Universal Enterprise MA1 Installation Manual

1-800-547-5740 • Fax: (503) 643-6322
www.ueitest.com • email: info@ueitest.com
MA1
INSTRUCTION MANUAL
Introduction
The MA1 is a high sensitivity direct reading AC ammeter. It is designed to simplify the setting of oil and gas thermostat heat anticipator and for measuring the performance of AC relays, solenoids and other low cur­rent AC devices.
Features include
• Ranges: 0 - 1.2 AC Amps
• A c c u r a cy: ±3% of full sca l e
Safety Notes
Before using this meter, read all safety information carefully. In this manual the word "WARNING" is used to indicate conditions or actions that may pose physical hazards to the user. The word "CAUTION" is used to indicate conditions or actions that may damage this instrument.
Operating Instructions
WARNING!
Like all direct reading ammeters, the MA1 must be connected IN SERIES with the circuit under test. The maximum value of current that can be measured with the MA1 is 1.2 AC amperes (1,200 AC milliamps). Do not exceed this value or the MA1 may be damaged.
Testing Heat anticipator
For the most efficient operation, the heat anticipator in the thermostat must be set to correspond to the value of the control circuit current.
Thermostats are of two types: preset or adjustable. Many cooling thermostats and some heating thermostats are preset. these require no adjustment.
Adjustable thermostats should be set to the value of current noted on the furnace rating label. If this information is not available then the control current must be measured and the heat anticipator set to the measured value of current as follows:
1. Remove the thermostat cover from the sub base.
2. Set the furnace controls to the ON position
3. For thermostats with a single stage heat control connect one lead of the MA1 to the “R” terminal on the sub base and the other lead of the MA1 to the “W” terminal (Fig 1).
4. Note the magnitude of the current on the meter scale of the MA. Set the heat anticipator to this value of current.
5. For thermostats with a two stage heat control repeat steps 1 thru 4 for stage 1. The second stage heat control current is measured by connecting one lead of the MA1 to the “RH” terminal and the other lead to the “W2” terminal (Fig 2).
6. Replace the thermostat cover and check the system for proper operation.
NOTE: If a fan limit control is used this can affect the length of the heating cycle. Check the ON and OFF fan control set points.
NOTE: If a longer heating cycle is desired, the pointer on the sub base can be adjusted to a slightly higher setting. If a shorter cycle is desired the pointer can be adjusted to a slightly lower setting.
Typical Values of Control Circuit Current:
1. 0.2 amperes for gas furnace without spark igniter.
2. 0.4 thru 0.8 amperes for gas furnace with spark igniter.
3. 1.0 amperes for oil furnace.
Other Uses For MA1
The MA1 can also be used to check the operating current of AC relays, solenoids, motors and other devices rated at 1.2 AC amperes or less.
1. Turn OFF the power to the device to be tested.
2. Disconnect one of the power input leads at the device to be tested.
3. Connect one lead of the MA1 to the device and the other lead to the power input wire previously disconnected (Fig 3).
MA1-MAN P. 1
(Fig 1)
(Fig 2)
(Fig 3)
MA1
Typical sub base
MA1
Power input lead
MA1
Typical sub base
Motor
Loading...
+ 2 hidden pages