Tripp Lite PDUMH30ATNET Brochure & Specs

Single-Phase Auto Transfer Switch / Switched PDU,
2.9kW 30A 120V, 2U Horizontal mount, 24 5-15/20R & 1 L5-30R outlets, 2 L5-30P inputs
MODEL NUMBER: PDUMH30ATNET
Description
Tripp Lite Switched ATS / Auto Transfer Switch provides a redundant power option for single-corded network
ATS will normally maintain continuous output to all outlets as derived from the primary input cable. If the primary
power source becomes unstable or fails altogether, the ATS will switch over to the secondary power source until
the primary input is restored and stable. Highly reliable solid-state switching between primary and secondary
inputs occurs in 1-5 milliseconds. Switched PDU features include individually controllable output receptacles and
built-in network interface. Super-fast switchover between primary and secondary power sources occurs within
milliseconds. ATS functionality is supported by any two compatible AC power sources, regardless of phase
angle, to support a variety of advanced redundant power networking applications. Enables fault tolerant
hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system. In a
two-UPS environment, the primary input cable must be supported by a full time sine wave UPS with zero transfer time. Tripp Lite SmartOnline series is highly
recommended for use as the primary UPS in a two-UPS application. ATS configurations utilizing separate mains circuits, backup generators and even
separate utility power grid feeds are fully supported. On-board ATS processor constantly evaluates power quality on both input sources to prevent transfer to
the secondary source when unavailable or of lower quality than the primary source. Front input LED's display primary or secondary power availability.
Features
120V 30A Power Distribution Unit (PDU) with Auto-Transfer Switch (ATS) and Switched output receptacles (agency derated to 24A continuous)
ATS features provide redundant power for critical network equipment with a single input power cord
Switched PDU features enable programmable or real-time power control of individual outlets via built-in network interface
Visual meter reports output amp and kW power consumption, plus voltage and temperature/humidity data with optional ENVIROSENSE sensor
25 switched outlets (24 5-15/20R & 1 L5-30R); 2U horizontal rackmount form factor; 11.9 in. / 30.2cm depth
Two NEMA L5-30P 10 ft. / 3m inputs connect to separate PRIMARY and SECONDARY power sources
ATS normally maintains output sourced from the primary input; As primary input power fails or becomes unstable, the ATS switches to power equipment
from the secondary input until power on the primary input is restored
Highlights
Single phase 30A 120V Auto
Transfer Switch / ATS PDU with
Solid State Switching
Enables redundant-power option
for single-corded network devices
Separate primary & secondary
inputs connect to any two
compatible power sources
2U rackmount, 2 L5-30P inputs,
25 switched outlets (24 5-15/20R,
1 L5-30R)
Individually switched outlets,
network interface and visual
current, voltage and
environmental monitoring
Applications
ATS PDU systems provide a
redundant power option with
individual outlet control for
single-corded network devices
Package Includes
PDU with attached L5-30P input
power cords
Installable 2U mounting brackets
User manuals with warranty
information
1 / 4
Highly reliable solid-state switching enables fast 1-5 millisecond trasfer between primary and secondary inputs
ATS configurations enable hot-swap UPS protection when used with a single UPS and redundant UPS protection when each input is connected to a
separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS similar to Tripp Lite SmartOnline)
Advanced ATS configurations using separate mains circuits, backup generators and out of phase utility feeds are fully supported
On-board processor evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the
primary source
3-6 millisecond transfer time between primary and secondary inputs
DHCP/Manual configuration support; Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP,
DHCP, BOOTP, NTP protocols
Compatible with optional ENVIROSENSE temperature monitor
Front panel LEDs confirm power availability on primary / secondary inputs and each output receptacle
TAA Compliant Version Available - Order Tripp Lite PDUMH30ATNETAA
Specifications
OVERVIEW
PDU Type Auto-Transfer Switch; Switched
OUTPUT
Output Capacity Details 2.9kW (120V input), 3.0kW (127V input), 2.4kW (100V input); 30A maximum (agency de-rated to 24A continuous)
Frequency compatibility 60 Hz
Output nominal voltage 100-127V nominal, single phase
Outlet quantity / type 24 5-15/20R (switched), 1 L5-30R (switched)
Outlet Type 5-15R, L5-30R
INPUT
PDU Input Voltage 100; 120; 127
Maximum Input Amps (A) 30
Maximum Input Amps (A) Details Agency de-rated to 24A continuous
Input connection type Two labelled L5-30P inputs support Primary and Secondary input connections
PDU Plug Type NEMA L5-30P
Phase Single-Phase
LEDS ALARMS & SWITCHES
Switches
ENTER and MODE switches toggle the digital display to show output amps and kW in 4 separately metered load banks (BANK 1: 5-20R outlets #1-12, BANK 2: 5-20R outlets #13-24, BANK 3: L5-30R outlet #25, BANK 4: Total output), input voltage (primary, secondary) and *temperature / humidity data (*with optional
ENVIROSENSE
sensor)
Front panel LEDs
25 LEDs display power on/off status for each outlet, plus 2 LEDs for power status on Primary and Secondary input connection and three additional LEDs to label the displayed numeric value as Amps, kW or Voltage
2 / 4