electrical connection between module and pilot operator on gas control.
Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,
replace gas control: if not, replace module.
NOTE: If the control, goes into lockout, reset system.
On models with vent damper plug, make sure vent damper has not been installed, then removed. Replace vent damper if necessary.
On other models, replace module.
Spark Stops When Pilot Lit?
YES
Main Burner Lights?
YES
System Runs Until Call For
Heat Ends.
YES
Call For Heat Ends
System Shuts OFF?
NO
NO
NO
NO
Check continuity of ignition cable and ground wire.
Clean ame rod.
Check electrical connections between ame rod and module.
Check for cracked ceramic ame rod insulator.
Check that pilot ame covers ame rod and is steady and blue.
Adjust pilot ame.
If problem persists, replace module.
Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.
Check electrical connections between module and gas control. If okay, replace
gas control or gas control operator.
NOTE: If the control, goes into lockout, reset system.
Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.
Check that pilot ame covers ame rod and is steady and blue.
If checks okay, replace module.
Check for proper thermostat (controller) operation.
Remove MV lead at module: if valve closes, recheck temperature controller and
wiring: if not, replace gas control.
YES
Troubleshooting Ends.
NO
Repeat procedure until trouble free operation is obtained.
35
Page 36
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and
Conservation Act, this boiler is equipped with a feature that saves energy
by reducing the boiler water temperature as the heating load decreases.
This feature is equipped with an override which is provided primarily to
permit the use of an external energy management system that serves the
same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE
FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water temperature as the heating load decreases.
• This boiler is not used for any space heating
• This boiler is part of a modular or multiple boiler system having a total input of
300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
UTICA BOILERS
2201 Dwyer Avenue
Utica NY 13501
web site: www.ecrinternational.com
Loading...