Triton AS2000X Installation And Operating Instructions Manual

Page 1
Installers please note these InstructIons are to be left wIth the user
2180403L - June 2012
Installation and
operating
instructions
AS2000X
Page 2
Aquasensation AS2000X
CONTENTS Page
Plumbing and electrical notes ......................................................... 1
Introduction ................................................................................... 2
Safety warnings .............................................................................. 2
Main components .......................................................................... 3
Specifications .................................................................................. 3
Site requirements ........................................................................ 4 5
General installation notes ............................................................... 5
Siting of the shower ....................................................................... 6
Removing the cover........................................................................ 7
Plumbing connections ................................................................. 7 9
Fitting the shower to the wall ........................................................ 10
Electrical connections .................................................................... 11
Commissioning .......................................................................... 12 14
Fitting the riser rail .................................................................... 15 16
Operating the shower................................................................ 17 18
Adjusting the maximum temperature stop .................................... 18
Cleaning the filters ........................................................................ 19
Spare parts .................................................................................... 20
Fault finding .............................................................................. 21 22
Water/Cable entry points diagram .................................... 23
Guarantee, service policy, etc. ..................................................rear cover
To check the product suitability for commercial and multiple installations, please contact Triton’s specification advisory service before installation.
Telephone:
Facsimile:
E mail:
0844 980 0730
0844 980 0744
technical@tritonshowers.co.uk
Page 3
Aquasensation AS2000X
1
1 PLUMBING NOTES
1.1 All installations must comply with Water
Regulations or Water Bylaws.
1.2 Supply pipes must be flushed to clear
debris before connecting the shower unit.
1.3 DO NOT connect the shower unit to
the mains cold water supply as it would damage the unit and also, the installation would be in breach of Water Regulations.
1.4 DO NOT use excessive force when making
connections to the flexible hose or showerhead – finger tight is sufficient.
1.5 ALL plumbing connections are to be
completed and water supplies turned on BEFORE switching on the electricity supply. The shower must not be operated dry without water.
1.6 DO NOT solder pipes or fittings within
300 mm of the shower appliance, as heat transfer can damage components.
1.7 When installed, the top of the shower unit
must be at least 75 mm lower than the base of the cold water storage cistern to prevent the pump being run dry without water.
1.8 A dedicated cold water supply must be
taken directly from the cold water cistern to the shower. This draw-off must be on the opposite side of the cistern to the float operated valve to reduce the risk of air entering the unit.
1.9 The action of the pump is to increase the
flow rate. If the supply pipework cannot handle the resulting flow rate then:
1.9.1 The anticipated flow rate may not
be achieved.
1.9.2 Air may be drawn into the hot supply from the vent pipe causing spluttering and temperature fluctuations at the showerhead.
1.10 Fullway isolating valves MUST be fitted
on the hot and cold water supplies to the shower as an independent means of isolating the water supplies should maintenance or servicing be necessary. DO NOT use stop taps or ball-o-fix type valves which restrict flow.
2 ELECTRICAL NOTES
2.1 The installation must comply with BS 7671
‘Requirements for electrical installations’ (IEE wiring regulations). Make sure the incoming hot and cold water supplies to the shower are adequately earth bonded.
2.2 DO NOT turn on the electrical supply
until the plumbing connections have been completed. Only then can the electricity be switched on in order to power the solenoid to turn water on to the shower when commissioning. The shower must not be operated dry without water.
2.3 The mains supply must be 230/240V, at
50Hz, connected to the unit via a double pole switched 3 Amp fused connection unit (not supplied) with a minimum 3 mm contact separation gap in each pole.
2.4 In accordance with ‘The Plugs and Sockets
etc. (Safety) Regulations 1994’, this unit is intended to be permanently connected to the fixed electrical wiring of the mains system.
2.5 Fuses do not give personal protection
against electric shock.
2.6 A 30mA residual current device (RCD)
MUST be installed. This may be part of the consumer unit or a separate unit.
Page 4
Aquasensation AS2000X
2
INTRODUCTION
This book contains all the necessary fitting and operating instructions for your Triton Power Shower. Please read them carefully.
The shower installation must be carried out by suitably competent person and in sequence of this instruction book.
Care taken during the installation will ensure a long and trouble free life from your shower
IMPORTANT: All plumbing connections must be completed BEFORE making the electrical connections.
Please read through the whole of this book before beginning your installation.
IMPORTANT: The fittings on the pipe inlet elbows are of the push-in type. The pipework must be cut with a pipe cutter and all burrs and rough edges removed from the end of the tube. The fittings can be used with copper and plastic pipe. Where chrome plated pipe is used, remove the first 25 mm of plating.
Note: The pump inside this product is rated 15 minutes on / 45 minutes off duty cycle.
SAFETY WARNINGS
a. DO NOT insert fingers into the push-in inlet
fittings. Doing so could cause injury.
b. Under no circumstances must this product
be connected to mains cold or hot water supplies. Failure to comply will invalidate
the guarantee.
c. The shower MUST NOT be used if
suspected of being frozen.
d. The outlet of this appliance MUST NOT be
connected to any form of tap or fitting not recommended by the manufacturer.
e. The showerhead cartridge MUST be cleaned
regularly to remove scale and debris.
f. This appliance MUST be earthed.
g. Switch off immediately at the isolating
switch if water ceases to flow during use.
h. DO NOT operate the shower outside the
guidelines laid out in ‘site requirements’.
i. DO NOT operate the shower if the
showerhead or spray hose becomes damaged.
j. DO NOT restrict flow out of the shower by
placing the showerhead in direct contact with your body.
Replacement parts can be ordered from Triton Customer Service. See ‘spare parts’ for details and part numbers.
WARNING!
The power shower does not contain
a thermostatic valve – it will not shut
off in the event of failure of either
the hot or cold water supplies.
A 30mA residual current device (RCD) MUST be installed in all UK 230V electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
Page 5
Aquasensation AS2000X
3
Hot water temperature
Maximum temperature 65°C.
BS 6700 recommends that the temperature of stored water should never exceed 65°C. A stored water temperature of 60°C is considered sufficient to meet all normal requirements and will minimise the effects of scale in hard water areas.
Maximum static inlet pressures
100 Kpa (1 bar) or 10m (supplies must be gravity fed at nominally equal pressures).
Minimum static inlet pressure
0.75 Kpa (0.0075 bar) or 75mm (required to prime the integral centrifugal pump).
Maximum supply head 10m.
SPECIFICATIONS
MAIN COMPONENTS
1. Top pipe entry and cable entry
2. Terminal block
3. Cover screw fixing
4. Motor retaining bracket
5. Rear pipe entry and cable entry
6. Wall fixing holes
7. Pipe inlet elbow - top
(contains single check valves)
8. Filter cover - top
9. Pump
10. PCB
11. Temperature control valve
12. Solenoid
13. Filter cover - bottom
14. Pipe inlet elbow - bottom
(contains single check valves)
15. Outlet
16. Bottom pipe entry
17. Potentiometer gear
Fig.1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Page 6
Aquasensation AS2000X
4
Fig.3 illustrates all the incorrect connections that
must be avoided.
All pipework to the shower unit must be routed where it remains below the level of water in the cistern. In the case of horizontal sections of pipework in lofts, it may be necessary to fit automatic air vents at high points on the supplies to remove the possibility of air locks.
For the operation of the shower only, it is recommended that the cold water storage cistern is capable of holding at least 114 litres (25 gallons). Where other hot and cold outlets are likely to be in use simultaneously, the storage capacity should be increased to 228 litres (50 gallons) in accordance with BS 6700.
Do ensure compliance with the Water Regulations/Bylaws.
DO NOT connect to a combination cylinder unless there is a guaranteed 114 litre cold supply to the cylinder as the shower can deliver up to 14 litres per minute. It is advisable to check that
Mains supply
Isolating
valve
Cold water cistern
Vent pipe tee
Isolating
valve
Hot supply
Hot water
cylinder
Drain
valve
Other hot water
draw-offs
Alternative connection
Shower unit
Ring main
25mm min
Isolating spur
(3A fused)
outside bathroom
Dedicated cold supply
10m max
75mm
min
Isolating
valves
SITE REQUIREMENTS
Water
The installation must be in accordance with Water Regulations/Bylaws and BS 6700.
For correct operation of this shower unit, both hot and cold water supplies to the appliance must be gravity fed, at nominally equal pressures, from a cold water storage cistern and a hot water storage cylinder.
The water circuit should be installed so that the flow is not significantly affected by other taps and appliances being operated elsewhere on the premises.
Fig.2 shows a recommended installation where the hot water supply for the shower is made via a tee connection on the underside of the horizontal section of pipework from the cylinder. Alternatively, the connection can be taken from the hot supply pipe to other outlets as long as it is the first draw-off below the ventilation pipe tee.
Fig.2 (Diagrammatic view – not to scale)
Page 7
Aquasensation AS2000X
5
the infill rate from the float operated valve meets the output requirements..
It is recommended that there is a minimum of approximately 114 litres (25 gallons) of hot water storage per appliance.
The shower MUST NOT be connected to the mains cold water supply.
DO NOT use jointing compounds.
GENERAL INSTALLATION NOTES
1. DO NOT take risks with plumbing or
electrical equipment.
2. DO NOT install this unit in a position where
it could become frozen.
3. Isolate electrical and water supplies BEFORE
proceeding with installation work.
4. Shower control MUST be fed from a cold
water storage cistern and hot water cylinder that provides nominally equal pressures.
Fig.3 (Diagrammatic view
not to scale)
5. The unit must be mounted onto the finished
wall surface (on top of tiles).
DO NOT tile up to the unit after fixing to
the wall.
6. If installing with rear inlet supplies, it is
recommended the supply pipework is sealed to the wall so as to prevent water from leaking back into the wall.
7. In solid wall installations, the supply
pipework should be housed within ducting in order to allow some free lateral movement when making connections and to ensure compliance with requirements of accessibility of pipes and pipe fittings.
Fig.4 shows a schematic wiring diagram of the unit.
Page 8
Aquasensation AS2000X
6
Shower can be mounted
either side of
the riser rail
Spill-over
level
Ceiling
Use soap dish
retaining ring
Height of
sprayhead
and shower
to suit user’s
requirement
Shower unit must not be
within an area
1 metre
from base
Space for cover
screw access
Fig.5
SITING OF THE SHOWER
IMPORTANT: If fitting to a tiled wall, always mount the unit on the surface of the tiles. NEVER tile up to the unit.
Refer to fig.5 for correct siting of the shower. Position the unit vertically where it will NOT be in direct contact with water from the showerhead.
Note: Allow sufficient room between the ceiling and the shower unit to access the top cover screw.
Position the shower and showerhead on the wall so that all controls can be comfortably reached when using the shower.
The showerhead and riser rail can be positioned either side of the shower unit.
Note: Water Regulations require the showerhead be ‘constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25 mm above the spill-over level of the relevant bath, shower tray or other fixed appliance’. The use of the supplied soap dish will in most cases meet this requirement, but if the showerhead can be placed within a bath, basin or shower tray, then a device must be fitted to prevent back-flow.
L E N
Potentiometer
Switch
Solenoid
Motor
Capacitor 2
RFI suppression coil
Capacitor 1
PCB
Thermal fuse
Fig.4 (schematic view )
WARNING!
The shower must not be positioned
where it will be subject to freezing
conditions.
Page 9
Aquasensation AS2000X
7
Fig.6
REMOVING THE COVER
To remove the cover, first pull off the cover trim (fig.6) to reveal the retaining screw.
Undo the screw and pull off the inner temperature control. Now remove the outer flow control assembly comprising of the flow control, maximum temperature stop and temperature disc (fig.7).
Note: If adjustment of the maximum temperature stop is required, refer to section ’Adjusting the maximum temperature stop’.
Remove the two cover fixing screws – top and bottom (fig.8).
Carefully lift the cover away from the backplate. Lay aside the cover and screws until the unit is fully installed.
Note: When removing the cover for future maintenance purposes be aware of the lead connecting the Start/Stop switch to the PCB harness. To release, squeeze the connection block arms and pull apart. DO NOT let the unit dangle by the lead.
PLUMBING CONNECTIONS
Plumbing to be carried out before wiring
Note: The outlet of the shower must not be connected to anything other than the hose and showerhead supplied.
DO NOT use jointing compounds on any pipe fittings for the installation.
When connecting pipework avoid using tight 90° elbows. Swept or formed bends will give optimum performance.
Isolate the mains water supply to the cold water cistern. Drain the hot and cold pipes by opening all taps.
The hot water supply can be taken from the hot supply pipe from the cylinder. Make sure that it is the first draw-off below the ventilation pipe tee in order to minimise the effects of water draw-off elsewhere in the house (see fig.2).
Note: There must not be any other draw-offs between the take-off point and the shower.
A dedicated cold water supply must be taken directly from the cold water cistern to the shower. This draw-off must be positioned
Temperature
disc
Flow control
Maximum
temperature
stop
Fig.7
Fig.8
Page 10
Aquasensation AS2000X
8
25 mm below the cold feed connection to the hot water cylinder on the opposite side of the cistern to the float operated valve (see fig.2). This minimises air ingress into the pipework.
Plumbing options other than those outlined in these fitting instructions could impair the performance. For example, if hot and cold connections are made after draw-off points to other outlets, (eg. washing machine, taps, etc.) it could result in unstable flows and temperatures should other appliances operate at the same time.
Run the hot and cold pipework to the shower position, making sure that the pipework does not rise above the level of water in the cold cistern at any point to avoid air locks. Under normal site conditions 15 mm pipework will be adequate.
Decide the position of the shower. Cut the pipework to the dimensions relevant to the chosen direction of water entry into the shower.
IMPORTANT: For rear entry only, the supplied elbows must be used. For ease of installation, the backplate area adjacent to the top pipe inlet must be cut out, including the top left wall fixing hole.
When fitting the elbows to incoming pipework, ensure the elbow collets are fully engaged with the pipe.
Dimensions are shown in fig.9 and fig.10.
Note: The pipe inlets are marked for hot and cold connections – left-hand side for hot inlet on bottom entry (fig.11), but right-hand side for hot inlet on top or rear entry (fig.12).
IMPORTANT: The fittings on the inlet elbows are the push-in type. The pipework must be cut with a pipe cutter and all burrs and rough edges removed from the end of the tube. The fittings can be used with copper and plastic pipe. If using chrome plated copper pipe, remove the first 25 mm of plating completely from the connecting surfaces. If not completely removed then the collet will not grip the pipe and under pressure the pipe may be forced out.
Fig.9
Top
19 mm
26 mm
Cold
Hot
Area of
backplate
to remove
Wall
19 mm
34 mm
26 mm
Rear edge
of
backplate
Hot Cold
Wall
Rear
23.5 mm
Bottom
Fig.10
Page 11
Aquasensation AS2000X
9
Note: Pipework must be clipped or fixed to the
wall so that it cannot be moved or removed without the aid of a tool.
Note: The pipe inlets contain filters. These should be periodically removed and cleaned in order to maintain the performance of the shower. See section ‘cleaning’ on how to access the filters.
IMPORTANT: The inlets contain check valves, so before completing the connection of the water supplies to the shower flush out the pipework to remove all swarf and system debris that may cause damage to internal parts. This can be achieved by connecting a hose to the pipework and turning on the water supplies long enough to clear the debris to waste.
IMPORTANT: Two factory fitted blanking plugs are fitted to the top pipe inlets. These should be left in position if bottom pipe entry is required. For top or rear pipe entry, the two plugs MUST be removed and refitted into the bottom pipe inlets. Failure to fit the blanking plugs will result in the unit working erratically.
Insert the pipe removal tool supplied between the flange of the plug and the grey collet and lever the plug outward (fig.13). Whilst holding back on the collet, pull out each plug by hand. When refitting the plugs in the bottom pipe inlets, make sure they are pushed fully home.
Note: The unit is supplied with a splash guard (fig.14) to prevent water ingress when top
entry pipework is used. If fitting top entry pipework, make sure the splash guard is correctly fitted (fig.14) before replacing the cover.
Bottom (rising)
supply
Top
(falling)
or rear supply
Hot side
Hot side
Top
(falling)
or rear supply
Hot side
Fig.11
Fig.12
Blanking
plug
Fig.13
Splash guard
Fig.14
Page 12
Aquasensation AS2000X
10
FITTING THE SHOWER TO THE WALL
IMPORTANT: Before fitting the shower, make sure the pipework is flushed out to remove all debris, flux, etc.
For top pipe entry or top cable entry, remove the relevant cut-outs by either breaking out or by using a knife or junior hacksaw (fig.15).
If top entry for both pipe and cable is required, then additionally remove the shaded area (fig.15) by using a knife or junior hacksaw.
For bottom pipe entry, remove the cut-out and break off the two circular parts (fig.16). Replace the cut-out.
For rear pipe entry only, the supplied elbows must be used with the necessary portion of backplate cut away as shown in fig.9.
It will be necessary if rear cable entry is required, for conduit or other routing of the electrical cable to be completed before fixing the shower to the wall.
Offer the backplate unit up to the completed pipework and manoeuvre so that the end of the pipes enter fully into the inlet fittings.
Mark positions for wall fixing holes using backplate as template (fig.17). Note that four fixing holes are provided but using only two should be adequate for most site conditions.
Using the pipe removal tool supplied, push back and hold the collets from the pipework (fig.18) to disengage the pipework from the inlet elbows.
Remove unit from the wall.
Drill and plug the wall.
(An appropriate drill bit should be used. If the wall is brick, plasterboard or a soft building block, appropriate wall plugs and screws should be fitted).
Note: If fitting rising supplies to the unit, ensure debris does not enter the pipes when drilling the wall.
Offer the backplate unit up to the completed pipework and manoeuvre so that the end of the pipes enter fully into the inlet fittings.
Check the backplate is square and the fixing holes are aligned (fig.17).
Secure to the wall with fixing screws supplied.
Remove shaded area
Cut out
for cable
Fig.15
Fig.16
Fig.17
Page 13
Aquasensation AS2000X
11
ELECTRICAL CONNECTIONS
The supply cable must conform to relevant tables in current IEE regulations. In most cases 1 mm² twin and earth will be adequate.
The electrical rating of the shower is on the rating label within the unit.
SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS.
Cable entry points are shown in fig.1. Conduit entry can only be from the rear.
Route the cable into the shower, taking care to avoid the area of the wall fixings and connect to the terminal block (fig.19) as follows:
Earth cable to terminal marked E
Neutral cable to terminal marked N
Live cable to terminal marked L
IMPORTANT: Fully tighten the terminal block screws and check that no cable insulation is trapped under the screws.
Note: The supply cable earth conductor must be sleeved.
The earth continuity conductor of the electrical installation must be effectively connected electrically to all exposed metal parts of other appliances and services in the room in which the shower is to be installed, to conform to current IEE regulations.
Note: Fuses do not ensure user protection against electric shock. In the interest of electrical safety, all mains electric and pumped showers should be fitted with a 30mA residual current device (RCD). This may be part of the consumer unit or a separate unit.
DO NOT switch on the electricity supply until the water has been turned on to the unit and connections have been tested for leaks.
IMPORTANT: The cover may be left off initially only for commissioning.
Fig.18
Terminal block
Fig.19
WARNING!
This unit must be earthed. Isolate the
supply before starting.
Page 14
Aquasensation AS2000X
12
COMMISSIONING
The first operation of the shower is intended to flush out any remaining system debris and to ensure water is purged through the unit. This operation must be carried out with the flexible hose screwed to the shower outlet but without the sprayhead attached.
Make sure the outlet of the flexible hose is directed to waste.
Check the isolating valves controlling the water supply to the unit are fully open.
Note: There is no need to fit the cover at this stage but be aware of live parts when the electricity is switched on temporarily.
Fit the temperature control onto the splined spindle (fig.20).
On the PCB, make sure the commissioning link is positioned on the middle two pins (fig.21).
Switch on the electric supply at the isolating switch. Water will begin to flow under gravity pressure.
Once the unit has been commissioned, disconnect the electricity supply before removing the commissioning link.
In order to dispel air and to prime both supplies to the shower unit, turn the temperature control several times within its rotational limits. ONCE
WARNING!
Before normal operation of the
shower, it is essential that the
commissioning and setup procedure
are correctly completed. Failure to do
so could cause the pump to run dry
without water and invalidate your
guarantee.
WARNING!
Be aware of live parts in the unit
when the electricity is switched on.
DO NOT tamper with any parts and
DO NOT deviate from the following
instructions.
Temperature control
Fig.20
Commissioning
link
Fig.21
Cold
Hot
Fig.22
Fig.23
Page 15
Aquasensation AS2000X
13
RESISTANCE IS FELT, DO NOT FORCE THE CONTROL FURTHER.
Note: The temperature control rotates less than one complete turn (fig.22). DO NOT force it beyond these limits.
To stop the water flow, switch off the electricity supply at the isolating switch.
Check for leaks in the pipework and remedy if necessary. If rear entry has been used then seal around pipes with mastic to prevent the possibility of water entering the wall cavity.
DO NOT use plaster as this could cause difficulty if maintenance is required later.
Setup procedure
MAKE SURE THE ELECTRICITY TO THE UNIT IS SWITCHED OFF.
Pull off the temperature control. Remove the commissioning link from the PCB (fig.23) and store safely for future use.
Inside the cover, attached to the flow control potentiometer is a 4-wire lead. Fit the connector on the end of this lead to the 4 pins on the PCB (fig.24) – it can fit either way.
Make sure the potentiometer control is rotated fully anti-clockwise (fig.25).
Replacing the cover
Offer the cover to the backplate unit. Inside the cover, attached to the stop/start switch is a two wire lead. The socket on the end of this lead must connect to the plug attached to the backplate unit (fig.26).
Fit the cover, making sure the connector is fitted to the PCB and the wires are clear of obstructions. Secure with the top and bottom fixing screws
(fig.8).
WARNING!
Once the unit has been commissioned,
turn off the electricity supply at
the mains before removing the
commissioning link.
Fig.24
Fig.25
Fig.26
Page 16
Aquasensation AS2000X
14
With your fingers, rotate the valve spindle fully anti-clockwise (fig.27) to the fully hot position.
Replace the flow control so that it aligns with the ‘min’ position.
Fit the temperature disc (it will only fit one way) and maximum temperature stop (fig.28).
Note: If adjustment of the maximum temperature stop is required, refer to section ’Adjusting the maximum temperature stop’.
Replace the temperature control onto the valve spindle. Make sure the pointer aligns with setting ‘9’ on the temperature disc (fig.29).
Secure with the retaining screw and fit the cover trim.
Switch on the electricity supply at the isolating switch. Make sure both water supplies are still turned on.
Once the installation of the riser rail is complete, the shower is ready for normal operation.
Fig.29
Flow control
Temperature
disc
Temperature
control
Retaining
screw
Cover
trim
Maximum
temperature
stop
Fig.28
Fig.27
Page 17
Aquasensation AS2000X
15
*FITTING THE RISER RAIL
Decide the position for the rail on the wall within the shower area. Proceed as follows:
Fit the showerhead holder onto the riser rail. The correct orientation of the holder is when the showerhead holder is sloping DOWN (fig.30).
To fit the showerhead holder onto the riser rail unit, press and hold the button on the underneath of the showerhead holder to release the locking mechanism, then slide onto the rail.
Slide the supplied soap dish onto the riser rail below the showerhead holder (fig.31).
Slide the top and bottom finishing trims onto the riser rail (fig.32).
Push the two fixing brackets into the ends of the riser rail (fig.33).
Offer the rail assembly to the wall (fig.34). Using the brackets as templates, mark two upper holes and two lower holes. Note there are four provisions for screws per bracket – select the two most suitable for your requirements. Make sure the rail is aligned vertically.
Drill and plug the wall.
(An appropriate drill bit should be used. If the wall is brick, plasterboard or a soft building block, appropriate wall plugs and screws should be fitted).
Screw to the wall.
Slide the finishing trims onto the brackets. Make sure the lug on each rail bracket end engages into the slot on the fatter end of each trim before push fitting the thinner ends in place (fig.35).
WARNING!
Check there are no hidden cables or
pipes before drilling holes for wall
plugs. Use great care when using
power tools near water. The use of
a residual current device (RCD) is
recommended.
Fig.33
Fig.30
Fig.32
Fig.31
Fig.34
*All kits are for illustration purposes only and are not
supplied unless otherwise stated.
Page 18
Aquasensation AS2000X
16
Washers
Shower
Showerhead
Showerhead
Holder
To remove a trim, push a small screwdriver or similar through the slot in the trim end and carefully pull away from the wall bracket.
Slide the soap dish down the rail so that its bracket engages on top of the lower finishing trim.
Adjusting the showerhead holder
To adjust the height, press the button underneath the holder to release the locking mechanism (fig.36). Still pressing the button, move the holder up or down to suit user’s requirement.
Fitting the hose and showerhead
Feed the flexible hose through the soap dish aperture (fig.37) so the dish acts as a retaining ring (Water Regulations).
Screw the flexible hose to the shower outlet and showerhead, checking the supplied washers are in place at both ends of the flexible hose (fig.38).
Place the showerhead into the holder and check that it fits correctly (fig.39).
Note: The holder is slightly tapered and the showerhead and hose will only fit from one direction.
IMPORTANT: It is the conical end of the hose which grips into the holder. The showerhead will not fit in the holder without the hose attached. At this stage, disconnect the showerhead and lay aside until the shower unit has been commissioned.
CAUTION: This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Fig.35
Fig.37
Fig.39
Fig.36
Fig.38
Page 19
Aquasensation AS2000X
17
OPERATING THE SHOWER
Check all plumbing and electrical supplies are connected and switched on.
To start the shower, press the ‘Start/Stop’ button (fig.40).
Adjust the control (fig.41) until the flow rate is satisfactory.
For maximum flow, turn the flow control fully anti-clockwise. For minimum flow, rotate the flow control fully clockwise.
To adjust the temperature rotate the control (fig.42). The temperature is numbered for ease of use. The temperature ranges from-‘1’ – fully cold to ‘9’ – fully hot.
Once the preferred temperature is reached, no further adjustment is required, providing the hot and cold water supplies remain constant.
To stop the shower, press the ‘Start/Stop’ button once more. This stops the pump and water flow.
Unless the shower is to be used again immediately, the shower should also be switched off at the electricity isolating switch.
As a safety feature, the temperature control has a built-in stop to prevent you accidentally exceeding your highest desired temperature. If adjustment is required see section ‘Adjusting the maximum temperature stop’.
To override this stop, depress the button (fig.43) while the control is up against the stop and turn the control anti-clockwise to the higher settings (pressing the button before the stop will not operate the override mechanism even if the control is turned with the button depressed).
To return to the normal temperature range just turn the temperature control clockwise until it is past the maximum temperature stop. Make sure the temperature control is in the normal temperature range when the shower is switched off. The stop comes in a factory set position based on 65°C stored hot water temperature.
Note: As the flow control is adjusted it is normal for the sound of the pump to alter in pitch.
Temperature
control
Override
button
Fig.40
Fig.42
Fig.41
Fig.43
Page 20
Aquasensation AS2000X
18
ADJUSTING THE MAXIMUM TEMPERATURE STOP
As a safety feature the shower has a built-in maximum temperature stop to prevent you accidentally exceeding your highest desired temperature. This is set in the factory to provide a maximum temperature based on the hot and cold water supplies being 65°C and 15°C respectively.
IMPORTANT: Only adjust the maximum temperature stop when the hot water is at its usual storage temperature.
Procedure
Rotate the temperature control to setting ‘9’ on the temperature disc.
Remove the cover trim to reveal the retaining screw (fig.44).
Undo the retaining screw and carefully pull off the temperature control, making sure it is still aligned to setting ‘9’.
Now remove the maximum temperature stop.
To increase the temperature stop setting, reposition the mechanism anti-clockwise within the arc of the grooves (fig.45).
To decrease the temperature stop setting, reposition the mechanism clockwise within the arc of the grooves (fig.45).
Replace the temperature control onto the valve spindle. Make sure the pointer aligns with setting ‘9’ on the temperature disc (fig.28).
Secure with the retaining screw and refit the cover trim.
Fig.44
Maximum
temperature
stop
Increase stop position
Decrease stop position
Fig.45
Page 21
Aquasensation AS2000X
19
CLEANING THE FILTERS
Note: Turn off the electricity and both hot and cold water supplies to the unit before proceeding further.
To remove the cover, first pull off the flow knob cover trim (fig.6) to reveal the retaining screw.
Undo the screw and pull off the temperature control. Now remove the outer flow control assembly comprising of the flow control, maximum temperature stop and temperature disc.
Remove the two cover fixing screws – top and bottom (fig.8). Carefully lift the cover away from the backplate. To release the PCB connector, squeeze the connection block arms and pull apart.
Remove the single retaining screw from either the upper or lower filter cover (fig.46), depending upon whether top/rear entry or bottom entry is used. Pull off the filter cover. Carefully hook out the filters together with ‘O’ rings. Thoroughly clean and replace making sure the ‘O’ rings are in position.
Refit the filter cover and secure with the retaining screw.
Make sure the potentiometer control is rotated fully anti-clockwise (fig.25).
With your fingers, rotate the valve spindle fully anti-clockwise (fig.26) to the fully hot position.
Fit the cover, making sure the PCB connector is fitted and the wires are clear of obstructions. Secure with the top and bottom fixing screws (fig.8).
Replace the flow control so that it aligns with the ‘min’ position.
Fit the temperature disc (it will only fit one way) and maximum temperature stop (fig.27).
Replace the temperature control onto the valve spindle. Make sure the pointer aligns with setting ‘9’ on the temperature disc (fig.28).
Secure with the retaining screw and fit the cover trim.
Switch on the electricity supply to the unit and then turn on both water supplies.
INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY
Retaining screw
Filter cover
Filter
Filter
Upper filter shown Fig.46
WARNING!
Switch off the electricity supply
and turn off both hot and cold
water supplies to the unit before
proceeding further.
Page 22
Aquasensation AS2000X
20
SPARE PARTS
Ref. Description Part No.
1 Terminal block ........................... 22001320
2 Plastic inlet elbow plug x1 ......... 7052140
3 Pump and motor assembly ........ 84000130
4 Pipe inlet elbow ........................83305320
c/w filters and check valves
5 Temperature valve ..................... 83305280
6 Link pin ..................................... 22009060
7 PCB unit .................................... 7073738
8 Solenoid assembly .................... 22012190
9 Gear .......................................... 7052184
10 Filter (pair) ................................83305330
– Pipe trim ...................................7052146
– Pipe removing tool .................... 7052144
– Potentiometer harness ...............P09440900
– Bracket ...................................... 7052183
– Wire kit .....................................83311410
11 Cover assembly .........................P09440600
– Maximum temperature stop ......7052186
– Temperature control ..................P09441000
c/w override button
– Flow control .............................. 7053275
– Temperature disc .......................7053277
– Flow control trim .......................7053276
– Temp control cover trim ............7053280
– Rear entry elbow ....................... 22008180
11
1
3
4
5
6
7
8
9
10
2
Page 23
Aquasensation AS2000X
21
FAULT FINDING
IMPORTANT: Switch OFF the electricity at the mains supply and remove the correct circuit fuse before attempting any fault finding inside the unit.
Symptom Cause Action/Cure
1.1.1 Turn the temperature control clockwise.
1.2.1 Turn the temperature control clockwise.
1.3.1 Remove filter and clean. If problem is with
check valve, contact Customer Service.
1.4.1 Isolate shower and consult a competent plumber or contact Customer Service.
2.1.1 Turn temperature control anti-clockwise.
2.2.1 Turn temperature control anti-clockwise.
2.3.1 Turn shower off and wait for hot water
cylinder to reheat.
2.4.1 Remove filter and clean. If problem is with check valve, contact Customer Service.
2.5.1 Turn shower off. Consult a competent plumber or contact Customer Service.
3.1.1 Blown fuse. Check supply. Renew fuse. If it fails again consult a competent electrician.
3.1.2 Power cut. Check other appliances and if necessary, contact local Electricity Supply Co.
3.2.1 Consult a competent electrician or contact Customer Service.
3.3.1 Thermal protection on motor has operated. Allow appliance to cool and reset itself. If it persists, contact Customer Service.
3.4.1 Remove cover and connect start/stop switch.
1 Water too hot.
2 Water too cold.
3 Pump does not
operate.
1.1 Not enough cold water flowing through shower.
1.2 Increase in the ambient cold water temperature.
1.3 Cold inlet filter blocked or check valve sticking.
1.4 Cold water supply blocked or cut off.
2.1 Not enough hot water flowing through shower.
2.2 Decrease in ambient cold water temperature.
2.3 No hot water in the storage cylinder.
2.4 Hot inlet filter blocked or check valve sticking.
2.5 Hot water supply blocked or otherwise cut off.
3.1 Interrupted power supply.
3.2 Electrical malfunction.
3.3 Motor overheated.
3.4 Start/stop switch not
connected.
Any maintenance or repair to the shower must be carried out by a suitably
competent person.
Page 24
Aquasensation AS2000X
22
FAULT FINDING
Symptom Cause Action/Cure
4.1.1 Check water elsewhere in house and if
necessary contact the local Water Company.
4.2.1 Switch off shower and contact Customer Service.
4.3.1 Clean showerhead.
4.4.1 Clean filters.
5.1.1 Isolate water to unit. Remove check valves.
Clean and replace.
6.1.1 Call Customer Service.
6.2.1 Call Customer Service.
7.1.1 Call Customer Service.
7.2.1 Replace pump.
8.1.1 Fit blanking plugs into unused inlets.
4 Water does not
flow or is reduced.
5 Cross flow of hot and cold water into system.
6 Water dripping from showerhead when turned off.
7 Pump is noisy or air lock in pump.
8 Unit running erratically.
4.1 Water supplies cut off.
4.2 Shower blocked or air
in the system.
4.3 Showerhead blocked.
4.4 Blocked filters.
5.1 Dirt/debris in check
valves.
6.1 Debris in solenoid valve.
6.2 Potentiometer faulty.
7.1 Air lock in pump.
7.2 Worn pump bearings.
8.1 Blanking plugs not fitted into unused inlets.
In the unlikely event of a fault occurring please contact Triton Customer service.
DO NOT remove the shower from the installation.
Page 25
Aquasensation AS2000X
23
Entry Points
Diagram Key:
Water Entry Points
Cable Entry Points
Page 26
Aquasensation AS2000X
24
Page 27
Aquasensation AS2000X
25
Page 28
Triton Showers Triton Road Nuneaton Warwickshire CV11 4NR
Triton is a division of Norcros Group (Holdings) Limited
Customer Service: % 0844 980 0750
Trade Installer Hotline:
%
0844 980 0730
Fax:
0844 980 0744
www.tritonshowers.co.uk
E-mail: serviceenquiries@tritonshowers.co.uk
TRITON reserve the right to change product specification without prior notice. E&OE. © TRITON SHOWERS 2012
Extended Warranty AVAILABLE NOW. Call 0844 980 0740 for more details.
UK SERVICE POLICY
In the event of a product fault or complaint occurring, the following procedure should be followed:
1. Telephone Customer Service on 0844 980 0750 having available,
your details including post code, the model number and power rating of the product, together with the date of purchase and, where applicable, details of the particular fault.
2. If required, the Customer Service Advisor will arrange
for a qualified engineer to call.
3. All products attended to by a Triton service engineer must be
installed in full accordance with the Triton installation guide applicable to the product. (Every product pack contains an installation
guide, however, they can also be bought via our Customer Service Spares Department).
4. Our engineer will require local parking and if a permit is required this
must be available to the engineer on arrival at the call.
5. It is essential that you or an appointed representative (who must
be over 18 years of age) is present for the duration of the service
engineer's visit. If the product is in guarantee you must produce proof of purchase.
6. Where a call under the terms of guarantee has been booked and
the failure is not product related (i.e. scaling and furring, incorrect
water pressure, pressure relief device operation or electrical/plumbing installation fault) a charge will be made. A charge will also be issued
if nobody is at home when the service engineer calls or adequate parking/permit is not available.
7. If the product is no longer covered by the guarantee an up front
fixed fee will be charged before the site visit.
8. Should proof of purchase not be available on an “in-guarantee” call,
or should the service engineer find that the product is no longer under guarantee, the engineer will charge the same fixed price and the customer will be expected to pay the engineer before he leaves. If payment is not made on the day an administration charge will be added to the fixed charge.
9. If a debt is outstanding from a previous visit, or from any other Triton
purchase. Triton reserves the right to withhold service until the debt has been settled.
10. Triton takes the health, safety and wellbeing of its employees very
seriously and expects customers to treat all staff members with respect. Should any employee feel threatened or receive abuse, either verbally or physically, Triton reserves the right to withhold service and will support the employee with a legal prosecution.
Replacement Parts Policy
It is the policy of Triton Showers to maintain parts availability for the duration of production and a period of 5 years thereafter in accordance with industry standards. In the event of a spare part not being available a substitute part will be supplied.
Spare parts can be ordered via our online spare parts store, or by telephoning Triton Spares Department. Payment should be made by credit/debit card (excluding American Express or Diners Card). Payment can also be made by pre-payment of a pro-forma invoice, by cheque or postal order.
Telephone orders are based on information given during of the call. Before contacting Triton, please verify your requirements using the information contained in the user guide. Triton cannot accept liability for incorrect part identification.
TRITON STANDARD GUARANTEE
Triton guarantee this product against all mechanical and electrical defects arising from faulty workmanship or materials for a period of one year for domestic use only, from the date of purchase, provided that it has been installed by a competent person in full accordance with the fitting instructions.
Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge so long as it has been properly maintained and operated in accordance with the operating instructions, and has not been subject to misuse or damage.
This product must not be taken apart, modified or repaired except by a person authorised by Triton. This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially. This guarantee does not affect your statutory rights.
What is not covered:
1. Breakdown due to: a) use other than domestic
use by you or your resident family; b) wilful act or neglect; c) any malfunction resulting from the incorrect use or quality of electricity, gas or water or incorrect setting of controls; d) failure to install in accordance with this installation guide.
2. Repair costs for damage caused by foreign
objects or substances.
3. Total loss of the product due to non-availability
of parts.
4. Compensation for loss of use of the product or
consequential loss of any kind.
5. Call out charges where no fault has been found
with the appliance.
6. Call out charges where the water supply cannot
be isolated, this includes consequential losses arising from unserviceable supply valves.
7. The cost of repair or replacement of pressure
relief devices, showerheads, hoses, riser rails and/or wall brackets, isolating switches, electrical cable, fuses and/or circuit breakers or any other accessories installed at the same time.
8. The cost of routine maintenance, adjustments,
overhaul modifications or loss or damage arising therefrom, including the cost of repairing damage, breakdown, malfunction caused by corrosion, furring, pipe scaling, limescale, system debris or frost.
3-1-2012
Loading...