4.9 K-factor Pendent Sprinkler
Wet Pipe and Dry Pipe Systems
www.tyco-fire.com
General
Description
TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers (TY2234)
are decorative, fast response, frangible bulb sprinklers designed for use
in residential occupancies such as
homes, apartments, dormitories, and
hotels. When aesthetics and optimized
flow characteristics are the major consideration, the Series LFII Residential
Sprinklers (TY2234) should be the first
choice.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
• wet and dry pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per
NFPA 13 D
• wet and dry pipe residential sprinkler
systems for residential occupancies
up to and including four stories in
height per NFPA 13R
• wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
The recessed version of the Series
LFII Residential Sprinklers is intended
for use in areas with finished ceilings.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 inch
(6,4 mm) of recessed adjustment or up
to 1/2 inch (12,7 mm) of total adjustment
from the flush ceiling position. The
adjustment provided by the Recessed
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Escutcheon reduces the accuracy to
which the pipe drops to the sprinklers
must be cut.
The Series LFII Residential Sprinklers
have been designed with heat sensitivity and water distribution characteristics proven to help in the control
of residential fires and to improve the
chance for occupants to escape or be
evacuated.
Dry Pipe System Application
The Series LFII Residential Pendent
and Recessed Pendent Sprinklers
offers a laboratory approved option
for designing dry pipe residential sprinkler systems, whereas, most residential
sprinklers are laboratory approved for
wet systems only.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for
the Series LFII Residential Pendent and
Recessed Pendent Sprinklers (TY2234)
need not be increased over the number
of design sprinklers (hydraulic design
area) as specified for wet pipe sprinkler
systems, as is accustomed for density/
area sprinkler systems designed per
NFPA 13 .
Consequently, the Series LFII Residential Sprinklers offer the features
of non-water filled pipe in addition
to not having to increase the number
of design sprinklers (hydraulic
design area) for systems designed to
NFPA 13, 13D, or 13R.
NOTICE
The Series LFII Residential Pendent
and Recessed Pendent Sprinklers
(TY2234) described herein must be
installed and maintained in compliance
with this document and the applicable
standards of the National Fire Protection Association (NFPA), in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY2234
Technical
Data
Approvals
UL Listed (for use with wet pipe and dry
pipe systems)
C-UL Listed (for use only with wet pipe
systems)
Certified to all requirements of
NSF/ANSI 61
(Refer to the Design Criteria section for
details on these approvals.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=4.9 gpm/psi
Temperature Rating
155°F (68°C) or 175°F (79°C)
Finishes
Natural Brass, Pure White, Signal White, or
Chrome Plated
4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (T Y2234)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers are UL
and C-UL Listed for installation in
accordance with this section.
Residential Sprinkler
Design Guide
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer’s recommendations that may be
acceptable to the local authority having
jurisdiction.
System Ty p e s
Per the UL Listing, wet pipe and dry
pipe systems may be utilized. Per the
C-UL Listing, only wet pipe systems
may be utilized.
Refer to Technical Data Sheet TFP485
for the use of residential sprinklers in
residential dry pipe systems.
Ceiling Types
Smooth flat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13, as
applicable.
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA 13D
or NFPA 13R, the minimum re quired
sprinkler flow rates are given in
NOMINAL
MAKE-IN
1/2"
NPT
PLATE SEATING
SURFACE
2-1/4"
(57,2 mm)
1-5/8"
(41,3 mm)
FIGURE 1
Tables A and B as a function of temperature rating and the maximum
allowable coverage areas. The
sprinkler flow rate is the minimum
required discharge from each of the
total number of “design sprinklers” as
specified in NFPA 13D or NFPA 13R.
The number of “design sprinklers”
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when
designing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers
is to be the greater of the following:
•
The ow rates given in Table A or
B as a function of temperature
rating and the maximum allowable
coverage area.
•
A minimum discharge of 0.1 gpm/ft2
over the “design area” comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
The number of design sprinklers specified in NFPA 13 for wet pipe systems is
to be applied when designing dry pipe
systems.
Dry Pipe System Water Delivery
When using the Series LFII Residential
Sprinklers (TY2234) in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the
most remote operating sprinkler.
Obstruction to
Water Distribution
Sprinklers are to be located in accordance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
2-7/8" DIA.
(73,0 mm)
WRENCH
FLATS
STYLE 20
RECESSED
the obstruction criteria described within
the Technical Data Sheet TFP490.
Operational Sensitivity
Sprinklers are to be installed with a
deflector-to-ceiling distance of 1-1/4 to
4 inches.
Sprinkler Spacing
The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot
exceed the length of the coverage area
(Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 20 feet
for a 20 ft. x 20 ft. coverage area).
Page 3
TFP400
Page 3 of 6
Minimum Flow and Residual Pressure
WET PIPE SYSTEM
Maximum
Coverage
Area
Ft. x Ft.
(m x m)
12 x 12
(3,7 x 3,7)
14 x 14
(4,3 x 4,3)
16 x 16
(4,9 x 4,9)
18 x 18
(5,5 x 5,5)
20 x 20
(6,1 x 6,1)
Notes:
1. For cover age are a dimen sions l ess tha n or bet ween th ose indicated , use the minimum required ow for the next highest coverage area for which hydraul ic desi gn
criter ia are stated.
2. Requireme nt is based on minimum ow in gpm (lp m) from each spr inkle r. The asso ciated residual pre ssure s are ca lculated usin g the nominal
K-factor. Refe r to Hydraulic De sign under the D esign C riter ia sect ion.
3. F or NFPA 13 residential applic ation s, the greater of 0.1 gpm/ft.2 over the de sign ar ea or the ow in accordance with th e crite ria in thi s table m ust be u sed.
Ordinary Temperature Rating
(1)
155°F (68°C)
Flow
Pressure
gpm
(l/min)
13
(49,2)
13
(49,2)
13
(49,2)
17
(64,3)
20
(75,7)
psi
(bar)
7.0
(0,48)
7.0
(0,48)
7.0
(0,48)
12.0
(0,83)
16.7
(1,15 )
Intermediate Temperature Rating
175°F (79 °C)
Flow
gpm
(l/min)
13
(49,2)
13
(49,2)
13
(49,2)
17
(64,3)
20
(75,7)
Pressure
psi
(bar)
7.0
(0,48)
7.0
(0,48)
7.0
(0,48)
12.0
(0,83)
16.7
(1,15 )
(2)(3)
Deflector to
Ceiling
Smooth
Ceilings
1-1/4 to
4 inches
Beamed
Ceilings per
NFPA 13D
or 13R
1-1/4 to 1- 3/4
inches below
bottom of
beam.
Installation
Typ e
Recessed
using Style 20
Escutcheon or
non-recessed
per NFPA 13D,
13R , o r 13
Minimum
Spacing
Ft.
(m)
8
(2,4)
TABL E A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
Maximum
Coverage
Area
Ft. x Ft.
(m x m)
12 x 12
(3,7 x 3,7)
14 x 14
(4,3 x 4,3)
16 x 16
(4,9 x 4,9)
18 x 18
(5,5 x 5,5)
20 x 20
(6,1 x 6,1)
Notes:
1. For cover age are a dimen sions l ess tha n or bet ween th ose indicated , use the minimum required ow for the next highest coverage area for which hydraul ic desi gn
criter ia are stated.
2. Requireme nt is based on minimum ow in gpm (lp m) from each spr inkle r. The asso ciated residual pre ssure s are ca lculated usin g the nominal
K-factor. Refe r to Hydraulic De sign under the D esign C riter ia sect ion.
3. F or NFPA 13 residential applic ation s, the greater of 0.1 gpm/ft.2 over the de sign ar ea or the ow in accordance with th e crite ria in thi s table m ust be u sed.
Ordinary Temperature Rating
(1)
155°F (68°C)
Flow
Pressure
gpm
(l/min)
13
(49,2)
14
(53,0)
15
(56,8)
18
(68,1)
21
(79,5)
psi
(bar)
7.0
(0,48)
8.2
(0,57)
9.4
(0,65)
13.5
(0,93)
18.4
(1,27 )
Minimum Flow and Residual Pressure
Intermediate Temperature Rating
175°F (79 °C)
Flow
gpm
(l/min)
13
(49,2)
14
(53,0)
15
(56,8)
18
(68,1)
21
(79,5)
Pressure
psi
(bar)
7.0
(0,48)
8.2
(0,57)
9.4
(0,65)
13.5
(0,93)
18.4
(1,27 )
DRY PIPE SYSTEM
(2)(3)
Deflector to
Ceiling
Smooth
Ceilings
1-1/4 to 4
inches
Beamed
Ceilings
per NFPA 13D
or 13R
1-1/4 to 1- 3/4
inches below
bottom of
beam.
Installation
Typ e
Recessed
using Style 20
Escutcheon or
non-recessed
per NFPA 13D,
13R , o r 13
Minimum
Spacing
Ft.
(m)
8
(2,4)
TABL E B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
Page 4
TFP400
2-7/8" DIA.
1-1/8" (28,6 mm)
WRENCH
WRENCHING AREA
WRENCH RECESS
Page 4 of 6
7/16±1/8"
(11,1±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
Installation
TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 m m).
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutcheon Plate by under- or over- tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Pendent Sprinklers
The Series LFII Residential Pendent
Sprinklers must be installed in accordance with the following instructions:
Step 1. Install pendent sprinklers in the
pendent position with the deector parallel to the ceiling.
Step 2. With pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
tting.
Step 3. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench ats.
2-1/4" DIA.
TY2234
FIGURE 2
(73,0 mm)
(57,2 mm)
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-3/8" (34,9 mm)
Recessed Pendent Sprinklers
The Series LFII Residential Recessed
Pendent Sprinklers must be installed
in accordance with the following
instructions:
Step A. Install recessed pendent sprinklers in the pendent position with the
deector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
tting.
Step C. Tighten the sprinkler into the
sprinkler tting using only the W-Type 7
Recessed Sprinkler Wrench (Figure 4).
With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench ats.
Step D. After the ceiling has been
installed or the nish coat has been
applied, slide on the Style 20 Closure
over the Series LFII Residential Sprinkler and push the Closure over the
Mounting Plate until its ange comes in
contact with the ceiling.
(END "A" USED
FOR TY2234)
FIGURE 3
W-T YPE 6
SPRINKLER WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 5
TFP400
Page 5 of 6
Care and
Maintenance
TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section:
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprinklers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, nonoperation in the event of a fire or inadvertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installation section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to the
standards of any authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Series LFII 4.9K Residential
Pendent Sprinkler (TY2234), (specify
temperature rating), with (specify) finish,
P/N (specify):
155°F (68°C)
Natural Brass ................. 51-201-1-155
Pure White (RAL 9010)* .........51-201-3 -155
Signal White (RAL 9003) ........51-201- 4-155
Chrome Plated................51-201-9-155
175° F (7 9°C )
Natural Brass ................. 51-201-1-175
Pure White (RAL 9010)* .........51-201- 3-175
Signal White (RAL 9003) ........ 51-201-4 -175
Chrome Plated................51-201- 9 -175
* Eastern Hemisphere sales only
Recessed Escutcheon
Specify: Style 20 Recessed Escutcheon with (specify*) finish, P/N (specify*)