Turbo Air TAS-09NH, TAS-12NH, TAS-18NH, TAS-24NH Service Manual

Page 1
1
Service mannal
Room airconditioner
Split Wall-Mounted Type
NOTE:
Before servicing the unit, please first read the service
manual and then contact with your service center if
meet problem
Page 2
2
Table of Contents
1Summary
………………………………………………………………………………………………………………3
2Model explaining
…………………………………………………………………………………………………….5
3Installation
……………………………………………………………………………………………………………..4
4Exploded view and part list
………………………………………………………………………………………..8
5Operation principle
………………………………………………………………………………………………….8
6Parameter
………………………………………………………………………………………………………………9
7Wiring diagrams
……………………………………………………………………………………………………...13
8PCB principle chart
……………………………………………………………………………………………….....17
9PCB function …………………………………………………………………………………......
17
10Troubleshooting………………………………………………………………………………....
30
Page 3
3
1. Summary
model
indoor unit 790×270×180 790×270×180 940×270×180 1080×335×245 Net
Dimension
outdoor unit 700×225×500 795×255×510 795×255×510 870×310×700
3. Attention of installation
3.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be
followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
3.2 Warning
Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
TAS-09NH
TAS-12NH
TAS-18NH
TAS-24NH
Page 4
4
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a windows is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane
arrives.
There is risk of property damage, failure of product, or electric shock.
Page 5
5
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or
inefficient operation.
Operational
Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a
precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other object through air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Page 6
6
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and mew batteries or different types of
batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote of the batteries
have leaked.
The chemical in batteries could cause burns or other health hazards.
3.3 Installation details
Wrench torque sheet for installation
Outside diameter Torque
mm inch Kg.m
φ6.35 1/4 1.8
φ9.52 3/8 4.2
φ12.7 1/2 5.5
φ15.88 5/8 6.6
φ19.05 3/4 6.6
Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit 7K 9K 12K 18K 24K 28K
mm2 1.0 1.0 1.5 2.5 2.5 2.5
Pipe length and the elevation
Standard length
Max. Max. Additional
Capacity Pipe size
(m) Elevation Elevation refrigerant
Btu/h GAS LIQUID
B (m) A (m) (g/m)
9K-12K 3/8’’ (φ9.52) 1/4’’ (φ6.35) 3.5 5 10 30
18K-22K 1/2’’ (φ12.7) 1/4’’ (φ6.35) 4 10 15 30
24K-28K 5/8’’ (φ15.88) 3/8’’ (φ9.52) 5 15 20 65
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Lo Hi
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
8
Caution:Capacity is base on standard length and maximum allowance length is base of reliability.Oil trap should be install per 5-7 meters.
4
Indoor unit and outdoor unit explosion diagram and spare parts list(see explosion diagram file)
5. Refrigerant cycle diagram working principle
Page 21
19
9. PCB function:
NOTE: Ts is the set temperature, Tr is indoor room temperature, TP1 is indoor coil pipe temperature, TP2 is outdoor
coil pipe temperature.
Display panel
[1]only two LED
running lamp(green)power on light, flash one time/ one second during anti cooled wind.
timer lamp(yellow)only light at timer state.
[2]eleven LED
running lamp(green):power on light, flash one time/ one second during anti cooled wind.
temperature lamp(green)1631 set temp. and room temp. display, light is set temp. flash is set temp.
[3]two LED and two 8LED
running lamp(green):power on light, flash one time/ one second during anti cooled wind.
timer lamp(yellow):only light at timer state.
running
Page 22
20
8LED display set temp., also it can display timer time and failure code.
[4]LED multi-colour panel
according to display mode: dehumidification, cooling, ventilation, heating, auto, sleep, fan speed, swing, timer, indoor
fan running.
Cooling
Start up the compressor: when the room temperature is more than Ts+1, compressor start-up
Shut down the compressor: when the room temperature is less than or equal to the set temperature Ts-1℃,
compressor shutdown
When the temperature of coil pipe of the indoor units is less than or equal to 1 for one minute and the
compressor has continuous run for more than ten minutes, the compressor and outdoor blower fan shut down
through the electric control board and the indoor blower fan is running at low speed.
When the temperature of coil pipe of the indoor units is more than or equal to 7℃ and the compressor has
shutdown for more than three minutes, the compressor and outdoor blower fan start to run and the indoor blower
fan is running at set speed.
When the temperature of coil pipe of the indoor units is equal to or less than -10 for three minutes in the
compressor has continuous run for three minutes, the compressor, indoor and outdoor blower fans and swinging
wind shut down. Restart up six minutes later; if the above situations appear again within six minutes, all the
outputs are shut down through the electric control board and display failure.
When you press turbo button of remote, the air conditioner enter turbo running, compressor and outdoor blower
fan turn on all along, indoor blower fan run at high speed, turbo indication is light.
After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the temperature
of indoor coil pips is more than 25 in the continuous 20 minutes. The controller will automatically shut down if the temperature of indoor coil pips is more than 25 in another continuous 20 minutes, that is the abnormality
protection of outdoor units and the indicator lamp keeps its former state of flashing. If the temperature of indoor coil pips is less than 25 in the second 20 minutes or the compressor shuts down, the electric control board will
store to the normal display and the time is restarted when starting up the compressor next time.
Page 23
21
1° C
7° C
Tr
-10° C
compresso
r
outdoor blower fan
door
blower fan
compresso
r
door
blower fan
Tr
Heating (only applicable to heat pump units)
Start up the compressor: when the room temperature is less than Ts-1, compressor start-up
Shut down the compressor: when the room temperature is more than or equal to the set temperature Ts+3℃,
compressor shutdown
The electric heating start-up in the heating mode shall meet the following conditions: start up the compressor
Page 24
22
and indoor blower fan none defrost TP1< 49℃ ④Tr ≤20℃.
The electric heating shutdown in the heating mode shall meet one of the following conditions: shutdown indoor blower fan Tr 23℃ ③ TP1≥50℃.
In the heating mode, the indoor flower fan can be set as high/ medium/ low /automatic running mode by remote
control however the anti cool air function is prior. In the heating mode, the anti cool air control function is to
control shutdown of the indoor blower fan by detecting the temperature of coil pipe of evaporator so as to attain
the purpose of preventing cold air from blowing.
For the waste heat emission function in the heating mode, in principle, the indoor blower fan shall be on for
fifteen seconds after the electric heating is closed.
When the temperature of coil pipe of indoor units is more than or equal to 56℃, the outdoor blower fan shuts
down and it enters the overload protection; when the temperature of coil pipe of indoor units is less than or equal to 52, the outdoor blower fan starts up and it exit the overload protection.
When the temperature of coil pipe of indoor units rises to 63, the compressor and outdoor blower fan are closed
and two minutes later, the change valve is closed. The indoor blower fan is running at the set speed. Restart up six
minutes later; if the above situations appear again within ten minutes, all the outputs are shut down through the
electric control board and display failure.
When you press turbo button of remote, the air conditioner enter turbo running, compressor ,outdoor blower fan
and four-way valve turn on all along, indoor blower fan run at high speed and it must meet start condition, turbo
indication is light.
After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the temperature of indoor coil pips is less than 30 (heating) in the continuous 20 minutes. The controller will automatically shut down if the temperature of indoor coil pips is less than 30 in another continuous 20 minutes, that is the
abnormality protection of outdoor units and the indicator lamp keeps its former state of flashing.
Page 25
23
+
3
-
1
COMPRESSOR
start-up
start-up
outdoor blower fan
start-up start-up
start-up
start-up
blower fa
n
lower
speed
low speed
low speed
lower speed
low speed
start-up
2
MIN
2
MIN
start-up
start-up
over 6 MIN
four-way valve
Tr
Tr
Page 26
24
compresso
r
door
blower fan
Tr
36
Defrost (only applicable to the heating mode)
1. the intelligent defrost
In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor coil
pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not according to
conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically enters defrosting
process. When defrosting, close the indoor and outdoor blower fan and four-way valve.
2. Outdoor PCB for defrost.
In the heating mode, the unit defrost by outdoor control board unit start defrost shall all meet the following conditions a、compressor continuous running over 7 minutes; b、defrost relay shut off;(-5℃) c、compressor cumulate running time over 50 minutes.;
first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.
Defrost time(minute) Next defrost interval time(minute)
15 30
10--15 40
7--10 60
3--7 70
3 80 (2)end defrost condition(meet one of follows) a、defrost time have fifteen minutes. b、defrost relay turn on;(>8℃)
cpress ON/OFF key in defrost process.
3. Outdoor sensor for defrost
Page 27
25
unit start defrost shall meet one of the following conditions
a. compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the
temperature of coil pipe of the outdoor units is equal to or less than -15℃ for one minutes (Tp2≤-15℃).
b. compressor cumulate running time over 40 minutes and it continuous running over 3 minutes, the
temperature of coil pipe of the outdoor units is equal to or less than -5℃ for one minutes (Tp2≤-15℃).
c. Air conditioner first power on or it wait over 30 minutes ,the temperature of coil pipe of the outdoor units is
equal to or less than -2℃ (Tp
2
≤-15℃)
end defrost condition(meet one of follows)
a. the temperature of coil pipe of the outdoor units is more than 15℃ (Tp
2
≥-15℃).
b. defrost time have fifteen minutes.
compresso
r
outdoor
blower fan
door
blower fan
TP2
Tr
Page 28
26
compresso
r
outdoor blower fan
door
blower fan
TP2
Tr
Tr
compresso
r
outdoor blower fan
door
blower fan
TP2
Page 29
27
outdoor blower fan
door
blower fan
TP2
defrost time over 15 MIN or TP2 >15° C
Tr
compresso
r
Sequence chart in defrosting mode
end defrost
start-up
shutdown start-up
shutdown
start-up
start-up
start-up
shutdown
defrost
our-way
valve
door
blower fa
n
start-up
start-up
start-up
start-up
shutdown
shutdown
outdoor blower fan
compressor
start defrost
Dehumidification
Dehumidification running is to eliminate the water vapor in the air by using the cool circulating capacity, but the
dehumidification will not decrease the indoor temperature in great deal. The air conditioner automatically repeats on
and off circulation according the room temperature, which is shown in the following figure.
Page 30
28
indoor
blower fan
°C
°C
door
blower fa
n
Tr
shutdown
shutdown shutdown shutdown shutdown
shutdown
shutdownshutdownshutdownshutdown
low speed
Tr≤10℃
shutdown
start-up
start-up
start-up
start-up start-up
start-up
start-up
start-up
forbid dehumidify
In the dehumidification mode, the indoor fan is running at the low speed for twenty seconds at first, then it select
working mode.
Ventilation working mode (only applicable to single cooling unit)
In the ventilation mode.When ventilating, the compressor, outdoor blower fan, four-way valve and electric heating are
all closed and the indoor blower fan is running at the set speed.
compresso
r
outdoor blower fan
door
blower fan
Tr
Automatic mode
Conditions for entering the automatic running mode are: After power-up for the first time, start up and select the
automatic operating mode of remote or press emergency key, the working mode depends on Tr and if the working
Page 31
29
mode had set , it doesn’t change by Tr and the default set temperature is 25 ℃.
2
5
T
r
2
1
26° C
mode
Time on and time off
When the time on or time off is used, the clock of remote controller shall be corresponding to the current clock and the
timing times is less than or equal to 24 hours, when the timing time is reached, unit will start-up or shutdown.
Sleep function
When the sleep key is press, air conditionerenter sleep state, indoorblower fan running at low speed, only sleep
indication display.
Emergency key function
There is a forcible execution key on the panel of indoor units and the air conditioner can run by pressing the key when
the remote control is out of work or missing.
When pressing down the forcible execution key, then power up and enter the self-check program.
Failure display
LED lamp display
code explain code explain
failure
The reason of fault and solution
DF
display at
on state
flicker 1/1
SEC
defrost
indication
Normal, the defrost state is removed, it will return to normal condition automatically
display at
off state
flicker 1/3
SEC
anti cold wind
1 Normal (during heating mode ) 2It will be removed when the coil pipe temperature
sensor reaches certain temperature.
E2 display at flicker 1/1 display room temp. 1、Check whether the resistance of the sensor is normal
Page 32
30
off state SEC at on/off
state
sensor fault
(the resistance is 5КΩ in the normal temperature 25 )℃ , when it is abnormal the sensor should be
replaced.
2、Check whether there is short circuit or open circuit in
the wire of the sensor, and whether the plug is
connected well, whether there is welding off or
rosin joint on the electric control board, if there is
any, it should be repaired.
3When the 1 and 2 are both normal, then the
components or integrated circuit is damaged, the
electric control board should be replaced.
E3
display at
off state
flicker 3/5
SEC
display
at on/off
state
coil temp.
sensor fault
1、Check whether the resistance of the sensor is normal
(the resistance is 5КΩ in the normal temperature 25 )℃ , when it is abnormal the sensor should be
replaced.
2、Check whether there is short circuit or open circuit in
the wire of the sensor, and whether the plug is
connected well, whether there is welding off or
rosin joint on the electric control board, if there is
any, it should be repaired.
3 When the 1 and 2 are both normal, then the
components or integrated circuit is damaged, the
electric control board should be replaced.
E4
display at
on/off
state
flicker 4/6
SEC
display
at off
state
outdoor unit
abnormal
1 Check whether the winding resistance and
operation current of the compressor are normal.
2Check whether the high and low pressure is normal
when the unit is running.
3Check (whether the coil pipe sensor is normal)
whether the contact of the inserter on the circuit
board is well, the coil pipe temperature sensor is
fixed, the evaporation of the indoor unit is well,
the key is to check the evaporator temperature
detected by the coil pipe temperature sensor has
reached the cooling or heating temperature.
4Check whether the surface of the condenser is too
dirty, it should be cleaned when it is too dirty.
5Check whether the capacitance of the outdoor motor
and the fan is damaged, it should be replaced when
it is damaged.
6If the above items are normal, the electric control
board should be replaced.
E5
PG motor
display at
off state
flicker 5/7
SEC
display
at off
state
no feedback
signal of indoor
fan
1、Check whether two sets of plugs on the outlet end of
the motor have loosed from the socket of the
electric control board, insert it firmly when loosing.
2Check whether the indoor motor has damaged, the
motor should be replaced when it is damaged
3 Check whether the controllable silicon and other
components on the electric control board have
Page 33
31
damaged, replace the controllable silicon or electric
control board when they are damaged.
E6
PG motor
display at
off state
flicker 6/8
SEC
display
at off
state
no over zero
signal
1Firstly check whether the indoor fan is normal. 2Check whether the signal outputting from the
integrated chip of the electric control board is
normal, the electric control board should be
replaced when the signal is abnormal.
E7
display at
off state
flicker 7/9
SEC
display
at off
state
outdoor
feedback fault
1Check whether the winding resistance and operation
current of the compressor are normal
2Check whether the high and low pressure is normal
when the unit is running.
3Check whether the indoor and outdoor wiring is
right; when it is wrong, connect them again
according to the circuit diagram
4 Check whether the contact of the inserter on the
circuit board and the connection are well, otherwise
repair.
5Check whether the signal feedback wire is
disconnected, replace or connect the feedback
signal wire.
6Check whether the supply power is phase-lacking or
phase opposition.
7Check whether the AC electromagnetic contactor is
well.
E8
display at
off state
flicker 8/10
SEC
display
at off
state
frost protection/over heat protection
1、Check whether the filter of the indoor unit is dirty or
blocked, and clean if it is dirty.
2Check whether the indoor fan is running normally,
and replace the motor if it is abnormal.
3Check whether indoor pipe temperature sensor is
normal, and replace the sensor if it is abnormal.
4Check whether the system pressure is normal, if
abnormal, should check whether there is leakage,
and fill the refrigerant again.
Page 34
32
10. TROUBLE SHOOTING
Is CN (Tr sensor connector)
connected properly?
Is Tr sensor resistance value
(5KO at 25? ) normal?
Indoor P. C. board is defective. Replace P. C. board.
Connect CN properly.
Replace TA sensor.
Is CN (TP1 sensor connector)
connected properly?
Is TP1 sensor resistance value
(5KO at 25? ) normal?
Indoor P. C. board is defective. Replace P. C. board.
Connect CN properly.
Replace TC sensor.
YES
YES
YES
YES
NO
NO
NO
NO
Indoor Tr sensor
error
Indoor TP1 sensor
error
Page 35
33
Turn off power
supply once, and
turn it on again.
Does compressor continue to
operate?
Start to operate indoor
unit in cooling
operation at airflow
level LOW,wait
three minutes..
Does indoor fan operate?
Fan motor
operates
normally.
Is it possible to detect AC
220V between
pin(high/middle/low) and
pin(common) of motor
connector .
Replace indoor
fan motor.
Replace main
P.C. board.
Replace bearing.
YES
YES
YES
NO
NO
NO
Turn off indoor unit and rotate
cross-flow fan by hand when the
unit is on standby.Is it possible to
rotate cross-flow fan by hand
properly?
Only indoor fan motor does not operate.
Is capacitor of indoor fan ok?
YES
NO
YES
Replace
capacitor
NO
<Primary check>
(1) Is it possible to detect the power supply voltage (200-240V) between L and N on the terminal block? (2) Does the indoor fan motor operate in cooling operation?
Page 36
34
Compressor does not operate.
Turn on power supply.
Does compressor delay
three minutes by
temperature changes or
others?
Does OPERATION indication indicate?
Is it possible to detect AC
220-240V on terminal
block or contactor of
compressor?
Are all of compressor
cords normal?
Is compressor motor
winding normal?(Check
winding resistor.)
Is capacitor for
compressor normal?
Is overload relay normal?
Does compressor start?
Does compressor stop
after a while?
Is gas quantity normal?
(Check gas pressure.)
Microcontroller is defective or
miniature relay is defective..
Is resistance value of room
sensor (Tr) and heat exchanger
sensor (TP1) normal?
Room sensor or heat
exchanger sensor is
defective.
Replace room sensor
or heat exchanger
sensor.
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Compressor is defective.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload
relay.
Supply gas.
Replace compressor.
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO NO
NO
NO
NO
NO
NO
NO
NO
Check power supply.
Replace compressor.
Wait three minutes
<Primary check>
(1) Is the room temperature higher than the preset temperature in cooling operation? (2) Is the crossover cable connected properly?
Page 37
35
Replace
P.C. board.
Is receiver on
indoor unit exposed
to direct sunlight?
Batteries are
exhausted.
Press START/STOP
button.
Is there any thyristor
fluorescent light
nearby?
Does indoor unit
operate when
moving remote
control near receiver
or indoor unit?
P.C. board is
defective.
Is transmission
mark indicated?
Press RST button on remote control with tip of pencil.
Press START/STOP
button.
Does radio sound is
affected by remote
control when a
signal is transmitted
at distance of 5 cm
from radio?
Does indoor unit
start to operate by
automatic restart
function?
Is transmission
mark indicated?
Does indoor unit
beep and operate?
Remote control is
defective.
Keep indoor unit
away from
thyristor
fluorescent light.
Avoid direct
sunlight.
Replace
batteries.
Normal
operation
Replace remote
control.
The unit does not beep at all. OPERATION indication on indoor unit is not indicated.
NO
NO
NONO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
NO
YES
YES
Page 38
36
Trouble
Is the power
applied to the unit?
Check power supply mains or
interconnection wires
Is the power normal? check
the voltage between L&N of
terminal block
Check the wiring of indoor and
outdoor
Press the power ON/OFF button
of wire control or remote control
YES
YES
NO
NO
Does the beeper
beep?
Is the display all
off?
Check the connector on display PCB connected to control PCB
Check the display PCB itself
Is the unit display
normal?
Does outdoor unit run?
Does the
compressor run
normally?
Check the failure code
according to the failure
table
Normal
Check the
compressor ,wires
and it’s
capacitor.
YES
YES
YES
YES
YES
YES
NO
NO
NO
Does the control
ok?
Does the control
PCB ok?
Control failure
Control PCB failure
NO
NO
YES
NO
Trouble shooting
NO
Does the indoor
unit run?
Page 39
37
Indoor unit and outdoor unit dont operate
Indoor and outdoor unit
dont operate
Press emergency key, does
the air conditioner
running?
Replace fuse of
indoor PCB.
YES
YES
YES
NO
NO
NO
NO
Make the power
supply ok.
Replace remote
control.
YES
NO
Replace remote
receiver or display
panel.
NO
YES
YES
Replace transformer.
Does the transformer has
output?
Does the fuse of indoor
PCB burn out?
Change a good remote,
does the air conditioner
running?
Is the power supply no
problem?
Does the 12V and 5V of
indoor PCB have?
Replace PCB.
normal
Does the electric switch
cut off?
Does the electric switch
cut off after a few
nimutes?
Is the wires of indoor
unit and outdoor unit no
problem?
YES
Reconnect the wires.
NO
Is the insulation of
indoor unit and outdoor
unit no problem?
YES
Find the reason and
replace the failure
componet.
NO
Is the resistance of each
main component no
problem?
Rreplace the failure
componet.
NO
YES
YES
YES
Loading...