7.7kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V IEC309 32A Blue Inputs, 16-C13 2-C19 Outlets, 2U, TAA
MODEL NUMBER: PDUMH32HVATNET
High-capacity 7.7kW 200-240V PDU with ATS provides remote power monitoring and enables redundant power for non-redundant hardware. LED display and LX Platform network interface enables remote outlet control and monitoring of site power status and PDU load levels.
Description
The PDUMH32HVATNET 7.7kW Single-Phase 200-240V Switched Automatic Transfer Switch / ATS PDU provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 2U of space in EIAstandard racks and features 18 switched outlets (16 C13 and two C19) in two load banks, each bank protected by a 20A circuit breaker.
Dual 3-meter input cords with IEC309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase 230V power sources. The PDU constantly evaluates the power quality of both input sources.
Dynamic solid-state (TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1–5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption.
Built-in LX Platform network management interface. The Java-free LX Platform HTML5-based network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separate) provide a variety of environmental monitoring capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
Features
Primary and Secondary Inputs for Power RedundancyProvides remote power monitoring and enables redundant power for network devices single-corded and other non-redundant power supply configurationsDual 3m input cords with IEC309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase power sources
Automatic Transfer SwitchingDynamic solid-state (TRIAC) automatic transfer switchingSwitches to secondary power source if primary source fails or becomes unstable1–5 ms transfer time ensures uninterrupted operation of connected equipmentBuilt-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source
Multifunction Digital LED DisplayReports source A and source B input power status and other information, including power availability, line voltage, frequency, amps, kilowatts and power factor
Advanced LX Platform InterfaceLX Platform interface allows full remote access for power monitoring with email notifications via secure web browser, SNMP, telnet or SSHReal-time load/current data with billing-grade accuracy (+/- 1 percent)Automated alerts help prevent accidental overloads, power loss and
Highlights
●Single-phase IEC309 200-240V 32A Blue (2P+E) input
●16 C13 and 2 C19 230V switched outlets in 2 breakered load banks
●Automatic transfer switching within 1–5 ms
●Ethernet network interface for remote access
●Digital LED display for real-time status and current monitoring
Package Includes
●PDUMH32HVATNET 7.7kW Single-Phase 200-240V ATS / Switched PDU
●Rack-mounting brackets
●Plug-lock cable retention sleeves
●USB configuration cable
●Owner’s manual
1 / 4
downtimeOptional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities
Broad Communications CompatibilityProtocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP
Breaker Protected Output Load BanksProtect each of 2 single-phase output banksFront-panel LED indicates when breaker has tripped
Cord Retention SleevesSet of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
Mounts Horizontally in 2U of Rack SpaceCompatible with EIA-standard 19 in. 4-post racks and rack enclosures
TAA-CompliantCompliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
Specifications
OVERVIEW
UPC Code |
037332186874 |
|
|
PDU Type |
Switched; Auto-Transfer Switch |
|
|
INPUT |
|
PDU Input Voltage |
200-240V |
|
|
Recommended Electrical Service |
Two single-phase 32A 200-240V circuits |
|
|
Maximum Input Amps |
32 |
|
|
PDU Plug Type |
(2) IEC-309 32A BLUE (2P+E) |
|
|
Input Phase |
Single-Phase |
|
|
Input Cord Details |
Set of two inputs connect to separate PRIMARY and SECONDARY power sources; accepts inputs at all phase |
|
angles |
|
|
Input Cord Length (ft.) |
10 |
|
|
Input Cord Length (m) |
3.05 |
|
|
OUTPUT |
|
Output Capacity Details |
7.7kW (240V), 7.4kW (230V), 7.0kW (220V), 6.7kW (208V), 6.4kW (200V); 32A maximum total output; 16A |
|
maximum per breakered load bank; 16A maximum per C19 outlet; 10A maximum per C13 outlet |
|
|
Frequency Compatibility |
50 / 60 Hz |
|
|
Output Receptacles |
(16) C13; (2) C19 |
|
|
Output Nominal Voltage |
200-240V |
|
|
Overload Protection |
Includes two branch-rated 20A output circuit breakers; Breaker 1 controls the upper row of 9 outlets (8 C13, 1 C19); |
|
Breaker 2 controls the lower row of outlets (8 C13, 1 C19) |
|
|
USER INTERFACE, ALERTS & CONTROLS |
|
Front Panel LCD Display |
Digital display reports output amps in 3 separately metered load segments (BANK 1: Outlets #1-9; BANK 2: Outlets |
|
#10-18; BANK 3: Total Output), whole-PDU output kW load level and input voltage on primary and secondary input |
|
lines |
|
|
Front Panel LEDs |
Front panel LEDs confirm amp / kilowatt / voltage reporting information |
|
|