Turck FDNP-S0808H-WW Data Sheet

FDNP-S0808H-WW
This station provides 8 inputs and 8 outputs. There are 4 dual input connectors on the left and 4 dual output connectors on the right. This unit is specically designed to work with 2 position valves. All inputs are powered by bus power. All outputs are powered by auxiliary power.
Each eurofast
®
Each eurofast
®
output connector provides AUX-, Output A, and Output B. Outputs are individually short-circuit protected, but monitored as a group. Output A is indicated by the upper LED. Output B is indicated by the lower LED. The AUX- is the output ground.
The node address can be set using the rotary switches located under the device cover or through software node commissioning. The unit automatically detects the communication rate.
The FDNP-S0808H-WW supports explicit messaging, polled, change of state, and cyclic I/O messages.
Recommended Cordsets: Bus Line: RSM RKM 579-*M Auxiliary Power: RSM RKM 47-*M Inputs / Outputs: VB2-RS 4.4T-*/2 RK 4.4T-*/* or RK 4.4T-*-RS 4.4T Auxiliary Power T: RSM 2RKM 40
FDNP-S0808H-WW Dimensions
• Advanced DeviceNet™ station
• 4 x 2 discrete inputs and
4 x 2 discrete outputs
Applications
• For wet or dry environments
• For use with eight 3-wire or four
4-wire proximity and photoelectric sensors, and eight discrete actuators
Features
• PNP short-circuit protected inputs
• 1.4 amp short-circuit protected outputs
• Glass lled nylon with nickel
plated brass connectors
• Rotary address switches
TURCK Inc. 10240190 Rev 2.3 7/11
FDNP-S0808H-WW
Connectors
5-pin Male
DeviceNet™ minifast
4-pin Male
Auxiliary Power minifast
1 = Shield 2 = V + 3 = V – 4 = CAN_H 5 = CAN_L
®
1 = V
+
AUX
2 = Pass thru 3 = Pass thru 4 = V
-
AUX
®
Input / Output Connector
I/O Data Mapping
Item Number F0127 Product Type / Code: 7/2033
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input
Data
0 I-7 I-6 I-5 I-4 I-3 I-2 I-1 I-0
1 IGS OGS - - - - - -
Output
Data
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 O-7 O-6 O-5 O-4 O-3 O-2 O-1 O-0
Module Specications
Supply Voltage
Bus Power 11-26 VDC, powers communication Internal Current Consumption <75 mA (from bus power) Auxiliary Power 18-26 VDC, optically isolated, powers outputs
Abbreviations
I = Input Data (0=OFF, 1=ON) IGS = Input Group Status (0=Working, 1=Fault) O = OutputData (0=OFF, 1=ON) OGS = Output Group Status (0=Working, 1=Fault)
TURCK Inc. 10240190 Rev 2.3 7/11