Tyco DS-3 Series General Description Manual

Page 1
Worldwide
Contacts
Series DS-3 Dry-Type Sprinklers
11.2K Horizontal Sidewall Standard Response, Extended Coverage
www.tyco-fire.com
General Description
TYCO Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Coverage, Ordi­nary Hazard (ECOH) are decorative glass bulb automatic sprinklers� They are intended for use in applications where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures; for example, horizontal piping extensions through a wall to protect an unheated area of a building�
Series DS-3 Extended Coverage Ordinary Hazard Horizontal Sidewall, Dry-Type Sprinklers are designed for extended coverage use in ordinary hazard occupancies ( ECOH) per NFPA 13�
Series DS-3 Dry-Type Sprinklers provide protection of coverage areas up to 16 ft x 20 ft (320 ft2) as compared to standard coverage horizontal side­wall sprinklers having a maximum cov­erage area of 10 ft x 10 ft (100 ft2) for ordinary hazard occupancies�
NOTICE
Series DS-3 Dry-Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Series DS-3 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Installation of Series DS-3 Dry­Type Sprinklers in a recessed installa­tion will void all sprinkler warranties, as well as void the sprinkler’s laboratory Approvals.
Sprinkler Identification Number (SIN)
TY5339
Technical Data
Approvals
UL and C-UL Listed
Refer to Table A and the Design Criteria section
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connections
1 Inch NPT ISO 7-R 1
Discharge Coefficient
Refer to Table B
Temperature Ratings
155°F (68°C) and 200°F ( 93°C)
Finishes
Sprinkler: Refer to Table E
Escutcheon: Refer to Table E
Physical Characteristics
Inlet � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Copper Plug � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Copper Yok e ����������������������� Stainless Steel Casing �������������Galvanized Carbon Steel Insert � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Bulb Seat � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Bulb �������������������������Glass (3 mm ) Compression Screw � � � � � � � � � � � � � � � � �Bronze Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Gu id e Tu be � � � � � � � � � � � � � � � � � Stainless Steel Water Tube � � � � � � � � � � � � � � � � � Stainless Steel Spring ��������������������� Stainless Steel Sealing Assembly ��Beryllium Nickel w/TEFLON Pin ������������������������ Stainless Steel Button Spring � � � � � � � � � � � � � � � Stainless Steel Helper Spring � � � � � � � � � � � � � � � Stainless Steel Escutcheon � � � � � � � � � � � � � � � � � � � Carbon Steel
Operation
When TYCO Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Cov­erage, Ordinary Hazard (ECOH) are in service, water is prevented from enter­ing the assembly by the Plug with Sealing Assembly (Ref� Figure 1) in the Inlet of the sprinkler�
The glass bulb contains a fluid that expands when exposed to heat� When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, and the Bulb Seat is released�
The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward� This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Sealing Assembly from the Inlet allow­ing the sprinkler to activate and flow wa te r�
Page 1 of 8 AUGUST 2018 TFP550
Page 2
TFP550
1" NPT
SPRINGINLET
TUBE
PLUG
SPRING SEAL
PLUG WITH
YOKE CASING
SCREW
COMPRESSION
SEAT
TUBE
DEFLECTORINSERT FRAME
BULB
BAND
Page 2 of 8
GASKETED
PLATE
SPRING
INLET
WATER
FIGURE 1
SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339 (ECOH )
AS S E MBLY
Temperature
Rating
155° F (68°C) Red
200°F (93°C) Green
Notes:
1. Listed by Underwriters La boratori es, Inc. (ma ximum orde r length of 4 8 inches)
2. Listed by Under writers L aborato ries for us e in Canada (ma ximum ord er length of 48 inches).
Bulb
Color Code
Natural
Brass
SPRINKLER FINISH
Chrome
Plated
1, 2
TABLE A
SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS
EXTENDED COVERAGE, ORDINARY HAZARD (TY5339)
LABORATORY LISTINGS AND APPROVALS
Sprinkler Fittings
Design
Install 1 inch NPT Series DS-3 Dry-Type Sprinklers in the 1 inch NPT outlet or
Criteria
The TYCO Series DS-3 Dry-Type Sprin­klers, 11�2K Horizontal Sidewall, Stan­dard Response, Extended Coverage, Ordinary Hazard (ECOH) are for use in ordinary hazard occupancies with non­combustible unobstructed construction and with a ceiling slope not exceed­ing 2 inches per foot (9�2° ), using the design criteria provided in Table C, as well as any additional requirements specified in NFPA 13 for Extended Cov­erage Sidewall Spray Sprinklers�
A 36 in� (914 mm) clearance must be maintained between the top of the sprinkler deflector and any miscella­neous storage�
Series DS-3 Dry-Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof slope of 4 inches per foot (18�4°) as
run of the following fittings:
malleable or ductile iron threaded tee ttings that meet the dimen­sional requirements of ANSI B16.3 (Class 150)
cast iron threaded tee ttings that meet the dimensional requirements of ANSI B16.4 (Class 125)
Do not install Series DS-3 Dry-Type Sprinklers into elbow fittings� The Inlet of the sprinkler can contact the interior of the elbow�
The unused outlet of the threaded tee is plugged as shown in Figure 6�
Series DS-3 Dry-Type Sprinklers can also be installed in the 1 inch NPT outlet of a GRINNELL Figure 730 Mechanical Tee� However, the use of the Figure 730 Tee for this arrangement is limited to wet pipe systems�
shown in Figure 8 and using the design criteria provided in Table C�
White
Polyester
GUIDE
(381 mm to 476 mm)
(483 mm to 584 mm)
(591 mm to 679 mm)
(692 mm to 794 mm)
(800 mm to 895 mm)
(902 mm to 1003 mm)
(1010 mm to 1105 mm)
(111 mm to 1219 mm)
Notes:
• K-factor Le ngth is dete rmined as f ollows:
• Flush: Order Lengt h from Figur e 2 plus 1/2 in.
• Deep: Or der Lengt h from Figure 4 plus 3-1/4 in.
• Withou t Escutche on: Order Length from Figure 5
BULB
Length,
Inches
(mm)
2-1/2 to 14-3/4
(63 mm to 375 mm)
15 to 18-3/4
19 to 23
23-1/4 to 2 6- 3/4
27-1/4 to 31-1/4
31-1/2 to 35-1/4
35 -1/ 2 t o 3 9-1/2
39-3/4 to 43-1/2
43-3/4 to 48
(12,7 m m)
(82,6 mm)
minus 2-1/4 in. (57,2 mm)
TABLE B
DISCHARGE COEFFICIENTS
K-factor,
gpm/psi
(lpm/bar½)
11. 2
(161, 3)
10.9
(1 57,0 )
10.8
(155 ,5)
10.7
(154 ,1)
10.6
(152,6)
10.5
(151,2)
10.4
(149,8)
10.3
(148,3)
10.2
(146,9)
½
Page 3
TFP550
Page 3 of 8
Coverage
1
Application
Series DS-3 (TY5339)
Horizontal Sidewall
Dry-Type Sprinkler (ECOH)
OH Group 1 (0.15 gpm/sq.ft)
Standard Response
Series DS-3 (TY5339)
Horizontal Sidewall
Dry-Type Sprinkler (ECOH)
OH Group 2 (0.20 gpm/sq.ft)
Standard Response
Notes:
1. Backwall (where sprinkler is located) by sidewall (length of throw).
2. Req uirement i s based on mi nimum ow in GPM f rom each sp rinkler. The i ndicated r esidual p ressure s are based o n the nomina l K-factor of 11.2.
3. T he center line of the sprinkler waterway is located below t he deecto r as shown in Figures 2, 3, and 4.
4. M inimum spa cing is for la teral dist ance betw een sprin klers loc ated along a s ingle wall. O therwi se adjacent sprinkl ers (that is, sidewall sprinklers on an adjac ent wall, on an opp osite wall, or p endent sp rinkler s) must be loc ated outside of the maximum liste d protecti on area of the ex tended coverage sidewall sprin kler bein g utilized.
Area
W x L,
ft x ft
(m x m)
16 x 16
(4,9 x 4,4)
16 x 18
(4,9 x 5,5)
16 x 20
(4,9 x 6,1)
16 x 16
(4,9 x 4,4)
16 x 18
(4,9 x 5,5)
16 x 20
(4,9 x 6,1)
Minimum
Flow2,
gpm
(lpm)
38
(144)
43
(163)
48
(182)
51
(193)
58
(220)
64
(242)
Minimum
Pressure2,
psi
(bar)
11. 5
(0,79)
14.7
(1,01)
18.4
(1,27)
20.7
(1,4 3)
26.8
(1,85)
32.7
(2,25)
Top of
Deflector-to-Ceiling
Distance3,
Inches
(mm)
6 to 12
(150 to 300)
Temperature
Rating
155°F, 200°F
(68°C, 93°C)
Minimum
Spacing4,
TABLE C
SERIES DS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
Temperatures for Heated Area
Ambient Temperature
Discharge End of Sprinkler
Notes:
1. For prote cted area te mperatu res that occ ur betwee n values lis ted above, us e the next coo ler tempe rature.
2. The se lengths are inclus ive of wind velo cities up to 3 0 mph (18,6 kph).
Exposed to
40°F (4°C)
30°F
(-1° C)
20°F
(-7° C)
10°F
(-12 °C)
0°F
(-18 °C )
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
-50°F
(-46°C)
-60°F
(-51°C)
40°F (4°C)
Minimum Exposed Barrel Length2,
0 0 0
0 0 0
4
(100)
8
(200)
12
(305)
14
(355)
14
(355)
16
(405)
18
(455)
20
(510)
20
(510)
50°F
(10°C)
Inches
(mm)
0 0
1
(25)
3
(75)
4
(100)
6
(150 )
8
(200)
8
(200)
10
(255)
10
(255)
1
60°F
(16°C)
0
0
1
(25)
3
(75)
4
(100)
4
(100)
6
(150 )
6
(150 )
The configuration shown in Figure 7 is only applicable for wet pipe systems where the sprinkler fitting and water­filled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry-Type Sprinkler has the minimum exposure length depicted in Figure 10� Refer to the Exposure Length section�
For wet pipe system installations of 1 inch NPT Series DS-3 Dry-Type Sprin­klers connected to CPVC piping, use only the following TYCO CPVC fittings:
1 in. x 1 in. NPT Female Adapter (P/N 80145)
1 in. x 1 in. x 1 in. NPT Sprinkler Head Adapter Tee (P/N 80249)
For dry pipe system installations, use only the side outlet of maximum 2-1/2 inch reducing tee when locating Series DS-3 Dry-Type Sprinklers directly below the branch line� Otherwise, use the configuration shown in Figure 6 to assure complete water drainage from above Series DS-3 Dry-Type Sprinklers and the branch line� Failure to do so may result in pipe freezing and water damage�
TABLE D
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED LENGTHS
ft
(m)
8
(2,4)
Page 4
TFP550
OF WATERWAY
ORDER LENGTHS:
2-1/4" (57,2 mm)
CRITERIA SECTION)
OF WATERWAY
3-11/16" DIA.
ORDER LENGTHS:
FACE OF
OF WATERWAY
3-1/2" DIA.
ORDER LENGTHS:
FACE OF
Page 4 of 8
3" to 45-1/4" (76,2 to 1149,4 mm)
IN 1/4" (6,4 mm) INCREMENTS
FACE OF
SPRINKLER FITTING
1" NPT,
NOMINAL MAKE-IN
9/16" (14,3 mm)
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
2-3/4" DIA. (69,9 mm)
FIGURE 2
SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER
WITH FLUSH ESCUTCHEON ( TY5339 )
1" to 44" (25,4 to 1117,6 mm)
IN 1/4" (6,4 mm) INCREMENTS
FACE OF
SPRINKLER FITTING
1" NPT,
NOMINAL MAKE-IN
9/16" (14,3 mm)
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
2-3/4" DIA.
(69,9 mm)
FIGURE 3
SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER
WITH DEEP ESCUTCHEON (TY5339 )
5-1/4" to 48" (133,4 to 1219,2 mm)
IN 1/4" (6,4 mm) INCREMENTS
FACE OF SPRINKLER FITTING
1" NPT,
NOMINAL MAKE-IN
9/16" (14,3 mm)
SPRINKLER FITTING
(REFER TO DESIGN
FIGURE 4
SERIES DS-3 ECOH HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER
WITHOUT ESCUTCHEON (TY5339)
MOUNTING
SURFACE
MOUNTING
SURFACE
2" ± 1/8"
(50,8 ± 3,2 mm)
9/16" (14,3 mm)
(93,7 mm)
CENTERLINE
4-1/8" ± 3/8"
(104,8 ± 9,5 mm)
9/16" (14,3 mm)
(88,9 mm)
CENTERLINE
MINIMUM
DEFLECTOR TO
MOUNTING
SURFACE
9/16"
(14,3 mm)
CENTERLINE
NOTICE
Do not install Series DS-3 Dry-Type Sprinklers into any other type fitting without first consulting the Technical Services Department. Failure to use the appropriate fitting may result in one of the following:
failure of the sprinkler to operate properly due to formation of ice over the Inlet Plug or binding of the Inlet Plug
insufficient engagement of the Inlet pipe-threads with consequent leakage
Drainage
In accordance with the minimum requirements of the NATIONAL FIRE PROTECTION ASSOCIATION for dry pipe sprinkler systems, branch, cross, and feed-main piping connected to Dry Sprinklers and subject to freezing tem­peratures must be pitched for proper drainage�
Exposure Length
When using Dry Sprinklers in wet pipe sprinkler systems to protect areas subject to freezing temperatures, use Table D to determine a sprinkler’s appropriate exposed barrel length to prevent water from freezing in the con­necting pipes due to conduction� The
exposed barrel length measurement must be taken from the face of the sprinkler fitting to the surface of the structure or insulation that is exposed to the heated area� Refer to Figure 7 for an example�
For protected area temperatures between those given above, the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values�
Clearance Space
In accordance with NFPA 13, when connecting an area subject to freez­ing and an area containing a wet pipe sprinkler system, the clearance space around the sprinkler barrel of Dry-Type Sprinklers must be sealed. Due to temperature differences between two areas, the potential for the formation of condensation in the sprinkler and sub­sequent ice build-up is increased. If this condensation is not controlled, ice build-up can occur that might damage the Dry-Type Sprinkler and/or prevent proper operation in a re situation.
Use of the Model DSB-2 Dry Sprin­kler Boot, described in Technical Data Sheet TFP591 and shown in Figure 9, can provide the recommended seal.
Page 5
TFP550
DSB-2
PLUGGED
BOOT)
2-3/4" DIA.
DISTANCE
EXPOSURE
Page 5 of 8
TO DRY
SYSTEM
DSB-2
INTENDED
FOR FREEZER
STRUCTURES
AREA
SUBJECT
TO
FREEZING
FIGURE 5
SPRINKLER FITTING
UNHEATED AREA
MAXIMUM
THROW
RUN
OUTLET
INTENDED
FOR FREEZER
STRUCTURES
SPRINKLER
FITTING
(SEE DESIGN
CRITERIA SECTION)
TO DRY
SYSTEM
AREA
SUBJECT
TO
FREEZING
FIGURE 6
SPRINKLER FITTING
UNHEATED AREA
(69,9 mm)
CLEARANCE
HOLE
ADHESIVE
DSB-2 BOOT
LENGTH
(SEE DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
DSB-2
INTENDED
FOR FREEZER
STRUCTURES
HEATED
AREA
FIGURE 7
SPRINKLER FITTING
HEATED AREA
INSULATED
FREEZER
STRUCTURE
6" (152,4 mm)
TO 12" (304,8 mm)
CEILING TO TOP
OF SPRINKLER
DEFLECTOR
4/12
SLOPE
MAXIMUM
FIGURE 8
SPRINKLER PLACEMENT
UNDER SLOPED CEILINGS
IN LOADING DOCKS
STRAP TIES
(ENDS ON
OPPOSING
SIDES OF
DS-3
SHOWN
WITH FLUSH
ESCUTCHEON
FIGURE 9
MODEL DSB-2 DRY SPRINKLER
BOOT WITH SERIES DS-3
DRY-TYPE PENDENT SPRINKLER
Page 6
TFP550
SHOWN
WRENCH FLAT
Page 6 of 8
Installation
TYCO Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Coverage, Ordi­nary Hazard (ECOH) must be installed in accordance with this section�
General Instructions
Series DS-3 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Crite­ria section� Refer to the Design Criteria section for other important require­ments regarding piping design and sealing of the clearance space around the Sprinkler Casing� With reference to Figure 10, do not grasp the sprinkler by the deflector� Failure to follow this instruction may impair performance of the device�
Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb� With the sprin­kler held horizontally, a small air bubble should be present� The diameter of the air bubble is approximately 1/16 in� (1,6 mm) for the 135°F (57°C) rating to 1/8 in� (3,2 mm) for the 360°F (182°C) rating�
A leak-tight 1 inch NPT sprinkler joint should be obtained by applying a min­imum-to-maximum torque of 20 to 30 lb-ft (26,8 to 40,2 N·m)� Higher levels of torque may distort the sprin­kler Inlet with consequent leakage or impairment of the sprinkler�
Do not attempt to compensate for insufficient adjustment in an escutch­eon plate by under or over-tightening the Sprinkler� Re-adjust the position of the sprinkler fitting to suit�
Step 1. Install horizontal sidewall sprin­klers with the center line of waterway parallel to the ceiling and perpendicu­lar to the back wall surface� The word “TOP” on the deflector must face upwards toward the ceiling�
Step 2. With a non-hardening pipe­thread sealant such as TEFLON applied to the Inlet threads, hand-tighten the sprinkler into the sprinkler fitting� Do not grasp the sprinkler by the deflector (Ref� Figure 10)�
Step 3. Wrench-tighten the sprinkler using either:
a pipe wrench on the Inlet Band or the Casing (Ref. Figure 1)
the W-Type 8 Sprinkler Wrench on the Wrench Flat (Ref. Figure 11)
Apply the Wrench Recess of the W-Type 8 Sprinkler Wrench to the Wrench Flat�
FIGURE 10
DO NOT GRASP
DEFLECTOR
Note: If sprinkler removal becomes necessary, remove the sprinkler using the same wrenching method noted above� Sprinkler removal is easier when a non-hardening sealant was used and torque guidelines were followed� After removal, inspect the sprinkler for damage�
Step 4. After applying a wall finish, slide on the outer piece of the escutch­eon until it comes in contact with the mounting surface�
For Deep Escutcheons, slide the outer skirt over the inner cup to make firm contact with the mounting surface�
Care and Maintenance
TYCO Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Coverage, Ordi­nary Hazard (ECOH) must be main­tained and serviced in accordance with this section�
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action�
Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation�
A Vent Hole is provided in the Bulb Seat (Figure 1) to indicate if the Dry Sprinkler is remaining dry� Evidence of leakage from the Vent Hole indicates poten­tial leakage past the Inlet seal and the need to remove the sprinkler to deter-
ENGAGEMENT
AREA
WRENCH
FLATS
APPLY
WRENCH AS
FIGURE 11
W-TYPE 8
SPRINKLER WRENCH
mine the cause of leakage; for example, an improper installation or an ice plug� Close the fire protection system control valve and drain the system before removing the sprinkler�
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced�
Automatic sprinklers must never be painted, plated, coated, or other­wise altered after leaving the factory� Modified sprinklers must be replaced� Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush�
Care must be exercised to avoid damage to the sprinklers – before, during, and after installation� Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced� Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb� (Refer to Installa­tion Section�)
The owner is responsible for the inspec­tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSO­CIATION (e�g�, NFPA 25), in addition to the standards of any other authorities having jurisdiction� Contact the install­ing contractor or product manufacturer with any questions�
Automatic sprinkler systems are rec­ommended to be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes�
Page 7
P/N* 61 — XXX — X — XXX
TFP550
Page 7 of 8
ESCUTCHEON TYPE
161
163
171
173
151
153
Notes:
1. Does no t apply to ass emblies without esc utcheon.
2. Dr y-Ty pe Sprink lers are fu rnished b ased upon “ Order Len gth” as meas ured per Figures 2, 3 & 4.
3. A fter the me asureme nt is taken, ro und it to the ne arest 1/4 inch inc rement. * Use Pre x “I” for ISO 7-R1 Con nection (e.g ., I-61-161-1-0 55).
Flush Escutcheon
(1 in. NPT), 155°F (68°C)
Flush Escutcheon
(1 in. NPT), 200°F (93°C)
Deep Escutcheon
(1 in. NPT), 155°F (68°C)
Deep Escutcheon
(1 in. NPT), 200°F (93°C)
Without Escutcheon
(1 in. NPT), 155°F (68°C)
Without Escutcheon
(1 in. NPT), 200°F (93°C)
SPRINKLER
1
SIGNAL WHITE
4
9
0
FINISH
NAT URA L
BRASS
(RAL9003)
POLYESTER
CHROME
PL ATED
CHROME
PL ATED
TABLE E
SERIES DS-3 HORIZONTAL SIDEWALL, DRY-TYPE SPRINKLERS (ECOH)
PART NUMBER SELECTION
Limited Warranty
For warranty terms and conditions, visit www�tyco-fire�com�
Ordering Procedure
Contact your local distributor for avail­ability� When placing an order, indi­cate the full product name, including
description and Part Number (P/N)�
Dry-Type Sprinklers
When ordering Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Cover­age, Ordinary Hazard (ECOH), specify the following information:
• SIN TY5339
• Order Length: Dry-Type Sprinklers are furnished based upon Order Length as measured from the face of the wall to the face of the sprinkler tting (Ref. Figures 2, 3 & 4). After the measurement is taken, round it to the nearest 1/4 inch increment.
• Inlet Thread Connections: 1 Inch NPT (Standard)
ISO 7-R 1 (For information on ISO Inlet Thread Connections, contact your Johnson Controls Sales Representative�)
• Temperature Rating
• Sprinkler Finish
Escutcheon Type and Finish, as applicable
• Part Number from Table E
ESCUTCHEON
SIGNAL WHITE
(RAL9003)
POLYESTER
SIGNAL WHITE
(RAL9003)
POLYESTER
1
FINISH
BRASS
PL ATED
CHROME
PL ATED
ORDER
LENGTH
055 5.50 in.
082 8.25 in.
180 18.00 in.
187 18.75 in.
372 37. 25 i n .
480 48.00 in.
2
Sprinkler Wrench
Specify W-Type 8 Sprinkler Wrench, P/ N 56-8 92-1- 0 01
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler Boot, P/N 63-000-0-002
This Part Number includes one (1) Boot, two (2) Strap Ties, and 1/3 oz of Adhesive (a sufficient quantity for installing one boot)�
Page 8
TFP550
Page 8 of 8
1400 Pennbroo k Parkwa y, Lansdale, PA 1944 6 | Telephon e +1-215-362- 0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; TEFLON is a regi stered tradema rk of DuPont
Loading...