UNI-T UT253A, UT253B Operating Manual

Page 1
P/N:110401103625 DATE:2018.06.26 REV.3
Page 2
Contents
TITLE PAGE Warnings 2 I. Introduction 4 II. Model Comparison 5 III. Electrical Symbols 6 IV. Technical Specifications 7 V. Meter Description 10 VI. Operating Instructions 12
1. Power On/Off 12
2. Backlight Control 12
3. Data Hold and Save 12
4. Data Access and Exit 13
5. Data Transmission to PC 13
6. Data Delete 14
7. Leakage Current, Current and Voltage Measurements 14 VII. Battery Replacement 18 VIII. Packing List 19
1
Page 3
Warning
Thank you for purchasing . In order to use the product properly, please follow instructions below:
2 3
s
UNIT large jaw leakage current clamp meter
Read user's manual carefully. Strictly observe safety rules and notes mentioned in this manual.
Page 4
I. Introduction
UNIT large jaw leakage current clamp meter, supported by latest CT and digital integration technologies and coupled with large diameter clamp(80mm
80mm, able to enclose 80mm cable or 96mm 4mm flat steel ground wire) and automation function, is professional tool for measuring leakage current, current and voltage. It can simultaneously measure one-way leakage current and three-way voltages and offer simultaneous display on the screen, which all together allow users to operate easily and quickly. The meter is widely used in electric power, communications, meteorology, railway, oil field, construction, metrology, R&D institutes, mining, ect.
This kind of meter is designed with clamp iron core made with special alloy and latest magnetic screening technology, which make it able to avoid magnetic interference from outside and ensure high accuracy, stability and
4 5
reliability all the year around. It contains RS232 interface that allows its maximum storage of 200 sets of data to transfer into PC, thus facilitating further operations such as on-line monitoring, history lookup, dynamic display, history data recall, save and printing. Other functions such as backlight and data hold together with those mentioned above turn the meter a necessary tool for electrical safety testing.
II. Model Comparison
Model
UT253A
UT253B
Range
0.00mA 1200A 0.01mA 80mm 80mm
0.0mA 2000A 0.1mA 80mm 80mm
Resolution
Jaw Size
Page 5
III. Electric Symbols
IV. Technical Specifications
Extreme danger! To avoid personal injury or accidents due to electric shock, observe safety rules strictly.
Danger To avoid personal injury or accidents due to electric shock, please follow safety regulations.
Warning Conform to safety notes, otherwise it may cause personal injury or damage to the meter.
Dual insulation
Alternating Current AC
Direct Current DC
6 7
Functions
Power
Measuring Mode
Jaw Size
Range
Resolution
Conductor Location
Data Save
RS232 Port
to measure leakage current, current and three-phase AC voltage
6V DC(LR6 4 Alkaline dry battery,12 hours of battery life)
Clamp-shape CT integral mode
80mm 80mm (Able to clamp 80mm conductor or 96mm 4mm flat steel ground line)
Current: AC 0.00mA 1200A; Voltage: AC 0.00V 600V
Current: AC 0.01mA; Voltage: AC 0.01V
Placed at the center of clamp jaw
Maximum 200 sets, indicated by FULL flash icon.
Yes, for data transmission to PC for further data analysis
Page 6
Measuring Accuracy (23 3 70%
RH, conductor located
at the center of jaw
Communication Line
Frequency
Function Switchover
Sample Rate
Circuit Voltage
Display Mode
Dimensions
Backlight
Data Hold
0.00mA 300A: 1.5% 3dgt
300A 1200A: 2% 3dgt
1200A 2000A: 3% 3dgt
0.00V 600V 1.5% 3dgt
RS232 type, 1.8 meters long
Self-identification between 50Hz and 60Hz
Automatic about 2 times per second
To measure AC voltage below 600V
LCD 128dots 64dots Display Zone: 43mm 29mm
( Long wide thick)275mm 145mm 40mm
Controlled by LIGHT button
Data maintained: Indicated by HOLD icon
Overload Display
Auto Power Off
Battery Voltage
Weight
Operating Current
Operating
Temperature/ Humidity
Storage
Temperature/ Humidity
Insulation Strength
Safety Standards
Followed
Out of range indicated by OL icon
Automatically 15minutes later after power on, to conserve power energy
Low battery icon displays with battery voltage below 5.2V, please change batteries.
The meter 1kg(battery and accessories included)
50mA consumed with backlight on; 25mA when turning off backlight
-10 40 80%rh
-10 60 70%rh
AC 2kV/rms(Between iron core and housing)
IEC1010-1, IEC1010-2-032, Pollution Class 2, CAT (600V)
8 9
Page 7
V. Meter Description
1. Clamp Jaw
2. Function Buttons
3. LCD Display
4. Voltage Input Terminal
5. Jaw Opening Trigger
6. RS232 port (to transfer data to PC)
7. Screws (to connect upper and lower covers, 6pcs)
8. Battery Cover
9. Screw (to fix battery cover, 1pcs)
101112
Page 8
VI. Operating Instructions
1. Power on/off Press POWER button to power on, display LCD and enter into measuring mode, repress to turn off the meter. The meter will automatically switch off 15 minutes later after power on. You should change the battery if dark LCD appears after power on and may be caused by low battery voltage. Under data save status, you need to press HOLD button to cancel the operation before press POWER button to power off the meter.
2. Backlight Control Use LIGHT button to control backlight, suitable for dark sites and at night. The default is backlit status after power on.
3. Data Hold and Save Under measuring mode, press HOLD button to maintain displayed data, indicated by HOLD icon, and repress to cancel the operation. The meter
will automatically number current data at the time of saving, indicated by group number such as SAVE NO. 001 . Maximum data storage is 200 sets and is achieved when FULL icon shows
4. Data Access and Exit Under measuring mode, Press MENU to access data research with indication of READ icon. You can start data research from R 001 , press Up button to increment by 1, down button to increment by 10 and MENU button to exit this status and return to measuring mode.
5. Data Transmission to PC The accessory RS232 connection line is used for communication of the meter with PC. With the meter power on and the software running, several following operations such as history lookup, data recall, save, report sheet, history printing can all be performed. The more data the meter saves, more time it will take to read out. History data can be saved in Txt or Excel format.
13
Page 9
6. Data Delete Press CLEAR button to select data clearing option under data access mode, then use Left or Right button to move the cursor for selecting YES or NO , finally press MENU button to confirm the operation or return to the measuring mode.
7. Leakage Current, Current and Voltage Measurements
Dangerous Voltage! To avoid personal injury or accidents in case of electric shock, only trained and authorized staff is allowed to operate and must strictly observe safety rules
Danger! To avoid any damage to the meter or personal injury in case of electric shock do not measure voltage above 600V
Please Keep the jaw properly open or close when measuring leakage current or current.
Try to place the conductor at the center of the jaw
14
Please keep the jaw clean and regularly maintained after finishing measurement.
Ensure correct wire connection to avoid short-circuit problem during voltage measurement
Disconnect test leads with measured lines before pulling them out of the meter in case of electric shock
Clamping live and wires is to measure leakage current of electric instruments(2 wires needed)
Clamping the ground wire is to measure its leakage current (single wire needed)
Clamping all three phases and four wires is to measure total leakage current(four wires needed)
Clamping the main wire is to measure current of the main circuit (single wire needed).
neutral
15
Page 10
Measuring Reference Figure:
Measuring Leakage Current of Built-in Cable
Measuring
Tank
Measuring Total Leakage
Measuring Instrument Leakage Current
Measuring Ground Leakage Current
Measuring Current and
Voltage Phase Angles
16
Grounding Line
17
Page 11
VII. Battery Replacement
VIII. Packing List
Warning !
To avoid potential risks do not measure when battery cover is not well
placed.
Please ensure right battery polarity, otherwise it will damage the meter. Change batteries timely when low battery icon displays. Take out batteries when not used for a long time.
1. Low battery icon displays with voltage lower than 5.2V, please change the battery timely.
2. Press POWER button to switch off, loosen one screw on battery cover and open it after confirming the meter is off, finally change with new specified batteries and close the battery cover.
3. Press POWER button to switch on and check if batteries are successfully replaced, if not, repeat the second step.
18
The Meter
Carrying case
Data transmission software CD
RS232 exclusive communication line
Battery(LR6 Alkaline Dry Battery)
Giftbox/User's Manual/ Warranty Card/Certificate
1
1
1
1
1 set
19