Tripp Lite SMX700HG User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMX700HG
Highlights
700VA line interactive tower UPS
Maintains 230V nominal output over an input range of 155 to 274V
Professional features include serial port, USB port, IEC320 plug & outlets,
built-in isolation transformer
Input: IEC320 C14 (230V 3.6A) / Output: 6 IEC320 C13 (230V)
2 year product warranty
Description
Tripp Lite's SMX700HG offers medical-grade UPS protection with built-in line interactive voltage regulation, intelligent monitoring and unattended
shutdown capability. Tested to CE/IEC 60601-1 as medical electrical equipment. Built-in isolation transformer with Faraday shield removes common
mode noise while maintaining full AC surge suppression in all modes. Resistant to electrostatic discharge. Includes high quality hospital-grade plug
and outlets. 700VA power handling capacity supports computers, inter-networking equipment and other critical loads during commercial power
failures. Line interactive voltage regulation corrects brownouts as low as 155V and overvoltages as high as 274 back to normal 230V levels, saving
battery reserves for use only during complete power failures. Includes 6 outlets, diagnostic LEDs and built-in USB & RS-232 communications ports
that work with downloadable PowerAlert Software and cabling to provide automatic unattended shutdown of connected network and PC applications.
Applications
Tested to CE/IEC 60601-1. UPS provides ultimate safety and reliability for patient point of care solutions, telemedicine, nurse's stations, wireless
communications systems, electronic prescribing applications, medical imaging and mission critical equipment. Not recommended for life support
applications.
Package Includes
SMX700HG Medical Grade UPS System
One USB and One DB9 monitoring cable
Warranty information
Instruction manual
Features
Ideal UPS protection for applications in medical patient-care areas where UL 60601-1 listed medical electrical equipment is required
Built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise while maintaining full AC surge
suppression in all modes
Line-interactive voltage regulation corrects brownouts and overvoltages from 155 to 274 volts back to usable 230V output levels, without
using battery power
Hospital-grade plug and outlets offer added degree of safety and reliability to input/output connections
Full line isolation offers a higher degree of safety and prevents operational problems in sensitive electronic equipment
Resistant to electrostatic discharge
Supports loads up to 700VA/450 watts
36 minutes half load runtime (with 350VA load), 14.5 minutes full load runtime (with 700VA load)
6 protected hospital-grade outlets; IEC C14 inlet on 6-inch dongle
RS-232 and USB monitoring ports for remote monitoring and unattended shutdown
PowerAlert unattended shutdown software available via free download from www.tripplite.com (cabling included)
Complete surge protection, line isolation and EMI/RFI noise filtering
2 year product warranty
5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace
Battery replacement door
Grounding lug
Specifications
SYSTEM OVERVIEW
Voltage compatibility 230V AC
Frequency compatibility
50/60 Hz (auto-select)
OUTPUT
Output VA 700
Output watts 450
Output nominal voltage
230V AC
Output voltage regulation
LINE MODE: Sine wave line voltage 230V (-18% / +8%) BATTERY MODE: PWM sine wave output 230V +/-5%
Output frequency regulation
LINE MODE: Passes line frequency of 50Hz +/-10% BATTERY MODE: Inverter output regulated to 50/60Hz +/-0.5Hz
Outlet quantity / type 6 IEC C13
Overload protection Resettable circuit breakers
INPUT
Maximum input amps 3.6A / 828 watts
Input connection type IEC C14 inlet
Input cord length 6 inch dongle., 16 gauge
Recommended Electrical Service
10A 230V
BATTERY
Full load runtime 14.5 minutes (700VA)
Half load runtime 36 minutes (350VA)
DC system voltage 36V DC
Typical battery lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
VOLTAGE REGULATION
Voltage regulation description
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to maintain usable, computer grade output without consuming battery power over an input voltage range of 155 to 274V AC
Overvoltage correction
Input voltages between 206 and 245V AC are reduced by 9%
Direct pass through Input voltages between 200 and 244V AC are passed through unchanged
Brownout correction Input voltages between 183 and 199V AC are boosted by 10%
Loading...