Highlights
Metered 0U 63.75 in. vertical rack PDU
208/230/240V 20A maximum capacity
Built-in ammeter displays whole-PDU current usage
10 ft. detachable input cable with locking L6-20P plug and 38 output
receptacles (6 C19, 32 C13)
Tooless button-mount installation
Cord retention brackets keep vital equipment plugs connected
Description
Tripp Lite Metered Power Distribution Units give IT Managers the ability to monitor network power consumption levels to prevent mains, generator,
UPS or PDU overloads and to ensure proper load balance in complex redundant power applications. Each built-in, easy to read, two-character LED
display offers continuous PDU current monitoring data in one-amp increments. Switch-free unfiltered electrical pass-through reliably distributes UPS
or generator power to multiple servers and vital networking equipment in rack enclosures, network closets and more. Tooless mounting enables
simple installation in button-mount compatible racks. Included mounting brackets support vertical installation in standard 2 and 4 post racks or other
surfaces, such as under-counter or wallmount configurations. Plug retention brackets keep vital equipment plugged in and continuously powered.
PDUMV20HV 63.75 in. vertical 0U metered rack PDU supports 20A maximum capacity at 208/230/240V (agency derated to 16A). Includes 10 ft.
detachable line cord with L6-20P input plug. 32 C13 and 6 C19 outlets support up to 38 directly connected pieces of networking equipment. Outlets
are arranged in a single unbreakered load bank. Built-in 2 character displays offer continuous information on PDU power consumption.
Applications
Ideal for network configurations where a metered, non-switched PDU is required to distribute UPS or generator power to multiple pieces of
networking equipment
Package Includes
PDUMV20HV 63.75 inch basic PDU with owner's manual
Set of 2 bolt-on plug retention brackets and installation hardware
Set of mounting brackets and installation hardware
Features
208/230/240V 20A Metered Power Distribution Unit (PDU) in 63.75 in. 0U vertical form factor.
20A maximum capacity (Agency derated to 16A)
L6-20P input plug with 10 ft. line cord (detachable via C20 inlet)
38 total output receptacles (6 C19, 32 C13)
Outlets are arranged in a single unbreakered, metered 20A load bank
Current meter offers the ability to monitor network power consumption levels to prevent mains, generator, UPS or PDU overloads and to
ensure proper load balance in complex redundant power applications
Easy to read, two-character LED display offers continuous whole-PDU current monitoring data in one-amp increments
Circuit breaker free format prevents power interruptions due to tripped breakers while still providing mains panel protection from overloads
and short circuit fault conditions
Switch-free unfiltered electrical pass-through reliably distributes UPS or generator power to critical networking equipment
Tooless installation supports fast installation in button-mount compatible equipment racks
Included nut & bolt mounting brackets support installation in racks or other flat surfaces, such as under-counter, wallmount and other
surfaces
Cord retention brackets keep vital equipment plugs connected
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208/240V
Frequency compatibility 50/60
OUTPUT
Output nominal voltage 208/230/240V
Outlet quantity / type 38 total (6 C19, 32 C13)
Overload protection Outlets are arranged in a single unbreakered load bank
INPUT
Maximum input amps 20A maximum (Agency de-rated to 16A continuous)
Input connection type L6-20P (208/240V 20A) - detachable via C20 inlet
Input cord length 10 ft.
Recommended Electrical Service
208V, 240V
LEDS ALARMS & SWITCHES
Front panel LEDs Includes built-in 2-character LED meter to display whole PDU power consumption
Switches n/a
PHYSICAL
Shipping weight (lbs) 6
Shipping weight (kg) 2.8
Shipping Dimensions (HWD/in)
64.5 x 3.5 x 4.75
Shipping Dimensions (HWD/cm)
163.8 x 8.9 x 12.1
Unit weight (lbs) 5.2
Unit weight (kg) 2.4
Unit Dimensions (HWD/in) 63.75 x 2.25 x 3.75
Unit Dimensions (HWD/cm) 162 x 5.7 x 9.5
Material of construction Aluminum
Form factors supported 0u vertical installation in equipment racks, plus under-counter and wallmount
Style Vertical Rackmount, Wallmount, Raceway, Workbench
ENVIRONMENTAL
Relative Humidity 0-95% non-condensing
CERTIFICATIONS
Certifications Tested to UL60950-1 (USA, Canada), NOM (Mexico), CE (IEC 60950)
WARRANTY
Product Warranty Period Lifetime