7.4kW Single-Phase Metered PDU, 230V Outlets
(2-C19, 16-C13), IEC-309 230V 32A Blue, 12 ft.
(3.66 m) Cord, 2U Rack-Mount, TAA
MODEL NUMBER: PDUMH32HV
Features
●
32A single phase 230V Metered Power Distribution Unit / PDU
●
Set of two lighted current meters separately report power consumption in amps for each output load
bank
●
Attached IEC-309 32A (2P+E) input plug with 12-ft. (3.66 m) line cord
●
2U horizontal rackmount format installs in two rack spaces
●
18 total 230V outlets (2 C19, 16 C13)
●
Outlets are arranged in two separately breakered and metered 16A load banks (each with 8 C13 and 1
C19 outlet)
●
Mounting flanges support installation in 2 and 4 post racks, with additional support for wall-mount and
under-counter installation formats
●
Mounting ears are reversible for front or rear facing rackmount installation
●
Front-panel grounding lug
●
Included cord retention brackets
Highlights
●
Metered single phase 32A 230V
2U horizontal rackmount PDU
●
Set of 2 current meters reports
current in amps for each output
load bank
●
Attached 12-ft. (3.66 m) cord
with IEC-309 32A (2P+E) input
plug
●
18 total 230V outlets (2 C19, 16
C13)
●
Reversible housing, 12.5 in. /
31.75cm depth
●
TAA Compliant
Package Includes
●
2U metered PDU
●
Mounting brackets
●
Plug retention brackets
●
User manual
Specifications
OVERVIEW
UPC Code 037332159045
PDU Type Metered
1 / 3
INPUT
PDU Input Voltage 230V
Recommended Electrical Service Single-phase 32A 230V service
Maximum Input Amps 32
PDU Plug Type IEC-309 32A BLUE (2P+E)
Input Phase Single-Phase
Input Cord Length (ft.) 12
Input Cord Length (m) 3.66
OUTPUT
Output Capacity Details 7.4kW (230V) / 32A total capacity / 16A max per breakered outlet bank; 16A max per C19 outlet; 10A max per C13
outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (16) C13; (2) C19
Output Nominal Voltage 230V
Overload Protection Two 20A circuit breakers protect 9 outlets each
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Set of 2 digital meters continuously report output current for breakered load bank; Bank 1 (Upper row of 9 outlets),
Bank 2 (Lower row of 9 outlets)
Switches n/a
PHYSICAL
Form Factors Supported 2U rackmount
Material of Construction Metal
Minimum Required Rack Depth (cm) 40.64
Minimum Required Rack Depth
(inches)
16
PDU Form Factor Horizontal (2U)
Shipping Dimensions (hwd / cm) 19.81 x 42.67 x 49.02
Shipping Dimensions (hwd / in.) 7.80 x 16.80 x 19.30
Shipping Weight (kg) 6.67
Shipping Weight (lbs.) 14.70
Unit Dimensions (hwd / cm) 8.9 x 44.5 x 31.75
Unit Dimensions (hwd / in.) 3.5 x 17.5 x 12.5
Unit Weight (kg) 6.21
Unit Weight (lbs.) 13.7