Tripp Lite PDUMV30HV User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: PDUMV30HV
Highlights
Metered 0U 63.75 in. vertical rack PDU
208/240V 30A maximum capacity
Two built-in ammeters display current usage for both 15A breakered load
banks
10 ft. input cable with locking L6-30P plug and 30 output receptacles (6 C19,
24 C13)
Tooless button-mount installation
Cord retention brackets keep vital equipment plugs connected
Description
Tripp Lite Metered Power Distribution Units give IT Managers the ability to monitor network power consumption levels to prevent mains, generator,
UPS or PDU overloads and to ensure proper load balance in complex redundant power applications. Each built-in, easy to read, two-character LED
display offers continuous PDU current monitoring data in one-amp increments. Switch-free unfiltered electrical pass-through reliably distributes UPS
or generator power to multiple servers and vital networking equipment in rack enclosures, network closets and more. Tooless mounting enables
simple installation in button-mount compatible racks. Included mounting brackets support vertical installation in standard 2 and 4 post racks or other
surfaces, such as under-counter or wallmount configurations. Plug retention brackets keep vital equipment plugged in and continuously powered.
PDUMV30HV 63.75 in. vertical 0U metered rack PDU supports 30A maximum capacity at 208/240V (agency derated to 24A). Includes 10 ft.
attached line cord with L6-30P input plug. 24 C13 and 6 C19 outlets support up to 30 directly connected pieces of networking equipment. Outlets
are arranged in two separately metered and breakered 15A load banks (each with 3 C19 and 12 C13 outlets). Set of 2 built-in 2 character displays
offer continuous information on PDU power consumption for each of the two built-in loading banks.
Applications
Ideal for network configurations where a metered, non-switched PDU is required to distribute UPS or generator power to multiple pieces of
networking equipment
Package Includes
PDUMV30HV 63.75 inch basic PDU with owner's manual
Set of 2 bolt-on plug retention brackets and installation hardware
Set of mounting brackets and installation hardware
Features
208/240V 30A Metered Power Distribution Unit (PDU) in 63.75 in. 0U vertical form factor.
30A maximum capacity (Agency derated to 24A)
Attached L6-30P input plug with 10 ft. line cord
30 total output receptacles (6 C19, 24 C13)
Outlets are arranged in two separately breakered and metered 15A load banks (each with 3 C19 and 16 C13 outlets)
Current meters offer the ability to monitor network power consumption levels to prevent mains, generator, UPS or PDU overloads and to
ensure proper load balance in complex redundant power applications
Pair of easy to read, two-character LED displays offer continuous PDU current monitoring data in one-amp increments for each metered
load bank
Circuit breaker offers protection from overloads and short circuit fault conditions
Sleeved circuit breaker assembly prevents accidental shutoff and requires no tools to reset if tripped
Switch-free unfiltered electrical pass-through reliably distributes UPS or generator power to critical networking equipment
Tooless installation supports fast installation in button-mount compatible equipment racks
Included nut & bolt mounting brackets support installation in racks or other flat surfaces, such as under-counter, wallmount and other
surfaces
Cord retention brackets keep vital equipment plugs connected
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208/240V
Frequency compatibility
50/60
OUTPUT
Output nominal voltage
208/240V
Outlet quantity / type 30 total (6 C19, 24 C13)
Overload protection Outlets are arranged in two separately breakered load banks. The top 15A breaker covers outlets on the upper half, the
bottom 15A breaker covers outlets on the lower half of the PDU. Each breakered bank covers 12 C13 and 3 C19 outlets.
INPUT
Maximum input amps 30A maximum (Agency de-rated to 24A continuous)
Input connection type L6-30P (208/240V 30A)
Input cord length 10 ft.
Recommended Electrical Service
208V, 240V
LEDS ALARMS & SWITCHES
Front panel LEDs Includes 2 built-in 2-character LED meters to display power consumption of items plugged into each separately
breakered 15A loading bank.
Switches n/a
PHYSICAL
Shipping weight (lbs) 13
Shipping weight (kg) 5.9
Shipping Dimensions (HWD/in)
64.5 x 3.5 x 4.75
Shipping Dimensions (HWD/cm)
163.8 x 8.9 x 12.1
Unit weight (lbs) 8
Unit weight (kg) 3.6
Unit Dimensions (HWD/in)
63.75 x 2.25 x 3.75
Unit Dimensions (HWD/cm)
162 x 5.7 x 9.5
Material of construction
Aluminum
Form factors supported
0u vertical installation in equipment racks, plus under-counter and wallmount
Style Vertical Rackmount, Wallmount, Raceway, Workbench
ENVIRONMENTAL