Triton AS2000 SR User guide

Page 1
AS2000 SR
Power Shower
Installation and Operating Instructions
Installers: please note these
Instruc tIons are to be left wIth the user
IMPORTANT SAFETY ADVICE
The shower unit MUST BE switched off at the isolating switch when
not in use. This is a safety procedure recommended for all electrical appliances.
The showerhead and hose supplied with this product are a safety critical part of your shower. Failure to use genuine Triton parts may cause injury and invalidate your guarantee.
2181606C - September 2019
Page 2
INTRODUCTION - PLEASE READ
WARNING
T
his appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have
been given supervision or instruction concerning use of the
appliance in a safe way and understand the hazards involved.
C
hildren may not play with the appliance. Cleaning and user
maintenance shall not be made by children.
Power Shower
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Products manufactured by Triton are safe and without risk provided they are installed, used and maintained in good working order in accordance with our instructions and recommendations.
WARNING: DO NOT operate shower if frozen, or suspected of being frozen.
It must thaw out before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged. DO NOT restrict ow out of the shower by placing showerhead in direct contact
with your body.
DO NOT operate the shower if water ceases to ow during use or if water has
entered inside the unit because of an incorrectly tted cover.
The spray head must be descaled regularly. Fit only showerheads recommended by the manufacturer and never t any
additional device to restrict the water outlet ow.
The outlet must not be connected to any tap or tting other than those specied. This appliance must not be connected to the water mains supply and not
connected by a hose set.
Minimum inlet pressure 0.075 metres 0.75kPa (0.0075 bar) Maximum inlet pressure 10 metres 100kPa (1 bar)
This book contains all the necessary tting and operating instructions for your power shower.
Care taken during the installation will provide a long, trouble-free life from your shower.
2
Page 3
IMPORTANT - PLEASE READ THESE
Power Shower
GENERAL GUIDANCE NOTES BEFORE PROCEEDING
1 GENERAL
1.1 Isolate the electrical and water supplies before
removing the cover.
1.2 Read all of these instructions and retain them
for later use.
1.3 DO NOT take risks with plumbing or electrical
equipment.
1.4 Isolate electrical and water supplies before
proceeding with the installation.
1.5 The unit must be mounted onto the nished
wall surface (on top of the tiles). DO NOT tile up to or seal around ANY PART of the unit using silicone sealer after xing to the wall.
1.6 Contact Customer Service (see back page for
contact details), if any of the following occur:
a) If it is intended to operate the shower at
pressures above the maximum or below the minimum stated.
b) If the unit shows a distinct change in
performance.
c) If the shower is frozen.
1.7 If it is intended to operate the shower in areas
of hard water (above 200 ppm temporary hardness), a scale inhibitor may have to be tted. For advice on the scale inhibitor, contact Customer Service.
1.8 The showerhead must be cleaned regularly
with descalent to remove scale and debris.
1.9 This product is not suitable for mounting into
steam rooms or steam cubicles.
2
PLUMBING
2.1 The plumbing installation must comply with
Water Regulations, Building Regulations or any particular regulations as specied by Local Water Company or Water Undertakers and
should be in accordance with BS EN 806.
2.2 DO NOT connect the shower unit to the mains
cold water supply as it will damage the unit and the installation will be in breach of water regulations.
2.3 The supply pipe must be ushed to clear debris before connecting to the shower unit.
2.4 DO NOT solder pipes or ttings within 300mm of the shower unit, as heat can transfer along the pipework and damage components.
2.5 DO NOT use excessive force when making connections to the exible hose or showerhead, nger tight is sufcient.
2.6 All plumbing connections must be completed before making the electrical connections.
2.7 Water supplies must be turned on before switching on the electricty. The shower must not be operated dry without water.
2.8 This appliance MUST NOT be connected to the inlet supply by a hose-set.
2.9 When installed, the top of the shower unit must be at least 75mm lower than the base of the cold water storage cistern to prevent the pump being run dry without water.
2.10 A dedicated cold water supply must be taken directly from the cold water cistern to the shower. This draw-off must be on the opposite
side of the cistern to the oat operated valve to reduce the risk of air entering the unit.
2.11 The action of the pump is to increase the ow rate. If the supply pipework cannot handle the resulting ow rate then:
2.11.1 The anticipated ow rate may not be achieved.
2.11.2 Air may be drawn into the hot supply from the vent pipe causing spluttering and temperature uctuations at the showerhead.
2.12 Fullway isolating valves must be tted on the hot and cold water supplies to the shower as an independent means of isolating the water supplies should maintenance or servicing be necessary. Do not use stop taps or ball-o-x type valves which restrict ow.
If this isolator is tted in a loft space, the loft
must have a xed access ladder and be boarded, with appropriate lighting from the access point to the isolator.
3
ELECTRICAL
3.1 The installation must comply with BS 7671
‘Requirements for electrical installations’ (IEE wiring regulations), building regulations or any particular regulations as specied by the local Electrical Supply Company.
3.2 In accordance with ‘The Plugs and Sockets etc. (Safety) Regulations 1994’, this appliance is intended to be permanently connected to the xed wiring of the electrical mains system.
3.3 Make sure all electrical connections are tight to prevent overheating.
3.4 Fuses do not give personal protection against electric shock. A 30mA residual current device (RCD) MUST be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
3.5 Switch off immediately at isolating switch if water ceases to ow during use.
3.6 Other electrical equipment i.e. extractor fans, pumps, must not be connected to the circuits within the unit.
3.7 Switch off at isolating switch when not in use.
This is a safety procedure recommended with all electrical appliances.
3.8 Do not turn on the electrical supply until the plumbing connections have been completed.
3.9 The mains supply must be 230/240V, at 50Hz, connected to the unit via a double pole switched 3 Amp fused connection unit (not supplied) with a minimum 30mm contact separation gap in each pole.
3.10 As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage.
3
Page 4
Power Shower
To check the product suitability for commercial and multiple installations, please contact Triton’s specication advisory service before installation. Please see back of book for contact information.
Find our step-by-step installation video for this product on our YouTube
channel. Go to youtube.com/TritonShowers and search for 'how to guides'.
CONTENTS Page
INTRODUCTION
IMPORTANT SAFETY INFORMATION & GENERAL GUIDANCE NOTES (please read)
SPECIFICATIONS ..................................................................................................... 5
MAIN COMPONENTS..............................................................................................6
WATER AND CABLE ENTRY POINTS ........................................................................ 7
SITE REQUIREMENTS & RECOMMENDED INSTALLATION .................................8 - 9
GENERAL INSTALLATION NOTES ............................................................................ 9
SITING OF THE SHOWER ...................................................................................... 10
PLUMBING CONNECTIONS ..........................................................................11 - 12
FITTING THE SHOWER TO THE WALL ............................................................12 - 13
ELECTRICAL CONNECTIONS ................................................................................ 14
COMMISSIONING .........................................................................................15 - 16
TEMPERATURE CONTROL SET UP ......................................................................... 17
OPERATING THE SHOWER .................................................................................... 18
CLEANING THE FILTERS ........................................................................................ 19
FAULT FINDING .............................................................................................20 - 21
SPARE PARTS ......................................................................................................... 22
GUARANTEE, SERVICE POLICY, ETC. ..................................................... REAR COVER
4
Page 5
Power Shower
IMPORTANT
The shower installation must be carried out by a suitably competent person and in sequence of this instruction book.
Please read through the whole of this book before beginning your installation.
DO NOT use jointing compounds on any pipe fittings for the installation.
Switch off immediately at the isolating switch if water ceases to flow during use.
DO NOT operate the shower outside the guidelines laid out in ‘site requirements’.
SPECIFICATIONS
Hot Water Temperature
Maximum temperature 65°C. A stored water temperature of 60°C is considered sufficient to meet all normal requirements and will minimise the effects of scale in hard water areas.
Temperature Control
To obtain the maximum performance, this unit should be installed, operated and maintained as instructed in this book. Optimum performance is achieved with water supplies of 15°C cold and 60°C hot and with nominally equal pressures.
Maximum static inlet pressures
100 Kpa (1 bar) or 10m (supplies must be gravity fed at nominally equal pressures).
Minimum static inlet pressure
0.75 Kpa (0.0075 bar) or 75mm (required to
prime the integral centrifugal pump).
Maximum total head 2m
This is the vertical distance that you are able to pump the water.
5
Page 6
Power Shower
`
1
Fig.1
3
7
11
3
6
2
8
9
3
10
5
3
4
MAIN COMPONENTS
1. Cover screw fixing
2. Motor retaining bracket
3. Wall fixing holes
4. Pipe inlets – swing (contains single check valves)
5. Filter cover
6. Pump
1
7. PCB / power supply
8. Setting ring
9. Temperature control valve
10. Solenoid outlet
11. Cover connector
Cover outline
6
Page 7
Power Shower
HC
C
H
Swivel water inlet feature for top or bottom connection
Fig.2
Entry Points Key:
C
H & C Water
Entry Points
Cable
Entry Points
H
Rear Entry
Rear Entry
H C
7
Dimensions:
H: 292mm
W:
219mm
D: 115m m
Page 8
Power Shower
Fig.3a - Recommended Installation (Diagrammatic view – not to scale)
Mains supply
Isolating
valve
Drain valve
Isolating
valve
Cold water cistern
Vent pipe tee
Hot water
cylinder
Other hot water
draw-offs
Hot supply
Fig.3b - Incorrect Connections (Diagrammatic view not to scale)
Dedicated cold supply
10m
75mm
max
min
Isolating
valves
Alternative connection
25mm min
Shower unit
Ring main
Isolating spur
(3A fused)
outside bathroom
8
Page 9
Power Shower
SITE REQUIREMENTS
Water
The installation must be in accordance with Water Regulations/Bylaws and BS-EN 806.
For correct operation of this shower unit, both hot and cold water supplies to the appliance must be gravity fed, at nominally equal pressures, from a cold water storage cistern and a hot water storage cylinder. The water circuit should be installed so that the flow is not significantly affected by other taps and appliances being operated elsewhere on the premises.
Fig.3a shows a recommended installation where the hot water supply for the shower is made via a tee connection on the underside of the
horizontal section of pipework from the cylinder. Alternatively, the connection can be
taken from the hot supply pipe to other outlets as long as it is the first draw-off below the ventilation pipe tee.
IMPORTANT: Failure to conform to Fig.3a can allow air ingress into the product which can impair performance and may invalidate the guarantee.
Fig.3b illustrates incorrect connections that must be avoided.
All pipework to the shower unit must be routed where it remains below the level of water in the cistern. In the case of horizontal sections of pipework in lofts, it may be necessary to fit automatic air vents at high points on the supplies to remove the possibility of air locks.
For the operation of the shower only, it is recommended that the cold water storage cistern is capable of holding at least 114 litres (25 gallons). Where other hot and cold outlets are likely to be in use simultaneously, the storage capacity should be increased to 228 litres (50 gallons) in accordance with BS-EN 806.
DO NOT connect to a combination cylinder unless there is a guaranteed 114 litre cold supply to the cylinder as the shower can deliver up to 14 litres per minute. It is advisable to check that the infill rate from the float operated valve meets the output requirements. It is recommended that there is a minimum of approximately 114 litres (25 gallons) of hot water storage per appliance.
Under no circumstances should this product be connected to mains cold or hot water supplies. Failure to comply will invalidate the guarantee.
GENERAL INSTALLATION NOTES
1. DO NOT take risks with plumbing or electrical equipment.
2. Isolate electrical and water supplies BEFORE proceeding with installation work.
3. Shower control MUST be fed from a cold water storage cistern and hot water cylinder that provides nominally equal pressures.
4. If installing with rear inlet supplies, it is recommended the supply pipework is sealed to the wall so as to prevent water from leaking back into the wall.
5. In solid wall installations, the supply pipework should be housed within ducting in order to allow some free lateral movement when making connections and to ensure compliance with requirements of accessibility of pipes and pipe fittings.
Fig.4 shows a schematic wiring diagram of the unit.
Fig.4
Thermal fuse
L E N
Motor
Solenoid
Potentiometer
Switch
PCB
9
Page 10
Power Shower
Shower can be mounted
either side of
the riser rail
Spill-over
level
Ceiling
Use soap dish
retaining ring
Height of
sprayhead
and shower
to suit user’s
requirement
Shower unit must not be
within an area
1 metre
from base
Space for cover
screw access
Rotate inlets upwards
Re-secure screw
Remove screw
Fig.5
Fig.6
SITING OF THE SHOWER
WARNING!
The shower must not be
positioned where it will be
subject to freezing conditions.
IMPORTANT: The unit must be mounted onto
the finished wall. NEVER tile up to the unit.
Refer to fig.5 for correct siting of the shower.
Position the unit vertically where it will NOT be in direct contact with water from the showerhead. Allow sufficient room between the ceiling and the shower unit to access the top cover screw.
Position the shower and showerhead on the wall so that all controls can be comfortably reached when using the shower.
The showerhead and riser rail can be positioned either side of the shower unit.
Note: Water Regulations require the showerhead be ‘constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill-over level of the relevant bath, shower tray or other fixed appliance’. The use of the supplied soap dish will in most cases meet this requirement, but if the showerhead can be placed within a bath, basin or shower tray, then a device must be fitted to prevent back-flow.
Fig.7
DECIDE ON WATER ENTRY
Decide the position of the shower in relation to water pipe entry. The unit will be supplied with the inlets in the bottom position.
If top or rear entry is required carefully lift the cover away from the backplate and lay aside until needed later.
Remove the inlet retaining screw from the pipe inlet (fig.6) and swing inlets upwards to the top position and re-secure with the screw (fig.7).
10
Page 11
Power Shower
19 mm
26 mm
Cold
Hot
Wall
Fully engage exposed
pipe protruding
from wall
23.5 mm
PLUMBING CONNECTIONS
Plumbing to be carried out before wiring
Note: The outlet of the shower must not be
connected to anything other than the hose and showerhead supplied.
When connecting pipework avoid using tight 90° elbows. Swept or formed bends will give optimum performance.
Isolate the mains water supply to the cold water cistern. Drain the hot and cold pipes by opening all taps.
The hot water supply can be taken from the hot supply pipe from the cylinder. Make sure that it is the first draw-off below the ventilation pipe tee in order to minimise the effects of water draw-off elsewhere in the house (see fig.3a).
Note: There must not be any other draw-offs between the take-off point and the shower.
A dedicated cold water supply must be taken directly from the cold water cistern to the shower. This draw-off must be positioned 25mm below the cold feed connection to the hot water cylinder on the opposite side of the cistern to the float operated valve (see fig.3a). This minimises air ingress into the pipework.
Plumbing options other than those outlined in these fitting instructions could impair the performance. For example, if hot and cold connections are made after draw-off points to other outlets, e.g. washing machine, taps, etc. it could result in unstable flows and temperatures should other appliances operate at the same time.
Run the hot and cold pipework to the shower position. To avoid air locks, make sure that the pipework does not rise above the level of water in the cold cistern at any point. Under normal site conditions 15mm pipework will be adequate.
Cut the pipework to the dimensions relevant to the chosen direction of water entry into the shower.
When fitting elbows to incoming pipework, ensure the elbows are fully engaged with the exposed pipe.
Dimensions are shown in fig.8 and fig.9.
Fig.8
122mm
Top
Rear
44.5 mm
Bottom
Fig.9
26 mm
Hot Cold
cover
Rear edge of cover
19 mm
Wall
11
Page 12
Power Shower
Bottom
(rising) supply
Top
(falling)
or rear supply
Hot side
Hot side
Top
(falling)
or rear supply
Hot side
Fig.10
Fig.11
Fig.12
The pipe inlets are marked for hot and cold connections – left-hand side for hot inlet on bottom entry (fig.10) and right-hand side for hot inlet on top or rear entry (fig.11).
IMPORTANT: The fittings on the inlets are the push-in type. DO NOT insert fingers into the push-in inlet fittings, doing so could cause injury. The pipework must be cut with a pipe cutter and all burrs and rough edges removed from the end of the tube. The fittings can be used with copper and plastic pipe. If using chrome plated copper pipe, remove the first 25mm of plating completely from the connecting surfaces. If not completely removed then the collet will not grip the pipe and under pressure the pipe may be forced out.
Pipework must be clipped or fixed to the wall so that it cannot be moved or removed without the aid of a tool.
Note: The pipe inlets contain filters. These should be periodically removed and cleaned in order to maintain the performance of the shower. See section Cleaning the Filters’ on how to access them.
IMPORTANT: The inlets contain check valves. Before completing the connection of the water supplies to the shower, flush out the pipework to remove all swarf and system debris that may cause damage to internal parts. This can be achieved by connecting a hose to the pipework and turning on the water supplies long enough to clear the debris to waste.
Bottom
Top
Fig.13
FITTING SHOWER TO THE WALL
Depending on whether top, bottom or rear pipe entry has been chosen, fit pipe trims to suit chosen installation (fig.12 and fig13).
If the cover has not already been removed to change the position of the pipe inlets, carefully lift the cover away from the backplate and lay aside until needed later.
Offer the backplate unit up to the completed pipework and manoeuvre so that the end of the pipes fully enter into the inlet fittings.
12
Page 13
Power Shower
Fig.14
Fig.15
Using the backplate as template, mark the positions for the four wall fixing holes (fig.14).
Using the pipe removal tool supplied, push back and hold the collets from the pipework to disengage the pipework from the inlets (fig.15).
Remove the unit from the wall.
Drill and plug the wall using the appropriate drill and fixings for the wall type (i.e. brick, plasterboard)
Note: If fitting rising supplies to the unit, ensure debris does not enter the pipes when drilling the wall.
Offer the backplate unit back up to the completed pipework and again manoeuvre so that the end of the pipes fully enter into the inlet fittings.
Check the backplate is square and the fixing holes are aligned and secure to the wall.
Once the backplate is secured, add retaining clips to hot and cold inlets as shown in fig.16. This will prevent pipes from moving by locking the push fit collets.
Fig.16
13
Page 14
Power Shower
LIVE CONNECTION
(Brown or Red Wire)
NEUTRAL CONNECTION
(Blue or Black Wire)
ELECTRICAL CONNECTIONS
This product does not require earthing, however, the supply cable must conform to relevant tables in current IEE regulations. In most cases
0.75 mm² twin cable
If replacing an existing Triton Power Shower then the floating earth can still be terminated at the product terminal block.
ENSURE THE ELECTRICITY SUPPLY IS SWITCHED OFF AT THE MAINS.
Cable entry points are shown in fig.2.
Route the cable into the shower, taking care to avoid the area of the wall fixings and connect to the terminal block (fig.17) as follows:
Neutral cable to terminal marked N
Live cable to terminal marked L
Earth cable (If present) to terminal marked E
IMPORTANT: Make sure wires are within the terminal block clamps and not undernreath. Fully tighten the terminal block screws and check that no cable insulation is trapped under the screws or clamps.
Note: Fuses do not ensure user protection against electric shock. In the interest of electrical safety, all mains electric and pumped showers should be fitted with a 30mA residual current device (RCD). This may be part of the consumer unit or a separate unit.
DO NOT switch on the electricity supply until the water has been turned on to the unit and connections have been tested for leaks.
Fig.17
14
Page 15
Commissioning ON
(switch in UP position)
Pump will not operate
Maximum temperature stop
Overide button
Maximum temperature stop
Start/stop button
Correctly tted
cover connector
(PCB pins aligned)
Incorrectly tted cover connector
(PCB pins misaligned)
Fig.19
Power Shower
COMMISSIONING
WARNING! BEFORE NORMAL OPERATION OF THE SHOWER, IT IS ESSENTIAL THAT THE COMMISSIONING AND SET UP PROCEDURE ARE CORRECTLY COMPLETED. FAILURE TO DO SO COULD CAUSE THE PUMP TO RUN DRY WITHOUT WATER AND INVALIDATE THE GUARANTEE.
The first operation of the shower is intended to flush out any remaining system debris and to
Fig.18
ensure water is purged through the unit. This operation must be carried out with the flexible hose screwed to the shower outlet but without the showerhead attached. Make sure the outlet of the hose is directed to waste and the isolating valves controlling the water supply to the unit are fully open.
On the PCB, ensure the dip switch is in the ON position (fig.18) to allow commissioning without pump operation.
Fit the cover assembly, attaching the 8 way connector leads to the 8 way pins on the PCB (fig.19)this will only fit one way. DO NOT let the cover dangle by the lead. Offer the cover to the unit and temporarily secure using the screws provided.
Fig.20
WARNING!
COVER RETAINING SCREWS
ONLY the SUPPLIED SCREWS should be
used. The use of non supplied screws WILL
invalidate product specications & guarantee.
Fit the temperature control knob with the override button just to the right of vertical position, ensuring the travel stop engages with the maximum temperature stop (fig.20).
Switch on the electricity supply at the isolating switch. Start the unit by pressing the start/stop button (fig.20). Water will begin to flow under gravity pressure.
15
Page 16
Power Shower
Commissioning OFF
(switch in DOWN position)
Pump will operate
12 O’clock postion
In order to dispel air and to prime both supplies to the shower unit, turn the temperature control several times within its rotational limits.
Note: The temperature control is fitted with a maximum temperature stop, pressing the override is required to achieve fully hot position.
(fig.21). ONCE RESISTANCE IS FELT, DO NOT FORCE THE CONTROL FURTHER.
To stop the water flow, press the start/stop button to switch off the unit and isolate the electricity supply at the isolating switch. Remove the temperature control knob and front cover assembly, unplugging the 8 way connector lead from the PCB and carefully put both aside.
Check for leaks in the pipework and remedy if necessary. If rear entry has been used then seal around pipes with mastic to prevent the possibility of water entering the wall cavity. DO NOT use plaster as this could cause difficulties if maintenance is required at a later date.
Set up Procedure
On the PCB, position the dip switch to the OFF position to allow pump operation (fig.22).
Check the maximum temperature stop is still in position at 12 O'clock (fig.23).
Make sure the start/stop button on the front cover assembly is in the OFF position (flush with the cover). Attach the 8 way connector lead to the 8 way pins on the PCB (refer back to fig.19) and offer the front cover assembly to the unit. Ensure the wires are clear of the front cover assembly and secure with the screws provided.
Switch the electricity supply back on at the isolating switch. Make sure both water supplies are still turned on.
Once the installation of the riser rail is complete, the shower will be ready for temperature control set up and then normal operation.
Fig.21
Hot Cold
Fig.22
Fig.23
16
Page 17
Power Shower
3 O’clock postion
Maximum temperature stop
Fig.24
Fig.25
Fig.26
TEMPERATURE CONTROL SET UP
On the temperature valve you will see a mark on the brass valve spindle when positioned at 3 O'clock (fig.24), this is the factory setting.
Important
As a safety feature the shower has a built-in maximum temperature stop to prevent accidental rotation to higher temperatures.
The mixed water temperature can be adjusted from cold through to a top limit, which can be preset during installation.
Increasing Maximum Temperature
Stop
To increase the maximum temperature above the factory setting, operate the shower unit by pressing the start/stop button and rotate the brass valve spindle anti-clockwise (fig.25) until desired temperature is reached, making sure this is a settled temperature from handset - use the temperature knob to move spindle. This will now become your new maximum temperature stop setting. Do not move the spindle again at this point.
Fit the temperature control knob with the override button just to the right of vertical position, ensuring the travel stop engages with the maximum temperature stop. Operate the shower making sure you have the desired temperature setting, re-adjust if required. Secure the temperature knob in place with the retaining screw and push fit the screw trim into place ensuring the cutout at the bottom of the trim engages with the ridge in the bottom of the screw hole (fig.26).
17
Page 18
Power Shower
OPERATING THE SHOWER
Make sure all plumbing and electrical supplies are connected and switched on.
To start the shower, press the start/stop button (fig.27).
Adjust the flow control (fig.28) until the flow rate is satisfactory.
For maximum flow, turn the flow control fully clockwise. For minimum flow, rotate the flow control fully anti-clockwise.
To adjust the water temperature, rotate the temperature control clockwise for cold and anti­clockwise for hot (fig.29).
To stop the shower, press the start/stop button once more. This stops the pump and water flow.
The shower should be isolated from the electricity supply after use, unless it is to be used again immediately.
As a safety feature, the temperature control has a built-in stop to prevent accidentally exceeding your highest desired temperature. If adjustment is required see section ‘Temperature Control Set up’.
To override this stop, press the button (fig.26) while the control is up against the stop and turn the control anti-clockwise to the higher temperature settings. To return to the normal temperature range just turn the temperature control clockwise until it is past the maximum temperature stop. Make sure that the temperature control is in the normal temperature range when the shower is switched off. The stop comes in a factory set position based on water supply temperatures in SPECIFICATION on
Pg.5.
Note: As the flow control is adjusted it is quite
normal for the sound of the pump to alter in pitch.
Fig.27
Fig.28
Fig.29
18
Page 19
Power Shower
INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY
CLEANING THE FILTERS
Fig.30
WARNING!
Switch off the electricity supply
and turn off both hot and cold
water supplies to the unit before
proceeding further.
To remove the cover, first remove the screw trim from the temperature control knob and then remove the retaining screw.
Remove the temperature control.
Remove the top and bottom cover fixing screws and carefully lift the cover away from the backplate.
Note: Be aware of the lead connected to the PCB unit. Carefully pull the lead from the PCB. DO NOT let the cover dangle by the lead.
Remove the single retaining screw from the centre of filter cap (fig.30). Carefully remove the filters and the ‘O’ rings. Thoroughly clean the filters and replace. Refit the filter cap ensuring the ‘O’ rings are back in position. Secure filter cap with the retaining screw.
Make sure the valve spindle is correctly aligned. See section ‘Temperature Control Set Up’.
Offer the cover to the unit and reattach the connector lead to the PCB. Ensure the wires are clear of the cover. Secure the cover with the top and bottom fixing screws.
Refit the temperature knob with the override button just to the right of vertical position, ensuring the travel stop engages with the maximum temperature stop (g.26).
Secure the temperature knob in place with the retaining screw and push fit the screw trim into place.
Retaining screw
19
Page 20
Power Shower
FAULT FINDING
IMPORTANT: Switch OFF the electricity at the mains supply and remove the correct circuit fuse before attempting any fault finding inside the unit.
Any maintenance or repair to the shower must be carried out by a suitably competent person.
In the unlikely event of a fault occurring please contact Triton Customer service. DO NOT remove the shower from the installation.
Symptom Cause Action/Cure
1 Water too hot.
2 Water too cold.
3 Pump does not
operate.
1.1 Not enough cold water flowing through shower.
1.2 Increase in the ambient cold water temperature.
1.3 Cold inlet filter blocked or check valve sticking.
1.4 Cold water supply blocked or cut off.
2.1 Not enough hot water flowing through shower.
2.2 Decrease in ambient cold water temperature.
2.3 No hot water in the storage cylinder.
2.4 Hot inlet filter blocked or check valve sticking.
2.5 Hot water supply blocked or otherwise cut off.
3.1 Interrupted power supply.
3.2 Electrical malfunction.
3.3 Motor overheated.
3.4 Start/stop switch not
connected.
1.1.1 Turn the temperature control clockwise.
1.2.1 Turn the temperature control clockwise.
1.3.1 Remove filter and clean. If problem is with
check valve, contact Customer Service.
1.4.1 Isolate shower and consult a competent plumber or contact Customer Service.
2.1.1 Turn temperature control anti-clockwise.
2.2.1 Turn temperature control anti-clockwise.
2.3.1 Turn shower off and wait for hot water
cylinder to reheat.
2.4.1 Remove filter and clean. If problem is with check valve, contact Customer Service.
2.5.1 Turn shower off. Consult a competent plumber or contact Customer Service.
3.1.1 Blown fuse. Check supply. Renew fuse. If it fails again consult a competent electrician.
3.1.2 Power cut. Check other appliances and if necessary, contact local Electricity Supply Co.
3.2.1 Consult a competent electrician or contact Customer Service.
3.3.1 Thermal protection on motor has operated. Allow appliance to cool and reset itself. If it persists, contact Customer Service.
3.4.1 Remove cover and connect start/stop switch.
20
Page 21
Power Shower
FAULT FINDING
Symptom Cause Action/Cure
4 Water does not flow or is reduced.
5 Cross flow of hot and cold water into system.
6 Water dripping from showerhead when turned off.
7 Pump is noisy.
4.1 Water supplies cut off.
4.2 Shower blocked or air
in the system.
4.3 Showerhead blocked.
4.4 Blocked filters.
5.1 Dirt/debris in check
valves.
6.1 Debris in solenoid valve.
6.2 Potentiometer faulty.
7.1 Air lock in pump.
7.2 Faulty pump.
4.1.1 Check water elsewhere in house and if necessary contact the local Water Company.
4.2.1 Switch off shower and contact Customer Service.
4.3.1 Clean showerhead.
4.4.1 Clean filters.
5.1.1 Isolate water to unit. Remove check valves.
Clean and replace.
6.1.1 Call Customer Service.
6.2.1 Call Customer Service.
7.1.1 Call Customer Service.
7.2.1 Replace pump.
21
Page 22
Power Shower
WEEE Directive – Policy Statement
As a producer and a supplier of electric showers, Triton Showers is committed to the protection of the environment via our own environmental policy and the compliance with the WEEE directive.
Triton Showers is fully registered with the Environment Agency under the following schemes:
Repic: Producers take-back scheme (PTS), registration number WEE/EJ3466QV
Valpak: Distributor take-back scheme (DTS), registration number 9659
All our electric products are labelled accordingly with the crossed out wheeled bin symbol. This indicates, for disposal purposes at end of life, that these products must be taken to a recognised collection points, such as local authority sites/local recycling centres; this will be free of any charges. Do not return to Triton Showers.
To purchase a genuine Triton spare part for your product, please visit
www.tritonshowers.co.uk/spares
for product codes and prices. Alternatively please call our Customer Services team on 024 7637 2222 to order direct.
Please have your model name available.
22
Page 23
Power Shower
23
Page 24
In the event of a product fault or complaint occurring,
UK SERVICE POLICY
the following procedure should be followed: DO NOT REMOVE THE PRODUCT
1. Telephone Customer Service on 024 7637 2222 having
available your details including post code, the model number and power rating of the product, together with the date of purchase and, where applicable, details of the particular fault.
2. If required, the Customer Service Advisor will arrange for a quali ed engineer to call.
3. All products attended to by a Triton service engineer must be installed in full accordance with the Triton installation guide applicable to the product. Every product pack contains an installation guide, however, they can also be downloaded free at www.tritonshowers.co.uk.
4. Our engineer will require local parking and if a permit is required, this must be available to the engineer on arrival at the call.
5. If loft access is required for isolation or to complete a repair, the loft must have a  xed access ladder and be boarded, with appropriate lighting from the access point to and around the repair area.
6. It is essential that you or an appointed representative, who must be over 18 years of age, is present for the duration of the service engineer’s visit. If the product is in guarantee you must produce proof of purchase.
7. Where a call under the terms of guarantee has been booked and the failure is not product related (i.e. scaling and furring, incorrect water pressure, pressure relief device operation or electrical/plumbing installation fault) a charge will be made. A charge will also be issued if nobody is at the property when the service engineer calls or adequate parking/permit is not available.
8. If the product is no longer covered by the guarantee an up-front  xed fee will be charged before the site visit.
9. Your receipt must be retained as proof of purchase. Should proof of purchase not be available on an ‘in-guarantee’ call, or should the service engineer  nd that the product is no longer under guarantee, the engineer will charge the same  xed price and will request payment prior to departing. If payment is not made on the day an administration charge will be added to the  xed charge.
10. If a debt is outstanding from a previous visit, or from any other Triton purchase, Triton reserves the right to withhold service until the debt has been settled.
11. Triton takes the health, safety and wellbeing of its employees very seriously and expects customers to treat all staff members with respect. Should any employee feel threatened or receive abuse, either verbally or physically, Triton reserves the right to withhold service.
Replacement Parts Policy
In line with AMDEA guidelines, Triton retains functional spares for as long as there is a market for them and in most cases, well beyond. Due to the vast array of product types, the life cycle of products can vary and therefore so can the length of time parts can be supplied. Spare parts can be ordered via our online spare parts store or by telephoning Triton Customer Service Spares Department on 024 7637 2222. Payment should be made by credit / debit card (excluding American Express or Diners Card). Payment can also be made by pre-payment of a pro-forma invoice, by cheque or postal order.
Telephone orders are based on information given during the call. Before contacting Triton, please verify your requirements using the Triton website or your professional installer. Triton cannot accept liability for incorrect part identi cation.
Triton Showers Triton Road Nuneaton Warwickshire, CV11 4NR
Triton is a division of Norcros Group (Holdings) Limited
Triton reserve the right to change product speci cation without prior notice. E&OE. © TRITON SHOWERS 2019
TRITON STANDARD GUARANTEE
With the exception of accessories, Triton guarantee the product against all manufacturing defects for a period of 1 years (for domestic use only) from the date of purchase, provided that it has been installed by a competent person in full accordance with the  tting instructions.
All accessories such as shower heads, hoses and riser rails carry a 1 year parts only guarantee against manufacturing defects.
Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge, so long as it has been properly maintained and operated in accordance with the operating instructions and has not been subject to misuse or damage. This product must not be taken apart, modi ed or repaired except by a person authorised by Triton. This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially. This guarantee does not affect your statutory rights.
What is not covered:
1. Breakdown due to:
a) use other than domestic use by the property occupants;
b) wilful act or neglect; c) any malfunction resulting from the incorrect use or
quality of electricity, gas or water or incorrect setting of controls; d) failure to install in accordance with this installation guide.
2. Claims for missing parts once the product has been installed.
3. Repair costs for damage caused by foreign objects or substances.
4. Total loss of the product due to non-availability of parts.
5. Compensation for loss of use of the product or consequential loss of any kind.
6. Call out charges due to an abortive visit or where no fault has been found with the appliance.
7. The cost of repair or replacement of isolating switches, electrical cable, fuses and/or circuit breakers or any other accessories installed at the same time. Replacement of the Pressure Relief Device that only activates when the shower outlet is blocked is also excluded.
8. The cost of routine maintenance, adjustments, overhaul modi cations or loss or damage arising therefrom, including the cost of repairing damage, breakdown, malfunction caused by corrosion, furring, frost or exposure to freezing conditions.
9. Callout charges where the water supply cannot be isolated, this includes consequential losses arising from unserviceable supply valves, or inaccessible product or valves located in a loft space without suitable access.
For the latest Terms & Conditions please see:
www.tritonshowers.co.uk/terms
Customer Service: 024 7637 2222
Trade Installer Hotline: 024 7637 8344
E-mail: serviceenquiries@tritonshowers.co.uk
E-mail: technical@tritonshowers.co.uk
www.tritonshowers.co.uk
Loading...