Instantaneous water heater appliance capabilities 6
Preparing the mixer valve 7
Siting of the shower 7
Installation 8
Connecting the supply pipes 9
Fitting the fixed head pipework 10
Making good 10
Fitting the faceplate and controls 10
Commissioning 11
Operating the shower 12
Cleaning the filters 12
Cleaning 12
Spare parts 13
Fault finding 14
Guarantee, service policy, etc. rear cover
− 5
− 9
− 11
− 15
To check the product suitability for commercial and multiple installations, please contact
Triton’s specification advisory service before installation.
Telephone: 0870 067 3767
Facsimile: 0870 067 3334
E mail: technical@tritonshowers.co.uk
Dual control thermostati c mixer
INTRODUCTION
This book contains all the necessary fitting and
operating instructions for your Triton Antares
dual control thermostatic mixer shower. Please
read them carefully. Read through the whole of
this book before beginning your installation.
The shower installation
a suitably competent person and in sequence of
this instruction book.
Care taken during the installation will provide a
long and trouble free life from your shower.
For best performance within the specified
running pressure range a minimum flow of eight
litres per minute should be available to both
inlets.
The mixer shower MUST NOT be subjected to
water temperatures above 80°C.
This mixer shower is designed for use with
traditional low pressure ‘gravity’ water systems,
using a cold water cistern and hot water cylinder
as well as for the higher pressure systems found
in the UK up to a maximum of 5 bar running
pressure.
IMPORTANT
with combination and multipoint hot water
appliances, the supplied flow restricters
MUST be installed.
This mixer shower is suitable for fully
modulating type combination boilers and multipoint hot water heaters. It is also suitable for
thermal storage, unvented systems and pumped
gravity systems.
IMPORTANT
instantaneous water heater, make sure it is
capable of delivering hot water at a minimum
switch-on flow rate of 3 litres per minute. At
flow rates between 3 and 8 litres per minute,
the appliance must be capable of raising the
water temperature to a minimum of 52°C.
Water temperature at the inlet to the mixer
must remain relatively constant when flow
rate adjustments are made (refer to the water
heater operating manual to confirm compatibility
with this mixer shower).
: When installing this mixer
: Before installing with a gas
MUST be carried out by
This mixer shower is supplied with an integral
single check valve and integral large area filter
in each inlet. Inlet connections are by ½” BSP to
22mm or 15mm compression (not supplied).
SAFETY WARNINGS
a Layout and sizing of pipework MUST be
such that when other services are used,
pressures at the shower control inlets do not
fall below the recommended minimum.
b DO NOT choose a position where the
shower could become frozen.
c DO NOT connect this mixer shower
to any form of tap or fitting not
recommended by the manufacturer.
d The showerhead MUST be regularly cleaned
to remove scale and debris.
e Conveniently situated service valves in
each inlet supply MUST be fitted as an
independent method of isolating the
shower should maintenance or servicing be
necessary.
f If it is intended to operate the shower
in areas of hard water (above 200 ppm
temporary hardness), a scale inhibitor may
have to be fitted. For advice on the Triton
scale inhibitor, please contact Customer
Service.
g DO NOT operate the shower outside
the guidelines as laid out in ‘site
requirements’.
Replacement parts can be ordered from Triton
Customer Service. See ‘spare parts’ for details and part
numbers.
Due to continuous improvement and updating,
specification may be altered without prior notice.
1
MAIN COMPONENTS
2
3
4
1
8
7
5
6
Dual control thermostati c mixer
Ref Description
1 Mixer valve
2 Trimplate
3 On/Off flow control knob
4 Threaded trim ring
5 Threaded trim ‘O’ ring seal
6 Temperature control knob
7 Trim ring
8 Trim ring seal
−Fixing screws/wall plugs
2
Dual control thermostati c mixer
SITE REQUIREMENTS
The installation must be in accordance with
Water Regulations and Byelaws.
Running water pressure:
Gravity fed – 0.1 bar min.
1.0 bar max.
Mains fed – 1.0 bar min.
5.0 bar max.
Maximum static water pressure:
Gravity and mains – 10 bar
DO NOT connect the mixer shower to
a gravity hot supply and a mains cold
supply (or vice versa).
For the best performance within the specified
running pressure range a minimum flow of eight
litres per minute should be available to both
inlets.
While the mixer shower is operational (open
outlet), inlet pressures must not be capable of
exceeding 7 bar. For effective operation of the
internal seals, the maximum static pressure must
not be exceeded.
Note: On sites where the running pressure is
above 5 bar, the use of a suitably sized pressure
reducing valve fitted in the cold mains supply
pipework can provide nominally equal pressures
at the shower mixer.
The pipework should be installed such that the
flow is not significantly affected by other taps
and appliances being operated elsewhere on the
premises.
Note: Where thermal store systems and
instantaneous gas water heaters are used, if
excessive draw offs take place the boiler may
not be able to maintain an adequate output
temperature. This could result in the shower
temperature becoming noticeably cooler.
Water temperature requirements
Maximum hot water temperature = 80°C
Recommended maximum = 65°C
Minimum hot water temperature = 52°C
Maximum cold water temperature = 20°C
BS 6700 recommends that the temperature of
stored water should never exceed 65°C.
A stored water temperature of 60°C is
considered sufficient to meet all normal
requirements and will minimise the effects of
scale in hard water areas.
Temperature adjustment range
The mixed water temperature can be adjusted
from cold through to a top limit which must
be pre-set during installation with full anti-scald
protection throughout the range (35°C to 40°C)
providing the hot water temperature at the inlet
remains 10°C above the outlet temperature.
Should there be a loss of flow to either incoming
supply then water from the shower will stop or
be reduced to a trickle until both supplies are
restored.
3
Dual control thermostati c mixer
Service
valves
Balanced cold mains supply
Cold mains supply
Mixer
Expansion
vessel
Pressure
reducing valve
Stop tap
Unvented
hot water
storage unit
Safety devices
not shown
Pipework to
fixed head
Pipework to
fixed head
CH flow
Cold
mains
supply
Hot water
CH return
Service
valves
Mixer
valve
Stop
tap
Expansion
vessel
Pressure
reducing valve
Combination
boiler
Fig.2 (diagrammatic view – not to scale)
Fig.3 (diagrammatic view – not to scale)
TYPICAL SUITABLE INSTALLATIONS
a) Instantaneous gas-heated systems,
e.g. combination boilers (fig.2)
The shower control MUST be installed with a
multipoint gas water heater or combination
boiler of a fully modulating design (i.e.
to maintain relatively stable hot water
temperatures).
A drop tight pressure reducing valve
MUST
be fitted if the supply pressures exceed 5 bar
running.
An expansion vessel (shown in
fig.2) MUST
be fitted, and regularly maintained, to ensure
the shower mixer is not damaged by excess
pressures. This may already be installed within
the boiler (check with manufacturer) and is in
addition to the normally larger central heating
expansion vessel.
The layout and sizing of pipework
MUST be
such that nominally equal inlet supply pressures
are achieved and the effects of other draw-offs
are minimised. The hot supply temperature
MUST remain a minimum of 10°C hotter than
the required blend temperature for optimum
performance.
b) Unvented mains pressure systems
(fig.3)
The shower control can be installed with an
unvented, stored hot water cylinder.
For systems with no cold water take off after the
appliance reducing valve, it will be necessary to
fit an additional drop tight pressure reducing
valve when the mains pressure is over 5 bar.
The drop tight pressure reducing valve must be
set at the same value as the unvented package
pressure reducing valve.
Note: An additional expansion vessel (fig.3)
may be required if a second pressure reducing
valve is installed. This does not apply to
packages with a cold take off after the pressure
reducing valve to the cylinder.
The layout and sizing of pipework
such that nominally equal inlet supply pressures
are achieved and the effects of other draw-offs
are minimised.
MUST be
4
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.