Tripp Lite PDUMV30HV Data Sheet

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: PDUMV30HV
Highlights
Metered single phase 30A 208/240V, 0U 63.75in / 162cm vertical rackmount
PDU
Pair of digital meters report output current in amps for each load bank
Attached 10ft / 3m cord with NEMA L6-30P input plug
30 outlets (6 C19, 24 C13) in two separately breakered load banks
Toolless button-mount and bolt-down bracket installation hardware included
Description
Tripp Lite single phase Metered PDU / Power Distribution Units offer real-time local reporting of load level in amps via built-in digital display. Enables visual monitoring of PDU load levels to prevent overloads as additional equipment is added. Offers reliable rackmount multi-outlet power distribution from any protected UPS, generator or mains input power source. High quality design includes rugged all-metal housing and secure rackmount installation with included mounting accessories.
Applications
Ideal means of powering networking equipment in datacenters, computer rooms and network closets
Package Includes
PDUMV30HV 63.75 inch basic PDU with owner's manual
Set of 2 bolt-on plug retention brackets and installation hardware
Set of mounting brackets and installation hardware
Features
30A single phase 208/240V Metered Power Distribution Unit / PDU (Agency derated to 24A continuous)
Set of two lighted meters report PDU output current in amps for each output load bank
Attached NEMA L6-30P 30A 208/240V input plug and 12ft / 3.6m cord
0U 63.75in / 162cm vertical rackmount format installs using no rack spaces
30 output receptacles (6 C19, 24 C13)
Outlets are arranged in two 15 outlet load banks, each with separate 15A breaker and current metering
Toolless installation in button-mount compatible equipment racks
Bolt-down installation brackets support installation in other racks and additional surfaces
Specifications
OVERVIEW
PDU Type Metered
OUTPUT
Frequency compatibility
50 / 60 Hz
Output nominal voltage
200-240V nominal, single phase
Overload protection Outlets are arranged in two separately breakered load banks. The top 15A breaker covers outlets on the upper half,
the bottom 15A breaker covers outlets on the lower half of the PDU. Each breakered bank covers 12 C13 and 3 C19 outlets.
Outlet quantity / type 30 total (6 C19, 24 C13)
Outlet Type IEC-C13, IEC-C19
INPUT
PDU Input Voltage 200; 208; 240
Maximum Input Amps (A)
30
Maximum Input Amps (A) Details
30A maximum (Agency de-rated to 24A continuous)
PDU Plug Type NEMA L6-30P
Input cord length (ft.) 10
Input cord length (m) 3.05
Phase Single-Phase
LEDS ALARMS & SWITCHES
Switches n/a
Front panel LEDs Includes 2 built-in 2-character LED meters to display power consumption of items plugged into each separately
breakered 15A loading bank.
PHYSICAL
Shipping Dimensions (HWD/in)
64.5 x 3.5 x 4.75
Shipping Dimensions (HWD/cm)
163.8 x 8.9 x 12.1
Shipping weight (lbs)
13
Shipping weight (kg) 5.9
Unit Dimensions (HWD/in)
63.75 x 2.25 x 3.75
Unit Dimensions (HWD/cm)
162 x 5.7 x 9.5
Unit weight (lbs) 8
Unit weight (kg) 3.6
Material of construction
Aluminum
Style Vertical Rackmount, Wallmount, Raceway, Workbench
Form factors supported
0u vertical installation in equipment racks, plus under-counter and wallmount
PDU Form Factor Vertical (0U)
ENVIRONMENTAL
Loading...