UEi HA1 User Manual

INSTRUCTION MANUAL
HA1
1-800-547-5740 • Fax: (503) 643-6322
www.ueitest.com • email: info@ueitest.com
Introduction
The HA1 hermetic analyzer is designed to pro­vide the service technician with an easy to use, reliable test instrument. To obtain the maxi­mum benefit from the HA1, please take time to read these instructions.
Note: Under some test conditions 120 V AC may be present on a test cable. Refer to section on operation.
Features include
• Free locked rotors by reversing motor action
• Indicates continuity and ground faults by front
panel indicator lights
• Front panel input jacks to facilitate VOM
measurement of voltage and resistance
• Dual 120/240 V AC operation
• Color coded for easy use
Safety Notes
Before using this instrument, read all safety
information carefully. In this manual the word
“WARNING” is used to indicate conditions or actions that may pose physical hazards to the user. The word “CAUTION” is used to indicate conditions or actions that may damage this instrument.
International Symbols
Controls and Indicators
1. PWR Breaker: This is a combination 25A circuit breaker and a POWER ON switch.
2. CAP100/200/300: Selects one of the three starting capacitor ranges.
Position Range
100MFD 88-180MFD 200MFD 161-193MFD 300MFD 249-301MFD
3. REV/OFF/FWD: Switch determines the mode of operation of the compressor. In the FWD position, power is applied to the compressor motor run winding, and the start capacitor is connected to the START cable. In the REV position, power is applied
Hermetic Compressor Analyzer
to the compressor motor start winding and the start capacitor is connected to the RUN cable. In the OFF position, the power circuit to the motor is broken.
The REV position is momentary. The OFF and FWD positions are sustained.
4. FAULT/CONT./START: Is a multi-function switch. The FAULT (momentary action) position is used to check for shorts between the COM and the RUN/ START windings. The CONT. (sustained action) posi­tion is used to check for GROUND, RUN and START continuity. In the START (momentary action) position,
the start capacitor is connected to the
compressor motor through the REV/OFF/FWD switch.
5. Ground Test (Yellow): This push button switch
tests for ground continuity between system ground and the frame of the appliance being tested.
The HA1 introduces an “artificial ground” to make possible the testing for short circuits between the motor winding and the frame of appliances which
may not be directly grounded. For example, units
with two wire power cords would not be connected
to system ground (unless a separate ground connection were present).
6. Start Test (Red): This push button switch test two
conditions, depending on the position of the FAULT/ CONT./START switch.
Switch Position Condition Tested
FAULT Short between START winding
and frame
CONT. Continuity of START winding
7. Run Test (Black): This push button switch tests
two conditions, depending on the position of the
FAULT/CON./START switch.
Switch Position Condition Tested
FAULT Short between RUN winding
and frame
CONT. Continuity of RUN winding
8. Indicator Light: LINE NORM (white)/REV (red). These lights are used to indicate the “condition” of the power source to which the HA1 is connected.
Line Voltage Indicator Light Status
110 V AC NORM on/REV off Normal
REV on/NORM off Neutral and line wires
reversed at power
receptacle. Refer to
CAUTION under section on
110 V AC operation
NORM and REV System ground open or not
on (half intensity) connected at power receptacle
220 V AC NORM and REV Normal
on (full intensity)
9. Test Jacks: The four test jacks are connected directly to the test cable of the corresponding color:
COMMON = white GROUND* = yellow START = red RUN = black
The purpose of the test jacks is to facilitate
resistance and voltage readings by enabling
voltmeter/ohm meter test leads to be
connected to the compressor motor circuit
by inserting them into the appropriate jack
at the HA1 front panel.
*Since this cable is an “artificial” ground line it is colored yellow instead of green.
Operating Instructions
NOTE: Every effort has been made to make the HA1 a safe and versatile tester. However, under some circumstances line voltage may be present on the HA1 test cables when the control switches are in the OFF position. For this reason it is very important to read and become familiar with the section on Operating Instructions.
The following procedures have been detailed so a thorough understanding of the operation sequence
may be gained. In practice, the following tests may
be performed very quickly.
110 V AC Operation
CAUTION!
The HA1 is wired so that the white COMMON test cable is connected to the neutral side of the line. The red START and black RUN cables are connected to the hot side of the line by the POWER BREAKER switch and the REV/OFF/FWD switch. If the 110 V AC receptacle has been accidentally reverse wired, the white COMMON cable will be “hot” as soon as the HA1 is plugged into the power receptacle. To warn against such a condition, the red REV LINE indica­tor will light as soon as the HA1 is plugged into a grounded receptacle. In this case follow procedure B for reversed line condition.
A. Normal Test Procedure
1. The REV/OFF/FWD switch must be in the
OFF position.
2. Plug the HA1 into a grounded 110 V AC
receptacle and turn on the POWER switch.
This is a push on - push off switch. The white
NORM LINE indicator should light.
NOTE: If the receptacle is ungrounded, both the NORM and the REV LINE indicator will light, but at half intensity. The absence of a grounded line will not prevent any of the following tests from being made. IMPORTANT: verify that the receptacle is not also reverse wired by measuring the voltage between the white COM cable and a ground connection. A reversed line will measure 110 V AC. A normal line will measure zero volts. If the receptacle is reverse wired, follow procedure B.
3. Remove power to the unit which is to be tested.
4. Remove and identify the connectors going to
the common, start, and run terminals of the compressor motor.
5. Connect the test cables of the HA1 to the
compressor motor.
• Yellow GROUND cable to compressor
motor frame
• Red START cable to the start terminal
• Black RUN cable to the run terminal
• Leave the white COMMON cable
disconnected until step 7
6. Push the FAULT/CONT./START switch to the FAULT position and hold it there while press- ing the red START TEST and black RUN TEST
switches in turn. If either the START indica- tor or RUN indicator lights, there is a short
between that winding and the frame. STOP the
test and replace the unit.
7. Connect the white COMMON cable to the
common terminal of the compressor motor.
8. Press, in turn, the GROUND TEST, START TEST, and RUN TEST switches. The
appropriate indicator will light indicating continuity in the circuit being tested.
NOTE: To test for ground continuity the appliance must be plugged into a grounded 110 V AC receptacle or be grounded through an external connection.
If either the run or start winding indicate open,
stop the test and replace the unit.
9. Select the appropriate motor start capacitor.
10. Press the FAULT/CONT./START switch to the START position and, holding it there, throw the REV/OFF/FWD switch to the FWD posi-
tion. If the compressor starts, release the
START switch. The compressor will continue to run. The compressor may be stopped by returning the REV/OFF/FWD switch to the OFF position.
If the compressor does not start immediately,
the rotor may be locked. Release the START switch and return the REV/OFF/FWD switch to the OFF position.
11. To “bump” the compressor, press the FAULT/CONT./START switch to the START position and, holding it there, throw the REV/ OFF/FWD switch to the REV position. If the compressor starts immediately, then
release both switches. Repeat step 10 to
assure that the compressor will run in the forwards direction.
If the compressor does not start immediately
in reverse, then release both switches. A locked rotor will result in excessive current being drawn by the compressor.
12. Steps 10 & 11 may be repeated a few times in
an attempt to free a locked rotor, but care should be taken not to overheat the motor
windings. If the compressor still does not start,
then it should be replaced.
13. Push the POWER BREAKER switch OFF. Disconnect the HA1 test cables from the motor.
HA1
Hermetic Compressor Analyzer
Limited Warranty
The HA1 is warranted to be free from defects in materials and workmanship for a period of three year’s from the date of purchase.
If within the warranty period your instrument should become
inoperative from such defects, the unit will be repaired or replaced
at UEi’s option. This warranty covers normal use and does not cover
damage which occurs in shipment or failure which results from alteration, tampering, accident, misuse, abuse, neglect or improper maintenance. Batteries and consequential damage resulting from failed batteries are not covered by warranty.
Any implied warranties, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to
the express warranty. UEi shall not be liable for loss of use of the
instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim or claims for such damage, expenses or economic loss. A purchase receipt or other proof of original purchase date will be required before warranty repairs will be rendered.
Instruments out of warranty will be repaired (when repairable) for a
service charge. Return the unit postage paid and insured to:
1-800-547-5740 • FAX: (503) 643-6322
www.ueitest.com • Email: info@ueitest.com
This warranty gives you specific legal rights. You may also have
other rights which vary from state to state.
HA1-MAN 1/07 Copyright © 2007 UEi
PLEASE
RECYCLE
B. Reversed Line Operation
If the 110 V AC receptacle is reverse wired the main thing to remember is that the white COMMON cable
will be “hot” regardless of any HA1 switch setting. Therefore, exercise extreme care.
Follow the same procedure as for Normal Operation (A) steps 1 through 6, but keep the white COMMON
cable isolated to prevent accidental contact with it.
Before doing step 7, unplug the HA1 from the power
receptacle, connect the white COMMON cable to the
common terminal of the motor, and then plug the HA1 into the power receptacle.
Proceed with the tests outlines in steps 8 through 12,
section A.
220 V AC Operation
CAUTION!
The white COM cable will be hot as soon as the HA1 line cord is connected to 220 V AC. Always make sure that power to the HA1 is shut off before connecting the HA1 cables to the compressor motor on 220 V AC operation.
1. The REV/OFF/FWD switch and the PWR BREAKER switch must be in the off position.
2. Remove power to the unit which is to be tested.
3. Some compressor units have fans mounted in
the same housing as the compressor. If possible turn
down the thermostat, or disconnect the fan, so that the fan will not operate during the compressor tests. The fan noise could make it difficult to listen to the action of the compressor.
4. Remove and identify the connectors going to
the COMMON, START, and RUN terminals of the compressor motor.
5. Connect the test cables of the HA1 to the
compressor motor.
• Yellow GROUND cable to compressor
motor frame
• Red START cable to the start terminal
• Black RUN cable to the run terminal
• Leave the white COMMON cable disconnected until step 10
6. Use an adapter cord of at least #14 AWG wire size
to connect the HA1 to the 220 V AC input terminals.
7. Turn on the power to the HA1.
NOTE: Remember to keep the white COM cable out of the way. It will have 110 V AC on the clip.
8. Push the POWER BREAKER to the ON position.
Both LINE NORM/REV indicators will light.
9. Push the FAULT/CONT./START switch to the
FAULT position and hold it there while pressing the red START TEST and black RUN TEST switches in
sequence. If either the START indicator or RUN indicator lights, there is a short between that winding and the frame. STOP the test and replace the unit.
10. Turn off the 220 V AC power source to the HA1.
Connect the white COM cable to the common
terminal of the compressor motor.
11. Press, in turn, the GROUND, TEST, START TEST,
and RUN TEST switches. The appropriate indicator will light indicating continuity in the circuit being
tested. If either the run or start winding indicate
open, stop the test and replace the unit.
12. Select the appropriate motor start capacitor.
13. Press the FAULT/CONT./START switch to the
START position and, holding it there, throw the REV/OFF/FWD switch to the FWD position. If the
compressor starts, release the START switch. The compressor will continue to run. The compressor may be stopped by returning the REV/OFF/FWD switch to the OFF position.
If the compressor does not start immediately, the rotor
may be locked. Release the START switch and return the REV/OFF/FWD switch to the OFF position.
14. To “bump” the compressor, press the FAULT/CONT./START switch t the START posi­tion and, holding it there, throw the REV/OFF/ FWD switch to the REV position. If the com-
pressor starts immediately then release both switches. Repeat step 13 to assure that the com­pressor will run in the forwards direction.
If the compressor does not start immediately
in reverse, then release both switches. A locked rotor will result in excessive current being drawn by the compressor.
15. Steps 13 and 14 may be repeated a few times
in an attempt to free a locked rotor, but care should be taken not to overheat the motor
windings. If the compressor still does not start,
then it should be replaced.
15. Turn off the 220 V AC power source to the HA1. Disconnect the HA1 test cables from the motor.
Specifications
Running Current
25
Capacitor Range Position Range
100MFD 88-180MFD 200MFD 161-193MFD 300MFD 249-301MFD
Input Voltage
110 to 250 V AC