RADIATION TABLES
The output of a radiator is measured in square feet of radiation. To determine the number of square feet of radiation in a radiator:
1. Measure the height of the radiator.
2. Count the number of columns in a section.
3. Count the number of sections. Multiply the total number of sections by the number of square feet per section as shown in the following tables:
7 SECTIONS2 COL
36”
SIZE SHOWN 28 SQ. FT. RADIATION
7 SECTIONS5 TUBE
38”
SQ. FT. RADIATION PER SECTION
Height One Two Three Four Inches Column Column Column Column Window
13 3 16 33⁄4 18 21⁄4 34 20 11⁄2 2— —5 22 3 4 — 23 12⁄3 21⁄3 ——— 26 2 22⁄3 33⁄4 5— 32 21⁄2 31⁄3 41⁄2 61⁄2 — 38 3 4 5 8 — 45 5 6 10
1
4
Tube Type Radiators
SQ. FT. RADIATION PER SECTION
Height Three Four Five Six Window Inches Tube Tube Tube Tube Seven Tube
14 21⁄2 17 3 20 13⁄4 21⁄4 22⁄3 33 23 2 21⁄2 33 26 21⁄3 23⁄4 31⁄2 44 32 3 31⁄2 41⁄3 5— 38 31⁄2 41⁄4 56—
1
2
2
3
3
4
SIZE SHOWN 35 SQ. FT. RADIATION
167⁄8
SIZE SHOWN 5 SQ. FT. RADIATION
1311⁄16
Wall Type Radiators
Wall radiators are measured by their height, length and thickness. The following shows the number of square feet of heating surface per section:
SQ. FT. RADIATION PER WALL RADIATOR SECTION
Type of Height Length or Thickness Heating Sq. Ft.
Section Inches Width, In. Inches Radiation
5-A 135⁄16 165⁄8 27⁄8 5 7-A 135⁄16 217⁄8 27⁄8 7 7-B 217⁄8 133⁄16 31⁄16 7 9-A 185⁄16 291⁄16 27⁄8 9 9-B 291⁄16 185⁄16 311⁄16 9
PIPE RELIEF VALVE WITHIN 12” OF FLOOR OR IN ACCORDANCE WITH LOCAL CODES
HEADER Recommended Sizing PEG 112–150 : 2” PEG 187–225 : 2.5” PEG 262–300 : 3”
2”
STEAM MAIN RISER (SUPPLY)
EQUALIZER 2” RECOMMENDED. IF RETURN PIPE IS LARGER, INCREASE SIZE TO EQUAL RETURN PIPE SIZE
24” MIN.
WATER LINE
28”
NOTE: BOTH 2” SUPPLY TAPPINGS MUST BE USED. ALL NEAR BOILER SUPPLY HEADER PIPING MUST BE A MINIMUM OF 2”. DO NOT REDUCE.
HEADER RECOMMENDED SIZING 3 SECTION: 2” 4 SECTION: 2.1/2” 5 SECTION: 3”
FROM BOTTOM OF BOILER
STEAM MAIN RISER(S)
2”
SKIMMING TEE
RECOMMENDED 12” MIN.
CLOSE NIPPLE
RETURN
CLEANOUT TEES
EQUALIZER 2” RECOMMENDED. IF RETURN PIPING IS LARGER, INCORPORATE SIZE TO EQUAL THE RETURN PIPE SIZE
PIPE RELIEF VALVE WITHIN 12” OF FLOOR OR IN ACCORDANCE WITH LOCAL CODES
24” MIN.
WATER LINE
28”
22.1/2”
SUPPLY CONNECTION
SKIP TAPPING
ON BACK
OF BOILER
2”
FROM BOTTOM OF BOILER
CLOSE NIPPLE
HARTFORD LOOP CONNECTION
RETURN MAIN
CLEANOUT TEES
Ed: 12/00