Tripp Lite PDUMNV32HV2LX User Manual

Page 1
7.7kW Single-Phase Monitored PDU, LX Interface, 200-240V Outlets (36 C13/6 C19), IEC 309 32A Blue, 10 ft. (3.05 m) Cord, 0U 1.8m/70 in. Height, TAA
MODEL NUMBER: PDUMNV32HV2LX
7.7kW 0U PDU distributes and monitors single-phase power in an IT or industrial environment. Built-in Java-free network interface helps you remotely monitor load levels to prevent overloads that cause downtime.
The PDUMNV32HV2LX 7.7kW Single-Phase Monitored PDU provides real-time remote monitoring of voltage, frequency and load levels via built-in network connection. By reducing the frequency of on-site visits, these advanced remote capabilities can save you money and reduce downtime.
Highlights
7.7kW 200-240V single-phase monitored 0U PDU
42 outlets—36 C13, 6 C19—with plug-lock insert sleeves
Pre-installed WEBCARDLX with latest version of PADM20 for enhanced remote management
Digital ammeter for on-site load monitoring in real time
IEC 309 32A Blue (2P+E) input with 10-ft. (3.05 m) AC power cord
Package Includes
PDUMNV32HV2LX 7.7kW Single-Phase Monitored PDU
Built-in LX Platform interface
Configuration cable
(42) Plug-lock insert sleeves
Rack-mounting hardware
PDUMVROTATEBRKT mounting bracket accessory
Owner’s manual
The 0U PDU features 42 outlets (36 C13 and 6 C19) with included plug-lock insert sleeves to prevent cables from becoming accidentally disconnected. A 10-ft. (3.05 m) cord with IEC 309 32A Blue (2P+E) plug connects the PDU to a compatible AC power source, generator or protected UPS.
The built-in Java-free HTML5-based LX Platform network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities. Protocols supported include IPv4, IPv6, HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
A digital ammeter allows you to monitor each load bank's current and the total connected PDU load in real time to ensure they remain well below maximum capacity with no danger of overload. The PDU mounts in 0U of space in EIA-standard 19-inch racks using the included toolless mounting buttons or the included rack-mounting brackets. Use the included PDUMVROTATEBRKT kit to install the unit with outlets facing the rear for better airflow or equipment access.
1 / 4
Page 2
Features
Distributes and Monitors Network-Grade Single-Phase Power
7.7kW 200-240V monitored PDU with single-phase input
IEC 309 32A Blue (2P+E) plug with 10-ft. (3.05 m) cord connects to compatible AC power source
Firmware upgrades support future product enhancements
42 Outlets Distribute AC Power
36 C13 and 6 C19 outlets split into 2 separately breakered 20A load banks
Plug-lock insert sleeves prevent cables from becoming accidentally disconnected
Digital Ammeter
Reports current for each load bank and total connected PDU load
Supports IP-address self-ID
Rotates 180° for easy reading at either angle
Measurement accuracy plus minus 1A
Built-In LX Platform Interface
Pre-installed WEBCARDLX with the latest version of PowerAlert Device Manager firmware (PADM20) provides enhanced remote management capabilities
PADM20 and PowerAlert Element Manager (PAEM) form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations
Supports 10/100 Mbps auto-sensing for communication with an Ethernet network
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities
No Java required
Broad Communications Compatibility
Supports IPv4, IPv6, HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP
Supports automatic and manual assignment of IP address
Essential Safety Features
Tiered access allows administrator and guest to log in via web browser
Immediate alert notifications via email or SNMP traps
Supports user-specified alarm notification thresholds
Real-time clock backup maintains day/date even if PDU is unpowered
Easy 0U Installation in EIA-Standard 19 in. Racks
Mounts vertically using included toolless buttons or rack-mounting brackets
Included PDUMVROTATEBRKT allows mounting with rear-facing outlets
TAA-Compliant
Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
2 / 4
Page 3
Specifications
OVERVIEW
UPC Code 037332204899 PDU Type Monitored
INPUT
PDU Input Voltage 200-240V Recommended Electrical Service Single-phase 32A 200-240V service Maximum Input Amps 32 PDU Plug Type IEC-309 32A BLUE (2P+E) Input Phase Single-Phase Input Cord Length (ft.) 10 Input Cord Length (m) 3.05
OUTPUT
Output Capacity Details 7.7kW (240V), 7.4kW (230V), 7kW (220V), 6.7kW (208V), 6.4kW (200V) / 32A total capacity; 16A max per
Frequency Compatibility 50 / 60 Hz Output Receptacles (36) C13; (6) C19 Output Nominal Voltage 200-240V Overload Protection Two 20A circuit breakers protect 21 outlets each
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Digital meter reports PDU output current in amps, Scroll IP-address information; Display can be rotated 180 degrees
Front Panel LEDs Front panel LEDs indicate which loading segment the digital LCD current display is reporting; Bank 1 LED indicates
Switches Press the SCROLL IP button and release to display the configured IP address in 2 digit intervals; Press the SELECT
PHYSICAL
Form Factors Supported 0U vertical rackmount installation supported with included mounting brackets; supports toolless mounting in button-
Material of Construction Metal
breakered outlet bank; 16A max per C19 outlet; 10A max per C13 outlet
for installation with the input cable at the top
the meter is reporting load level for outlets 1-21; Bank 2 LED indicates the meter is reporting load level for outlets 22-42; Both LEDs lighted indicates the meter is reporting load level for all outlets combined
/ ROTATE button and release after one second to advance the local display power power consumption for the 3 reported segments: Bank 1, Bank 2 and Banks 1+2; Press the SELECT / ROTATE button and release after two seconds to rotate the display 180 degrees
mount compatible racks
PDU Form Factor Vertical (0U) Shipping Dimensions (hwd / cm) 13.21 x 16.26 x 185.42 Shipping Dimensions (hwd / in.) 5.20 x 6.40 x 73.00
3 / 4
Page 4
Shipping Weight (kg) 6.67 Shipping Weight (lbs.) 14.70 Unit Dimensions (hwd / cm) 177,8 x 5,6 x 6,7 Unit Dimensions (hwd / in.) 70 x 2.2 x 2.65 Unit Weight (kg) 4.40 Unit Weight (lbs.) 9.7
ENVIRONMENTAL
Operating Temperature Range 0C ~ 50C (32F ~ 122F) Storage Temperature Range -30°C to +60°C (-22°F to +140°F) Relative Humidity 5-95% non-condensing Operating Elevation (ft.) 0-10,000 Operating Elevation (m) 0-3000
COMMUNICATIONS
SNMP Compatibility Pre-installed LX platform interface provides remote monitoring via Java-free HTML5 web interface, telnet, SSH and
SPECIAL FEATURES
High Availability PDU Features Auto Probe Monitoring (included)
STANDARDS & COMPLIANCE
Certifications Tested to IEC60950-1: 2005 2nd Edition; EN 60950-1: 2006 (CE), CE Class A (Emissions), RoHS compliant, TAA
WARRANTY
Product Warranty Period (Worldwide)
SNMP management systems
Compliant
2-year limited warranty
© 2021 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: https://www.tripplite.com/products/product-certification-agencies
4 / 4