Tyco Rapid Response LFII, TY2524 Series Manual

800-381-9312
Technical Services
+1- 40 1-7 81- 822 0
www.tyco-fi re.com
RAPID RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are decora­tive, fast response, fusible solder sprin­klers designed for use in residential oc­cupancies such as homes, apartments, dormitories, and hotels.
The Cover Plate/Retainer Assembly con­ceals the sprinkler operating compo­nents above the ceiling. The  at pro le of the Cover Plate provides the optimum aesthetically appealing sprinkler design. Additionally, the concealed design of the Series LFII Residential Flat-Plate Con­cealed Pendent Sprinklers provides 1/2 inch (12,8 mm) vertical adjustment. This adjustment provides a measure of  ex­ibility when cutting  xed sprinkler drops.
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are in­tended for use in the following systems:
• wet and dry pipe residential sprin­kler systems for one- and two-fam­ily dwellings and mobile homes per NFPA 13D
• wet and dry pipe residential sprin­kler systems for residential occu­pancies up to and including four sto­ries in height per NFPA 13R
• wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13.
The Series LFII Residential Sprinklers have been designed with heat sensitiv­ity and water distribution characteristics proven to help in the control of residen-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fi re situation or cause it to operate prematurely.
tial  res and to improve the chance for occupants to escape or be evacuated.
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap protects the sprinkler during ceiling installation or  nish. After ceiling installation is com­plete, the Protective Cap is removed and the Cover Plate/Retainer Assem­bly is installed. Removing the Protec­tive Cap is required for proper sprinkler performance.
Dry Pipe System Application
The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler offers a laboratory approved option for design­ing dry pipe residential sprinkler sys­tems, whereas, most residential sprin­klers are laboratory approved for wet systems only.
Through extensive testing and as ref­erenced in U.S. Patent 7,712,543, it has been determined that the number of de­sign sprinklers (hydraulic design area) for the Series LFII Residential Flat-Plate Concealed Sprinklers (TY2524) need not be increased over the number of design sprinklers (hydraulic design area) speci­ ed for wet pipe sprinkler systems, as is customary for density/area sprinkler systems designed per NFPA 13, 13D, or 13R.
Consequently, the Series LFII Residen­tial Flat-Plate Concealed Sprinklers (TY2524) offer the features of non-wa­ter  lled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems de­signed to NFPA 13, 13D, or 13R. Non­water  lled pipe will permit options for areas sensitive to freezing.
NOTICE
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) described herein must be installed and maintained in compliance with this doc­ument and the applicable standards of the National Fire Protection Association, in addition to the standards of any au­thorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain­ing their fi re protection system and de­vices in proper operating condition. The installing contractor or sprinkler manu­facturer should be contacted with any questions.
Sprinkler Identifi cation Number (SIN)
TY2524
Page 1 of 6 APRIL 2012 TFP443
TFP443
Page 2 of 6
BODY
(1/2" NPT)
CAP
SADDLE
SUPPORT
CUP WITH
ROLL FORMED
THREADS
GUIDE
PIN
GUIDE PIN
HOUSING
DEFLECTOR
THREAD INTO
SUPPORT CUP
UNTIL MOUNTING
SURFACE IS
FLUSH WITH
CEILING
SPRINKLER/SUPPORT CUP
ASSEMBLY
SEALING
ASSEMBLY
SPRINKLER
WRENCHING
AREA
COMPRESSION
SCREW
LEVER
SOLDER LINK
ELEMENT
DEFLECTOR
(OPERATED
POSITION)
RETAINER
WITH THREAD
DIMPLES
EJECTION
SPRING
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
— SPRINKLER WRENCH —
SOLDER
TAB
COVER PLATE/RETAINER
ASSEMBLY
COVER
PLATE
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED
PENDENT SPRINKLER (TY2524)
— ASSEMBLY —
SPRINKLER-
SUPPORT CUP
ASSEMBLY
DISPOSABLE
1/2"
NPT
COVER-
RETAINER
2-1/2" DIA.
(63,5 mm)
SPRINKLER-
SUPPORT CUP
ASSEMBLYASSEMBLY
3-3/16" DIA.
(81,0 mm)
1/2" (12,7 mm)
THREADED
ADJUSTMENT
1/8" GAP
(3,2 mm)
3/16"
(4,8 mm)
FACE OF
SPRINKLER
FITTING
1-7/8"±1/8"
(47,6 mm ±3,2 mm)
MOUNTING
SURFACE
TIP OPERATED POSITION
PROTECTIVE CAP
FIGURE 3
PROTECTIVE CAP AND ACTIVATED DEFLECTOR
— INSTALLATION DIMENSIONS —
OPERATED
SPRINKLER
COVER
PLATE
RETAINER
7/8" (22,2 mm)
1-1/8" (28,6 mm)
DEFLECTOR IN
TFP443
Page 3 of 6
Technical Data
Approvals
UL and C-UL Listed
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only listed with the Series LFII Concealed Cover Plates having a factory-applied  nish.
For details on approvals, refer to the De­sign Criteria section.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coeffi cient
K=4.9 GPM/psi
Temp erat ure Rati ng
Sprinkler: 160°F (71°C) Cover Plate: 139°F (59°C)
Vertical Adjustment
1/2 inch (12,7 mm)
Finishes
Refer to the Ordering Procedure section.
Physical Characteristics
Cover Plate/Retainer Assembly:
Cover Plate . . . . . . . . . . . . . Copper
Ejection Spring . . . . Stainless Steel
Retainer . . . . . . . . . . . . . . . . Brass
Sprinkler/Support Cup Assembly:
Body . . . . . . . . . . . . . . . . . . . Brass
Cap . . . . . . . . . . . . . . . . . . . Bronze
Saddle . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly . . . . . . .Beryllium
Soldered Link Halves . . . . . . Nickel
Lever . . . . . . . . . . . . . . . . . . Bronze
Compression Screw . . . . . . . Brass
De ector . . . . . . . . . . . . . . . Bronze
Guide Pin Housing. . . . . . . . Bronze
Guide Pins . . . . . . . . . . . . . Bronze
Support Cup . . . . . . . . . . . . . . Steel
1/2
(70,6 LPM/bar
Nickel w/ TEFLON
1/2
)
Operation
When exposed to heat from a  re, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup As­sembly. At this point, the De ector, sup­ported by the Guide Pins, drops down to its operated position.
The Solder Link Element of the Sprinkler/ Support Cup Assembly is comprised of two link halves that are soldered togeth­er with a thin layer of solder. When the rated temperature is reached, the sol­der melts and the two link halves sepa­rate, allowing the sprinkler to activate and  ow water.
Design Criteria
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are UL and C-UL Listed for installation in ac­cordance with this section:
Residential Sprinkler Design Guide
When conditions exist that are outside the scope of the provided criteria, re­fer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be accept­able to the authority having jurisdiction.
System Type
Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized.
Refer to Technical Data Sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems.
Hydraulic Design (NFPA 13D and 13R)
For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin­kler  ow rate are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler  ow rate is the mini­mum required discharge from each of the total number of “design sprinklers” as speci ed in NFPA 13D or NFPA 13R. The number of “design sprinklers” spec­i ed in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems.
Hydraulic Design (NFPA 13)
For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis­charge from each of the four sprinklers is to be the greater of the following:
• The  ow rates given in Tables A and B as a function of temperature rating and the maximum allowable cover­age area.
• A minimum discharge of 0.1 gpm/ft2. over the “design area” comprised of the four most hydraulically demand­ing sprinklers for the actual coverage areas being protected by the four sprinklers.
The number of “design sprinklers” speci ed in NFPA 13 for wet pipe sys­tems is to be applied when designing dry pipe systems.
Dry Pipe System Water Delivery
When using the Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) in dry pipe sprinkler systems, the time for water delivery exceed 15 seconds for the most remote operat­ing sprinkler.
Obstruction to Water Distribution.
Sprinklers are to be located in accor­dance with the obstruction rules of NFPA 13D, 13R, an d 13 as ap pl ic able for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490.
Operational Sensitivity
Install sprinklers relative to the ceiling mounting surface as shown in Figure 3.
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup can delay sprinkler op­eration in a  re situation.
Sprinkler Spacing
The minimum spacing between sprin­klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot ex­ceed the length of the coverage area (Table A) being hydraulically calculated (e.g., a maximum of 12 feet for a 12 ft. x 12 ft. coverage area or 20 feet for a 20 ft. x 20 ft. coverage area.)
TFP443
Page 4 of 6
(c, d, e)
(b)
Sloped Ceiling
(c, d, e)
(Greater than 4 inch rise
up to maximum 8 inch
rise for 12 inch run)
160°F (71°C)
Sprinkler
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
22 GPM (83,3 LPM)
20.2 psi (1,39 bar)
24 GPM (90,8 LPM)
24.0 psi (1,65 bar)
Minimum Flow and Residual Pressure
Maximum
Coverage
(a)
Area
Ft. x Ft .
(m x m)
Maximum
Spacing
Ft.
(m)
Horizontal Ceiling
(Maximum 2 inch rise
for 12 inch run)
(c, d, e)
160°F (71°C)
Sprinkler
12 x 12
(3,7 x 3,7)
14 x 14
(4,3 x 4,3)
16 x 16
(4,9 x 4,9)
18 x 18
(5,5 x 5,5)
20 x 20
(6,1 x 6,1)
(a) For coverage area dimensions less than or between those indicated, use the minimum required  ow for the next highest coverage area for which
Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum  ow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details.
(c) For NFPA 13D 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped ceiling con gurations up to 8:12 pitch.
Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontal ceiling criteria.
(d) For NFPA 13R applications, Horizontal Ceiling criteria may be used for sloped ceiling con gurations up to 8:12 pitch when acceptable to
the local authority having jurisdiction.
(e) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.
this table must be used.
12
(3,7)
14
(4,3)
16
(4,9)
18
(5,5)
20
(6,1)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
20 GPM (75,7 LPM)
16.7 psi (1,15 bar)
2
over the design area or the  ow in accordance with the criteria in
WET PIPE SYSTEM
Sloped Ceiling
(Greater than 2 inch rise
up to maximum 4 inch
rise for 12 inch run)
160°F (71°C)
Sprinkler
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
22 GPM (83,3 LPM)
20.2 psi (1,39 bar)
24 GPM (90,8 LPM)
24.0 psi (1,65 bar)
SERIES LFII RESIDENTIAL FL AT-PLATE CONCEALED PENDENT SPRINKLER (TY2524)
TABLE A
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
— WET PIPE SYSTEMS —
Maximum
Coverage Area
Ft. x Ft . (m x m)
(a)
Maximum Spacing
Ft.
Horizontal Ceiling Minimum Flow and Residual Pressure
(m)
Minimum Flow and Residual Pressure
(Maximum 2 Inch Rise for 12 Inch Run)
160°F (71°C) Sprinkler
DRY PIPE SYSTEM
12 x 12
(3,7 x 3,7)
14 x 14
(4,3 x 4,3)
16 x 16
(4,9 x 4,9)
18 x 18
(5,5 x 5,5)
20 x 20
(6,1 x 6,1)
(a) For coverage area dimensions less than or between those indicated, use the minimum required  ow for the next highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum  ow in GPM (LPM) from each sprinkler. The associated residual pressures
are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details.
(c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.
this table must be used.
12
(3,7)
14
(4,3)
16
(4,9)
18
(5,5)
20
(6,1)
15 GPM (56,8 LPM)
9.4 psi (0,65 bar)
15 GPM (56,8 LPM)
9.4 psi (0,65 bar)
16 GPM (60,6 LPM)
10,7 psi (0,74 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
21 GPM (79,5 LPM)
18,4 psi (1,27 bar)
2
over the design area or the  ow in accordance with the criteria in
(b)
(c)
SERIES LFII RESIDENTIAL FL AT-PLATE CONCEALED PENDENT SPRINKLER (TY2524)
TABLE B
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
— DRY PIPE SYSTEMS —
TFP443
Page 5 of 6
Installation
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must be installed in accordance with this section:
General Instructions
Damage to the Solder Link Element dur­ing installation can be avoided by han­dling the sprinkler by the Support Cup only; that is, do not apply pressure to the Solder Link Element (Figure 1).
A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min­imum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.
Do not attempt to compensate for insuf­ cient adjustment in the Cover Plate/ Retainer Assembly by under- or over­tightening the sprinkler. Re-adjust the position of the sprinkler  tting to suit.
Step 1. Install pendent sprinklers in the pendent position, with the center­line of the sprinkler perpendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe-thread sealant ap-
plied to the pipe threads, and using the W-Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler/Sup­port Cup Assembly into the  tting. The W-Type 18 Wrench accepts a 1/2 inch ratchet drive.
Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec­tive Cap helps prevent damage to the De ector and Guide Pins during ceiling installation and/or during application of the  nish coating of the ceiling.
NOTICE
As long as the protective Cap remains in place, the system is considered “Out Of Service”.
Step 5. After the ceiling has been com­pleted with the 2-1/2 inch (63 mm) diam­eter hole and in preparation for install­ing the Cover Plate/Retainer Assembly, remove and discard the Protective Cap, and verify that the De ector moves up and down freely.
If the sprinkler has been damaged and the de ector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler.
Step 6. Screw on the Cover Plate/Re­tainer Assembly until its  ange contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly such that it lifts a ceiling panel out of its normal position.
If the Cover Plate/Retainer Assembly cannot be engaged with the Mounting Cup or the Cover Plate/Retainer Assem­bly cannot be engaged suf ciently to contact the ceiling, the Sprinkler Fitting must be repositioned.
Care and Maintenance
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinkler (TY2524) must be maintained and serviced in accordance with ths section:
Before closing a  re protection system main control valve for maintenance work on the  re protection system that it con­trols, obtain permission to shut down the affected  re protection system from the proper authorities and notify all person­nel who may be affected by this action.
Absence of a Cover Plate may delay the sprinkler operation in a  re situation.
The owner must assure that the sprin­klers are not used for hanging any ob­jects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-opera­tion in the event of a  re or inadvertent operation may result.
When properly installed, there is a nomi­nal 1/8 inch (3,2 mm) air gap between the lip of the Cover Plate and the ceil­ing, as shown in Figure 3. This air gap is necessary for proper operation of the sprinkler by allowing heat  ow from a  re to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a  re situation. If the ceiling needs repainting after sprinkler installation, exercise care to ensure that the new paint does not seal off any of the air gap. Failure to do so may impair sprinkler operation.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted units. Non-factory applied paint may adversely delay or prevent sprinkler operation in the event of a  re.
Do not pull the Cover Plate relative to the Retainer. Separation may result.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi­ ed or overheated sprinklers must be replaced.
Care must be exercised to avoid dam­age to the sprinklers - before, during, and after installation. Sprinklers dam­aged by dropping, striking, wrench twist/ slippage, or the like, must be replaced.
The owner is responsible for the in­spection, testing, and maintenance of their  re protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan­dards of any other authorities having ju­risdiction. Contact the installing contrac­tor or sprinkler manufacturer regarding any questions.
Automatic sprinkler systems are rec­ommended to be inspected, tested, and maintained by a quali ed Inspec­tion Service in accordance with local requirements and/or national codes
.
TFP443
Page 6 of 6
Limited Warranty
Products manufactured by Tyco Fire Production Products (TFPP) are war­ranted solely to the original Buyer for ten (10) years against defects in ma­terial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFPP. No warran­ty is given for products or components manufactured by companies not af­ liated by ownership with TFPP or for products and components which have been subject to misuse, improper in­stallation, corrosion, or which have not been installed, maintained, modi ed or repaired in accordance with applicable Standards of the National Fire Protec­tion Association, and/or the standards of any other authorities having jurisdiction. Materials found by TFPP to be defec­tive shall be either repaired or replaced, at TFPP’s sole option. TFPP neither as­sumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFPP shall not be responsible for sprinkler system design errors or inaccurate or incomplete in­formation supplied by Buyer or Buyer’s representatives.
In no event shall TFPP be liable, in con­tract, tort, strict liability or under any other legal theory, for incidental, indi­rect, special or consequential damages, including but not limited to labor charg­es, regardless of whether TFPP was in­formed about the possibility of such damages, and in no event shall TFPP’s liability exceed an amount equal to the sales price.
The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of mer­chantability and  tness for a particular purpose.
This limited warranty sets forth the ex­clusive remedy for claims based on fail­ure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any oth­er legal theory.
This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indicate the full product description and Part Number (P/N).
Sprinkler/Support Cup Assembly
Specify: Series LFII (TY2524), K=4.9 (70,6), Residential Flat-Plate Concealed Pendent Sprinkler without Cover Plate/ Ret ain er A s semb ly, P/N 51-114 -1-160 .
Cover Plate/Retainer Assembly for Horizontal or Sloped Ceiling Applications
Specify: Series LFII (TY2524), K=4.9 (70,6), Residential Flat-Plate Concealed Pendent Sprinkler Cover Plate/Retain­er Assembly with (specify)  nish, P/N (specify):
Off White . . . . . . . . . . . . . . . . P/N 56-201-0-135
Pure White*
(RAL9010) . . . . . . . . . . . . . . P/N 56-201-3-135
Signal White**
(RAL9003) . . . . . . . . . . . . . . P/N 56-201-4-135
Standard White (Grey White)
(RAL9002) . . . . . . . . . . . . . . P/N 56-201-5-135
Custom . . . . . . . . . . . . . . . . . . .P/N 56-201-X-135
* Eastern Hemisphere sales only
** Previously known as Bright White
Note: All Custom Cover Plates are painted us­ing Sherwin Williams Interior Latex Paint. Contact TYCO Customer Ser vice with any questions related to custom orders.
Optional Cover Plate/Retainer As­sembly for Horizontal Ceiling Applications Only
Specify: Series LFII (TY2524), K=4.9 (70,6), Residential Flat-Plate Concealed Pendent Sprinkler Cover Plate/Retain­er Assembly with (specify)  nish, P/N (specify):
Off White . . . . . . . . . . . . . . . . .P/N 56-122-0-135
Pure White*
(RAL9010) . . . . . . . . . . . . . . . . P/N 56-122-3-135
Signal White**
(RAL9003) . . . . . . . . . . . . . . . . P/N 56-122-4-135
Custom . . . . . . . . . . . . . . . . . . . P/N 56-122-X-135
* Eastern Hemisphere sales only
** Previously known as Bright White
Note: All Custom Cover Plates are painted us­ing Sherwin Williams Interior Latex Paint. Contact TYCO Customer Ser vice with any questions related to custom orders.
Sprinkler Wrench
Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265.
Copyright © 2012 Tyco Fire Protection Products. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Loading...