TSI Alnor 8495 Data sheet

Air Velocity
Transducer Display
and Monitor
The TSI Transducer Display & Monitor provides a scaleable digital display for transducers with current or voltage outputs. The monitor’s variable time con­stant controls the response time of the display. High and low alarms can indicate readings outside of a user-defined range. These alarms can be audible, visual and/or remote via relay contacts. The Transducer Display & Monitor also provides 500 mA of unregulated 12 VDC power to operate your trans­ducer. The microprocessor-based design provides flexibility through menu-driven, field selectable options including signal input, full scale reading, time constant and alarm levels.
Field Selectable Options
• Signal input (0-5 VDC, 0-10 VDC, 1-5 VDC, 2-10 VDC, 0-20 mA, 4-20 mA)
• Full scale reading (0.1000 to 99990)
• Zero adjust (0.1000 to 99.99)
• Span adjust (0.1 to 1.9)
• Low alarm (0 to full scale)
• High alarm (0 to full scale)
• Audible alarm/mute
• Time constant (1 to 20 seconds)
• Visual alarm latched or unlatched
• Relays latched or unlatched
The Transducer Display & Monitor Model 8495 is an ideal accessory for TSI’s Air Velocity Transducers, pro­viding flexibility in outputs while also powering the transducer. The adjustable full scale reading allows you to scale the display to fit your application. For example, if mounting the transducer in a duct, you can select a full scale reading that includes a multiplication factor to convert to units of volumetric flow rate or even mass flow rate. The span adjustment can be used as a density correction factor, allowing you to correct the readings for changes in temperature or pressure. When using an air velocity transducer in a fluctuating flow, increasing the variable time constant will provide a more stable display of velocity or flow. If monitoring velocity or flow in a critical process application, using the high and low alarms will indicate readings outside of an accept­able range.
Model 8495
When using the TRANSDUCER DISPLAY & MONITOR with the TSI C
ERTIFIER
®
Air Velocity Calibrator, the unit will display actual air velocity. Entering a density correction factor automatically converts the velocity to standard conditions. This allows the user to read air velocity directly from the Transducer Display & Monitor instead of reading pressure and then calculating velocity.
TSI instruments are backed by more than 38 years of experi­ence in air flow measurement technology. It’s this type of experience and innovation that provides you with accurate and reliable instruments. Along with TSI’s expertise, each instrument is backed by a two year limited warranty and a great service policy. In addition to fast service, calibrations are NIST* traceable and a free certificate of cali­bration is included.
P/N 2980075 Rev.B
Copyright ©2004 by TSI Incorporated Printed in U.S.A.
TSI Incorporated
Corporate Headquarters—Tel: 651 490 2811 Toll Free: 1 800 874 2811 Fax: 651 490 3824 E-mail: answers@tsi.com Contact TSI or visit www.tsi.com for information on specific office locations worldwide.
Specifications
Model 8495
Full Scale Value Resolution
0.1000 to 1.0000 0.0001
1.000 to 10.000 0.001
10.00 to 100.00 0.01
100.0 to 1000.0 0.1 1000 to 10000 1 10010 to 99990 10
Accuracy
(1&2)
±.25% of reading ±1 digit of resolution
Time Constant 1 to 20 seconds in 1 second intervals Transducer Connections Detachable terminal strip Display 5 digit LED Output Power 12 VDC unregulated, supplies 500 mA
minimum with TSI-supplied AC Adapter
Signal Input Ranges 0-5VDC, 1-5VDC, 0-10VDC, 2-10VDC,
0-20mA, or 4-20mA
Temperature Stability 0.0014%/°F (0.003%/°C) Temperature Range 32 to 122°F (0 to 50°C) Input Impedance Greater than 500KΩ for 0-5 V input,
greater than 1MΩ for 0-10 V input, 250Ω for current input
Input Power 11-30 VDC or 18-28 VAC, requires 500
mA maximum
Power Consumption 19VA maximum Housing ABS plastic Dimensions 8.0 in.
×
6.2 in.× 2.5 in.
(20.3 cm
×
15.8 cm× 6.5 cm)
* National Institute of Standards and Technology.
1
±.02% of reading/°C = .01% of reading/°F away from 25°C.
2
±.025% of full scale = effect of EMI per IEC801-3.
Specifications subject to change without notice. Specifications in parentheses ( ) indicate metric equivalents.