Tripp Lite PDUMNH30 User Manual

2.9kW Single-Phase Monitored PDU - 120V Outlets (16 5-15/20R), L5-30P, 10 ft. (3.05 m) Cord, 2U Rack-Mount, TAA
MODEL NUMBER: PDUMNH30
2U PDU provides real-time local and remote monitoring of voltage, frequency and load levels.
Features
2.9kW Single-Phase Monitored PDU with LX Platform InterfaceTripp Lite's PDUMNH30 distributes and
Highlights
16 NEMA 5-15/20R outlets with cord retention brackets
Digital readout monitors current to prevent circuit overload
Pre-installed WEBCARDLX with latest version of PADM20 for enhanced remote management
Temperature, humidity and contact-closure monitoring options
L5-30P input with 10-ft. (3.05 m) cord
Applications
Give IT personnel enhanced oversight of network power conditions by remotely monitoring site power conditions and PDU load levels
Provide reliable distribution of AC power to supported equipment in IT, industrial and similar applications
Configure for 2U rack-mount installation with included hardware, making it easy to integrate with a wide range of data center and network applications
Package Includes
PDUMNH30 2.9kW Single­Phase Monitored PDU
Rack-mounting brackets
Cord retention brackets
Cable ties
Owner's manual
1 / 3
Specifications
OVERVIEW
UPC Code 037332157652 PDU Type Monitored
INPUT
PDU Input Voltage 120V Recommended Electrical Service Single-phase 30A 120V service Maximum Input Amps 24 Maximum Input Amps Details Agency de-rated to 24A continuous PDU Plug Type NEMA L5-30P Input Phase Single-Phase Input Cord Length (ft.) 10 Input Cord Length (m) 3.05
OUTPUT
Output Capacity Details 2.88kW (120V) / 24A total capacity; 20A max per breakered load bank; 16A max per outlet Frequency Compatibility 50 / 60 Hz Output Receptacles (16) 5-15/20R Output Nominal Voltage 120V Overload Protection Two 20A breakers protect 8 outlets each Customized Load Management
Receptacles
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Digital current meter reports PDU output current in amps for 3 loading segments (Bank 1, Bank 2 and Banks 1&2
Front Panel LEDs Front panel LEDs indicate which loading segment the digital LCD current display is reporting; Bank 1 current level is
Switches Toggle switch prompts local display of power consumption in three segments (1) Breakered load bank 1, (2)
PHYSICAL
Material of Construction Metal Minimum Required Rack Depth (cm) 44.45 Minimum Required Rack Depth
(inches)
n/a
combined)
reported when the Bank 1 LED is on; Bank 2 current level is reported when the Bank 2 LED is on; Total output of both banks is reported when both LEDs are on
Breakered load bank 2, (3) Breakered banks 1&2 combined
17.5
PDU Form Factor Horizontal (2U)
2 / 3
Loading...