Tripp Lite SU6K, SUIOK User Manual

9
TRIPPaUTE
POWER PRorEcTloN
N
11 11
W.
35th Street
Chlcago,
Customer Support:
Application Services: (773) 869-1236
60609 USA
(773) 869-1234
www.tripplite.com
Capyrighl
1
All
ri@u
mrved.
0
MOI
Tripp
tile.
Smam3nlieN
is
a
rcgisterrd
trademark
of
Tripp
Lite.
This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite Systems.
SmartOnline UPS
UPS Location Warnings
Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight. Install your UPS in a structurally sound area. Your UPS care when moving and lifting the unit. Only operate your UPS at indoor temperatures between 32" F and 104" F (between
0"
C and 40" C). For best results, keep indoor temperatures between 62" F and
84" F (between 17" C and 29" C). Leave adequate space around all sides of the UPS for proper ventilation: 12 in. (30 cm.) clearance at the rear; 4 in. (10 cm.) at sides and on top. Do not install the UPS near magnetic storage media, conuption.
is
extremely heavy; take
as
this may result in data
UPS Connection Warnings
The power supply for this unit must be single phase rated in accordance with the
equipment nameplate. It also must be suitably grounded.
Equipment Connection Warnings
Do not use Mpp Lite UPS Systems in life support applications in which a mal­function or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device.
Connect your UPS's Grounding Terminal to a grounding electrode conductor. The SUGK contains its own energy source (battery). The output terminals may be live even when the UPS is not connected to an AC supply.
Battery Warnings
Your UPS does not require routine maintenance. Do not open your UPS for any reason. There are no user-serviceable parts inside. Because the batteries present a risk of electrical shock and bum from high short­circuit current, batteries should be changed only by trained service personnel observing proper precautions. Replace the existing batteries with the same number and type of new batteries [(Sealed Lead-Acid) SUlOK (forty 12V/7AH batteries)]. Do not open the batteries. Do not short or bridge the battery terminals with any object.
The UPS batteries are recyclable. Refer to local codes for disposal requirements, or
if in the USA call 1-800-SAV-LEAD (1-800-728-5323) for complete recycling information. Do not dispose of the batteries in a fire.
Connect only Tripp Lite battery packs to your UPS's external battery connectors. Do not operate your UPS without batteries. Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type. Potentially lethal voltages exist within this unit as long as the battery supply connected. Service and repair should be done only by trained personnel. During
any service work, the UPS should be tumed off or put into manual bypass (see pg.
12).
During "hot-swap" battery replacement (when the UPS
is
connected equipment
in
backup Do not connect or disconnect the battery cabinets while the UPS the battery supply or when the unit
the event of a blackout.
turned
ON)
your UPS will be unable to provide battery
is
SU6K (twenty 12V/7AH batteries);
is
on manual bypass and
not in bypass mode.
is
operating from
is
Familiarize yourself with the location and function of the front and rear panel features before installing and operating your UPS.
0
FRONT
1.
"ON/OFFn Switch:
ON and OFF.
2.
"SELECT" Button:
through different power readings on the LCD Display by momentarily pressing the button; it also allows you to silence the UPS alarm by pressing and holding the button for
3.
LCD Display:
of UPS operating conditions and diagnostic data. It will illuminate after you have properly completed installation and start-up and after the ON.
4.
"I/P (Input) LED:
supply
5.
"AC/DC" (Converter) LED:
UPS's AC/DC converter is activated.
6.
"DC/ACW (Inverter)
UPS's DC/AC inverter
7.
"O/P (Output) LED:
is supplying AC power to connected equipment.
8.
"BYPASS" LED:
mains powerwithout engaging its converter or inverter. Connected equipment will not receive battery power in the event of a blackout.
9.
"BATTERY" LED:
battery to provide connected equipment with can be cancelled by pressing and holding the "SELECT" switch for alarm will be cancelled, but the LED will remain illuminated.
PANEL
UPS
3
seconds.
is
0
SYSTEM
This
present.
This green light will illuminate when the UPS
0
,
5
This momentary rocker switch turns the UPS System's inverter
This button performs two functions: it allows you to browse
backlit
(16x2
character) dot matrix display indicates a wide range
"ON/OFFm Switch
This green light will illuminate constantly to indicate an AC input
This green light will illuminate constantly to indicate the
LED:
This green light will illuminate constantly to indicate the
is
activated.
This green light will illuminate constantly to indicate your UPS
is
This red light will illuminate when the UPS
AC power.
An
is
alarm
0
is
providing filtered
discharging the
will sound which
3
seconds. The
turned
SUBP
REAR PANELS
1.
Manual
in "BYPASS" mode, which must be done before performingany maintenance on the UPS with the connected load supported. (See page 12 for step-by-step into "BYPASS.") While this switch is on "BYPASS." connected equipment will receive filtered AC mains power, but will not receive battery power in the event of a blackout.
2.
Input Terminal Block:
power input. Unscrew and remove terminal block plate for access. The optional SUBP battery pack's IEC-320 connector accepts
3.
Output Terminal Block:
A plate covering the terminal block must be unscrewed and removed for access.
4.
Input Voltage Select Terminal Block:
receive your 208V AC or 240V AC line voltage. A plate covering the terminal block must be unscrewed and removed for access.
5.
External Battery Connector:
SUlOK requires a SU6K or SUlOK systems for extra runtime. Refer to instructions available with the optional SUBP Battery Pack for connection instructions and safety warnings.
6.
Exhaust Fan:
7. AS-400
computer interface via the AS-400 Cable included. It uses AS-400 communications to report UPS status and power conditions. Using this port, an IBMAS-400 computer can automatically save open files and shut down blackout. See "Communications." pg. 13. for details.
8.
"Smart"
workstation or server. It uses RS-232 communications to report UPS and power
conditions. It monitor and manage network power and to automatically save open files and shut down equipment during a blackout. See "Communications." pg. 13. for details.
9.
Dry
indicate line-fail and low-battery status. See "Communications." pg. 14, for details.
10.
Accessory Slot:
to remotely control and monitor your UPS. Contact Tripp Lite Customer Support for more information and a Hst of available tivity products.
11.
"Battery Start" Switch:
UPS and use it as a stand-alone power source when utility-supplied AC power present. The switch enables the
UPS, make sure your UPS and external battery cabinets are properly installed. Press
and hold the "Battery Start" Switch and then press the
UPS ON. To turn it OFF after "cold-start," press the
12.
Battery Fuses (SU6K & SUBP's Only):
battery or battery bank.
13.
AC
14.
AC
15.
Remote "Emergency Power OFF" Connector:
remote emergency shutdown. See "Communications," pg. 14. for details.
16.
Inverter Operation
Switches that should be set to match your input voltage and input frequency. Your input voltage and frequency DIP switch settings WILL
17.
Grounding
IT
recommended conductor size
18.
Stabiltzers:
Bypass Switch:
This red and yellow dial is used
in
one step of putting the
instructions
Use these terminals to connect your UPS to the AC main
its
charger's input power cord.
Use these terminals to connect your UPS to equipment.
Use these terminals to set your UPS's to
Use this to connect Tripp Lite Battery Packs. The
SUlOKBP or SUBP to operate; additional SUBP's
can
be added to
This cools and ventilates the inside of the UPS.
Interface Port:
-232
is
used with Tripp Lite software and the included RS-232 Cable to
Contact Interface Port:
This female DB9 port connects your UPS to an IBM AS-400
its
operating system during a
Interface Port:
This female DB9 port connects your UPS to a
This female DB9 port sends contact-closure signals to
Remove the small cover panel and use optional accessories
SNMP. network management and connec-
This momentaryrocker swltch allows you to "cold-start" your
UPS's DC/AC Inverter. Before
"cold-starling"
"ON/OFF" switch to turn your "ON/OFF" Switch.
The 30A/600V fuses protect your connected
Input Breakers: Output Breaker:
One double-pole circuit breaker controls input power to the
Triple-pole circuit breakers control output power from the
This RJll modular jack allows
DIP
Switches:
NOT
CONVERT the voltage or frequency.
Terminal:
This terminal connects to a grounding electrode conductor.
Behind this removable panel are four DIP
MUST
match your input. Your UPS
IS NOT SAFE TO OPERATE YOUR UPS WITHOUT CONNECTING IT. The
is
8 AWG based on the UL 1778 standard.
These supports extend to keep your UPS from rolling or tipping.
UPS
for going
is
not
your
UPS.
UPS.
INVERTER OPERATION DIP SWITCH SETTINGS
Using a small tool, set the four Inverter Opera­tion DIP Switches (located on the rear panel of your UPS, see pg. your input voltage, input frequency and desired operational mode.
InDut Voltage Selection
(D~P
switch&
(Input Voltage Select Terminal Block)
(SUIOKPM
4-5
for location) to match
#
1
~r
#2)
SHOWN)
NOT
Terminal
CONVERT
Input Voltage
These DIP switches and the Input
Select Block must BOTH be set to match your input voltage. Your UPS WILL the voltage.
Jn~ut Volt= DIP Switch Position Select Terminal Block
240V
#1
DOWN & #2 DOWN
Invut Frequencv Selection
(DIP Switch
Your Input Frequency setting MUST match your input frequency. Your UPS WILL NOT CONVERT the frequency.
Input Frequency DIP Switch Position
60
#3)
Hz
#3
DOWN
Overational Mode Selection
(DIP Switch
The "On-Line" Mode provides on-line operation with zero transfer time. The "Economy" Mode provides line-interactive operation for increased efficiency when on-line protection is unnecessary, thus reducing operating costs without affecting your reliability during
Input Frequency DIP Switch Position
#4)
On-Line Economy
a
power outage.
#4
UP
#4 DOWN
UPS'S output
UPS LOCATION
Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not stack the UPS Systems or external battery packs.
INPUTAND OUTPUT CONNECTION
WIRING
Choose appropriate cabling (depending on current carried; see chart below) to connect your UPS to an AC power supply and your equipment to your UPS:
MODEL
SU6K
SU
SELECTION
RATED
CURRENT
208/240
30A 8 AWG (8mm1/60"C) 50A6AWG (14mrn1/60"C)
IOK
INPUT
I0
3 Wlre
RATED
OUTPW
CURRENT
120-208/240V 103 Wlre
30A 8 AWG (8mm1/6W)
50A6AWG (14mm2/60"C)
RATED
OUE'UT
CURRENT
120V 103Wlre
2 x 32A 6 AWG [14rnm1/60"C)
2 x 50A4 AWG (22mmv/6(PC)
OUTPUT
PROTECnON
CIRCurr
32A 63A
WIRING
CONNECTIONS
Connect your wiring to the input and output terminal blocks located on the lower rear
OFF
panel of your UPS (see figure below). Before cable connection, turn the UPS out the fuse holder. Ensure the cable is fitted with a cable sleeve and
35
connector clamp. The minimum tightening torque is
Ibs. per square inch. Connect
and pull
is
secured by a
the ground wire (typically colored green and yellow) to the terminal marked with the letter "G."
Cable Connection for
AC
INPUT
156-264V50/60HZ
6kVA
or
lOkVA
Output
LUOV
(6kVA
shown)
CAUTION: Observe the appropriate cable connection regulations
1e.g. National Electrical Code (NEC) in the U.S.] at all times. Using cables of improper size may damage your equipment and cause fire hazards.
TOTH,"AEkDING
(GROUND)
+
GROUND
CONNECTION
UPS
Ground the UPS and the load equipment as shown in the figure.
LOAD
1
LOAD
2
LOAD
3
EXTERNAL BATTERY PACK CONNECTION
(SUGK:
Since SUGK models contain internal batteries, connecting external battery packs (to extend runtime) is optional. and require an external battery pack connection to a supplied battery connection cable, insert one end into the External Battery Connector on the rear panel of your UPS and the other end into the Battery Output Connector on the rear panel of the external battery pack. Use the plug on either end of the supplied cable, but make sure that it is fully inserted into the connector. See figure below for daisy-chaining one or more external battery packs to your UPS.
Optional;
SU1OK:
Required)
SUlOKPM models, however. do not have internal batteries
SUlOKBP or a SUBP. Using the
SUBP SUlOKBP SUlOKPM
Note: Optional Tripp Lite external battery packs (SUBP's) feature individual 120V AC input line cords and individual internal battery chargers. By adding multiple SUBP's individually connected to 120V AC input, the recharge time of a battery system will be dramatically reduced as compared to systems relying on only the
UPS'S main charger. While adding SUBP's without connecting their chargers will increase a battery system's reserve capacity, this
will also increase the system's overall recharge time. See the figure to the right for the schematic diagram of
Acmpu,
1
avo
the SUBP external battery pack.
BArrERY FUSE
THE DIAORAU
OF
REPLACEMENT
If
one of your fuses has blown, you will
notice no output voltage at zero load. Blown
as
shown
in
fuses should be replaced diagram on the right. Since SUGK models contain internal batteries, the battery fuse holders are located on the rear panel of the UPS. Since
SUlOK models operate solely from external batteries, the battery fuse holders are located on the rear panel of the external battery models also support connections to optional external battery packs, which may require battery fuse replacement.
the
THE EXTENSIBLE BATTERY CABINET
f
pack(s). Note: SUGK
BA77ERY CONDITION VERIFICATION
When the UPS you to the UPS battery's charge condition.
is
operating from battery power, the alarm and LCD Display will both alert
Batterv Charge Condition
Alarm
ED Dis~lav
FULL Short Beep (every 2 seconds) ON BAlTERY
BA'IT
=
XXV
Wo
LOW Short Beep (every 1/2 second) BA'ITERY LOW
BAT
=
XXV
Wo
UNDER Continuous Beep BA'ITERY UNDER
SHUT DOWN
INITIAL BAVERY CHARGING (OPTIONAL)
Your UPS System's battery is fully charged prior to shipping. However, if your UPS has been stored for on the AC Input Breaker. The LCD Display will illuminate and indicate "ON BYPASS." DO NOT turn on the AC Output Breaker to apply the load until the battery charged. Once the UPS level automatically.
TURNING THE UPS
Make sure the Bypass Key is set to NORMAL.
Turn
the AC Input Circuit Breaker ON, then
an
extended period, recharge its battery for 8 hours. To charge, turn
is
in use, it will charge the batteries and maintain the charge
ON
UPS
is
properly installed (see Installation section) and the Manual
turn
the Output Circuit Breakers ON.
is
fully
If your AC input Voltage Selection, pg.
However, the
is
providing power normally within your selected range (see Input
6,
and Specs, pg. 17). your connected load will energize.
UPS'S inverter is not yet on. Press the front "ON/OFF" switch ON to
begin inverter operation.
If
your AC input
is
not providing power normally, you have the option of starting from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the
"ON/OFF" switch for three seconds to start your UPS in "ON BA'ITERY mode. Note that some electronic equipment may draw more amps during startup: when starting from battery, consider reducing the initial load on the UPS.
The UPS will perform a brief self-test and show the results on the LCD Display. (See
10,
Self-Test section, pg.
for display sequence.) After a successful self-test, the UPS
will provide AC power from the inverter to your load.
TURNING THE UPS
OFF
Press the front "ON/OFFm Switch OFF. Your load will still be energized. The inverter
is
now off, but your UPS is not fully deactivated. The LCD Display will show "ON
BYPASS." Turn the AC Input and Output Circuit Breakers OFF. Your load will no longer be
energized, and the LCD display will be dark.
SELF-TESTING
When you turn the below
for
display sequence.'
'Note: ~startingfiom battery,
diagram below
appears
SELECT
when the
FREQ
UPS
ON,
it will perform a brief (about
the
BATIERY
LED
will be
Ut
and the
I/P
LlPS
b
operating normally under utfllty-supplled AC Input power.
OUT
.
XXHz
and BYPASS
25
second) self-test. See figure
LED5
wlll MI. TheJInd
LCD
dlsplay In
(he
SELECT
Sltll~lOlllll~
UPS SYSTEM
INPUT
AC OK
UPS SYSTEM
,,,,
A
$!
UPS SYSTEM UPS SYSTEM
UPS SYSTEM
OFF
UPS SYSTEM
SELECT
AC/DC OK
UPS SYSTEM
INVERTER
k~nloniini
SELECT
UPS SYSTEM
ziii$
1
UPS SYSTEM
TEST
CUKSERULL
-3
P
+
unrm
UPS SYSTEM
LCD DISPLAY SELECT SWITCH
Momentarily press the "SELECT" switch on the front panel to browse through different power readings on the LCD Display. The LCD Display will show which one of four
operational modes your UPS is currently in: Also, as you press the "SELECT" switch, the LCD Display will browse through load. input, bypass, output and battery conditions.
Normal, Economy, On-Battery, or Bypass.
"NORMAL" MODE OPERATION
"ECONOMY' MODE OPERATION "ON
"ON-BATTERY" MODE OPERATION
BYPASS"
MODE OPERATION
OPERATION ON BYPASS-VOLTAGE OUT OF RANGE
While in Bypass Mode, the
If
output voltage.
20%
and
the output voltage passes out of an acceptable range (between
lower than nominal), the UPS displays the condition on its supplying output power to its load. If power levels return to an acceptable level. the UPS resumes supplying power to the load, and its or too low at one time, but has returned to nominal.
UPS
monitors the input voltage, which on Bypass equals the
LCD
LCD
reports that output voltage was too high
15%
higher
and stops
LCD
Bypass Voltage Condition
>
15Oh
Higher
than
Nominal >20% Lower Was Too High. Now Nominal Was Too Low. Now Nominal
than
Nominal
Display Message BYPASS AC TOO HI BYPASS AC TOO BYPASS AC WAS HI BYPASS AC WAS LO
M
OPERATION ON OVERLOAD
When the
time depending on the severity of the overload). If the UPS is still overloaded at the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.
Overload Condition
102% - 125%
125%
>150%
-
150%
UPS
detects an output overload, it will commence a countdown (the length of
LCD
Display Message
Overload 102% Load=XXXOh
Overload 125% Load=XXXOh
Overload 150% Load=XXXOh
X.XXKW
XXXKW
X.XXKW
Countdown to Shutdown
1
minute
30 seconds
2 seconds
11
BATERY CHARGE WA RNlNGS
Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately.
Battery Charge Warning
Battery charge nearly depleted
AC/DC charger not operating
LCD Display Message
BATTERY LOW
CHARGER
FAILURE!
OPERATION UNDER SHUTDOWN
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the "Input," "Output" and "Bypass" will be illuminated.
Condition Extended Overload
Output Short Circuit
Remote Shutdown Command
(FROM DB9 INTERFACE) Remote Shutdown Command
RJ
1
(from
Internal Faults
1 interface)
(>
1500%)
LCD Display Message OVERLOAD 150% SHUTDOWN SHORTClRCUlTl SHUT DOWN
REMOTE SHUTDOWN EMERGENCY SHUTDOWN INVERTERTOO LO SHUTDOWN INVERTERTOO SHUT DOWN DC BUS SHUTDOWN OVERTEMPERA'IURE SHUTDOWN
STOP!
+/-
HIGH/LOW
HI
LEDs
OPERATION
Turn
this switch to
PASS"
before performing
OF
MANUAL BYPASS SWITCH
"BY-
UAHUAL
BYPASS
SWITCH
-
any maintenance on the UPS with the connected
AC~N~U~
load supported. Connected equipment will receive filtered AC mains power, but will not receive battery power in the event
l~~UTE~
FROU
WE
*C
LIN~
of a blackout.
SWITCHING
Turn Turn Turn
UPS
TO "BYPASS" MODE
the "ON/OFFn Switch OFF. (LCD will read "ON BYPASS.")
the "Manual Bypass" Switch
clockwise
from NORMAL to BYPASS.
the AC Input Circuit Breaker OFF. Open battery fuse holders and remove the battery fuses from all battery packs and from all SUGK models.
SWITCHING
UPS
TO
"NORMAL"
MODE
Replace all battery fuses in the battery fuse holders and close the battery fuse holders.
Turn
the AC Input Circuit Breaker ON.
Turn
the "Manual Bypass" Switch counterclockwise from BYPASS
back to NORMAL.
Turn
the "ON/OFF Switch ON.
RS-232 INTERFACE
This female DB9 port connects your UPS via an RS-232 cable to a workstation or server
equipped with status and power conditions. Using this port, manage network power and automatically save open files and shut down equipment during a blackout. Contact Mpp Lite Customer Support at (773) 869-1233 for informa­tion on available SNMP, network management and connectivity software and products.
RS-232 signals and operations include: load level, battery status, battery level. operation mode, AC input voltage, AC output voltage, AC input frequency. temperature inside unit, set shut-down delay time,
Hardware:
Baud Rate: 2400 BPS Data Length: 8 bits Stop Bit: Parity: NONE
Tripp Lite software. The port uses RS-232 communications
Mpp Lite software can monitor and
enable/disable alarm and remote shutdown.
Pin assienment;
Pin
1
bit
2: Pin 3: Pin 5: GND (Signal Ground)
TXD
(Transmit Data)
RXD
(Receiving Data)
to
report UPS
AS-400 INTERFACE:
This female DB9 port connects your UPS to an IBM AS-400 computer AS-400 cable. The
to allow an AS-400 to automatically save open files and shut down its operating system during a blackout. AS-400 protocol includes: operation on inverter, operation on AC
power supply, operation on battery and low battery alarm.
pin assimment:
Pin 5: Common Pin 6: Pin 7: Low battery alarm Pin Pin 9: Operation on battery
Operation on AC power supply
8:
Operation on inverter
port uses AS-400
communications to report UPS status. It can be used
via
the included
LOW
BATTERY
INVERTER
AS-400
Battery Low Battery Direct Mains Supply Inverter
*Inactive:
INTERFACE
may
be
in
El
1941
TABLE
Pin
6,5
OFF
OFF
ON
OFF
either
state.
I
Pin 7.5
ON
OFF
*
Pin 8.5
ON ON
OFF
ON
Pin
OFF
I
9,5 ON ON
*
13
DRY CONTACT INTERFACE:
This female DB9 contact-closure port allows your UPS to send contact-closure signals
to indicate that it is on battery back-up mode and if its batteries are running low. The
can
port
Pin assipnment;
also receive a remote shutdown signal.
LOW
BATTERY
b
COY
NC
I
-
If
I
C
lmin.U.3mA
1
I
REMOTE FROM
SHUTDOWN
EXTERNAL
SIGNAL
I
SIGNALFROM COMPUTER
MAXIMUM CAPACITY AC250Vn4
DC30vnA
DRY
CONTACT INTERFACE TABLE
UPS Operating Mode
Normal Back Up Low Battery
*
Inactive:
may
be
OF
DRY CONTACT:
Pin
OPEN CLOSE CLOSE
in
either state.
8,3
Pin
OPEN
CLOSE
REMOTE EMERGENCY POWER OFF:
This
RJ
11
modular jack allows remote emergency shutdown.
Pin assignment
lSU6K
Shown]
1,3
I
.'
!
If there power off.
is
a short between pins 2 and
3,
2
and
5, 4 and
5,
or 3 and
Pin
4,
the UPS will
1
Service
Your
Smartonline UPS
A
below.
up
information, call
2-
TRlPP LlTE warrants date of initial purchase. After 90 days from the suchdcfcchve products. Toobtain sen ~cc under thls warranty, you must callTRlPP LlTEoran
must be returned to TRlPP Lm or an authorized TRIPP LITE service center with transportallon chnmes prcpa~d and must be acmmpanted bv a brief description of the problem encounlered and proof of date and place of purchase. This warranty does not apply to equipment Lhich has been damaged bv accidenl, ncaligence or misapplication or has been altered or modified in any way. This warranh, applies only to the original purchaser who must havc pr&ly registercd'ihe product within 10 days of purchase.
ThewarranhesofallTRIPPL~suppres~null
of all TRIPP LlTE EXCEPT
MERCHANTABILITY thereforc. the afor~aid limihtion(s) or exclusion(s) may not apply to the purchaser.
EXCEPT
CONSEQLJENTIALDAMAGESARISINGOIJTOFTHE
S~ecifsallv, TRIPP LITE is not liable for anv costs. such as lost ~rofits or revenue. loss of eaulomcnt. loss of use of wuioment. loss of software.
I&S
The policy of TRIPP LITE Is one of continuous improvement. Specificaliow are subject lo change without notice.
variety of service contracts is also available from
service contracts and
Tripp
Year Limited Warranty
tls
products tncludtng
UPS
Splems are null and vold ~f
AS
PROVIDED HEREIN, TRrPP LlTE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTlES OF
ANDFlTNESS FOR A PARTICULAR PURPOSE. Somestatesdonot pennit limitationorexclusion of implied warranties;
AS
PROVIDED ABOVE,
of
dais;
costs of substilutes, claims by ihird parties, or othe'rwise.
is
covered by the 2-year limited warranty period described
Tripp
Lite. including start-
3-
to 5-year SafeSure on-site service contracts. For more
Lite Customer Service at
batteries
to be free from defects In materials and workmanship for a period of two years from the
d.lte of purchase, TRIPP Lm's obli@ition undcr this warranty is llm~ted to
andvold ~f they havebeenconnected totheoutputof any UPSsystem Thcwarranhes
il
surge suppressor has been connected to its output receptacles.
IN
NO EVENT WILL TRIPP LlTE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL. INCIDENTAL OR
USEOFTHlSPRODUCT,EVBN
(773)
869-1233.
,
replacing
..
. .
authorized
TRlPP LITE scrvicccenter. Producls
..
.
.
.
.
IF
ADVISEDOFTHE POSSIBILlTYOFSUCH DAMAGE.
..
.
parts on
Ultimate Lifetime Insurance Policy
(Valid in U.S. and Canada ONLY)
TRIPP LITE warrants, for the lifetime of the product, (a1 TRIPP LITE's option) to repair or replace (on a pro rata basis) directly connected equipment that is damaged due to power transients while properly connected to TRIPP LITE products offering the Insurance Policy. Reimbursement or restoration for data loss is not included. Power transients include spikes and surges on the AC power, data or telephone lines that
AC Power Line Transients: To claim damages, the TRIPP LITE product must be plugged into a properly wired and grounded outlet. No extension cords or other electrical connections may be used. The installation
theNationalElcctricalCode(NEC).
forth by equipment resulting from a cause other than an "AC power transient". If user meets all of the above requirements, TRIPP or replace (at TRIPP allowed for damage entering from telephone or data lines, unless they arc separately protected, as described below.
Telephoneand DataLineTransients: TrippLite
dala lines & when all such paths are protected by a Tripp Lite protection product(s) and the the AC power (utility) line is
and/or simultaneously coverage.
Reimbursement dollar limits will be equal lo that of the Tripp Lite power protection product. Coverage is excluded where a suitable environment for the protection device is not provided, including, equipment must also include a properly installed and operating "primary protection" device at the telephone service entrance (such devices arenormally added during telephone line
All above warranties are null and void if the TRPP LlTE product has been improperly installed, tampered with or altered in any way, or if theconnected equlpmmt was not used under normal ope;atingconditionsor in accodance with any iabels or instructions. All cl;imsundcr
this
does not inriude damage resulting from accident or misuse, and appiies to the domestic (USA & Canada) use of these products only. Tripp Lite reserves the right
by requesting the equipment in question oi thdt prov%ed by any coverage of connected equipment provided by other sources, i;lcluding, but noi ltmited io, any manufacturer's warranty and/or any extended warranties.
EXCEPT AS PROVIDED ABOVE, TRIPP LlTE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF
MERCHANTAB~TP(ANDRTNESSFORAPARTICULARPURPOSE.Somestatesdonotpermitlimitationorexclusionofimplied
therefore, the aforesaid EXCEPT AS PROVIDED ABOVE,
CONSEQLJENTIAL DAMAGE. Specifically, TRlPP LITE is not liable forany costs, such as lost profits or revenue, lossof equipment, lossof useofequipment, loss of software, loss of data, costs of substitutes, claims by third parties or otherwise.
To receive service under this warranty, you must be the original purchaser/user of the product in question You must obtatn a Returned Material must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
protectedbyaTrippLitepowerprotectiondevice(UPS,surgesuppressororIineconditioner)with
warranty must be submitted in writing toTripp L~tc within 30days of the occurrenceor theclaim will not beconstdered. This warranty
Authoriwtlon (RMA) number fromTRlPP LITE. Products must be returned InTRIPP LITE w~th transportation charres prepn~d and
the TRIPP LlTE products havc been designed to protect against (as recognized by industry standards).
Exceptasprovided above, Lhiswarranty doesnot coverany damage toproperly connected electronic
LlTE's option) equiprnent up to the specified value (See ULTIMAFLifelime Insurance Policy Limits). No coverage is
willrepairorreplacedirectlymnnectedequipmentthat
installalion).
-
..
to
determine whether the damage to the connected equipment is due to malfunction of the Tripp Lite product
be sent to Tripp Lile for examination. This policy is above and beyond, only to the extent needed,
limitation(s) or exclusion(s) may not apply to purchaser.
IN
DAMAGES
NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR
ARISING
OUT OF
THE
USE
OF
musl comply with all applicable electrical and safety codes set
isdamaged by transientsontelephone
but not limited lo, lack of a proper safety ground. Telephone servin
THIS
PRODUCT,
EVEN
IF
ADVISED
OF
ULTlMATEOLifetime
LIE will repair
UllimateLifetimelnsurance
warranties;
THE
PosmnrrY
OF
SUCH
15
ACINPUT
SURGE
*
-
PROTECTOR
*'
INPUT FILTER
,
ACT0 DC
CONVERTER
-
DCTOAC INVERTER
-
STATIC
BYPASS
SW~CH
-
OUTPUT
FILTER
-
MANUAL
BYPASS
SWITCH
-
OUTPUT
lSoLATIoN
XFM
-
BREAKER
I I
STANDARD
BAllERIES:
240
VDC
dLs
SUBP EXTERNAL
BATTERY CABINET(S):
240
MC
dLt
120
VAC INPUT
-
-
I
CHARGER
POWER SUPPLY
CPU
CONTROLLER
-LEDS LCD
-TO RS-232 As400 DRY CONTACT ACCESSORY SLOT REP0
(Notc: Excludingisolation transformer)
Model SU6K SUlOK
&&
Inputvoltage 156V-280VSlngle Phase 156V-280VSinglePhase Input Frequency
50/60 Hz t 3 Hz
50/60 Hz 2 3 Hz
(selectable, pg. 7) (selectable. pg. 7) Input Current 32A 50A Inrush Current <150A <200A Power Factor
(Full
Load) ~0.99 >0.99 Emciency (Full Load/On-Line) >87Oh >88% Circuit Breaker 40A 63A
OU~DU~
VA 6000 10000
Watts (Power Factor: 0.7) 4200 Waveform (On-Line) Waveform (On-Battery) Output Voltage
(RMS)
Slnewave Sinewave Slnewave
120/208/240V 120/208/240V
7000 Slnewave
Output Frequency 50/60 Hz 50/60 Hz
(2
Voltage
Max.
Regulation
Harmonic
0.2 HZ on battery)
k3Oh 23Oh
Distortion
(2
0.2 Hz on battery)
(Llnear Full Load) ~3% <3% (Non-Linear Nl Load) <6% <6%
Overload Capabilttfes 102%
(continuous)
102%
(continuous)
102%-125Oh (1 min.) 102Y0-125~h (1
min.)
125%-150°h (30 sec.) 125%-150% (30 sec.)
>
150% (2 sec.)
>
150% (2 sec.) Short Clrcuit Capability 90AD 160A' Circuit Breakers Crest Factor
Ihe
short
clrcult
capability
of
10
2W
l2OV
3
x 32A 3 x 63A
3:
1 3: 1
for
the
6kVA
ls
greater
than
ISOA,
and
for
the
1
OkVA
Ls
.greater
Lhnn
320A.
Battery & Charger
Battery- 12V/7AH 12V/7AH Battery Quantity Protection
20
40
3OA/600Vfuse 30A/600Vfuse Recharge Voltage 274VDC 274VDC Recharge Rate (to 90%) Low Battery Shutdown
Typlcal
BackupTime
8
hrs.
4
hrs.
2OOVDC 2OOVDC
(Full Load) 8 mln. 10 min. (Half Load) 25 min. 31 min.
Operation
On-Line Transfer Ttme (Une to Battery. Battery to Line) 0 ms 0 ms
AudIble Nolse
(Full
Load @ 1 meter)
<50 dBA c55 dBA
Indicator#
Both models Include
an
LCD Display and LEDs (AC Line In. AC to DC. DC to AC. AC Output. Battery
Back-Up. Bypass).
Communications
Both models lnclude
an
RS-232 DB9 female connector.
an
AS-400 DB9 female connector, a
dry
contact
DB9 female connector and an accessory slot.
~mectlons
InputTe~minal Block OutputTerminal Block Extended Battery Input Socket
40A
4OA
40A
60A
60A
40A
phwical SpeciBcntiom
Dimensions
of UPS and Battery Cabinet
(HxDxWJ 22-1/5x24-4/5x 11 in. 22-1/5x24-4/5x 11 in.
(56.5
x
63 x 28 cm.) (56.5 x 63 x 28 cm.)
Net Weight (UPS)
286 Ib. (130 kg) 242 Ib. (110 Net Weight (Battery Cabinet) 278 Ib. (126
kg) kg)
Loading...