Tyco DS-3 Series General Description Manual

Worldwide
Contacts
Series DS-3 Dry-Type Sprinklers
11.2K Horizontal Sidewall Standard Response, Extended Coverage
www.tyco-fire.com
General Description
TYCO Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Coverage, Ordi­nary Hazard (ECOH) are decorative glass bulb automatic sprinklers� They are intended for use in applications where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures; for example, horizontal piping extensions through a wall to protect an unheated area of a building�
Series DS-3 Extended Coverage Ordinary Hazard Horizontal Sidewall, Dry-Type Sprinklers are designed for extended coverage use in ordinary hazard occupancies ( ECOH) per NFPA 13�
Series DS-3 Dry-Type Sprinklers provide protection of coverage areas up to 16 ft x 20 ft (320 ft2) as compared to standard coverage horizontal side­wall sprinklers having a maximum cov­erage area of 10 ft x 10 ft (100 ft2) for ordinary hazard occupancies�
NOTICE
Series DS-3 Dry-Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Series DS-3 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Installation of Series DS-3 Dry­Type Sprinklers in a recessed installa­tion will void all sprinkler warranties, as well as void the sprinkler’s laboratory Approvals.
Sprinkler Identification Number (SIN)
TY5339
Technical Data
Approvals
UL and C-UL Listed
Refer to Table A and the Design Criteria section
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connections
1 Inch NPT ISO 7-R 1
Discharge Coefficient
Refer to Table B
Temperature Ratings
155°F (68°C) and 200°F ( 93°C)
Finishes
Sprinkler: Refer to Table E
Escutcheon: Refer to Table E
Physical Characteristics
Inlet � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Copper Plug � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Copper Yok e ����������������������� Stainless Steel Casing �������������Galvanized Carbon Steel Insert � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Bulb Seat � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Bulb �������������������������Glass (3 mm ) Compression Screw � � � � � � � � � � � � � � � � �Bronze Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze Gu id e Tu be � � � � � � � � � � � � � � � � � Stainless Steel Water Tube � � � � � � � � � � � � � � � � � Stainless Steel Spring ��������������������� Stainless Steel Sealing Assembly ��Beryllium Nickel w/TEFLON Pin ������������������������ Stainless Steel Button Spring � � � � � � � � � � � � � � � Stainless Steel Helper Spring � � � � � � � � � � � � � � � Stainless Steel Escutcheon � � � � � � � � � � � � � � � � � � � Carbon Steel
Operation
When TYCO Series DS-3 Dry-Type Sprinklers, 11�2K Horizontal Sidewall, Standard Response, Extended Cov­erage, Ordinary Hazard (ECOH) are in service, water is prevented from enter­ing the assembly by the Plug with Sealing Assembly (Ref� Figure 1) in the Inlet of the sprinkler�
The glass bulb contains a fluid that expands when exposed to heat� When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, and the Bulb Seat is released�
The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward� This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Sealing Assembly from the Inlet allow­ing the sprinkler to activate and flow wa te r�
Page 1 of 8 AUGUST 2018 TFP550
TFP550
1" NPT
SPRINGINLET
TUBE
PLUG
SPRING SEAL
PLUG WITH
YOKE CASING
SCREW
COMPRESSION
SEAT
TUBE
DEFLECTORINSERT FRAME
BULB
BAND
Page 2 of 8
GASKETED
PLATE
SPRING
INLET
WATER
FIGURE 1
SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER TY5339 (ECOH )
AS S E MBLY
Temperature
Rating
155° F (68°C) Red
200°F (93°C) Green
Notes:
1. Listed by Underwriters La boratori es, Inc. (ma ximum orde r length of 4 8 inches)
2. Listed by Under writers L aborato ries for us e in Canada (ma ximum ord er length of 48 inches).
Bulb
Color Code
Natural
Brass
SPRINKLER FINISH
Chrome
Plated
1, 2
TABLE A
SERIES DS-3 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS
EXTENDED COVERAGE, ORDINARY HAZARD (TY5339)
LABORATORY LISTINGS AND APPROVALS
Sprinkler Fittings
Design
Install 1 inch NPT Series DS-3 Dry-Type Sprinklers in the 1 inch NPT outlet or
Criteria
The TYCO Series DS-3 Dry-Type Sprin­klers, 11�2K Horizontal Sidewall, Stan­dard Response, Extended Coverage, Ordinary Hazard (ECOH) are for use in ordinary hazard occupancies with non­combustible unobstructed construction and with a ceiling slope not exceed­ing 2 inches per foot (9�2° ), using the design criteria provided in Table C, as well as any additional requirements specified in NFPA 13 for Extended Cov­erage Sidewall Spray Sprinklers�
A 36 in� (914 mm) clearance must be maintained between the top of the sprinkler deflector and any miscella­neous storage�
Series DS-3 Dry-Type Sprinklers may be installed on sloped ceilings in loading docks with a maximum roof slope of 4 inches per foot (18�4°) as
run of the following fittings:
malleable or ductile iron threaded tee ttings that meet the dimen­sional requirements of ANSI B16.3 (Class 150)
cast iron threaded tee ttings that meet the dimensional requirements of ANSI B16.4 (Class 125)
Do not install Series DS-3 Dry-Type Sprinklers into elbow fittings� The Inlet of the sprinkler can contact the interior of the elbow�
The unused outlet of the threaded tee is plugged as shown in Figure 6�
Series DS-3 Dry-Type Sprinklers can also be installed in the 1 inch NPT outlet of a GRINNELL Figure 730 Mechanical Tee� However, the use of the Figure 730 Tee for this arrangement is limited to wet pipe systems�
shown in Figure 8 and using the design criteria provided in Table C�
White
Polyester
GUIDE
(381 mm to 476 mm)
(483 mm to 584 mm)
(591 mm to 679 mm)
(692 mm to 794 mm)
(800 mm to 895 mm)
(902 mm to 1003 mm)
(1010 mm to 1105 mm)
(111 mm to 1219 mm)
Notes:
• K-factor Le ngth is dete rmined as f ollows:
• Flush: Order Lengt h from Figur e 2 plus 1/2 in.
• Deep: Or der Lengt h from Figure 4 plus 3-1/4 in.
• Withou t Escutche on: Order Length from Figure 5
BULB
Length,
Inches
(mm)
2-1/2 to 14-3/4
(63 mm to 375 mm)
15 to 18-3/4
19 to 23
23-1/4 to 2 6- 3/4
27-1/4 to 31-1/4
31-1/2 to 35-1/4
35 -1/ 2 t o 3 9-1/2
39-3/4 to 43-1/2
43-3/4 to 48
(12,7 m m)
(82,6 mm)
minus 2-1/4 in. (57,2 mm)
TABLE B
DISCHARGE COEFFICIENTS
K-factor,
gpm/psi
(lpm/bar½)
11. 2
(161, 3)
10.9
(1 57,0 )
10.8
(155 ,5)
10.7
(154 ,1)
10.6
(152,6)
10.5
(151,2)
10.4
(149,8)
10.3
(148,3)
10.2
(146,9)
½
TFP550
Page 3 of 8
Coverage
1
Application
Series DS-3 (TY5339)
Horizontal Sidewall
Dry-Type Sprinkler (ECOH)
OH Group 1 (0.15 gpm/sq.ft)
Standard Response
Series DS-3 (TY5339)
Horizontal Sidewall
Dry-Type Sprinkler (ECOH)
OH Group 2 (0.20 gpm/sq.ft)
Standard Response
Notes:
1. Backwall (where sprinkler is located) by sidewall (length of throw).
2. Req uirement i s based on mi nimum ow in GPM f rom each sp rinkler. The i ndicated r esidual p ressure s are based o n the nomina l K-factor of 11.2.
3. T he center line of the sprinkler waterway is located below t he deecto r as shown in Figures 2, 3, and 4.
4. M inimum spa cing is for la teral dist ance betw een sprin klers loc ated along a s ingle wall. O therwi se adjacent sprinkl ers (that is, sidewall sprinklers on an adjac ent wall, on an opp osite wall, or p endent sp rinkler s) must be loc ated outside of the maximum liste d protecti on area of the ex tended coverage sidewall sprin kler bein g utilized.
Area
W x L,
ft x ft
(m x m)
16 x 16
(4,9 x 4,4)
16 x 18
(4,9 x 5,5)
16 x 20
(4,9 x 6,1)
16 x 16
(4,9 x 4,4)
16 x 18
(4,9 x 5,5)
16 x 20
(4,9 x 6,1)
Minimum
Flow2,
gpm
(lpm)
38
(144)
43
(163)
48
(182)
51
(193)
58
(220)
64
(242)
Minimum
Pressure2,
psi
(bar)
11. 5
(0,79)
14.7
(1,01)
18.4
(1,27)
20.7
(1,4 3)
26.8
(1,85)
32.7
(2,25)
Top of
Deflector-to-Ceiling
Distance3,
Inches
(mm)
6 to 12
(150 to 300)
Temperature
Rating
155°F, 200°F
(68°C, 93°C)
Minimum
Spacing4,
TABLE C
SERIES DS-3 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY-TYPE SPRINKLERS
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
Temperatures for Heated Area
Ambient Temperature
Discharge End of Sprinkler
Notes:
1. For prote cted area te mperatu res that occ ur betwee n values lis ted above, us e the next coo ler tempe rature.
2. The se lengths are inclus ive of wind velo cities up to 3 0 mph (18,6 kph).
Exposed to
40°F (4°C)
30°F
(-1° C)
20°F
(-7° C)
10°F
(-12 °C)
0°F
(-18 °C )
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
-50°F
(-46°C)
-60°F
(-51°C)
40°F (4°C)
Minimum Exposed Barrel Length2,
0 0 0
0 0 0
4
(100)
8
(200)
12
(305)
14
(355)
14
(355)
16
(405)
18
(455)
20
(510)
20
(510)
50°F
(10°C)
Inches
(mm)
0 0
1
(25)
3
(75)
4
(100)
6
(150 )
8
(200)
8
(200)
10
(255)
10
(255)
1
60°F
(16°C)
0
0
1
(25)
3
(75)
4
(100)
4
(100)
6
(150 )
6
(150 )
The configuration shown in Figure 7 is only applicable for wet pipe systems where the sprinkler fitting and water­filled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry-Type Sprinkler has the minimum exposure length depicted in Figure 10� Refer to the Exposure Length section�
For wet pipe system installations of 1 inch NPT Series DS-3 Dry-Type Sprin­klers connected to CPVC piping, use only the following TYCO CPVC fittings:
1 in. x 1 in. NPT Female Adapter (P/N 80145)
1 in. x 1 in. x 1 in. NPT Sprinkler Head Adapter Tee (P/N 80249)
For dry pipe system installations, use only the side outlet of maximum 2-1/2 inch reducing tee when locating Series DS-3 Dry-Type Sprinklers directly below the branch line� Otherwise, use the configuration shown in Figure 6 to assure complete water drainage from above Series DS-3 Dry-Type Sprinklers and the branch line� Failure to do so may result in pipe freezing and water damage�
TABLE D
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED LENGTHS
ft
(m)
8
(2,4)
Loading...
+ 5 hidden pages