OutdoorYDK-50-6B1YDK-50-6B1YDK-50-6B1A2929GS010
Capacitor Dual3/30µF 400VAC3/30µF 400VAC3/35µF 400VAC5/40µF 400VAC
Dimension
IndoorW x H x Dmm815x285x1951035x322x2051080x298x2001080°ø298°ø200
This Installation section explains how and where to connect this new air conditioner. Please read make sure all accessories are included as shown below and read manual thoroughly. This Installation section is provided to assist the person knowledgeable in air conditioner installation and should not be installed by anybody who is not thoroughly familiar
with this type of installation. Please contact a professional installer if necessary.
ACCESSORIES SUPPLIED WITH THE UNIT:
9
0
AUTO
(24 Series Only)
Page 3
3
OPTIONAL ACCESSORIES
ACCESSORIES NOT SUPPLIED WITH THE UNIT :
NoPart NameQ'tyDescriptionRemark
1Drain Hose Extension1PVC, 20mm x 2M
2Tape Finish1PVC, W80mm x 25M
3Insulator Plate1PE, T8.0
4Putty1Gray, 80g
5Wall Cap1HIPS,
6Bracket Saddle2SCT, T0.824 Series Only
7Cable Tie2DACT-190A24 Series Only
1234
567
Page 4
4
INSTRUCTION OF INSTALLATION
Below is an overview for the connection of the Indoor unit to the Outdoor unit.
O VERVIEW
This appliance must be installed according to national power supply acquirement.
10cm (3.95in)
from ceiling
10cm (3.95in) from
side wall
30cm (11.8in) from
side wall
Wall
Wall Cap
At least 30cm
(11.8in) from unit
10
cm
more than
4 inch
Power
Source
more than
4 inch
Installation Plate
Circuit Breaker
10
cm
Adding additonal tubing will decrease efficiency.
Power cable
Maximum Height7M (21Ft)
Maximum Length15M (49Ft)
Standard Length: 25ft (7.6m)
Adding Refrigerant: 0.32 oz/ft (30g/m)
more than
27 inch
70
cm
Wrap with
Tape
cm
60
more than
24 inch
Copper
Tubing
(Not Supplied)
Ground Wire
(Not Supplied)
Drain
Hose
Page 5
5
INSTALLATION
1. Determine the type of wall (sheetrock, concrete, etc.)
and make sure it is strong enough to hold indoor unit.
Select an approximate position for the unit, taking the
required distances away from walls/AC outlet into
consideration.
INDOOR UNIT
• Do not install the unit in an area with direct sunlight, near
heat sources (radiator, etc.), or an area where leakage of
flammable gas may be expected.
• Select a position in the room, high on the wall, where the
whole room can be uniformly cooled.
• Select a location that can hold the weight of the unit and
where the copper tubing, drain hose and Indoor to Outdoor
Wire have the shortest distance to the Outdoor unit.
• Make sure the Indoor unit is installed at least 10cm (3.95in)
away from the top and left side wall and at least 30cm
(11.8in) from AC outlet and right side wall.
OUTDOOR UNIT
• Do not install the unit in an area near heat sources,
exhaust fans, or an area where leakage of flammable gas
may be expected.
• Do not install the unit in a humid, damp or uneven location.
• Select a location that is well ventilated .
• Leave enough room around the unit for air intake, exhaust
and possible maintenance.
2. Determine if the hole is to be made at the left or right
hole location.
3. Using drill with hole-cutting attachment or equivalent, cut
a hole 70mm (2.75") in diameter. The hole should be
made at a slight downward slant to the outdoor side.
Measure the thickness from the inside to outside edges
and cut a PVC pipe at a slight angle 1/4" shorter than the
thickness of the wall and insert pipe in wall.
4. For sheetrock, wooden or similar wall, measure down
from the ceiling using a level or tape measure and attach
the wall bracket to the wall using 4 screws. If you are not
able to line up the holes with the beams, use toggle
bolts. Make sure the wall bracket is even and flush
against the wall.
IndoorOutdoor
Cut at slight angle
CAUTION
• Before making hole, make sure there are no studs, pipes,
electrical wiring or conduit directly behind the area to be cut.
For Concrete, or similar type wall, make holes into the wall and insert concrete nails instead of screws.
INST ALLING THE INSTALLATION PLATE
To install the wall bracket, follow the procedures below. One hole is required for the tubing and may be either on the left or right side.
SELECTING A SITE:
• TAS-18/24
• TAS-15
• TAS-12
70(2.75)
Page 6
6
2. Make sure the drain hose and copper tubing are
wrapped with the rubber insulation. Using the tape,
wrap the indoor/outdoor wire, copper tubing and drain
hose together.
MOUNTING THE INDOOR UNIT
The Indoor unit must be mounted before connecting the indoor/outdoor wire, drain hose and copper tubing. To mount,
follow the procedures below:
1. The tubing can be extended in 4 directions as shown
below. No cutting is necessary for left/rear and
right/rear tubing connections. If using left or right tubing connections, remove the plastic area with a hacksaw so pipes can go through.
Left
Tubing
Right
Tubing
Left/Rear
Tubing
Right/Rear
Tubing
CAUTION:
• Make sure the Indoor unit’s AC cord is not connect-
ed to AC power when performing these procedures.
• Be sure to comply with local codes on running a wire
from the indoor to the outdoor unit.
• DO NOT LET THE INDOOR/OUTDOOR WIRE
COME IN DIRECT CONTACT WITH THE TUBING
OR HOSE!
3. Shape the tubing so it can easily go through the hole
in the wall. Push the indoor/outdoor wire, copper tubing and drain hose through the hole in the wall angling
downward. Situate the indoor unit on the wall bracket
by lifting the indoor unit slightly above the wall bracket
and then down so it is securely locked in place.
Installation Plate
Insert Putty
Drain Hose
CAUTION:
• When using the tube reamer, hold the tube downward and make sure no copper scraps fall into the tubing.
2. Make a flare at the end of the copper tube with a flare
tool.
Make sure the inside surface and edges are smooth
and the sides are uniform length.
1. Cut the copper tube extension to the desired length
with a tube cutter. It is highly recommended that 1 foot
is added to the requested length. After cutting, deburring may be necessary (see below diagram). Perform
this with a tube reamer.
BEFOREAFTER
PREPARING THE COPPER TUBING (NOT INCLUDED)
A copper tubing extension (not included) may need to be cut. If this is the case, it will also have to be deburred and
flared as shown below:
Flare tool
Flare nut
Connection
pipe
Page 7
7
1. Remove the flare nut stoppers from the inside unit.
Determine the location of the copper tubing and
where the bends will be. Gently bend the copper tubing, making sure to use big angles so no crimping will
occur. Try to do this on the first try as repeated bending may break or crimp the tubing.
2. Remove the plastic stoppers from the tubing. Connect
the large and small copper tubing to the respective
extension and rotate the flare nut with your finger until
a smooth match is made. Make sure the copper
extension has foam rubber (insulation) on it.
Flare Nutcoupler
CONNECTING THE COPPER TUBES
To connect the copper tubes, follow the procedures below:
NOTE:
When removing the flare nut stopper from the inside unit, confirm “Ping”, sounds because the mixed gas is charged in
the inside unit,
3. Once a smooth match is made, tighten the flare nut
using a wrench. Be very careful not to strip the
threads or flare nut. Repeat this process for the small
and large tubing. When tightening the flare nut, use
another wrench to securely hold the coupler from
twisting and possibly damaging the tubing.
4. Remove the flare nut stoppers from the outdoor unit’s
valves. Connect the larger copper tubing to the larger
valve on the outdoor unit. Connect the smaller copper
tubing to the smaller valve on the outdoor unit.
5. Perform a leak test on all copper tube connections. To
prevent heat loss and damage to walls from condensation, the copper tube connections coming from the
wall must be insulated. Do this by wrapping foam rubber or equivalent around the connection approximately 8mm thick so no copper tubing is exposed.
NOTES:
• As with all wiring and hookups on this unit, make sure
the AC plug on the indoor unit is unplugged.
• Be very careful not to strip the threads or flare nut.
• When insulating the connections, use foam rubber or
equivalent.
1. Connect the drain hose extension to the drain hose
coming from the indoor unit by loosing the clamp on
the extension using a phillips screwdriver, attaching
the hoses together and then tightening the clamp.
2. Run the drain hose, slanted downward, outside. If the
drain pipe is exposed
indoors, make sure it is
thoroughly insulated so
condensation does not
ruin walls or furniture or
come in contact with the
AC connection or extension. Also, do not crease
or form a trap in the tubing.
Insert Putty
Drain Hose
CONNECTING THE DRAIN HOSE
To connect the drain hose, follow the procedures below:
Page 8
CONNECTING THE CABLES
One electric power cable must be connected to the outdoor unit. The indoor unit is connected to outdoor unit through the
connection cable. To install the cables follow as below.
1. Open the connection cover on the indoor unit.
2. Open the SVC cover on the side of outdoor unit.
3. Connect the connection cable to terminal blocks of the indoor and outdoor unit as shown below.
- Must be connected with the same terminal number of indoor and outdoor unit.
- Be sure not to slip the cables out of terminal.
4. Connect the power cable and earth cable.
5. Reinstall the connection cover and the SVC cover.
6. Install the conduit kit. (The conduit kit is optional)
[Connetion Cable]
Indoor Unit
Terminal Block
1
2345
Circuit breaker
(Main Power)
1
Terminal Block
Outdoor Unit
CAUTION
• The supply voltage must be the same as the rated voltage of air conditioner.
• Prepare the power source for exclusive use with the air conditioner.
• A circuit breaker must be installed between the power source and the unit.
• This air conditioner must be installed according to the national electric rules.
INFORMATION
• The information for the cables of this air conditioner is as below.
ITEMSPECIFICATIONS
POWER CABLE
CONNECTION CABLE12K~24K BTU/h
CONDUIT SIZE0.875 inch (22.2mm)
12K~15K BTU/h3G AWG 14 SJT or SPT-3
18K~24K BTU/h3G AWG 12 SJT or SPT-3
1. After selection the appropriate site, position the outdoor unit and make sure the space around the outdoor unit.
(See overview instruction of installation)
2. Mount the outdoor unit on appropriate base using anchor bolts.
3. Install the CUSHION RUBBER provided to prevent vibration and noise.
4. If the outdoor unit is expose to direct sunlight or strong wind, install shield around the outdoor units.
❈ The outdoor unit must be installed on stable and rigid base.
ModelAB
TAS-12/15/18360580
TAS-24350550
After running the wire, hose and tubing outside, tape them up as shown below to insulate.
1. Tape the two copper tubes, drain hose (and the
electrical wiring if local codes permit) together with
the supplied tape. Make sure the electrical wiring
does not come in direct contact with the copper tubing or drain hose. Approximately 1 foot outside the
hole, let the drain hose out and separate from the
copper tubing and wiring.
Drain hose
3. Wrap the piping joints with the
insulator plate and fas
ten it with vinyl tape.
pipe
Plate
2. Begin wrapping from the point the tubing comes out of
the outdoor unit and continue to the hole in the wall.
Leave no gaps or breaks and cover the entire length
of the tubing. As you wrap, overlap the previous turn
by half the width of the tape.
4.
After wrapping the connection pipe with tape,
fasten it to the outside wall with saddles, etc.
Wall cap
Pipe
Tape
vinyl tape
Saddle
(Not supplied)
Page 10
10
AIR PURGING
Air and moisture remaining in the refrigerant system may create adverse conditions
as indicated below:
• pressure in the system rises
• operating current rises
• cooling efficiency drops
• moisture in the refrigerant circuit may freeze and block capillary tubing
• water may lead to corrosion of parts in the refrigerant system
Therefore, the indoor unit and tubing between the indoor and outdoor unit must
AIR PURGING WITH VACUUM PUMP (TEST RUN)
Remove the valve caps from the wide and narrow service valves on the
outdoor unit. Note that both narrow and wide tube service valves on the outdoor
unit are kept closed at this stage (shipping position).
Leak Test
(Save for reuse.)
CA UTION:
Be sure to use a manifold valve for air purging. If it is not avail able, use a stop valve for this purpose.
The “Hi” knob of the manifold valve must always be kept closed.
3. Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the
gauge reading reaches 150 P.S.I.G. Next, test for leaks with liquid soap.
CA UTION:
To avoid nitrogen entering the refrigerant system in a liquid
state, the top of the nitrogen gas cylinder must be higher than its bottom when you pressurize the system. Usually, the
cylinder is used in a vertical standing position.
4. Do a leak test of all joints of the tubing (both indoor and outdoor) and both wide and narrow service valves. Bubbles
indicate a leak. Be sure to wipe off the soap with a clean cloth.
5. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at
the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
LoHi
Pressure
Gauge
Manifold Valve
Outdoor Unit
Indoor Unit
Charge Hose
Nitrogen Gas
Cylinder
(Vertical
Position)
1. Apply the putty to any area
on the outside hole that air
or rain can get into.
Apply Putty
Here
Tubing
2. After applying putty,
insert the wall Cap at
Indoor side
and Outdoor side.
Insert Putty
Wall Cap
(For DS-110R)
Drain Hose
APPLYING PUTTY AND INSERTING THE WALL CAP
After running the wires and tubing outside, putty should be inserted around the opening on the outside to protect against
rain, wind, etc. To apply putty, see below:
Indoor sideWall
Outdoor side
be leak tested and evacuated to remove any noncondesables and moisture from
the system.
Confirm each tube (narrow and wide tubes) between the indoor and outdoor units
has been properly connected and all wiring for the test run has been completed.
1. With the service valves on the outdoor unit remaining closed, remove the
threaded cover on the wide tube service port.
2. Attach a manifold valve (with pressure gauge) and dry nitro gen gas cylinder
to this service port with charge hoses.
Page 11
11
Evacuation
1. Attach the charge hose end described in the leak test
area to a vacuum pump to evacuate the tubing and
indoor unit. Confirm the Lo knob of the manifold valve is
open. Then, run the vacuum pump. The operation time
for evacuation varies with the tubing length and capacity
of the pump. The following table shows the amount of
time for evacuation:
2. When the desired vacuum is reached, close the Lo knob
of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a hex wrench, turn the narrow tube service valve
stem counter-clockwise to fully open the valve.
2. Turn the wide tube service valve stem counter-clockwise
to fully open the valve.
CA UTION:
To avoid gas from leaking when removing the charge hose,
make sure the wide tube service valve is fully open and
turned all the way out.
3. Loosen the charge hose connected to the wide tube ser-
vice port slightly to release the pressure, then remove the
hose.
4. Replace the threaded cover on the wide tube service port
and fasten it securely. This process is very important to
prevent gas from leaking from the system.
5. Replace the valve caps at both wide and narrow service
valves and fasten them securely.
This completes air purging with a vacuum pump. The air
conditioner is now ready to test run..
LoHi
Pressure
Gauge
Manifold Valve
Outdoor Unit
Indoor Unit
Charge Hose
Vacuum
Pump
If tubing length is less than
33 ft. (10 m)
10 min. or more
If tubing length is longer than
33 ft. (10 m)
15 min. or more
Required time for evacuation when 30 gal/h vacuum
pump is used
Page 12
12
TEST RUN
Check that all tubing and wiring have been completed correctly. Check again that the wide and narrow tube service
valves are fully opened. Turn on the power and run the system.
Service Valve Construction
• Valve Position Closed
The valve systems of both the wide and narrow tubes are turned all the way in. The unit is shipped from the factory in
this position and it is also used for Pump Down and Air Purging.
• Valve Position Fully Open
The valve stems of both the wide and narrow tubes are turned all the way out. This is normal operating and Test Run
position.
• Valve Position Half Open
With the narrow tube valve stem is turned to the halfway-down position. This position is used for pressure measurement and gas charging.
CAUTION:
When opening or closing the service valve stem, be sure to use a hex wrench.
PUMP DOWN
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the wide tube service valve.
2. Open the wide tube service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the narrow tube service valve (all the way in).
4. Turn on the unit s operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5 kg/cm2 (14.2 to 7.1 psi), fully close the wide tube valve stem
and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been
collected in the outdoor unit.
Page 13
13
3. REFRIGERANT CYCLE DIA GRAM
Page 14
14
4. WIRING DIA GRAM
• Indoor Unit
◆ TAS-12/18/24◆ TAS-15
• Outdoor Unit
◆ TAS-12/15/18◆ TAS-24
Page 15
15
5. CONTROL BLOCK DIA GRAM
Page 16
16
6. TROUBLE SHOOTING
Outdoor unit does
not run?
Does
the compressor run
normally?
Indoor unit does
not run
Check the failure
code according to
the self diagnostic
Is the unit
display
mormal?
check the failure
code according to
the self-diagonostic
Normal
check the
connecting
point of
magnetic
contactor
YES
YES
YES
YES
NO
NO
YES
Is the power
applied to the
unit
Is the
power normal?
check the voltage between
L & N of terminal
block
press the power ON/OFF
button on remote controller
Does the
beeper beep two
times?
Is the display
all off?
• Check the connector on display
PCB connected to control PCB
• Check the display PCB itself
Check power supply mains
or interconnection wires
Check the wiring of indoor
Is the
switch position
on switch pannel at
"Remote"
Does
control PCB
status LED repeat one
second "on and
off"?
• control PCB fault
• Micom or reset
IC fault
• Check the remote signal receiver
• Check the connection between signal
receiver and control PCB
Place the switch
position to the
"Remote" and then
Check it once
more
YES
NO
YES
NO
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
NO
Is the
unit display
normal?
Trouble
Page 17
17
Note 1)
1 Neither indoor unit nor outdoor unit runs.
Check the following points first. (There are f ollo wing case in normal operation)
a. Is the timer mode set the "timer ON".
b. Is the timer mode set the "timer-OFF" and the time had passed?
2 Neither outdoor fan nor compressor runs while indoor fan runs.
Check following points first. (There are f ollo wing cases in normal operation)
a. Is the temperature set point suitable?
b. Has the 3 minutes time guard f or compressor operated?
1. Error Code I - ON LED blinking 3 times at Emergency Mode
1 When the compressor do not run.
i) Check the voltage between and of terminal block.
(Indoor Unit, Outdoor Unit)
ii) Check connecting wire of indoor unit and outdoor unit.
iii)Check relay RL1 on pow er P.C.B (outdoor PCB)
2 Check fixing of indoor coil thermistor.
3 Check the GAS LEAKAGE of the pipe.
2. Error Code 2 - ON LED blinking
1 Check the sensor and its circuit.
2 It occurs when sensor is open or short.
3. Error Code 3 – TIMER LED blinking
1 Check the Indoor Fan Motor.
2 Check the RPM feedback circuit.
③ Indoor Fan Motor does not work for 5 seconds.
Y
L
Self-Diagnostic Function
Page 18
18
Confirm following statement.
When the unit operate normally , Sometimes the outdoor unit and indoor unit cannot operate.
1 Check the function select switch. Is it timer mode?
2 The function select switch locate the sleep mode and is the setting time over?
3 Is the setting mode DEHUMIDIFIER mode?
The power is applied to the unit
Check the voltge between and
of terminal block
Y
L
Check the
Breaker or Fuse
Self Diagnostic
function is ON
Check according to
self Diagnostic function
Control P.C.B defect
Check the indoor unit display
is the display all off?
Press the ON/OFF switch of
Remote Control
Is the indoor unit display all off?
Pull out the power plug
and then insert the power plug
after 5 second
Control P.C.B is normal
Recheck from the beginning
Rating voltage more than 90%
Rating voltage
under 90%
NoNo
No
Yes
Yes
Neither Indoor Unit nor Outdoor Unit Runs
Page 19
Outdoor Unit Runs but Indoor Fan Do Not Run
Check rotation of indoor fan
Rotate indoor fan by hand
YES
Check input Voltage (Vs) of Fan
Motor connector at power P.C.B
DC POWER OK
Check the winding resistance of
Indoor unit fan motor
Normal
Check the Vsp of indoor PCB
NO
DC 30V(Vs),
DC 15V(Vc)
Fail
Open or short
❈ Vsp=0~5V DC
Check the F an Motor
bearing and fan
Check the power P.C.B.
(outdoor PCB)
The circuit for DC POWER
Change of fan motor
Check the connecting wire of
indoor fan motor
Run again
Check the starting of indoor fan motor
Run again
No
Normal
19
Page 20
20
Confirm following statement.
When the unit operate normally , Sometimes the outdoor unit and indoor unit cannot operate.
1 Is the setting temperature proper?
2 Is the unit during 3min. Time delay of compressor.
3 During frost prevention of lndoor unit.
The DC power is SMPS power source. DC Power Supply in circuit needs 30V , 15V and 12V.
+12V is used for Compressor Driving Relay, Buzzer Driving Swing and Swing Motor.
DC 30V is used for Indoor F an Motor P o wer and DC 15V(Vc) is used f or Motor Drive .
(Refer to PCB Circuit Diagram : Outdoor Unit)
Oscillator(2)
19
OSC
CC13
104
5V
8M
20
VDD-10%
V
SS+10%
Fig 2-1
DESCRIPTION
Oscillatory Frequency drive Micom, it is made up 8MHz resonator oscillatory Freqency.
Ocillatory wave is as follo wing Fig 2-1.
Page 37
Sensor(3)
ROOM SENSOR
I/D SENSOR
CN3
R7R6330
330
CC5
103
103
CC6
24
25
MICOM
R10
12.7KF
R11
12.7KF
Room temperature and Evaporator temperature Sensor Input
DESCRIPTION
Temperature
Number 24, 25 of Micom is Terminal of A/D
convertor Input.
Room temperature and Evaporator temperature is
sensing by change of Thermister Resistance,
Micom is put in 5V by ratio between R10 (12.7KΩ)
and R11 (12.7KΩ).
Relation between temperature and voltage is
following Table 3-1.
CC5, 6 is Noise filter.
Voltage (V)
(°C)
No. 1No. 3
-51.1271.127
0 1.3781.378
5 1.6501.650
10 1.9361.936
152.2282.228
Table 3-1
Indoor Fan Motor Control(4)
DESCRIPTION
Indoor Fan motor pow er is DC30V(Vs)
Indoor Fan motor RPM is controled by Vsp(0~5V)
Vsp control pulse OUTPUT is Pin6, IC1
PIN31 is Indoor Fan motor RPM f eed back input.
35
Page 38
36
DESCRIPTION
Signal from Remote Controller put in only Control Data Signal at Micom Terminal of Number 33, which is gotten
fid of Carrier (38KHz) from Receive Module. Signal Wa ve repeat third as f ollo wing Fig 5-1.
But in Secondary Wave Custom Code is Re v ersed F ace .
LEADER CODE
CUSTOM
CODE
DATA
CODE
CHECK
SUM
TAILER
9ms4.5ms16bit16bit24bit8bit
Fig 5-1
Fig 5-2
BIT STRUCTURE
Remote Controller(5)
0.56ms0.56ms1.69ms
1.12ms2.25ms
bit 0bit 1
Selecting Mode(6)
(SELECT S/W INPUT, OUTPUT)
MICOM
13
R25
1K
RA2
5V
CA2
F4104Z
P2
MODE
SELECT
PUSH S/W
DESCRIPTION
There are Mode according to SW position as
following Table 6-1.
According as port of fixed Micom is Low, the unit is
operating as following Table 6-1.
Table 6-1
POSITION MODE
OPENREMOCON
GNDEMERGENCY
Page 39
37
DESCRIPTION
MICOM Po wer is supplied 5V at Number 42 using VDD, Number 19, 20 Vsing Oscillator, CC10 is noise filter.
Micom Power Supply(7)
VDD 42
CE3
10µF
16V
CC3
104
CC10
104
+
5V
41
40
39
22
21
19
OSC
8MHz
20
VSS
MICOM
Page 40
38
DESCRIPTION
V oltage less than about 0.8V put in Micom Terminal of Number 18 and then Micom reset. Reset IC detect
Po wer ON and Voltage less than 4.25V , and then send Reset Signal.
Reset(8)
R385.6K
1K R35
18
CC4
CE4
4.7uF/50V
IC5
7042P
10.3
MICOM
4.25V
H
L
t
t
POWER
ON
Vcc (+5V)
DELAY TIME
FOR POWER ON
RESET
Page 41
39
DESCRIPTION
Micom 34 Terminal put out Buzzer Dr iving Pulse,
its output is driving Buzzer through Buffer .
Ocillatory Frequency of buzzer is selected by
internal Micom.
This unit is setting at 4KHz.
VCC
12V
KID 65004
MICOM
34
611
R37
1K
BZ1
Buzzer Driving(10)
DESCRIPTION
* When power source is put at fist, Funtion selection input is recognized.
And when the unit is running the microcomputer ignore variation of funtion selection input.
• JS3: open (°C), short (°F)
• R21, R23: Indoot Fan Motor RPM select option with A/D signal.
Function Selecting(9)
Page 42
40
DESCRIPTION
There are one Stepping Motor for Flap (up and down) and it is used 4 face Drive Method.
It is driving as following Fig 12-1. (Ring Count Method of 8 Status)
Ø 4
Ø 3
Ø 2
Ø 1
B
+
6
5
4
3
2
1
12V
IC3
KID65004
CN5
1
MICOM
2
3
4
M1
FOR SWING
Fig 12-1
(Normal Rotating)(Reversed Rotating)
Stepping Motor Driving(12)
Ø 4
Ø 3
Ø 2
Ø 1
Page 43
ERROR
No
ERROR
No
ERROR
No
No
No
No
Yes
Select ON/OFF button
Select Mode button
Select F AN SPEEDbutton
Select F AN DIR. b utton
Po wer Supply
TEST START
Po wer supply again
Check the Follo wing
BATTERY SPRING
MICOM
PCB
LCD
Is Display at the
beginning ON?
Is Display at the
beginning ON?
Is it normal?
Is it normal?
Is it normal?
• REMOTE CONTROLLER ASSMBLY FUNCTIONAL TEST METHOD
41
ERROR
No
ERROR
No
(Whenever y ou selectted Temp.
Button, it is changed by 1°C (18~32°C)
Buzzer Driving
Remocon Input
Comp Relay Driving
Zero Crosing Detect
Function S/W
Temperature
Sensor Input
LED Driving
Emergency
Mode
Function
S/W
Reset Curcuit
Oscillation
8. KEY COMPONENTS OF ELECTRONIC CIRCUIT
Page 46
(2) U2, 4 (KID65004) DARLINGTON ARRAYS
IN1 116 OUT 1
IN2 215 OUT 2
IN 3 314 OUT 3
IN 4 413 OUT 4
IN5 512 OUT 5
IN6 611 OUT 6
IN7 710 OUT 7
GND 89 COMMON FREE
WHEELING DIODES
COMMON
10.5KΩ
7.2KΩ
3KΩ
OUTPUT
GND
INPUT
100K500
100
100
0.3
10K
6K
500
1K
5K
28K
6K
30pF
2K
5K
200
240
1.4
K
2.7
K
3.3
K
0.19K
INPUT
OUTPUT
GND
SCHEMATIC DIAGRAM
1
2
3
Fin 2 is ground
for Cose 221A.
Case is ground
for Case 1.
10K
INPUT
GND
10K
300
36K
64K
520
26K
60K
29K
20K
20K
40
pF
50K
50 200
300
200
100
16K
210
012
OUTPUT
KID65004AP
(Equivalent Circuit)
(Top View)
(3) U8 (KIA7805P) : VOLTAGE REGULATOR (5VDC)
Pin 1. INPUT
2. GROUND
3. OUTPUT
(4) U7 (KIA7812P) : VOLTAGE REGULATOR (12VDC)
Pin 1. INPUT
2. GROUND
3. OUTPUT
44
(Equivalent Ciircuit)
Page 47
45
(5) U9 (KIA7042P) : RESET IC
KIA70
42P
OUTLINE
INPUT
GROUND
OUTPUT
VCC
1
3
2
OUT
GND
Page 48
46
1
INDOOR UNIT
PROCEDURES PHOTOS
1. Stop the Air conditioner and disconnect the power cord from the wall
outlet.
2. Removing the Insert Grille and Frame Grille. (Fig 1~2)
1 Draw up the Insert Grille and remove it.
2 Loosen one screw for fixing the Cov er Ter-Block.
3 Loosen two screw at the Fr ame Grille.
4 Remove the F rame Grille.
3. Removing the Control Box. (Fig 3)
1 Remove room and coil thermistors.
2 Disconnect the fan motor lead wire from connection at the
Control PCB.
3 Disconnect the stepping motor lead wire from connection at the
Control PCB.
4 Remove the select switch from connection at the Control PCB.
5 Loosen a screw for fixing ground wire.
6 Remove the Control Box
4. Removing the Drain Pan. (Fig 4)
1 Disconnect the Body drain hole. (left and right Body)
2 Disconnect three hook and remove the Drain Pan.
5. Removing the Indoor Evaporator . (Fig 5~6)
1 Remove one screw f or fixing indoor Ev aporator at the Body.
2 Remove the hook for fixing Brac k et Pipe at the back of Body.
3 Remove Indoor Evaporator.
6. Removing the Cross Flow F an. (Fig 7)
1 Remove set screw f or fixing Motor shaft.
2 Remove Cross Flow Fan.
7. Remove Motor IDU and Bearing Plastic.
9. DISASSEMBLY INSTRUCTIONS
Fig 1
Fig 3
Fig 4
Fig 5
Fig 6
◆TAS-12
Fig 2
Fig 7
Page 49
47
◆TAS-15
PROCEDURES PHOTOS
1. Stop the Air conditioner and disconnect the power cord from the wall
outlet.
2. Removing the Insert Grille and Frame.
! Loosen three screws for fixing the the Insert Grille and Frame.
(Pull out the frame cap before loosening three screws) (Fig 1)
@ Loosen three screws at the Drain Pan.
# Remove the Insert Grille and Frame.
3. Removing the Control Box.
After doing above procedures:
! Disconnect indoor room and coil thermistors. (Fig 3)
@ Disconnect the fan motor lead wire from connection at the main
PCB. (Fig 3)
# Disconnect the swing motor connection wire.
$ Loosen a screw for fixing ground wire.
% Loosen two screws for fixing the body.
4. Removing the Drain Pan.
After doing above procedures:
! Loosen a screw for fixing body. (Fig 4)
@ Unhook the right part of Drain Pan.
5. Removing the Indoor Coil.
After doing above procedures:
! Loosen four screws for fixing indoor coil at left and right side. (Fig 5)
@ Loosen a screw for fixing the brack et tube at the back side. (Fig 6)
# Remove the indoor coil. (Fig. 6-1)
6. Removing the fan motor .
After doing above procedures:
! Loosen two screws for fixing holder moter at left and right side.
(Fig 7, 8)
@ Loosen a screw for fixing fan motor and b low er .
# Renove the fan motor.
Fig 2
Fig 1
Fig 3
Fig 4
Fig 5
Fig 6
Fig 6-1
Page 50
48
PROCEDURES PHOTOS
7. Removing the blower.
After doing above procedures:
! Loosen a screw for fixing holder bearing.
@ Remove the blow er .
Fig 8
Fig 7
Page 51
49
PROCEDURES PHOTOS
1. Stop the operation of the Air conditioner and disconnect the power cord
from the wall outlet.
2. Removing the Insert Grille and Frame Grille. (Fig 1~2)
1 Draw up the Insert Grille and remove it.
2 Loosen the screws fixed at the Cov er Ter-Block.
3 Loosen two screw at the Fr ame Grille.
4 Remove the F rame Grille.
3. Removing the Control Box. (Fig 3)
1 Remove room and coil thermistors.
2 Disconnect the fan motor lead wire from connection at the
Control PCB.
3 Disconnect the stepping motor lead wire from connection at the
Control PCB.
4 Remove the select switch from connection at the Control PCB.
5 Loosen the screw fixed at the ground wire.
6 Remove the Control Box
4. Removing the Drain Pan. (Fig 4)
1 Disconnect the Body drain hole. (left and right Body)
2 Disconnect three hooks and remove the Drain Pan.
5. Removing the Indoor Evaporator . (Fig 5~6)
1 Remove the hook fixed at the Plate mounting of the back of Body.
2 Remove Indoor Evaporator.
6. Removing the Cross Flow F an. (Fig 7)
1 Remove the set screw fix ed at the Motor shaft.
2 Remove the Cross Flow F an.
7. Remove the Motor IDU and the Bearing Plastic.
Fig 1
Fig 3
Fig 4
Fig 5
Fig 6
◆T AS-18/24
Fig 2
Fig 7
Page 52
50
2
OUTDOOR UNIT
◆TAS-12/15/18
PROCEDURES PHOTOS
1.Stop the operation of the air conditioner and dis connect the wire from in
door unit to out door unit.
2. Disassemble the case. (Fig 1~2)
1 Remove the Top Panel.
2Remove the Side Cabinet.
3Remove the Front Cabinet.
3. Removing the Propeller Fan. (Fig 3)
1Loosen the screw fixed at the motor bracket.
2Remove the Plain Washer .
3Remove the Propeller Fan.
4. Remove the panel control. (Fig 4)
1Disconnect the wire at the control panel.
2Loosen the screw fixed at the panel control.
3Remove the parts on panel control.
5. Remove the partition panel. (Fig 5)
1Loosen four screws at the bracket motor.
2Disconnect the wire at the control panel.
6. Removing the Over load Protector . (Fig 6)
1Remove the cocondenser
2Loosen three volts at compressor.
3Remove the compressor.
Fig 1
Fig 2
Fig 3
Fig 5
Fig 4
Fig 6
Page 53
51
◆TAS-24
PROCEDURES PHOTOS
1.Stop the operation of the air conditioner and disconnect the wire from in
door unit to out door unit.
2. Disassemble the case. (Fig 1~2)
1 Remove the Top Panel.
2Remove the Front Cabinet.
3Remove the Side Cabinet and Bac k Cabinet.
3. Removing the Propeller Fan. (Fig 3)
1Loosen the screw fixed at the motor bracket.
2Remove the Plain Washer .
3Remove the Propeller Fan.
4. Removing the panel control. (Fig 4)
1Disconnect the wire at the control panel.
2Loosen the screw at the panel control.
3Remove the parts on the panel control.
5. Removing the vaccum pump .
6. Remove the partition panel. (Fig 5)
1Loosen four screws at the bracket motor.
2Disconnect the wire at the control panel.
7. Removing the Over load Protector . (Fig 6)
1Remove the cocondenser
2Loosen three volts at the compressor.
3Remove the compressor.