Tyco RC-1 User Manual

Model RC-1 Retard Chamber For Variable Pressure Wet Pipe Sprinkler Systems 300 psi (20,7 bar)
Tech ni cal Service s: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page 1 of 4 JULY 2009 TFP920
General Description
The Tyco® Model RC-1 Retard Chamber is required in installations that will be subject to pressure varia­tions, as are generally associated with public water supplies, in order to help prevent false alarms. The RC-1 is spe­cifically intended for use as a separate­ly ordered item for the Model AV-1-300 Alarm Check Valve ( TFP910). It can, however, also be used as a separately ordered item for changing out older style Retard Chambers used with the Central Model F/G, Gem Model A, or Star Model E/F Alarm Check Valves.
The Model RC-1 Retarding Chamber is a re-designation for the Gem Model F211 for use with Gem Model F20/ F200/F2001 Alarm Check Valves, as well as the Star Model S310 for use with Star Model S30/S300/S3001 Alarm Check Valves.
NOTICE
The Mode l RC-1 Retard Chamber described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the integrity of this device.
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The insta lli ng co ntr actor o r s pri nkl er manufacturer should be contacted relative to any questions.
Technical Data
Approvals
UL and ULC Listed, as well as FM Approved for use with the Model AV-1-300 Alarm Check Valves.
UL and ULC Listed, as well as FM, LPCB, and VdS Approved for use with the following Alarm Check Valves:
Model AV-1-175 Gem Model F20/F200/F2001 Gem Model A Star Model S30/S300/S3001
Working Water Pressure
300 psi (20,7 bar)
Construction
The Model RC-1 Retard Chamber shown in Figure 1 is cast iron, and a 3/4” x 1/2” x 3/4” Tee is provided at the outlet (top) for connection of a pressure alarm switch and/or water motor alarm. The Restriction Assem­bly shown in Figure 2 is provided with the AV-1-300 trim or ordered sepa­rately for retrofitting other valves. This assembly is comprised of brass re­strictions assembled to a cast iron or malleable iron threaded tee fitting. The screen is stainless steel.
Operation
When water flows steadily into the sprinkler system due to sprinkler op­eration, the Waterway Clapper in the Alarm Check Valve opens as shown in Figure 3. Water is then permitted to flow into the centrally located groove in the Seat Ring and out through the Alarm Port towards the Restriction As­sembly (Figure 2).
When the flow through the Inlet Re­striction of the Restriction Assembly exceeds the flow out through the Out­let Restriction, the Retard Chamber begins to fill. Subsequently, the Wa­ter Motor Alarm and/or the Pressure Alarm Switch activate. The alarms con­tinue to operate as long as the Water­way Clapper remains open. When the Clapper closes as a result of discon­tinued water flow, water in the alarm lines automatically drains out through the 1/8 inch (3,2 mm) drain orifice in the Restriction Assembly ( Figure 2).
In the case of variable pressure sys­tems, a transient surge in supply pres­sure that is sufficient only to open the Clapper momentarily will not cause a false alarm. The volume of the Retard Chamber is sufficiently large enough that it will not fill to operate the con­nected alarm devices. Any water in the alarm line is then automatically drained, further reducing the possibil­ity of a false alarm due to a successive transient surge in supply pressure.
3/4" x 1/2" x 3/4"
REDUCING TEE
3/4" x 1-1/2"
END-TO-END
8-1/8"
(206,0 mm)
DIA.
1/2" NPT INLET
CONNECTION
3/4" NPT WATER
CONNECTION
MOTOR ALARM
9-1/8"
(232,0 mm)
WATERFLOW
CONNECTION
PRESSURE
ALARM SWITCH
1/2" NPT
1 GAL.
(3,8 L)
CAPACITY
NOMINAL
NIPPLE
SCREEN
ORIFICE
ORIFICE
WITH 0.125" (3.2 mm)
RESTRICTION FITTING
WITH 0.219" (5.6 mm)
RESTRICTION FITTING
DRAIN
INLET
PRESSURE
WATERFLOW
ALARM SWITCH
MOTOR ALARM
VALVE
RESTRICTION
(3,2 mm)
OUTLET
ORIFICE
RETARD CHAMBER
BEGINS TO FILL
INLET EXCEEDS OUTLET,
RESTRICTION ASSEMBLY
WHEN FLOW THROUGH
ASSEMBLY
1/8"
CHAMBER
RETARD
INLET
ALARM PORT
RING GROOVE AND
THROUGH SEAT
WATERFLOW
MAIN
DRAIN
ALARM ACTUATE
WATERFLOW PRESSURE
CHAMBER OVERFLOWS,
ONCE RETARD
WATER MOTOR
ALARM SWITCH AND
WATERFLOW
TO SYSTEM
WATERFLOW
TO WATER
7/32"
ORIFICE
(5,6 mm)
UPON SPRINKLER FLOW, WATERWAY
CLAPPER OPENS
GAUGE
GAUGE
SUPPLY
PRESSURE
PRESSURE
SYSTEM
CHECK
VALVE
ALARM
TFP920
Page 2 of 4
Installation
The Tyco® Model RC-1 Retard Cham­ber must be installed in accordance with the specific instructions provided with the Tyco® Model AV-1-300 Alarm Check Valve (TFP910). The standard trim for these Alarm Check Valves in­cludes all necessary components in­cluding the Restriction Assembly shown in Figure 2.
s)NTHECASEOFRETROlTTING#ENTRAL
Model F/G Alarm Check Valves, re­fer to Figure 4.
s)NTHECASEOFRETROlTTING'EM-OD-
el A Alarm Check Valves, refer to Figure 5.
s)NTHECASEOFRETROlTTING3TAR-OD-
el E/F Alarm Check Valves, refer to Figures 6 and 7.
Apply pipe thread sealant sparingly to male threads only.
Care and Maintenance
Responsibility lies with the owner for the inspection, testing, and mainte­nance of their fire protection system and devices in compliance with this document, as well as with the appli­cable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any authority having jurisdiction. Contact the installing contractor or product manufacturer regarding any questions.
Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.
Specific consideration must be given to cleaning the Screen within the Re­striction Assembly, as well as the Y­Strainer. More frequent cleaning than that required by NFPA 25 may be nec­essary as determined after the first in­spection and is a function of the wa­ter quality with respect to water borne debris.
NOTICE
Bef ore c los ing a f i re pr ote cti o n system control valve for inspection or m aintenanc e wor k o n th e f ire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities, and notify all personnel who may be affected by this action.
After placing a fire protection system in service, notify the proper authorities an d a dvis e those responsible for monitoring proprietary and/or central station alarms.
FIGURE 2
RESTRICTION ASSEMBLY
FIGURE 3
MODEL RC-1 RETARD CHAMBER
OPERATION
FIGURE 1
MODEL RC-1
RETARD CHAMBER
1/2" x 2" Nipple Select per Table
DESCRIPTION
3/4" x 1/2" 90° Reducing Elbow
NIPPLES & FITTINGS
1/2" x 1-1/2" Nipple 3 4
1
2
NO.
than TFSBP.
Includes nipple and tee per Figure 1.
Nipples & fittings
from sources other
may be acquired
1. . . . . . . .
. . . . . . .
2
1
1
. . . . . . . .
. . . . .3
1
QTY.
1
P/N 52-353-1-005
1/2" Y-STRAINER
RETARD CHAMBER
P/N 52-211-1-002
RETARD CHAMBER DRAIN TRIM
3
RESTRICTION
ASSEMBLY
P/N 92-210-1-005
TO ACCOMMODATE NEW
RETARD CHAMBER TRIM
(SEE FIGURE 2)
ROTATE EXISTING
WATERFLOW
CONNECTION
PRESSURE
ALARM SWITCH
1/2" NPT
3/4" NPT WATER
CONNECTION
MOTOR ALARM
2
2
WITH ALARM TRIM
REFER TO DATA
SHEET 7-3.0
(6"/DN150 SHOWN)
ALARM CHECK VALVE
CENTRAL MODEL F/G
2
4
1
MODEL RC-1
2
8" (DN200) 3/4" x 1-1/2"
3/4" x 4-1/2"
Nipple 4 SizeValve
4" (DN100) 6" (DN150)
3/4" x 6"
ALARM SWITCH
PRESSURE
CONNECTION
WATERFLOW
1/2" Y-STRAINER P/N 52-353-1-005
VALVE SIZE & TRIM
LENGTHS TO SUIT
ARRANGEMENT
NIPPLE
WITH BASIC TRIM
ALARM CHECK VALVE
(6"/DN150 SHOWN)
REFER TO DATA
GEM MODEL A
SHEET TD1
MOTOR ALARM
POINT
CONNECTION
DRIP FUNNEL
(IF REQUIRED)
P/N 92-210-1-005
ASSEMBLY
(SEE FIGURE 2)
RESTRICTION
1/2" NPT
ALARM SWITCH
WATERFLOW
CONNECTION
PRESSURE
3/4" NPT WATER
MOTOR ALARM
CONNECTION
3/4" NPT WATER
RETARD CHAMBER
REFER TO DATA
WITH ALARM TRIM
GEM MODEL A-3
SHEET TD1-1
REMOVE
ALARM TRIM
REMOVE
ORIGINAL
TO THIS
1/2" NPT
RETARD CHAMBER
P/N 52-211-1-002
MODEL RC-1
TEE PER FIGURE 1)
(INCLUDES NIPPLE &
TFP920
Page 3 of 4
repaired or replaced, at TFSBP’s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of prod­ucts. TFSBP shall not be responsible for sprinkler system design errors or inac curate or incomplete information sup plied by Buyer or Buyer’s repre­sentatives.
In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for inciden­tal, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFSBP was informed about the pos­sibility of such damages, and in no event shall TFSBP’s liability exceed an amount equal to the sales price.
The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warran­ties of merchantability and fitness for a particular purpose.
This limited warranty sets forth the ex clusive remedy for claims based on failure of or defect in products, materi­als or components, whether the claim is made in contract, tort, strict liability or any other legal theory.
This warranty will apply to the full ex­tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.
Limited Warranty
Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in mate rial and work­manship when paid for and properly installed and maintained under nor­mal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for products or com ponents manufactured by companies not affili­ated by ownership with TFSBP or for products and components which have been subject to misuse, improper in­stallation, corrosion, or which have not been installed, maintained, modi­fied or repaired in accordance with ap plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFSBP to be defective shall be either
FIGURE 4
MODEL RC-1 RETARD CHAMBER
WITH CENTRAL MODEL F/G ALARM CHECK VALVES
FIGURE 5
MODEL RC-1 RETARD CHAMBER
WITH GEM MODEL A ALARM CHECK VALVES
may be acquired from sources other
Nipples & fittings
tee per Figure 1.
Includes nipple and
. . . . .13 3/4" x 3-1/2" Nipple
than TFSBP.
2
1
1/2" x 1-1/2" Nipple
NIPPLES & FITTINGS
Reducing Elbow
3/4" x 1/2" 90°
DESCRIPTION
1
2
NO.
. . . . .
. . . . . . . .31
QTY.
1
DISCARD EXISTING
STAR MODEL E
REFER TO DATA
SHEET 2-1.1.20
ALARM CHECK VALVE
WITH ALARM TRIM
(SEE FIGURE 2)
2
SEPARATE
CHAMBER
EXISTING 1/2"
TO FACILITATE
UNION HALVES
ASSEMBLY OF
NEW RETARD
RETARD CHAMBER DRAIN TRIM
TRIM
RETARD CHAMBER TRIM
TO ACCOMMODATE NEW
ROTATE EXISTING
MOTOR ALARM
CONNECTION
3/4" NPT WATER
1/2" NPT
ALARM SWITCH
PRESSURE
CONNECTION
WATERFLOW
P/N 92-210-1-005
ASSEMBLY
RESTRICTION
MODEL RC-1
P/N 52-211-1-002
RETARD CHAMBER
1/2" Y-STRAINER
P/N 52-353-1-005
2
2
3/4" x 2" NIPPLE
REMOVE AND
3
1
2
2
(SEE FIGURE 2)
TO ACCOMMODATE NEW
RETARD CHAMBER TRIM
ROTATE EXISTING
RETARD CHAMBER DRAIN TRIM
(6"/DN150 SHOWN)
REFER TO DATA
SHEET 2-1.1.10
ALARM CHECK VALVE
WITH ALARM TRIM
STAR MODEL F
TO FACILITATE
TRIM
NEW RETARD
ASSEMBLY OF
CHAMBER
UNION HALVES
EXISTING 1/2"
SEPARATE
REMOVE AND
DISCARD EXISTING
3/4" x 2" NIPPLE
1/2" Y-STRAINER
P/N 52-353-1-005
3
1
2
MODEL RC-1
RETARD CHAMBER
P/N 52-211-1-002
2
PRESSURE
MOTOR ALARM
RESTRICTION
ASSEMBLY
CONNECTION
P/N 92-210-1-005
2
CONNECTION
ALARM SWITCH
3/4" NPT WATER
WATERFLOW
1/2" NPT
QTY.
. . . . . . . .
. . . . .
. . . . .3 3/4" x 3-1/2" Nipple
Includes nipple and tee per Figure 1.
Nipples & fittings
than TFSBP.
from sources other
may be acquired
2
1
NO.
Reducing Elbow
NIPPLES & FITTINGS
DESCRIPTION
3/4" x 1/2" 90°
1/2" x 1-1/2" Nipple
1
2
1
1
3
1
© 2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS
, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
TFP920 Page 4 of 4
FIGURE 6
MODEL RC-1 RETARD CHAMBER
WITH STAR MODEL E ALARM CHECK VALVES
FIGURE 7
MODEL RC-1 RETARD CHAMBER
WITH STAR MODEL F ALARM CHECK VALVES
Ordering Information
Orders for the Tyco® Model RC-1 and additional components, as applicable, must include the description and Part Number (P/N).
RC-1
Specify: Model RC-1 Retard Chamber w/galvanized steel fittings, P/N 52-211-1-002.
Separately Ordered Parts for Retrofitting Other Valves
When retrofitting according to Figures 4, 5, 6, or 7, the Restriction Assembly, Y-Strainer, and associated pipe nipples and fittings must be ordered separately to complete installation. Pipe nipples and fittings can be acquired from sources other than TFSBP.
Specify: 1/2 inch Y-Strainer, P/N 52-353-1-005.
Specify: Restriction Assembly, P/N 92-210-1-005.
Loading...