Unitek Classic Q3 550, Classic Q3 400, Classic Q3 400-1000, Classic Q3 400-1500, Classic Q3 400-2000 Series Manual

...
Manual
Classic Q3 1000-2000A
4 Quadrant
Thyristor Drive
Q3-1000 - 2000A
Teil 1 Thyristor Drive Q3 x/x- 1000 to 2000A Teil 2 Analoque Control Electronic REG4
Edition
1108
Classic Q3 1000-2000A
Contents
Contents Page
Basic Information
Safety advice 3 Standards and guidelines 3 General information 4 Features 5 Technical data 6, 7 Specification 8
Mechanical installation 9 Dimensions 10, 11
Electrical installation
Connections 12 Connection diagram 13 CE advice 14 Auxiliary voltage connection 15 Transformer power connection 16 Option - synchronization 17 Motor connection 19 Field connection 20 Actual value connection 21 Components 22 Adjustments 22 Circuit diagram 23 Current control loop 24 Signals 25 Measurements25
Commissioning + REG4 26, 27 Fault 28, 29 Guarantee 30 Protocol 31, 32
2
1 Basic information
Electronic equipment is not fault proof. This fact should be borne in mind for all possible operating conditions.
ATTENTION - High voltageAC 500V~, DC 650V= 500V~ac, 650V=dc
Before installation or commissioning begins, this manual must be thoroughly read and understood by the technical staff involved. If any uncertainty arises, the manufacturer or dealer should be contacted. Q3 devices are power electric parts used for regulating energy flow. Protection rating IP00.
Standards and guidelines
The device and its associated components can only be installed and switched on where the local regulations and technical standards have been strictly adhered to: EU Guidelines 89/392/EWG, 84/528/EWG, 86/663/EWG, 72/23/EWG
EN60204, EN50178, EN60439-1, EN60146, EN61800-3 IEC/UL IEC364, IEC 664, UL508C, UL840 VDE Regulations VDE100, VDE110, VDE160 TÜV Regulations Trade body guidelines VGB4
Safety advice - Standards and guidelines
The user must ensure that in the event of:
- device failure
- incorrect operation
- loss of regulation or control the axis will be safely de-activated. It must also be ensured that the machine or equipment are fitted with device in dependent monitoring and safety features.
Setting adjustments
- should only be carried out by suitably trained personnel
- should only be carried out in accordance with health and safety guidelines
Assembly
- should only be carried out when all voltages have been removed.
QS
Test results are archived with the device serial number by the manufacturer.
-
CE The device adheres to the following: Guideline EU 89/336/EWG. EMC stan
Q3 1000-2000A 3
-
Classic Q3 1000-2000A
General information
Attention:
This manual Q3 only describes the basic control unit.
Manual Q3
This device description must be read in conjunction with the manual for
- an analogue control REG xx
- an external field control F2 xx
- options Multi xx
General information
Series Classic Q3
4
1 Basic information
Build
- switch cabinet mounting
- according to the VDE, DIN and EU regulations
- standard control electronics REG
-
intrinsically safe power section with current control loop
- controlled or uncontrolled field supply unit
- optional units
Galvanic isolation between
- the power section and the housing
- the power section and the control electronics
The distance of air gaps and leakage paths adhere to the VDE standards (>8mm).
Features
Components
- only components customary in trade and industrially standardised are used
- high-quality bases for the IC with external connections
- LED displays
- precision potentiometers for fine adjustments
- plug-in jumpers for the system set-up
Characteristics
* Series Classic Q3 * Thyristor drive for dc motors * Power range 6.75kW to 1.1MW * Drive and brake in all 4 quadrants' * Energy recovery * Intrinsically safe power section * Fast analogue current control * Temperature watchdog - power section * Circular current-free dual bridge circuit * Controlled or uncontrolled field rectifier * 26-pin interface * Features of the control electronics:
see Manual REGxx or third-party product documentation
* Optional units
Q3 1000-2000A 5
Classic Q3 1000-2000A
Technical data
Q3 400/450-1000-2000
Power connection 360 ... 440V~ Auxiliary voltage connection 360 ... 440V~, 200 … 250V~ oder Option Output voltage max. ± 450V= Cooling ventilation fan Field supply - external Field current controller F2.1 400/340-20
Q3 400/450- 1000 1500 2000
Input current A~ 800 1200 1600
Output current - peak 5s
- continuous
El. power kW 450 675 900
Fuses ff
Power chokes
Armature chokes Armature chokes are necessary only for special applications
Dimensions w x h x d mm 550x800x520 550x800x520 550x800x520
A= A=
AFF
Type
mH 0,05 0,03 0,02
2000 1000
installed 6x1000
3x
KU240-1000
3000 1500
installed 12x1000
3x
KU240-1500
4000 2000
installed 12x1000
3x
KU240-2000
Q3 500/550-1000 bis 2000
Power connection 450 ... 550V~ Auxiliary voltage connection 360 ... 440V~, 200 … 250V~ oder Option Output voltage max. ± 550V= Cooling ventilation fan Field supply - external Field current controller Unitek F2.1 400/340-20
Q3 500/550- 1000 1500 2000
Input current A~ 800 1200 1600
Output current - peak 5s
- continuous
El. power kW 550 825 1100
Fuses
Power chokes
Armature choke Armature chokes are necessary only for special applications
Dimensions w x h x d mm
A= A=
ff AFF
Type
mH 0,05 0,03 0,02
2000 1000
Installed 6x1000
3x
KU240-10003xKU240-15003xKU240-2000
550x800x520550x800x520550x800x52
3000 1500
Installed 12x1000
4000 2000
Installed 12x1000
0
6
1 Basic information
Specification
Mains frequency 50 or 60Hz ±5% Protection rating IP 00 Format VDE 0100 group C,
VDE 0160 Humidity rating class F acc. to DIN 40040 Site of installation < 1000m above sea level Operating temperature range 0 ... 45°C Extended operating temp. range up to 60°C reduced by 2%/°C Storage temperature range -30°C to + 80°C
Current control loop circuit Amplification
- input signal 0 to ±10V=
- output 0 to ±200% type current Over-current limiting 10s 200% type current Control precision ±2% Control range 1:50 Enable >+10V Speed control loop circuit (with manual REG) Control precision (without actual value error) <±0.1% Control range >1:1000
Interface control electronics X3 Function Connector no.
+ 24V ±10% X3: 1 and 2 + 15V ±2% X3: 3 and 4
- 24V ±10% X3: 5 and 6
- 15V ±2% X3: 7 and 8 Device GND 0 X3: 9, 10, 11, 12, 13, 14 I command value (GND) 0 X3: 15 I command value (signal) +10V= X3: 16 Current controller enable +10V= X3: 17 Drive disable1 +10V= X3: 18 Drive disable 2 +10V= X3: 19 N (speed) actual +10V= X3: 20 I (current) actual +5V= X3: 21 Over-current power section +10V= X3: 22 Option UA ±10V= X3: 23 Option UA 0-10V= X3: 24 Drive ready BTB +10V X3: 25
+5V X3: 26
Techniscal data
Q3 1000-2000A 7
Classsic Q3 1000-2000A
Air flowdirection
Mounting
Ambient temperature 0 to <45°C (reduced, up to 60°C) max. cooling unit temperature 80°C (internal watchdog)
Air-mass throughput 1000-2000A 2500m³h
Dissipation loss with max. power
Unit Q3-x/x Unit W Mains choke W
1000 3700 1000
1500 5400 1300
2000 7200 1600
8
2 Mechanical installation
1-phase mains choke
Faetures
UN 400V~50/60Hz
UK 4%
Protection rating IP00
Isolation class T40/E
Vertical angle bracket
Dimensions
Units Q3-x/x
1000
1500
2000
Choke type
KU240-10 00
KU240-15 00
KU240-20 00
with filter: KDFxx
L mHPVW
0,05 1000 320 270 470 250 190 98 10
0,03 1300 320 270 470 250 190 98 10
0,02 1500 320 270 470 250 190 98 10
Dimensions a b c d e
Weight kg
Screw M
Q3 1000-2000A 9
Classsic Q3 1000-2000A
Dimensions
10