TSI Alnor 6130, 6140 Data sheet

Page 1
Combustion Analysis
TSI’s Series CA-6100 CA-C
ALC
portable
combustion analyzers are ideal for light
commercial to residential applications. Boiler
service professionals are provided flue gas data
to tune burners on furnaces, boilers and other
Models with O
2
, stack temperature and
ambient temperature have user-selectable fuels,
calculated CO
2
, efficiency and excess air.
Options measure CO and draft pressure.
Features
• Industry-leading service
• Large display and intuitive operation
• Real-time data provides quick tuning feedback
• 10-hour battery life lowers operating costs
• Automatic baseline calibration of sensors
• Recalibrates easily for critical safety checks
• Quick new sensor installation
• Heavy-duty pump designed for field service
Series CA-6100 CA-CALC
TM
Combustion Analyzers
Applications
• Tune boilers, furnaces and appliances for optimum efficiency and safety
• Check building combustion ventilation
• Check CO safety of appliances
• Monitor burner performance
• Supplement preventative maintenance
Models available for:
• Boiler/Burner Service and Repair Contractors
• Boiler/Furnace Maintenance Companies
• Building Contractors
• Commercial Boiler Owners
• Boiler Manufacturers
• Plant Engineers
• School and Office Maintenance Staff
• Utility Companies
Page 2
P/N 2980190 4/02 Copyright © 2002 by TSI Incorporated Printed in U.S.A.
TSI Incorporated
500 Cardigan Road , Shoreview, MN 55126 USA
Tel: 651 490 2711 Toll Free: 1 800 777 8356 Fax: 651 490 2874 E-mail: [email protected] TSI Germany—Tel: +49-241-523030 Fax: +49-241-5230349 E-mail: [email protected]
TSI Sweden—Tel: +46-18-52-70-00 Fax: +46-18-52-70-70 E-mail: [email protected]
Operating Conditions:
Instrument Temperature Range:
Operating Range:
32 to 113°F (0 to 45°C)
Storage Range: -20 to 122°F (-30 to 50°C)
Instrument Humidity Range:
Continuous:
15 to 90% non-condensing
Intermittent: 0 to 99%
Maximum Flue Gas Probe Temperature:
Continuous:
1,292°F (700°C) (handle shielded)
General Data:
Instrument:
External Dimensions:
4.5 × 7.5 × 2.5 in. (11.4 × 19.1 × 6.4 cm)
Weight: 1.2 lbs/1.4 lbs with probe (0.54/0.64 kg) Display: LCD
Pump:
Flow Rate:
Nominal 0.8 lpm
Maximum Flue Pressure: ±30 in. H2O (±80 mBar)
Standard Flue Gas Sampling Probe:
Probe/Hose Material:
Stainless steel/rubber
Probe Length: 12 in. std (30 cm) Hose Length: 7 ft (2.13 m) Probe Diameter: 3/16 in. (0.48 cm)
Communication Interface:
Type:
Serial
Baud Rate: 1,200 to 19,200 selectable
Power Requirements:
Batteries:
4 size AA alkaline batteries
Battery Life: >10 hours (pump on) AC Adapter (optional): P/N 2613033 Backup Battery: Lithium Backup Battery Life: 3 yrs
Sensors:
Oxygen (O2)*:
Range:
0 to 25%
Resolution: 0.1% O
2
Carbon Monoxide (CO)*:
Range:
0 to 2,000 ppm
Resolution: 1 ppm
Flue Gas Temperature Probe:
Range:
32 to 1,292°F (0 to 700°C)
Resolution: 1°F (1°C)
Draft Pressure:
Range:
±30 in. H2O (±80 mBar)
Resolution: 0.01 in. H2O (0.01 mBar)
Supply Air Temperature Probe (Optional)**:
Range:
-40 to 392°F (-40 to 150°C)
Resolution: 1°F (1°C)
Calculated Data:
Carbon Dioxide (CO2)—Calculated from O2and fuel type:
Range:
0 to CO2Max
Excess Air (EA):
Range:
0 to 1,000%
Loss ASME:
Range:
-25 to 100%
Efficiency ASME (net):
Range:
0 to 125%
Loss qA (Siegert):
Range:
-25 to 100%
Efficiency (η) based on qA:
Range:
0 to 125%
Lambda (λ):
Range:
0 to 11
CO Air Free:
Range:
0 to 20% (10,000 ppm=1%)
CO/CO2Index:
Range:
0 to 1.000
Series CA-6100 CA-CALC Combustion Analyzers Specifications
* Electrochemical sensor ** P/N 3013033
Specifications are subject to change without notice.
* Calculated from fuel type and O
2
Ordering Information
)
2
∆T)
)*
2
λ)
Index
2
Model
CA-6110 CA-6120 CA-6130 CA-6140
Carbon Monoxide (CO)
Draft Differential Pressure
Ambient, Stack Temp. (
Oxygen (O
Carbon Dioxide (CO
•
•
•
•
•
•••
•
•
•
•
•
•
CO/CO
Efficiency (Loss) (qA)
Excess Air (
CO Air Free (Undiluted)
•
•••
•
•
•
•
•
•
•
Water Trap and Filter
Data Storage/Review/Print
7 Factory-Default and
•
•
•
•
•
•
•
•
•
•
•
For current information
www.tsi.com
1 User-Defined Fuel
Loading...