7.7kW Single-Phase Monitored PDU, LX
Interface, 200-240V Outlets (36 C13/6 C19), IEC
309 32A Blue, 10 ft. (3.05 m) Cord, 0U 1.8m/70 in.
Height, TAA
MODEL NUMBER: PDUMNV32HV2LX
7.7kW 0U PDU distributes and monitors single-phase power in an IT or industrial environment. Built-in
Java-free network interface helps you remotely monitor load levels to prevent overloads that cause
downtime.
Description
The PDUMNV32HV2LX 7.7kW Single-Phase Monitored PDU provides real-time remote monitoring of
voltage, frequency and load levels via built-in network connection. By reducing the frequency of on-site
visits, these advanced remote capabilities can save you money and reduce downtime.
Highlights
●
7.7kW 200-240V single-phase
monitored 0U PDU
●
42 outlets—36 C13, 6
C19—with plug-lock insert
sleeves
●
Pre-installed WEBCARDLX with
latest version of PADM20 for
enhanced remote management
●
Digital ammeter for on-site load
monitoring in real time
●
IEC 309 32A Blue (2P+E) input
with 10-ft. (3.05 m) AC power
cord
Package Includes
●
PDUMNV32HV2LX 7.7kW
Single-Phase Monitored PDU
●
Built-in LX Platform interface
●
Configuration cable
●
(42) Plug-lock insert sleeves
●
Rack-mounting hardware
●
PDUMVROTATEBRKT
mounting bracket accessory
●
Owner’s manual
The 0U PDU features 42 outlets (36 C13 and 6 C19) with included plug-lock insert sleeves to prevent
cables from becoming accidentally disconnected. A 10-ft. (3.05 m) cord with IEC 309 32A Blue (2P+E)
plug connects the PDU to a compatible AC power source, generator or protected UPS.
The built-in Java-free HTML5-based LX Platform network interface enables full remote access for PDU
status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports
10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2
modules (sold separately) provide a variety of environmental monitoring capabilities. Protocols supported
include IPv4, IPv6, HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and
NTP.
A digital ammeter allows you to monitor each load bank's current and the total connected PDU load in real
time to ensure they remain well below maximum capacity with no danger of overload. The PDU mounts in
0U of space in EIA-standard 19-inch racks using the included toolless mounting buttons or the included
rack-mounting brackets. Use the included PDUMVROTATEBRKT kit to install the unit with outlets facing
the rear for better airflow or equipment access.
1 / 4
Features
Distributes and Monitors Network-Grade Single-Phase Power
●
7.7kW 200-240V monitored PDU with single-phase input
●
IEC 309 32A Blue (2P+E) plug with 10-ft. (3.05 m) cord connects to compatible AC power source
●
Firmware upgrades support future product enhancements
42 Outlets Distribute AC Power
●
36 C13 and 6 C19 outlets split into 2 separately breakered 20A load banks
●
Plug-lock insert sleeves prevent cables from becoming accidentally disconnected
Digital Ammeter
●
Reports current for each load bank and total connected PDU load
●
Supports IP-address self-ID
●
Rotates 180° for easy reading at either angle
●
Measurement accuracy plus minus 1A
Built-In LX Platform Interface
●
Pre-installed WEBCARDLX with the latest version of PowerAlert Device Manager firmware (PADM20)
provides enhanced remote management capabilities
●
PADM20 and PowerAlert Element Manager (PAEM) form a powerful tool for expanding maintenance
functions in large installations, including firmware update checks and backup and restoration of device
configurations
●
Supports 10/100 Mbps auto-sensing for communication with an Ethernet network
●
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring
capabilities
●
No Java required
Broad Communications Compatibility
●
Supports IPv4, IPv6, HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP
and NTP
●
Supports automatic and manual assignment of IP address
Essential Safety Features
●
Tiered access allows administrator and guest to log in via web browser
●
Immediate alert notifications via email or SNMP traps
●
Supports user-specified alarm notification thresholds
●
Real-time clock backup maintains day/date even if PDU is unpowered
Easy 0U Installation in EIA-Standard 19 in. Racks
●
Mounts vertically using included toolless buttons or rack-mounting brackets
●
Included PDUMVROTATEBRKT allows mounting with rear-facing outlets
TAA-Compliant
●
Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
2 / 4