TSI Alnor PAN200 Data sheet

Duct Leakage Testers
ENERGY AND COMFORT
Positive and Negative Duct Accreditation (PANDA) System
Model PAN200 Series
The Positive and Negative Duct Accreditation (PANDA) system provides contractors, commissioning engineers, and research and development technicians with the best in class choice of test equipment to quantify air leakage in ductwork and other areas as well as the ability to measure the performance of ducted systems. The PANDA system provides a fast, accurate, automated solution and helps to ensure compliance with SMACNA, EN12237, EN1507, and EUROVENT 2/2 standards, enhancing energy savings in buildings.
Pass/Fail Reporting for Standards
SMACNA HVAC Air Duct Leakage Test Manual
EN12237 Ventilation for Buildings—Ductwork— Strength & Leakage of Circular Sheet Metal Ducts
EN1507 Ventilation for Buildings—Sheet Metal Ducts with Rectangular Section—Requirements for Strength and Leakage
EUROVENT 2/2 Air Leakage Rate in Sheet Metal Air Distribution Systems
Model PAN200
Features and Benefits
Positive and Negative Duct Leakage Testing in one system
Find and fix duct leaks to save energy
High accuracy gives confidence in measurements
High-flow fan for testing large duct sections
Pressurizes duct quickly, allowing testing to begin in minutes
Fits in the back of vans and trucks
Includes TSI Model 9565-P and Model 5825 instruments:
– Automatically calculate leakage rate in real time
– Simultaneously displays flow leakage rate and
static pressure
– Monitors barometric pressure and temperature to
automatically correct to Standard Temperature and Pressure (STP)
– Simplify report generation and documentation by
downloading stored data
– Works with Model 8934 Portable Printer for
field documentation
TSI Incorporated
- 500 Cardigan Road, Shoreview, MN 55126-3996 USA
USA Tel: +1 800 874 2811 E-mail: info@tsi.com Website: www.tsi.com UK Tel: +44 149 4 459200 E-mail: tsiuk@tsi.com Website: www.tsiinc.co.uk France Tel: +33 491 11 87 64 E-mail: tsifrance@tsi.com Website: www.tsiinc.fr Germany Tel: +49 241 523030 E-mail: tsigmbh@tsi.com Website: www.tsiinc.de India Tel: +91 80 41132470 E-mail: tsi-india@tsi.com China Tel: +86 10 8251 6588 E-mail: tsibeijing@tsi.com Singapore Tel: +65 6595 6388 E-mail: tsi-singapore@tsi.com
Contact your local TSI Distributor or visit our website www.tsi.com for more detailed specifications.
P/N 5001368 Rev A Copyright © 2011 by TSI Incorporated Printed in U.S.A.
Duct Leakage Testers
ENERGY AND COMFORT
Specifications
Model PAN200 Series
Pressure Measurement (5825)
Range ±15 in.
W.G. (±3,735 Pa)
Resolution 0.001 in. W.G. (0.1 Pa) Accuracy 1% of reading ±0.005 in. W.G. (±1 Pa) Actual Duct Static Range ±10 in. W.G. (±2,500 Pa) at Zero Flow
Volume Flow Measurement (9565-P)
High leakage range Wilson Radial Flow Grid
21 to 424 cfm (10 to 200 l/s), 36 to 720 m
3
/hr
Low leakage range Conical Inlet Nozzle Adapter
2 to 27.5 cfm (1 to 13 l/s),
3.6 to 46.9 m
3
/hr,
Resolution 0.01 cfm (0.01 l/s), 0.01 m
3
/hr
Accuracy ±2.5% of reading ±0.02 cfm (±0.01 l/s),
±0.04 m
3
/hr
Temperature Measurement (9565-P)
K Type thermocouple probe T
o EN60584 (IEC 584)
Range -40 to 1200°F (-40 to 650°C) Resolution 0.1°F (0.1°C) Accuracy ±0.1% of reading ±2°F
(±0.056% of reading ±1.1°C)
Barometric Pressure Measurement (9565-P)
Range 20.36 to 36.648 in.
Hg
(690 to 1,241 hPa),
517.5 to 930.87 mm Hg
Accuracy ±2% of reading
Power requirements
Model PAN221 220 to 240
V, 1 Phase, 50/60 Hz, 10A
Model PAN221-110 110 to 120 V, 1 Phase, 50/60 Hz, 16A
Weight
157 lbs (71 kg)
Dimensions (L x W x H)
44.5 in. x 26 in. x 20 in. (1,130 mm x 660 mm x 510 mm)
PAN221, PAN221-110
Instruments included V
ELOCICALC
®
Model 9565-P meter,
DP-C
ALCModel 5825 micromanometer.
See spec sheets for details on individual instruments.
Model 9565-P
Specifications subject to change without notice. TSI, TSI logo, V
ELOCICALC
, and DP-C
ALC
are trademarks of TSI Incorporated.
Model 5825
Loading...