Utica H2O Stainless SteelSingle CoilIndirect Water Heaters
8.0
H2O
LUB
Dimensions/WeightsModel
HOT OUTLET
T+P VALVE
DOM. COLD INLET
AQUASTAT
WELL
DRAIN
STANDARD UNIT
3/4" NPT
RECIRC. PORT
1 1/2" NPT
HOT OUTLET
1 1/4" NPT
BOILER SUPPLY
1 1/2" NPT
DOM. COLD INLET
9.5
8.0
AQUASTAT
WELL
DRAIN
COMMERCIAL UNIT
Dimensions & Weights
Models
H2OI30UB
H2OI40UB
H2OI40LUB
H2OI50UB
H2OI60UB
H2OI60LUB
H2OI80UB
H2OI115UB
H2OI80CUB
H2OI115CUB
H2OI80HOUB
H2OI115HOUB
H2OI80HOCUB
H2OI115HOCUB
Height
(Inches)
(Inches)
3222.585
4222.5100
3426.0100
5222.5110
6022.5125
4426.5120
5426.5140
7226.5175
5426.5120
7226.5175
5426.5155
7226.5190
5426.5155
7226.5190
8.0
8.0
Dia.
BOILER RETURN
BOILER SUPPLY
T+P VALVE
1 1/4" NPT
BOILER RETURN
Shp.
Wgt.
(Lbs.)
Storage Capacity
(Gals.)
H2OI30UB30
H2OI40UB407.53/41
H2OI40LUB42
H2OI50UB508.03/41
H2OI60UB608.43/41
H2OI60LUB607.53/41
H2OI80UB808.011
H2OI115UB1158.911
H2OI80CUB808.01-1/41-1/4
H2OI115CUB1158.91-1/41-1/4
H2OI80HOUB8013.511
H2OI115HOUB11514.411
H2OI80HOCUB8013.51-1/21-1/4
H2OI115HOCUB11514.41-1/21-1/4
Note: Max. Working pressure 150 psi for all capacities.
General Information (See Installation, Operation and Maintenance Manual for complete instructions)
Max. First
Model
H2OI30UB182242155215116,20010.02.7
H2OI40UB202266166230124,50010.02.9
H2OI40LUB193251157215117,90010.02.8
H2OI50UB222290177245132,80010.03.1
H2OI60UB240311186257139,40010.03.2
H2OI60LUB220284166230124,50010.02.9
H2OI80UB257328185256138,60012.03.7
H2OI115UB309388206285154,20012.04.0
H2OI80CUB257328185256138,60012.03.7
H2OI115CUB309388206285154,20012.04.0
H2OI80HOUB386507314435235,67015.09.0
H2OI115HOUB439568336465251,78015.09.5
H2OI80HOCUB386507314435235,67015.09.0
H2OI115HOCUB439568336465251,78015.09.5
Note: All ratings are based on 200° F boiler water supply and 50° F cold water inlet.
See installation manual for ratings at different temperatures and flow rates.
Specifications subject to change without notice.
Factory installed brass drain and relief valves, welded stainless steel cold water dip tube factory
installed and pressure tested, Honeywell L4080B aquastat for field installation.
(L) Low profile models for applications with low clearances.
(C) Commercial models with larger tappings for higher flow rates.
(HO) High Output models available to meet greater demand.
Continuous
Rating
Gal./Hr. @
Conforms to UL STD 174
Certied to CAN/CSA STD C22.2 No. 110-94
Note: Max. Working pressure 150 psi for all capacities.
General Information(See Installation, Operation and Maintenance Manual for complete instructions)
Specifications subject to change without notice.
Standard
Equipment
Options
Certification/
Decoding
Factory installed brass drain and relief valves, welded stainless steel cold water dip
tube factory installed and pressure tested, Honeywell L4080B aquastat for field installation.
(L) Low profile models for applications with low clearances.
(C) Commercial models available for applications with larger connections.
ST=Storage TankL=Lowboy
30=30 Gals.
40=40 Gals.
60=60 Gals.
80=80 Gals.
115=115 Gals.
C=Commercial
UB=Utica BoilerCapacity:
1 1/2" NPT
COLD INLET
9.5
COMMERCIAL UNITS
Dimensions & Weights
Models
H2OST30UB
H2OST40UB
H2OST60UB
H2OST60LUB
H2OST80UB
H2OST115UB
H2OST80CUB
H2OST115CUB
Height
(Inches)
34.023.575
44.023.590
62.023.5115
46.023.5110
56.028.0140
74.028.0175
56.028.0140
74.028.0175
AQUASTAT
WELL
DRAIN
Dia.
(Inches)
Shp. Wgt.
(Lbs.)
Conforms to UL STD 174
Certied to CAN/CSA STD C22.2 No. 110-94
Schematic
Diagram
(Typical
Installation)
Page 6
Utica H2O Stainless SteelBuffer Tanks
H2O
114
WC UBBT
40
Dimensions/WeightsModel
H2OBT40114UB
H2OBT40112UB1-1/2
H2OBT402UB
H2OBT60114UB
H2OBT60112UB1-1/2
H2OBT602UB2
H2OBT80112UB
H2OBT80114UB1-1/2
H2OBT802UB2
H2OBT115114UB
H2OBT115112UB1-1/2
H2OBT1152UB2
H2OBT40114WCUB
H2OBT40112WCUB1-1/2
H2OBT402WCUB
H2OBT60114WCUB
H2OBT60112WCUB1-1/2
H2OBT602WCUB2
H2OBT80114WCUB
H2OBT80112WCUB1-1/2
H2OBT802WCUB2
H2OBT115114WCUB
H2OBT115112WCUB1-1/2
H2OBT1152WCUB2
Note: Max. Working pressure 60 psi for all capacities.
General Information(See Installation, Operation and Maintenance Manual for complete instructions)
Specifications subject to change without notice.
Standard
Equipment
Options(WC) With Coil
Certification/
Dimensions & Weights
Model
H2O40BT114UB
H2O40BT112UB
H2O40BT2UB
H2O60BT114UB
H2O60BT112UB
H2O60BT2UB
H2O80BT114UB
H2O80BT112UB
H2O80BT2UB
H2O115BT114UB
H2O115BT112UB
H2O115BT2UB
Height
A
(Inches)
42.03111
44.031.511.5
54.040.511.5
72.061.511.5
B
(Inches)C(Inches)
Shp. Wgt.
(Lbs.)
(97 WC)
115
(125 WC)
125
(135 WC)
160
(170 WC)
Decoding
87
Storage Capacity
(Gals.)
40
60
80
115
40
60
80
115
Factory installed brass drain and relief valves, welded stainless steel cold
water dip tube factory installed and pressure tested, Honeywell L4080B
aquastat for field installation.
BT=Buffer Tank114=1-1/4” NPT
40=40 Gals.
60=60 Gals.
80=80 Gals.
115=115 Gals.
112=1-1/2” NPT
Piping Connections
NPT (Inches)
WC=With Coil
2=2” NPT
1-1/4
2
1-1/4
1-1/4
1-1/4
1-1/4
2
1-1/4
1-1/4
1-1/4
UB=Utica BoilerCapacity:
Conforms to UL STD 174
Certied to CAN/CSA STD C22.2 No. 110-94
Page 7
UTICA H2O STAINLESS STEEL BUFFER TANKS
•
Reduces chiller or boiler short cycling
(Short cycling results in reduced operating efciency and shorter equipment life)
•
Used in systems having several low BTU cooling or heating loads calling at different times
•
Full size tappings on buffer tank for peak performance (1-1/4”, 1-1/2”, and 2”)
• Used in systems operating below the design load condition, which is most of the time.
H2O HYDRAULICALLY DECOUPLED
To/From
Boiler/Chiller/Heat-Pump
Buffer Tanks
To/From
System
Buffer Tank Sizing - Calculating Capacity
Utica H2O buffer tanks are a simple, cost effective way to improve overall system efciency by reducing unnecessary equipment short cycling.
The recommended capacity or volume of a buffer tank is based on four variables.
1) The duration of the heating or cooling source “on time” (minutes). The desired length of “on time” for each run cycle depends on the
type of equipment used. Heat pump and chiller manufacturers typically recommend a minimum of 5 to 10 minutes on time, and boiler
manufacturers may recommend a minimum of 10 minutes “on time”. Check with your equipment manufacturer. Generally, the longer the
“on time”, the higher the overall operating efciency.
2) The minimum rate of heat input (BTU/HR). This is based on the heat pump or chiller output, or the boiler output at the minimum ring rate if
the boiler has a variable input system that ramps input down as the demand decreases.
3) The minimum system load (BTU/HR). This is the demand placed on the system with the smallest zone calling for heat.
4) The allowable tank temperature rise (deg. F). This varies depending on the type of heating or cooling system used, and on the
design of the distribution system. Chillers may require a tight, (6 deg. F), differential to assure good dehumidication and prevent freezing,
heat pumps may require a (10 deg. F) differential to maintain a high COP, and boilers with hydronic heating distribution systems may require
a differential anywhere between 10 to 40 deg. F depending on the application.
The following formula determines the tank volume:
T X (
Q heat input - Q min. heat load
Water to Water Heat Pump Example:
Town and Country Mechanical wants a minimum heat pump on time of 10 minutes. The heat pump output is 46,500 BTU/HR.
The smallest zone is a 7,000 BTU/HR bathroom. The allowable temperature differential is 90 to 100 deg. F for the radiant heat zones.
Tank temp. rise
=
V
X 500
x (
10
46,500 - 7,000
(
100-90
)
) x 500
V
=
V = Buffer tank volume (gallons) T = desired heat source “on cycle” (min.)
)
Q heat source = heat source output (BTU/HR) Q min. heat load = heat output to minimum load
Tank temp rise (deg. F)
=
79.0 Gallons minimum volume. Choose the H2O80BT buffer tank.
Page 8
Utica H2O StainlessSteel Dual and Single CoilSolar Water Heaters
DRAIN VALVE
3/8" ID
THERMAL WELL
4" X 10"
ELECTRICAL BOX
1.5
ELECTRIC BACKUP UNITS
H2O
D60
EUB
Bottom Coil
Heating
Surface Sq.
Min. Boiler
Water Flow
Through
Dimensions/WeightsModel
TOP COIL
SUPPLY
COLD
WATER IN
BOTTOM SOLAR
COIL RETURN
T+P VALVE
TOP COIL
3/8" ID THERMAL WELL
1/2" NPT RECIRC.
RETURN PORT
TOP HEATING COIL
FOR BACKUP
BOTTOM COIL
3/8" ID THERMAL WELL
BOTTOM HEATING COIL
FOR SOLAR
DUAL COIL UNITS
Dimensions & Weights
SINGLE COIL
Height
(Inches)
62.023.5135
56.028.0145
74.028.0180
DUAL COIL
62.023.5165
56.028.0175
74.028.0205
62.023.5175
56.028.0185
74.028.0215
Models
H2OI60EUB
H2OI80EUB
H2OI115EUB
H2OI60DUB
H2OI80DUB
H2OI115DUB
H2OI60DEUB
H2OI80DEUB
H2OI115DEUB
TOP COIL
RETURN
HOT WATER
OUT
BOTTOM SOLAR
COIL SUPPLY
Dia.
(Inches)
Storage Capacity
(Gals.)
Top Coil
Heating Surface
Sq. Ft.
SINGLE COIL
H2OI60EUB60N/A8.31
H2OI80EUB80N/A8.01
H2OI115EUB115N/A8.91
DUAL COIL
H2OI60DUB607.48.31
H2OI80DUB807.48.01
H2OI115DUB1157.48.91
H2OI60DEUB607.48.31
H2OI80DEUB807.48.01
H2OI115DEUB1157.48.91
Note: Max. Working pressure 150 psi for all capacities.
General Information(See Installation, Operation and Maintenance Manual for complete instructions)
Note: All ratings are based on 180° F boiler water supply and 50° F cold water inlet. For Dual Coil units,
continuous ratings shown are for the lower coil only. Specifications subject to change without notice.
Factory installed brass drain and relief valves, welded stainless steel cold water dip tube
factory installed and pressure tested, Honeywell L4080B aquastat for field installation.
Standard
Equipment
Shp.
Wgt.
(Lbs.)
Options(E) Electric Back-Up models for supplemental heating.
Removable thermal well to accept a solar control thermostat or thermistor. Dual coil units
equipped with two aquastat wells which control each coil independently and built-in recirculation tapping. Units with Electric Back-Up are provided with 4” x 10” electrical box with pre-wired
heating element, thermostat, and hi-limit. All electric back-up units provided with 240 volt AC,
3500 watt element.
Certification/
Decoding
Conforms to UL STD 174
Certied to CAN/CSA STD C22.2 No. 110-94
Ft.
Coil
E=Electrical
Back up
(3500 Watts)
Piping
Connections
NPT
(Inches)
Pressure
Drop Through
Coil
Contractor
Assistance:800.325.5479
PN 240009329 Rev. 11/13
P.O. Box 4729
Utica, New York 13504
tel: 315.797.1310
• fax: 315.797.3762
www.uticaboilers.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.