Turbo Chef Technologies Tornado 2, Tornado User Manual

Page 1
TurboChef Technologies Inc.
Tornado and Tornado 2 (NGC) Ventless Submittal Information
1. Spec Sheets 1.1
2. UL Ventless Label 2.1
3. UL Listing 3.1
4. UL KNLZ Explained 4.1
5. Test Report 5.1
6. KNLZ Letter 6.1
7. Mechanical Code Sections 7.1
8. Emissions by Product 8.1
9. Fire and Smoke Statement 9.1
10. Heat Loading Calculations 10.1
11. Sampling of Letters from the Following States/Jurisdictions 11.1
Minnesota 11.11
Michigan 11.
of Saint Louis, MO 11.13
City
12
12. Surface Temperatures 12.1
© 2008–2012 TurboChef Technologies, Inc. DOC-1122 / Rev F / Nov 2012
Page 2
Proj ect _______________________________________________________
Item No. ______________________________________________________
Quan tit y _______________________________________________________________________
TORNADO
THE
TORNADO
PERFORMANCE
n
The Tornado® evenly and consistently toasts, browns and crisps food up to 12X faster than traditional cooking methods, resulting in a high level of throughput without compromising quality
VENTILATION
n
UL 710B (KNLZ) listed for ventless
operation.
n
EPA 202 test (8 hr):
- Product: Pepperoni Pizzas
- Results: 0.21 mg/m
- Ventless Requirement: <5.00 mg/m
n
Internal catalytic filtration to limit smoke, grease, and odor emissions.
3
2
®
EXTERIOR CONSTRUCTION
n
430 stainless steel front, top, sides and back
n
4” (102 mm) adjustable legs
n
Cool to the touch pull down door with microwave seal
®
INTERIOR CONSTRUCTION
n
304 stainless steel interior
n
Fully insulated cook chamber
n
Removable / variable cooking surfaces
n
Exposed bottom browning element
STANDARD FEATURES
n
Integral recirculating catalytic converter for UL 710B (KNLZ) listed
ventless operation
n
Variable-speed High h recirculating impingement airow system
n
Variable cooking surfaces (racks, stones and platters)
n
Independently-controlled bottom browning element
n
Smart Voltage Sensor Technology* (U.S. only)
n
Smart menu system capable of storing up to 128 recipes
n
Built-in self-diagnostics for monitoring oven components and
performance
n
Stackable design (requires stacking kit)
n
Manual snooze mode
n
Includes plug and cord (6 ft. nominal)
n
Smart card compatible
n
Warranty – 1 year parts and labor
3
COMES WITH STANDARD ACCESSORIES
n
1 Aluminum Paddle (NGC-1478)
n
1 Bottle Oven Cleaner (103180)
n
1 Bottle Oven Guard (103181)
n
2 Trigger Sprayers (103182)
n
2 Non-stick Baskets (100011)
3
5
1. Blower Motor
2. Impingement Heater
3. Impinged Air
4. Bottom Browning Element
5. Microwave Bursts
6. Catalytic Converter
1
4
6
This product conforms to the ventilation recommendations set forth by NFPA96 using EPA202 test method.
* Smart Voltage Sensor Technology does not compensate for lack of or over voltage situations. It is the responsibility of the owner to supply voltage to the unit according to the specications on the back of this sheet.
Ventless certication is for all food items except for foods classied as “fatty raw proteins.” Such foods include bone-in, skin-on chicken, raw hamburger meat, raw bacon, raw sausage, steaks, etc. If cooking these types of foods, consult local HVAC codes and authorities to ensure compliance with ventilation requirements.
Ultimate ventless allowance is dependent upon AHJ approval, as some jurisdictions may not recognize the UL certification or application. If you have questions regarding ventless certifications or local codes please email ventless.help@turbochef.com
TurboChef reserves the right to make substitutions of components or change specications without prior notice.
NGC-1299/Revision M/
October 2012
Page 3
26” (660 mm)
Standard
25.7” (653 mm)
23”
(584 mm)
Max Circuit Requirement 20 amp
Plug IEC 309, 5-pin, 32 amp
Max Input 10500 watts
Microwave Input Power 3500 watts
NGCED (NGC-1180-1D)
Phase 3 Phase
Voltage 230 VAC
Frequency 50
Curr
ent 30 amp
Max Circuit Requirement 32 amp
Plug IEC 309, 4-pin, 32 amp
Max Input 10500 watts
Microwave Input Power 3500 watts
NGC
UK (NGC-1180-1K)
hase 1 Phase
P
Voltage 230 VAC
Frequency 50 Hz
Current 30 amp
Max Circuit Requirement 32 amp
Plug IEC 309, 3-pin, 32 amp
Max Input 6700 watts
Microwave Input Power 3500 watts
APAN
J
NGCJD - 50Hz/ 3 Phase (NGC-1180-1D-2005-1)
NGCJ
D - 60Hz/ 3 Phase (NGC-1180-1D-2005-2)
NGCJK - 50
NGC
Hz/ 1 Phase (NGC-1180-1K-2005-3)
Hz/ 1 Phase (NGC-1180-1K-2005-4)
JK - 60
P
hase 1 or 3 Phase
Voltage 200 VAC
Frequency 50 or 60
Curr
ent 30 amp
Max Circuit Requirement 30 amp
Plug P
Max Input 10500 or 6700 watts
Microwave Input Power 3500 watts
Hz
Hz
SE-marked
3-Phase
1-Phase
, 3 or 4-blade, 30 amp
SHIPPING INFORMATION
U.S.: All ovens shipped within the U.S. are packaged in a double-wall cor-
rugated box banded to a wooden skid.
tional: All International ovens shipped via Air or Less than Con-
Interna
tainer Loads are packaged in wooden crates.
Box size: 34” x 30” x 30” (864 mm x 762 mm x 762 mm) Crate size: 37”x 33” x 34” (940 mm x 838 mm x 864 mm) Item class: 85 NMFC #26770
pproximate boxed weight: 260 lb. (118 kg)
A Approximate crated weight: 320 lb. (145 kg)
Minimum entry clearance required for box: 30.5” (775 mm) Minimum entry clearance required for crate: 33.5” (851 mm)
*All AU-New Zealand ovens with clips allow for 5 pin plug.
TurboChef recommends installing a type D circuit breaker for all installations.
4240 International Pkwy, Suite 105 / Carrollton, Texas 75007 USA
US: 800.90TURBO (800.908.8726) / International: +1 214.379.6000
HS code 8419.81
TurboChef Global Operations
Fax: +1 214.379.6073 / turbochef.com
®
TORNADO
19”
(483 mm)
11.25” (286 mm)
DIMENSIONS
Single Units
Height 19” 483 mm
on legs 23” 584 mm
idth 26” 660 mm
W
Depth 25.7” 653 mm
with handle 28.2” 716 mm
Weight 190 lbs. 86 kg
Stacked Units
Height 38” 965 mm
Width 26” 660 mm
Depth 25.7” 653 mm
with handle 28.2” 716 mm
Weight 380 lbs
Cook Chamber
eight 8” 203 mm
H
W
idth 15.5” 394 mm
Depth 14.7” 373 mm
Volume 1.05 cu.ft. 29.9 liters
Wall Clearance
Top 4” 102 mm
Sides 2” 51 mm
(Stacking Kit Required)
. 172 kg
(Oven not intended for built-in installation)
ELECTRICAL SPECIFICATIONS
NORTH AMERICA
NGC (NGC-1180-1)
Phase 1 Phase
oltage 208/240 VAC
V
Frequency 60 Hz
Current 30 amp
Max Circuit Requirement 30 amp
Plug/Cord NEMA 6-30P; 1.5m,
Max I
nput 5990/6675 watts
Microwave Input Power 3500 watts
NGCBK (NGC-1180-1K-2020)
Phase 1 Phase
Voltage 220 VAC
Frequency 60
ent 30 amp
Curr
Max Circuit Requirement 30 amp
Plug IEC 309, 3-pin, 32 amp
Max Input 6700 watts
Microwave Input Power 3500 watts
EUROPE/ASIA-PACIFIC
NGCEW (NGC-1180-1W f NGCEW (NGC-1180-1W-2024 for Australia/New Zealand)* NGCKW (NGC-1180-1W-2004 for
Phase 3 P
Voltage 400 VAC
Frequency 50
ent 16 amp
Curr
or standard)
Hz
South Korea)**
hase
Hz or 60 Hz**
H07RN-F
Australia/New Zealand
Page 4
Proj ect _______________________________________________________
Item No. ______________________________________________________
Q u a n t i t y _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _______________________________________
TORNADO 2
TM
TORNADO 2
PERFORMANCE
The Tornado 2TM oven evenly and consistently toasts, browns, and crisps food up to twelve times faster than traditional cooking methods, resulting in a high level of throughput without compromising quality.
VENTILATION
n
UL 710B (KNLZ) listed for ventless
operation.†
n
EPA 202 test (8 hr):
- Product: Pepperoni Pizzas
- Results: 0.21 mg/m
- Ventless Requirement: <5.00 mg/m
n
Internal catalytic filtration to limit smoke,
grease, and odor emissions.
3
2
EXTERIOR CONSTRUCTION
n
Stainless steel exterior with powder-coated side panels
n
4” (102 mm) legs
n
Cool to the touch pull down door with microwave seal
TM
INTERIOR CONSTRUCTION
n
304 stainless steel interior
n
Fully insulated cook chamber
n
Removable / variable cooking surfaces
n
Exposed bottom browning element
STANDARD FEATURES
n
Integral recirculating catalytic converter for UL 710B (KNLZ) listed
ventless operation
n
Variable-speed High h recirculating impingement airflow system
n
Variable cooking surfaces (racks, stones, and platters)
n
Independently-controlled bottom browning element
n
Smart Voltage Sensor Technology* (U.S. only)
n
Smart menu system capable of storing up to 128 recipes
n
Built-in self-diagnostics for monitoring oven components
and performance
n
Stackable design (requires stacking kit)
n
Manual snooze mode
n
Includes plug and cord (6 ft. nominal)
n
Smart card compatible
n
Warranty – 1 year parts and labor
COMES WITH STANDARD ACCESSORIES
n
3
1 Aluminum Paddle (NGC-1478)
n
1 Bottle Oven Cleaner (103180)
n
1 Bottle Oven Guard (103181)
n
2 Trigger Sprayers (103182)
n
2 Non-stick Baskets (100011)
3
5
4
6
1. Blower Motor
2. Impingement Heater
3. Impinged Air
4. Bottom Browning Element
5. Microwave Bursts
6. Catalytic Converter
1
This product conforms to the ventilation recommendations set forth by NFPA96 using EPA202 test method.
* Smart Voltage Sensor Technology does not compensate for lack of or over voltage situations. It is the
 responsibilityoftheownertosupplyvoltagetotheunitaccordingtothespecicationsonthebackofthissheet.
Ventlesscerticationisforallfooditemsexceptforfoodsclassiedas“fattyrawproteins.”Suchfoodsinclude
bone-in, skin-on chicken, raw hamburger meat, raw bacon, raw sausage, steaks, etc. If cooking these types of foods, consult local HVAC codes and authorities to ensure compliance with ventilation requirements.
Ultimate ventless allowance is dependent upon AHJ approval, as some jurisdictions may not recognize the UL certification or application. If you have questions regarding ventless certifications or local codes please email ventless.help@turbochef.com
TurboChefreservestherighttomakesubstitutionsofcomponentsorchangespecicationswithoutpriornotice.
DOC-1134/Revision H/
October 2012
Page 5
26” (660 mm)
TM
TORNADO 2
19”
(483 mm)
11.5”
(292 mm)
DIMENSIONS
Single Units
Height 19” 483 mm
on legs 23” 584 mm
Width 26” 660 mm
Depth 25.7” 653 mm
with handle 28.45” 723 mm
Weight 190 lb. 86 kg
Stacked Units
Height 38” 965 mm
Width 26” 660 mm
Depth 25.7” 653 mm
with handle 28.45” 723 mm
Cook Chamber
Height 8” 203 mm
Width 15.5” 394 mm
Depth 14.7” 373 mm
Volume 1.05 cu.ft. 29.9 liters
Wall Clearance
Top 4” 102 mm
Sides 2” 51 mm
(Stacking Kit Required)
(Oven not intended for built-in installation)
ELECTRICAL SPECIFICATIONS
NORTH AMERICA (NGC-1280-1)
Phase 1 Phase
Voltage 208/240 VAC
Frequency 60 Hz
Current 30 amps
Max Circuit Requirement 30 amps
Plug/Cord NEMA 6-30P; 1.5m, H07RN-F
Max Input 5,990 watts (208) / 6,675 watts (240)
Microwave Input Power 3,500 watts
NGCBK (NGC-1280-1K-2020)
Phase 1 Phase
Voltage 220 VAC
Frequency 60 Hz
Current 30 amps
Max Circuit Requirement 30 amps
Plug IEC 309, 3-pin, 32 amp
Max Input 6,700 watts
Microwave Input Power 3,500 watts
EUROPE/ASIA-PACIFIC
NGCEW (NGC-1280-1W for standard) NGCEW (NGC-1280-1W-2024 for Australia/New Zealand)* NGCKW (NGC-1280-1W-2004 for South Korea)**
Phase 3 Phase
Voltage 400 VAC
Frequency 50 Hz or 60 Hz**
Current 16 amps
MaxCircuitRequirement 20 amps
Standard
Australia/New Zealand
25.7” (653 mm)
23”
(584 mm)
Plug IEC 309, 5-pin, 32 amp
Max Input 10,500 watts
Microwave Input Power 3,500 watts
NGCED (NGC-1280-1D)
Phase 3 Phase
Voltage 230 VAC
Frequency 50 Hz
Current 30 amps
MaxCircuitRequirement 30 amps
Plug IEC 309, 4-pin, 32 amp
Max Input 10,500 watts
Microwave Input Power 3,500 watts
NGCUK (NGC-1280-1K)
Phase 1 Phase
Voltage 230 VAC
Frequency 50 Hz
Current 30 amps
Max Circuit Requirement 32 amps
Plug IEC 309, 3-pin, 32 amp
Max Input 6,700 watts
Microwave Input Power 3,500 watts
JAPAN
NGCJD - 50Hz/ 3 Phase (NGC-1280-1D-2005-1)
NGCJD - 60Hz/ 3 Phase (NGC-1280-1D-2005-2)
NGCJK - 50Hz/ 1 Phase (NGC-1280-1K-2005-3)
NGCJK - 60Hz/ 1 Phase (NGC-1280-1K-2005-4)
Phase 1 or 3 Phase
Voltage 200 VAC
Frequency 50 or 60 Hz
Current 30 amps
Max Circuit Requirement 30 amps
Plug PSE-marked, 3 or 4-blade, 30 amp
Max Input 6,700 or 10,500 watts
Microwave Input Power 3,500 watts
3-Phase
1-Phase
SHIPPING INFORMATION
U.S.: All ovens shipped within the U.S. are packaged in a double-wall corrugated box banded to a wooden skid. International: All International ovens shipped via Air or Less than Container Loads are packaged in wooden crates.
Box size: 34” x 30” x 30” (864 mm x 762 mm x 762 mm) Crate size: 37”x 33” x 34” (940 mm x 838 mm x 864 mm) Item class: 85 NMFC #26770 HS code 8419.81
Approximate boxed weight: 260 lb. (118 kg) Approximate crated weight: 320 lb. (145 kg)
Minimum entry clearance required for box: 30.5” (775 mm) Minimum entry clearance required for crate: 33.5” (851 mm)
*All AU-New Zealand ovens with clips allow for 5 pin plug.
TurboChef recommends installing a type D circuit breaker for all installations.
4240 International Pkwy, Suite 105 / Carrollton, Texas 75007 USA
US: 800.90TURBO (800.908.8726) / International: +1 214.379.6000
TurboChef Global Operations
Fax: +1 214.379.6073 / turbochef.com
© 2009-2010 TurboChef Technologies, Inc.
Page 6
Page 2.1
Page 7
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
misleading manner, without any manipulation of the data (or drawings).
KNLZ.E151487
KNLZ.E151487
- Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
...
8/26/2008
http://database.ul.com/cgi
-
bin/XYV/template/LISEXT/1FRAME/showpage.html?name=KNLZ.E151487
...
Page 3.1
Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
Grease-laden Air
Page Bottom
Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
Grease-laden Air
See General Information for Commercial Cooking Appliances with Integral Systems for Limiting the Emission of Grease-laden Air
TURBOCHEF TECHNOLOGIES INC E151487
SUITE 105
4240 INTERNATIONAL PKY
CARROLLTON, TX 75007 USA
Commercial microwave/convection ovens, Models C3/C, HHB, NGC, i5.
Last Updated on 2008-02-14
Questions? Notice of Disclaimer Page Top
Copyright © 2008 Underwriters Laboratories Inc.®
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product.
Designs and/or Listings (files) must be presented in their entirety and in a non-
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2008 Underwriters Laboratories Inc.®"
Page 8
laden
Commercial
The Listing Mark of Underwriters Laboratories Inc. on the product is the only method provided by UL to identify products manufactured under its Listing
KNLZ.GuideInfo
- Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
...
8/28/2008
http://database.ul.com/cgi
-
bin/XYV/template/LISEXT/1FRAME/showpage.html?&name=KNLZ.GuideI
...
Page 4.1
KNLZ.GuideInfo
Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
Grease-laden Air
View Listings Page Bottom
[Heaters and Heating Equipment] (Heaters, Cooking Appliances) Commercial
Cooking Appliances with Integral Systems for Limiting the Emission of Grease-
Air
See General Information for Heaters, Cooking Appliances
This category covers cooking equipment intended for commercial use, such as pressurized deep fat fryers and other appliances for use in commercial kitchens, restaurants or other business establishments where food is prepared. Each appliance covered in this category is manufactured with an integral system feature to limit the emission of grease-laden air from the cooking process to the room ambient.
These appliances have been evaluated for the limit of 5 mg/m3 for the emission of grease-laden air to the room ambient in accordance with the recommendations of the National Fire Protection Association Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, NFPA 96, using the EPA-202 test method prescribed for cooking appliances provided with integral recirculating air systems.
These products are not intended for connection to a ducted exhaust system.
Appliances in this category are not provided with an integral fire extinguishing system. Authorities having jurisdiction should be consulted as to the requirements for this equipment with respect to fire extinguishing systems, such as the need for field installed systems in accordance with NFPA 96.
For products with integral recirculating systems including fire extinguishing systems, refer to Commercial, with Integral Recirculating Systems (KNKG).
In cases where the nature or construction of equipment is such that special precautions beyond the requirements of the National Electrical Code must be observed in installations or use, suitable warning or special instructions are marked on the equipment.
Appliances Listed in this category are suitable for wiring with either copper or aluminum power supply conductors unless marked "Use Copper Wire Only For Power Supply Connections" .
Commercial cooking appliances of certain types are designed for permanent connections to water supply and sewer lines at the point of installation. Authorities having jurisdiction should be consulted as to the requirements for this equipment with respect to sanitation and connection to water supply and waste disposal lines.
Neither the toxicity of coatings nor the physiological effects on persons consuming food products prepared by use of these appliances has been investigated.
For cooking oil filters that are not an integral part of another appliance, see Commercial Filters for Cooking Oil (KNRF
For additional information, see Electrical Equipment for Use in Ordinary Locations (AALZ) and Heating, Cooling, Ventilating and Cooking Equipment (AAHC).
).
The basic standard used to investigate products in this category is ANSI/UL 197, "Commercial Electric Cooking Appliances".
Appliances Listed in this category with an integral cooking oil filter have been additionally investigated to the requirements in the standard " Filters for Cooking Oil", ANSI/UL 1889.
and Follow-Up Service. The Listing Mark for these products includes the name and/or symbol of Underwriters Laboratories Inc. (as illustrated in the Introduction of this Directory) together with the word "LISTED," a control number and one of the following product names as appropriate: "Commercial Cooking Appliance," "Cooking Appliance," or other appropriate product identity specified in the individual Listing, along with the words "with integral system for limiting the emission of grease-laden air. "
Page 9
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
misleading manner, without any manipulation of the data (or drawings).
Last Updated on 1999-02-19
KNLZ.GuideInfo
-
Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
...
8/28/2008
http://database.ul.com/cgi
-
bin/XYV/template/LISEXT/1FRAME/showpage.html?&name=KNLZ.GuideI
...
Page 4.2
Questions? Notice of Disclaimer Page Top
Copyright © 2008 Underwriters Laboratories Inc.®
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product.
Designs and/or Listings (files) must be presented in their entirety and in a non-
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2008 Underwriters Laboratories Inc.®"
Page 10
Page 5.1
Page 11
Page 5.2
Page 12
Page 6.1
April 10, 2007
Mr. James Pool Turbochef Technologies Inc Suite 105 4240 International Pky Carrollton, TX 75007 United States
Our Reference: File E151487
Subject: INTEGRAL RECIRCIRCULATING SYSTEM
Dear Mr. Pool:
In reply to your e-mail message received today, I offer the following.
Products in the KNLZ category (as well as KNKG) are evaluated to UL710B. It used to be that UL197 and supplement SB in UL197 was the standard that they were evaluated to. Basically, UL197 and Supplement SB became UL710B. There is no more Supplement SB in UL197 (9th Ed.).
Any information and documentation involving UL Mark services are provided on behalf of Underwriters Laboratories Inc. (UL) or any authorized licensee of UL.
Very truly yours,
Fred Zaplatosch Staff Engineer 3015CNBK Tel: 847-664-2853 Fax: 847-313-2853 fred.zaplatosch@us.ul.com
Page 13
EXHAUST SYSTEMS
Page 7.1
EXHAUST SYSTEMS
airfrom theexhaust outletdischarges away from such locations.
506.4 Ductsserving TypeIIhoods. Single or combinedType
II exhaust systems for food-processing operations shall be
of
independent
all otherexhaust systems. Commercialkitchen exhaust systems serving Type II hoods shall comply with Sec­tions 506.4.1 and 506.4.2.
506.4.1 TypeIIexhaust outlets. Exhaust outlets for ducts
serving Type II hoods shall complywith Sections401.4 and
401.4.2. Such outlets shall be protected against local weather conditions and shall meet the provisions for exte­rior wall opening protectives in accordance with the
national Building Code.
506.4.2 Ducts. Ducts and plenums serving Type II hoods
of
shall be constructed
rigid metallic materials. Duct con-
struction, installation, bracing and supports shall comply
6.
with Chapter
Ducts subjectto positive pressure and ducts conveying moisture-laden or waste-heat-Iaden air shall be constructed, joined and sealed in an approved manner.
506.5 Exhaust equipment. Exhaust equipment, including
fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.5 and shall be
of
an approved design or shall be
listed for the application.
506.5.1 }:xhaust fans. Exhaust fan housings servinga Type
as
I hood shall be constructed
required for grease ducts in
accordance with Section 506.3.1.1.
Exception: Fans listed and labeled in accordance with
UI-I762.
506.5.1.1
located outside
Fan
motor. Exhaust fan motors shall be
of
the exhaust airstream.
506.5.2 Exhaust fan discharge. Exhaustfans shall beposi-
tioned so that the discharge will not impinge on the roof,
of
other equipment or appliances or parts
the structure. A
vertical discharge fan shall be manufactured with an
of
approved drain outlet at the lowest point
of
permit drainage
grease to an approved grease reservoir.
the housing to
506.5.3 Exhaust fan mounting. An upblast fan shall be
hinged and supplied with a flexible weatherproof electrical cable to permitinspection and cleaning. Theductwork shall extend a minimum
of18inches (457 mm) above the roof
surface.
506.5.4 Clearances. Exhaust equipment serving a Type I
hood shall have a clearance to combustible construction not less than18inches (457 mm).
Exception: Factory-builtexhaust equipment installed in
accordance with Section 304.1 and listed for a clearance. '
506.5.5 Terminationlocation. Theoutlet
of
exhaustequip-
ment serving Type Ihoods shall be in accordance with Sec-
I tion 506.3.12.
Exception: The minimum horizontal distance between
vertical discharge fans and parapet-type building struc­tures shall be 2 feet (610 mm) provided that such struc-
507.1 General. Commercialkitchen exhaust hoods shall com-
ply with therequirements orType II and shallbedesigned to capture and confinecooking vapors and residues. Commercial kitchen exhaust hood sys­tems shall operate during the cooking operation.
Inter-
507.2 Where required. A Type I or Type II hood shall be
installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under asinglehood requires aType Ihood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed.
..
of
l,~sser
tures are not higher than the topofthe fan discharge opening.
SECTION 507
COMMERCIAL KITCHEN HOODS
of
this section. Hoods shall be TypeI
Exceptions:
1.
Factory-built commercial exhaust hoods which are tested in accordance with UL 710, listed, labeled and installed in accordance with Section 304.1 shall not be required to comply with Sections 507.4, 507.7,
507.11,507.12,507.13,507.14 and 507.15.
2.
Factory-built commercial cooking recirculating sys­tems which are tested in accordance with UL 710B, listed, labeled and installed in accordance with Sec­tion 304.1 shall not be required to comply with Sec­tions 507.4,507.5,507.7,507.12,507.13,507.14and
507.15.
3.
Net exhaust volumes for hoods shall be permitted to bereduced during no-load cooking conditions, where engineered or listed multispeed or variable-speed controls automatically operate the exhaust system to
of
maintain capture and removal
cooking effluents as
required by this section.
507.2.1 Type I hoods. TypeI hoods shall be installedwhere
cooking appliances produce grease or smoke, such as occurs with griddles,fryers, broilers, ovens, ranges and wok ranges.
507.2.1.1 Operation. Type I hood systems shall be
designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation lock with the cooking appliances, by means sors or by means
of
the exhaust fan shall occurthrough an inter-
of
heat sen-
of
other approved methods.
507.2.2. TypeIIhoods. Type II hoods shall be installed
where cooking or dishwashing appliances produce heat,
of
steam, or products
or smoke, such
combustion and do notproduce grease
as
steamers, kettles, pasta cookers and
dishwashing machines.
Exceptions:
1.
Under-counter-type commercial dishwashing machines.
2.
A Type II hoodis notrequired for dishwashers and potwashers that are provided with heat and water
vapor exhaust systems that are supplied by the appliance manufacturer and are installed in accor­dance with the manufacturer's instructions.
....3.A single light-duty electric convection, bread,
retherm or microwave oven. The additional heat and moisture loads generated by such appliances
of
shall be accounted for in the design
the HVAC
system.
I
4. A Type II hood is not required for the following electrically heated appliances: toasters, steam tables, popcorn poppers, hot dog cookers, coffee makers, rice cookers, egg cookers, holding/warm­ing ovens. The additional heat andmoisture loads generated by such appliances shall be accounted for in the design
of
the HVAC system.
507.2.3 Domestic cooking appliances used for commer­cial purposes.
Domestic cooking appliances utilized for
commercial purposes shall beprovided with Type I or Type
as
I
II hoods
required for thetypeofappliances and processes
in accordance with Sections 507.2, 507.2.1 and 507.2.2.
507.2.4 Extra-heavy-duty. Type I hoods for use over
extra-heavy-duty cooking appliances shall not cover other appliances that require fire extinguishing equipment and such hoods shalldischarge to anexhaust system that is inde-
of
pendent
other exhaust systems.
507.3 Fuel-burning appliances. Where vented fuel-burning
appliances are located in the same room or space as the hood, provisions shall be madeto preventthe hoodsystemfrom inter-
of
fering with normal operation
507.4 Type I materials. Type I hoods shall be constructed
the appliance vents.
of steelnotless than 0.043 inch (1.09 mm) (No.18MSG) in thick­ness, or stainless steel not less than 0.037 inch (0.94 mm) (No. 20 MSG) in thickness.
507.5 TypeIIhood materials. Type II hoods shall be con-
of
structed
steel not less than 0.030 inch (0.76 mm) (No. 22 Gage) in thickness,stainless steelnot less than0.024 inch (0.61 mm) (No. 24 Gage) in thickness, copper sheets weighing not less than 24 ounces per square foot (7.3 kg/m
2
),
orofother
approved material and gage.
507.6 Supports. TypeI hoods shallbe secured inplace by non-
combustible supports. All Type I and Type II hood supports
of
shall be adequate for the applied load
the hood, the unsup­ported ductwork, the effluent loading, and the possible weight of
personnel working in or on the hood.
507.7 Hood joints, seams
and
penetrations. Hood joints,
seams and penetrations shallcomply with Sections507.7.1 and
507.7.2.
507.7.1 Type I hoods. Externalhood joints, seams andpen-
etrations for Type I hoods shall be made with a continuous external liquid-tight weld or braze to the lowest outermost perimeter
of
the hood. Internal hoodjoints, seams, penetra-
tions, filter support frames, and other appendages attached
inside the hood shall not berequired to bewelded orbrazed but shall be otherwise sealed to be grease tight.
Exceptions:
1.
Penetrations shall not be required to be welded or brazed where sealed by devices that are listed for the application.
2.
Internal welding or brazingofseams, joints, and
of
penetrations
the hood shall not be prohibited provided that the jointis formed smooth orground so as to not trap grease, and is readily cleanable.
507.7.2 TypeIIhoods. Joints, seams and penetrations for
Type II hoods shall be constructed as set forth in Chapter shallbe sealed on the interiorofthe hood and shallprovide a smooth surface that is readily cleanable and water tight.
507.8 Cleaning
to provide for thoroughcleaning
and
grease gutters. A hood shall bedesigned
of
theentire hood. Grease gut­ters shall drain to an approved collection receptaclethat is fab­ricated, designed and installed to allow access for cleaning.
507.9 Clearances for Type I hood. A Type I hood shall be
of
installed with a clearance to combustibles
not less than
inches (457 mm).
Exception: Clearance shall not be required from gypsum
wallboard attached to noncombustible structures provided thata smooth, cleanable, nonabsorbent andnoncombustible material is installedbetween the board over an area extending not less than
h90d and thegypsum wall-
18
inches (457
mm) in all directions from the hood.
507.10 Hoods penetrating a ceiling. Type Ihoods orportions
thereofpenetrating a ceiling, wall or furred space shall comply
of
with all the requirements
Section 506.3.10.
507.11 Grease filters. Type I hoods shall be equipped with
listed grease filters designed for the specific purpose. Grease-collecting equipment shall be provided with access for cleaning. The lowest edge
of
a grease filter located above the cooking surface shall be not less than the height specified in Table 507.11.
TABLE
MINIMUM DISTANCE BETWEEN THE LOWEST EDGE OF A
GREASE FILTER
TYPEOFCOOKING
APPLIANCES
Without exposed flame 0.5 Exposed flame and burners Exposed charcoal and charbroil type 3.5
For
SI:
1foot =304.8
AND
HEATING SURFACE
mm.
507.11.1 Criteria. Filters shall be
arrangement as will permit the required quantity
507.11
THE COOKING SURFACE OR THE
HEIGHTABOVE COOKING
SURFACE (feet)
2
of
such size, type and
of
air to pass through such units at rates not exceeding those for which the filter or unit was designed
or' approved. Filter
units shall be installed in frames or holders so as to be
of
readily removable without the use
separate tools, unless
6,
18
44
2006 INTERNATIONAL
MECHANICAL
CODE@
2006
INTERNATIONAL
MECHANICAL
CODE@
45
Page 14
UL 710B (KNLZ)
Page 8.1
Emissions by Product
275
250
225
200
175
150
125
100
Product Cooked per 8 hour period
75
3
2.75
2.5
2.25
2
1.75
1.5
1.25
PM Emissions [ppm]
1
0.75
50
25
Pizza's Cooked Emissions
0
C3/C HHB i5 NGC
TurboChef Model
0.5
0.25
0
Page 15
Page 9.1
October 18, 2004 Mr. Mike Denny
Building Services, 224 West Knight St. City of Sioux Falls, South Dakota, 57102 Ph: 605-367-8252
Re: Fire and smoke containment Dear Mr. Denny: The TurboChef ovens have been extensively tested and conform to UL 923 and UL KNLZ
standards. The UL 923 standard is the electrical/product safety standard and the KNLZ is the low particulate matter emissions standard to which we conform. While both standards address difference aspects of the oven, they both have inherent overlap as it relates to grease/smoke/fire handling.
As it relates specifically to fire safety, UL 923 specifies:
Section 57 Cavity Fire Containment Test:
The performance of an appliance subjected to this test shall be considered acceptable if all of the following conditions are met:
a) There is no emission of fire, flame, or molten metal outside the appliance nor glowing or ignition of the cheesecloth, tissue paper, or wood surface;
b) The fuse rated 3 A does not open; c) Following the test, the appliance complies with the requirements of Leakage Current, Section 33,
and Dielectric Voltage-Withstand Test, Section 39, as applicable to primary circuits; and d) Following the test and following 10 c of operation (opening and closing the door), the appliance complies with the requirements in 57.12. The radiation emission shall not xceed
5mW/cm2.
Test Method:
Section 57.2 requires that 4 potatoes each weighing between 150g and 200g be placed inside the oven under test and cooked using full microwave power and hot air (if applicable) until the potatoes catch fire. Note: The test must be repeated until it catches fire. During this test, pieces of tissue paper and cheesecloth are placed above, below and around the product to ensure that the fire and/or excessive heat generated is safely contained within the confines of the appliance.
As it relates to grease handling, UL KNLZ specifies:
UL KNLZ Guide Information Excerpt:
“These appliances have been evaluated for the limit of 5 mg/m air to the room ambient in accordance with the recommendations of the National Fire Protection Association Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, NFPA 96, using the EPA-202 test method prescribed for cooking appliances provided with integral recirculating air systems.”
3
for the emission of grease-laden
C:\Windows\Temp\Rar$DI00.000\Fire smoke and grease statement v2_11.doc
Page 16
Test Method:
Page 9.2
The UL KNL
Z category requires that products must have less than 5.0 mg/m3 of particulate matter
emissions during 8 continuous hours of cooking a “worst case” food product as measured by EPA
202. Note: Our products were tested using full-fat pepperoni pizzas.
As it pertains specifically to smoke: Smoke typically consists of visible grease particulate that escapes from a product during operation. Our ovens utilize a recirculating airpath that is catalytic scrubbed, thus the airborne grease is combusted as it crosses our catalyst. Given this, under typical/normal operating conditions, our product does not emit smoke.
If you have any issues or specific questions regarding the above, please contact me directly.
Best regards,
James K. Pool III
James K. Pool III Vice President Engineering, TurboChef Technologies, Inc., Ph: 214.379.6020 Email: james.pool@turbochef.com
C:\Windows\Temp\Rar$DI00.000\Fire smoke and grease statement v2_11.doc
Page 17
NGC Energy.xls
Do Not Change the following values
Power
Cooking
100
5000
$0.96
10.08
Snooze Idle
0
1100
$0.00
10.08
Idle
605
1400
$1.62
0
Total/Month
$81.72
$980.62
HVAC Requirements Per Operating Time -- Note: Approximations Only
80820000
4749300
85569300
1981
6.759028
Page 10.1
NGC Tornado (1 PHASE)
Changeable Parameters Operating Time 12 Hours Energy Costs $0.11 kWHr Snooze Mode 0.00 Hours Cook Cycles/Day 100 Cooks/Day
Typical Cook Time 60 Seconds
Time (min)
Warm up
Total/Day
Average Energy Cooking And Idle (J) Warmup Energy (J)
11/6/2008 Confidential James K. Pool
15 5277 $0.15 11.75
(Watts) Cost/Day Balance of Time (hrs)
$2.72 Yearly
Total
Energy (J)
Total average
Power (W)
Total Environmental
Load kBtu/hr
Average
Cooling
Requirement
(ton of AC)
0.563
Page 18
ARNOLD SCHWARZENEGGER
Gover
nor
State of California—Health and Human Services Agency
Department of Health Services
SANDRA SHEWRY
D
irecto
r
July 23, 2004
Ruth Sender OhCal Foods, Inc. 20501 Ventura Blvd., Suite 375 Woodland Hills, CA 91364
RE: Exemption from Mechanical Exhaust Ventilation for
TurboChef Model NGC Rapid Cook Oven Dear Ms. Sender: Thank you for your application of April 26, 2004, for a review of the TurboChef Model
NGC Rapid Cook Oven for exemption from the mechanical exhaust ventilation requirements of Section 114140 of the California Uniform Retail Food Facilities Law (CURFFL). Specifically, you have requested an exemption to allow unventilated NGC Rapid Cook Ovens to be installed and operated at various Subway locations throughout California.
You have provided documentation and I have verified that the TurboChef Model NGC Rapid Cook Oven has been evaluated and listed by UL for conformance with ANSI/NSF Standard 4.
Under the provisions of CURFFL Section 114140, the Department may exempt heating and cooking equipment that does not produce toxic gases, grease, smoke, or heat when properly installed and operated as recommended by the manufacturer. Based on the information and documentation you have provided, the TurboChef Model NGC Rapid Cook Oven is granted LIMITED exemption from mechanical exhaust ventilation under the following conditions:
1. Unless approval is granted by the local enforcement agency, there shall be no more than one unventilated oven in operation at each Subway location.
2. No other heating or cooking appliances subject to mechanical ventilation requirements may be operated without mechanical ventilation in the food facility, unless permission to operate more than one unventilated appliance is granted by the local enforcement agency.
Food and Drug Branch, MS 7602, P.O. Box 997413, Sacramento, CA 95899-7413
Intern
e
t Address:
www.dhs.ca.gov/fdb
Page 11.1
3
Page 19
Ms. Ruth Sender J
uly
23,
2004
Page 2
3. The oven shall not be used for cooking
meats, poultry, fish, or other foods that may produce grease laden vapors. Such use will require that mechanical ventilation be installed over the unit.
4. The oven must be operated and installed in a well-ventilated area approved for food preparation.
5. The oven must be installed, maintained, operated, and serviced according to the specifications of the manufacturer and local codes.
6. This exemption shall not be deemed to supersede any local fire or building code requirements.
This exemption shall be in effect until revoked. However, should any local enforcement agent find that the operation of the TurboChef Model NGC Rapid Cook Oven without mechanical ventilation creates a sanitation or safety problem, the local enforcement agent may require the unit to be used only with mechanical ventilation. These problems may include, but are not limited to, problems of installation, use, maintenance, cleaning or other site specific considerations which exceed the above limitations or pose a discernable health or safety hazard.
This letter may be used as evidence of the evaluation of the TurboChef Model NGC Rapid Cook Oven. However, it is not to be construed as an endorsement of the subject item and may not be used for advertising or promotional purposes.
If you have any questions you may call me at (916) 650-6617. Sincerely,
Susan Strong, REHS Program Specialist, Retail Food Unit
Cc: Mike Boian, REHS
Northern California Technical Advisory Committee
Page 11.2
Page 20
Ms. Ruth Sender J
uly
23,
2004
Page 3
Virginia Lineberry, REHS Bay Are
a Technical Advisory Committee
Donna Fenton, REHS Central Valley Technical Advisory Committee
Nelson Kerr, REHS Southern California Technical Advisory Committee
Gary Erbeck, REHS CCDEH, Food Safety Policy Committee
Page 11.3
Page 21
State of California—Health and Human Services Agency
601 N. 7
th
Street, MS-357, P.O. Box 942732, Sacramento, CA, 94234-7320
(916) 445-2263
Internet Address:
www.dhs.ca.gov
Page 11.4
DIANA M. BONT
Director
October 25, 2002
Peter J TurboChef Technologies, Inc. 10500 Metric Drive, Suite 128 Dallas, Texas 75243
Dear Mr. Ashcraft:
RE: Exemption from External Mechanical Exhaust Ventilation
Thank you for your letter of October 7, 2002 requesting exemption from mechanical exhaust ventilation requirements specified in Section 114140 of the California Uniform Retail Food Facilities Law (CURFFL) for the Model C3/C Rapid Cook Oven.
Á, R.N
., Dr. P.H.
. Ashcraft
Depart
ment of Health Services
Food & Drug Branch
GRAY DAVIS
vernor
Go
Descriptive materials and cut sheets accompanying your application specify that this oven is Sanitation Classified by NSF International for compliance with ANSI/NSF Standard 4 for commercial heating and cooking appliances.
Under the provisions of Section 114140, the Department may exempt heating and cooking equipment that does not produce toxic gases, grease, smoke, or heat when properly installed and operated as recommended by the manufacturer. Results of tests conducted by the Pacific Gas & Electric, Food Service Technology Center, indicate that the oven produces no significant emissions of smoke and grease-laden air while in use. Based on the information you have provided and the certifications by recognized testing laboratories, the TurboChef Technologies Model C3/C Rapid Cook Oven is granted LIMITED exemption from mechanical ventilation requirements under the following conditions:
1. There may be up to two (2) unventilated Model C3/C ovens in Subway sandwich stores in California.
2. The oven(s) must be installed, maintained, operated, and serviced according to the specifications of the manufacturer and local codes.
3. Any modification, alteration, or removal of any component of the integral air filtration system voids this limited exemption.
4. All air filtration components must be installed and operational at all times the appliance is in use.
5. The oven must be installed in an approved food preparation area with sufficient room ventilation to maintain acceptable working conditions.
about saving energy, visit the following web site:
Do your part to help California save energy. To lear
www.consumerenergycenter.org/flex/index.html
n more
Page 22
Peter Ashcraft
Page 11.5
r 25, 2002
Octobe
This exemption shall be in effect until revoked. However, should any local enforcement agent find that the operation of the TurboChef Technologies Model C3/C Rapid Cook Oven without mechanical ventilation creates a sanitation or safety problem, the local enforcement agent may require the unit to be used only with external mechanical ventilation. These problems may include but are not limited to problems of installation, use, maintenance, cleaning or other site specific considerations which exceed the above limitations or pose a discernable health or safety problem.
This letter may be used as evidence of the evaluation of the TurboChef Model C3/C Rapid Cook Oven. However, it is not to be construed as an endorsement of the subject equipment and may not be used for advertising or promotional purposes.
If you have any questions you may call me at (916) 327-6905.
Sincerely,
Jeffrey C. Lineberry, MPH Chief, Retail Food Unit
Cc: Mike Boian, REHS
Northern California Technical Advisory Committee Butte County Environmental Health P.O. Box 5364 Chico, CA 95927
Leslie Gentry, REHS Bay Area Technical Advisory Committee Solano County Environmental Health 601 Texas Street Fairfield, CA 94533
Donna Fenton Central Valley Technical Advisory Committee Environmental Health Services 2700 “M” Street, Suite 300 Bakersfield, CA 93301
Page 23
Peter Ashcraft October 25, 2002
Elizabeth Quaranta Southern California Technical Advisory Committee
San Diego County Environmental Health 1255 Imperial Avenue San Diego, CA 92101
Gary Erbeck, Food Policy Committee
California Conference of Directors of Environmental Health
San Diego County Environmental Health 1255 Imperial Avenue San Diego, CA 92101
Page 11.6
Page 24
Page 11.7
Page 25
Page 11.8
Page 26
SBD-5863 (R. 10/00)
Evaluation #
Safety & Buildings Division 201 Wes
t Washington Avenue P.O. Box 2658 Madison, WI 53701-2658
Wisconsin
Building Products Evaluation
Material
Manufacturer
SCOPE OF EVALUATION
Section 507.2.2 of the 2003 and 2004 Supplement of the International Mechanical Code, IMC, regarding exhaust
system requirements where commercial cooking and dishwashing appliances produce grease, smoke, heat or steam have been evaluated for compliance with certain requirements of the Wisconsin Commercial Building Code (WCBC), Chapters Comm 61-65. Pursuant to s. Comm 61.61 the TurboChef Models Tornado (NGC), C3/C and High H (HHB) microwave ovens are approved for use in the State of Wisconsin to satisfy the intent and the provisions of IMC 507.2.2 as adopted by the Wisconsin Commercial Building Code.
This evaluation does not include the review for compliance to provisions of the current Wisconsin Commercial Building Code other than those specifically referenced above.
The use of the TurboChef Models Tornado (NGC), C3/C and High H (HHB) microwave ovens are subject to the description, limitations and conditions described in this evaluation.
DESCRIPTION AND USE
The current Wisconsin Commercial Building Code together with the 2000 edition of the International Mechanical Code, IMC, does not specifically address, acknowledge or prohibit the utilization of recirculating hoods and vent less
steam removal systems in conjunction with commercial kitchen appliances and their operation where grease, smoke, heat or steam is produced. The revision under the 2003 edition and 2004 Supplement of the IMC clarify the use of such appliances.
Section 507.2.2 of the 2003 International Mechanical Code read as follows:
507.2.2 Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce
heat or steam and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing
machines.
Microwave Oven
TurboChef Model NGC
TurboChef Technologies, Inc.
10500 Metric Dr., Suite 128
Dallas, TX 75243
200424-H Revision 2
Page 11.9
Page 27
COMMERCE Product Evaluation No. 200424-H Revision 2
The evaluation number assigned to this approval is to accompany each plan submitted for projects that utilizes the TurboChef Models: Tornado (NGC), C3/C and High H (HHB) ovens.
Deviations from this approval shall void the use of the approval.
Pursuant to s. Comm 61.61(7), the department may reexamine an approval and issue a revised approval at any time.
This approval will be valid through December 31, 2009, unless manufacturing modifications are made to the product or a re-examination is deemed necessary by the department. The product approval is applicable to projects approved under the current edition of the applicable codes. This approval may be
void for project approvals made under future applic
able
ed
itions. The Wisconsin Building Product Evaluation number must be provided when plans that include this
product are submitted for review.
DISCLAIMER
The department is in no way endorsing or advertising this product. This approval addresses only the specified applications for the product and does not waive any code requirement not specified in this document.
Revision Date: March 22, 2006 Approval Date: September 30, 2004 By: __________________________________ Lee E. Finley, Jr. Product & Material Review Integrated Services Bureau
200424-H.doc
Page 11.10
Page 2
Excep
counter or that is enclosed on five sides in a counter, provided that such appliances do not increase the ambient temperature more than 10º F at a distance greater than 5 feet away from such appliance during operation.
LIMITATIONS OF APPROVAL
tion:
ingle light-duty electric convection, bread, retherm or microwave oven designed for installation on a
3. A s
Page 28
Working Together to Promote Food Safety
Minnesota Department of Health • Environmental Healt
h
Serv
ices Sec. • P.O. Box 64975 • St. Paul, MN 55164-0975 • (651) 215-0870
Minnesota Department of Agriculture • Dairy and Food Inspection Div. • 90 W. Plato Blvd. • St. Paul, MN 55107-3219 • (651) 296-2627
An equal opportunity employer
DATE: June 11, 2004
TO: All Local Health Agencies
Minnesota Department of Health (MDH) EHS Sanitarians and Supervisors
Minnesota Department of Agriculture (MDA)
FROM: Colleen Paulus
Manager, MDH Environmental Health Services Section
Kevin Elfering Director, MDA Meat, Food and Dairy Division
SUBJECT: Inter Agency Review Council Document 04-04V
TurboChef Tornado Oven Model NCG
Please distribute the attached information to sanitarians on your staff who work in the Food Program.
Attached please find IARC Guidance Document #04-04V regarding the new TurboChef Tornado Microwave/Convection Oven Model NCG that is being proposed in Subway Sandwich Shops throughout Minnesota. This document is very similar, but not exactly the same as IARC Document #03-01 issued April 9, 2003, which addresses the TurboChef Rapid Cook Oven Model No. C3. The emissions test for total particulate matter was much lower from the test conducted on the previous oven (0.5mg/m
3
vs. 3.8 mg/m3). However, as you will note in the attached conditions for acceptance, unless
there is a sufficient amount of general ventilation existing in the space, additional cooling capacity may
be needed and verified by a certified testing and balancing contractor.
If you have any questions regarding the TurboChef Tornado Oven Model NCG use, you may contact the Vent Committee Chair, Lorna Girard, at 651/296-1591 or at
lorna.girard@state.mn.us
If you have any questions regarding the IARC, please contact Sue Hibberd at 651/215-0866 or at
sue.Hibberd@health.state.mn.us
Page 11.11
Page 29
S
TATE OFMICHIGAN
DEPARTMENT OF AGRICULTURE
L
ANSING
JENNIFER M. GRANHOLM
GOVERNOR
DAN WYANT
DIRECTOR
April 14, 2004
Mr. James Boyd, Plan Review Specialist Kent County Health Department Environmental Health Division 700 Fuller Avenue, N.E. Grand Rapids, MI 49503
Re: Turbo-Chef Convection / Microwave Oven Models C3/C and NGC
Dear Mr. Boyd:
You requested an evaluation of the Turbo Chef oven model NGC, that is proposed to be installed in Subway restaurants state-wide. MDA recommends that both model NGC and C3/C may be installed and used without ventilation in any food establishment as they are UL197SB listed. These ovens contain an internal filter and vent that has been shown, under proper test conditions, to emit very little grease (pepperoni pizzas were used in testing).
Preparation in these ovens without additional ventilation should be limited to pizzas, sub sandwiches, reheating of par-baked or cooked foods, other similar items and baking. Neither MDA nor the manufacturer recommends cooking raw, fatty protein products (i.e. raw meat) in these ovens.
Michigan's mechanical code rules (R 408.30935a) specifically exempt from ventilation "listed factory-built commercial cooking recirculating systems which are tested in accordance with UL 197" and installed per listing and manufacturer's directions. However, a mechanical inspector may require ventilation if the building has inadequate general ventilation.
If you have any questions please call me at (517) 373-2779.
Sincerely,
Kevin Besey, Supervisor Food Service Sanitation Section Food and Dairy Division
cc: James Pool, Turbo Chef Dave Adams, Assistant Chief, Mechanical Division, BCC, MDCIS Michigan local Health Departments / MDA Regions
CONSTITUTION HALLy P.O. BOX 30017y LANSING, MICHIGAN 48909
www.michigan.gov
y
(517) 373-1104
Page 11.12
Page 30
Page 11.13
Page 31
Page 11.14
Page 32
Page 11.15
Page 33
Page 11.16
Page 34
HI|IFÐtr
Page 11.17
BiffLMHG
filÅ*sf{i\TÐ,R$w,¡l
E LtlJ ûRE ll
À!*Ð 5AfËTY
€ûÉ{tftssÍ01{,f
FñËffi${T
ì/åù,¡
AldE.É\¡ELt5
VtrPëSS9E¡IIT
VICTÐ'R
HELEHAJ
CUEVÀ5
H.
UB,AT'IY
ì¡"dlLLtALlS
Rs
C¡rv rF
Los ANc=r-=s
C*,LIFORFIIÅ
IEFX¡*rr
B I'ILE}Ii{G ATËE}
I{TETH
¡Ë.1
ROÊ:f RT
RAY¡,i0t'tÐs. 0HAN,
FIG{.EROÅ
LWAI,¡GEI-ES.
GEiEtr\¡- IS{HÂGER
¡ts4uTir"= C!E:F.
R.
CA Ðtr
"EUÐF
SÂF:ETV
STFÉET
01¡.RtM
c.E., s.Ë..
James K Pool III
TurboChef Technologies
42 40 lnternational
Pa rkway
Carrollton, TX 75034
Telephone: 21 4-379-6020
Models:
NGC+, NGO
PLEASE
The item
(LAPC)
Code
This letter your
organization and shown as evidence
(*new
model
added),
REFER
TO THE APPLICATION NUMBER
processed
or
under the above file number
Los Angeles
and/or
the letterhead
copy may not be reproduced for
CONDITIONS OF APPROVAL:
ON ALL
Mechanical
ofapproval.
*NTC}NI O R VILLÀR¡.,ITÛSA
has been
Code
!,t.åYoR
CORRESPONDENCE,
tested, examined and
(LAMC)
is
and
hereby approved
use in labeling
File Number: M-100012 Effective Date:
04101 1201
Expiration Dafe: 04101
I
12012
Manufacturer: SAME
Item: WARMING OVEN
PHONE CALLS & SAMPLES
found to comply with
revoked
unless
or
advertising, but copies of this letter may be
applicable
for
cause.
Los
Angeles Plumbin¡
used within
Each item shall have
In order
Arrangement shall
notice
this
Jason T Tran Mechanical
1. This
2.Installation of
product
shall
be used to warm
product
this
is not required
20ll Edition.
product
This
3.
manufacturer and LAMC, 2011
renew
to
be
will
Testing Laboratory, Test Engineer
shall be installed,
name
the
this approval,
made
be
or trademark
application
an
to remove any
shipped collect by the most
pre-cooked
hot
to have
operated,
maintained
and
Edition.
of nranufacturer
and reexamination
test samples remaining
convenient
and
carrier or
food items
an exhaust system
model
fee
in the
only. Any other
per
Sections 95.507.1.1
in
accordance
with
numbqr'"yherc it will
must be
submitted on or before
Laboratory. Samples remaining
disposed of in accordance with
Plumbing
Inspection Bureau
/ Mechanical Inspection
type of cooking shall not
95.507.1.2
and
printed
instructions
be visible for inspection,
expiration
the
after
from
21
days from
applicable regulation,
be allowed,
of LAMC,
the
date shown
the
above. date of
Page 35
z
a I
Couxw
Los Axorl¡s
oF
A{. Prhlio
\\
'
r ¡rrrr
,
JONATHAN
D¡rector
and
JONATHAN E. FREEDMAN
Chief Deputy Director
ANGELO BELLOMO,
Environmental
VERONICA
Act¡ng Director, Bureau of
PLAN CHECK PROGRAM
5050
Commerce
Baldwin Park, California
(626)
TEL
$¡$¡r¡v:äÍb I iOhèâlf h: Iãcôuntv :¡i:a¡v/éh/
FIELDING,
E.
Health Officer
Health
BAUCHMAN, R.E,H.S.
Dr¡ve
430-s560
.
HeAItlt
M.D.,
R.E.H.S., Director
District
91706
(626)
FAX
813-1444
May 3l,20ll
James
Senior Vice President, Engineering
K. Pool III
TurboChef Technologies,
4240 International Parkway,
Carrollton, Texas 75007
M.P,H.
Surveillance and
Inc.
Suite 1
Enforcement
1
0
PtâñorECr(mßER:
ItÉ-Paø
BOARD Gloria Molina
First Distr¡ct
Mark R¡dley-Thomas
Second D¡str¡ct
Zev Yaroslavsky
Th¡rd Distr¡ct
Don Knabe
Fourth
M¡chaèl D. Antonovich
F¡fth Distr¡ct
'0t
OF SUPERVISORS
Distr¡ct
/
Ventilation Exemption
Application Type:
Effective Date: Expiration Date:
Telephone:
Email:
RE: Exemption
Model Tornado
Dear
Mr. Pool:
The County completed
(NGCD6)
114149.1(a)
You have
approval, and Tornado
was 1.153 ffidfrì',
a
ovens for
provided
(NGC)
from mechanical
(NGC)
Los Angeles
of
review
of
exemption from
of
the California Retail Food
documentation
provided
also
oven. The
which is below
appliance.
Plan Check
No.
and Tornado 2
Department
TurboChef
the
the results
test results indicate
the limit
exhaust
ventilation for TurboChef Technologies,Inc.
(NGCD6)
of Public Health,
Technologies,
the mechanical
Code.
that
these ovens have
of the eight-hour
of 5 mg/ m'to
ME-2010-009 Equipment
specific
5t3r/2011
6t1t2016
(2r4)
379-6020
James. Pool
@Jurbochef.
ovens
Environmental Health, Plan
Inc. Model:
exhaust ventilation requirements
Tornado
Underwriter's Laboratory KNLZ
cooking emissions test
that
particulate
the
matter concentration
be considered a
com
(NGC)
and Tornado 2
conducted on the
grease
low
Check has
of Section
produced
emission
Page 36
TurboChef
Page 11.19
May
3I,20lI
Page2
of3
Oven
Therefore, required contingencies are met:
additional mechanical
by the
L There
2.
3. The
4.
County of Los Angeles
shall
(NIGCD6)
No other
equipment
manufacturer's
Any
modification,
of the integral
and
this limited
operational
5. The Tornado
bread, be cooked
6.
No items
unventilated
bakery
no
be
more
per
oven
producing
heat
must
air
ex
at aII ti
or Tomado
products,
in
the equipment
generate
that
Tornado
ventilation
than two
food
facility.
food
or
similar
unless
grease-laden
Tomado
or
in
the form
Department
unventilated
related
equipment requiring
t the addition
items
mechanical
vapors
2
oven.
of a Type I
of Public
model Tomado
maintained
used
for
only.
No raw
ventilation
l.l
a_!
i;)
shall
Type
or
Health,
provided
(NGC)
ventilation
of mechanicai
uipment, including
ANSI
ponents
be
certification
the cooking
animal
prepared
ventilation.
accordins to
must
be
or warming
protein
provided.
is
or
cooked in
II hood is not
the following
or Tornado 2
shall be
the
any component
of
the equipment
installed
and
of
products
the
pizza,
shall
7.
The
for food
8.
If
the ownership
then
9.
This
supersede
fire safetv.
Tornado
preparation.
the
new
exemption
any local
Tornado
or
changes
owner/
from
2
oven must
at
a
operator
mechanical
building
be operated
food
facility
will
be informed
exhaust ventilation
and ltre
code requirements
that is
of the
in
a well-ventilated
operating
the exempt
operating
shall not
pertaining
area approved
equipment,
conditions.
be deemed
to
electrical
to
and
Page 37
TurboChef
Page 11.20
May
31,2071
Page
3 of3
This
exemption
revoked.
installation
at a specific location
are not limited to,
considerations
This
letter may
Tornado 2
of the
Oven
shall be in effect for
However,
of mechanical
problems
which
be used as
(NGCD6)
subject items
this exemption
exhaust ventilation
results in
a sanitation
of installation,
exceed
rapid
and may
the above limitations
evidence
cooking
not
be used for
period
a
shall not
of five
preclude
when operation
or safety
use, maintenance,
of the evaluation
ovens.
However, it is
advertising
years
from
the date of
this Department
of
violätion. These
cleaning
pose
or
a discernable health
from requiring
Tomado
the
problems
or other site
letter,
this
or Tornado 2
may include, but
or safety hazard.
of the TurboChef Model Tomado
not to
or
be construed as an
promotional
purposes.
or until
the
oven
specific
(NGC)
endorsement
or
Should (626)
Chief
Plan
you
430-ss60.
EHS
Check
have
any
geonu,
Program
questions
R.E.H.S.
or need
additional
information, please
ise
Noborio,
Environmental
Plan
Check
Health
Program
contact
R.E.H.S.
Specialist
me at
IV
PLANcHEcxr,¡u
ru^,
14É'
240
-oof
Page 38
TURBOCHE F T ECHN O LOGIES , INC.
Tornado 2 Oven Surface Temperatures
(271°C) for the duration of the test.
After 4-Hour Idle at 520°F/271°C (Values in °F/°C)
83/28 84/29 91/33 103/39 98/37 96/36 93/34
82/28 76/24 75/24 76/24 77/25 85/29 88/31
83/28 109/43 133/56 138/59 118/48 92/33 90/32
77/25 75/24 74/23 77/25 79/26 82/28 88/31
82/28 123/ 146/ 148/ 130/ 90/32 81/27
78/26 78/26 79/26 82/28 82/28 81/27 78/26
83/28 125/52 142/61 149/65 128/53 83/28 80/27
81/27 78/26 81/27 83/28 77/25 75/24 78/26
84/29 89/32 111/44 108/42 100/38 80/27 80/27
77/25 78/26 83/28 84/29 88/31 82/28 85/29
94/34 96/36 98/37 102/39 99/37 92/33 86/30
77/25 81/27 83/28 83/28 86/30 82/28 84/29
Page 12.1
TM
-
79/26 80/27 72/22 71/22 71/22 84/29 83/28
81/27 80/27 80/27 81/27 75/24 77/25 99/37
84/29 82/28 86/30 88/31 83/28 76/24 93/34
84/29 85/29 93/34 89/32 86/30 84/29 83/28
83/28 91/33 102/39 94/34 86/30 92/33 82/28
87/31 85/29 90/32 89/32 87/31 86/30 86/30
88/31 92/33 95/35 92/33 90/32 88/31 83/28
93/34 99/37 99/37 95/35
97/36 98/37 98/37 97/36
91/33 95/35 96/36 97/36
82/28 89/32 95/35 96/36
78/26 81/27 82/28 87/31
87/31 91/33 91/33 94/34
90/32
79/26 80/27 79/26
97/36
83/28 95/35 80/27
97/36
83/28 83/28 83/28
91/33
80/27 79/26 78/26
78/26
75/24 75/24 76/24
93/34
88/31 81/27 76/24
© 2012 TurboChef Technologies, Inc.
DOC-1374 / Rev B / November 2012
Page 1 of 2
Page 39
After 4-Hour Idle and 2 Hours of Cooking at 520°F/271°C (Values in °F/°C)
90/32 90/32 97/36 114/46 106/41 107/42 106/41
100/38 93/34 92/33 97/36 100/38 102/39 101/38
91/33 114/46 135/57 142/61 132/56 110/43 103/39
103/39 95/35 93/34 102/39 106/41 102/39 99/37
91/33 130/54 154/68 163/73 148/64 118/48 100/38
109/43 106/41 105/41 113/45 110/43 93/34 94/34
89/32 124/51 154/68 162/72 144/62 112/44 102/39
123/51 113/45 109/43 119/48 102/39 88/31 99/37
90/32 94/34 118/48 114/46 122/50 112/44 97/36
92/33 131/55 120/49 110/43 111/44 107/42 102/39
99/37 106/41 111/44 118/48 126/52 111/44 98/37
87/31 101/38 110/43 103/39 101/38 100/38 102/39
Page 12.2
91/33 92/33 88/31 88/31 87/31 99/37 97/36
93/34 93/34 93/34 97/36 88/31 87/31 106/41
96/36 96/36 101/38 102/39 96/36 88/31 104/40
95/35 97/36 104/40 103/39 97/36 96/36 95/35
95/35 103/39 111/44 107/42 100/38 105/41 95/35
93/34 99/37 101/38 103/39 102/39 102/39 100/38
97/36 104/40 108/42 110/43 114/46 110/43 102/39
98/37 105/41 108/42 106/41
104/40 103/39 105/41 108/42
98/37 103/39 109/43 110/43
90/32 103/39 112/44 113/45
90/32 93/34 96/36 100/38
97/36 100/38 100/38 104/40
101/38
111/44 106/41 105/41
109/43
120/49 118/48 111/44
109/43
125/52 114/46 121/49
106/41
106/41 103/39 104/40
88/31
90/32 90/32 92/33
105/41
98/37 93/34 86/30
© 2012 TurboChef Technologies, Inc.
DOC-1374 / Rev B / November 2012
Page 2 of 2